Académique Documents
Professionnel Documents
Culture Documents
Condensing
Central Heating Boiler
The Health & Safety Executive operates the ‘Gas Safe Register’,
a self-certification scheme for gas heating appliances.
© Baxi Heating UK Ltd 2009 All rights reserved. No part of this publication may The flowchart opposite gives guidance for installers on the
be reproduced or transmitted in any form or by any means, or stored in any process necessary to ensure compliance with Building
retrieval system of any nature (including in any database), in each case whether
electronic, mechanical, recording or otherwise, without the prior written Regulations.
permission of the copyright owner, except for permitted fair dealing under
Copyrights, Designs and Patents Act 1988.
The Company Secretary, Baxi Heating UK Ltd, The Wyvern Business Park,
Stanier Way, Derby, DE21 6BF.
0086
ISO 9001
This product has an energy rating (A) on a scale of A to G. FM 00866
For more information see www.boilers.org.uk. This is a certification mark.
Choose Building
Regulations Notification
Route
IMPORTANT - Installation, Commissioning, Service & Repair This company declares that no substances harmful
to health are contained in the appliance or used
This appliance must be installed in accordance with the manufacturer’s instructions and during appliance manufacture.
the regulations in force. Read the instructions fully before installing or using the
appliance. The appliance is suitable only for installation in GB and IE
and should be installed in accordance with the rules in
In GB, this must be carried out by a competent person as stated in the Gas Safety force, and only used in a suitably ventilated location.
(Installation & Use) Regulations.
In GB, the installation must be carried out by a Gas Safe
Registered Installer. It must be carried out in accordance
Definition of competence: A person who works for a Gas Safe registered company with the relevant requirements of the:
and holding current certificates in the relevant ACS modules, is deemed competent. • Gas Safety (Installation & Use) Regulations.
• The appropriate Building Regulations either The Building
Regulations, The Building Regulations (Scotland), Building
In IE, this must be carried out by a competent person as stated in I.S. 813 “Domestic
Regulations (Northern Ireland).
Gas Installations”. • The Water Fittings Regulations or Water Byelaws in
Scotland.
NOTE: The addition of anything that may interfere with the normal operation of the • The Current I.E.E. Wiring Regulations.
appliance without express written permission from the manufacturer or his agent could
Where no specific instructions are given, reference should
invalidate the appliance warranty. In GB this could also infringe the Gas Safety
be made to the relevant British Standard Code of Practice.
(Installation and Use) Regulations.
In IE, the installation must be carried out by a competent
Warning - Check the information on the data plate is compatible with local supply Person and installed in accordance with the current edition
conditions. of I.S. 813 ‘Domestic Gas Installations’, the current Building
Regulations and reference should be made to the current
ETCI rules for electrical installation.
The boiler meets the requirements of Statutory Instrument “ The Boiler (Efficiency) Codes of Practice, most recent version should be used
Regulations 1993 No 3083” and is deemed to meet the requirements of Directive
92/42/EEC on the energy efficiency requirements for new hot water boilers fired with In GB the following Codes of Practice apply:
liquid or gaseous fuels:- Standard Scope
BS 6891 Gas Installation.
BS 5546 Installation of hot water supplies for domestic
Type test for purpose of Regulation 5 certified by: purposes.
BS 5449 Forced circulation hot water systems.
Notified Body 0087. BS 6798 Installation of gas fired hot water boilers.
BS 5440 Part 1 Flues.
BS 5440 Part 2 Ventilation.
Product/Production certified by: BS 7074 Expansion vessels and ancillary equipment for
Notified Body 0086. sealed water systems.
BS 7593 Treatment of water in domestic hot water
central heating systems.
For GB/IE only.
In IE the following Codes of Practice apply:
Standard Scope
I.S. 813 Domestic Gas Installations.
The following BS standards give valuable additional information;
BS 5546 Installation of hot water supplies for domestic
purposes.
BS 5449 Forced circulation hot water systems.
BS 7074 Expansion vessels and ancillary equipment for
sealed water systems.
BS 7593 Treatment of water in domestic hot water
central heating systems.
General
The following advice should be adhered to, from when first handling the boiler to the final stages of installation, and also during maintenance.
Most injuries as a result of inappropriate handling and lifting are to the back, but all other parts of the body are vulnerable, particularly shoulders, arms and
hands. Health & Safety is the responsibility of EVERYONE.
There is no ‘safe’ limit for one man - each person has different capabilities. The boiler should be handled and lifted by TWO PEOPLE.
Wear appropriate Personal Protection Equipment e.g. protective gloves, safety footwear etc.
Preparation
Co-ordinate movements - know where, and when, you are both going.
Minimise the number of times needed to move the boiler - plan ahead.
Always ensure when handling or lifting the route is clear and unobstructed. If possible avoid steps, wet or slippery surfaces, unlit areas etc. and take special
care on ladders/into lofts.
Technique
When handling or lifting always use safe techniques - keep your back straight, bend your knees. Don’t twist - move your feet, avoid bending forwards and
sideways and keep the load as close to your body as possible.
Where possible transport the boiler using a sack truck or other suitable trolley.
Always grip the boiler firmly, and before lifting feel where the weight is concentrated to establish the centre of gravity, repositioning yourself as necessary.
See section 8.3 of these instructions for recommended lift points.
Remember
The circumstances of each installation are different. Always asses the risks associated with handling and lifting according to the individual conditions.
If at any time when installing the boiler you feel that you may have injured yourself STOP !!
DO NOT ‘work through’ the pain - you may cause further injury.
IF IN ANY DOUBT DO NOT HANDLE OR LIFT THE BOILER - OBTAIN ADVICE OR ASSISTANCE BEFORE PROCEEDING !!
1.0 Introduction 7
10.0 Installation 29
11.0 Electrical 35
Benchmark Checklist 58
Contents of Pack
1.1 Description
1. Wall Plate
2. Flue Elbow
3. Heat Exchanger
4. Burner
5. Air Box
6. Fan Protection Thermostat
13
12
Fig. 3
7
11
Fig. 4 Fig. 6
10
3.1
Flow NO
temperature less
than set point ?
1. Switched Live On: When the switched live switches
on if the flow temperature is less than the set point
then pump overrun occurs. When the switched live
YES switches on if the flow temperature is greater than the
set point then pump overrun occurs.
10 second
Pump On.
2. Pump On: The pump is on while the fan, spark
generator and gas valve are off. After 10 seconds if the
flow switch has made then fan pre-purge occurs. After
10 seconds if the flow switch has not made then anti-
NO
Flow switch made ? cycle occurs.
5 second
8. Anti-cycle: The pump, fan, spark generator and gas
Fan Post Purge.
valve are off. After 3 minutes if the flow temperature is
less than the set point then pump on occurs. After 3
minutes if the flow temperature is greater than the set
point then pump overrun occurs.
YES All TRVs
shut down ?
9. Ignition Lockout: The pump, fan, spark generator
and gas valve are off. The boiler can only be reset by
manually using the reset button.
NO
1 minute
Pump Overrun.
3 minute
Anti-cycle.
Appliance Type C13 C33 C53 Injector (Natural Gas) Electrical Supply 230V~ 50Hz
6.5mm Diameter (Appliance must be connected to an
Appliance Category CAT I 2H earthed supply)
CO/CO2 Ratio Up to a maximum
Heat Input (Q)(Gross) Max Min of 0.004 Power Consumption 80W
15/2 HE Plus kW 16.88 10.2 2
CO Level 9% ± 1%
Btu/hr 57,600 34,840 External Fuse Rating 3A
15/2 HE Plus kW 16.49 10.1 Both Sides 5mm Min Gas Connection
Btu/hr 56,260 34,520 Above Casing 200mm Min G1/2” B.S.P. Thread
Below Casing 50mm Min
24/2 HE Plus kW 23.8 10.1 Controls
Btu/hr 81,200 34,520 Front (For Servicing) 500mm Min
boiler thermostat, safety thermostat,
Front (In Operation) 5mm Min
30 HE Plus kW 32.61 10.1 flow switch, electronic flame sensing,
Btu/hr 113,280 34,520 Weights kg temperature protection thermostat &
Packaged Boiler Carton 36.2 condensate blockage sensor
Max Gas Rate (2H - G20 - 20mbar) Packaged Flue Kit 3.6
(After 10 Mins) Installation Lift Weight 26.0 Inlet Pressure at Gas Valve (Natural Gas)
(15/2) (24/2) (30)
Min 18.1 mbar
Btu/hr 52,000 75,000 102,980 Recommended System
Max 22.5 mbar
m3/hr 1.64 2.31 2.95 Temperature Drop
Condensing 20°C 36°F (see Section 10.1)
ft3/hr 52.1 83.3 104.2
Flow Temperature (adjustable)
55° C to 78° C (± 5° C)
DIMENSIONS
E A 600mm
At Least 1.5°
B 320mm
C 390mm
A
D 125mm Ø Min.
E 150mm
F 125mm
B
360° Orientation
D C
The 1.5° fall provided by the elbow
is to allow condensate to run back to
the boiler, for disposal through the
Tube Ø 110mm condensate discharge pipe.
Fig. 7
Return
6.4 Low Head Installation
6.5 Pump
Fig. 11 If Conditions Require,
This System Possible 1. Providing that the cold feed and open vent pipe are
positioned correctly (e.g. the system is not prone to
pumping over, air entrainment etc.) the pump may be fitted
22mm
200mm on the primary return pipe.
Feed & Vent
Min Pipe
Air
Separator
Boiler Pump
Flow
Return
Fig. 12
Alternative Low Head Installation
230V gr
50Hz 230V b
gr
L N E b Y Plan 50Hz
g/y L N E
w Diverter Motor Motor
b br
Cylinder Valve
Stat gr
S Plan o g/y S Plan
1 o g/y Valve Valve
br Cylinder o
C 2
Stat
Boiler
Boiler
L E N P/F
L E N P/F
Timer
Timer
L
N L
CH on NE L Pump N
CH on NE L Pump
HW on
HW on
HW off
Y Plan, Fully TRV’d System, CH Interlocked By Boiler Flow Switch S Plan, Fully TRV’d System, CH Interlocked By Boiler Flow Switch
Room Thermostat should not be fitted Room Thermostat should not be fitted
Pump must be run from Boiler P/F connection for Part L1 compliance Pump must be run from Boiler P/F connection for Part L1 compliance
By-pass not permitted (must be valved off) for Part L1 compliance By-pass not permitted (must be valved off) for Part L1 compliance
Temporary
DHW CH
Hose
Mains Return
Fig. 14
Inlet
© Baxi Heating UK Ltd 2009 15
7.0 Site Requirements
7.1 Location
Zone 0
2. If the boiler is sited in an unheated enclosure then it is
recommended to incorporate an appropriate device for
0.6 m
frost protection in the system controls.
Window
Recess
3. If the boiler is fitted in a room containing a bath or
Zone 2
shower and NOT FITTED with any optional integral
timer or thermostat, it can be fitted in zone 2, (Figs. A &
B shows zone dimensions for a bathtub. For other
examples refer to the Current I.E.E. Wiring Regulations)
Fig. A reference must be made to the relevant requirements.
In GB Only
In GB this is the current I.E.E. Wiring Regulations and
Building Regulations.
In IE reference should be made to the current edition of
I.S. 813 “Domestic Gas Installations” and the current
ETCI rules.
In Operation
Fig. 16
50mm
per me It is also permissible to discharge into a downpipe carrying
tre of
pipe ru rainwater, providing this pipe connects to a foul water drain.
n
2.5° M Holes in the soak-away must
inimum
fall face away from the building
IMPORTANT:
Top View Rear Flue
• Only ONE 25mm clearance is allowed per installation.
• Under car ports we recommend the use of the plume
Fig. 16a
displacement kit.
• The terminal position must ensure the safe and
Property Boundary Line
nuisance - free dispersal of combustion products.
Plume
Displacement Kit
N
R D A
M C E
I I I I
S
F B
F J,K
L A
A
G H
Air Inlet
H
I
100mm
© Baxi Heating UK Ltd 2009 Fig. 17c MIN. 19
8.0 Flue Options
Y Concentric
The maximum equivalent lengths are 4m (horizontal) or
X
(vertical). Their lengths exclude the standard elbow and
flue/terminal assembly (horizontal) and terminal assembly
(vertical).
NOTE: Horizontal flue pipes should always be installed with a 1.5° fall from the
terminal to allow condensate to run back to the boiler.
B
A
Y
A+B+2x45°Bends
Concentric
The maximum equivalent lengths are 4m (vertical). Their
Y lengths exclude the standard elbow and terminal assembly
(vertical).
X Twin Flue
The total maximum equivalent flue length is 150m.
NOTE: Each 1m of flue duct should be calculated as 2m.
M
L
J
22 © Baxi Heating UK Ltd 2009
8.0 Flue Options
For Vertical Flues
8.4 For Vertical Flue Systems
Vertical Flue
Adaptor
1. Undo the screws securing the blanking plate to the
boiler top panel. Discard the plate.
Gasket 2. Fix the vertical adaptor and gasket to the top panel with
the previously removed screws.
2. Fix both the air and flue adaptors with their gaskets
onto the boiler top panel. Secure with screws.
Air Duct
Adaptor
Flue Duct
Adaptor
Gasket
Gasket
m
0m The standard horizontal flue kit allows for flue lengths
80
between 270mm (105/8”) and 800mm (32”) from elbow to
m
0m terminal (Fig. 18).
27
Kit No 5121371
Content of kit
1 70/110 Concentric Flue
1 1m 70 Dia Exhaust Flue Pipe
0.94 metre
2 Support Brackets
1 93° Elbow/Plume Outlet Assembly
1 Flue Trim
2 “O” Rings
1 Elbow with Gasket
Fig. C
4. It is possible to reduce or increase (with the addition of
extensions) the length of either or both the 70/110 concentric
and 70Ø exhaust.
24 24
15/
15/
2&
2&
22 22
20 20
9.2 Determining Permissible Lengths - P.D.K.
24/
24/
2
2
18 18
30
30
16 16 In the graph the solid line diagonal represents the
70Ø Exhaust (metres)
8 8
additional bends).
6 6
22
18
30
45° Elbow
Flue Length - Worked Example
X Potterton Promax 30 HE Plus
93° Elbow
Y In Fig. D opposite an additional 93° elbow and pair of 45°
elbows have been included in the 70Ø exhaust.
1 metre Extension
Also 3 straight extension pieces have been used.
7. Fit the boiler flue elbow to the boiler top panel, ensuring
the gasket is in place (Fig. F).
Plume Outlet
Elbow 9.3 General Fitting Notes - P.D.K. (cont.)
200mm Min.
Fig. I
200mm Min.
Fig. J
2.0
7. Ensuring the wall plate is level both horizontally and
3.0
vertically, drill and plug at least 4 securing positions at
4.0 the top and bottom through the wall plate. Utilising the
(metres)
slots available ensure the wall plate is square and secure
to the wall (Fig. 22).
Distance in metres from boiler to the wall.
For pipe lengths greater than 4m increase the off-set by 26mm
for every additional metre to maintain approx 1.5° inclination. 8. Additionally drill 2 relief holes 10mm deep in the wall
(Fig. 22).
Fig. 21
9. Loosely route the condensate discharge pipe to the
lower left hand side of the wall plate.
Relief Holes
Wall Plate
Fig. 22
© Baxi Heating UK Ltd 2009 29
10.0 Installation
Fig. 22a
Outercase
Wall Plate
Fig. 24
10.4 Making the Water Connections
Return Pipe Connection (Fig. 25)
Suggested Lifting 1. The boiler has two side water connections which are
Points shown as labelled FLOW and RETURN. The front connection is the
shaded area flow pipe and the rear threaded connection is the return.
HORIZONTAL FLUE
5. Take the flue and mark off (Z) from the terminal end
as indicated (Fig. 27).
Inner Flue Support Bracket 6. Ensure the inner flue support bracket is positioned in
the flue (Fig. 28).
7. Engage the flue into the flue elbow using soap solution
to ease the engagement ensuring the flue is assembled as
shown (Fig. 29).
Fig. 28
8. Place the gasket over the flue exit on the boiler.
Flue Elbow 11. Make good between the wall and air duct outside the
building ensuring at least a 1.5° drop between the
terminal and elbow.
Gasket
VERTICAL FLUEING
Fig. 30
Flue Trim
Fig. 29
2. Undo the two screws securing the cable clamp and place
to one side (Fig. 31).
5. Lay the cable through the cable clamp to gauge the length
Fig. 31 of cable required when it is connected to the 4-way
Blue (CN11) Jumper terminal block.
Cable Clamp
Red (CN12) Jumper Fig. 32
6. Connect the (S/L), (N) and ( ) wires to the
4-way terminal block (Fig. 33) and refit the cable clamp
(Fig. 31).
Fig. 33
op
PCB g
op
w g br
b bk r w
r
gy r br b y bk
op
gy r Flow
Overheat
g/y g/y Thermostat
br Gas
Flow g/y Valve
Thermistor b w
CH 325 Vdc Flame Spark
Flow DC Fan bk Detection Electrode
Switch bk Electrode
L N Optional
Pump
Feed
Fan g/y
Overheat Condensate
Thermostat Trap
b - Blue r - Red
bk - Black g - Green
w - White g/y- Green/Yellow
br - Brown op - Opaque
gy - Grey y - Yellow
Optional
Pump
Feed N
L
Flow
Thermistor
y b br
r
g/y
r
CH b
Flow Switch
y
br g/y
Spark
Electrode
b
gy Flame
Detection
Electrode
gy
br
br
Main g/y
PCB
w
Layout of PCB Pins
op Condensate Trap
w
br g
r bk
b
Gas Valve
w r
g/y bk
bk Fan Overheat
Thermostat
Fan bk
Flow Overheat
Thermostat
Wiring Key
b - Blue
bk - Black
br - Brown
r - Red
w - White
g/y - Green/Yellow
g - Green
gy - Grey
op - Opaque
y - Yellow
36 © Baxi Heating UK Ltd 2009
12.0 Commissioning the Boiler
Fig. 35
8. With the system cold and all controls calling for heat
check the gas pressure at the inlet tapping of the gas valve
(Fig. 36). The pressure must be a minimum of 18.1 mbar
(Working Pressure). Check that the gas rate is no greater
than 3.3m3/h.
Fig. 36
Inlet Gas Pressure Test Point
a) Burner.
b) Heat exchanger fins.
c) Fan compartment (Check also for condensate leaks).
Combustion Box Fig. 41 d) Insulation.
Door Panel e) Door seals-Important: Pay particular attention to
the condition of the combustion box door seals.
f) Electrodes.
g) The condensate trap.
NOTE: Remove the trap drain plug and place a vessel
underneath to catch the condensate (care should be
taken as this could be hot). Clean the trap and refit
the drain plug. Check for leaks.
h) Top of heat exchanger.
© Baxi Heating UK Ltd 2009 39
14.0 Servicing the Boiler
Injector Pipe e) Remove the gas injector pipe from the gas valve
(push-fit) (Fig. 42).
Combustion Box Base 13. Complete the relevant Service Interval Record
Securing Screws
Burner Securing section of the Benchmark Commissioning Checklist at
Screws Fig. 44 the rear of this publication and then hand it back to the
user.
40 © Baxi Heating UK Ltd 2009
15.0 Changing Components
Electrical Connections 4. Place a tube on the drain point to drain water away
from electrics. Turn anticlockwise to open (Fig. 45).
Safety
Thermostat The thermistor, safety thermostat, interface PCB and
the flow switch can be accessed after removal of the
outer case.
Fig. 46
15.2 Flow Temperature Thermistor and
Safety Thermostat (Fig. 46)
Flow Pipe
Fig. 47
Clip
Hinge down
PCB Housing
Earth 1. Loosen the screw holding the injector pipe into the
venturi.
Protection
Sensor
Venturi
Electrical Connections
Fig. 52
Electrical Connection
44 © Baxi Heating UK Ltd 2009 Wing Nuts
15.0 Changing Components
Case Pressure Pipe 4. Disconnect the electrical plug from the gas valve.
Gas Tap 10. Fit the new gas valve and reassemble in reverse
order.
Fig. 53 Electrical Plug
NOTE: Check for gas tightness after replacing gas
valve.
Combustion Box
The burner and heat exchanger can be changed after
Door Panel
removal of the combustion box door. To change the
heat exchanger, the fan and burner must be removed
first (see section 15.6 and 15.10).
Flow
Switch 15.11 Heat Exchanger
Fig. 56
1. Drain the boiler (see section 15.1 paragraph 2 & 3).
Securing Screws
2. Remove all components in the base of the airbox.
Heat Exchanger
Assembly
Fig. 59
46 © Baxi Heating UK Ltd 2009
15.0 Changing Components
Lower Insulation
Pad Fig. 60 15.13 Heat Exchanger Upper Insulation Pad
(Fig. 60)
Burner
1. Remove all components in the base of the airbox.
Combustion
3. Remove the heat exchanger (see section 15.11).
Box Base
A B C
Key G.C. Description Manufacturers
No. No. Part No.
D PCB 5129147
E Fan 5109925
E
F Gas Valve 241900
Lockout Boiler On Mains On General Fault Finding should only be carried out by
LED Light LED Light LED Light someone who is appropriately qualified.
(Red) (Green) (Green)
Lights
Off Off Off Go to Electrical Supply
YES
section of the fault finding
instructions. Lights
ON
On Flash On YES Go to Thermistor section
of the fault finding
instructions.
ON
Lights
On Off Flash Live & Neutral Reversed
YES
Incoming Live and Neutral
Low Electrical Supply
reversed. Lights
ON Incoming Voltage less than
Flash Off Flash YES 180V. Check System
Controls & System Wiring.
ON Otherwise contact Electricity
Lights
Go to Dry-Fire Provider.
On Flash Flash
YES
section of the fault finding
instructions.
ON Lights
LV Wiring Harness Ensure 8-
On On On YES way PCB connector securely
pushed in. If fault persists
Lights ON replace LV wiring harness.
On Off On YES Go to Ignition Lockout section
of the fault finding instructions.
ON Lights
Flash On Flash YES PCB Fault
Replace PCB.
Lights ON
Flash Off On Go to Overheat Lockout
YES
section of the fault finding
instructions.
ON Lights
On On Flash YES PCB Fault
Replace PCB.
Lights ON
Flash Flash On Go to Fan Lockout
YES
section of the fault finding
instructions.
ON
Lights
Flash On On YES PCB Fault
Replace PCB.
ON
ON
No Switched Live to
NO boiler. Check Systems
240V at A ?
Controls and System
Wiring.
YES
NO A
Check wiring from
240V at B ?
terminal block to PCB.
YES
L N Optional
Pump
Live
Check for shorts on
NO
pump, fan & gas valve.
PCB fuse OK ?
Replace if shorted &
replace fuse.
YES
Replace PCB.
B
Fuse
ON
Are YES
Flow & Return reversed ? Swop Flow & Return.
NO E
Is the NO
Fill system with water and
system full of water ?
bleed out all air.
L N Optional
Pump Replace PCB.
Live
YES
YES
Turn Turn
NO NO mains off, unplug
Is the mains off & on. After 5 sec, is 7-way connector to PCB.
pump running ? there 240V Is there continuity between
F and G ?
at E?
YES NO
Unplug
5-way PCB
YES
connector. Is there continuity
Replace PCB.
between H (run pump from
switched live) ?
H
G
Viewed from
Wire Entry end
NO
7-way Connector
F
Disconnect YES
Flow Switch Inline
connector. With pump running is
Wires from inline
there continuity across flow connector to PCB faulty.
switch ?
L N Optional
NO Pump
Live
Remove NO
flow switch from boiler. Is there a NO
Is there a physical blockage to blockage in the system ? Replace Flow Switch.
the paddle within the
flow switch ?
YES YES
ON
I
NO
Check isolation valve and
Is there gas at gas valve inlet
gas supply. J
?
5-way Connector
YES
Remove
Reset Lockout. NO 5-way connector YES
Is there gas flow from gas valve. Is there 240 Replace Gas Valve.
(check at meter) ? Vdc between I & J
during ignition ?
YES NO
Remove
the larger or the
Is NO Lead from PCB to Gas
Remove Gas Valve & check two 6-way PCB connectors.
there at least NO Is there continuity from I to L
inlet filter for blockage. Valve faulty.
18mbar dynamic at gas valve Otherwise incorrect gas supply & from J to K ?
inlet ? to boiler.
YES
Replace PCB.
YES
Is
Condensate Trap
YES
Clear blockage and dry
blocked or water on sensors. K
terminals ?
L
NO
6-way Connector
Is
YES Replace spark or flame
spark or flame detection detection probe and
probe damaged ? gaskets.
NO
Is NO
spark gap between 3 and Set spark gap to 3.5mm.
4mm ?
YES
Is
wiring from PCB YES Is the NO
to spark probe & flame burner blocked or Replace PCB.
detection probe OK ? damaged ?
NO YES
ON
Disconnect
NO
black stat on flow pipe.
When flow < 60° C is there Replace Stat.
continuity across stat ?
YES
Reconnect stat. NO
Disconnect fan stat.
When fan temp < 60° C Replace Stat.
is there continuity
across stat ?
YES
Reconnect stat.
NO M
Disconnect the larger of Wiring from PCB to
the 6-way PCB connectors.
thermostats faulty.
Is there continuity
across M ?
Disconnect
thermistor NO
(red sensor on flow pipe). Replace thermistor.
Is resistance between
0.5kΩ & 20kΩ ?
YES
Is
combustion chamber YES Replace combustion
door seal damaged or not in chamber door seal & trim
seal.
place ?
NO
Replace PCB.
Fan PCB
Connection Connection
Unplug
3-way PCB connector NO
N O
& unplug fan. Is there Rectify wiring.
continuity from N to O &
Q
from P to Q ?
P
YES
Fan PCB
Connection Connection
Unplug
the smaller of the NO
6-way PCB connector. Is there
Rectify wiring.
continuity from R to S & from T
R
to U & from
T S
V to W ? V U
W
YES
Viewed from
Wire Entry end
Replace fan.
ON
Unplug
thermistor, NO
Is thermistor resistance between Replace thermistor.
0.5kΩ & 20kΩ ?
D
YES
Plug in
thermistor, leave NO
8-way connector unplugged. Wiring from PCB to
Is resistance at D between thermistor faulty. Viewed from
0.5kΩ & 20kΩ ? Wire Entry end
YES
Replace PCB.
ALL SYSTEMS
The system has been flushed and cleaned in accordance with BS7593 and boiler manufacturer’s instructions Yes
What system cleaner was used?
What inhibitor was used? Quantity litres
Burner Operating Pressure (at maximum rate) mbar OR Gas Inlet Pressure (at maximum rate) mbar
Cold Water Inlet Temperature °C
Hot water has been checked at all outlets Yes Temperature °C
Water Flow Rate l/min
ALL INSTALLATIONS
If required by the manufacturer, record the following CO2 % OR CO ppm OR CO/CO2 Ratio
The heating and hot water system complies with the appropriate Building Regulations Yes
The boiler and associated products have been installed and commissioned in accordance with the manufacturer’s instructions Yes
The operation of the boiler and system controls have been demonstrated to and understood by the customer Yes
The manufacturer’s literature, including Benchmark Checklist and Service Record, has been explained and left with the customer Yes
Customer’s Signature
(To confirm satisfactory demonstration and receipt of manufacturer’s literature)
*All installations in England and Wales must be notified to Local Authority Building Control (LABC) either directly or through a Competent Persons Scheme.
A Building Regulations Compliance Certificate will then be issued to the customer.
58
©Heating and Hotwater Industry Council (HHIC) www.centralheating.co.uk
SERVICE RECORD
It is recommended that your heating system is serviced regularly and that the appropriate Service Record is completed.
Service Provider
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s
instructions.
Always use the manufacturer’s specified spare part when replacing controls.
Signature Signature
Signature Signature
Signature Signature
Signature Signature
Signature Signature
59
All descriptions and illustrations provided in this leaflet have been carefully
prepared but we reserve the right to make changes and improvements in
our products which may affect the accuracy of the information contained in
this leaflet. All goods are sold subject to our standard Conditions of Sale
which are available on request.
P O T T E RTON
A Trading Division of Baxi Heating UK Ltd (3879156)
A D ivis io n o f B a x i Gro u p
Brooks House, Coventry Road, Warwick. CV34 4LL
After Sales Service 0844 871 1560 Technical Enquiries 0844 871 1555
Website www.potterton.co.uk
e&oe