Vous êtes sur la page 1sur 18

PRACTICES MANUAL

Unit Ref.: UCP Date: October 2010 Pg: 2 / 115

7.4.2 Annex 2: Temperature sensor calibration......................................................................................................... 104


7.4.3 Annex 3: Level sensor calibration...................................................................................................................... 108
7.4.4 Annex 4: pH sensor calibration .......................................................................................................................... 112

7 PRACTICES MANUAL

7.1 GENERAL DESCRIPTION OF THE SYSTEM

In this section, the process unit and the control loops used in measuring
experiments for level, flow, temperature and pH regulation are described, together
with the different equipment and necessary instruments for the physical simulation of
the corresponding dynamic systems.

7.1.1 General description of the system

This unit consists on a hydraulic circuit, with an bottom tank (1) and a
superior process tank (2), both dual ones, two pumps of centrifugal circulation (3),
two flowmeters with a manual control valve (4), three on/off solenoid valves (5) and
a motorized proportional valve (infinitely variable) (6). Of course, together with the
tubes, the union elbows, connections, feedthroungh, main valve and the appropriate
drainage for the circuit operation. All the above-mentioned is set on a designed
support structure so, that it is placed on a work table (7).

As additional fixed elements, there is also a turbine flow sensor that is


installed in one of the upward lines of flow (8), and a temperature sensor located in a
lateral bottom of the process tank (9) together with a serpentine with electric heating
(11).

The interchangeable additional elements are an agitator (10), the


immersion level sensor should be located in the process tank (12) and the pH sensor
(solenoid), can be in the process tank or also in the second tank (13), to study the
PRACTICES MANUAL

Unit Ref.: UCP Date: October 2010 Pg: 3 / 115

effect of the time out.

Figure 1.1.1 Main diagram of the equipment

The UCP elements indicated in the diagram are:

1. A main tank and collector with an orifice in the central dividing


wall (2 x 25 dm), and drainage in both compartments (made in
methacrylate).

2. A dual process tank (2 x 10 dm), interconnected through an


orifice and a ball valve and an overflow in the dividing wall
(methacrylate); a graduate scale and a threaded drain of adjustable
level with bypass (metallic).

3. Two centrifugal pumps.


PRACTICES MANUAL

Unit Ref.: UCP Date: October 2010 Pg: 4 / 115

4. Two variable area flowmeters (0.2-2 l/min, and 0.2-10 l/min),


and with a manual valve.

5. Line of on/off regulation valves (solenoid). Usually one is


opened (AVS-1), and the other two are usually closed with
different Cv (AVS-2 and AVS-3); and manual drainage valves of
the superior tank.

6. A motorized control valve (AVP-1; piston type) with rotation


indicator.

7. Structures, panels, pipes and connections made in stainless


steel and methacrylate.

8. A flow sensor, fixed, turbine type.

9. A temperature sensor.

10. A helix agitator.

11. An electric resistor (0.5 KW), fixed.

12. Level sensor 0-300 mm (of capacitive immersion, 4-20 MA), can
be dismantled.

13. PH sensor (glass electrode, ddp(V)), collapsible (tank).

14. On/off level sensor. This sensor determines the performance of


the immersion resistor.

15. Control loops: interface, controller, monitor and keyboard (PC


and cards), electric connections.
PRACTICES MANUAL

Unit Ref.: UCP Date: October 2010 Pg: 5 / 115

7.1.2 Operation of the subsystems

For the level, flow and temperature control test, the liquid (water) is
impelled from the tank by the pump, located to the left of the front of the equipment,
going through the flowmeter, the solenoid valve (usually open), the motorized valve,
the turbine (flow sensor) and the process tank. It is possible to use the second pump
in the level tests, as it will be indicated.

The pH control test of requires a second parallel line of flow (right),


provided only with pump and a flowmeter. The compartments of the inferior tank
should be loaded with diluted solutions of an acid and a base, respectively.

The process tank is divided in two halves, with an orifice between them
that allows their communication or isolation.

The right compartment has an overflow of variable level (that it prevents


the complete overflow of the tank, and it allows to modify its effective liquid
volume), two drains with solenoid valves with different Cv (normally closed), and a
third one with a normal drainage valve.

The left compartment is only connected to a drainage valve.

The level control tests require all the elements of the circuit and of the
tank, besides the sensor located in it. In some experiments, it is required the second
pump placed to the right-hand side of the equipment.

The TEMPERATURE CONTROL tests, in these cases, as we will see later


on, can be carried out with experiments in closed circuit or in open circuit. In the
close circuit case, fill the superior tank with the right pump 1 (AB-1) and carry out
the experiment. In open circuit, keep a constant water flow using the pump 1, this
PRACTICES MANUAL

Unit Ref.: UCP Date: October 2010 Pg: 6 / 115

way, a small water flow is adjusted and the superior overflow is used as a drainage
system. In this case, it is necessary to use the agitator to guarantee a good
temperature uniformity.
PRACTICES MANUAL

Unit Ref.: UCP Date: October 2010 Pg: 7 / 115

7.2 THEORETICAL BASIS

Modeling, simulation, design and optimization require a series of processes that


will be explained in the following paragraphs. The understanding of these theoretical
concepts will help the student to follow the suitable instructions for the practices
procedure.

7.2.1 Modeling, simulation and control process

The development, and good operation of the industrial plants, requires the
right selection of the equipment and process parameters. This election is
supplemented with the instrumentation and the control, as well as with the dexterity
to adjust and to manipulate them correctly.

For it, the industrial engineering processes use different tools and technical
aspects based on:

1.- The modeling of the systems.

2.- The simulation of the stationary and dynamics response.

The control process is the objective of this modeling and simulation that
guarantees that the dynamic behavior is efficient and precise.

The design and the process optimization is based on calculations in


stationary state to specify, in a first approach, the operation conditions of the
equipment in the process plants. These design calculations in the stationary state
don't say anything about the dynamic response of the system, they only tell us where
we begin and where we end up, but anything about the process behavior. This type of
PRACTICES MANUAL

Unit Ref.: UCP Date: October 2010 Pg: 8 / 115

information is the one that informs about the study of the dynamics procedure.

The dynamics and the control study the non-stationary behavior of the
processes and the design of the control systems in function of the interferences. With
this, the design of the process systems is finished, that include the own process and
its control loops.

In a first approach, the process control unit has been designed for the study
of the dynamic behavior of the different control loops. The modeling and stationary
simulation of the processes is not deal with in this equipment.

7.2.2 Dynamics and control

Once the freedom degrees of the process are selected and the design
variables good values are calculated, these values should remain unaffected with the
deviations that take place during the real operation of the systems during the
stationary state.

The factors that cause such deviations are denominated interferences.


These can be internal or external to the process, random or programmed. The random
interference type are those that produce deviations from the programmed regime due
to some process input variables fluctuations. In the programmed interferences, it is
necessary to consider the transitory periods of starting-up, stop or changes in the
stationary state of the process.

The number of variables that you can fix coincides with the freedom
degrees (although they don't have to coincide with the free variables that were chosen
during the design phase). The variables that are more easily controlled are: level,
flow, pressure, temperature and composition. We will denominate them controlled
variables and their values we will be called set point. In a controller, the input
PRACTICES MANUAL

Unit Ref.: UCP Date: October 2010 Pg: 9 / 115

magnitude of the set point is fixed in a constant value. In a “programmer” controller


the inlet magnitude is a value that varies in function of the time, according to the
programmed law.

The variable used to regulate the set values is denominated manipulated


variable. The function of the regulating device of the system is to activate
automatically the control elements that allow to modify the value of the manipulated
variables, so that the controlled variables are the next to the set point.

7.2.2.1 Dynamics in open loop

The systems dynamics studies the non-stationary situations of the process.


This study is always previous to the design of the control that avoids the non-
reversibility of some deviations of the stationary state. In the process, the
manipulated variable acts changing the value of the controlled variables so, in the
simplest cases, it can be predicted using of a mathematical model. So, it is
fundamental to have an exhaustive knowledge of the process to will be studied.

The dynamic simulation of a process consists on:

1. Developing the material and energy balance equations, the


balances, the physical laws or other independent sources of
information.

2. Selecting the values of the necessary physical-chemical


magnitudes and the values of the preset points.

3. Obtaining the differential expressions of the variables determining


their temporary evolution for an interference in the stationary
regime starting from a defined initial state.
PRACTICES MANUAL

Unit Ref.: UCP Date: October 2010 Pg: 10 / 115

As a particular case, the design equations in the stationary state can be


obtained (null accumulation) and, starting from them, calculate the values of the
design and state variables in this regime.

The system dynamic in open loop represents the process behavior in the
absence of controllers. The velocity and the tolerance of the response of the process
in function of the interferences can be studied, this is the necessity of the control
system.

7.2.2.2 Feedback Control

The feedback control system consists, essentially, on measuring the


controlled variable, to compare its value with the one wanted (set point) and,
according to the error, to act on the control element of the manipulated variable. This
is a feedback system, in which the corrector action persists while the error is not null.
The corresponding signals spread in the circuit, making comparison cycles, of
calculation and of correction (in closed loop) with a certain time of response.

If a closed control is turned into manual operation, the operator can govern
directly the control valve and the value of the regulated variable obtained from the
transmitter can be observed in the controller. In this case, we are operating in open
loop, since the output signal of the controller is off.

The main elements of a control system in closed loop are:

• Sensor: Device that is able to measure the value of the controlled


variable (it is also denominated primary measure element).

• Transducer: Device that transforms the measures in normalized


equivalent signals, pneumatic or electric, according to the distance
between the process and control rooms, which are sent to the
PRACTICES MANUAL

Unit Ref.: UCP Date: October 2010 Pg: 11 / 115

comparator (also denominated signal conditioner element).

• Controller: Device that receives the error from the comparator,


interprets it, and it acts on the final element of control. There are
three types of corrective actions:

- Proportional: the signal sent to the final element is


proportional to the error. If the proportional constant is very
big the control behaves as an on/off control.

- Integral: the corrective signal sent is proportional to the


error accumulated with the time (integral error).

- Derivative: the signal is proportional to the velocity of


variation of the error.

These last two actions are usually combined with the primary signal
(proportional) to improve the control quality and even, they usually
combine the three in complex processes. These combined processes
are known as P.I.D. control (proportional-integral-derivative).

• Final element of control (actuator): Device that, according to the


signal of the controller, acts on the manipulated variable regulating
the inlet material or energy flow to the process (valve, volumetric
pump, compressor, rheostat, etc.).

The control systems are effective with small interferences. In the case of
big interferences, the final element can end up being totally open or totally closed,
and, above a certain value, the control would not act appropriately (saturated). In
these cases, to correct it, you should act manually on the parameters of the system.
PRACTICES MANUAL

Unit Ref.: UCP Date: October 2010 Pg: 12 / 115

The sensors, the transmitters and the final control elements are inserted in
the process in a logical way. The control devices are usually located in a control
room, and they are in normalized panels with graphic instruments for the variables
and a diagram of flow (in a simple pilot plant it can be a simple PC computer with a
monitor and a printer).

In the control diagrams, the variables are designated with the letters F
(flow), L (level), P (pressure), T (temperature), followed by the indicative letters of
the service and of the functions of the instruments: T (transmitter), C (controller), I
(indicator), R (register), A (alarms).

7.2.2.3 Forward control

The forward control makes the corrective action in the moment in which
the interference is detected, instead of waiting to its spread through the process, as it
happened in the feedback process. The action is independent of the value of the
controlled variable, making it depend on another, according to a calibrated preset.
This system is used with simple processes that don't require a great accuracy, or in
those processes in which the closed loop doesn't give good results, for example, in
processes in which that the measure and the corrective action take place in a great
period of time.

7.2.3 Dynamic simulation of the control systems

The dynamic simulation of the control systems allows studying the


response of the system facing up diverse interferences, such as changes in the input
variables, in the set point, or in the controller adjustments. The system consists of a
block that represents the process, and of another that corresponds the controller
connected to the first one forming a feedback loop.
PRACTICES MANUAL

Unit Ref.: UCP Date: October 2010 Pg: 13 / 115

Figure 2.3.1

The process consists basically of an input (q), a manipulated variable, also


called feedback (m) and an output (c) (controlled variable). The controlled variable is
subtracted to the set point (r) to obtain the error (e) (input to the controller). The
controller calculates an output signal by means of an appropriate control algorithm.
The characteristic response of a controller on/off comes determined by its hysteresis,
also called dead band. In a PID controller (proportional-integral-derivative) the signal
comes determined by the gain (Kc) or its percentage inverse (BP=100/Kc,
proportional band) and the integral (I) and derivative (D) times.

c = Kp[q, m]
[1]
e = r −c
∂e
m = Kc( e + ∫ e∂t + D
∂t )

In open loop, the state variables (outputs) are calculated starting from the
initial values and from the process pattern. It is defined in function of differential
equations for the transitory regime, or by state equations for the stationary regime
(invariable with the time).

These last ones are the techniques employed during the design phase of the
experiment and they allow calculating the values of the necessary input variables to
reach the stationary regime. The first ones allow studying the transitory periods
during the setting phases in setting-in, stops or changes in the stationary regime of
PRACTICES MANUAL

Unit Ref.: UCP Date: October 2010 Pg: 14 / 115

the process.

During the real operation of the process, the variables are modified with
the time as a consequence of diverse interferences in the input variables or in the set
point (programmed). In these cases, the process can only work correctly using a
closed loop control.

The dynamic behavior of the system is calculated by an iterative algorithm


at discreet intervals of time (Euler’s method). The first phase of the program is the
data input: fixed variables, initial values of the manipulated variables, set point of the
controlled variables, adjustment of the controller (hysteresis, parameters PID) and
interference variables.

Qt RT H,KC, I,D

m PROCESO Ct COMPARACIÓN eI CONTROL mt

Figure 2.3.2

The mathematical pattern of the process calculates the outlet (Ct ) in


function of the inlets (q t, mt ). This value is compared with the set point (rt ) and the
resulting error (et ) is calculated (the accumulated error (integral) or its derivative with
the time, the trapezoidal rules and finite increments are used in this case). Finally,
with these values, the controller output (s t ) and the manipulated variable (mt ) are
calculated making use of the adjustments of the control actions (H, Kc, I, D) and of
the calibration of the actuator, respectively.
PRACTICES MANUAL

Unit Ref.: UCP Date: October 2010 Pg: 15 / 115

The relationship between these last two variables can be settled down on
the base of a function (lineal) between the width of the actuator (m) and the signal of
the controller (±s).

Also, automatic graph representation commands of response can be


included (controlled and manipulated variables), time outs in the process (always
superior or similar to the time of sampling, t≥∆t) and sampling time of the controller
similar to those of the process (analogical control) or superiors (digital control).

In case a graphic register is used, this should be connected to the electric


signs of the sensor/conditioner (controller input) and to its output (actuator input) to
obtain a register of the response of the process.

7.2.4 Operation and calibration of the process equipment and control elements

The verification and calibration of all the sensors you can find in the
equipment can be carried out in two different ways. The Saced System that is
supplied with the equipment, has a calibration window specially designed for such a
purpose (see Calibration Manual).

However, and due to the importance that the calibration the sensors has in
the control process, the system offers two text windows in which the gain and the
zero can be introduced of each one of the transducers that the equipment has: flow,
level, temperature and pH.
PRACTICES MANUAL

Unit Ref.: UCP Date: October 2010 Pg: 16 / 115

Name of the sensor for


calibration.

Figure 2.4.1

In the same way, the verification of the operation of the pumps, solenoid
valves, agitator, etc. it can be carried out from the calibration window in the Saced
System. This process of operation test should be carried out with extreme care and
under the introduction of the professor's PASSWORD. This Password has been
indicated in the software manual. Once the professor's password is introduced, the
program allows you to select the channels included in the equipment for the digital
outputs as well as for the analogical ones. Verify each one of the elements assembled
in the equipment and carry out a good calibration of the sensors. We should point out
that, when storing the calibration values in the file UCP.EDB, these will be recovered
every time that you enter in the program, independently from the values introduced
by the students in the different practice sessions.

When selecting the different outputs that has the acquisition card
(analogical and digital outputs, and analogical and digital inputs), you can verify the
operation of all devices of the equipment. As an example we have the following
table:
PRACTICES MANUAL

Unit Ref.: UCP Date: October 2010 Pg: 17 / 115

Analogical port (Inputs) Digital Port (Outputs)


Channel Action/Sensor Channel Action/Sensor
Channel 0 pH sensor Channel 0 AVS-1
Channel 1 Level sensor Channel 1 AVS-2
Channel 2 Flow sensor Channel 2 AVS-3
Channel 3 Temperature sensor Channel 3 Resistor On/Off
Channel 4 Alarm of Level Channel 4 Agitator On/Off
Channel 5 Proportional Valve Channel 5 Pump 1 On /Off
Channel 6 Pump 2 On/Off
Table 2.4.1

To outputs and inputs it is necessary to add the analogical output that


corresponds to the motorized valve.
PRACTICES MANUAL

Unit Ref.: UCP Date: October 2010 Pg: 18 / 115

7.3 LABORATORY PRACTICES

It is very important for the formation of the student, the calibration of the
sensors, hence is recommendable that the students see the Annex 1 to Annex 4.

7.3.1 Practice 1: Flow control loops (manual)

7.3.1.1 Objectives

The objective of this experiment is to control the flow that circulates


through a conduction of water by a manual procedure. We assume that the manual
control works as:

• Manual regulation of the adjustable valve placed under the area


flowmeter.

• Manual control of the elements used in the equipment as the


motorized valve, solenoid valves, etc.

7.3.1.2 Required material

To make this practice, the following elements are necessary:

• UCP-F

• Water

• SACED Software.

7.3.1.3 Experimental procedure

1.- Connect the interface of the equipment and execute the program
PRACTICES MANUAL

Unit Ref.: UCP Date: October 2010 Pg: 19 / 115

SACED UCP-F.

2.- Inside the program, select the option Configuration and connect pump 1
(AB-1) (see Software Manual for a more detailed operation).

3.- In the manual regulation (no controller) the flow can be regulated by the
manual adjustable valve VR1, placed in the inferior part of the flowmeter. Vary its
position and observe the adjustment of the flow in function of its position.

4.- Select the option “Manual Control” of the software supplied with the
equipment.

5.- Connect pump 1 (AB-1) and vary the position of the motorized valve by
the Slip bar or the command associated to this action. Check a fixed position, the
flow is regulated.

6.- Vary the position of the valve and repeat the values to observe the
reproduction of the flow control.

7.- Use the controls prepared in the software for controlling the solenoid
valves AVS-1 and the on/off button of the pump. Observe how an on and off button
also produces a flow control of the liquid.

Vous aimerez peut-être aussi