Vous êtes sur la page 1sur 49

4/26/2014

EE 214 – Electromagnetics

Chapter 10: Transmission Lines

Habib Fathallah, PhD EE


Associate Professor, Electrical Engineering Department, College of Engineering
Presentation prepared based on : Engineering Electromagnetics, William H. Hayt, Jr., Eight Edition

Teaching Assistance: Abdulmalik Alwarafy

EE Dept., KSU, hfathallah@ksu.edu.sa, Office: 2C36

outlines
 INTRODUCTION.
 10.1 PHYSICAL DESCRIPTION OF TRANSMISSION LINE PROPAGATION.
 10.2 THE TRANSMISSION LINE EQUATIONS.
 10.3 LOSSLESS PROPAGATION.
 10.4 LOSSLESS PROPAGATION OF SINUSOIDAL VOLTAGES.
 10.5 COMPLEX ANALYSIS OF SINUSOIDAL WAVES.
 10.6 TRANSMISSION LINE EQUATIONS AND THEIR SOLUTIONS IN PHASOR FORM.
 10.7 LOW-LOSS PROPAGATION.
 10.8 POWER TRANSMISSION AND THE USE OF DECIBELS IN LOSS CHARACTERIZATION.
 10.9 WAVE REFLECTION AT DISCONTINUITIES.
 10.10 VOLTAGE STANDING WAVE RATIO.
 10.11 TRANSMISSION LINES OF FINITE LENGTH.
 10.12 SOME TRANSMISSION LINE EXAMPLES.
 10.13 GRAPHICAL METHODS: THE SMITH CHART.

Dr Habib Fathallah, EE 214, Spring 2014 1


4/26/2014

INTRODUCTION

• Transmission lines are used to transmit electric energy and signals from one point
to another, specifically from a source to a load.

• Examples are :
 Connection between a transmitter and an antenna.

 Connections between computers in a network.

 Connections between a hydroelectric generating plant and a substation several


hundred miles away.

INTRODUCTION con.
• Examples of Transmission Line Structures:
(a) Coax cable.

(b) Wire over ground.

(c) Tri-lead wire.

(d) Twisted pair (two-wire line).

• Long distance interconnects.

+ -
(a) (b)
-

- + - + -
(c) (d)

Dr Habib Fathallah, EE 214, Spring 2014 2


4/26/2014

INTRODUCTION con.

• E & H Fields – Micro strip Case

Signal path
Y

Z (into the page)


X

Electric field

Magnetic field

Ground return path

The signal is really the wave propagating


between the conductors

INTRODUCTION con.

• Transmission Line Definitions:

• General transmission line : is a closed system in which power is transmitted from


a source to a destination.
• A two conductor wire system with the wires in close proximity, providing relative
impedance, velocity and closed current return path to the source.
• Characteristic impedance : is the ratio of the voltage and current waves at any
one position on the transmission line, and is given by:

V
Z0 
I

• Propagation velocity : is the speed with which signals are transmitted through
the transmission line in its surrounding medium.

Dr Habib Fathallah, EE 214, Spring 2014 3


4/26/2014

INTRODUCTION con.

• Both Electric and Magnetic fields are present in the


transmission lines.

• These fields are perpendicular to each other and to the


direction of wave propagation for TEM mode waves, which is
the simplest mode, and assumed for most simulators(except
for microstrip lines which assume “quasi-TEM”, which is an
approximated equivalent for transient response calculations).

• Electric field is established by a potential difference between


two conductors Implies equivalent circuit model must
contain capacitor.

• Magnetic field induced by current flowing on the line

Implies equivalent circuit model must contain


inductor.

10.1 PHYSICAL DESCRIPTION OF TRANSMISSION


LINE PROPAGATION

• The basic transmission line circuit


is shown in the figures, voltage
and current waves are initiated
by closing switch S1.

Dr Habib Fathallah, EE 214, Spring 2014 4


4/26/2014

10.1 PHYSICAL DESCRIPTION OF


TRANSMISSION LINE PROPAGATION con.
• Transmission line can be represented as:

C1=C2=C3
L1=L2=L3=L4

Lumped-element model of a transmission line

10.2 THE TRANSMISSION LINE EQUATIONS.

• Fig. shows Lumped-element model


of a short transmission line section
of length z with losses.

Applying Kirchoff’s voltage and current laws


• Applying KVL to the loop that includes
(KVL and KCL) to the indicated loop and node.
the entire section length to get:

• Solving this for the ratio, ∆𝑽/∆𝒛 :

Dr Habib Fathallah, EE 214, Spring 2014 5


4/26/2014

10.2 THE TRANSMISSION LINE EQUATIONS con.

• Next, we write:

• Substituting this into (2) :

• In the limit as z approaches zero (or a small negligible value ) (4) simplifies to the
final form:

This eq. is the first of the two eq.s we are looking for

10.2 THE TRANSMISSION LINE EQUATIONS con.

• To find the second eq., we apply KCL


to the upper central node in the
circuit shown noting from the
symmetry that the voltage at the Applying Kirchoff’s voltage and current laws
node will be 𝑽 + ∆𝑽/𝟐 : (KVL and KCL) to the indicated loop and node.

• Using (3) and simplifying, we get:

Dr Habib Fathallah, EE 214, Spring 2014 6


4/26/2014

10.2 THE TRANSMISSION LINE EQUATIONS con.

• Again, we obtain the final form by allowing ∆𝒛 to be reduced to a negligible


magnitude. The result is:

The
second eq.

• These two equations are called Telegraphist’s equation, their solution leads
to wave equation in transmission line.
• Differentiating equation (5) with ‘z’ and (8) with ‘t’:

And

10.2 THE TRANSMISSION LINE EQUATIONS con.

• Substituting equation (8) and (10) in equation (9) we get:

• Differentiating equation (5) with respect to ‘t’


and equation (8) with respect to ‘z’. Then, Eq. (5) These two equations are

and its derivative are substituted into the general wave equation

derivative of (8) to obtain an equation for the for transmission line.

current which is in identical to that of (11):

Dr Habib Fathallah, EE 214, Spring 2014 7


4/26/2014

10.3 LOSSLESS PROPAGATION.


• Lossless propagation:
 Power is not dissipated but, deviated as the wave travels in the transmission line.
 All power at the I/P end reaches the O/P end.
• In our model, lossless propagation occurs when R=G=0 equation (11) becomes:

• The solution of equation (13) is of the form:

• Take the partial derivatives to equation (14) with respect to ‘z’ and ‘t’, using chain
rule the ‘z’ partial derivative is:

10.3 LOSSLESS PROPAGATION con.

• Where, f’ is derivative of ‘f’.

• Partial derivative w.r.t time ‘t’ is:

• The second derivative can also be taken w.r.t ‘z’ and ‘t’:

• Substitute eqn (17) in eqn (13), we have:

Dr Habib Fathallah, EE 214, Spring 2014 8


4/26/2014

10.3 LOSSLESS PROPAGATION con.

• So the wave velocity for lossless propagation is:

• We have from Telegraphist’s equation,(5) and (8), for lossless condition R=G=0:

• Substitute (14) in (20) and use the Chain rule:

10.3 LOSSLESS PROPAGATION con.

• Integrating (22) over time, obtaining the current in its forward and backward
propagating components:

• So here ‘𝑳𝒗’ is the characteristic impedence ‘𝒁𝒐 ’ for the lossless transmission line, and
is defined as the ratio of voltage to the current in a transmission line:

Dr Habib Fathallah, EE 214, Spring 2014 9


4/26/2014

10.3 LOSSLESS PROPAGATION con.

• Figure shows the forward


and backward propagating
voltage waves 𝑽+ and 𝑽−
both have positive polarity.

Current directions in waves


having positive voltage polarity.

• From (14) and (23):

• The current that associated with these voltages will flow in opposite direction.
• The –ve sign in the backward wave is due the –ve current

Summary

• Transmission lines (TLs) used to transmit signals from one point to another,
examples are: Coax cable, Wire over ground, Tri-lead wire, and Twisted pair.

• Characteristic impedance is the ratio of the voltage and current waves at any point
on the TL.

• Both Electric and Magnetic fields are present in the TLs and they are perpendicular
to each other and to the direction of wave propagation for TEM mode waves.

• TLs can be represented as a Lumped-element model.

• Wave eq.s in TLs are obtained through the solution of Telegraphist’s equation.

• In lossless propagation, power is not dissipated in the TL and all power at the I/P
end reaches the O/P end.

Dr Habib Fathallah, EE 214, Spring 2014 10


4/26/2014

outlines
Introduction .
10.1 PHYSICAL DESCRIPTION OF TRANSMISSION LINE PROPAGATION.
10.2 THE TRANSMISSION LINE EQUATIONS.
10.3 LOSSLESS PROPAGATION.
10.4 LOSSLESS PROPAGATION OF SINUSOIDAL VOLTAGES.
10.5 COMPLEX ANALYSIS OF SINUSOIDAL WAVES.
10.6 TRANSMISSION LINE EQUATIONS AND THEIR SOLUTIONS IN PHASOR FORM.
10.7 LOW-LOSS PROPAGATION.
10.8 POWER TRANSMISSION AND THE USE OF DECIBELS IN LOSS CHARACTERIZATION.
10.9 WAVE REFLECTION AT DISCONTINUITIES.
10.10 VOLTAGE STANDING WAVE RATIO.
10.11 TRANSMISSION LINES OF FINITE LENGTH.
10.12 SOME TRANSMISSION LINE EXAMPLES.
10.13 GRAPHICAL METHODS: THE SMITH CHART.

10.4 LOSSLESS PROPAGATION OF SINUSOIDAL VOLTAGES.

• Any transmitted signal can be decomposed into a discrete or continuous


summation of sinusoids.
• Beginning by assigning sinusoidal functions to the voltage functions in Eq. (14).
• We consider a specific frequency 𝒇𝟏 = 𝒇𝟐 = 𝑽𝟎 𝒄𝒐𝒔(𝝎𝒕 + ∅)

𝝎
• Where, |𝑽𝟎 | is the value of 𝑽 at 𝒛 = 𝟎, 𝒕 = 𝟎, ∅ = 𝟎, and phase constant 𝜷 =
𝒗𝒑

Real instantaneous
form of transmission
line voltages.

Dr Habib Fathallah, EE 214, Spring 2014 11


4/26/2014

10.4 LOSSLESS PROPAGATION OF SINUSOIDAL VOLTAGES con.

• Which we identify as a simple periodic function that repeats every incremental


distance 𝝀, known as the wavelength. The requirement is that 𝜷𝝀 = 𝟐𝝅, and so:

10.5 COMPLEX ANALYSIS OF SINUSOIDAL WAVES.

• Sinusoidal functions in complex form, based on Euler identity is:

(31)

• Where 𝒋 = −𝟏 and c.c is the complex conjugate of the preceding term.


• Then our voltage eqn becomes:

(32)

• i.e. our complex instantaneous eqn can be written as:


(33)

• And Phaser Voltage is , i.e for a study state condition:


(34)

Dr Habib Fathallah, EE 214, Spring 2014 12


4/26/2014

10.5 COMPLEX ANALYSIS OF SINUSOIDAL WAVES con.

(35)

(36)

10.5 COMPLEX ANALYSIS OF SINUSOIDAL WAVES con.

Dr Habib Fathallah, EE 214, Spring 2014 13


4/26/2014

10.6 TRANSMISSION LINE EQUATIONS AND THEIR SOLUTIONS IN


PHASOR FORM.
• From Wave eqn, for the real instantaneous voltage, we have:

• The wave equation in terms of phasor voltage:

• Z is the net series impedance and Y is the shunt admittance in a transmission


line. Where, 𝜸 is the propagation constant given by:
(41)

• Solution of eqn (38) is:


(42a)

10.6 TRANSMISSION LINE EQUATIONS AND THEIR SOLUTIONS IN PHASOR


FORM con.

(42b)

• In the same way as eqn. (37b), I(z,t) can be written as:

(43)

• Telegraphistic equation can be written as:

(44a)

(44b)

Dr Habib Fathallah, EE 214, Spring 2014 14


4/26/2014

10.6 TRANSMISSION LINE EQUATIONS AND THEIR SOLUTIONS IN PHASOR


FORM con.
• Substituting (42a) and (42b) into either (44a) or (44b) [we will use (44a)]:

(45)

• Equating coefficients of 𝒆−𝜸𝒛 and 𝒆𝜸𝒛

(46)

• From eqn (43) and (44):

(47)

• Comparing with ((37b) and (43),the phase of the characteristic impedance,


𝜽 = ∅ − 𝝃.

10.6 TRANSMISSION LINE EQUATIONS AND THEIR SOLUTIONS IN PHASOR


FORM con.

Dr Habib Fathallah, EE 214, Spring 2014 15


4/26/2014

10.7 LOW-LOSS PROPAGATION.

• Incorporating (41) into (42a) to obtain:

• Multiply by 𝒆𝒋𝒘𝒕 to get:

𝒏𝒆𝒑𝒆𝒓𝒔 𝑵𝒑
• Attenuation coefficient 𝜶 [ ]
𝒎 𝒎

10.7 LOW-LOSS PROPAGATION con.


• The low-loss approximation allows us to use the first three terms in the binomial series:

(54a)

(54b)

Dr Habib Fathallah, EE 214, Spring 2014 16


4/26/2014

10.7 LOW-LOSS PROPAGATION con.

• Applying the low-loss approximation to the characteristic impedance, Eq. (47). Using
(51), we find:

10.7 LOW-LOSS PROPAGATION con.

Dr Habib Fathallah, EE 214, Spring 2014 17


4/26/2014

10.8 POWER TRANSMISSION AND THE USE OF DECIBELS IN LOSS


CHARACTERIZATION

• Having found the sinusoidal voltage and current in a lossy transmission line, we
next evaluate the power transmitted over a specified distance as a function of
voltage and current amplitudes.

• The instantaneous power is:

• The time-averaged power < 𝑷 > is of interest:

• The time-averaged power in (60) is obtained from the phasor forms through:
Applies to any
single-frequency wave
• Where, the asterisk ∗ denotes the complex conjugate

10.8 POWER TRANSMISSION AND THE USE OF DECIBELS IN LOSS


CHARACTERIZATION con.
• Using (61) and (62) in (63):

Identical to the
time-integrated
result in (60).

• An important result of the preceding exercise is that power attenuates as 𝒆−𝟐𝜶𝒛 , or:

• Power drops at twice the exponential rate with distance as either voltage or current.
• A conventional measure of power loss is in decibel units. This is based on expressing
the power decreases as a power of 10, i.e. :

• Where, the constant k to be determined by setting 𝜶𝒛 = 𝟏, so:

Dr Habib Fathallah, EE 214, Spring 2014 18


4/26/2014

10.8 POWER TRANSMISSION AND THE USE OF DECIBELS IN LOSS


CHARACTERIZATION con.

• And by the definition, the power loss in dB is:

• Or equivalently:

• Where:

10.8 POWER TRANSMISSION AND THE USE OF DECIBELS IN LOSS


CHARACTERIZATION con.

Dr Habib Fathallah, EE 214, Spring 2014 19


4/26/2014

summary

• Any transmitted signal can be decomposed into a discrete or


continuous summation of sinusoids.

• Power attenuates as 𝒆−𝟐𝜶𝒛 in TLs.

• A conventional measure of power loss is in decibel units. This is based


on expressing the power decreases as a power of 10.

outlines
Introduction .
10.1 PHYSICAL DESCRIPTION OF TRANSMISSION LINE PROPAGATION.
10.2 THE TRANSMISSION LINE EQUATIONS.
10.3 LOSSLESS PROPAGATION.
10.4 LOSSLESS PROPAGATION OF SINUSOIDAL VOLTAGES.
10.5 COMPLEX ANALYSIS OF SINUSOIDAL WAVES.
10.6 TRANSMISSION LINE EQUATIONS AND THEIR SOLUTIONS IN PHASOR FORM.
10.7 LOW-LOSS PROPAGATION.
10.8 POWER TRANSMISSION AND THE USE OF DECIBELS IN LOSS CHARACTERIZATION.
10.9 WAVE REFLECTION AT DISCONTINUITIES.
10.10 VOLTAGE STANDING WAVE RATIO.
10.11 TRANSMISSION LINES OF FINITE LENGTH.
10.12 SOME TRANSMISSION LINE EXAMPLES.
10.13 GRAPHICAL METHODS: THE SMITH CHART.

Dr Habib Fathallah, EE 214, Spring 2014 20


4/26/2014

10.9 WAVE REFLECTION AT DISCONTINUITIES.

• A voltage wave is presumed to be incident on the load, and is expressed in


phasor form for all z as:

• When the wave reaches the load, a reflected wave is generated that back-
propagates.

• Fig. shows voltage wave reflection


from a complex load impedance.

• The phasor voltage at the load is the sum of the incident and reflected
voltage phasors, evaluated at z = 0:

10.9 WAVE REFLECTION AT DISCONTINUITIES con.

• The current through the load is the sum of the incident and reflected currents, also
at z = 0:

• And the reflection coefficient, 𝜞 is:

• Using (71) with (73), we write:

• And the transmission coefficient, 𝝉 is:

Dr Habib Fathallah, EE 214, Spring 2014 21


4/26/2014

10.9 WAVE REFLECTION AT DISCONTINUITIES con.

• The fractions of the incident wave power that are reflected and dissipated by the
load need to be determined.
• The incident power is found from (64), where we position the load at Z=L, with line
input at z = 0.

• The reflected power is found by substituting the reflected wave voltage into (76a);

• The fraction of reflected power at the load is obtained by the ratio of (76b) to (76a):

10.9 WAVE REFLECTION AT DISCONTINUITIES con.

• The fraction of the incident power that is transmitted into the load (or dissipated by
it) is therefore:

• For the connection of two semi-infinite transmission lines having different


characteristic impedances, reflections will occur at the junction, with the second line
being treated as the load.
• For a wave incident from line 1 (𝒁𝟎𝟏 ) to line 2 (𝒁𝟎𝟐 ), we find:

• The fraction of the power that propagates into the second line is then 𝟏 − 𝚪 𝟐 .

Dr Habib Fathallah, EE 214, Spring 2014 22


4/26/2014

10.9 WAVE REFLECTION AT DISCONTINUITIES con.

10.9 WAVE REFLECTION AT DISCONTINUITIES con.

Dr Habib Fathallah, EE 214, Spring 2014 23


4/26/2014

10.9 WAVE REFLECTION AT DISCONTINUITIES con.

10.9 WAVE REFLECTION AT DISCONTINUITIES con.

Dr Habib Fathallah, EE 214, Spring 2014 24


4/26/2014

10.10 VOLTAGE STANDING WAVE RATIO.


• The ratio of the maximum voltage to the minimum voltage is the
voltage standing wave ratio (VSWR) or ( SWR) given by:

Slotted line

10.10 VOLTAGE STANDING WAVE RATIO con.

• To understand the voltage measurements:


 First, if the slotted line is terminated by a matched impedance, then no reflected
wave occurs; the probe indicates the same voltage amplitude at every point.

• Fig. shows a sketch of


a coaxial slotted line
with distance scale.
The load is in place,
𝒔 = 𝟐. 𝟓, and the
min. occurs at a scale
reading of 47 cm.
• For a short circuit,
the min. is located at
a scale reading of 26
cm.

Dr Habib Fathallah, EE 214, Spring 2014 25


4/26/2014

10.10 VOLTAGE STANDING WAVE RATIO con.


 Second, if the slotted line is terminated by an open or short circuit , then the total
voltage in the line is a standing wave and the voltage probe provides no output when
it is located at the nodes; these occur periodically with half-wavelength spacing. As
the probe position is changed, its output varies as |cos(𝜷𝒛 + 𝝋)|, where z is the
distance from the load, and where the phase, φ, depends on the load impedance.

Fig. shows travelling


and standing waves
in a lossless open
circuited T.L

10.10 VOLTAGE STANDING WAVE RATIO con.

• If the load is a short circuit, the requirement of zero voltage at the short leads to a
null occurring there, and voltage in the line will vary as |sin(𝜷𝒛)| (where 𝝋 = ±𝝅/𝟐.

• A complicated situation, when the reflected voltage is neither 0 nor 100 percent of
the incident voltage. Some energy is absorbed by load and some is reflected.

• Slotted line supports a voltage that is composed of both a traveling wave and a
standing wave. It is customary to describe this voltage as a standing wave, even
though a traveling wave is also present.

• For animation video about SWR click: SWR.MP4

Dr Habib Fathallah, EE 214, Spring 2014 26


4/26/2014

10.10 VOLTAGE STANDING WAVE RATIO con.

• Voltage does not have zero amplitude at any point for all time, and the degree to

which the voltage is divided between a traveling wave and a standing wave is

expressed by the ratio of the max. amplitude found by the probe to the min.

amplitude (VSWR).

• This information, along with the positions of the voltage minima or maxima with

respect to that of the load, enable one to determine the load impedance.

10.10 VOLTAGE STANDING WAVE RATIO con.


• For the forward and backward-propagating waves occurring within the slotted line when
load is positioned at z = 0, with taking the I/P wave amplitude as V0, the total phasor
voltage is given by:

• If the load is a short circuit (𝒁𝑳 = 𝟎), ∅ is equal to 𝝅 ; if 𝒁𝑳 is real and less than 𝝅 𝒁𝟎 , ∅
is also equal to 𝝅 ; and if 𝒁𝑳 is real and greater than 𝒁𝟎 , ∅ is zero.

• Applying the algebraic trick of adding and subtracting the terms we get:

Dr Habib Fathallah, EE 214, Spring 2014 27


4/26/2014

10.10 VOLTAGE STANDING WAVE RATIO con.


• In real instantaneous form:

• Portion of the incident wave that reflects and back-propagates in slotted line
interferes with an equivalent portion of the incident wave to form a standing wave.
The rest of the incident wave (which does not interfere) is the traveling wave
• The min. and max. voltage amplitudes:

• The min. voltage amplitude is obtained when the two terms subtract directly
(having a phase difference of π). This occurs at locations:

10.10 VOLTAGE STANDING WAVE RATIO con.


• All positions within the slotted line occur at -ve values of z. Substitution of the
above eqn in 𝑽𝒔𝑻 (𝒛) leads to the min. amplitude:

• The voltage oscillates (through zero) in time, with amplitude 𝑽𝟎 (𝟏 − |𝚪|).


• Next, the max. voltage amplitude is obtained when the two terms 𝑽𝒔𝑻 (𝒛) add
in-phase. This will occur at locations:

• Substituting (89) into (85):

Dr Habib Fathallah, EE 214, Spring 2014 28


4/26/2014

10.10 VOLTAGE STANDING WAVE RATIO con.

• A voltage max. is located at the load (z = 0) if φ = 0; moreover, φ = 0 when reflection

coefficient is real and positive. This occurs for real 𝒁𝑳 when 𝒁𝑳 > 𝒁𝟎.

• Thus there is a voltage max. at the load when the load impedance is greater than 𝒁𝟎

and both impedances are real.

• With φ = 0, maxima also occur at 𝒁𝒎𝒂𝒙 = −𝒎𝝅/𝜷 = −𝒎𝝀/𝟐.

• For a zero-load impedance, φ = π, and the maxima are found at 𝒁𝒎𝒂𝒙 = −𝝅/

(𝟐𝜷), −𝟑𝝅/(𝟐𝜷), 𝒐𝒓𝒁𝒎𝒂𝒙 = −𝝀/𝟒, −𝟑𝝀/𝟒, and so forth.

• The minima are separated by multiples of one half-wavelength , and for a zero load

impedance, the first min. occurs when −𝜷𝒛 = 𝟎, or at the load.

10.10 VOLTAGE STANDING WAVE RATIO con.

• In general, a voltage min. is found at z = 0 whenever φ = π; this occurs if 𝒁𝑳 <


𝒁𝟎 where 𝒁𝑳 is real. The general results are illustrated in the following Fig.

• The SWR is given by:

The reflection coefficient phase


is φ, leads to the indicated
locations of max. and min.
voltage amplitude, as found
from Eqs. (86) and (89).

Dr Habib Fathallah, EE 214, Spring 2014 29


4/26/2014

10.10 VOLTAGE STANDING WAVE RATIO con.

10.11 TRANSMISSION LINES OF FINITE LENGTH

• When considering the prop. of sinusoidal voltages on finite-length lines with loads
that are not impedance matched, numerous reflections occur between the load
and generator, setting up a multiwave bidirectional voltage distribution in the line.
• To determine the net power transferred to the load in steady state, we must
include the effect of the forward- and backward-reflected waves.

Finite-length transmission line configuration Its equivalent circuit

Dr Habib Fathallah, EE 214, Spring 2014 30


4/26/2014

10.11 TRANSMISSION LINES OF FINITE LENGTH con.

• The line exists along the negative part of z axis.

• The easiest method of approaching the problem is not to attempt to analyze

every reflection individually, but rather to recognize that: in steady state, there

will exist one net forward wave and one net backward wave, representing the

superposition of all waves that are incident on the load and all waves that are

reflected from it.

• We may thus write the total voltage in the line as:

10.11 TRANSMISSION LINES OF FINITE LENGTH con.


• Where, 𝑽+
𝟎 and 𝑽𝟎 are complex amplitudes, composed respectively of the sum

of all individual forward and backward wave amplitudes and phases.


• In similar way, we may write the total current in th line as:

• We define the wave impedance, 𝒁𝒘 (𝒛) as the ratio of the total


phasor voltage to the total phasor current, and given by:

Dr Habib Fathallah, EE 214, Spring 2014 31


4/26/2014

10.11 TRANSMISSION LINES OF FINITE LENGTH con.


• Where, :

• And:

• From Euler identity:

• We have at 𝒛 = −𝒍 :

10.11 TRANSMISSION LINES OF FINITE LENGTH con.


• One special case is that in which the line length is half wave length, or an
integer multiple therefore:

• For half-wave line, the equivalent circuit can be constructed simply by removing the
line completely and placing the load impedance at the input.

• Another important special case is that in which the line length is an odd multiple of
a quarter wavelength i.e.:

Dr Habib Fathallah, EE 214, Spring 2014 32


4/26/2014

10.11 TRANSMISSION LINES OF FINITE LENGTH con.


• An application of the last equation is to the problem of joining two lines having
different characteristic impedances:
• Suppose the impedances are (from the left to the right) 𝒁𝟎𝟏 and 𝒁𝟎𝟑 .
• At the joint we can insert an additional line whose characteristic impedance is 𝒁𝟎𝟐
with length 𝝀/𝟒.
• We thus have a sequence of joined lines whose impedances progress as
𝒁𝟎𝟏 , 𝒁𝟎𝟐 , 𝒂𝒏𝒅 𝒁𝟎𝟑 in that order.
• Now a voltage wave is incident from line 1 onto the joint between 𝒁𝟎𝟏 and 𝒁𝟎𝟐 .
• Therefore the effective load at the far end of line 2 is 𝒁𝟎𝟑 . and the input impedance to
line 2 at any frequency is now: Zin(line 2) equals:

10.11 TRANSMISSION LINES OF FINITE LENGTH con.


• And since the length of line 2 is 𝝀/𝟒, we have:

• Reflections at the 𝒁𝟎𝟏 − 𝒁𝟎𝟐 interface will not occur if


𝒁𝒊𝒏 𝐥𝐢𝐧𝐞 𝟏 = 𝒁𝟎𝟏 𝐛𝐞𝐜𝐚𝐮𝐬𝐞 𝐨𝐟 𝐢𝐦𝐩𝐞𝐝𝐚𝐧𝐜𝐞 𝐦𝐚𝐭𝐜𝐡𝐢𝐧𝐠 . Therefore, we can match
the junction (allowing complete transmission through the three-line sequence.
• If 𝒁𝟎𝟐 is chosen so that:

• This value of 𝒁𝟎𝟐 leads to 𝒁𝒊𝒏 𝐥𝐢𝐧𝐞 𝟏 = 𝒁𝟎𝟏


• This technique is called quarter-wave matching.

Dr Habib Fathallah, EE 214, Spring 2014 33


4/26/2014

summary
• When the wave reaches the load, a reflected wave is generated that back-propagates.

• The phasor voltage (or current) at the load is the sum of the incident and reflected voltage
phasors.

• When connecting two semi-infinite transmission lines having different characteristic


impedances, reflections will occur at the junction, and the second line is treated as the load.

• Voltage standing wave ratio (VSWR) or ( SWR) is the ratio of the maximum voltage to the
minimum voltage.

• When considering the propagation of sinusoidal voltages on finite-length lines that have
loads that are not impedance matched, numerous reflections occur at the load and at the
generator, setting up a multi-wave bidirectional voltage distribution in the line.

• The wave impedance, 𝒁𝒘 (𝒛) is the ratio of the total phasor voltage to the total phasor
current.

outlines
Introduction .
10.1 PHYSICAL DESCRIPTION OF TRANSMISSION LINE PROPAGATION.
10.2 THE TRANSMISSION LINE EQUATIONS.
10.3 LOSSLESS PROPAGATION.
10.4 LOSSLESS PROPAGATION OF SINUSOIDAL VOLTAGES.
10.5 COMPLEX ANALYSIS OF SINUSOIDAL WAVES.
10.6 TRANSMISSION LINE EQUATIONS AND THEIR SOLUTIONS IN PHASOR FORM.
10.7 LOW-LOSS PROPAGATION.
10.8 POWER TRANSMISSION AND THE USE OF DECIBELS IN LOSS CHARACTERIZATION.
10.9 WAVE REFLECTION AT DISCONTINUITIES.
10.10 VOLTAGE STANDING WAVE RATIO.
10.11 TRANSMISSION LINES OF FINITE LENGTH.
10.12 SOME TRANSMISSION LINE EXAMPLES.
10.13 GRAPHICAL METHODS: THE SMITH CHART.

Dr Habib Fathallah, EE 214, Spring 2014 34


4/26/2014

10.12 SOME TRANSMISSION LINE EXAMPLES.

10.12 SOME TRANSMISSION LINE EXAMPLES con.

Dr Habib Fathallah, EE 214, Spring 2014 35


4/26/2014

10.12 SOME TRANSMISSION LINE EXAMPLES con.

10.12 SOME TRANSMISSION LINE EXAMPLES con.

Dr Habib Fathallah, EE 214, Spring 2014 36


4/26/2014

10.12 SOME TRANSMISSION LINE EXAMPLES con.

10.12 SOME TRANSMISSION LINE EXAMPLES con.

Dr Habib Fathallah, EE 214, Spring 2014 37


4/26/2014

10.12 SOME TRANSMISSION LINE EXAMPLES con.

10.12 SOME TRANSMISSION LINE EXAMPLES con.

Dr Habib Fathallah, EE 214, Spring 2014 38


4/26/2014

10.12 SOME TRANSMISSION LINE EXAMPLES con.

10.13 GRAPHICAL METHODS: THE SMITH CHART.

• Basically, this diagram shows curves of constant resistance and constant reactance.

• The diagram is constructed within a circle of


unit radius, using polar coordinates, with
radius variable |𝜞| and counterclockwise
angle variable 𝝓, where 𝜞 = 𝜞 𝒆𝒋𝝓 =
• The polar coordinates of the smith chart are
the magnitude and phase angle of the
reflection coefficient.
• The rectangular coordinates are the real and
the imaginary parts of the reflection
coefficient. We can reduce the TL problems
• The entire chart lies within the circle 𝜞 = 𝟏. labor, without seriously affecting
the accuracy, by using Smith charts

Dr Habib Fathallah, EE 214, Spring 2014 39


4/26/2014

10.13 GRAPHICAL METHODS: THE SMITH CHART con.


• The basic relationship upon which the chart is constructed is:

• The impedances that we plot on the chart will be normalized with respect to the
charc. impedance. Let us identify the normalized load impedance as 𝒛𝑳,

• In polar form, we have used 𝜞 and 𝝓 as the magnitude and angle of 𝜞. With
𝜞𝒓 and 𝜞𝒊 as the real and imaginary parts of 𝜞, we write:

10.13 GRAPHICAL METHODS: THE SMITH CHART con.

• Thus:

• The real and imaginary parts of this equation are:

Dr Habib Fathallah, EE 214, Spring 2014 40


4/26/2014

10.13 GRAPHICAL METHODS: THE SMITH CHART con.

• After several lines of elementary algebra we get:

(112)

(113)

Constant-r circles are shown on the 𝜞𝒓 , 𝜞𝒊


plane. The radius of any circle is 𝟏/(𝟏 + 𝒓)

10.13 GRAPHICAL METHODS: THE SMITH CHART con.

• The first equation describes a family of circles, where each circle is associated
with a specific value of resistance r.
• For example, if 𝒓 = 𝟎, the radius of this zero resistance circle is seen to be unity,
and it is centered at the origin (𝜞𝒓 = 𝟎, 𝜞𝒊 = 𝟎), and this for a pure reactance
termination leads to a reflection coefficient of unity magnitude.
• If 𝒓 = ∞, 𝒕𝒉𝒆𝒏 𝒁𝑳 = ∞ and we have 𝜞 = 𝟏 + 𝒋𝟎.
• The circle described by eq. (112) is centered at 𝜞𝒓 = 𝟏, 𝜞𝒊 = 𝟎 and has zero
radius. It is therefore the point 𝜞 = 𝟏 + 𝒋𝟎.
• As another example, the circle for 𝒓 = 𝟏, is centered at 𝜞𝒓 = 𝟎. 𝟓, 𝜞𝒊 = 𝟎 and
has a radius of 0.5. This circle is shown in the last, along with circles for
𝒓 = 𝟎. 𝟓, 𝒂𝒏𝒅 𝒓 = 𝟐, All circles are centered on the 𝜞𝒓 axis and pass through the
point 𝜞 = 𝟏 + 𝒋𝟎.

Dr Habib Fathallah, EE 214, Spring 2014 41


4/26/2014

10.13 GRAPHICAL METHODS: THE SMITH CHART con.

• Equation (113) also represents a family of circles, but each of these circles is defined by a
particular value of x, rather than r.

• If 𝐱 = ∞, 𝒕𝒉𝒆𝒏 𝒁𝑳 = ∞ and again 𝜞 = 𝟏 + 𝒋𝟎


• The circle described by (113) is centered at 𝜞 = 𝟏 + 𝒋𝟎
and has zero radius.
• If 𝒙 = +𝟏, then the circle is centered at 𝜞 = 𝟏 + 𝒋𝟏 and
has unit radius. Only one-quarter of this circle lies
within the boundary curve 𝜞 = 𝟏 as shown.
• A similar quarter-circle appears below the 𝜞𝒓 axis for
𝒙 = −𝟏
• The portions of other circles for 𝒙 = 𝟎. 𝟓, −𝟎. 𝟓, 𝟐, The portions of the circles of constant 𝒙
𝒂𝒏𝒅 − 𝟐 are also shown. The “circle” representing 𝒙 = lying within 𝜞 = 𝟏 are shown on the 𝜞𝒓,𝜞𝒊
axes. The radius of a given circle is 𝟏/|𝒙|
𝟎 is 𝜞𝒓 axis; this is also labeled in the Fig.

10.13 GRAPHICAL METHODS: THE SMITH CHART con.

• An example, if 𝒁𝑳 = 𝟐𝟓 + 𝒋𝟓𝟎 𝜴 line.

The reflection coefficient is approximately 0.62 at an angle φ of 83◦.

Dr Habib Fathallah, EE 214, Spring 2014 42


4/26/2014

10.13 GRAPHICAL METHODS: THE SMITH CHART con.

• By the current:

• Obtaining the normalized input impedance:

• Replacing 𝒛 with −𝒍 and dividing numerator and denominator by 𝒆 𝒋𝜷𝒍, we have


the general equation relating normalized input impedance, reflection coefficient,
and line length:

10.13 GRAPHICAL METHODS: THE SMITH CHART con.

• The last equation shows that the Input impedance at any point 𝒛 = −𝒍 can be
obtained by replacing 𝜞 𝐛𝐲 𝜞𝒆−𝒋𝟐𝜷𝒍 𝐢𝐧 𝐭𝐡𝐞 𝐞𝐱𝐩𝐫𝐞𝐬𝐬𝐢𝐨𝐧 𝐨𝐟 𝒛𝑳
• Hence the angle of 𝜞 decreases by 𝟐𝜷𝒍 as we move from the load to the line I/P.
• Only the angle of 𝜞 changes, the magnitude remains constant.
• Thus, as we proceed from the load 𝒛𝑳 to the input impedance 𝒛𝒊𝒏 , we move toward
the generator a distance 𝒍 in the transmission line, but we move through a clockwise
angle of 𝟐𝜷𝒍 on the Smith chart.
• Since the magnitude stays constant, the movement toward the source is made along a
constant-radius circle.
• One lap around the chart is accomplished whenever 𝜷𝒍 changes by 𝝅 𝒓𝒂𝒅, or when 𝒍
changes by one half wavelength. This agrees with our earlier discovery that the input
impedance of a half-wavelength lossless line is equal to the load impedance.

Dr Habib Fathallah, EE 214, Spring 2014 43


4/26/2014

10.13 GRAPHICAL METHODS: THE SMITH CHART con.

Dr Habib Fathallah, EE 214, Spring 2014 44


4/26/2014

10.13 GRAPHICAL METHODS: THE SMITH CHART con.

10.13 GRAPHICAL METHODS: THE SMITH CHART con.

• To obtain the location of the 𝑽𝒎𝒂𝒙 &𝑽𝒎𝒊𝒏 from Smith chart, we know that a max. or
min. must occur at the load when 𝒁𝑳 is a pure resistance;
 If 𝑹𝑳 > 𝒁𝟎 there is a max. at the load.
 If 𝑹𝑳 < 𝒁𝟎 there is a min.

• We can cut off the load end of a TL at a point where 𝒁𝒊𝒏 is a pure resistance and
replace that section with a resistance 𝑹𝒊𝒏 ; there would be no changes on the
generator portion of the line.
• Then, that the location of 𝑽𝒎𝒂𝒙 &𝑽𝒎𝒊𝒏 is at those points where 𝒁𝒊𝒏 is a pure
resistance.
• Purely resistive 𝒁𝒊𝒏 must occur on the x = 0 line (the 𝚪𝒓 axis) of the Smith chart.
• 𝑽𝒎𝒂𝒙 𝒐𝒓 𝑰𝒎𝒊𝒏 occur when r > 1, or 𝒂𝒕 𝒘𝒕𝒈 = 𝟎. 𝟐𝟓, and 𝑽𝒎𝒊𝒏 𝒐𝒓 𝑰𝒎𝒂𝒙 occur when r
< 1, or at 𝒘𝒕𝒈 = 𝟎.

Dr Habib Fathallah, EE 214, Spring 2014 45


4/26/2014

10.13 GRAPHICAL METHODS: THE SMITH CHART con.

• In Example 10.10, then, the max. at 𝒘𝒕𝒈 = 𝟎. 𝟐𝟓𝟎 occurs 0.250 − 0.135 = 0.115
wavelengths toward generator from the load.
• This is a distance of 0.115 × 200, or 23 cm from the load.

• The value of 𝒔 is read as the value of r at the


intersection of the |𝚪| circle and the r
axis, 𝒓 > 𝟏.
• In our example, this intersection is marked
point C, and 𝒓 = 𝟒. 𝟐; 𝒕𝒉𝒖𝒔, 𝒔 = 𝟒. 𝟐.

10.13 GRAPHICAL METHODS: THE SMITH CHART con.

• TL charts also used for normalized admittances, we let 𝒚𝑳 = 𝒀𝑳 /𝒀𝟎 = 𝒈 + 𝒋𝒃 and


use the r circles as g circles and the x circles as b circles.

• The two differences are:


1. Line segment where g > 1 and b = 0 corresponds to 𝑽𝒎𝒊𝒏 .

2. 180◦ must be added to the angle of 𝚪 as read from the perimeter of the chart. We use the
Smith chart in this way in next section.

• Special charts are available for non-normalized lines, particularly 𝟓𝟎 𝛀 charts and
𝟐𝟎 𝒎𝑺 charts.

Dr Habib Fathallah, EE 214, Spring 2014 46


4/26/2014

10.13 GRAPHICAL METHODS: THE SMITH CHART con.

• We next consider two examples of practical TL problems.


1. The determination of load impedance from experimental data.

2. The design of a single-stub matching network.

• Assuming we made
experimental measurements
on a 50 slotted line that
𝒔 = 𝟐. 𝟓.
• This determined by moving a
sliding carriage back and forth
along the line to determine
A sketch of a coaxial slotted line with distance scale.
𝑽𝒎𝒂𝒙&𝑽𝒎𝒊𝒏 readings as shown.
The load in place, s = 2.5, and min. occurs at a scale
reading of 47 cm. For a short circuit, min. is located at
a scale reading of 26 cm. The wavelength is 75 cm.

10.13 GRAPHICAL METHODS: THE SMITH CHART con.

• Let us locate short circuit one 𝝀/𝟐 away at 26.0 − 37.5 = −11.5 cm on the scale.

• Since the short circuit replaced the load, the load is located at −11.5 cm.

• Data show that the min. is 47.0 − (−11.5) = 58.5 cm from the load, or subtracting 𝝀/𝟐 ,
a min. is 21cm from the load.

• 𝑽𝒎𝒂𝒙 is thus 21−(37.5/2) = 2.25 cm from the load, or 2.25/75 = 0.03 wavelength from
the load.

• Now, we turn to the Smith chart. At 𝑽𝒎𝒂𝒙, the 𝒁𝒊𝒏 is a pure resistance equal to 𝒔𝑹𝟎 ;
on a normalized basis,𝒁𝒊𝒏 = 𝟐. 𝟓.

Dr Habib Fathallah, EE 214, Spring 2014 47


4/26/2014

10.13 GRAPHICAL METHODS: THE SMITH CHART con.

• We enter the chart at 𝒁𝒊𝒏 = 𝟐. 𝟓 and read 𝟎. 𝟐𝟓 on the wtg scale.

• Subtracting 0.03 wavelength to reach the load, we find that the intersection of the
𝒔 = 𝟐. 𝟓 (𝒐𝒓 |𝚪| = 𝟎. 𝟒𝟐𝟗) circle and the radial line to 0.22 wavelength is at
𝒁𝑳 = 𝟐. 𝟏 + 𝒋𝟎. 𝟖.

• The construction is sketched as shown.


• Thus 𝒁𝑳 = 𝟏𝟎𝟓 + 𝒋𝟒𝟎, a value assumes its
location at a scale reading of −11.5 cm, or
an integral # of 𝝀/𝟐 from that position.

10.13 GRAPHICAL METHODS: THE SMITH CHART con.

• As a final example, lets match this load to the 𝟓𝟎 𝛀 line by placing a short-circuited
stub of length d1 a distance d from the load as shown.

• We want to determine the lengths d &d1.

• 𝒀𝒊𝒏 of the length d containing the load


must be 𝟏 + 𝒋𝒃𝒊𝒏 for addition of 𝒀𝒊𝒏 of
the stub 𝒋𝒃𝒔𝒕𝒖𝒃 to give 𝒀𝒕𝒐𝒕 = 𝟏 + 𝒋 𝟎.
• Hence, the stub admittance is −𝒋𝒃𝒊𝒏 .
• We will therefore use the Smith chart as
an admittance chart instead of an
impedance chart.
A short-circuited stub of length d1 located at
distance d from a load 𝒁𝑳 , is used to provide
a matched load to the left of the stub.

Dr Habib Fathallah, EE 214, Spring 2014 48


4/26/2014

10.13 GRAPHICAL METHODS: THE SMITH CHART con.

1. 𝒁 of the load is 𝟐. 𝟏 + 𝐣𝟎. 𝟖, and its location is at −11.5 cm.


2. 𝒀 of the load is therefore 1/(2.1+ j0.8), and this value may be determined by adding 𝝀/𝟒 on
the Smith chart, as 𝐙𝐢𝐧 for a 𝝀/𝟒 line is 𝐑𝟐𝟎 /𝐙𝐋 , or 𝐙𝐢𝐧 = 𝟏/𝐙𝐋 , or 𝐘𝐢𝐧 = 𝐙𝐋 .

3. Entering the chart at 𝒁𝑳 = 𝟐. 𝟏 + 𝒋𝟎. 𝟖,


we read 0.22 on the wtg scale.

4. We add (or subtract) 0.25 and find


𝒀 = 𝟎. 𝟒𝟏 − 𝒋𝟎. 𝟏𝟔 corresponding to this
𝒁, this point is still located on the
𝒔 = 𝟐. 𝟓 𝒄𝒊𝒓𝒄𝒍𝒆.
A normalized load, 𝒛𝑳 = 𝟐. 𝟏 + 𝒋 𝟎. 𝟖, is
matched by placing a 0.129-wavelength short-
circuited stub 0.19 wavelengths from the load.

10.13 GRAPHICAL METHODS: THE SMITH CHART con.

• Now, finding the point or points on this circle in which the real part of 𝒀equal to unity.

5. There are two answers, 𝟏 + 𝒋𝟎. 𝟗𝟓 𝒂𝒕 𝒘𝒕𝒈 = 𝟎. 𝟏𝟔, and 𝟏 − 𝒋𝟎. 𝟗𝟓 𝒂𝒕 𝒘𝒕𝒈 =
𝟎. 𝟑𝟒, as shown.

• We select the 1st value since it leads to


the shorter stub. Hence 𝒚𝒔𝒕𝒖𝒃 =
− 𝒋𝟎. 𝟗𝟓, and the stub location
corresponds to 𝒘𝒕𝒈 = 𝟎. 𝟏𝟔.

6. Because the load 𝒀 was found at


𝒘𝒕𝒈 = 𝟎. 𝟒𝟕𝟎, then we move
(𝟎. 𝟓 − 𝟎. 𝟒𝟕) + 𝟎. 𝟏𝟔 = 𝟎. 𝟏𝟗
wavelength to get to the stub location.

Dr Habib Fathallah, EE 214, Spring 2014 49

Vous aimerez peut-être aussi