Thermostat
FOR SINGLE- OR MULTI-STAGE CONVENTIONAL/
HEAT PUMP SYSTEMS
INSTALLATION INSTRUCTIONS
APPLICATION Location
Do not install the thermostat where it can be affected by:
The T7350 Commercial Programmable Thermostat — drafts or dead spots behind doors and in corners.
controls 24 Vac commercial single zone heating, — hot or cold air from ducts.
ventilating and air conditioning (HVAC) equipment. The — radiant heat from sun or appliances.
T7350 consists of a thermostat and subbase. The — concealed pipes and chimneys.
thermostat includes the display and keypad for 7-day — unheated (uncooled) areas such as an outside wall
programming. The subbase includes equipment control behind the thermostat.
connections. The subbase mounts on the wall and the
thermostat mounts to the subbase. IMPORTANT
To avoid electrical interference, which can
cause erratic performances, keep wiring runs as
short as possible and do not run thermostat
MERCURY NOTICE wires adjacent to the line voltage electrical
distribution systems. Use shielded cable. The
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old cable shield must be grounded only at the
control in the trash. Dispose of properly. controlled equipment case.
62-0195-06
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
NOTE: Only TR21 models with no setpoint adjustment 2. Use a pencil to mark the mounting holes.
can be used for temperature averaging. (See Fig. 3.)
3. Remove the subbase from the wall and drill two
3/16 in. (4.8 mm) holes in the wall (if drywall) as
marked. For firmer material such as plaster or
wood, drill two 7/32 in. (5.6 mm) holes.
YES 4. Gently tap anchors (provided) into the drilled holes
NO
until flush with the wall.
5. Position the subbase over the holes, pulling wires
NO
NO
5 FEET
through the wiring opening.
(1.5 METERS) 6. Loosely insert the mounting screws into the holes.
7. Tighten mounting screws.
M4823A
WIRES THROUGH WALL
MOUNTING
HOLES
Fig. 1. Typical location of thermostat
or remote-mounted sensor.
SUBBASE
T4 T3
TR21 TR21
WALL
ANCHORS
T T T T (2)
MOUNTING
TR21 TR21 SCREWS
T T T T M19608
M29184
Mounting Thermostat on Subbase
Fig. 2. Four TR21 sensors providing temperature
averaging network for T7350 Thermostat.
(Fig. 4)
With the subbase installed, mount the thermostat:
1. Engage top subbase tabs into the thermostat top.
Mounting Subbase 2. Swing the thermostat down.
The subbase mounts horizontally. 3. Press the lower edge of the case to latch.
62-0195—06 2
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Setting Temperature
Refer to Table 2 for the default temperature setpoints. See
the Product Data (form 63-2605) for complete instructions
on changing the setpoints.
System Settings
— Auto: Thermostat automatically changes between
heating and cooling based on indoor temperature.
— Cool: Thermostat controls cooling.
— Off: Heating, cooling, and fan are all off.
— Heat: Thermostat controls heating.
B. PRESS LOWER EDGE OF CASE TO LATCH.
— Em Heat: Auxiliary heat serves as first stage.
Compressor stages are locked off.
Fan Settings
— On: See Table 1.
— Auto: Fan always cycles with call for heat or cool.
— Conventional: The equipment (i.e. plenum switch)
controls fan operation in heat mode. Thermostat
controls fan operation in cool mode.
— Electric Heat: Thermostat controls fan operation in
both heat and cool modes.
M19610
3 62-0195—06
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Heating 70°F (21°C) 55°F (13°C) 67°F (19°C) The PDA T7350 Configuration Tool or the PC Tool
Cooling 75°F (24°C) 85°F (29°C) 78°F (26°C) LonSpec can also be used as follows:
1. Open the PDA Config Tool Application.
2. Select the desired configuration.
3. On the summary screen, tap CnfgID.
Temporary Standby Set Set Schedule Room 4. The PDA determines the proper CnfgID.
Not Occupied12 StartTime
AM 5. Make note of the values.
PM % 6. Press both Copy and Run Schedule.
MonTueWedThuFri SatSunHol MinsDays 7. Tap until C1 appears on the right end of the dis-
System Fan play.
Em Heat Off Cool Auto Dehumid OnAuto
M19611
NOTE: While stepping toward C1, check other
Fig. 6. LCD display of all segments. items to ensure they are set properly. See
Setup Using Keypad section.
62-0195—06 4
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Occupied Selects occupied event start times for specified day. Repeatedly press this key
to toggle between two occupied events.
Not Occupied Selects not occupied event start times for specified day. Repeatedly press this
key to toggle between two not occupied events.
Clear Start Time Clears start time for specified period and day.
System Selects System Mode. Toggles through Em Heat, Heat, Off, Cool, and Auto.
Run Schedule Resumes running schedule (cancels Temporary Occupied action, Holiday, and/
or Temporary setpoint changes.)
a On: Continuous fan operation (occupied and standby). During not occupied periods, fan cycles with call for heat or cool.
Auto: Fan cycles with call for heat or cool during all periods. (See Product Data Sheet, form 63-2605, for more details.)
NOTES: The display returns to default screen after pressing Run Schedule (or after a period of time without keypress):
— ten seconds: when returning from temporary setpoint changes, info screen, temp occ, and temp not occ.
— one minute: when returning from setting clock/day.
— ten minutes: when returning from System Checkout.
— five minutes: when returning from all other modes.
5 62-0195—06
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
62-0195—06 6
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
7 62-0195—06
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
SUBBASE
2
X RH RC AUX W1 Y1 G
HEAT FAN
RELAY 1 RELAY
COMPRESSOR
HEAT
CONTACTOR 1
RELAY 2
L2 L2
1 1
L1 L1
(HOT) (HOT)
HEATING COOLING
TRANSFORMER TRANSFORMER
2 WHEN INSTALLED ON A SYSTEM WITH TWO TRANSFORMERS, REMOVE THE FACTORY-INSTALLED JUMPER.
M19764A
Fig. 7. Typical hookup of T7350A in two-stage heat and one-stage cool conventional system
with two transformers.
BYPASS
SET PT
SENSOR COMPRESSOR
GND
LED
CONTACTOR 2
1 2 3 4 5 6 7 8 9 10 11 12 DISCHARGE
AIR HEAT
SENSOR RELAY 2
SUBBASE
T5 T6 T7 T4 T3 OS OS AS AS W2 Y2
X RH RC AUX W1 Y1 G
HEAT FAN
RELAY 1 RELAY
COMPRESSOR
CONTACTOR 1
3
L2 ECONOMIZER L2
1 1
L1 L1
(HOT) (HOT)
HEATING COOLING
TRANSFORMER TRANSFORMER
2 WHEN INSTALLED ON A SYSTEM WITH TWO TRANSFORMERS, REMOVE THE FACTORY-INSTALLED JUMPER.
Fig. 8. Typical hookup of T7350B in two-stage heat and two-stage cool heat pump system
with two transformers.
62-0195—06 8
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
SENSOR
BYPASS
SET PT
SENSOR RELAY 2
GND
LED
1 2 3 4 5 6 7 8 9 10 11 12 DISCHARGE
AIR COMPRESSOR
SENSOR CONTACTOR 2
SUBBASE
T5 T6 T7 T4 T3 OS OS AS AS W2 Y2
2
X RH RC AUX W1 Y1 G
HEAT FAN
RELAY 1 RELAY
COMPRESSOR
HEAT
CONTACTOR 1
RELAY 3
L2 L2
1 1
L1 L1
(HOT) (HOT)
HEATING COOLING
TRANSFORMER TRANSFORMER
2 WHEN INSTALLED ON A SYSTEM WITH TWO TRANSFORMERS, REMOVE THE FACTORY-INSTALLED JUMPER.
M32141
Fig. 9. Typical hookup of T7350B in three-stage heat and two-stage cool conventional system
with two transformers.
BYPASS
SET PT
SENSOR STAGE 1
GND
LED
1 2 3 4 5 6 7 8 9 10 11 12 DISCHARGE
AIR COMPRESSOR
SENSOR CONTACTOR 2
SUBBASE
T5 T6 T7 T4 T3 OS OS AS AS W2 Y2
X RH RC AUX O/B Y1 G
CHANGE FAN
OVER RELAY
COMPRESSOR
CONTACTOR 1
3
L2 ECONOMIZER L2
1 1
L1 L1
(HOT) (HOT)
HEATING COOLING
TRANSFORMER TRANSFORMER
2 WHEN INSTALLED ON A SYSTEM WITH TWO TRANSFORMERS, REMOVE THE FACTORY-INSTALLED JUMPER.
Fig. 10. Typical hookup of T7350B in three-stage heat and two-stage cool heat pump system
with two transformers.
9 62-0195—06
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
SENSOR
HEAT
BYPASS
SET PT
SENSOR RELAY 2
GND
LED
1 2 3 4 5 6 7 8 9 10 11 12 DISCHARGE
AIR COMPRESSOR COMPRESSOR
SENSOR CONTACTOR 4 CONTACTOR 2
SUBBASE
T5 T6 T7 T4 T3 OS OS AS AS W3/Y4 Y3 W2 Y2
HS HC HP M M X RH RC AUX W1 Y1 G
5 COMPRESSOR
CONTACTOR 3
COMPRESSOR
CONTACTOR 1
4
L2
1 2 ECONOMIZER
L1
(HOT)
5 WHEN USING THE TR23-H FOR HUMIDITY SENSING THERE IS NO NEED TO WIRE HC TERMINAL
BECAUSE THE T3 TERMINAL IS INTERNALLY TIED TO HC, WHICH IS ALSO TIED TO TERMINAL 1
COMMON AT THE SENSOR. M29254
Fig. 11. Typical hookup of T7350D in two-stage heat and four-stage cool conventional system.
BYPASS
SET PT
LED
1 2 3 4 5 6 7 8 9 10 11 12 DISCHARGE MODULATING R
AIR – HEAT
SENSOR + (4-20 mA) X
SUBBASE
T5 T6 T7 T4 T3 OS OS AS AS MX MH MC
HS HC HP M M X RH RC AUX W1 Y1 G
4 2
COMPRESSOR
3 CONTACTOR 1
L2 L2
1 ECONOMIZER 1
L1 L1
(HOT) (HOT)
HEATING COOLING
TRANSFORMER TRANSFORMER
2 WHEN INSTALLED ON A SYSTEM WITH TWO TRANSFORMERS, REMOVE THE FACTORY-INSTALLED JUMPER.
4 WHEN USING THE TR23-H FOR HUMIDITY SENSING THERE IS NO NEED TO WIRE HC TERMINAL
BECAUSE THE T3 TERMINAL IS INTERNALLY TIED TO HC, WHICH IS ALSO TIED TO TERMINAL 1
COMMON AT THE SENSOR. M32143
Fig. 12. Typical hookup of T7350M in two-stage heat (one modulating) and two-stage cool (one modulating)
conventional system with two transformers.
62-0195—06 10
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
SENSOR
BYPASS
SET PT
SENSOR + (4-20 mA) X
GND
LED
1 2 3 4 5 6 7 8 9 10 11 12 DISCHARGE MODULATING R
AIR – HEAT
SENSOR + (4-20 mA) X
SUBBASE
T5 T6 T7 T4 T3 OS OS AS AS MX MH MC AUX
EB EB HS HC HP M M X RH RC AUX W1 Y1 G
4 2
2 WHEN INSTALLED ON A SYSTEM WITH TWO TRANSFORMERS, REMOVE THE FACTORY-INSTALLED JUMPER.
4 WHEN USING THE TR23-H FOR HUMIDITY SENSING THERE IS NO NEED TO WIRE HC TERMINAL
BECAUSE THE T3 TERMINAL IS INTERNALLY TIED TO HC, WHICH IS ALSO TIED TO TERMINAL 1
COMMON AT THE SENSOR. M32144
Fig. 13. Typical hookup of T7350H1017 for system with two independent heat stages (one modulating),
two independent cool stages (one modulating), and two transformers.
AIR COMPRESSOR
BYPASS
SET PT
LED
SUBBASE
T5 T6 T7 T4 T3 OS OS AS AS AUX W3/Y4 Y3 W2 Y2
EB EB HS HC HP M M X RH RC AUX W1 Y1 G
5 COMPRESSOR
CONTACTOR 3
LONWORKS®
BUS
COMPRESSOR
CONTACTOR 1
L2
1 2
L1
(HOT)
Fig. 14. Typical hookup of T7350H1009 in three-stage heat and three-stage cool conventional system
with one transformer.
11 62-0195—06
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
DEHUMIDIFICATION (T7350D,H,M)
There are five methods through which the T7350 can Reset Temp SetPt
control for dehumidification. Three of them modify the The room temperature setpoint resets to a specified
control algorithm, thus providing limited dehumidification number of degrees below the actual setpoint when room
through cooling. The other two use the auxiliary output to relative humidity (RH) rises above humidity high limit
control another device. setpoint.