Segunda parte: falta assim�trica AN�LISE NA BARRA 5

A) CURTO FASE-TERRA

Enter Faulted Bus No. -> 5

Enter Fault Impedance Zf = R + j*X in complex form (for bolted fault enter 0). Zf =
0

Single line to-ground fault at bus No. 5


Total fault current = 4.0799 per unit

Bus Voltages during the fault in per unit

Bus -------Voltage Magnitude-------


No. Phase a Phase b Phase c
1 0.7295 0.9397 0.9397
2 0.5890 0.9471 0.9471
3 0.6967 0.9606 0.9606
4 0.8417 0.9774 0.9774
5 0.0000 1.0261 1.0261
6 0.6954 0.9629 0.9629
7 0.6306 0.9824 0.9824
8 0.6862 0.9739 0.9739
9 0.7514 0.9744 0.9744
10 0.8956 0.9856 0.9856
11 0.8068 0.9554 0.9554

Line currents for fault at bus No. 5

From To -----Line Current Magnitude----


Bus Bus Phase a Phase b Phase c
1 2 1.3526 0.6763 0.6763
2 5 2.9015 0.0869 0.0869
3 2 0.3349 0.1312 0.1312
4 3 0.3333 0.1229 0.1229
4 10 0.6745 0.2176 0.2176
5 F 4.0799 0.0000 0.0000
6 2 0.2248 0.0948 0.0948
6 3 0.0017 0.0083 0.0083
6 4 0.2256 0.0719 0.0719
7 5 1.1784 0.0869 0.0869
7 8 0.1148 0.0084 0.0084
8 6 0.0008 0.0311 0.0311
8 9 0.1156 0.0227 0.0227
9 4 0.1156 0.0227 0.0227
11 7 0.7726 0.3863 0.3863

B) curto fase-fase
Enter Faulted Bus No. -> 5

Enter Fault Impedance Zf = R + j*X in complex form (for bolted fault enter 0). Zf =
0

Line-to-line fault at bus No. 5


Total fault current = 3.7204 per unit

Bus Voltages during the fault in per unit


Bus -------Voltage Magnitude-------
No. Phase a Phase b Phase c
1 1.0000 0.7043 0.7043
2 1.0000 0.6310 0.6310
3 1.0000 0.7160 0.7160
4 1.0000 0.8432 0.8432
5 1.0000 0.5000 0.5000
6 1.0000 0.7186 0.7186
7 1.0000 0.7044 0.7044
8 1.0000 0.7287 0.7287
9 1.0000 0.7739 0.7739
10 1.0000 0.8964 0.8964
11 1.0000 0.7824 0.7824

Line currents for fault at bus No. 5

From To -----Line Current Magnitude----


Bus Bus Phase a Phase b Phase c
1 2 0.0000 1.8501 1.8501
2 5 0.0000 2.5666 2.5666
3 2 0.0000 0.4251 0.4251
4 3 0.0000 0.4160 0.4160
4 6 0.0000 0.2713 0.2713
4 9 0.0000 0.1261 0.1261
5 F 0.0000 3.7204 3.7204
6 2 0.0000 0.2914 0.2914
6 3 0.0000 0.0090 0.0090
7 5 0.0000 1.1538 1.1538
8 6 0.0000 0.0291 0.0291
8 7 0.0000 0.0970 0.0970
9 8 0.0000 0.1261 0.1261
10 4 0.0000 0.8135 0.8135
11 7 0.0000 1.0568 1.0568

c) curto fase-fase-terra
Enter Faulted Bus No. -> 5

Enter Fault Impedance Zf = R + j*X in complex form (for bolted fault enter 0). Zf =
0

Double line-to-ground fault at bus No. 5


Total fault current = 3.8845 per unit

Bus Voltages during the fault in per unit

Bus -------Voltage Magnitude-------


No. Phase a Phase b Phase c
1 0.8712 0.6601 0.6601
2 0.8891 0.5269 0.5269
3 0.9197 0.6475 0.6475
4 0.9554 0.8128 0.8128
5 1.0479 0.0000 0.0000
6 0.9247 0.6485 0.6485
7 0.9655 0.6023 0.6023
8 0.9481 0.6502 0.6502
9 0.9491 0.7173 0.7173
10 0.9720 0.8770 0.8770
11 0.9080 0.7539 0.7539
Line currents for fault at bus No. 5

From To -----Line Current Magnitude----


Bus Bus Phase a Phase b Phase c
1 2 0.6439 1.8779 1.8779
2 5 0.0827 2.9345 2.9345
3 2 0.1249 0.4360 0.4360
4 3 0.1171 0.4279 0.4279
4 6 0.0685 0.2810 0.2810
4 9 0.0217 0.1336 0.1336
5 F 0.0000 4.1969 4.1969
6 2 0.0903 0.2979 0.2979
6 3 0.0079 0.0096 0.0096
7 5 0.0827 1.2654 1.2654
8 6 0.0296 0.0325 0.0325
8 7 0.0080 0.1134 0.1134
9 8 0.0217 0.1336 0.1336
10 4 0.2072 0.8421 0.8421
11 7 0.3678 1.0727 1.0727