Cable Fill User's Manual

Example 1 :

I need to lay 80 cat 5 cables. I want to save 30% of the cable tray for my future needs. What cable tray should I
use ?

Answer :
1. Insert 80 in the F6 cell
2. Select the "Cat 5" type of cable
3. Insert 70% in the N20 cell. This way only the acceptable cable trays will appear in green. The underdesigned
cable trays will be red.

Example 2 :

I intend to use a CF 54/300, but I want to reserve 20% of it for my future installation. How many power cables
can I lay in it ?

Answer :

1. Select the "Power" type of cable


2. Insert 80% in the N20 cell
3. Click on the CF 54/300 "Click here" button
4. Read the result : you can lay 18 power cables in the cable tray.

Note: Please contact KnowHow Networks Ltd at www.knowh.com with futher questions.

KnowHow Networks Ltd Freephone 0800 328 1744 www.knowh.com in partnership with Cablofil Inc
EZ Tray cable fill ratio table

1 Enter the maximum ratio you want to fill the cable tray to : 40%

2 Select the type of cable you are laying : 2


3 Click on the cable tray you want to use : www.kwhw.co.uk

Width Part # Fill ratio Surface

CF 30 4" (100 mm) CF 30/100 248% ###

(1" 1/2 deep) 12" (300 mm) CF 30/300 80% ###

2" (50 mm) CF 54/50 262% ###

4" (100 mm) CF 54/100 124% ###

CF 54 6" (150 mm) CF 54/150 81% ###

(2" deep) 8" (200 mm) CF 54/200 61% ###

12" (300 mm) CF 54/300 40% ###

18" (450 mm) CF 54/450 27% ###

24" (600 mm) CF 54/600 20% ###

4 You can lay : 262 cables in the cable tray !

5 Additional technical information exclusively provided free of charge by the Cablofil Team :

1 Cable : Weight Diameter


Lb/ft Kg/m in. cm
0.022 0.033 0.187 0.475

Weight Fill
262 Cables : Lb/ft Kg/m sqin. cm²
5.75 8.56 9.15 59.00

This calculation is based upon the square of the outside diameter of the cable (D) multiplied by the total number of cables to be used (N) :
Area of cables = N x D²
Example :
Cable outside diameter : 0.18 in.
Total number of cables needed : 100
The total cross sectional area of the cables will be calculated as 100 x 0.18² = 3.24 sqin.

This calculation method takes into account to some extent the natural cable "Swell" that is experienced when cables are placed in a tray. This
calculation assumes that the cable is a geometric square instead of a circle and yields an area approximately 28% greater than that of a circular
area calculation.

KnowHow Networks Ltd Freephone 0800 328 1744 www.knowh.com in partnership with Cablofil Inc
EZ Tray cable fill ratio table

Number of cables : 150

Cable type : 5

1 Cable : Weight Diameter


Lb/ft Kg/m in. cm
0.149 0.222 0.650 1.651 Annor (space optimised structure

Annor Design and Build Structured


150 Cables : Weight Fill and ICT Rooms
Lb/ft Kg/m sqin. cm2
22.35 33.26 63.38 408.87 see www.annor.net

Surface Fill ratio


CF 30 CF 30/100 3.7 sqin. 1722%
(1" 1/2 deep) CF 30/300 11.4 sqin. 554%
CF 54/50 3.5 sqin. 1817%
CF 54/100 7.4 sqin. 861%
CF 54 CF 54/150 11.2 sqin. 564%
(2" deep) CF 54/200 15.1 sqin. 419%
CF 54/300 22.9 sqin. 277%
CF 54/450 34.5 sqin. 184%
CF 54/600 46.1 sqin. 137%

This calculation is based upon the square of the outside diameter of the cable (D) multiplied by the total
number of cables to be used (N) :
Area of cables = N x D²
Example :
Cable outside diameter : 0.18 in.
Total number of cables needed : 100
The total cross sectional area of the cables will be calculated as 100 x 0.18² = 3.24 sqin.

This calculation method takes into account to some extent the natural cable "Swell" that is experienced when
cables are placed in a tray. This calculation assumes that the cable is a geometric square instead of a circle
and yields an area approximately 28% greater than that of a circular area calculation.

KnowHow Networks Ltd Freephone 0800 328 1744 www.knowh.com in partnership with Cablofil Inc
Base Data
Cable Weight Diameter
Cat 5 (2 pairs) 0.012 0.145
Cat 5 (4 pairs) 0.022 0.187
Cat 5 (6 pairs) 0.036 0.260
Cat 5 (12 pairs) 0.046 0.385
Cat 5 (25 pairs) 0.149 0.650
Power 0.091 0.413
NYM 3x001.5 0.091 0.413
NYM 3x002.5 0.121 0.453
NYM 5x001.5 0.128 0.472
Test 1.000 1.000
Other 0.000 0.000

KnowHow Networks Ltd Freephone 0800 328 1744 www.knowh.com in partnership with Cablofil Inc
Base Data
To enter new cables :

1. Select the row containing the "Other" cable


2. Click on "Insert > Cells"
3. In the "Cable" column : insert the ID of the cable
4. In the "Weight" column : insert the cable linear weight (Lb/ft)
5. In the "Diameter" column : insert the cable diameter (in.)

KnowHow Networks Ltd Freephone 0800 328 1744 www.knowh.com in partnership with Cablofil Inc