Vous êtes sur la page 1sur 2

Caution Who should be testing socket outlets?

Before use check the socket tester's case and pins for
Basically anyone who wants to know the mains socket
any signs of damage.
Your guide to easy Do not use if the case is broken or damaged. To check
about to be used is correctly wired and safe to plug into.

Socket Outlet Testing the correct functioning of the socket tester, plug it into
In particular those with a responsibility of care for their
own homes, employees and the public.
a known correctly-wired live 13A socket.
and instructions for use of: • Home owners
To clean the tester use only a soft dry cloth.
• Land lords
This unit is maintenance free and contains no user
Loopcheck 107 • Local authorities
serviceable components. In the unlikely event that this
Advanced socket unit malfunctions, it should be withdrawn from service • Police forces
tester with loop and returned to Kewtech. • Hospitals, including home visits
function This tester must not be used in a manner not specified
• Schools and colleges
by Kewtech. • Sports facilities
• Military housing and education
Good work practice BS EN

Use of a Socket Tester will be seen to show a


• IT managers 61010-1

responsible attitude to electrical safety, plus the very • Heads of department


reasonable price of Kewtech testers means they place a • Health and Safety officers
cost effective solution in the hands of many more users
kewtechcorp.com at the front end of responsibility and care.

The simple solution for testing What a Kewtech tester WILL What a Kewtech tester will NOT
socket outlets tell you tell you
Logical ‘Green The Loopcheck 107 is unique in that it is the only Kewtech socket testers are for simple first line
for Go’ socket tester that carries out a loop test at mains diagnosis for use by those with and without electrical
frequency to check the actual condition of the wiring. skills. If a problem at the socket is shown it should
Bright, easy to read
Particular emphasis is placed on detecting very immediately be investigated by a suitably qualified
LEDs
dangerous wiring conditions such as reversed line electrician or contractor recognised by organisations
Clear audible (live) earth connections, disconnected wires and high such as:
indication earth values. NAPIT (www.napit.org.uk)
Error free testing NICEIC (www.niceic.com)
ECA (www.eca.co.uk)
ECA of Scotland (www.select.org.uk)
STROMA (www.stroma.com)

Product features 230V 13 amp BS 1363 Socket Testers with This is an example of
• Bright, durable LEDs out-perform fragile, low self-check and patented ‘Fault Locate’ plus ‘Fault Locate’ showing
visibility neons Earth check line (live), neutral,
• First Socket Tester to indicate actual fault location reverse. LEDs flash red
• Patented ‘Fault Locate’ shows actual position of
– Line (live), Neutral or Earth plus warble tone.
Pin – Line (Live), Neutral or Earth
• Unique new Earth Loop Test • Unique earth loop test at mains frequency to
check the actual condition of the wiring
• Tough, smooth-contoured construction
• Built-in automatic visible self-check ensures total
• Rubber overmould tactile case confidence in correct functioning at all times This is an example of
• Advanced electronic circuits mean positive and • Tri-coloured LEDs (green, red, orange) give clear the Earth Loop Test
reliable indication and positive indication of Good wiring plus showing green – good,
• Modern production methods ensure great 17 possible fault conditions less than 1.8Ω.
performance and value • Mains polarity check
• Audible signal gives additional information • 30mA RCD check
• Microprocessor control with built-in self check

Specifications The result is shown by one of three LEDs. Rating 230V.  Input current: <18mA (L–E <7mA)
Socket wiring check Indication LED Tone Frequency: 50Hz.
Three green LEDs and a continuous tone indicate that the Good Green Continuous
socket is correctly wired. Earth, Line (Live) and neutral Suitable for use in environmental conditions:
Check Amber Warble
are all in the correct position. Any other indication, such Temperature 0–40˚C 
Urgent Check Red Warble
as open circuit or swapped connections, is shown by
an orange or red LED accompanied by a warble tone. Humidity: <95% non-condensing
Mains Polarity test
The socket is incorrectly wired and all further tests are This tester is not intended for continuous use – do not
This is a capacitively coupled pad. The user is the earth
inhibited. leave connected in a socket for longer than 2 minutes.
reference point for true earth.
Note:  Like all socket (and other similar) testers a neutral
This test is used to indicate that there is not a line (live)
– earth swap cannot be detected unless the distribution
neutral swap of the mains supply at the supply entry point
board is fitted with an RCD in which case the RCD will trip.
to the premises.
Socket condition check
This is carried out by injecting a loop impedance test RCD test (30mA RCD only)
current between line (live) and neutral and also between Operation of the test switch injects a test current of
neutral and earth. If during the pre-test there is an 30mA Line (Live) to earth to provide an operational check
indication the earthed metal work could raise to touch for the RCD. The test current is restricted to 300ms.
voltage of greater than 25V the test is inhibited.
Instructions for use 2 Switch on. 3 Read the socket outlet condition.
Note: This tester is intended for use only on a 230V When first powered up the LEDs in the grey triangle The tester will then check the condition of the wiring
mains 13A socket outlet. (BS 1363 configuration) flash green then red once as it performs a self test. and show the result in the three LED Loop Test bar.
This is immediately followed by a socket correct wiring Green LED with
1 Plug the tester into a 13A socket outlet. test. The LEDs will continuous tone
show all green with indicates the
a continuous tone if wiring condition is
the wiring is correct. good with safety
Any other LED colour earth path less
or warble tone than 1.80Ω.
indicates incorrect Flashing amber
wiring and all further LED with warble
tests are inhibited. tone indicates
Check the indication the incoming
displayed by the mains should be
LEDs against the table for an indication of the wiring checked to see if the system is using an earth rod for
status. protection. Safety earth path is between 1.80Ω and
After approximately 4 seconds the green LEDs turn off. 92Ω. If the system is protected by an earth rod then
an RCD should be present.

Flashing red LED with warbling means the earth path Additional functions 5 RCD Check (30mA RCD)
is over 93Ω. This may not be dangerous but the
4 Polarity Check Press the purple test switch for at least half a second to
value should be checked using an earth loop tester
The LEDs in the grey triangle flash green with a start the RCD test.
with a read out to check the value meets the wiring
regulations. continuous tone if it is correct. If the LED goes out
If the LEDs flash red with a warble tone this is and the tone stops
The tester is designed not to trip RCDs.
potentially a very hazardous condition – immediate the RCD has tripped
If the main distribution board is fitted with an RCD and it attention required. and is working.
trips during the test this could be:
If the LED remains
a)  there is already high leakage current between Line
illuminated and the
(Live) and earth
tone continues, the
b)  the earth and neutral are reversed. test button has not
Either needs investigation by a qualified electrician. been pressed for
long enough to start the test. If the LED in the Loop Test
bar goes out and the three LEDs in the grey triangle
flash amber accompanied by a warble tone, the test
current has been applied for 300ms and the RCD has
not tripped. It should be investigated.

Wiring Indication Chart


LEDs show actual pin location Line, Earth, Neutral

Note: LEDs will also flash to indicate fault condition.

Kewtech Corporation Limited


T: 01494 792 212 F: 01494 791 826 E: sales@kewtechcorp.com

kewtechcorp.com