Wiring for

Damper Actuators and Control Valves


July 2011
Wiring for Damper Actuators and Control Valves
General Wiring Instructions

WARNING: The wiring technician must be trained and experienced CAUTION: It is good practice to power electronic or digital controllers
with electronic circuits. Disconnect power supply before attempting any from a separate power transformer than that used for actuators or other
wiring connections or changes. Make all connections in accordance end devices. The power supply design in our actuators and other end
with wiring diagrams and follow all applicable local and national codes. devices use half wave rectification. Some controllers use full wave
Provide disconnect and overload protection as required. Use copper, rectification. When these two different types of power supplies are
twisted pair, conductors only. If using electrical conduit, the attachment connected to the same power transformer and the DC commons are
to the actuator must be made with flexible conduit. connected together, a short circuit is created across one of the diodes in
the full wave power supply, damaging the controller. Only use a single
Always read the controller manufacturer’s installation power transformer to power the controller and actuator if you know the
literature carefully before making any connections. Follow all controller power supply uses half wave rectification.
instructions in this literature. If you have any questions, contact
the controller manufacturer and/or Belimo. Multiple actuators, one transformer
Multiple actuators may be powered from one transformer provided the
Transformer(s) following rules are followed:
Belimo actuators require a 24 VAC Class 2 transformer. The 1. The TOTAL current draw of the actuators (VA rating) is less than or
actuator enclosure cannot be opened in the field, there are no equal to the rating of the transformer.
parts or components to be replaced or repaired. 2. Polarity on the secondary of the transformer is strictly followed.
This means that all No. 1 wires from all actuators are connected
– EMC Directive: 2004/108/EC to the common leg on the transformer and all No. 2 wires from all
– Software Class A: Mode of Operation Type 1 actuators are connected to the hotleg. Mixing wire No. 1 & 2 on one
– Low Voltage Directive: 2006/95/EC leg of the transformer will result in erratic operation or failure of the
actuator and/or controls.
Example: 3 AF Actuators Supplied, 16 Ga. wire (refer to table on
page 3) Multiple actuators, multiple transformers
350 ft. (allowable wire length) ÷ 3 actuators = 117 ft. maximum wire run Multiple actuators positioned by the same control signal may be powered
from multiple transformers provided the following rules are followed:
Typical Transformer Sizing 1. The transformers are properly sized.
2. All No. 1 wires from all actuators are tied together and tied to the
Required VA negative leg of the control signal. See wiring diagram.
Actuator Series Voltage Per Actuator

N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.


EFB, EFX 24 16 Wire type and wire installation tips
AFB, AFX 24 10 For most installations, 18 or 16 Ga. cable works well with Belimo
AF 24 10 actuators. Review job requirements and determine whether a plenum
NFB, NFX 24 9 or appliance rated cable is appropriate. Use code-approved wire nuts,
terminal strips or solderless connectors where wires are joined. It is
LF 24 7
good practice to run control wires unspliced from the actuator to the
TF 24 5
controller. If splices are unavoidable, make sure the splice can be
GMB 24 7 reached for possible maintenance. Tape and/or wire-tie the splice to
AMB / ARB 24 6 reduce the possibility of the splice being inadvertently pulled apart.
NMB 24 6
LMB / LRB 24 3 Wire length for actuator installation
CMB 24 1.5 Keep power wire runs below the lengths listed in the following tables.
If more than one actuator is powered from the same wire run, divide
AHB 24 4.5
the allowable wire length by the number of actuators to determine the
LHB 24 3
maximum run to any single actuator.
LUB 24 3
AMQB 24 26
NMQB 24 23
LMQB 24 23
AHQB 24 23
LHQB 24 23
GK / GKR 24 21
NK 24 22
AHK 24 20
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
2
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.

AMQ… NMQ…
GK/
VA EF AF NF LF…US TF…US NKQ… GM/GR… AM/AR… NM… LM/LR… CM… AH… LH… LU… TR… LMQ… AHQ…
GKR…
LHQ…
wire
gauge 16 10 9 7 5 21 22 7 6 6 5 1.5 6 5 5 1 18

MAX Distance between Actuator and Supply (feet)


20 175 200 200 250 800 200 250 250 1100 70
18 145 220 250 325 450 110 105 325 375 375 450 1150 375 450 450 1200 125

24 VAC
16 225 350 390 500 700 165 160 500 600 600 700 1200 600 700 700 1400 200

800-543-9038 USA
14 360 550 600 800 1100 275 260 800 925 925 300
12 550 900 1000 1125 1175 440 420 1125 1150 1150 500

EF AF..UP AF NF..UP LF…US TF…US GM… AM… NM… LM… CM… LU

VA
wire 21 8.5 11 6.5 7.5 6 7 7.5 6.5 4.5 3.5 3
gauge
MAX Distance between Actuator and Supply (feet)
20 175 150 175 250 350 400
18 110 265 215 375 325 375 325 300 325 450 600 750

110 VAC
16 165 415 345 575 500 575 500 450 500 700 1000 1125

866-805-7089 CANADA
14 275 650 545 900 800 900 800 700 800 1125 1150 1175
12 440 1050 895 1150 1125 1150 1125 1125 1125

EF AF..UP AF…US NF..UP LF…US TF…US GM… AM… NM… LM… CM… LU

VA
wire 29 18 11 9.5 7 6 7 7.5 6.5 4.5 3.5 3
gauge
MAX Distance between Actuator and Supply (feet)
20 175 150 175 250 325 400
18 80 120 215 220 325 375 325 300 325 450 600 750

220 VAC
16 125 200 345 350 500 575 500 450 500 700 1000 1125
14 200 300 545 550 800 900 800 700 800 1125 1500 1175
12 310 475 895 900 1125 1150 1125 1125 1125

203-791-8396 LATIN AMERICA / CARIBBEAN


*Belimo actuators and auxiliary switches are designed as a IEC protection class II, double insulated, and do not require an independent ground wire to
earth, unless otherwise indicated in this document
Wire Size vs. Length of Run for Damper Actuators and Control Valves

3
4
SY1 SY2 SY3 SY4 SY5
Amps Amps Amps Amps Amps
wire gauge 1.8 3 3 6 6.5
MAX Distance between Actuator and Supply (feet)
18 92 55 55
16 144 87 87 43 40

24 VAC
14 233 140 140 70 65

800-543-9038 USA
12 357 214 214 107 99
10 606 364 364 182 168
8 905 543 543 271 250

SY1 SY2 SY3 SY4 SY5 SY6 SY7 SY8 SY9 SY10 SY11 SY12
Amps Amps Amps Amps Amps Amps Amps Amps Amps Amps Amps Amps
wire gauge 0.5 1 1 1.3 1.5 1.8 3.2 4 3.2 4 3 4
MAX Distance between Actuator and Supply (feet)
18 1515 758 758 583 505 421 237 189 237 189 253 189
16 2381 1190 1190 916 794 661 372 298 372 298 397 298

110 VAC
14 3846 1923 1923 1479 1282 1068 601 481 601 481 641 481
Wire Size vs. Length of Run for SY Series Actuators

12 5882 2941 2941 2262 1961 1634 919 735 919 735 980 735

866-805-7089 CANADA
10 10000 5000 5000 3846 3333 2778 1563 1250 1563 1250 1667 1250
8 14925 7463 7463 5741 4975 4146 2332 1866 2332 1866 2488 1866

SY1 SY2 SY3 SY4 SY5 SY6 SY7 SY8 SY9 SY10 SY11 SY12
Amps Amps Amps Amps Amps Amps Amps Amps Amps Amps Amps Amps
wire gauge 0.3 0.5 0.5 0.6 0.7 0.8 1.6 2 1.6 2 1.6 2.2
MAX Distance between Actuator and Supply (feet)
18 5051 3030 3030 2525 2165 1894 947 758 947 758 947 689
16 7937 4762 4762 3968 3401 2976 1488 1190 1488 1190 1488 1082

220 VAC
14 12821 7692 7692 6410 5495 4808 2404 1923 2404 1923 2404 1748
12 19608 11765 11765 9804 8403 7353 3676 2941 3676 2941 3676 2674
10 33333 20000 20000 16667 14286 12500 6250 5000 6250 5000 6250 4545
8 49751 29851 29851 24876 21322 18657 9328 7463 9328 7463 9328 6784
The NEC mandates that 24 VAC over 100 VA power requires CLASS 1 wiring conduit. Local codes may vary. Do NOT mix CLASS 1 & CLASS 2 circuits in

203-791-8396 LATIN AMERICA / CARIBBEAN


the same conduit. Generally, 24 VAC actuators over 100 VA should be changed to 120 VAC models.

N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.


Wiring for Damper Actuators and Control Valves
On/Off, Spring Return, Electronic Fail-Safe, 24V
W236_11

Actuators: EFB24(-S) EFX24(-S) AF24(-S) US NFB24(-S) NFX24(-S) LF24(-S) US


TF24(-S) US GKB24-3 GKX24-3 NKQB24-1 NKQX24-1

Hazard Identification
Warnings and Cautions appear at appropriate sections throughout INSTALLATION NOTES
this manual. Read these carefully.
1 Provide overload protection and disconnect as required.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, 3 Actuators may also be powered by 24 VDC.
may result in minor or moderate injury. It may also be used to Actuators with plenum rated cable do not have
alert against unsafe practices. 5
numbers on wires; use color codes instead.

2
Equipment damage!
Actuators may be connected in parallel. Power
A Actuators with appliance cables are numbered.
consumption and input impedance must be observed.

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this APPLICATION NOTES
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other Meets cULus requirements without the need of an
individual who has been properly trained in handling live electrical electrical ground connection.
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury. On/Off

On/Off
24 VAC Transformer 1 3 5

Line Blk (1) Common –


24 VAC Transformer 2 3 5
Volts Red (2) +
Blk (1) Common
Line
Volts a open a
Red (2) + Hot Wht (3) +
a closed
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.

1 0
The indication of direction
is valid for switch position 1.
NKQ

On/Off

24 VAC Transformer 1 3 5

Line Blk (1) Common –


Volts a
Red (2) + Hot

Wht (3) + Y1 input

GK

Refer to page 26 for auxiliary switch (-S models) wiring.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


5
Wiring for Damper Actuators and Control Valves
On/Off, Spring Return, 120, 230V and UP
W231_A_11

Actuators: EFB120(-S) EFX120(-S) AFBUP(-S) AFXUP(-S) AF120(-S) US/AF230(-S) US


NFBUP(-S) NFXUP(-S) LF120(-S) US/LF230(-S) US TF120(-S) US

Hazard Identification
Warnings and Cautions appear at appropriate sections throughout INSTALLATION NOTES
this manual. Read these carefully.

CAUTION 14
TF120(-S) US can be supplied with both 120 VAC
Indicates a potentially hazardous situation which, if not avoided, and 230 VAC.
may result in minor or moderate injury. It may also be used to
alert against unsafe practices. 19 UP models and TF120(-S) US uses “L” instead of “H”
on #2 wire.
Equipment damage!
2 Actuators may be connected in parallel. Power 20 All 120 VAC, 230 VAC and UP actuators use appliance rated
consumption and input impedance must be observed. cables.
UP Universal Power Supply (UP) models can be supplied
WARNING with 24 VAC up to 240 VAC.
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other APPLICATION NOTES
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical Meets cULus requirements without the need of an
safety precautions when exposed to live electrical components electrical ground connection.
could result in death or serious injury.

On/Off

120 VAC 14 UP
2 20 19
230 VAC

N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.


Wht N Wht (1) Neutral
Line
Volts Blk H Blk (2) Hot

Refer to page 26 for auxiliary switch (-S models) wiring.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


6
Wiring for Damper Actuators and Control Valves
Floating Point, Spring Return, 24V

W232_11

Actuators: LF24-3(-S) US TF24-3(-S) US LFC24-3...US

Hazard Identification
INSTALLATION NOTES
Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.
3 Actuators may also be powered by 24 VDC.
CAUTION Actuators with plenum rated cable do not have numbers on
Indicates a potentially hazardous situation which, if not avoided, 5 wires; use color codes instead. Actuators with appliance
may result in minor or moderate injury. It may also be used to cables are numbered.
alert against unsafe practices. Actuators Hot wire must be connected to the control board
6 common.
Equipment damage!
2 Actuators may be connected in parallel. Power For triac sink the Common connection from the actuator
consumption and input impedance must be observed. 11 must be connected to the Hot connection of the controller.
The actuator must be connected to the control board common.
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this APPLICATION NOTES
product, it may be necessary to work with live electrical Meets cULus requirements without the need of an
components. Have a qualified licensed electrician or other electrical ground connection.
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components † Actuator Wire Number Color
could result in death or serious injury.
TF24-3 US 4 Org
TF24-3-S US 5 Org
LF24-3 US 4 Grn
Floating Point LF24-3-S US 5 Wht
Triac Source
24 VAC Transformer 3 5

Blk (1) Common 24 VAC Transformer


Line
Line
Volts Red (2) + Hot Volts
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.

a Wht (3) +
2 5
Hot Com
b † + Blk (1) Common
Red (2) + Hot
CW CCW
LF24-3(-S) US Wht (3) +
The indication of direction LFC24-3-R US † +
is valid for switch position CW. LFC24-3-S US
CW CCW
TF24-3(-S) US LF24-3(-S) US
TF24-3(-S) US

The indication of direction


Controller
is valid for switch position CW.
Triac Sink

24 VAC Transformer
Triac Sink with Separate Transformer
Line
Volts

2 5 11
24 VAC Transformer
Hot Com
Blk (1) Common 24 VAC Transformer
Line
Red (2) + Hot 6 Volts
Line
Wht (3) + Volts 2 5
† +
Blk (1) Common
CW CCW
LF24-3(-S) US Hot Com
TF24-3(-S) US
Red (2) + Hot 6
Controller Wht (3) +
The indication of direction
† +
is valid for switch position CW.
CW CCW
LF24-3(-S) US
TF24-3(-S) US

The indication of direction


Controller
is valid for switch position CW.

Refer to page 26 for auxiliary switch (-S models) wiring.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


7
Wiring for Damper Actuators and Control Valves
On/Off and Floating Point, Non-Spring Return, 24V
W332_11

Actuators: LMB24-3(-S) (-P5) (-P10) (-T) AMB24-3(-S) LMX24-3(-T) AMX24-3(-T) LRB24-3(-S) ARX24-3
TR24-3(-T) US NMB24-3 GMB24-3… NMX24-3(-T) GMX24-3… ARB24-3(-S) LRX24-3
CMB24-3… ARB24-3-5 GRB24-3-5 GRB24-3-7 GMB24-3-X1 LRCB24-3(-S)

Hazard Identification
Warnings and Cautions appear at appropriate sections throughout INSTALLATION NOTES
this manual. Read these carefully.
3 Actuators may also be powered by 24 VDC.
CAUTION
5 Actuators with plenum rated cable do not have
Indicates a potentially hazardous situation which, if not avoided, numbers on wires; use color codes instead.
may result in minor or moderate injury. It may also be used to Actuators with appliance cables are numbered.
alert against unsafe practices.
16
The TR24-3-T US actuators are provided with
Equipment damage! a numbered screw terminal strip instead of cable.
2 Actuators may be connected in parallel. Power
consumption and input impedance must be observed. 17 TR24-3 US actuators cannot be wired in parallel.

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this APPLICATION NOTES
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other Meets cULus requirements without the need of an
individual who has been properly trained in handling live electrical electrical ground connection.
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

On/Off Floating Point

24 VAC Transformer 2 3 5 24 VAC Transformer 2 3 5

Line Blk (1) Common


Line Blk (1) Common
Volts Red (2) + Volts Red (2) +

N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.


a
a open Wht (3) + Wht (3) +
a closed
1 0 LMB(X)24-3... 1 0 LMB(X)24-3...
The indication of direction NMB(X)24-3... NMB(X)24-3...
is valid for switch position 1. AMB(X)24-3... The indication of direction AMB(X)24-3...
GMB(X)24-3... is valid for switch position 1. GMB(X)24-3...
CMB24-3... CMB24-3...
LRB(X)24-3... LRB(X)24-3...
ARB(X)24-3... ARB(X)24-3...

On/Off – SPDT Switch Floating Point

24 VAC Transformer 16 17 5 24 VAC Transformer 5 16 17

Line Blk 1 Common Line Blk 1 Common


Volts Red 2 + Volts Red 2 +

Wht 3 + Wht 3 +
Note: TR24-3 (-T) US cannot Note: TR24-3 (-T) US cannot
be wired in parallel with be wired in parallel with
TR24-3 (-T) US TR24-3 (-T) US
any actuator. any actuator.

Refer to page 26 for auxiliary switch (-S models) and -P5, -P10 potentiometer wiring.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


8
Wiring for Damper Actuators and Control Valves
Floating Point, Electronic Fail-Safe, 24V
W612_11

Actuators: GKB24-3

Hazard Identification
Warnings and Cautions appear at appropriate sections throughout INSTALLATION NOTES
this manual. Read these carefully.
1 Provide overload protection and disconnect as required.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, 3 Actuators may also be powered by 24 VDC.
may result in minor or moderate injury. It may also be used to Control signal may be pulsed from either the Hot (source)
alert against unsafe practices. 5 or the Common (sink) 24 VAC line.
Equipment damage! Contact closures A & B also can be triacs.
2 Actuators may be connected in parallel. Power 8 A & B should both be closed for triac source and open for
consumption and input impedance must be observed. triac sink.

WARNING 9 For triac sink the common connection from the actuator
Live Electrical Components! must be connected to the hot connection of the controller.
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical APPLICATION NOTES
safety precautions when exposed to live electrical components Meets cULus requirements without the need of an
could result in death or serious injury. electrical ground connection.

Floating Point
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.

GKB24-3

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


9
Wiring for Damper Actuators and Control Valves
On/Off and Floating Point, Non-Spring Return, 100 to 240V
W364_11

Actuators: LMX120-3 AMX120-3 LRX120-3 CMB120-3


NMX120-3 GMX120-3 ARX120-3

Hazard Identification
Warnings and Cautions appear at appropriate sections throughout INSTALLATION NOTES
this manual. Read these carefully.
15 LMB(X), NMB(X), AMB(X), GMB(X), LRB(X), and ARB(X)
CAUTION can be supplied with either 120 VAC or 230 VAC.
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to 19 All 120VAC and 230VAC actuators use appliance rated
alert against unsafe practices. cables.
Equipment damage!
2 Actuators may be connected in parallel. Power A Actuators with appliance cables are numbered.
consumption and input impedance must be observed.

WARNING
Live Electrical Components! APPLICATION NOTES
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical Meets cULus requirements without the need of an
components. Have a qualified licensed electrician or other electrical ground connection.
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

On/Off Floating Point

2 19 2 19
100 to 240 VAC 15 100 to 240 VAC 15

N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.


N L1 Blu (1) Common – N L1 Blk (1) Common
H L2 Blk (2) + H L2 Red (2) +

a open a
Wht (3) + Wht (3) +
a closed

The indication of direction 1 0


The indication of direction 1 0
is valid for switch position 1. is valid for switch position 1.

Refer to page 26 for auxiliary switch (-S models) wiring.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


10
Wiring for Damper Actuators and Control Valves
Proportional, Spring Return, 24V
W233_A_11

Actuators: EFB24-SR(-S) EFX24-SR(-S) AFB24-SR(-S) AFX24-SR(-S) AF24-SR US AFA24-SR US


NFB24-SR(-S) NFX24-SR(-S) LF24-SR(-S) US TF24-SR(-S) US

Hazard Identification
Warnings and Cautions appear at appropriate sections throughout INSTALLATION NOTES
this manual. Read these carefully.
3 Actuators may also be powered by 24 VDC.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, 5 Actuators with plenum rated cable do not have
may result in minor or moderate injury. It may also be used to numbers on wires; use color codes instead.
alert against unsafe practices. Actuators with appliance cables are numbered.
Equipment damage! 6 Only connect common to neg. (–) leg of control circuits.
4 Up to four actuators may be connected in parallel if not
mechanically linked. Power consumption and input
impedance must be observed.

WARNING APPLICATION NOTES


Live Electrical Components!
During installation, testing, servicing and troubleshooting of this Meets cULus requirements without the need of an
product, it may be necessary to work with live electrical electrical ground connection.
components. Have a qualified licensed electrician or other A 500 Ω resistor converts the 4 to 20 mA control
individual who has been properly trained in handling live electrical 7
signal to 2 to 10 VDC.
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components 8 The AFA24-SR US and TF24-SR(-S) US are supplied
could result in death or serious injury. without position feedback.

† Actuator Wire Number Color


3 4 EFB24-SR(-S) 5 Org
24 VAC Transformer 7
EFX24-SR(-S) 5 Org
Line Blk (1) Common AFB24-SR(-S) 5 Org
Volts AFX24-SR(-S) 5 Org
Red (2) + Hot
Ω AF24-SR US 5 Wht
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.

(–) 500 Ω 5 NFB24-SR(-S) 5 Org


Control Signal NFX24-SR(-S) 5 Org
(+) Wht (3) Y Input,
VDC/mA 2 to 10 LF24-SR US 5 Grn
2 to 10 VDC (–) LF24-SR-S US 5 Wht
Feedback Signal (+) † (5) U Output,
2 to 10V
6
CW CCW
EFB24-SR(-S) 24 VAC Transformer 3 4 7
EFX24-SR(-S)
AFB24-SR(-S)
AFX24-SR(-S)
Line Blk (1) Common
AF24-SR US Volts Red (2) + Hot
NFB24-SR(-S)
NFX24-SR(-S) Ω
LF24-SR(-S) US (–) 500 Ω 5
Control Signal
(+) Wht (3) Y Input,
VDC/mA
2 to 10V

6 8

AFA24-SR US
TF24-SR(-S) US

Refer to page 26 for auxiliary switch (-S models) wiring.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


11
Wiring for Damper Actuators and Control Valves
Proportional, Non-Spring Return, Electronic Fail-Safe, 24V
W333_11

Actuators: LMB24-SR (-T) NMB24-SR LMX24-SR (-T) NMX24-SR (-T) LRB24-SR TR24-SR (-T) US
AMB24-SR GMB24-SR AMX24-SR (-T) GMX24-SR ARB24-SR LRX24-SR ARX24-SR
CMB24-SR-L CMB24-SR-R GKB24-SR GKX24-SR NKQB24-SR NKQX24-SR

Hazard Identification
Warnings and Cautions appear at appropriate sections throughout INSTALLATION NOTES
this manual. Read these carefully.
3 Actuators may also be powered by 24 VDC.
CAUTION
5 Actuators with plenum rated cable do not have
Indicates a potentially hazardous situation which, if not avoided, numbers on wires; use color codes instead.
may result in minor or moderate injury. It may also be used to Actuators with appliance cables are numbered.
alert against unsafe practices.
6 Only connect common to neg. (–) leg of control circuits.
Equipment damage! Terminal models (-T) have no-feedback.
4
Up to four actuators may be connected in parallel if not
mechanically linked. Power consumption and input
impedance must be observed.
APPLICATION NOTES
WARNING
Meets cULus requirements without the need of an
Live Electrical Components!
electrical ground connection.
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
A 500 Ω resistor converts the 4 to 20 mA control
components. Have a qualified licensed electrician or other 7 signal to 2 to 10 VDC.
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

24 VAC Transformer 3 4
24 VAC Transformer 3 4

N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.


Blk (1) Common Line Blk (1) Common
Line
Volts Red (2) + Hot
Volts Red (2) + Hot
Ω Ω
5 (–) 500 Ω 5
(–) 500 Ω 7 Control Signal
Control Signal (+) Wht (3) Y Input, 2 to 10V
(+) Wht (3) Y Input 2 to 10V VDC/mA
VDC/mA 7
6 2 to 10 VDC (–)
Feedback Signal (+) Org (5) U Output, 2 to 10V

TR24-SR (-T) US
6
1 0
LMB(X)24-SR...
NMB(X)24-SR...
AMB(X)24-SR...
GMB(X)24-SR...
LRB(X)24-SR...
ARB(X)24-SR...
LHB(X)24-SR...
AHB(X)24-SR...
LUB(X)24-SR
CMB24-SR...
GK...
NK...

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


12
Wiring for Damper Actuators and Control Valves
Proportional, Non-Spring Return, 100 to 240V
W365_11

Actuators: LMX120-SR AMX120-SR ARX120-SR


NMX120-SR LRX120-SR

Hazard Identification
Warnings and Cautions appear at appropriate sections throughout INSTALLATION NOTES
this manual. Read these carefully.
15 LMB(X), NMB(X), AMB(X), GMB(X), LRB(X), and
CAUTION ARB(X) can be supplied with either 120 VAC or 230 VAC.
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to 6 Only connect common to neg. (–) leg of control circuits.
alert against unsafe practices.

Equipment damage! 19 All 120 VAC and 230 VAC actuators use appliance rated
2 Actuators may be connected in parallel. Power cables.
consumption and input impedance must be observed. A Actuators with appliance cables are numbered.

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical APPLICATION NOTES
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical Meets cULus requirements without the need of an
components perform these tasks. Failure to follow all electrical electrical ground connection.
safety precautions when exposed to live electrical components
could result in death or serious injury. 7 A 500 Ω resistor converts the 4 to 20 mA control
signal to 2 to 10 VDC.

100 to 240 VAC


15 2 19

N L1 Wht (1) Neutral


Cable 2
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.

H L2 Blk (2) Hot +

6 Blk (1) Common


Red (2) Hot +
7
Cable 1

5
(–)
Control Signal
VDC/mA (+) Wht (3) Y Input, 2 to 10V
2 to 10 VDC (–)
Feedback Signal (+) Org (5) U Output, 2 to 10V

1 0

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


13
Wiring for Damper Actuators and Control Valves
Phasecut Control Signal, Spring Return and Non-Spring Return, 24V
W225_2_11

Actuators: AF24-PC US LMX24-PC AMX24-PC LRX24-PC


NMX24-PC GMX24-PC ARX24-PC

Hazard Identification
Warnings and Cautions appear at appropriate sections throughout INSTALLATION NOTES
this manual. Read these carefully.
3 Actuators may also be powered by 24 VDC.
CAUTION
5 Actuators with plenum rated cable do not have
Indicates a potentially hazardous situation which, if not avoided, numbers on wires; use color codes instead.
may result in minor or moderate injury. It may also be used to Actuators with appliance cables are numbered.
alert against unsafe practices.

Equipment damage!
2 Actuators may be connected in parallel. Power
consumption and input impedance must be observed.
APPLICATION NOTES
WARNING Meets cULus requirements without the need of an
Live Electrical Components! electrical ground connection.
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.

2 3 5
24 VAC Transformer

Line Blk (1) Common –

N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.


Volts Red (2) Hot +

Wht *(3) Y Input, 0 to 10V phasecut


(–)
Control Signal
(+)
0 to 10 V Phasecut Org‡ (5) U Output, 2 to 10V

…PC

* White color wire for AF24-PC US, Pink color for all others.
‡ White color wire for AF24-PC US, Orange color for all others.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


14
Wiring for Damper Actuators and Control Valves
Proportional, Spring Return, 24V, 3 kΩ or 10 kΩ Control Input
W604_11

Actuators: LF24-ECON-R03 US LF24-ECON-R10 US AF24-ECON-R03 US

Hazard Identification INSTALLATION NOTES


Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.
Actuators with plenum rated cable do not have numbers on
5
CAUTION wires; use color codes instead. Actuators with appliance
Indicates a potentially hazardous situation which, if not avoided, cables are numbered.
may result in minor or moderate injury. It may also be used to Min-position is adjustable from 0 to 100% with a
alert against unsafe practices. 26 potentiometer on the actuator cover.
Equipment damage! A relay or switch can spring return the actuator when the
2 Actuators may be connected in parallel. Power consumption 27 RTU fan de-energizes, or if low ambient temperature is sensed.
and input impedance must be observed.
A standard relay can be used to close the sensor circuit to
28 engage economizer mode, e.g. outside air changeover device
WARNING
Live Electrical Components! like a dry bulb or enthalpy limit switch. Honeywell ® logic
During installation, testing, servicing and troubleshooting of this module W7459A and enthalpy sensor C7400 also provide
product, it may be necessary to work with live electrical terminals for this switching.
components. Have a qualified licensed electrician or other A remote CO2 sensor or DDC controller can change the
individual who has been properly trained in handling live electrical 29 standard relay opening or closing the sensor circuit. This
components perform these tasks. Failure to follow all electrical device can be a relay or a dry bulb/enthalpy limit switch.
safety precautions when exposed to live electrical components
could result in death or serious injury.
Override control for Y2 only accepts 0 to 10 VDC
30 override control.

Override Control
Override
AF24-ECON

W203
Wire Input Signal LF24-ECON… position Application
24 VAC Transformer 5 2
Y1 24 VAC Drive closed (0%) Morning warm-up cycle
B
Y1 Common Drive open (100%) Smoke Purge Line Blk (1) Common
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.

Y1 Open wire Drive to min. position Mechanical cooling in Volts Red (2) + Hot
use, RTU thermostat
calls for heat. 27 Wht (3) Y1
A Org (4) Y2 Min-pos, 0 to 10V
Y2 0 VDC to 10 VDC Min. position of 0% to 100% Override potentiometer
via a remote C02 Grn (5) U Output, 2 to 10V
sensor/controller or Default
CW CCW
DDC controller. 0
1
(–) .8
Control Signal .2
A Override
Closed (0%) 0 to 10 VDC
(+) 26 .4 .6
MIN

Override AF24-ECON-R03 US
B Open (100%) LF24-ECON-R03 US
Standard Economizer Mode Wiring 29 30 LF24-ECON-R10 US
W202

24 VAC Transformer 5 2
Line Blk (1) Common
Volts Red (2) + Hot
27 Wht (3) Y1
3 kΩ NTC* Org (4) Y2 Min-pos, 0 to 10 V
MA thermistor 28
Grn (5) U Output, 2 to 10V
setpoint 55∞F
Default
CW CCW 1
0
(–) .8
Control Signal .2
0 to 10 VDC
(+) 26 .4 .6
MIN

AF24-ECON-R03 US
LF24-ECON-R03 US
29 30 LF24-ECON-R10 US

*10 kΩ NTC thermistor for -R10 types.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


15
Wiring for Damper Actuators and Control Valves
Proportional, Spring Return, 24V, 2 to 10 VDC (or 4 to 20 mA)
Control Signal or Three-Position On/Off Control
W605_11

Actuators: LF24-SR-E US

Hazard Identification INSTALLATION NOTES


Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.
3 Actuators may also be powered by 24 VDC.
CAUTION 5 Actuators with plenum rated cable do not have numbers on
Indicates a potentially hazardous situation which, if not avoided, wires; use color codes instead. Actuators with appliance
may result in minor or moderate injury. It may also be used to cables are numbered.
alert against unsafe practices.
7 A 500 Ω resister converts the 4 to 20 mA control signal to
Equipment damage! 2 to 10 VDC.
2 Actuators may be connected in parallel. Power consumption
and input impedance must be observed. 26 Min-position is adjustable from 0 to 100% with a
potentiometer on the actuator cover.
WARNING 31 For three-position control set direction of rotation to CW (default).
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this 32 Switch A, actuator spring returns when open (e.g., fan interlock).
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical Three-Position Control with a SPDT Switch or Two Contact
safety precautions when exposed to live electrical components Closures (e.g. fan, cooling Y)
could result in death or serious injury.

W176
21 24 VAC Transformer 5 3

Line Blk (1) Common

APPLICATION NOTES 24 VAC


Volts Red (2) x + Min-position

Meets cULus requirements without the need of an 32 Wht (3) D Y Full Open
electrical ground connection.

21 Provide overload protection and disconnect as required. Grn (5) U Output, 2 to 10V

Default 1
.8

N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.


31 CW CCW .6
Three-Position Control Signals .4

Switch A Wire 2-Red (x) Wire 3-White (D) Position 26 .2


0

Open** Any Any Closed (via spring) LF24-SR-E US MIN

Closed 24 VAC Open Min-position*


Closed Open 24 VAC Full Open*
Closed 24 VAC 24 VAC Full Open*
* Desired position achieved by driving actuator with motor. Min-Position with Full Open Override (with a single
** An example would be to interlock the actuator power supply with the fan
motor starter.
contact closure) W176

2 to 10 VDC Control of LF24-SR-E US 21 24 VAC Transformer 5 3


W179

24 VAC Transformer 5 3 2 Line Blk (1) Common


21
Volts Red (2) x + Min-position
Line Blk (1) Common 24 VAC
32 Wht (3) D Y Full Open
Volts Red (2) + Hot
Ω
(–) Grn (5) U Output, 2 to 10V
Control Signal (+) Wht (3) Y Input, 2 to 10V
Default 1
2 to 10 VDC 31 CW CCW
.8
Grn (5) U Output, 2 to 10V .6
7
.4
Default
CW CCW
1
.8 26 0
.2
.6

.4 LF24-SR-E US MIN
26 0
.2

LF24-SR-E US MIN

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


16
Wiring for Control Valves
On/Off and Floating Point, Spring and Non-Spring Return, 24V
W606_11

Actuators: NV24-3 US NVD24-3 US NVFD24 (-E) US

Hazard Identification WARNING


Warnings and Cautions appear at appropriate sections throughout Live Electrical Components!
this manual. Read these carefully. During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
CAUTION components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
Indicates a potentially hazardous situation which, if not avoided, components perform these tasks. Failure to follow all electrical
may result in minor or moderate injury. It may also be used to safety precautions when exposed to live electrical components
alert against unsafe practices. could result in death or serious injury.
Equipment damage!
2 Actuators may be connected in parallel. Power consumption
and input impedance must be observed. APPLICATION NOTES
Meets cULus requirements without the need of an
electrical ground connection.
Floating Point and On/Off Control (diagram shown with default
position of S1.2: Off)
On/Off Control-using actuator to drive open/close, spring upon
power loss. (diagram shown with default position of S3.2: 3-way
24 VAC Transformer 2 Off, 2-way On)

Line Blk (1) – Common


24 VAC Transformer 2
Volts Wht (2) + extending
Line Blk (1) – Common

Wht (3) + retracting


Volts Red (2) + Hot
Wht (3) Y1 Input
NV24-3 US
NVD24-3 US
NVFD24 US
= actuator plunger extending NVFD24-E US

= actuator plunger retracting

Triac Source Floating Point


24 VAC Transformer (AC only)
On/Off Control (diagram shown with default position of S1.2: Off) Line
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.

Volts
2
24 VAC Transformer 2
Hot Com
Blk (1) – Common

Line Blk (1) – Common


Wht (2) + Hot
Volts Wht (2) + extending
Wht (3) Y1 Input
Controller
Wht (3) + retracting
NV24-3 US
NVD24-3 US
NV24-3 US
NVD24-3 US
Triac Sink Floating Point
24 VAC Transformer (AC only)
Line
On/Off Control-using actuator to drive one direction and spring the
opposite direction. NOTE: A bridge must be made inside the NVF Volts
2
between terminals 2 and 3 (diagram shown with default position of
Hot Com
S3.2: 3-way Off, 2-way On) Blk (1) – Common

Wht (2) + Hot


24 VAC Transformer 2
Controller Wht (3) Y1 Input
Line Blk (1) – Common
NV24-3 US
Volts Wht (2) + Hot NVD24-3 US

Wht (3) Y1 Input

SPRING RETURN ACTUATORS MODEL DESIGNATION


NVFD24 US
NVFD24-E US retracting plunger (spring up) extending plunger (spring down)
NVFD24 US NVFD24-E US
NVFD24-MFT US NVFD24-MFT-E US
NVF24-MFT US NVF24-MFT-E US

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


17
Wiring for Control Valves
MFT, Spring and Non-Spring Return, 24V
W607_11

Actuators: NVF24-MFT (-E) US NVFD24-MFT (-E) US NV24-MFT US NVD24-MFT US

Hazard Identification INSTALLATION NOTES


Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.
For triac sink the Common connection from the actuator
10
CAUTION must be connected to the Hot connection of the controller.
Position feedback cannot be used with a triac sink controller.
Indicates a potentially hazardous situation which, if not avoided,
The actuator internal common reference is not compatible.
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
Equipment damage!
2 Actuators may be connected in parallel. Power consumption APPLICATION NOTES
and input impedance must be observed.
Meets cULus requirements without the need of an
WARNING electrical ground connection.
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this 8 Control signal may be pulsed from either the Hot (Source)
product, it may be necessary to work with live electrical or Common (Sink) 24 VAC line.
components. Have a qualified licensed electrician or other IN4004 or IN4007 diode.
individual who has been properly trained in handling live electrical 12
(IN4007 supplied, Belimo part number 40155)
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury. Triac Source Floating Point

24 VAC Transformer (AC only)


Floating Point Control. (diagram shown with default position of Line
S3.2: 3-way Off, 2-way On.) Volts
2
Hot COM
24 VAC Transformer 2 Blk (1) Common
Red (2) + Hot
Line Blk (1) – Common
12 Requires diode Wht (3) Y1 Input, 2 to 10V
Volts Red (2) + Hot
A Wht (5) U Output, 2 to 10V
Wht (3) Y1 Input CCW CW
NVF24-MFT US
12 12 NVF24-MFT-E US
NVFD24-MFT US
2 to 10 VDC B
Wht (5) U Output, 2 to 10V Controller NVFD24-MFT-E US
Feedback Signal Position NV24-MFT US
Feedback NVD24-MFT US
NVF24-MFT US
NVF24-MFT-E US
NVFD24-MFT US Direction of rotation switch
NVFD24-MFT-E US

N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.


CCW CCW
NV24-MFT US
CW CW
NVD24-MFT US

A B 1 A B 1

Pulse Width Modulation Control Wiring (diagram shown with default


position of S3.2: 3-way Off, 2-way On)
12
24 VAC Transformer 2

Line Blk (1) – Common


Triac Sink Floating Point
Volts Red (2) + Hot
24 VAC Transformer (AC only)
8 Line
Wht (3) Y Input
(–) Volts
2 to 10 VDC 10 2
Feedback Signal (+) Wht (5) U Output
Hot COM
NVF24-MFT US Blk (1) Common
NVF24-MFT-E US
NVFD24-MFT US Red (2) + Hot
NVFD24-MFT-E US Wht (3) Y1 Input, 2 to 10V
NV24-MFT US
NVD24-MFT US Wht (5) U Output, 2 to 10V
NVF24-MFT US
12 NVF24-MFT-E US
NVFD24-MFT US
NVFD24-MFT-E US
MFT Typical 2 to 10 VDC or 4 to 20 mA Wiring (diagram shown with Controller
NV24-MFT US
default position of S3.2: 3-way Off, 2-way On) NVD24-MFT US

24 VAC Transformer 2

Line Blk (1) Common SPRING RETURN ACTUATORS MODEL DESIGNATION


Volts Red (2) + Hot
retracting plunger (spring up) extending plunger (spring down)
Ω
(–) 500 Ω NVFD24 US NVFD24-E US
Control Signal NVFD24-MFT US NVFD24-MFT-E US
VDC/mA (+) Wht (3) Y1 Input, 2 to 10V
NVF24-MFT US NVF24-MFT-E US
(–)
2 to 10 VDC (+) Wht (5) U Output, 2 to 10V
Feedback Signal
NVF24-MFT US
NVF24-MFT-E US
NVFD24-MFT US
NVFD24-MFT-E US
NV24-MFT US
NVD24-MFT US

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


18
Wiring for Damper Actuators and Control Valves
MFT, Spring Return, 24V
W228_A_11

Actuators: TF24-MFT US LF24-MFT(-S) US

Hazard Identification INSTALLATION NOTES


Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully. 3 Actuators may also be powered by 24 VDC.
CAUTION 5 Actuators with plenum rated cable do not have numbers on
wires; use color codes instead. Actuators with appliance
Indicates a potentially hazardous situation which, if not avoided, cables are numbered.
may result in minor or moderate injury. It may also be used to
alert against unsafe practices. Control signal may be pulsed from either the Hot (Source)
8 or Common (Sink) 24 VAC line.
Equipment damage!
4 Actuators may be connected in parallel if not mechanically For triac sink the Common connection from the actuator must
10 be connected to the Hot connection of the controller. Position
mounted to the same shaft. Power consumption and input
impedance must be observed. feedback cannot be used with a Triac sink controller. The
actuator internal common reference is not compatible.
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this APPLICATION NOTES
product, it may be necessary to work with live electrical Meets cULus requirements without the need of an
components. Have a qualified licensed electrician or other electrical ground connection.
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical 7 A 500 Ω resistor converts the 4 to 20 mA control signal to
safety precautions when exposed to live electrical components 2 to 10 VDC.
could result in death or serious injury.
9 Contact closures A & B also can be triacs. A & B should both be
closed for triac source and open for triac sink.
Floating Point
12 IN4004 or IN4007 diode. (IN4007 supplied, Belimo part
24 VAC Transformer 4 10 5 number 40155).

Line Blk (1) – Common


Volts Two Position
Red (2) + Hot
A
Wht (3) Y1 Input 24 VAC/DC Transformer 4 3 5
8 B
(–)
12 Line Blk (1) Common
2 to 10 VDC 9
Feedback Signal (+) † (5) U Output 2 to 10V Volts
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.

Red (2) Hot

CCW CW
a
(–) Wht (3) Y Input
Position
Feedback VDC (+) † (5) U Output
Direction of rotation switch
CCW CW
CCW CCW
CW CW

A B 5 A B 5

Override Control to min, mid, max, Positions

PWM 24 VAC Transformer (AC only) 5


Line Blk (1) Common
24 VAC Transformer (AC only) 4 5
Volts Red (2) + Hot
A
Line Blk (1) Common Ω B
8
Volts Red (2) + Hot (–)
Control Signal C
Wht (3) Y Input 2-10 VDC or 4 to 20 mA (+) 500 Ω
Wht (3) Y1 Input, 2 to 10V
(–) 1/4 watt
Position (+) † (5) U Output 7 A B C
Feedback VDC Functions
CCW CW Min* 0%
Mid* 50%
Max* 100%
Normal** Control mode acc. to Y
* Default selectable 0-100%. See Configuration Data Sheet.
† Actuator Wire Number Color
** Customizable. See Configuration Data Sheet.

TF24-MFT US 5 Org
LF24-MFT US 5 Wht Refer to page 26 for auxiliary switch (-S models) wiring.
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
19
Wiring for Damper Actuators and Control Valves
MFT, Spring Return, Non-Spring Return, Electronic Fail-Safe, 24V
W400_A_11

Actuators: EFB24-MFT(-S) EFX24-MFT(-S) AFB24-MFT(-S) AFX24-MFT(-S) NFB24-MFT(-S) NFX24-MFT(-S)


LMX LRX NMX AMX ARX GKX NKQ ARX24-MFT-5 ARB24-MFT-5 GRX24-MFT-5
GMX24-MFT-X1 GRB24-MFT-S GRB24-MFT-5 GRB24-MFT-7

Hazard Identification INSTALLATION NOTES


Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully. 3 Actuators may also be powered by 24 VDC.
CAUTION Actuators with plenum rated cable do not have numbers on
5
Indicates a potentially hazardous situation which, if not avoided, wires; use color codes instead. Actuators with appliance
may result in minor or moderate injury. It may also be used to cables are numbered.
alert against unsafe practices. Control signal may be pulsed from either the Hot (Source)
8
Equipment damage! or Common (Sink) 24 VAC line.
4 Actuators may be connected in parallel if not mechanically For triac sink the Common connection from the actuator
10
mounted to the same shaft. Power consumption and input must be connected to the Hot connection of the controller.
impedance must be observed. Position feedback cannot be used with a triac sink controller.
The actuator internal common reference is not compatible.
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed
APPLICATION NOTES
electrician or other individual who has been properly trained in handling live Meets cULus requirements without the need of an electrical
electrical components perform these tasks. Failure to follow all electrical safety ground connection.
precautions when exposed to live electrical components could result in death or
serious injury. A 500 Ω resistor converts the 4 to 20 mA control signal
7
to 2 to 10 VDC.
VDC/4-20 mA
Contact closures A & B also can be triacs. A & B should
9
24 VAC Transformer 4 3 5
both be closed for triac source and open for triac sink.

Line Blk (1) Common


Volts Red (2) + Hot Two Position
500 Ω
Ω 1/4 watt
(–)
Control Signal 24 VAC/DC Transformer 4 3 5
(+) Wht (3) Y1 Input, 2 to 10V
4 to 20 mA or 2 to 10 VDC
7 Pnk (4) Y2 Input Line Blk (1) Common
Grn (5) U Output, 2 to 10V Volts Red (2) Hot
CCW CW a

N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.


(–) Wht (3) Y Input
Position
Pnk (4) Y2 Input
Feedback VDC
(+) Org (5) U Output
Floating Point (except NKQ)

24 VAC Transformer 10 4 3 5

Line Blk (1) Common –


Volts Red (2) Hot +
A
Wht (3) Y1 Input Override Control to min, mid, max, Positions
8
B
Pnk (4) Y2 Input
(–) 9 24 VAC Transformer (AC Only) 5
2 to 10 VDC 3
Feedback Signal (+) Org (5) U Output 2 to 10V

Line Blk (1) Common


Direction of rotation switch
CCW CCW
Volts Red (2) + Hot
CW CW A
A B 5 A B 5 Ω B
(–)
Control Signal C
2-10 VDC or 4 to 20 mA (+) Wht (3) Y1 Input, 2 to 10V
500 Ω Pnk (4) Y2 Input
Triac Source and Sink Diagrams (See page 21) 7 1/4 watt
Org (5)
PWM (except NKQ)

24 VAC Transformer (AC only) 4 5 Functions a b c


Min* 0%
Line Blk (1) Common Mid* 50%
Volts 8
Red (2) + Hot Max* 100%
Wht (3) Y Input Normal** Control mode acc. to Y
Position (–) Pnk (4) Y2 Input
Feedback VDC (+) * Default selectable 0-100%. See Configuration Data Sheet.
Org (5) U Output ** Customizable. See Configuration Data Sheet.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


20
Wiring for Damper Actuators and Control Valves
MFT, Non-Spring Return, 24V
W402_11

Actuators: LMX LRX NMX AMX ARX ARX24-MFT-5


ARB24-MFT-5 GMX24-MFT GMX24-MFT-X1 GRX24-MFT-5 GRX24-MFT-7 GRB24-MFT-5
GRB24-MFT-7

Hazard Identification INSTALLATION NOTES


Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.
Actuators with plenum rated cable do not have numbers on
5
CAUTION wires; use color codes instead. Actuators with appliance
cables are numbered.
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to 6 Only connect common neg (-) leg of control circuits.
alert against unsafe practices.
For triac sink with common connection from the actuator
Equipment damage! 11 must be connected to the hot connection of the controller.
4 Actuators may be connected in parallel if not mechanically The actuator must be connected to the control board
mounted to the same shaft. Power consumption and input common.
impedance must be observed.

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical APPLICATION NOTES
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components Meets cULus requirements without the need of an
could result in death or serious injury. electrical ground connection.

Triac Sink Triac Sink with Separate Transformer


24 VAC Transformer
Line 24 VAC Transformer
Volts 24 VAC Transformer Line
11 4 5 6 Volts
Line
Hot Com 5
Blk (1) Common Volts 4
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.

Red (2) + Hot Blk (1) Common


Wht (3) Y1 Input Hot Com
Red (2) + Hot
Wht (3) Y1 Input
Pnk (4) Y2 Input
Org (5) U Output 2 to 10 V
Pnk (4) Y2 Input
Org (5) U Output 2 to 10 V
Controller

Controller

Triac Source

24 VAC Transformer
Line
Volts
4 5
Hot Com
Blk (1) Common
Red (2) + Hot
Wht (3) Y1 Input

Pnk (4) Y2 Input


Org (5) U Output 2 to 10 V

Controller

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


21
Wiring for Damper Actuators and Control Valves
Wiring Multiple MFT Actuators
W234_A_11

Control Type: PWM

Hazard Identification INSTALLATION NOTES


Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.
3 Actuators may also be powered by 24 VDC.
CAUTION Actuators with plenum rated cable do not have numbers on
Indicates a potentially hazardous situation which, if not avoided, 5
wires; use color codes instead. Actuators with appliance
may result in minor or moderate injury. It may also be used to cables are numbered.
alert against unsafe practices.
Control signal may be pulsed from either the Hot or
Equipment damage! 8
4 Common 24 VAC line.
Actuators may be connected in parallel if not mechanically
mounted to the same shaft. Power consumption and input
impedance must be observed.

WARNING Pulse Width Modulation


Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical 5
components. Have a qualified licensed electrician or other 24 VAC Transformer (AC Only) Master
individual who has been properly trained in handling live electrical .1 to 25.5 sec
components perform these tasks. Failure to follow all electrical Line Blk (1) Common
Volts 8
safety precautions when exposed to live electrical components
Red (2) + Hot
could result in death or serious injury. 3

Position
(–) Wht (3) Y Input
Feedback VDC
(+) Org (5) U Output
0 to 5 VDC
Wiring multiple...MFT actuators to single shaft and/or on 2 to 10 VDC
valves. All MFT actuators are wired in master-slave
configuration. CCW CW

MFT actuator configurations should also co-ordinate with


each other. Meaning the master input = controllers output.
Master output = slave input. Slave output = controller input. Slave 5

N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.


Example Blk (1) Common
Controller Master Slave Slave
Output Feedback Input Feedback Red (2) + Hot

0.1 to 25.5 sec 2 to 10 VDC 2 to 10 VDC 0 to 5 VDC Wht (3) Y Input


2 to 10 VDC
Org (5) U Output
Multiple Actuators Mounted to One Control Shaft
Model Max. Qty Per Shaft Torque Generated CCW CW
EFB24-MFT(-S) 3 810 in-lb 4
EFX24-MFT(-S)
AFB24-MFT(-S) 3 432 in-lb
AFX24-MFT(-S)
GMX(B)24-MFT 2 640 in-lb
GKX(B)24-MFT 2 640 in-lb

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


22
Wiring for Damper Actuators and Control Valves
Spring Return and Non-Spring Return, 24V for use with
Wnew60408_6 Honeywell® Electronic Series 90, or a 0 to 135 Ω input

Actuators: AFB24-MFT95 AFX24-MFT95 GMX24-MFT95 AMX24-MFT95 NMX24-MFT95 LMX24-MFT95

High Limit Control Typical wiring diagrams for multiple actuators


INSTALLATION NOTES used with the W973, W7100 and T775 controllers

W017

W020
24 VAC Transformer 5 Q209A
21 Minimum Position
Actuators with plenum rated cable do 21 24 VAC Transformer Potentiometer 5
5 not have numbers on wires; use color Line Blk (1) Common
Volts Red (2) + Hot Line Blk (1) Common
codes instead. Actuators with 23 Volts Red (2) + Hot
appliance cables are numbered. 23
22 W Pnk (4) W 24
Provide overload protection and Series 90
R Wht (3) R
22 B R W Pnk (4) W 25
21 disconnect as required. Controller
H205 Wht (3) R
B R W B Gry (5) B Changeover W R B
Actuators and controller must have Org (6) ‘U5’ Output 2 to 10 VDC
Controller Gry (5) B
22 separate transformers. Series 90 high limit control - 280 Ω
Org (6) ‘U5’ Output 2 to 10 VDC
-MFT95
Consult controller instruction data for 22 -MFT95
W
23 more detailed information. Shunting
Wiring Multiple Actuators to a Series 90 Controller Resistor
B
Resistor value depends on the type of Occupied

W018
Contact
24 controller and the number of 24 VAC Transformer 5 Y
21 Honeywell T675A
actuators. No resistor is used for one R
Morning Warmup
R W
actuator. Honeywell® resistor kits may Line Blk (1) Common 24
also be used. Volts Red (2) + Hot
23
W973, W7100
Controller

To reverse control rotation, use the W Pnk (4) W 25


25 reversing switch. Shunting
Resistor R Wht (3) R 21
B Gry (5) B Line Blk (1) Common
Wire Colors 24
Series 90 Org (6) ‘U5’ Output 2 to 10 VDC Volts Red (2) + Hot
Controller 23
1 = Black 3 = White 5 = Gray -MFT95
2 = Red 4 = Pink 6 = Orange 21
No. of
Pnk (4) W 25
Line Blk (1) Common
actuators Resistance Wht (3) R
Override 2 1300 Ω
Volts Red (2) + Hot 3 910 Ω Gry (5) B
Switch A Switch B Damper Position 23 4 768 Ω Org (6) ‘U5’ Output 2 to 10 VDC
Resistor Kit No. ZG-R06 To other
Damper Open No. of Pnk (4) W 25 actuators -MFT95
actuators Resistance
2 140 Ω Wht (3) R
Damper Closed
3 71.5 Ω Gry (5) B Used with the W973 and W7100 controllers
The direction of rotation switch is set so that the fail safe position and the 4 47.5 Ω
5 37.5 Ω Org (6) ‘U5’ Output 2 to 10 VDC
position of the damper is closed with no signal at wire R.
6 28 Ω To other
Resistor Kit No. ZG-R03 actuators -MFT95
5 Honeywell Q209A
21 24 VAC Transformer Minimum Position
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.

W015

21 24 VAC Transformer Potentiometer


Line Blk (1) Common
Volts Red (2) + Hot
Wiring Multiple Actuators to a Series 90 Controller Line Blk (1) Common
23 using a Minimum Position Potentiometer
A Volts Red (2) + Hot
23
W019

Pnk (4) W S963A


24 Minimum Position 23 22
24 VAC Transformer 5
135 Ω Wht (3) R 21 Potentiometer
W R B W Pnk (4) W 25
B 24
Gry (5) B Line R R W Wht (3) R
Blk (1) Common
Org (6) ‘U5’ Output 2 to 10 VDC Volts B Gry (5) B
Red (2) + Hot Shunting
Series 90 25 Resistor
Org (6) ‘U5’ Output 2 to 10 VDC
24 VAC Transformer -MFT95 Controller W973, W7100 Honeywell
21 B W T775 T675A Morning
B R Pnk (4) W Warmup -MFT95
Line Blk (1) Common Wht (3) R
R
Volts Red (2) + Hot 22
W Gry (5) B
23 Shunting
Resistor
A Org (6) ‘U5’ Output 2 to 10 VDC
W Pnk (4) W 24 24 23
Line -MFT95
R Wht (3) R B R W
Volts B
B Gry (5) B H205 Change- Occupied
over Controller Contact
22 Controller Org (6) ‘U5’ Output 2 to 10 VDC 21
-MFT95 Line Blk (1) Common
Volts Red (2) + Hot
23
Low Limit Control 21 22
Line Pnk (4) W 25
Blk (1) Common
W016

Volts Wht (3) R


24 VAC Transformer 5 Red (2) + Hot
21 23 Gry (5) B
22 Org (6) ‘U5’ Output 2 to 10 VDC
Line Blk (1) Common Pnk (4) W 25
Volts Red (2) + Hot To other
Wht (3) R actuators -MFT95
23
Gry (5) B
22 W W R B Pnk (4) W 24 Org (6) ‘U5’ Output 2 to 10 VDC
Series 90 Wht (3) R To other
R actuators -MFT95
Controller
B Gry (5) B

Series 90 low limit control Org (6) ‘U5’ Output 2 to 10 VDC


135 Ω for 0 to 50% control
280 Ω for 0 to 100% control -MFT95

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


23
Wiring for Damper Actuators and Control Valves
Proportional, Spring Return, 24V, 6 to 9 VDC
Output Power Supply 20 VDC provides power to controllers
W609_11

Actuators: LF24-MFT-20 US LF24-MFT-S-20 US

6 to 9 VDC Control of LF24-MFT (-S) -20 US


Hazard Identification

W027
Warnings and Cautions appear at appropriate sections throughout 24 VAC Transformer
this manual. Read these carefully. 21
Line Blk (1) Common 3
CAUTION
Volts Red (2) + Hot
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to Wht (3) Y Input, 6 to 9V
alert against unsafe practices. Control Signal Wht (4) Output +20 VDC
6 to 9 VDC (+)
Equipment damage! Wht (5) U Output 2 to 10V
2 Actuators may be connected in parallel. Power consumption Power to Controller
and input impedance must be observed. Wht (6) Common +20 VDC
Controller Common (–)
CW CCW
WARNING 2
Feedback 2-10 VDC
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this LF24-MFT (-S) -20 US
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical Multiple LF24-MFT (-S) -20 US Actuators from One Controller
safety precautions when exposed to live electrical components

W029
could result in death or serious injury.
21 24 VAC Transformer
Line Blk (1) Common 3
Volts Red (2) + Hot
INSTALLATION NOTES
Wht (3) Y Input, 6 to 9V
Control Signal
3 Actuators may also be powered by 24 VDC 6 to 9 VDC (+) Wht (4) Output +20 VDC

21 Provide overload protection and disconnect as required. Feedback 2-10 VDC Wht (5) U Output 2 to 10V

Power to Controller Wht (6) Common +20 VDC


CW CCW
Controller Common (–)

N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.


2
Typical Control Wiring for MP-52XX Series Actuators to
Controllers Requiring External 20 VDC Power Supply LF24-MFT (-S) -20 US
W215

21 24 VAC Transformer
CP-8102 1 MP-52XX
TP-810X Vac Line
2 Blk (1) Common
TP-8121 Power Black 3
TP-8124 Volts Red (2) + Hot
TP-8232 +20 (Red) Red 3
OP1 (Yellow) Yellow N.C. Wht (3) Y Input, 6 to 9V
Typical COM (Blue) Blue COM
Controller Wht (4) Output, +20 VDC
Brown N.O.
Aux.
Switch Orange Wht (5) U Output 2 to 10V
Green
1 24 Vac: Black/Blue Wht (6) Common +20 VDC
120 Vac: White CW CCW
240 Vac: White/Black
Wire cross reference 2
Belimo modulating actuators Belimo
are 24 VAC/DC, if 120 or 240 MP-52XX (SR or MFT) To other actuators
LF24-MFT (-S) -20 US
is available an external Black/Blue, Power 2, Hot
transformer is required. Black, Power 1, Com
Red, +20 4, +20 VDC
Yellow, OP1 3, Signal
2 Maximum of 2 Blue, COM 6, Com VDC
Brown, N.O. S3, N.O. “-S” type
3 MP-52XX-500 models include Orange, N.C. S2, N.C. “-S” type
internal SPDT auxiliary switch. Green, Ground Not used

Refer to page 26 for auxiliary switch (-S models) wiring.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


24
Wiring for Damper Actuators and Control Valves
Wiring Multiple MFT Actuators
W234_2_B_11

Control Type: VDC or 4-20mA MFT95

VDC or 4-20mA
Hazard Identification
24 VAC Transformer Master 5
Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.
Line Blk (1) Common
Volts
CAUTION Red (2) + Hot
3
Indicates a potentially hazardous situation which, if not avoided, (–)
may result in minor or moderate injury. It may also be used to Control Signal
(+) Wht (3) Y Input, 2 to 10 V
2 to 10 VDC or
alert against unsafe practices. 4 to 20 mA
500 Ω
Org (5) U Output 2 to 10 V
1/4 watt
Equipment damage!
4 Actuators may be connected in parallel if not mechanically CCW CW
mounted to the same shaft. Power consumption and input
impedance must be observed.
5
WARNING Slave
Live Electrical Components!
Blk (1) Common
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical Maximum Red (2) + Hot
components. Have a qualified licensed electrician or other 4 actuators
individual who has been properly trained in handling live electrical per shaft. Wht (3) Y Input, 2 to 10 V
components perform these tasks. Failure to follow all electrical
Org (5) U
safety precautions when exposed to live electrical components
could result in death or serious injury.
CCW CW

4
INSTALLATION NOTES

3 Actuators may also be powered by 24 VDC.


Multiple Actuators Mounted to One Control Shaft
Actuators with plenum rated cable do not have numbers on
5
wires; use color codes instead. Actuators with appliance
cables are numbered. 24 VAC Transformer Master 5
21
21 Provide overload protection and disconnect as required.
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.

Line Blk (1) Common


Volts Red (2) + Hot
23 Consult controller instruction data for more detailed 23
information. 3 W Wht (3) W
25
R Pnk (4) R
25 To reverse control rotation, use the reversing switch. B Gry (5) B
Org (6) U Output, 2 to 10 V
-MFT95
Wiring multiple...MFT actuators to single shaft and/or on
Slave 5
valves. All MFT actuators are wired in master-slave
configuration. Blk (1) Common
MFT actuator configurations should also co-ordinate with Red (2) + Hot 23

each other. Meaning the master input = controllers output. Wht (3) Y1 Input 25
Master output = slave input. Slave output = controller input. Pnk (4) Y2 Input
Org (6) U Output 2 to 10 V
Example
CCW CW
Controller Master Slave Slave
Output Feedback Input Feedback -MFT
2 to 10 VDC 2 to 10 VDC 2 to 10 VDC 0 to 5 VDC 4

Multiple Actuators Mounted to One Control Shaft


Model Max. Qty Per Shaft Torque Generated
EFB24-MFT(-S)
3 810 in-lb
EFX24-MFT(-S)
AFB24-MFT(-S)
3 432 in-lb
AFX24-MFT(-S)
GMX(B)24-MFT 2 640 in-lb
GKX(B)24-MFT 2 640 in-lb

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


25
Wiring for Damper Actuators and Control Valves
Auxiliary Switch Wiring
W224_A_11

Actuators: EFB...-S EFX...-S AFB...-S AFX...-S AF...-S US NFB...-S NFX...-S LF...-S US TF...-S US
AMB(X)...-S LMB(X)...-S ARB(X)...-S LRB(X)...-S S1A/S2A LMB(X)...(-P5)(-P10)

INSTALLATION NOTES APPLICATION NOTES

1 One built-in auxiliary switch (1xSPDT), for end position Meets cULus requirements without the need of an
indication, interlock control, fan startup, etc. electrical ground connection.
Two built-in auxiliary switches (2xSPDT), for end position
13 indication, interlock control, fan startup, etc. Same voltage must be used for dual switch models.
† Either 24 VAC or line voltage, not both.
WARNING
Live Electrical Components! Auxiliary Switch Wiring for LF…-S US, TF…-S,
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical LMB(X)24-3-S, AMB(X)24-3-S, LRB(X)24-3-S, ARB(X)24-3-S
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical 1
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components S1
NC
could result in death or serious injury. S2

Auxiliary Switch Wiring for EFB...-S, EFX...-S, AFB...-S, S3 0° to 95°


NO
AFX...-S, NFB...-S, NFX...-S LF…-S US
TF…-S US
13
† LMB(X)24-3-S
AMB(X)24-3-S
S1
NC LRB(X)24-3-S
S2 ARB(X)24-3-S
S3 10°
NO
Auxiliary Switch Ratings
S4
Product Voltage Resistive Inductive
NC
S5 Load Load
10° to 90°
S6 10° to 85° for EF...
EFB...-S, EFX...-S 250 3.0 A 0.5 A
NO
AFB...-S, AFX...-S 250 3.0 A 0.5 A
EFB…-S AFB…-S NFB…-S
EFX…-S AFX…-S NFX…-S AF...-S US 250 7.0 A 2.5 A

N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.


NFB...-S, NFX...-S 250 3.0 A 0.5 A
Auxiliary Switch Wiring for AF… -S US
LF...-S US 250 3.0 A 0.5 A
13 TF...-S US 250 3.0 A 0.5 A
S1
NC
AMB(X)...-S 250 3.0 A 0.5 A
S2
LMB(X)...-S 250 3.0 A 0.5 A
S3 5°
NO
ARB(X)...-S 250 3.0 A 0.5 A
S4
NC
LRB(X)...-S 250 3.0 A 0.5 A
S5
S1A, S2A 250 3.0 A 0.5 A
S6 25° to 85°
NO

AF…-S US
Potentiometer and Auxiliary Switch Wiring for
LMB(X)24-3(-S)(-P5)(-P10)
Add on Auxiliary Switches
S1A/S2A for GMB(X), AMB(X), NMB(X), LMB(X), GRB(X),
ARB(X), NRB(X), LRB(X)
S1
S1 NC
NC
S2
S2
S3
5/10K Ω
S3 NO
NO
S4
NC
S1A S5
S6 Potentiometer Auxiliary Switch
NO

S2A

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


26
Interface Wiring Detail
SYx-MFT, 24V, 120/230V

Actuators: SYx-MFT

Notes:
INSTALLATION NOTES 1. Motor CAMS have been factory calibrated and should not be moved.
2. An adaption must be performed if any limit switch is adjusted. This will
calibrate the beginning and end stopping points. Press the adaption
CAUTION button for 3 seconds and release.

MFT Connection


Control Signal +


Control Signal -
FDBK +
FDBK -


Adaption 

24V
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.

Direction of Rotation

N
H

Control Signal +


Control Signal -
FDBK +
FDBK -


 Adaption

120/230V
Direction of Rotation

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


27
SYx-P Interface Wiring Detail

LED Open

LED Close

N Power Supply (4)


Sensitivity switch setting
+ Power Supply (5) is position #3 for factory
Control Signal (6) default. To widen dead-
Control Signal (7) band, select a higher
number (up to 9).

Feedback (11)
Feedback (12)
Sensitivity

VR1
VR2

Notes:
INSTALLATION NOTES 1. Do not change sensitivity or dip switch settings with power applied!
2. VR1 and VR2 are factory calibrated and should not be moved.
CAUTION 3. Motor CAMS have been factory calibrated and should not be moved.

8 7 6 5 4 3 2 1 OFF 8 7 6 5 4 3 2 1 OFF
Dip
INPUT = 2-10 VDC RESPONSE = DIRECT
Switch
ON ON
Settings
8 7 6 5 4 3 2 1 OFF 8 7 6 5 4 3 2 1 OFF
INPUT = 4-20mA RESPONSE = REVERSE
ON ON

8 7 6 5 4 3 2 1 OFF
8 7 6 5 4 3 2 1 OFF LOSS OF SIGNAL = CLOSED
INPUT = 1-5 VDC (Direct Acting)

N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.


ON LOSS OF SIGNAL = OPEN
ON (Reverse Acting)

8 7 6 5 4 3 2 1 OFF 8 7 6 5 4 3 2 1 OFF LOSS OF SIGNAL = OPEN


OUTPUT = 4-20mA (Direct Acting)

ON ON
LOSS OF SIGNAL = CLOSED
(Reverse Acting)

8 7 6 5 4 3 2 1 OFF 8 7 6 5 4 3 2 1 OFF
OUTPUT = 2-10 VDC LOSS OF SIGNAL = STOP
ON ON

WARNING

Potentiometer For 2-position actuators with 1k feedback option


Potentiometer points 1, 2, 3 are wired to terminal blocks 8, 9, 10.
(Factory Pre-set) When a valve is closed: 8, 9 1k Ω
9, 10 0k Ω
When a valve is opened: 8, 9 0k Ω
9, 10 1k Ω

For modulating actuators with 1k feedback option*


*On modulating Potentiometer points 1, 2, 3 are wired to terminal blocks 8, 9, 10.
When a valve is closed: 8, 9 1k Ω
actuators DO NOT 9, 10 0k Ω
master/slave using When a valve is opened: 8, 9 0k Ω
optional potentiometer. 9, 10 1k Ω

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


28
Wiring for Damper Actuators and Control Valves
On/Off, 24V, 120V or 230V
W546_11

SY Actuator Wiring Diagram, SY1…5-24V – On/Off


SY1…12-120V or 230V On/Off

Hazard Identification
INSTALLATION NOTES
Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.
Observe class 1 and class 2 wiring restrictions.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, Transformer sizing = SY actuator draw X 1.25 (safety margin)
may result in minor or moderate injury. It may also be used to (Ex. SY2-24 requires 3.0A x 1.25 = 3.75A,
alert against unsafe practices. 3.75A X 24 VAC = 90VA Transformer).
Indicates an action or condition that may cause irreversible
damage to the actuator(s) or associated equipment.
Equipment damage! NOTES SY1…12-120V or 230V
Power consumption and input impedance must be observed.
sCaution: Power Supply Voltage
s)SOLATIONRELAYSMUSTBEUSEDINPARALLELCONNECTIONOFMULTIPLEACTUATORS
NOTES SY1…5-24 using a common control signal input.
s(, CANNOTBECONNECTEDTOTERMINALANDSIMULTANEOUSLY
Each actuator should be powered by a single, isolated sRequired: 4ERMINALNEEDSTOBEFIELDWIREDTOENABLEHEATERCIRCUIT
33 control transformer.

s)SOLATIONRELAYSMUSTBEUSEDINPARALLELCONNECTIONOFMULTIPLEACTUATORS
using a common control signal input.
s(CANNOTBECONNECTEDTOTERMINALANDSIMULTANEOUSLY
sRequired: 4ERMINALNEEDSTOBEFIELDWIREDTOENABLEHEATERCIRCUIT

33 24V AC/DC Transformer G G Ground 120V or 230V AC/DC


G G Ground

1 Common N L1 1 Common
Line Open Open
Volts
3 Open H L2 3 Open
4 Closed 4 Closed
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.

Close Close
Connect to #1 for fully Connect to #1 for fully
5 open indication
5 open indication

6 Connect to #1 for fully


closed indication
6 Connect to #1 for fully
closed indication

7 HTR 7 HTR

A A
LS3 LS3
B B
A-C (Open Indication) A-C (Open Indication)
C C
D D
LS4 LS4
E E
D-F (Closed Indication) D-F (Closed Indication)
F F
Contact Rating: 5A 250 VAC Max. Contact Rating: 5A 250 VAC Max.

SY2…5-24 SY2…12-120V or 230V

A LS3 A LS3

B B
A-B (Open Indication) A-B (Open Indication)
C Contact Rating: 5A 125 VAC Max.
C Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max. 3A 250 VAC Max.
E LS4
E LS4

F A-E (Closed Indication)


F A-E (Closed Indication)

SY1-24 SY1-110 (220)

SY1 Contact Arrangements

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


29
Wiring for Damper Actuators and Control Valves
Proportional, 24V, 120V or 230V
W547_11

SY Actuator Wiring Diagram, SY1-24P and SY1-110P (220P)

Hazard Identification INSTALLATION NOTES


7ARNINGSAND#AUTIONSAPPEARATAPPROPRIATESECTIONSTHROUGHOUT
this manual. Read these carefully. /BSERVE#LASSAND#LASSWIRINGRESTRICTIONS
CAUTION 4RANSFORMERSIZING39ACTUATORDRAW8SAFETYMARGIN
)NDICATESAPOTENTIALLYHAZARDOUSSITUATIONWHICH IFNOTAVOIDED %X39 REQUIRES!X! !86!#6!4RANSFORMER
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
APPLICATION NOTES
Indicates an action or condition that may cause irreversible
damage to the actuator(s) or associated equipment.
Ground shielded wire at control panel chassis.
34 Tape back ground at actuator.
%QUIPMENTDAMAGE
0OWERCONSUMPTIONANDINPUTIMPEDANCEMUSTBEOBSERVED 36 Use of feedback is optional.

NOTES SY1…24P NOTES SY1…110P (220P)


Each actuator should be powered by a single, isolated sCaution:0OWERSUPPLYVOLTAGE
33 control transformer.
s0OWERSUPPLY#OM.EUTRALAND#ONTROL3IGNAL "–" wiring to a common is
s0OWERSUPPLY#OM.EUTRALAND#ONTROL3IGNAL "–" wiring to a common is prohibited. Terminals 4 and 6 need to be wired separately.
prohibited. Terminals 4 and 6 need to be wired separately. s$ONOTCHANGESENSITIVITYORDIPSWITCHSETTINGSWITHPOWERAPPLIED
s$ONOTCHANGESENSITIVITYORDIPSWITCHSETTINGSWITHPOWERAPPLIED

33 24V AC/DC Transformer G G Ground 120 or 230 VAC


G G Ground

Line 4 Power Supply Com N L1 4 Power Supply Com


Voltage
5 Power Supply Hot H L2 5 Power Supply Hot
6 Control Signal (-) 6 Control Signal (-)
Control signal

N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.


Control signal
7 Control Signal (+) 7 Control Signal (+)
34 34
8 Internal Use Only 8 Internal Use Only
9 Internal Use Only 9 Internal Use Only
10 Internal Use Only 10 Internal Use Only
11 Feedback (-) 11 Feedback (-)
Feedback Feedback
12 Feedback (+) 12 Feedback (+)
36 36

A LS3
A LS3

B B
! "/PEN)NDICATION ! "/PEN)NDICATION
C #ONTACT2ATING !6!#-AX
C #ONTACT2ATING !6!#-AX
!6!#-AX !6!#-AX
E LS4
E LS4

F ! %#LOSED)NDICATION
F ! %#LOSED)NDICATION

SY1-24P SY1 -110P (220P)

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


30
Wiring for Damper Actuators and Control Valves
Proportional, 24V, 120V or 230V
W547_2_11

Actuator: SY2…5-24MFT SY2...12-120MFT SY2...12-230MFT

Hazard Identification INSTALLATION NOTES


7ARNINGSAND#AUTIONSAPPEARATAPPROPRIATESECTIONSTHROUGHOUT
this manual. Read these carefully. /BSERVE#LASSAND#LASSWIRINGRESTRICTIONS
CAUTION 4RANSFORMERSIZING39ACTUATORDRAW8SAFETYMARGIN
Indicates a potentially hazardous situation which, if not avoided, %X39 REQUIRES!X! !86!#6!4RANSFORMER
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
Indicates an action or condition that may cause irreversible APPLICATION NOTES
damage to the actuator(s) or associated equipment.
Ground shielded wire at control panel chassis.
%QUIPMENTDAMAGE 34 Tape back ground at actuator.
0OWERCONSUMPTIONANDINPUTIMPEDANCEMUSTBEOBSERVED
36 Use of feedback is optional.

NOTES SY2...5-24MFT NOTES SY2...12-120MFT (230MFT)


Each actuator should be powered by a single, isolated sCaution:0OWERSUPPLYVOLTAGE
33
control transformer.
s0OWERSUPPLY#OM.EUTRALAND#ONTROL3IGNAL "–" wiring to a common is
prohibited.

A Internal Use Only

B Internal Use Only


PC Tool 1 Internal Use Only
Service Jack

2 Internal Use Only

3 Internal Use Only

Control Signal (+) Y ŏ /- Power Supply Com


Control Signal 24V AC/DC
Control Signal (-) ~/+ Power Supply Hot
ŏ1
Address
Feedback Signal (+) U5
Feedback 33

Feedback Signal (-) ŏ2 8 Internal Use Only


Adaption
36 34 Not Used - C1 9 Internal Use Only

Not Used - C2 10 Internal Use Only


Y2 Y1 SYx-24MFT
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.

G PE

Power Supply Com – 120v (N) / 230v (L1)


Power Supply Hot – 120v (H) / 230v (L2)

A Internal Use Only


N L
B Internal Use Only
PC Tool
Control Signal (+) Y Service Jack 1 Internal Use Only
Control Signal
Control Signal (-) ŏ1 2 Internal Use Only

Feedback Signal (+) U5 3 Internal Use Only


Feedback
Feedback Signal (-) ŏ2
36
Not Used - C1
34
Not Used - C2
Adaption Address

8 Internal Use Only


A LS3
Y1
9 Internal Use Only
B SYx-120MFT
Y2

10 Internal Use Only


! "/PEN)NDICATION SYx-230MFT
C #ONTACT2ATING !6!#-AX
!6!#-AX G PE
E LS4

F ! %#LOSED)NDICATION

SY2...5-24MFT

SY2...12-120MFT
(230MFT)

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


31
Wiring for Damper Actuators and Control Valves
On/Off, 24V, 120 or 230V
W549_11

SY Actuator Wiring Diagram, SY1…5-24 – Multiple Wiring


SY1…12-110 (220) – Multiple Wiring

Hazard Identification INSTALLATION NOTES


Warnings and Cautions appear at appropriate sections throughout this
manual. Read these carefully. Observe class 1 and class 2 wiring restrictions.
Transformer sizing = SY actuator draw X 1.25 (safety margin)
CAUTION
(Ex. SY2-24 requires 3.0A x 1.25 = 3.75A,
Indicates a potentially hazardous situation which, if not avoided, may result in 3.75A X 24 VAC = 90VA Transformer).
minor or moderate injury. It may also be used to alert against unsafe practices.

Indicates an action or condition that may cause irreversible damage to the


actuator(s) or associated equipment. NOTES
Equipment damage! sCaution: Power Supply Voltage.
Power consumption and input impedance must be observed. s)SOLATIONRELAYSMUSTBEUSEDINPARALLELCONNECTIONOFMULTIPLEACTUATORS
using a common control signal input.
s(, CANNOTBECONNECTEDTOTERMINALANDSIMULTANEOUSLY
sRequired: 4ERMINALNEEDSTOBEFIELDWIREDTOENABLEHEATERCIRCUIT

24V AC Transformer G Actuator B


G Actuator B
G Ground 120 or 230 VAC G Ground

Line 1 Common N L1 1 Common


Open K1
Voltage * Open K1
3 Open 3 Open
H L2
4 Closed 4 Closed
Close K1-B Close K1-B
5 5
6 6
7 HTR 7 HTR

A A
LS3 LS3
B B
A-C (Open Indication) A-C (Open Indication)
C C
D D
LS4 LS4
E E

N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.


D-F (Closed Indication) D-F (Closed Indication)
F F
Contact Rating: 5A 250 VAC Max. Contact Rating: 5A 250 VAC Max.

SY2…5-24 SY2…12-110 (220)

G Actuator A G Actuator A
G Ground G Ground

1 Common 1 Common
*
3 Open 3 Open
4 Closed 4 Closed
K1-A K1-A
5 5
6 6
7 HTR 7 HTR

* The isolation relays may not be needed.


Dependent on signal
A LS3 A LS3
B B
A-C (Open Indication) A-C (Open Indication)
C C
D D
LS4 LS4
E E
D-F (Closed Indication) D-F (Closed Indication)
F F
A LS3 A LS3
Contact Rating: 5A 250 VAC Max. Contact Rating: 5A 250 VAC Max.

B B SY2…5-24 SY2…12-110 (220)


A-B (Open Indication) A-B (Open Indication)
C Contact Rating: 5A 125 VAC Max.
C Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max. 3A 250 VAC Max.
E LS4
E LS4

F A-E (Closed Indication)


F A-E (Closed Indication)

SY1 -24 SY1-110 (220)

SY1 Contact Arrangements

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


32
Wiring for Control Valves
Proportional, 24V
W550_11

SY Actuator Wiring Diagram, SY1-24P – Multiple Wiring

Hazard Identification 33 24V AC/DC Transformer G


Actuator B
G Ground
Warnings and Cautions appear at appropriate
sections throughout this manual. Read these carefully. Line 4 Power Supply Com
Voltage 5 Power Supply Hot
CAUTION
6 Control Signal (-)
Indicates a potentially hazardous situation which, if
not avoided, may result in minor or moderate injury. 7 Control Signal (+)
It may also be used to alert against unsafe practices. 8 Internal Use Only
35
9 Internal Use Only
Indicates an action or condition that may cause 10 Internal Use Only
irreversible damage to the actuator(s) or
associated equipment. 11 Feedback (-)
Feedback (B)
12 Feedback (+)
Equipment damage! 36
Power consumption and input impedance
A
must be observed. LS3

B
A-B (Open Indication)
C Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.
E LS4
INSTALLATION NOTES F A-E (Closed Indication)

Observe class 1 and class 2 wiring restrictions. SY1 -24P

Transformer sizing = SY actuator draw X 1.25 (safety margin)


(Ex. SY2-24 requires 3.0A x 1.25 = 3.75A,
3.75A X 24 VAC = 90VA Transformer). Actuator A
33 24V AC/DC Transformer G G Ground

NOTES SY1-24P 4 Power Supply Com


Line
Voltage 5 Power Supply Hot
Each actuator should be powered by a single, isolated
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.

33 control transformer.
6 Control Signal (-)
sSY1-24P notes: Power supply Com/Neutral and Control Signal 7 Control Signal (+)
"–" wiring to a common is prohibited. Terminals 4 and 6 need to
be wired separately otherwise irreversible damage will occur. 35 8 Internal Use Only
s$ONOTCHANGESENSITIVITYORDIPSWITCHSETTINGSWITH 9 Internal Use Only
power applied.
10 Internal Use Only

11 Feedback (-)
Control Signal Feedback (A)
12 Feedback (+)
APPLICATION NOTES 36
A LS3

Recommended twisted shielded pair for control wiring. B


35
Ground shielded wire at control panel chassis. A-B (Open Indication)
Tape back ground at actuator. C Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.

36 Use of feedback is optional. E LS4

F A-E (Closed Indication)

SY1 -24P

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


33
Wiring for Control Valves
Proportional, Multiple Wiring, 24V
W550_2_11

Actuators: SY2...5-24MFT

Hazard Identification
INSTALLATION NOTES
Warnings and Cautions appear at appropriate
sections throughout this manual. Read these carefully.
Observe class 1 and class 2 wiring restrictions.

CAUTION Transformer sizing = SY actuator draw X 1.25 (safety margin)


Indicates a potentially hazardous situation which, if (Ex. SY2-24 requires 3.0A x 1.25 = 3.75A,
not avoided, may result in minor or moderate injury. 3.75A X 24 VAC = 90VA Transformer).
It may also be used to alert against unsafe practices.

NOTES SY2...5-24MFT
Indicates an action or condition that may cause
irreversible damage to the actuator(s) or Each actuator should be powered by a single, isolated
33 control transformer.
associated equipment.

Equipment damage!
Power consumption and input impedance
must be observed. APPLICATION NOTES
Recommended twisted shielded pair for control wiring.
35 Ground shielded wire at control panel chassis.
Tape back ground at actuator.

36 Use of feedback is optional.

Actuator A
A Internal Use Only

B Internal Use Only


PC Tool 1 Internal Use Only
Service Jack

2 Internal Use Only

3 Internal Use Only

Control Signal (+) Y ŏ /- Power Supply Com


24V AC/DC
Control Signal (-) ŏ1 ~/+ Power Supply Hot

N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.


Feedback Signal (+) U5 Address 33
Feedback

Feedback Signal (-) ŏ2 8 Internal Use Only


36
35 Adaption
Not Used - C1 9 Internal Use Only

Not Used - C2 10 Internal Use Only


Y1 Y2
SYx-24MFT

G PE

Actuator B
A Internal Use Only

B Internal Use Only


PC Tool 1 Internal Use Only
Service Jack

2 Internal Use Only

3 Internal Use Only

Control Signal (+) Y ŏ /- Power Supply Com


Control Signal 24V AC/DC
Control Signal (-) ~/+ Power Supply Hot
ŏ1

Feedback Signal (+) U5 Address 33


Feedback

Feedback Signal (-) 8 Internal Use Only


A 36
ŏ2
Adaption
LS3 35 Not Used - C1 9 Internal Use Only
B Not Used - C2 10 Internal Use Only
A-C (Open Indication) SYx-24MFT
Y1 Y2

C
D
LS4 G PE

E
D-F (Closed Indication)
F
Contact Rating: 5A 250 VAC Max.

SY2…5-24MFT

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


34
Wiring for Control Valves
Proportional, 120 or 230V
W552_1_11

Actuators: SY1-110P SY1-220P

Actuator B
G G Ground
Hazard Identification 120 or 230 VAC
Warnings and Cautions appear at appropriate N L1 4 Power Supply Com
sections throughout this manual. Read these carefully.
H L2 5 Power Supply Hot
CAUTION 6 Control Signal (-)
Indicates a potentially hazardous situation which, if 7 Control Signal (+)
not avoided, may result in minor or moderate injury.
35 8 Internal Use Only
It may also be used to alert against unsafe practices.
9 Internal Use Only
10 Internal Use Only
Indicates an action or condition that may cause
irreversible damage to the actuator(s) or 11 Feedback (-)
associated equipment. Feedback (B)
12 Feedback (+)
36
Equipment damage!
Power consumption and input impedance A LS3

must be observed. B
A-B (Open Indication)
C Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.
E LS4

F
INSTALLATION NOTES A-E (Closed Indication)

SY1 -110P (220P)


Observe class 1 and class 2 wiring restrictions.

Actuator A
G G Ground
APPLICATION NOTES
4 Power Supply Com
Recommended twisted shielded pair for control wiring.
35 5 Power Supply Hot
Ground shielded wire at control panel chassis.
Tape back ground at actuator. 6 Control Signal (-)
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.

Control Signal
36 Use of feedback is optional. 7 Control Signal (+)

35 8 Internal Use Only


9 Internal Use Only
NOTES SY1-110P (220P) 10 Internal Use Only
sCaution: Power supply voltage. 11 Feedback (-)
Feedback (A)
s$ONOTCHANGESENSITIVITYORDIPSWITCHSETTINGSWITH 12 Feedback (+)
power applied. 36
A LS3

B
A-B (Open Indication)
C Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.
E LS4

F A-E (Closed Indication)

SY1 -110P (220P)

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


35
Wiring for Control Valves
Proportional, Multiple Wiring, 120/230V
W552_2

Actuators: SY2...12-120MFT SY2...12-230MFT

Hazard Identification INSTALLATION NOTES


Warnings and Cautions appear at appropriate
sections throughout this manual. Read these carefully.
Observe class 1 and class 2 wiring restrictions.

CAUTION
Indicates a potentially hazardous situation which, if
not avoided, may result in minor or moderate injury. APPLICATION NOTES
It may also be used to alert against unsafe practices.
Recommended twisted shielded pair for control wiring.
35
Indicates an action or condition that may cause Ground shielded wire at control panel chassis.
irreversible damage to the actuator(s) or Tape back ground at actuator.
associated equipment. 36 Use of feedback is optional.

Equipment damage!
Power consumption and input impedance
must be observed. NOTES SY2...12-120MFT (230MFT)
sCaution: Power supply voltage.

Power Supply Com – 120 VAC (N) / 230 VAC (L1)


Power Supply Hot – 120 VAC (H) / 230 VAC (L2)

A Internal Use Only


N L
B Internal Use Only
PC Tool
Control Signal (+) Y Service Jack 1 Internal Use Only

Control Signal (-) ŏ1 2 Internal Use Only

Feedback Signal (+) U5 3 Internal Use Only


Feedback
Feedback Signal (-) ŏ2
36
Not Used - C1
35
Not Used - C2
Adaption Address

8 Internal Use Only

N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.


Y1
9 Internal Use Only
Y2
G PE SYx-120MFT
Actuator A 10 Internal Use Only
SYx-230MFT

Power Supply Com – 120 VAC (N) / 230 VAC (L1)


Power Supply Hot – 120 VAC (H) / 230 VAC (L2)

A Internal Use Only


N L
B Internal Use Only
PC Tool
Control Signal (+) Y Service Jack 1 Internal Use Only
Control Signal
Control Signal (-) ŏ1 2 Internal Use Only

Feedback Signal (+) U5 3 Internal Use Only


Feedback
Feedback Signal (-) ŏ2
36
Not Used - C1
35
A Not Used - C2
Adaption Address
LS3
B 8 Internal Use Only
A-C (Open Indication)
Y1 9 Internal Use Only
C SYx-120MFT
Y2

G PE Actuator B 10 Internal Use Only


SYx-230MFT
D
LS4
E
D-F (Closed Indication)
F
Contact Rating: 5A 250 VAC Max.

SY2...12-120MFT
SY2...12-230MFT

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


36
Wiring for Control Valves
On/Off, 24V, 120V

Actuators: ZONE 24NC ZONE24NO ZONE24NC-S ZONE24NO-S ZONE120NC ZONE120NO


ZONE120NC-S ZONE120NO-S

T-STAT
L1(HOT)
MOTOR
L2

24 120/230 Red Red


Motor Lead Color Black Black

TO AUXILIARY
CIRCUIT

Built-in Auxiliary Switch (optional) (-S models)


N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


37
Wiring Diagrams for Fire and Smoke Damper Actuators
W610_11

Actuators: FSLF120(-S) US FSLF24(-S) US FSNF120(-S) US FSNF24(-S) US FSAF120(-S) US


FSAF24(-S) US

Hazard Identification INSTALLATION NOTES


Warnings and Cautions appear at appropriate sections throughout 3 Actuators may also be powered by 24 VDC.
this manual. Read these carefully.
13 Two built-in auxiliary switches (2xSPDT), for end position
CAUTION indication, interlock control, fan startup, etc.
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to 21 Provide overload protection and disconnect as required.
alert against unsafe practices.
39 S4 makes to S6 when the actuator is powered open.
Equipment damage!
2 Actuators may be connected in parallel. Power consumption 40 Double insulated.
and input impedance must be observed. Two built-in auxiliary switches (2xSPST), for end position
41 indication, interlock control, fan startup, etc.
Equipment damage!
4 Actuators may be connected in parallel if not mechanically
linked. Power consumption and input impedance must
be observed.
24V 120V
Wht C N 1 Neutral
APPLICATION NOTES 21
Blk H L1 2 Hot
3 Ground
Meets cULus requirements without the need of an electrical
ground connection. No ground on 24 V models
FSNF24 US
2
FSNF120 US
All on this page indicates manual reset high
temperature limit or relay.
Auxiliary Switch Wiring for FSLF24-S US, FSLF120-S US

21 24V 120V
1 Common, Neutral Violet S1
C=Blk N=Wht

N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.


41
H=Red L1=Blk 2 Hot Violet S2
NC
10°
3 Ground
Gray S4

No ground for 24V models FSLF24 US


FSLF120 US 2 Gray S6
NO 85°
39 40
FSLF24-S US
FSLF120-S US

21 24 VAC Transformer Auxiliary Switch Wiring for FSNF24-S US, FSNF120-S US


Line Blk (1) Common
Volts Red (2) + Hot 3 S1
NC
S2 5°
FSAF24 US 4 13
All S3
NO
White
N N Wht (1) Neutral Tagged S4
21 NC
L1 H Blk (2) Hot S5
40 85°
120 VAC S6
NO
FSAF120 US 4 FSNF24-S
FSNF120-S

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


38
Wiring Diagrams for Fire and Smoke Damper Actuators
W611_11

Actuators: FSAF24-BAL (-S) US FSAF24-SR US

Auxiliary Switch Wiring for FSAF24-BAL-S US,


Hazard Identification FSAF24-SR-S US
Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.

CAUTION S1
NC
13
Indicates a potentially hazardous situation which, if not avoided, S2 10°
may result in minor or moderate injury. It may also be used to S3
40
alert against unsafe practices. NO

Equipment damage! S4
2 Actuators may be connected in parallel if not mechanically NC
S5
mounted to the same shaft. Power consumption and input 30° to 90°
impedance must be observed. S6
NO

Equipment damage! FSAF24-BAL-S US


4 Actuators may be connected in parallel if not mechanically FSAF24-SR-S US 2
linked. Power consumption and input impedance must
be observed. Balancing Control Fire and Smoke

APPLICATION NOTES 21 24 VAC Transformer

Line Blk (1) Common


Meets cULus or UL requirements without the need of an 3
electrical ground connection. Volts Red (2) + Hot

(3) Override Open


INSTALLATION NOTES
OVERRIDE CONTROL
37
See technical
3 Actuators may also be powered by 24 VDC. documentation for FSAF24-BAL 2
typical methods.
6 Only connect common neg (-) leg of control circuits.
A 500 Ω resister converts the 4 to 20 mA control signal to Proportional Control Fire and Smoke
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.

7
2 to 10 VDC.

Two built-in auxiliary switches (2xSPDT), for end position 21 24 VAC Transformer
13
indication, interlock control, fan startup, etc.
Line Blk (1) Common
3
21 Provide overload protection and disconnect as required. Volts Red (2) + Hot

37 Only connect Hot, Wire 2 to Wire 3 override controls. Wht (3) Y1 Input, 2 to 10V
(–)
40 Double Insulated Control Signal
2 to 10 VDC (+) Grn (5) U Output, 2 to 10V

All on this page indicates manual reset high FSAF24-SR US 2


temperature limit or relay.
21 24 VAC Transformer
Auxiliary Switch Wiring for FSAF24-S US, FSAF120-S US
Line Blk (1) Common
3
Volts Red (2) + Hot

Violet S1 Ω
NC (–) 500 Ω
Violet S2 41 4 to 20 mA
Control Signal (+)
Wht (3) Y1 Input, 2 to 10V
10°
7
Gray S4 (–)
NC
2 to 10 VDC Grn (5) U Output, 2 to 10V
Gray S6
(+)
Feedback Signal
NO 30 to 90°
6 FSAF24-SR US 2
FSAF24-S US
FSAF120-S US 4

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


39
Notes

N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


40
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc. Notes

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


41
Notes

N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


42
Belimo Platinum Distributors

ACR Supply Company Inc. G & O Thermal Supply Tower Equipment Co., Inc.
USA

4040 S. Alston Avenue 5435 N. Northwest Highway 1320 West Broad Street
Durham, NC 27713 Chicago, IL 60630 Stratford, CT 06615
Phone: 919-765-8081 Phone: 773-763-1300 Phone: 800-346-4647
With branches in NC With branches in IL Twinco Supply Corporation
Aireco Supply Industrial Controls Distributors LLC 55 Craven Street
9120 Washington Boulevard 1776 Bloomsbury Avenue Huntington Station, NY 11746-2143
Savage, MD 20763-0414 Wanamassa, NJ 07712 Phone: 800-794-3188
Phone: 301-953-8800 Phone: 800-631-2112 With branches in NY
With branches in MD, VA With branches in Wilson-Mohr, Inc.
GA, KY, IN, MA, ME, NC, NY, OH, PA, TN 12610 West Airport Blvd, Suite 100
Amcon Controls, Inc.
11906 Warfield Street Interstate HVAC Controls Sugarland, TX 77478
San Antonio,TX 78216 30 Vineland Street Phone: 281-295-8850
Phone: 210-349-6161 Brighton, MA 02135
Houston, TX branch 713-464-7002 Phone: 617-782-9000

CANADA
Mandeville, LA branch 985-624-3303 For a complete list of distributors
Jackson Controls in Canada, please visit our
Applied Automation 1708 E. 10th Street website: www.belimo.ca
A Wilson Mohr Company Indianapolis, IN 46201 or call toll free: 866-805-7089
3186 South Washington Street, #230 Phone: 317-231-2200
Salt Lake City, UT 84115 M & M Controls
Phone: 801-486-6454 9E West Aylesbury Road
Boston Aircontrols, Inc. Timonium, MD 21093 For a complete list of distributors

LATIN AMERICA AND THE CARIBBEAN


8 Blanchard Road Phone: 410-252-1221 in Latin America and the Caribbean,
Burlington, MA 01803 With a branch in Alexandria, VA please visit our website: www.belimo.us
Phone: 781-272-5800 MICONTROLS, Inc. or call: 203-791-8396
Charles D. Jones Co. 6516 5th Place South
445 Bryant Street, Unit #1 Seattle, WA 98124
Denver, CO 80204-4800 Phone: 800-877-8026
Phone: 800-777-0910 With branches in WA, OR
With branches in CO, MO, KS Meier Supply
Climatic Control Div/ICD 123 Brown Street
5061 W. State Street Johnson City, NY 13790
Milwaukee, WI 53208 Phone: 607-797-7700
Phone: 800-242-1656 With branches in NY, PA
With branches in WI Minvalco, Inc.
Cochrane Supply and Engineering, Inc. 3340 Gorham Avenue
30303 Stephenson Highway Minneapolis, MN 55426-4267
Madison Heights, MI 48071-1633 Phone: 952-920-0131
Phone: 800-482-4894 With branches in MN
With branches in MI and Maumee, OH RSD/Refrigeration Supply Distribution
Columbus Temperature Control 26021 Atlantic Ocean Drive
1053 E. 5th Avenue Lake Forest, CA 92630
Columbus, OH 43201 Phone: 949-380-7878
Phone: 800-837-1837 With branches in
CA, NV, OR, AK, AZ, ID, UT, WA, MT
Controlco
985 3rd Street Saint Louis Boiler Supply, Co.
Oakland, CA 94607 617 Hanley Industrial Court
Phone: 510-636-7900 St. Louis, MO 63144
With branches in CA, NV Phone: 314-962-9242
Control Products South Side Control Supply, Co.
9101 Jameel, Suite 130 488 N. Milwaukee Avenue
Houston, TX 77447 Chicago, IL 60610-3923
Phone: 713-849-7200 Phone: 312-226-4900
With branches in IL, IN
Edward C. Smyers & Co.
223 Fort Pitt Boulevard Stromquist and Company
Pittsburgh, PA 15222-1505 4620 Atlanta Road
Phone: 412-471-3222 Smyrna, GA 30080
Phone: 404-794-3440
Engineered Control Systems
With a branch in Orlando, FL
4805 N.W. 79th Avenue
Suite 11 Temperature Control Systems
Miami, FL 33166 10315 Brockwood Road
Phone: 305-418-8901 Dallas, TX 75238
With branches in FL Phone: 214-343-1444
With branches in OK, TX
Belimo worldwide: www.belimo.com
BELIMO Americas
USA Locations, 43 Old Ridgebury Road, Danbury, CT 06810
Tel. 800-543-9038, Fax 800-228-8283, marketing@us.belimo.com
1049 Fortunado Loop, Sparks, NV 89436
Tel. 800 987-9042, Fax 800-987-8875, marketing@us.belimo.com

Canada Locations, 14/16 – 5716 Coopers Avenue, Mississauga, Ontario L4Z 2E8
Tel. 866-805-7089, Fax 905-712-3124, marketing@us.belimo.com

Latin America and the Caribbean Customer Service,


Tel. 203-791-8396, Fax 203-791-9139, marketing@us.belimo.com

Vous aimerez peut-être aussi