Vous êtes sur la page 1sur 10

J Control Autom Electr Syst

DOI 10.1007/s40313-016-0229-3

Super-Twisting Sliding Control Design of Three-Phase Inverter


for Stand-Alone Distributed Generation Systems
Dinh Hieu Phan1,2 · Shoudao Huang1

Received: 11 September 2015 / Revised: 29 November 2015 / Accepted: 18 January 2016


© Brazilian Society for Automatics–SBA 2016

Abstract This paper presents a super-twisting algorithm advances in small generators, power electronics, and energy
control strategy for a three-phase voltage source inverter of storage devices (Strzelecki and Benysek 2008; Marwali et al.
a distributed generation system in the stand-alone operation 2004, 2007; Ahn et al. 2010; He and Li 2012; Delghavi
mode to guarantee good performance of the load output volt- and Yazdanli 2011). Among DGSs, those using renewable
age under a sudden load, unbalanced load, and nonlinear energy sources are gaining more and more attention because
load. The proposed control is established for an inner-loop they are environment friendly and utilize unlimited poten-
current controller and an outer-loop voltage controller in a tial energy sources (Liserre et al. 2010; Blaabjerg et al.
dual-control scheme. The proposed controller is very simple 2006). The DGSs operate in grid-connected applications or
and robust to the parameter uncertainties. The stability and in stand-alone applications (Islanded mode). Generally, they
robustness of the proposed controller are proven based on are connected to the utility grid to provide maximum electric
the Lyapunov theory. The simulation results are illustrated power to the grid. However, in some areas, such as remote
by MATLAB/Simulink software and are compared to the rural regions and remote islands, where the connection is
performance of the traditional sliding controller to validate very expensive and impractical, the stand-alone connection
the effectiveness of the proposed controller. option is better. In the stand-alone operation mode, the DGSs
can operate in parallel by connecting the distributed gen-
Keywords Super-twisting algorithm · Distributed eration (DG) units together, or each DG unit can operate
generation systems · Inner-loop current controller · independently. The parallel operation of multiple DG units
Outer-loop voltage controller · Parameter uncertainties · must ensure a good load sharing (real power sharing, reac-
Total harmonic distortion tive power sharing, harmonic power sharing) by regulating
real power and reactive power independently (Marwali et al.
2004; Ahn et al. 2010; Zhang et al. 2013). Meanwhile,
1 Introduction the independent operation of each DG unit must guarantee
the performances (fast transient response, small steady-state
Recently, the number of distributed generation systems error, low total harmonic distortion) of load voltage under
(DGSs) has been rapidly increasing because of their advan- various load types (sudden load change, unbalanced load,
tages compared to the conventional central generation sys- nonlinear load). This paper focuses on the independent oper-
tems, such as decreasing systems and fuel cost, complying ation of each DG unit in the stand-alone operation.
with stricter environment regulations, and technological To improve the load voltage performance, many
researchers have been working on designing voltage con-
B Dinh Hieu Phan trollers for three-phase voltage inverters. First, conventional
phandinhhieucdt@gmail.com
proportion–integral (PI) controllers were proposed (Teodor-
1 College of Electrical and Information Engineering, Hunan escu and Blaabjerg 2004; Haque et al. 2008). In Teodorescu
University, Changsha, Hunan, People’s Republic of China and Blaabjerg (2004), a PI controller for a single voltage con-
2 Faculty of Mechanical Engineering, Hanoi University trol loop was presented, but the performance of this controller
of Industry, Hanoi City, Vietnam is not applicable to a nonlinear load. A dual-loop controller

123
J Control Autom Electr Syst

scheme consisting of PI outer-loop voltage controller and PI of the traditional sliding mode control is the discontinuity
inner-loop current controller was used in Haque et al. (2008). of control variables, resulting in the variable switch fre-
It obtained a good performance with a balanced load, but quency of the inverter, thus the high chattering phenomenon
it was not satisfactory with a nonlinear load. To overcome (Martinez et al. 2012). To surmount this disadvantage, a
this drawback, the outer-loop voltage controller based on PI super-twist algorithm (STA) has been presented in many liter-
control and resonant control was adopted in Nian and Zeng ature sources (Beltran et al. 2009; Moreno and Osorio 2008;
(2011). It compensates for the low-order harmonic compo- Benelghali et al. 2011; Valenciaga and Puleston 2008). This
nents of load voltage and hence reduces the total harmonic of algorithm allows the synthesis of a continuous control action
load voltage. However, this method is not robust to parame- with discontinuous time derivative, and thus it significantly
ter uncertainties. Recently, various advance control methods reduces the chattering phenomenon.
have been proposed for output voltage controllers. In Kim and In this paper, the STA is proposed for the dual controller
Lee (2010), a feedback linearization control for a three-phase with a STA outer-loop voltage controller and a STA inner-
uninterruptible power supply (UPS) inverter was presented. loop current controller to improve the performance of the load
It showed a good performance of the load voltage under a voltage under various load types (sudden load change, unbal-
balanced load and nonlinear load, but it did not mention the anced load, and nonlinear load). The proposed controller
performance of the load voltage under an unbalanced load. inherits the well-known robustness of the sliding technique,
An extended Lyapunov function-based control strategy for so it can satisfactorily deal with the effects caused by the
UPS single-phase inverter was proposed by Komurcugil et al. variation of the parameters and the sudden load disturbance.
(2015). This controller eliminates the steady-state error with- The outstanding characteristic of the proposed controller is
out destroying the global stability of the system and obtains the continuous voltage actions which reduce the load volt-
good load voltage performance. However, this controller is age chattering, so it improves the quality of load voltage.
not designed for UPS three-phase inverter which is more Additionally, the STA controller is not complex, and thus
complex than UPS single-phase inverter. In Kim et al. (2015), turning parameters of the controller is easy and the com-
an observer-based optimal voltage control was adopted for putational burden of the controller is low. The stability of
three-phase inverter. The optimal controller based on mini- the proposed controller will be proved by using the Lya-
mizing the well-known linear quadratic regulator achieves punov functions. Finally, the simulation results are produced
excellent performance of the load voltage under various by MATLAB/Simulink software will be presented.
load operations. Nevertheless, the determination of weight- The remainder of this paper is organized as follows:
ing matrices is difficult. Sect. 2 presents a brief description and mathematical mode
A repetitive control was also proposed to control the load of a three-phase inverter. The proposed controller design are
voltage of UPS inverter in Escobar et al. (2007a, b). Nev- described in Sect. 3. The results of simulations are reported
ertheless, the problems of this controller are slow response in Sect. 4. Finally, the conclusion is drawn in Sect. 5.
and a lack of the systematic method to stabilize the error
dynamic. The good performance of the output voltage of
the three-phase UPS was obtained under an unbalanced load 2 System Description and Mathematical Model
and nonlinear load by using a dissipativity-based adaptive
controller in Valderrama et al. (2003). However, this con- A general structure of the DGS-based renewable energy
troller is too complicated to implement. In Jin et al. (2014), an source is shown in Fig. 1. As described in Fig. 1, the DGS
adaptive control strategy based on a proportional–derivative consists of three parts: input power, power conversion unit,
controller was presented in a stand-alone DGS under para- and local loads. The input power derived from renewable
meter uncertainties and various loads. The good performance energy sources, such as wind, fuel, and solar energy, is con-
was obtained, but the complex adaptive controller leads to the verted into the primal electric power by using a generator, fuel
high computational burden. To overcome the complex adap-
tive control methods above, traditional sliding mode control
Input power Power conversion unit Local load
methods have been proposed for UPS inverters (Tai and
Chen 2002; Kukrer et al. 2009; Komurcugil 2012). In Tai Wind energy Balanced load
and Chen (2002), the UPS inverter was designed by using AC
or Three
the discrete-time sliding mode control scheme. This method Solar energy DC phase
LC Unbalanced
load
filter
inverter
proved robust on low-output voltage distortion, but the exper- DC
Fuel cell Nonlinear load
iment results pointed out the high total harmonic distortion
(THD) of the load voltage under a nonlinear load. Although
the good performance of the load voltage is obtained, the con-
trol design is only for the single-phase inverter. The drawback Fig. 1 Block diagram of a stand-alone DGS

123
J Control Autom Electr Syst

Lf dVLd 1 1
Via iia VLa = wVLq − I Ld + Iid
Lf
dt Cf Cf
Vib iib VLb iLb
Vdc LOAD dVLq 1 1
Lf = −wVLd − I Lq + Iiq
Vic iic VLc iLc dt Cf Cf
Cf Cf Cf dIid 1 1
=− VLd + w Iiq + Vid
dt Lf Lf
dIiq 1 1
Balanced resistive load =− VLq − w Iid + Viq (2)
RL dt Lf Lf
A
B
C
where w is the angular frequency, VLd , VLq is the load d − q
Nonlinear load axis voltage, and I Ld , I Lq is the load d − q axis currents,
respectively.
D1 D3 D5
A Let us introduce the parameters of filter L f = k1 , C f =
B Cload
C Rload k2 . It is difficult to exactly determine those parameters, and
D2 D4 D6 thus they may be considered as variable parameters. It means
that k1 = k1n + k1 , k2 = k2n + k2 with k1n , k2n are
Fig. 2 Schematic diagram of three-phase inverter of stand-alone DGS
nominal parameters, while k1 andk2 are parameter uncer-
with LC filter tainties.
The Eq. (2) can be rewritten as
cells, and solar cells. The power conversion unit includes an dIid
AC–DC converter (wind turbines) or a DC–DC boost con- (k1n + k1 ) = −VLd + (k1n + k1 )w Iiq + Vid
dt
verter (fuel cells, solar cells), a three-phase DC–AC inverter, dIiq
and a LC output filter or a transformer. The output voltage (k1n + k1 ) = −VLq + (k1n + k1 )w Iid + Viq
dt
and the electric power delivered to the local loads through dVLd
the power converter unit can be regulated by the controllers (k2n + k2 ) = w(k2n + k2 )VLq − I Ld + Iid
dt
which improve the quality and reliability of renewable energy dVLq
sources. The local load consumes the electric power gener- (k2n + k2 ) = −w(k2n + k2 )VLd − I Lq + Iiq
dt
ated from generation sources. In this paper, the renewable (3)
resources, the AC–DC converter, or the DC–DC boost con-
verter can be replaced by a stiff DC voltage source. Moreover, From the Eq. (3), the mathematical model of inverter side
the transformer is ignored due to its high price and big size, can be expressed as
and the low load voltage required is without the help of the
transformer. dIid VLd Vid k1 dIid
Figure 2 describes a schematic diagram of a three-phase =− + w Iiq + + (w Iiq − )
dt k k1n k dt
DC–AC inverter with a LC filter in the stand-alone mode.  1n     1n  
f1 u1  f1
From Fig. 2, the mathematical mode of the inverter with the
dIiq VLq Viq k1 dIiq
LC filter can be expressed as =− + w Iid + − (w Iid + )
dt k k1n k dt
 1n     1n  
dVL 1 1 f2 u2  f2
= Ii − IL
dt Cf Cf dVLd Iid k2 dVLd I Ld
= −wVLq + + (wVLq − )−
dIi
=
1
Vi −
1 dt    k2n k2n dt k2n
VL (1) f
   
dt Lf Lf 3
u3  f3
dVLq Iiq k2 dVLq I Lq
where Vi is a vector output voltage of the inverter Vi = = −wVLd + − (wVLd + )−
dt    k2n k2n dt k2n
[via , vib , vic ]T , Ii is a vector current of the inverter Ii = f4    
[i ia , i ib , i ic ]T , VL denotes a vector load voltage VL = u4  f4
[v La , v Lb , v Lc ]T , I L denotes a vector load current I L = (4)
[i La , i Lb , i Lc ]T , L f , C f is the inductance and capacitor of
the filter, respectively. where functions f 1 , f 2 , f 3 , and f 4 represent the nomi-
The Eq. (1) placed in the stationary abc can be transformed nal model. Meanwhile, functions  f 1 ,  f 2 ,  f 3 , and  f 4
into the following equation in the synchronously rotating denote the uncertain model, and signals u 1 , u 2 , u 3 , and u 4
d − q reference frame are the control input variables.

123
J Control Autom Electr Syst

Lf
3 STA Controller Design
Lf
Vdc LOAD
The effects of the voltage controller play a major role. Gen- Lf
erally, load-side inverter of DG systems is used to regulate
the load voltage by keeping the constant voltage and constant Cf Cf Cf
frequency (CVCF) in the stand-alone operation, even under
sudden load, unbalanced load, and nonlinear load. Under the S1-S6 iiabc iLabc, VLabc
effect of the nonlinear load, the non-sinusoidal load current
with low-order harmonics components would be generated. a,b,c
SVPWM θ d,q
Moreover, unbalanced load would generate the negative VLdq
sequence components of load current. Due to the conse- Viαβ
I idq
quence of the harmonics and negative sequence components ,
I idqref I Ldq
existed in the load current, it deteriorates the load voltage d,q V
STA current
loop controller
STA voltage
loop controller
idq
quality of the three-phase inverter (non-sinusoidal output
VLdqref
voltage with existence of low-order harmonics components).
Thus, the operations of the loads are influenced, espe- Fig. 3 Block diagram of proposed STA controller
cially, for the power quality demands such as communication
systems, medical equipment, semiconductor manufacturing
systems, and data processing systems. The voltage controller
regulates the load voltage to ensure the good performance of
output voltage (sinusoidal voltage, quick response, and low
TDH) even if sudden load, unbalanced load, and nonlinear
load.

3.1 Control Design Fig. 4 Block diagram of proposed STA current loop controller

The STA control technique is used to design the controller.


The purpose of the controller design is to ensure the good per- Taking the time derivative of the sliding variables of the
formance of the load voltage under a sudden load, unbalanced Eq. (6) then incorporated with the Eq. (5) leads to
load, and nonlinear load. For this purpose, a dual controller
design which consists of an inner-loop current controller and s1 = −i idref + f 1 +  f 1 + u 1
an outer-loop voltage controller is proposed. Both the cur- s2 = −i iqref + f 2 +  f 2 + u 2 (7)
rent controller and the voltage controller are involved in the
STA methods. The block diagram of the STA controller for
three-phase inverter in stand-alone is depicted in Fig. 3. Moreover, each component of the action control variables
From Eq. (4), the current controller relates to the following consist of two terms
equation.
u i = u eqi + ũ i (8)
dIid
= f1 +  f1 + u 1
dt where u eqi (i = 1, 2) are the equivalent control terms for
dIiq the nominal and unperturbed model, and ũ i are the terms of
= f2 +  f2 + u 2 (5)
dt control variables designed by using the STA.
The expression for the equivalent control terms u eqi can
The sliding variables can be chosen as be determined as

s1 = i id − i idref u eq1 = I˙idref − f 1


s2 = i iq − i iqref (6) u eq2 = I˙iqref − f 2 (9)

where i idref , i iqref are the reference values of the output cur- Substitution of Eqs. (8) and (9) into Eq. (7) produces
rent of the three-phase inverter which denote as i idref =
u 3 , i iqref = u 4 . ṡi = ũ i +  f i (10)

123
J Control Autom Electr Syst

functions  f i are divided into two terms expressed as

 f i = g1i (s, t) + g2i (t) (11)

where functions g1i (s, t) = 0 when si = 0, and functions


g2i (t) are the perturbations on the 2-SM manifold. On the
other hand, the components of the control terms ũ i can be
given as Fig. 5 Block diagram of proposed STA voltage loop controller

t
Taking the time derivative of the sliding variables of the
ũ i = −k1i φ1i (si ) − k2i φ2i (si )dt (12)
Eq. (16) then incorporating with the Eq. (15) leads to
0

ṡ3 = −V̇Ldref + f 3 +  f 3 + u 3
where φ1i (si ) = |si |1/2 sign(si ) and
ṡ4 = −V̇Lqr e f + f 4 +  f 4 + u 4 (17)
1 
φ2i (si ) = sign(si ) = φ1i (si )φ1i (si )
2 Similar to the current controller design, each component of
the action control variables consists of two terms
 (s ) = 1 s −1/2
with φ1i i 2 i is the partial derivative of φ1i (si ) with
respect to si . Values k1i and k2i are the fixed-gains which are
u i = u eqi + ũ i (18)
determined by the following equation

k1i ≥ 2δ1i where u eqi (i = 3, 4) are the equivalent control terms for
the nominal and unperturbed model, and ũ i are the terms of
5δ1i k1i + 6δ2i + 4(δ1i + δ2i /k1i )2
k2i ≥ k1i (13) control variables designed by using the STA strategy.
2(k1i − 2δ1i ) The expression for the equivalent control terms u eqi can
be determined as
where δ1i , δ2i are the positive constants, are expressed by the
following equation
u eq3 = V̇Ldref − f 3
|g (s , t)| ≤ δ1i |si |1/2 u eq4 = V̇Lqr e f − f 4 (19)
 1i i 
d 
 g2i (t) ≤ δ2i (14)
 dt  Substitution of Eqs. (18) and (19) into Eq. (17) also becomes

The block diagram of the STA inner-loop current controller


ṡi = ũ i +  f i (20)
is presented in Fig. 4.
Next, the STA outer-loop voltage controller design is
related to the following equation The components of the control terms ũ i are the same com-
ponents of the control terms of Eqs. (12) and (13).
dVLd The block diagram of the STA outer-loop voltage con-
= f3 +  f3 + u 3 troller is presented in Fig. 5.
dt
dVLq
= f4 +  f4 + u 4 (15)
dt 3.2 Stability of the Control System
Similar to the design of the current controller, the sliding t
variables of the voltage controller can be chosen as Defining z i = − k2i φ2i (si )dt + g2i (t) as new states. The
0
closed-loop system Eqs. (10) and (18) with the STA control
s3 = VLd − VLdref law of Eq. (12) can be written as follows:
s4 = VLq − VLqr e f (16)
ṡi = −k1i φ1i (si ) + z i + g1i (s, t) (21)
where VLdref , VLqr e f are reference values of the load output dg2i (s, t)
voltage. ż i = −k2i φ2i (si ) + (22)
dt

123
J Control Autom Electr Syst

The Lyapunov function can be chosen as: Table 1 System parameters


Parameter Value

4
4
V = Vi = ςiT Pi ςi = ς1T P1 ς1 + ς2T P2 ς2 DGS rated power 450 VA
1 1 Dc link voltage 280 Vdc
+ ς3T P3 ς3 + ς4T P4 ς4 (23) Switching frequency 5 kHz
Load output voltages 110 V
where ςiT = [φ1i (si ), z i ] and Fundamental frequency 60 Hz

Filter capacitance 6.67 µF
1 4k2i + k1i
2 −k
1i
Pi = PiT = > 0, k1i , k2i > 0 Filter inductance 10 mH
2 −k1i 2

The time derivative of each term Vi can be calculated as


(Moreno and Osorio 2008). V̇ is the negative definite function Eq. (31) and V is the
positive definite function Eq. (23), and therefore V and tra-
1 jectories of the states Eqs. (21) and (22) converge to zero in
V̇i = − ςiT Q i ςi (24)
|si |1/2 the finite time.

where

4 Simulation Results
k1i 2k2i + k1i
2 − k1i
Qi =
2 −k1i 1
In this section, the simulations are performed by MAT-
1 1 LAB/Simulink to evaluate the proposed controller. The
V̇i = − 1/2 ςiT Q i ςi ≤ − 1/2 λm (Q i ) ςi 22 (25)
|si | |si | nominal parameters employed in these simulations are listed
in Table 1 (Jin et al. 2014). 50 % uncertain parameters are con-
where λm (Q i ) are minimum eigenvalues of matrix Q i , ςi 22 sidered for this system to demonstrate the robustness of the
represents the square of the 2-Euclidean norm determined as: proposed controller, namely 0.5k1n = k1 , 0.5k2n = k2 .
The gains of STA for the current loop control and the voltage
ςi 22 = φ1i
2
+ z i2 = |si | + z i2 (26) loop control can be determined

Additionally, the standard inequality for quadratic forms k11 = 224, k12 = 2500
λm (Pi ) ςi 22 ≤ Vi = ςiT Pi ςi ≤ λ M (Pi ) ςi 22 (27) k21 = 224, k22 = 2500
k31 = 0.75, k32 = 8.35
where λm (Pi ) and λ M (Pi ) are minimum and maximum k41 = 0.75, k42 = 8.35 (32)
eigenvalues of matrix Pi , respectively. From Eqs. (26) and
(27), the following inequalities can be expressed as: Simulations are implemented to illustrate the excellent per-
1/2 1/2 1/2
formance of the proposed the STA controller under following
Vi ≥ λm (Pi ) ςi 2 ≥ λm (Pi ) |si |1/2 (28) different cases
Vi Case 1 Sudden change balanced resistive load (load change
ςi 22 ≥ (29)
λ M (Pi ) 100–0 % and 0–100 %, RL = 80 ).
Case 2 Unbalanced resistive load (close phase A, RL =
From Eqs. (25), (28), and (29), the time derivative of Vi can 80 ).
be bounded as: Case 3 Nonlinear load (three-phase diode rectifier, Cload =
1/2 3300 µF, Rload = 500 ).
−λm (Pi )λm (Q i ) 1/2 1/2
V̇i ≤ Vi = −γi Vi (30) Case 4 Sudden change nonlinear load (load change 100–
λ M (Pi ) 0 % and 0–100 %, three-phase diode rectifier, Cload =
1/2 3300 µF, Rload = 500 ).
where γi = λm (P i )λm (Q i )
λ M (Pi ) > 0, which shows that V func- Figures 6, 7, 8, and 9 show the simulation results of the
tion is a strong Lyapunov function. Finally, the total time proposed controller under the aforementioned cases. Each
derivative of V is bounded as follows: figure illustrates the waveforms of the load voltage (VL ), the
inverter current (Ii ), and the load current (I L ), and the total

4
4
V̇ ≤ V̇i = −γi Vi ≤ 0 (31) harmonic distortion (THD) of the load voltage. In Figs. 6
1 1
and 7, a resistor of 80  is used for balanced load and unbal-

123
J Control Autom Electr Syst

200 200

VLabc (V)
VLabc (V)

0 0

-200 -200
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2

2 2

Iiabc (A)
Iiabc (A)

0 0

-2 -2
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2

2 2

ILabc (A)
ILabc (A)

0 0
-2 -2
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2

Time (s)
Time(s)
Fundamental (60Hz) = 155.6 , THD= 0.69%
-3
x 10 Fundamental (60Hz) = 155.6 , THD= 0.02%
0.3
8

Mag (% of Fundamental)
7 0.25
Mag (% of Fundamental)

6
0.2
5
0.15
4
0.1
3

2 0.05

1 0
0 100 200 300 400 500 600 700 800 900 1000
0
0 100 200 300 400 500 600 700 800 900 1000 Frequency (Hz)
Frequency (Hz)

Fig. 8 Simulation results of STA controller with 50 % variable para-


Fig. 6 Simulation results of STA controller with 50 % variable para- meters under Case 3
meters under Case 1
200
200
VLabc (V)
VLabc (V)

0
0

-200
-200 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
2
2
Iiabc (A)
Iiabc (A)

0
0
-2
-2
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
2
ILabc (A)

2
ILabc (A)

0
0
-2
-2
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2

Time (s) Time(s)


Fundamental (60Hz) = 155.9 , THD= 0.12%
0.1 Fundamental (60Hz) = 155.6 , THD= 0.69%
0.09
Mag (% of Fundamental)

0.3
0.08
Mag (% of Fundamental)

0.07 0.25

0.06
0.2
0.05
0.04 0.15
0.03
0.1
0.02
0.01 0.05
0
0 100 200 300 400 500 600 700 800 900 1000
0
Frequency (Hz) 0 100 200 300 400 500 600 700 800 900 1000
Frequency (Hz)

Fig. 7 Simulation results of STA controller with 50 % variable para-


meters under Case 2 Fig. 9 Simulation results of STA controller with 50 % variable para-
meters under Case 4

anced load. Figure 6 presents the transient performances of


the load voltage, the inverter current, and the load current. a load resistor of500  and 3300 µF load capacitor are used
The transient time is very quick (5 ms). The load voltage for nonlinear load. As can be seen, the waveforms of the
is only slightly distorted within the transient time. Despite load voltage keep the sinusoidal form with a slight distortion,
the unbalanced load (Fig. 7), the load voltage still demon- while the waveforms of the inverter current and the load cur-
strates a good performance. Meanwhile, the inverter current rent are relatively distorted. Their transient performances are
and the load current are both unbalanced. In Figs. 8 and 9, guaranteed regardless of the nonlinear sudden change load.

123
J Control Autom Electr Syst

200 200

VLabc (V)
VLabc (V)

0 0

-200 -200
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2

2 2

Iiabc (A)
Iiabc (A)

0 0

-2 -2
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2

2 2

ILabc (A)
ILabc (A)

0 0

-2 -2
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2

Time (s) Time (s)


Fundamental (60Hz) = 1.933 , THD= 0.79% Fundamental (60Hz) = 0.0002304 , THD= 1.67%

0.6
0.3
Mag (% of Fundamental)

Mag (% of Fundamental)
0.5
0.25

0.4
0.2

0.3
0.15

0.1 0.2

0.05 0.1

0 0
0 100 200 300 400 500 600 700 800 900 1000 0 100 200 300 400 500 600 700 800 900 1000

Frequency (Hz) Frequency (Hz)

200 200
VLabc (V)

VLabc (V)

0 0

-200 -200
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2

2 2
Iiabc (A)

Iiabc (A)

0 0
-2 -2
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2

2 2
ILabc (A)

ILabc (A)

0 0
-2 -2
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2

Time (s) Time (s)


Fundamental (60Hz) = 0.0001544 , THD= 0.92%
Fundamental (60Hz) = 0.0002304 , THD= 1.67%
0.3
0.6
Mag (% of Fundamental)

0.25
Mag (% of Fundamental)

0.5

0.2
0.4

0.15
0.3

0.1
0.2

0.05
0.1

0
0 100 200 300 400 500 600 700 800 900 1000 0
0 100 200 300 400 500 600 700 800 900 1000
Frequency (Hz)
Frequency (Hz)

Fig. 10 Simulation results of traditional sliding controller with 50 % variable parameters under all cases

Figure 10 describes the simulation results of a traditional It can be observed from Table 2 that the steady-state errors
sliding mode controller under the aforementioned cases. of the load voltage are smaller than 0.2 % and the THD of the
50 % of variable parameters are also considered for this con- load voltage are lower than 0.69 % in all cases. Meanwhile,
troller. The performances of the load voltage, the inverter Table 3 shows that the steady-state errors of the load voltage
current, and the load current are presented to compare with are smaller than 1.45 % and the THD of the load voltage are
the performances presented in Figs. 6, 7, 8 and 9. The steady- lower than 1.67 % in all cases. It obviously demonstrates that
state performances and the THD of the load voltage using the the STA controller is better than the traditional controller in
proposed STA controller and the traditional sliding controller this paper.
are listed in Tables 2 and 3, respectively.

123
J Control Autom Electr Syst

Table 2 Steady-state
Load types Load voltages (V) THD (%)
performance of simulation
results with proposed control VLa VLb VLc

Balanced resistive load 110.001 110 109.995 0.02


Unbalanced resistive load 110.22 110.08 109.78 0.12
Nonlinear load 110.01 110.005 109.995 0.69

Table 3 Steady-state performance of simulation results with traditional Delghavi, M. B., & Yazdanli, A. (2011). Islanded-mode control of elec-
sliding control tronically coupled distributed-resource units under unbalanced and
nonlinear load conditions. IEEE Transactions on Power Delivery,
Load types Load voltages (V) THD (%) 26(2), 661–673.
VLa VLb VLc Escobar, G., Mattavelli, P., Stankovic, A. M., Valdez, A. A., &
Leyva Ramos, J. (2007a). An adaptive control for UPS to com-
Balanced resistive load 109.4 109.2 108.9 0.79 pensate unbalance and harmonic distortion using a combined
Unbalanced resistive load 108.6 108.85 108.8 0.92 capacitor/load current sensing. IEEE Transactions on Industrial
Electronics, 54(2), 839–847.
Nonlinear load 109.5 109.3 109.1 1.67
Escobar, G., Valdez, A. A., Leyva Ramos, J., & Mattavelli, P. (2007b).
Repetitive-based controller for a UPS inverter to compensate
unbalance and harmonic distortion. IEEE Transactions on Indus-
5 Conclusions trial Electronics, 54(1), 504–510.
Haque, M. E., Muttaqi, K. M., & Negnevitsky, M. (2008). Control of
In this paper, a fixed-gain STA for the outer-loop voltage a stand alone variable speed wind turbine with a permanent mag-
controller and inner-loop current controller of a three-phase net synchronous generator. InPower and Energy Society General
Meeting—Conversion and Delivery of Electrical Energy in the 21st
inverter has been proposed to ensure the good performance of century (pp. 1–9).
the load voltage under various load conditions. The proposed He, J., & Li, Y. W. (2012). An enhanced microgrid load demand sharing
controller is not only simple for the parameter calculations strategy. IEEE Transactions on Power Electronics, 27(9), 3984–
of the controller, but is also robust to the system uncertain- 3995.
Jin, W. J., Vu, N. T., Dang, D. Q., Ton, D. D., & Choi, H. H. (2014).
ties. Besides, the stability of the proposed control system A three-phase inverter for a standalone distributed generation sys-
has been mathematically proven. The problem of the pro- tem: Adaptive voltage control design and stability analysis. IEEE
posed controller does not completely compensate for the Transactions on Energy Conversion, 29(1), 46–56.
harmonic distortion of the inverter current, thus the high Kim, D. E., & Lee, D. C. (2010). Feedback linearization control of
three-phase UPS inverter systems. IEEE Transactions on Indus-
THD of the inverter current exists under a nonlinear load. trial Electronics, 57(3), 963–968.
Finally, to prove clearly the advantages of the proposed Kim, E., Mwasilu, F., Choi, H. H., & Jung, J. W. (2015). An
controller, the simulations have been carried out through observer-based optimal voltage control scheme for three-Phase
MATLAB/Simulink software. The simulation results have UPS systems. IEEE Transactions on Industrial Electronics, 62(4),
2073–2081.
illustrated the superior performance of the proposed con- Komurcugil, H. (2012). Rotating sliding line based sliding mode control
troller compared with the performance of the traditional for single-phase UPS inverters. IEEE Transactions on Industrial
sliding controller. Electronics, 59(10), 3719–3726.
Komurcugil, H., Altin, N., Ozdemir, S., & Sefa, I. (2015). An extended
Lyapunov-function-based control strategy for single-phase UPS
inverters. IEEE Transactions on Power Electronics, 30(7), 3976–
References 3983.
Kukrer, O., Komurcugil, H., & Doganalp, A. (2009). A three-level
Ahn, S. J., Park, J. W., Kang, S. H., & Nam, S. R. (2010). Power- hysteresis function approach to the sliding-mode control of single-
sharing method of multiple distributed generators considering phase UPS inverters. IEEE Transactions on Industrial Electronics,
control modes and configurations of a microgrid. IEEE Transac- 56(9), 3477–3486.
tions on Power Delivery, 25(3), 2007–2016. Liserre, M., Sauter, T., & Hung, J. Y. (2010). Future energy systems:
Beltran, B., Ahmed-Ali, T., & Benbouzid, M. (2009). High-order Integrating renewable energy sources into the smart power grid
sliding-mode control of variable-speed wind turbines. IEEE Trans- through industrial electronics. IEEE Industrial Electronics Maga-
actions on Industrial Electronics, 56(9), 3314–3321. zine, 4(1), 18–37.
Benelghali, S., Benbouzid, M., Charpentier, J., Ahmed-Ali, T., & Martinez, M. I., Tapia, G., Susperregui, A., & Camblong, H. (2012).
Munteanu, I. (2011). Experimental validation of a marine current Sliding-mode control for DFIG rotor and grid-side converters
turbine simulator: Application to a permanent magnet synchro- under unbalanced and harmonically distorted grid voltage. IEEE
nous generator-based system second-order sliding mode control. Transactions on Energy Conversion, 27(2), 328–338.
IEEE Transactions on Industrial Electronics, 58(1), 118–126. Marwali, M. N., Jung, J. W., & Keyhani, A. (2007). Stability analysis
Blaabjerg, F., Teodorescu, R., Liserre, M., & Timbus, A. V. (2006). of load sharing control for distributed generation systems. IEEE
Overview of control and grid synchronization for distributed power Transactions on Energy Conversion, 22(3), 737–745.
generation systems. IEEE Transactions on Industrial Electronics,
53(5), 1398–1409.

123
J Control Autom Electr Syst

Marwali, M. N., Jung, J. W., & Keyhani, A. (2004). Control of dis- Valderrama, G. E., Stankovic, A. M., & Mattavelli, P. (2003).
tributed generation system—part II: Load sharing control. IEEE Dissipativity-based adaptive and robust control of UPS in unbal-
Transactions on Power Electronics, 19(6), 1551–1561. anced operation. IEEE Transactions on Power Electronics, 18(4),
Moreno, J. A., & Osorio, M. (2008). A Lyapunov approach to second- 1056–1062.
order sliding mode controllers and observers. In Proceedings of Valenciaga, F., & Puleston, P. F. (2008). High-order sliding control for
the 47th IEEE conference on decision and control, Cacun (pp. a wind energy conversion system based on a permanent magnet
2856–2861). synchronous generator. IEEE Transactions on Energy Conversion,
Nian, H., & Zeng, R. (2011). Improved control strategy for stand-alone 23(3), 860–867.
distributed generation system under unbalanced and non-linear Zhang, Y., Yu, M., Liu, F., & Kang, Y. (2013). Instantaneous current-
loads. IET Renewable Power Generation, 5(5), 323–331. sharing control strategy for parallel operation of UPS modules
Strzelecki, R., & Benysek, G. (2008). Power electronics in smart elec- using virtual impedance. IEEE Transactions on Power Electronics,
trical energy networks. In Integration of distribution generation 28(1), 432–440.
with electrical power system (pp. 203–206). Berlin: Springer.
Tai, T. L., & Chen, J. S. (2002). UPS inverter design using discrete-time
sliding-mode control scheme. IEEE Transactions on Industrial
Electronics, 49(1), 67–75.
Teodorescu, R., & Blaabjerg, F. (2004). Flexible control of small wind
turbines with grid failure detection operating in stand-alone and
grid-connected mode. IEEE Transactions on Power Electronics,
23(3), 1323–1332.

123

Vous aimerez peut-être aussi