Vous êtes sur la page 1sur 14

Guide to the Design of Anchor Bolts

and Other Steel EI11bedments


by R. W. Cannon. D. A. Godfrey. and F. L. Moreadith

Preface AI loaded area, sq in.


There has been little published on the design of steel Az maximum area of the portion of the supporting
embedments. Many designers looking for guidance have surface that is geometrically similar to and
found the work of ACI Committee 349, Concrete Nuclear concentric with loaded area, sq in.
Structures, extremely helpful. Because there may be de- b dimension, out to out of bearing edges (see
signers who are not aware of this information, which is an Fig. 5-2), in.
appendix to the Code prepared by Committee 349, a mod- D major thread diameter of threaded anchor or
ified version is offered here which can be applied outside nominal diameter of anchor, in.
the design of nuclear structures. f; specified compressive strength of concrete, psi
Appendix B, "Steel Embedments" of "Code Require- f ut minimum specified tensile strength of anchol
ments for Nuclear Safety Related Concrete Structures (ACI steel, psi
349-76)" was adopted by the American Concrete Institute !y mInlmUm specified yield strength of embed-
in August 1979. The authors of this article were principal ment steel, psi
authors of Appendix B. The appendix was ballotted and
revised extensively several times before being accepted by h overall thickness of member, in.
ACI Committee 349. Additionally, the document was ex- Ld embedment depth for tensile anchorage mea-
tensively reviewed by the ACI Technical Activities Com- sured from anchorage bearing surface to con-
mittee (TAC). Following revision and ballotting by ACI 349 crete surface, in.
and further review by TAC, the document was accepted for
ballotting by the general membership of the Institute and m minimum side cover distance from the center
published in the August 1978 ACI JOURNAL Proceedings of of an anchor to the edge of the concrete (see
the American Concrete Institute. It was adopted as part of Fig. 5-1), in.
the Code in June 1979. n number of threads per in.
Appendix B is, for the most part, directly applicable to
concrete structures in general, not only to nuclear safety Pd design pullout strength of concrete in tension,
related structures. The parts of this article presented in lb
italic-type represents modifications which the authors feel U required strength to resist factored loads or
transform Appendix B into a general guide for designing related internal moments and forces
steel embedments. For the most part, the changes fall into
one of three categories: ~ strength reduction factor, dimensionless
1. 1980 proposed revisions to Appendix B.
2. Deleting references to ACI 349-76 and inserting ref-
erences to ACI 318-77. 2.0 - Scope
3. Technical changes which the authors feel constitute an
improvement in the content of Appendix B. 2.1 - This guide provides minimum requirements
It is important to emphasize that the regular-type por- for design and anchorage of steel embedments used
tions of this article have been subjected to a rigorous eval- to transmit loads from attachments into reinforced
uation by ACI Committee 349, TAC, and the general mem-
bership of the Institute. concrete structures by means of tension, bearing,
This guide defines minimum requirements for design of shear, friction, or any combination permitted by this
steel embedments used to transmit loads from attachments guide.
into reinforced concrete structures. Loads may be trans-
mitted into structures by means of tension, bearing, shear, Typical embedment details and concepts as refer-
friction, or any combination thereof. The design limits have enced in this guide are shown in Fig. 2-1 and 2-2.
been established using both analytical and test methods.
The commentary provides background information on the In addition to meeting these requirements consid-
provisions. eration shall be given to the effect of the forces ap-
plied to the embedment on the behavior of the overall
Keyword8: anchorage (structural); anchor bolts, anchors (fas-
teners); building codes; composite construction (concrete and steel); structure.
embedment; grouting; inserts; loads (forces); reinforced concrete; 2.2 - The requirements for the attachment to the
shear properties; structural design; studs.
embedment shall be in accordance with applicable
1.0 - Notation
codes and are beyond the scope of this guide.
2.3 - Design limits less conservative than those
a dimension out to out of bearing edges (see Fig. specified in this guide may be used by the engineer
5-2), in. if substantiated by experimental or detailed analyti-
reduction in projected area, sq in. cal investigation.

28 CONCRETE INTERNATIONAL/JULY 1981


BOUNDARY Of
STE:(L EMBEDMENT

SHEAR EMBEDMENTS

EMSEDMENTS

~(OMPR[5SI0N
.- \1EMB[R
-p
'>'NC.HC>R~ c

BOUNDARY CK
Sn:EL EMBEDMENT
HEAOc ccc~' f---~--I f-==...,.....--'-~~

Fig. 2-1 - Bearing embedments - Typical embed-


ment details.
3.0 - Definitions
. •,~. fJ'" ~ .~.
_ _ _B=-O:..::U.:::.;N=-DA",R=Y:..:O.::.F:.:=.:........_ _
..- STEEc. EMBD'.:[i iT
Anchor head - A nut, washer, plate, stud, or bolt
head or other steel component used to transmit an- TYPE B
chor loads to the concrete by bearing.
Attachment - The attachment is that structure Fig. 2-2 - Tension embedments - Typical embed-
ment details.
external to the surfaces of the embedment which
transmits loads to the embedment.
Embedment - The embedment is that steel com- 4.2 - Reactions on the embedment due to individ-
ponent in contact with the concrete or grout used to ual loads such as dead, live (including vibratory
transmit applied loads to the concrete structures. The loads), thermal and seismic, loads shall be considered.
embedment may be fabricated of plates, shapes, The loading combinations for embedment design shall
bolts, reinforcing bars, shear connectors, expansion be in accordance with Section 9.2 of ACI 318-77.
anchors, inserts, or any combination thereof. 4.3 - Material and testing requirements for
Expansion anchor - A component installed in embedment steel shall be specified by the engineer
hardened concrete for the transfer of loads into struc- to ensure that the intended function of the embed-
tural components by direct bearing and/or friction. ment and the attachment is compatible.
Grouted embedment - An embedment located in 4.4 - The strength of embedments as affected by
a formed or drilled hole in hardened concrete utilizing the size and grade of steel, spacing, and depth of
a grout to provide load transfer from the embedment embedment and any concrete dimensions which limit
to the concrete. or restrict the transfer of loads from steel to concrete
Inserts - Commercially available, predesigned, shall be considered as defined in Sections 5.0, 6.0, and
and prefabricated embedments installed prior to con- 7.0.
crete placement which are specifically designed for 4.5 - Shear lugs that meet the requirements of
attachment of bolted connections. Sections 5.5 and 6.1.2(b) shall be considered effective
only when located in a concrete compression zone
4.0 - General requirements and loading developed between the embedment and the concrete
combinations and transverse to the direction of the shear force for
4.1 - The embedment and surrounding concrete a given load combination unless adequate reinforce-
or grout shall be designed for transmitting to the con- ment is provided.
crete structure all loads used in the design of the at- 4.6 - A combination of bearing and shear friction
tachment. mechanisms shall not be used to develop the required
CONCRETE INTERNATIONAL/JULY 1981 29
5.2 - Tension - The design pullout strength of
concrete P d for any anchorage shall be based on a
uniform tensile stress of 4~ VI: acting on an effective
stress area which is defined'!:ly the projected area of
stress cones radiating toward the attachment from
the bearing edge of the anchotfi'; The effective area
is limited by overlapping stress cones, by the inter-
section of the cones with concrete surfaces, by the
bearing area of anchor heads, and by the overall
thickness of the concrete (see Fig. 5-1 and 5-2). The
".REJUCE BY THE TOTAL
inclination angle for calculating projected areas shall
be 45 deg. The ~ factor shall be taken as 0.65 for an
embedded anchor head unless the anchor head is be-
yond the far face reinforcement. In such cases a ~
factor of 0.85 may be used.
5.3 - Shear - The design shear strength of an-
chors subject to shear shall satisfy the requirements
of Sections 6.1.2 and 7.2.2.
5.4 - Reinforcement - If the requirements of Sec-
tion 6.1 are not satisfied, reinforcement shall be pro-
vided to develop the required strength. Reinforce·
ment requirements shall be in accordance with
applicable sections of ACI 318-77 and placed to pre-
Fig. 5-1 Effective stress area for anchorage pull-
out. vent failure of the concrete in tension.

5.5 - Bearing
5.5.1 - The bearing requirements of Sections 10.16
or 18.13 of ACI 318-77 shall apply to the maximum
bearing stress at a shear lug or anchor head except
as permitted by Section 5.5.2.
5.5.2 - The bearing requirements of Section 5.5.1
do not have to be met if the anchor head at the base
of the tensile stress component satisfies the following
conditions:
(a) The bearing area of the anchor head (excluding the
area of the tensile stress component) is at least 1.5
times the area of the tensile stress component.
(b) The thickness of the anchor head is at least 1.0
times the greatest dimension from the outer most
bearing edge of the anchor head to the face of the
tensile stress component.
(c) The bearing area of the anchor head is approxi-
mately evenly distributed around the perimeter of
the tensile stress component.

6.0 - Anchorage requirements


6.1 - Anchorage design shall be controlled by the
strength of embedment steel unless otherwise spec-
ified in this guide.
Fig. 5-2 - Stress area reduction for limited depth A,. 6.1.1 - Tension. Steel strength controls when the
design pullout strength of the concrete Pd as deter-
shear strength defined in accordance with Section 9.2 mined in Section 5.2 exceeds the minimum specified
of ACI 318-77. tensile strength of the tensile stress component of the
embedment steel and full load transfer is accom-
5.0 - Design requirements for concrete plished from steel to concrete within the depth of the
5.1 - The design provisions of this guide are based anchorage by one of the following methods:
on the strength design method. The assumptions, (a) A mechanical anchor at the base of the tensile
principles, and requirements of ACI 318-77 are ap- stress components which satisfies the requirements
plicable for all load combinations except as modified of Section 5.5.2. To prevent failure due to lateral
herein. bursting forces at an anchor head, the side cover dis-

80 CONCRETE INTERNATIONAL/JULY 1981


tance m shall be determined such that the lateral con- (a) 0.9 for concrete or grout against as-rolled steel
crete design strength (based on a uniform tensile with the contact plane a full plate thickness below the
stress of 4~ VI: acting on an effective area defined concrete surface.
by projecting 45 deg planes from the anchor head to (b) 0.7 for concrete or grout against as-rolled steel
the free surface) exceeds the lateral bursting force with contact plane coincidental with the concrete sur-
unless the requirements of Section 5.4 are met. The face.
~ factor shall be taken as 0.85. (c) 0.55 for grouted conditions with the contact
(b) Reinforcing bars with development lengths in plane between grout and as-rolled steel exterior to
accordance with the requirements of Chapter 12 of the concrete surface.
ACI318-77, for anchor steel composed of reinforce-
ment. 7.3 - Combined tension and shear
7.3.1 - For structural shapes and fabricated steel
6.1.2 - Shear. For steel strength to control the sections, the web shall be designed for the shear and
design shear strength: (a) For anchor bolts, studs, or the flanges designed for the tension, compression,
bars the side cover distance m for shear loading to- and bending.
ward a free edge shall be such that the concrete de- 7.3.2 - For bolts, studs, and bars the area of steel
sign strength (based on a uniform tensile stress of required for tension by Section 7.2.1 and for shear by
4~ VI: acting on an effective area defined by project- Section 7.2.2.2 shall be additive.
ing 45 deg planes to the free surface from the cen- 7.4 - The tensile stress area of a threaded anchor
terline of the anchor at the shearing plane) exceeds shall be taken as:
the ultimate shear strength of the bolts, studs, or 2

bars (based on fu ,) unless the requirements of Section [ 0.9743


0.7854 D - -n- ]
5.4 are met. The ~ factor shall be taken as 0.85.
(b) For shear lugs bearing in the direction of a free where D is the, major thread diameter and n is the
edge, the concrete design shear strength shall be de- number of threads per in.
termined based on a uniform tensile stress of 4~ VI: 7.5 - The tensile stress area of Section 7.4 shall
_acting on an effective stress area defined by pro-
be applied to all threaded anchors subject to direct
jecting 45 deg planes from the bearing edges of the
tensile and shear stress.
shear lug to the free surface and shall exceed the
ultimate shear strength of the steel (based on fu,) un- B.O - Expansion anchors
less the requirements of Section 5.4 are met. Bearing
This section provides minimum requirements for
area of the shear lug shall be excluded from the pro-
the design of typical expansion anchors used in con-
jected area. The ~ factor shall be taken as 0.85.
crete structures and does not restrict the use of other
6.1.3 - For combined tension and shear, the depth
expansion anchors provided the expansion anchors
of embedment shall be in accordance with Section
are designed and tested in accordance with the re-
6.1.1 and the minimum edge distance in accordance
quirements of this section.
with Section 6.1.2(a).
6.1.4 - Where reinforcement is provided in ac- 8.1 - Design requirements - Expansion anchors
cordance with Section 5.4, the side cover distance shall be designed to assure that the design strength
shall not be less than 1fa that required by Section of concrete for a given expansion anchor or group of
6.1.2. Under no conditions should the edge distance expansion anchors is greater than the strength of the
be less than the concrete cover requirements for re- anchor steel except as permitted in Section 8.2. This
inforcement in Section 7.7 of ACI 318-77. requirement shall be met by satisfying the require-
ments of Sections 8.1.1 or 8.1.2.
1.11 - Design requirements for embedment steel
7.1 - Embedment material shall be defined by the B.1.1 - Design by analysis
Engineer in contract documents. (a) Tension: The design pullout strength of concrete
7.2 - The design strength for embedments shall P d shall be as defined in Section 5.2 except that the
be based on a maximum steel stress of ~ fy or ~ (0.8 effective stress area shall be defined by the projected
i u ,), whichever is less. The design yield strength iy area of the stress cones radiating toward the concrete
shall not exceed 120,000 psi. The following values for surface from the innermost expansion contact surface
~ shall be used: between the expansion anchor and the drilled hole.
7.2.1 - Tension, compression, and bending. ~ = 0.9. Refer to Fig. 8-1 for typical details. The design pull-
7.2.2 - Shear out strength of concrete shall be equal to or greater
7.2.2.1 - Structural shapes and fabricated steel than the minimum specified tensile strength or av-
sections and shear lugs. ~ = 0.55. erage tensile strength if a minimum is not defined for
7.2.2.2 - The shear-friction provisions of Section the expansion anchor. The minimum edge distance
_ 11.7 of ACI 318-77 (as herein modified) shall be ap- requirement of Section 6.1.1(a) shall be satisfied.
plied to bolts, studs, and bars using a ~ of 0.85. The (b) Shear: Expansion anchors subject to shear shall
coefficient of friction J.I shall be: meet the requirements of Section 6.1.2(a).
CONCRETE INTERNATION~/JULY 1981 31
to determine the average test failure load. Tests shall
be conducted by a testing agency other than the an-
chor manufacturer and shall be certified by a profes-
sional engineer with full description and details of the
testing program, procedures, results, and conclu-
sions.
8.4.2 - The expansion mechanism of the anchor
shall be tested for the installed condition by one of
the following methods:
(a) The mechanism shall be actuated and tested
during installation by preloading the expansion an-
chor to a minimum value as specified by the engineer.
(b) A random selection of the installed anchors shall
be load tested to a minimum of 100 percent of the
required strength. The testing program shall be es-
tablished by the engineer.
8.5 - Expansion anchor selection - The engineer
shall review the expansion anchor design features,
failure modes, test results, and installation proce-
dures prior to selecting a specific expansion anchor
for an application. Expansion anchors shall not be
used to resist vibratory loads in tension zones of con-
crete members unless tests are conducted to verify
the adequacy of the specific anchor and application.
9.0 - Inserts
Concrete inserts shall be specified in accordance
Fig. 8-1 - Typical details of expansion anchors. with Section 7.1 and tested in accordance with Sec-
tion 8.4.1.
(c) For combined tension and shear, the depth of
embedment shall be in accordance with Section 9.1 - Design requirements - When inserts cannot
8.1.1(a) and the minimum edge distance in accordance be designed to meet the requirements of Sections 5.0,
with Section 8.1.1(b). 6.0 and, 7.0, the design strength shall be based on
(d) The design requirements for embedment steel actual test data of tests performed on inserts embed-
shall be in accordance with Section 7.0. ded in concrete. The tests shall cover the full range
8.1.2 Design by testing. Tests shall be conducted of possible loading conditions.
to verify that the concrete will develop the steel
strength of the expansion anchors. Design by test 9.2 - Strength reduction factor - When inserts
results shall be restricted to tests that are represen- cannot be designed to meet the requirements of Sec-
tative of the anchor spacing and load application. +
tions 5.0, 6.0, and 7.0, a factor of 0.5 shall be applied
8.1.S Strength reduction factors. The requirements to the average test failure loads in determining the
+
of Section 7.1 shall apply except that the factors for design strength.
expansion anchors shall be 0.9 times the values spec-
ified in Section 7.2. 10.0 - 6routed embedmenD
8.2 - Alternative design requirements - For ex- 10.1 - Grouted embedments shall meet the appli-
pansion anchors that do not meet the requirement of cable requirements of Sections 5.0, 6.0, and 7.0.
Section 8.1, the design strength shall be 0.35 times 10.2 - For general grouting purposes the material
the average test failure load. This factor applies to requirements for cement grout shall be in accordance
tension and shear test failure loads. The average test with Chapter 3 of ACI 318-77. Special grouts used to
failure load shall be equal to the average of the test achieve certain properties such as high strength, low
loads carried by test anchors at failure (maximum shrinkage, or expansion shall be the responsibility of
load) or at a magnitude of displacement of test an- the engineer and specified in contract documents.
chors as specified by the engineer. A linear interac- 10.3 - Grouted embedments shall be tested to ver-
tion shall be used for combined tension and shear. ify anchorage strength. Grouted embedments in-
8.3 - A single expansion anchor used to anchor an stalled in tension zones of concrete members shall be
attachment shall be designed for 1/2 of the design capable of sustaining design strength in cracked con-
strength defined herein. crete. Tests shall be conducted by an independent
8.4 - Testing testing agency and shall be certified by a professional
8.4.1 - Expansion anchors designed in accordance engineer with full description and details of the test-
with the guide shall be tested to verify anchorage or ing programs, procedures, results, and conclusions.
82 CONCRETE INTERNATIONAL/JULY 1981
10.4 - Grouted embedments shall be tested for the transfer through the grout is by direct bearing or
installed condition by testing randomly selected compression.
grouted embedments to a minimum of 100 percent of
the required strength. The testing program shall be 11.0 - Fabrieatlon and instaDation
established by the engineer. Welding of attachments to embedments shall be in
10.5 - The tests required by Sections 10.3 and 10.4 accordance with good practice to avoid excessive ex·
may be waived by the engineer if tests and installa- pansion of the embedment which could result in det-
tion data are available to ensure that the grouted rimental spalling or cracking of the concrete or ex-
embedment will function as designed or if the load cessive stress in the embedment anchors.

Commentary on Guide to the Design of Anchor


Bolts and Other Steel Embedments
I.O-Notation 4.O-General requirements and loading
In addition to the notation provided in Section 1.0, eombinations
the notation used in this guide is the same as in ACI The requirements of this section reference other
318-77. sections of the guide and ACI 318-77. The engineer,
using the applicable requirements of the referenced
2.9-Seope section, is responsible for the design of an embed-
ment which is compatible with the material, design
This guide provides minimum requirements for the
loads, and function of the attachment and the sup-
design of steel embedments used to transmit loads
porting structure.
from attachments into the reinforced concrete struc-
Sections 4.1 and 4.2 require that the engineer co-
tures governed by ACI 318-77.
ordinate the design of the attachment with the design
Design limits have been established using both an-
of the embedment and surrounding concrete and that
alytical and test methods. Analytically, limits on ca-
the embedment be designed for the load combinations
pacity for both concrete and steel have been estab-
of Section 9.2 of ACI 318-77 as a minimum. It is sug-
lished which are consistent with accepted ACI and
gested that special consideration be given to embed-
AISC practice. Where design limits have been estab-
ments designed for vibratory loads (e.g., increased
lished through test programs, test results have been
load factor).
published or are available from the original source. l -3
The variation in type of loading coupled with the
Tests have been performed on steel embedments to
determine the limiting ioad capabilities and anchor- various loading combinations result in a wide range
of design problems for the embedment designer.
age requirements for fabricated anchorages, concrete
Also, a wide range of material for embedments is
inserts, anchor bolts, welded studs, and expansion
anchors subject to loads applied in direct tension and available which restricts Section 4.3 from being more
shear. The effect of edge conditions, strength of con- explicit. From a practical point of view as well as
crete, size, strength, number, and spacing of anchors from an economic standpoint, it must be the respon-
was investigated. Typical arrangements and geome- sibility of the engineer to select appropriate materials
try of steel embedments are as reflected in the fig- for embedments and specify testing, if necessary, for
u~es of the guide, commentary, and references.
each class of embedments (as implied by Section 4.3)
Although typical embedment details and concepts which will ensure that the intended function of the
are referenced in Section 2.1, this does not preclude attachment is not impaired.
the use of other details of concepts to which the pro- Section 4.5 places limitations on shear lugs which
visions of this guide and ACI 318-77 are applicable. do not satisfy the requirements of Section 6.0, i.e.,
Various methods of joining the attachment to the that the embedment exhibit ductile behavior if sub-
embedment may be used, a few of which are shown jected to overload. The engineer is cautioned that
in figures which are a part of the guide. Section 2.2 shear lugs, even though located in the specified
specifies that the design of attachments is not a part compression zone, may not be fully effective if edge
of the guide; however, proper consideration should be distance between the lug bearing surface and free
given to their design to ensure compatibility with surface of the concrete is limited. The requirements
assumptions made in the design of the embedment. of Section 5.4 must be satisfied when those of Section
6.1.2(b) are not.
Although specific requirements are not given in the
3.9-Definitions guide, the engineer must ensure that the stiffness
In addition to the definitions provided in Section characteristics of the shear lugs are compatible with
3.0, the definition of other terms used in the guide the assumed bearing stress distribution between the
are the same as those in ACI 318-77. lugs and the concrete.
CONCRETE INTERNATIONAL/JULY 1981 ss
are excessive. For uniformly sized and spaced bar
deformations, the tensile stress in the steel varies
from a maximum at the surface of the concrete to
zero at the end of the bar as illustrated in Fig. 1. For
embedment lengths equal to the ld of Section 12.2, the
failure mode would be rupture of the steel at its ul-
timate tensile strength. Typically, complete failure is
preceded by developing a shallow surface cone (see
Fig. 1) when the bar reaches yield. This preliminary
distress occurs typically because the bar deforma-
tions along the embedded portion of the reinforce-
ment are trying to participate equally in the load
transfer from the bar to the concrete. Using the ld
values of Section 12.2 is conservative. However,
these requirements are specified in Section 6.1.1(b)
of the guide due to the lack of available data neces-
sary to reduce the embedment requirements.
A single mechanical anchor (e.g., head of an anchor
Fig. 1 - Load transfer behavior of deformed rein- bolt or stud) at the end of a smooth bar or rod be-
forcement. haves differently than deformed reinforcement. As
tensile load is increased, bond failure will occur such
that the entire tensile load is transferred into the
Section 4.6 prohibits the engineer from combining concrete by the anchor head. If the depth of embed-
the design shear strength of bearing (e.g., shear lugs) ment is less than that required to develop the ulti-
and shear friction (e.g., shear studs) mechanisms. mate tensile strength of the bar or rod concrete ten-
This exclusion is justified in that it is difficult to pre- sile failure will occur with initial cracking beginning
dict the distribution of shear resistance as a result of around the perimeter of the anchor head. A "pullout
the differential stiffness of the two mechanisms. cone failure" results as the cracking propagates to
the surface.
5.O-Design requirements for eonerete
The basic requirements for the development of 5.1-The combined requirements of Sections 5.0
embedments in reinforced concrete are provided by and 6.0 are intended to result in an embedment de-
Sections 5.0 and 6.0. The transfer of tensile stress sign which will exhibit ductile behavior in the case
from steel to concrete using deformed reinforcement of unanticipated overload. This philosophy is consis-
or headed anchors is accomplished by mechanical tent with the code in that sudden brittle failure is an
means if the location of the load transfer mechanism undesirable failure mode.
(either bar deformations or anchor heads) is in close Section 5.1 requires the designer to be cognizant
proximity to one or more concrete surfaces, tensile of satisfying applicable general requirements of the
cracking of the concrete will occur at the load trans- code.
fer mechanism. The extent of cracking is dependent
on the tensile strength of concrete and location of the 5.2-Tension-This section defines the method of
load transfer mechanism with respect to embedment calculating design pullout strength of concrete, i.e.,
depth and side cover distance. direct tensile capacity, for an embedment.
Development length requirements for deformed re- The tensile strength of concrete is generally ac-
inforcement are dependent on the relationship of the cepted as ranging from 6 to 7 times the square root
height and spacing of deformations with respect to of the compressive strength of concrete (in psi). The
bar size and the influence of adjacent stressed rein- distribution of principal tensile stress in the concrete
forcement. The basic development length require- along the potential pullout failure plane defined by
ments of Section 12.2 of ACI 318-77 are based on Section 5.2 is assumed to vary (based on References
clear side cover distances equal to or less than 3 in. 1,2, and 3) from a maximum at the mechanical anchor
(76.2 mm) and maximum bar spacing of 6 in. on the end of the steel embedment to zero at the sur-
(152.4 mm). Reinforcement in concrete members is face of the concrete. This constitutes an average re-
generally located near the surface and, therefore, the sistance provided by the concrete of approximately
development length requirements of Section 12.2 of 4 VI: acting on the projected tensile stress area.
ACI 318-77 are reasonably conservative to ensure a Failure is initiated at the outside periphery of the
ductile failure without tensile splitting of the con- mechanical anchor (anchor head) and, therefore, the
crete. area of the anchor head does not contribute to the
If a reinforcing bar is used as a tensile stress com- pullout strength of the concrete and should be sub-
ponent embedded into the interior of a concrete mass, tracted from the projected tensile stress area in com-
the development length requirements of Section 12.2 puting pullout strength. Thus, it is desirable to keep
CONCRETE INTERNATIONAL/JULY 1981
the effective size of anchor head as small as possible embedment is being anchored. For example, several
to reduce embedment requirements. Tests!,2 have cases are as follows:
shown that the head of a standard anchor bolt or 1. Biaxial compression in the plane of the structure
stud, without a plate or washer, is sufficient bearing will result in the total angle approaching zero as the
area to fully develop the tensile strength of bolts magnitude of in-plane biaxial compression stresses
without damage to the concrete when the head of the becomes very large. The mode of failure of the con-
bolt has sufficient side cover for development of the crete approached direct shear.
necessary confining pressure. This is the basis of the 2. Biaxial tension in the plane of the structure
requirement specified in Section 5.5.2 which defines would tend to result in a total angle limit of 180 deg
anchor head dimensions that are similar to the head with increasing magnitude of in-plane tension. How-
of standard anchor bolts. ever, as a real limit, the reinforced concrete would
When the individual tensile stress components crack with the crack width being controlled by main
(e.g., bolts or studs or an embedment configuration reinforcement designed in accordance with appropri-
are located sufficiently close together (i.e., center-to- ate provisions of ACI 318-77. In such cases of crack-
center spacing) for overlapping of the potential pull- ing due to biaxial tension (or flexural cracking of the
out failure planes of the individual anchors, then the face containing the embedment), the authors feel that
loss of the effective tensile stress area can be com- the total angle can still be taken as 90 deg in con-
pensated for by increased depth of embedment. The junction with 4+ fie to calculate pullout strength.
projected tensile stress area of the group must be +
The two factors specified in this section, i.e., 0.65
capable of developing the combined strengths of the and 0.85, represent a simplification of a very complex
tensile stress components as required by Section problem. When the anchor head is between the far
6.1.1. Otherwise, the reinforcement provisions of Sec- face reinforcement and the near face concrete, the
tion 5.4 must apply. pullout strength of the concrete is dependent pri-
marily on the tensile strength of the concrete and the
For fully developed embedments, the concrete di-
mension parallel to the development length must be
+ factor, 0.65, has been specified to correspond with
Section 9.3.2(f) of ACI 318-77 for bending stress in
of sufficient thickness to meet the nominal shear
plain concrete which also relies on concrete tensile
stress requirements of Section 11.11 for two-way ac-
strength. When the anchor heads are beyond the far
tion. When the anchorage is made up of a number of
face reinforcement, the entire depth of structure is
bolts or individual anchors, spaced over a relatively
involved in the failure in a manner consistent with
wide surface area of the structure, the effective
the shear provisions of Section 11.11. In this case,
stress area must be reduced to comply with Section
11.11 of ACI 318-77 as illustrated in Fig. 5-2 of the
+
using a factor of 0.85, the provisions of Section 5.2
are equivalent to those of Section 11.11.
guide.
The nominal inclination of the failure plane for pull-
+
Ideally, the factor could be varied over a consid-
erable range dependent upon such factors as depth
out of the concrete is 45 deg; due to principal stress of embedment, amount of main reinforcement in the
orientation; if the concrete is stress-free transverse near face, and state of stress in the plane of the struc-
to the pullout force. As the crack propagates toward ture. However, there is not sufficient data; nor is it
the surface the uncracked portion flexes as a shallow practical for design purposes to be more precise than
disc putting the outer surface in compression around 0.85 or 0.65 in the current version of the guide.
the perimeter and causing a change in the failure
plane inclination. For shallow embedments, generally 5.3-Shear-The strength of anchors subject to
less than 5 in. (127 mm), the flexural strength due to shear are not significantly affected by concrete
the disc action is greater than the cone pullout strength unless the anchors are located near an edge
strength such that an increase in load is required to or in the case of anchors (e.g., "shell-type" expansion
propagate the crack. For this reason, the normal 90 anchors) which exhibit nonlinear load deflection be-
deg failure cone (total angle) will approach 120 deg havior. For bolts (also studs or bars) shear is trans-
with decreasing anchor depth in correlating failure mitted from the bolt to the concrete through bearing
loads! to calculated values using 4 VI: as a uniform of the bolt at the surface, forming a concrete wedge
stress. The actual concrete spall for shallow depth approximately 1/4 of the bolt diameter in depth.
anchors will produce an even wider area of failure. Translation of the wedge under the shearing force
However, caution should be observed in the utiliza- cannot occur without vertical movement or an up-
tion of inclination angles greater than 45 deg because ward thrust of the wedge on the restraining plate as
of the possibility of surface cracking which might re- illustrated in Fig. 2. This thrust induces tensile elon-
strict flexural action. For this reason the use of in- gation in the anchor and thus the clamping force on
clination angles greater than 45 deg for shallow depth the wedge increases in direct proportion with the
anchors is not recommended. shear as long as the anchor steel remains elastic.
The inclination of the failure angle will also vary When the bolt is near an edge, the total shearing
as a function of state of stress in the plane of the force must be developed by tensile stress on a po-
concrete structure (e.g.; wall or slab) into which the tential failure plane radiating at 45 deg toward the
CONCRETE INTERNATIONAL/JULY 1981 S6
wedge. The depth of the wedge is then controlled by
bending and is reduced in direct proportion to an in-
creased depth of the wedge.
SHEAR
.' FORCE The location of the shear plane with respect to the
concrete surface affects the development of shear
friction resistance and is discussed under Section
7.2.2.2.
6.4-Reinforeement- Concrete tensile failure may
occur either directly or indirectly as a result of in-
sufficient embedment depth or side cover distance.
When embedment depths or side cover distances are
not sufficient to fully develop the strength of anchor
steel, reinforcement must be located to intercept po-
tential cracking planes: The reinforcement must be
sized and oriented to restrict propagation of cracking
should it occur. To accomplish this, reinforcement
must be fully developed on both sides of a postulated
crack. It is recommended that the reinforcement pat-
terns be concentric with the tensile stress field.
For direct tensile load transfer, Fig. 4 illustrates,
how the tensile capacity of studs might be assured
Fig. 2 - Concrete wedge due to shear. by reinforcing the potential concrete failure cone. For
hairpin reinforcement to effectively intercept the po-
tential failure planes, each leg should be located with
Ld/3 froIQ the edge of an anchor head. The portion
of the hairpin anchored in the potential failure cone
should extend a minimum of eight (8) bar diameters
of the reinforcement configurations into the potential
failure cone, the anchorage requirements of Chapter
12 should be satisfied. In any case the limiting di-
mensions of eight (8) bar diameters and Ld/3 should
be complied with.
If anchorage of the reinforcement cannot be accom-
plished in the available dimensions, the anchorage
/ configuration should be changed.
// Limited testing'l has shown that when the edge dis-
tance is less than 2fs of the minimum provision of Sec-
/ " " - POTENTIAL"
" FAILURE ' tion 6.1.2(a), premature concrete failure occurred for
/ PLANE the reinforcement pattern provided. For edge dis-
FREE tance from 113 to 2fs of the minimum, reinforcement
EDGE
did restrain 45 deg tensile cracking; however, con-
crete shear failure occurred on a plane parallel to the
shear plane at the uppermost surface of the reinforc-
ing steel. While the anchorage remained ductile the
shear strength was reduced by the increased bending
Fig. 3 - Potential shear failure near a free edge. of the bolt about the concrete failure plane; therefore,
reinforcement and confinement similar to that illus-
trated in Fig. 5 should be considered to preclude pre-
free edge from the anchor steel at the surface of the mature failure. When the edge distance was less than
concrete as illustrated in Fig. 3. If several bolts are !f3 of the Section 6.1.2(a) requirement, there was in-
parallel to a free edge, the effect of overlapping fail- sufficient anchorage of the reinforcement on the
ure planes (i.e., center-to-center spacing less than 6.6 wedge side of the crack and failure was controlled
ft (2 m) on the concrete design strength must be con- entirely by the tensile strength of the concrete.
sidered. Therefore, in no case should anchors with less than
When the steel is not fully anchored (i.e., minimum 113 the side cover required by Section 6.1.2(a) be con-
side cover distance is not provided) or the anchorage sidered active for shear capacity. The engineer
behavior is nonlinear in the normally elastic stress should be extremely cautious with edge distances less
range, there is a radical reduction in the clamping than those required by Section 6.1.2(a). If reinforce-
force of the plate restraining the movement of the ment cannot be provided to develop the required ca-
CONCRETE INTERNATIONAL/JULY 1981
SHEAR FOR,CE

8 X THE DIAMETER
OF THE HAIRPIN
:..f--+ REI NFORCEMENT

~-+_.!:l!. MAXIMUM DISTANCE FROM


3 ANCHOR HEAD FOR
REINFORCEMENT TO BE
CONSIDERED EFFECT'IVE

'!f MINIMUM

LOCATE LEGS OF HAIRPIN


ReiNFORCEMENT IN THIS
REGION
Fig. 5 - Example of reinforcement for shear near an
edge.
Fig. 4 - Example of reinforcement for direct tension.
TENSION.

t
FORCE
pacity, the shear capacity of all such anchors should
be completely discounted or the embedment config-
uration changed.
When the side cover distances for direct tension
are less than the Section 6.1.1(a) requirement, rein-
forcement must be provided to arrest tensile failure ·"~4·.
0.'· '4-
of the concrete due to lateral bursting forces at an- , I I \

SPIRAL
chor heads near the free surface. Tests have not been REINFORCEMENT
performed to date on the effectiveness of reinforce-
ment to prevent tensile failure due to lateral bursting
forces at an anchor head when the side cover dis-
tances are less than required by Section 6.2.2(a).
Therefore, the engineer should rely on accepted prac- POTENTIAL
FA1\.URE
tices for prestressing anchorages and spiral reinforce- PLANE

ment as illustrated in Fig. 6 is recommended. For


conventional anchor heads the lateral force may be
conservatively taken as 1/4 of the tensile capacity of
the anchor steel (based on the Poisson, effect in the
lateral direction). For expansion anchors this force
should not be taken as less than the pullout capacity
of the anchor because of the significant lateral force
required to restrain an expansion anchor. Fig. 6 - Example of reinforcement to prevent lateral
Any embedment configuration requiring reinforce- bursting.
ment must also permit development of the reinforce-
ment. If sufficient space is not available for appro- bursting force of the anchorage, anchorages shall
priate development, the engineer should consider comply with the requirements of Section 18.13 of ACI
alternative configurations. 318-77. The force required to pull out a cone of con-
6.5-Bearing- The bearing requirements of Sec- crete for an individual headed anchor (anchored in
tion 5.5.1 reference the bearing requirements of Sec- accordance with Section 6.1.1) is less than the force
tion 10.16 of ACI 318-77 deal with bearing stresses required to split the concrete and, therefore, splitting
on concrete supports which are not laterally rein- parallel to the tensile force does not occur irrespec-
forced to resist splitting stresses. 4 When reinforce- tive of the bearing stress at the anchor head. Split-
ment is provided to prevent splitting and develop the ting transverse to the tensile force can occur between
CONCRETE INTERNATIONAL/JULY 1981 87
those types which can be made ductile (custom de-
sign). Most commercially available expansion anchors
are not ductile and are penalized by requiring a
higher safety factor against failure (see Section 8.2
of the guide).
Fig. 8 is a typical load deflection curve for ductile
anchorages. Fig. 9 is typical of nonductile anchorages.
6.1.1-Tension. The requirement of this section
that the calculated pullout strength of concrete ex-
ceeds the minimum specified tensile strength of the
steel is to assure ductile behavior of the embedment
in the event of overload. Typical embedment steels
exhibit significant variation in actual yield strength
"J'
, .' I
above specified minimums and have a wide ratio of
, 1'0 1 "
a''. 4,' ,',' .
::,: .;~.' 'I/",~ ~
yield to tensile strength. Therefore, fut, rather than
a factor times fy, is used to ensure ductile behavior.
A minimum side cover distance is required at the
anchor head to confine the lateral thrust generated
Fig. 7 - Splitting transverse to tension load. by the full load transfer from steel to concrete. Be-
cause of the significant difference in restraint stiff-
ness around the periphery of the anchor head, lateral
anchor heads in multiple stress component anchor-
strains are not uniform and tend to concentrate in the
ages, particularly when the center-to-center spacing
region of minimum cover. The lateral bursting force
between the anchor heads is less than the anchor
is, therefore, of a magnitude relative to the longitu-
embedment depth (see Fig. 7). However, the splitting
dinal load similar to that of the lateral strain' to the
plane is at 90 deg to the plane of concern for bearing
longitudinal strain. Sample side cone blowouts are
restrictions and may be controlled with proper depth
represented by the test data given in Table 6.1.1.
of embedment. If the concrete has been previously
Equating the lateral bursting force to the concrete
cracked in the normal splitting plane, then the force
capacity for a single anchor bolt, stud, or bar results
required to propagate the crack is approximately 112
in
of the force required to initiate splitting. Under these
conditions splitting may control the failure mode.
However, the failure load is approximately the same fJP 4'v'C
as the force required for pullout cone failure in un- (lateral (concrete (projected
force) tensile area)
cracked concrete.
In compression anchorages, bearing stress is trans- strength)
mitted to the concrete at the concrete surface; there- Applying a • factor of 0.85 to concrete strength, a
fore, splitting is likely to occur only in compression conservative fJ or 0.25 and a tensile stress area of 0.75
anchorages of limiting supporting surface area. For of the gross area of bolt, stud, or bar
such anchorages, the normal bearing restrictions
should apply.
0.75nD2 ]
Section 5.5.2 describes anchor heads that do not fJP = fJ [ 4 x f ut = 4+ VI: nm 2
have to satisfy the requirements of Section 5.5.1 (see
Commentary for Section 5.2).

6.0-Anehorage requirements ,n:;-


The basic philosophy of anchorage requirements is
m=Dv7Wf
consistent with the ultimate strength design philos- If several bolts are paraIJel to a free edge, the effect
ophy of reinforced concrete. The failure mechanism of overlapping failure planes on the lateral concrete
is controlled by requiring yielding of the steel an- design strength must be considered.
chorage prior to brittle failure. While ductility is not Similar relationships can be developed for other
possible in all types of anchorages, it is required in embedment shapes that are embedded close to a

TABLE 6.1.1 - SaDlple side eone blowont test data

Bolt ASTM Side cover Concrete Lateral force


size material distance strength Failure load coefficient
D, in. specification m, in. f:' psi P,lb f3
3/, A 307 2 5500 + 22100 0.17
1 A 490 4'12 4245 94000 0.18

88 CONCRETE INTERNATIONAL/JULY 1981


,,' . " .
30-r--~~-r--__~~-------r------~-------' 12.5

.
~RE
10.0
. /'

~ ~-r------~~~---r~~~-r-------+-------;
,/
V """
"...~
:
T"N510N TEST,
7.5

/ TENSION TEST,
ffi
a.

~
A307 BOL TS

5.0 L P~ANSIONANCHOR

JO +-j~--+-------+"";"";---+--"";---+--"';";"'----i

2.5 / ..
'J

/
' ,,'

') ··1'
0.0

• 0.2 0.3 0,4 0.5 0.00 0.02 0.04 0;06 ' o.oa b.IO· ' 0.12 0.14
DEFLECTION, INCHES'
>DEfLECTION, INCHES

Fig. 8 - Ductile load deflection behavior. Fig. 9 - Nonductile load deflection behavior.
"free" edge of the concrete. For expansion anchors
it is recommended that the lateral bursting force, (JP,
be assumed equal to the average tension test failure
load of the anchor being used.
When the anchor steel is composed of reinforce-
ment without mechanical end anchorage the devel- ~ 20 -r---J-.,....-;:>""f:......--"'::>""'90~;;.....,---,.,f~,.......,--+-----;
a.
opment requirements of Chapter 12 are more than
adequate for development of the tensile strength of
"~
...:

the reinforcement. '"


l::'
~
o
6.1.2- Shear. A minimum edge distance is required ~ 10-H~~+--+--~~~....; __~~____~-+-----~
for full development of the shear strength of anchor
steel. The projected tensile stress area of a single
bolt, stud, or bar for shear toward an edge is exactly
half of the normal stress area for tensile loading of
an anchor without an edge effect. For a design shear
capacity of V and an edge distance of m 0.0 0,1 0.2 0.3..
DEFl,EeTIOH, INCHES:
0.5

Fig. 10 Effect of shear plane location on load de-


V= 4~v7. flection behavior.
2
For a friction coefficient of 0.7 for steel against con-
crete, the ultimate shear strength of a bolt equals: is always less than the tensile capacity alone. The
development requirements for tensile loading are
nD 2 therefore also good for combined loads.
V= 0.7 -4-fu. 6.1.4. - Side cover distances less than m/3 may re-
The minimum edge distance for a single bolt, stud, sult in side blowout cone failures and loss of anchor-
or bar is obtained by equating the two expressions age (see Section 6.4 of the Commentary).
for V: T.O-Design reqnirements for embedment steel
7.1- Embedments can be designed using a variety
\rt:-
m=DV107i:
of materials and attachments under varying loading
conditions and construction situations. The engineer
must therefore consider all this in his selection and
Similar relationships can be developed for other specification of materials, structural shapes, or types
embedment shapes that are embedded close to a of anchors best suited to fit each situation.
"free" edge of the concrete. 7.2.1-The ~ factor of 0.9 for tension compression,
It should be noted that plates embedded near an and bending for the embedment steel is consistent
edge will behave essentially as shear lugs and should with Section 9.3.2(a) of ACI 318-77.
be treated as such. 7.2.2.1- The +
factor of 0.5 for shear stress in
The utilization of reinforcement to reduce edge re- structural shapes, shear lugs, and fabricated sections
quirements for shear was discussed in Section 5.4. is consistent with the AISC shear yield stress for
6.1.3-Combined loading. The resultant load capac- plastic design which corresponds to the required
ity of anchors subject to combined tension and shear strength methods of ACI 318-77.
CONCRETE INTERNATIONAL/JULY 1981 S9
7.2.2.2 - The mechanism of shear transfer for failure if an overload condition should occur. In lieu
bolts and bars is commonly termed shear-friction. of design strength calculations as defined in Section
The location of the plane of stress transfer from bolt 8.1.1, design strengths can be established by tests as
to concrete directly affects the shear strength of the defined in Section. 8.1.2.
anchorage. The effect of shear plane location on an- Due to variations in installation conditions, expan-
chorage behavior is illustrated by the load deflection sion mechanisms, and repeatability of test results,
curves of Fig. 10. If the plate contacting the concrete the permissible design capacity for the expansion an-
is embedded in the concrete with its outer surface chor steel is reduced to 90 percent of the values spec-
flush with the exterior surface of concrete then, for ified in Section 7.2.
a given horizontal movement, the component of 8.2 - Alternative design requirements - Expan-
clamping force perpendicular to the plate is greater sion anchors that do not meet the ductility require-
than when the contact plane is flush with the exterior ments of Section 8.1 are penalized by this section.
concrete surface. This increased clamping force di- The permissible design strength is limited to approx-
rectly increases the frictional shear strength of the imately 113 of the average test failure load. An overall
anchorage as reflected in the 0.9 coefficient as com- factor of safety of 4.0 is achieved by combining the
pared with the commonly accepted coefficient of 0.7 0.85 factor with a load factor of 1.4 (i.e., only dead
for a flush mounted plate. load). This limitation is applied to both tension and
When the contact plate is mounted on a group pad shear test loads since shear capacity generated by
exterior to the concrete surface the forward bolts in shear friction resistance is a function of tensile an-
the direction of shear have only the width of grout chorage capacity.
from the bolt to the edge of the plate for an assured 8.3 - The use of one expansion anchor results in
edge distance to develop the shear strength of the a connection with no capability to redistribute load;
bolts. (Even if the grout pad is extended away from therefore, additional conservatism is required.
the plate the extended portion cannot be relied upon
to remain bonded and uncracked from drying shrink- 8.4 - Testing - Testing of expansion anchors to
age.) This nominal edge distance is not sufficient to verify anchor strength as used in Sections 8.1 or 8.2
develop the shear strength in the forward bolts; is required by Section 8.4.1. Anchor strength shall be
therefore, a much larger portion of the shear must established by tests and shall include testing of the
be carried by the back bolts. Plate rotation follows anchor expansion mechanism and its ability to trans-
grout failure, reducing the clamping force and sub- mit the load to adjacent concrete. Concrete capacity
sequent shear strength of the back bolts and thus the shall be determined in accordance with Sections 8.1.1
coefficient of friction is reduced for these anchorages. or 8.1.2. Tests performed to meet the requirements
of Section 8.1.2 may be incorporated in the tests spec-
7.3 - Combined tension and shear
ified in Section 8.4.1. It is not practical to specify in
7.3.1 - Normally accepted practice for structural
the guide a detailed testing program for expansion
shapes.
anchors due to the variety of applications and de-
7.3.2 - The effect of direct tension on an anchor-
signs. The testing requirements defined in ANSI!
age is a direct reduction of the clamping force which
ASTM E 488-76 are acceptable as a guide for estab-
provides shear transfer resistance. While this effect
lishing a testing program. However, the engineer is
can be offset somewhat in the elastic stress range by
responsible for assuring that the testing program
preloading bolts there is no difference in effect once
used qualified the particular anchor for the intended
the tensile load component exceeds the preload. The
application.
reduced shear strength corresponding to the loss il1
Testing of expansion anchors in the installed con-
clamping force affects the combined load capacity
ditions specified in Section 8.4.2 is to verify actuation
such that no more than a straight addition of com-
of the expansion mechanism. Test method (a) is in-
ponent strengths is allowed.
tended primarily for wedge type expansion anchors
7.4 - This section is consistent with the AISC
that are typically installed and tested via torquing,
"Specification for the Design, Fabrication and Erec-
and method (b) is intended primarily for shell type
tion of Structural Steel for Buildings."
anchors which should be tested by direct load appli-
7.5 - The shear failure plane can be excluded from
the threads by care in detailing the connection. Un-
cation.
der these conditions the gross area may be utilized 8.5 - Expansion anchor selection - The engineer
for shear. is cautioned to select an expansion anchor that is de-
signed, manufactured, and tested to be compatible
B.O - Expansion anchors with the load application, environment, and installa-
Section B.O was developed to provide guidance in tion conditions. Oracking of concrete in tension zones
the design and use of concrete expansion anchors. subsequent to anchor installation can result in a re-
8.1 - Design requirements - The preferred de- duction of anchor capacity and complete loss of pre-
sign for concrete expansion anchors is for the con- load if the cracking is coincident with the anchor lo-
crete to have a capacity greater than the anchor steel cation. In this kind of application the engineer should
and, therefore, provide indication of an impending have results from tests conducted in cracked concrete
40 CONCRETE INTERNATIONAL/JULY 1981
specimens. As an alternative, an appreciably higher 4. ACI Committee 318, "Commentary on Building Code
factor of safety than would otherwise be required Requirements for Reinforced Concrete (ACI 318-77),"
should be used to define design strength. American Concrete Institute, Detroit, 1977, 132 pp.
When such anchors are subject to vibratory loads 5. "Standard Test Methods for Strength of Anchors in
Concrete and Masonry Elements," (ANSI-ASTM E 488-76),
(i.e., nonseismic continuous or intermittent cyclic 1976 Annual Book of ASTM Standards, Part 18, American
loads), a complete loss of function can occur. Anchor Society for Testing and Materials, Philadelphia, pp. 843-
type and application must be qualified by testing or 851.
such use is prohibited. 6. ACI Committee 349, "Proposed Addition to: Code Re-
quirements for Nuclear Safety Related Concrete Structures
9.0 - Inserts (ACI 349-76)," ACI JOURNAL, Proceedings V. 75, No.8, Aug.
Inserts are not subject to the same variables as 1978, pp. 329-347.
expansion anchors and, therefore, the safety factors 7. PCI Design Handbook, Prestressed Concrete Institute,
are adjusted accordingly. Testing to verify capacity Chicago, 1971, 380 pp.
is a requirement. Received June 1980 and reviewed under Institute pUblication policies.

10.0 - Grouted elllbedllleDts


10.1 - Since grouted embedments are required to
transfer loads the same as cast-in-place embedments,
the appropriate design and anchorage requirements
defined in Sections 5.0, 6.0, and 7.0 are applicable. Robert W. Cannon, FAC/, is a Con-
10.2 - Grouts are used frequently for their special sulting Engineer in Maryville, Tennes-
characteristics. Special grouts shall be tested to ver- see. He recently retired from TVA
ify their required properties. Epoxy grouts are not after 25 years of Design and Research
in Reinforced Concrete and Structural
covered by this guide. Applications. A major portion of re-
10.3 - Grouted embedments designed to transfer search during the last eight years has
load between steel and grout or grout and concrete been in steel embedments. He is a
by tension, shear or bond shall be tested to verify member and past chairman of ACI
Committee 207, Mass Concrete, and 8
load transfer capabilities. The testing program shall member of ACI Committee 849, Nu-
be established by the engineer. clear Structures.
Special considerations are required for grouted
embedments that are designed to transfer tension
loads where cracking may be parallel to and coinci-
dent with the axis of the embedment. The testing A CI member Dwaine A. Godfrey is
program must address this situation if applicable. president and founder of Nuclear
Testing has demonstrated that the bond between Structures, Inc., Atlanta, Georgia. He
is involved in the analysis and design
grout and concrete can be lost due to cracking. In lieu of steel and concrete structures for
of relying on bond, a belled hole in the region of the nuclear generating plants. He is a
anchor head is suggested. member of ACI Committee 849, Con-
10.5 - Grouted embedments designed to transfer crete Nuclear Structures (currently
the chairman of the Working Group on
load by bearing or compression should only require Steel Embedments).
testing to verify compressive strength of grout and
do not require in place verification testing.
11.0 - Fabrication and installation
ACI member F. L. MoreaditlJ is
The engineer must consider and make provisions manager, Structural Department and
for fabrication and installation conditions that could Chief Structural Engineer; Power Di-
influence the load capacity. Thermal expansion due vision-Reading; Gilbert/Common-
wealth; Reading, Pa. He received his
to welding after the embedment has been set in con- Ph.D. from North Carolina State Uni-
crete is considered to be a frequent problem. versity in 1964 and was engaged in
teaching and consulting in reinforced
References and prestressed concrete at Old Do-
1. "Anchorage to Concrete," Research and Development minion University before joining Gil-
bert/Commonwealth in 1972. He is a
Report No. CEB 75-32. Civil Engineering Branch, Tennes- member of ACI Committee 859, Con-
see Valley Authority, Knoxville, Dec. 1976, 25 pp. crete Components for Nuclear Reac-
2. McMackin, P. J.; Slutter, R. G.; and Fisher, J. W., tors (Sub-group on Containment De-
"Headed Steel Anchors Under Combined Loading," AISC sign) and ACI Committee 849,
Engineering Journal, 2nd Quarter, 1973, pp. 43-52. Concrete Nuclear Structures (cur-
3. Bailey, John W., and Burdette, Edwin G., "Edge Ef- rently chairman of the Working Group
on Design with previous activity on
fects on Anchorage to Concrete," Civil Engineering Re- the Working Groups for Steel Embed-
search Series No. 31, University of Tennessee, Knoxville, ments and Impactive and Impulsive
Aug. 1977, 21 pp. Loads).
CONCRETE INTERNATIONAL/JULY 1981

Vous aimerez peut-être aussi