Vous êtes sur la page 1sur 95

Head Office/Factory :

Jl. Gatot Subroto Km 7,8 Kel Pasir Jaya, Kec. Jati Uwung, Tangerang 15135-Indonesia
Phone : (62-21) 5922404, 5928066 (Hunting) Fax. : (62-21) 59301979, 5922576, 5901469
c
Copyright Sumi Indo Kabel 2012
All rights reserved. This catalogue is the copyright work of PT. Sumi Indo Kabel Tbk. No part of this publication may be reproduced, stored in a retrieval system, or transmitted,
in any form or by means, electronic, mechanical, photocopying, recording or otherwise, without prior permission of PT. Sumi Indo Kabel.
All information contained in this catalogue is believed to be accurate at the time issue. PT. Sumi Indo Kabel reserve the right to change information or specification at any time
in the light of technical developments or revisions.

Issue : 5 Date: August 2012


Section 1 - Contents & Information

Low Voltage Catalogue Index


Page Number
SECTION 1 - Contents & Information
Index Page 1
General Cable Specification 2

SECTION 2 - PVC Insulated Cables


Unarmoured Cables
450/750 Volts PVC Insulated Cables (Cu/PVC, NYA) 5
450/750 Volts PVC Insulated Cables (Flexible Cu/PVC, NYAF) 6
300/500 Volts PVC Insulated and PVC Sheathed Cables (PVC/PVC, NYM) 8
300/500 Volts PVC Insulated and PVC Sheathed Cables (Flexible PVC/PVC, NYMHY) 10
450/750 Volts PVC Insulated and PVC Sheathed Cables (Flexible PVC/PVC, NYYHY) 11

600/1000 Volts PVC Insulated and PVC Sheathed Cables (PVC/PVC, NYY) 18
600/1000 Volts PVC Insulated, Copper Tape Shielded and PVC Sheathed Cables (PVC/PVC-S, NYSY) 30

Armoured Cables
600/1000 Volts PVC Insulated, Steel Wire Armoured and PVC Sheathed Cables (PVC/SWA/PVC, NYRY) 35
600/1000 Volts PVC Insulated, Flat Steel Wire Armoured and PVC Sheathed Cables (PVC/FSWA/PVC, NYFGbY) 41
600/1000 Volts PVC Insulated, Double Steel Tape Armoured and PVC Sheathed Cables (PVC/DSTA/PVC, NYBY) 46

SECTION 3 - XLPE Insulated Cables


Unarmoured Cables
600/1000 Volts XLPE Insulated and PVC Sheathed Cables (XLPE/PVC, N2XY) 52
600/1000 Volts XLPE Insulated, Copper Tape Shielded and PVC Sheathed Cables (XLPE/PVC-S, N2XSY) 62

Armoured Cables
600/1000 Volts XLPE Insulated, Steel Wire Armoured and PVC Sheathed Cables (XLPE/SWA/PVC, N2XRY) 67
600/1000 Volts XLPE Insulated, Flat Steel Wire Armoured and PVC Sheathed Cables (XLPE/FSWA/PVC, N2XFGbY) 73
600/1000 Volts XLPE Insulated, Double Steel Tape Armoured and PVC Sheathed Cables (XLPE/DSTA/PVC, N2XBY) 78

SECTION 4 - General Information


Current Carrying Capacity for XLPE Insulated cable (single core) 83
Current Carrying Capacity for XLPE Insulated cable (multicore) 84
Current Carrying Capacity for PVC Insulated cable (single core) 85
Current Carrying Capacity for PVC Insulated cable (multicore) 86
Correction factor of Curent carrying capacity 87
Cable arrangement for Installation purpose 88
Explanation of Flame Retardant / Fire Resistant Characteristic 91

Page - 1
Section 1 - Contents & Information

General Cable Specification

1 Scope
These specification apply to material and constructions of cross-linked thermosetting polyethylene
(XLPE) or Polivinyl chloride (PVC) insulated wire and cables for rated voltages 0.3/0.5 kV up to
0.6/1(1.2) kV in accordance to IEC 60502-1, SNI or SPLN ( Standard of Indonesia Electric Power
Company )

2 Conductor
The conductor shall be formed from plain annealed copper or aluminium complying with IEC
60228
The conductor shall be solid, circular stranded, compacted stranded or sector shape

3 Insulation
The insulation shall be cross-linked polyethylene (XLPE) or Polivinyl chloride (PVC) in
accordance to IEC 60502-1.

4 Identification of cores
Below is standard reference for core identification :
A. IEC 60445 - 2010 Phasa / AC System : Black, Brown or Grey
Neutral : Blue 1
Grounding : Green and Yellow

B. SNI Standard 3 Core ( 2 Alternative ) a. Green / Yellow, Blue, Brown


b. Blue, Black, Brown

4 Core ( 3 Alternative ) a. Gren / Yellow, Blue, Black, Brown


b. Blue, Black, Brown, Black
c. Blue, Brown, Black, Brown

5 Core System I : Green/Yellow, Blue, Black, Black, Brown


System O : Blue, Black, Brown, Black, Brown

Such that, the proposal cables shall be identified by color or numbered printed on the surface of
insulation in accordance with the following sequence or other sequence as follows *) :
Number of core Identification of cores
Single core Brown
Two cores Brown, Blue
Three cores Brown, Black, Grey
1
Four cores Brown, Black, Grey, Blue
Five cores Brown, Black, Grey, Blue, Green / Yellow stripe
Six core or more Black insulation with white numbered code.

Note : *) : Sumi Indo Kabel can comply for color identification as Request

Page - 2
Section 1 - Contents & Information

5 Cabling and filling


The multi cores shall be laid up together with suitable filler to give the completed cable a
substantially circular cross section and bound with suitable binder tape.

6 Metallic Shielding (if required)


The metallic shielding shall consist of either one or more Copper tapes or a concentric layer of
copper wires or aluminium mylar tape and drain wire

7 Inner sheath (armour cable only).


The inner sheath shall consist of extruded thermoplastic compound such as :polyvinyl chloride
(PVC), polyethylene (PE),halogen free (LSOH), etc in accordance to IEC 60502-1.

8 Metallic armour
The metallic armour shall consist of single layer of round galvanized steel wire or flat galvanized
steel wire and steel tape or double layer of galvanized steel tapes in accordance to IEC 60502-1.
The armour of single core cables shall consist of single layer of aluminium wire or double layers of
aluminium tape as non magnetic material.

9 Outer sheath
The outer sheath shall consist of a thermoplastic compound such as polyvinyl chloride (PVC),
polyethylene (PE), halogen free (LSOH), etc in accordance with IEC 60502-1.

Page - 3
Section 2 - PVC Insulated Cables
Unarmoured Cables

450/750 V PVC INSULATED WIRE (Cu/PVC)


acc. to IEC 60227

PVC Insulation Copper Conductor (Solid)

PVC Insulation Copper Conductor (Stranded)

Colour of Insulation : Red, White, Black, Green, Brown, Blue, Yellow, Grey, Green-yellow

450/750 V PVC INSULATED WIRE (Cu/PVC Flexible)


acc. to IEC 60227

PVC Insulation Copper Conductor (Flexible)

Colour of Insulation : Red, White, Black, Green, Brown, Blue, Yellow, Grey, Green-yellow

Note : Special application upon request


* Available product in accordance to : SPLN or other requirement.
* Tin coated Copper conductor.

Page - 4
Section 2 - PVC Insulated Cables
Unarmoured Cables

450/750 V PVC INSULATED WIRE


CU/PVC (IEC 60227)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 450/750 V
Insulation : PVC Compound type C Operating Temperature
Colour Ident. : Red, White, Black, Green, Grey Maximum 70°C
Brown, Blue, Yellow, Green-yellow

Conductor Nominal Nominal Maximum Minimum AC


Nominal Shape Diameter Thickness Overall Weight Conductor Insulation Test
Cross- of Number of of Diameter of Resistance Resistance Voltage
section conductor of wire Conductor Insulation wire at 20°C at 70°C
area (approx.) (Approx.) (Approx.)
mm² Number mm mm mm kg/km /km M.km V/5 min

1.5 RE 1 1.38 0.7 3.0 25 12.1 0.011 2500


1.5 RM 7 1.6 0.7 3.2 25 12.1 0.010 2500
2.5 RE 1 1.78 0.8 3.6 35 7.41 0.010 2500
2.5 RM 7 2.0 0.8 3.8 35 7.41 0.009 2500
4 RE 1 2.26 0.8 4.1 50 4.61 0.0085 2500
4 RM 7 2.6 0.8 4.4 55 4.61 0.0077 2500
6 RE 1 2.77 0.8 4.6 70 3.08 0.0070 2500
6 RM 7 3.1 0.8 4.9 75 3.08 0.0065 2500
10 RE 1 3.57 1.0 5.8 115 1.83 0.0070 2500
10 RM 7 4.1 1.0 6.3 120 1.83 0.0065 2500
16 RM 7 5.1 1.0 7.3 180 1.15 0.0050 2500
25 RM 7 6.4 1.2 9.0 280 0.727 0.0050 2500
35 RM 7 7.6 1.2 10.5 380 0.524 0.0040 2500
50 RM 19 9.2 1.4 12.5 530 0.387 0.0045 2500
70 RM 19 10.9 1.4 14.0 730 0.268 0.0035 2500
95 RM 19 12.6 1.6 16.5 985 0.193 0.0035 2500
120 RM 37 14.2 1.6 18.0 1220 0.153 0.0032 2500
150 RM 37 15.9 1.8 20.0 1525 0.124 0.0032 2500
185 RM 37 17.6 2.0 22.0 1875 0.0991 0.0032 2500
240 RM 61 20.3 2.2 25.5 2465 0.0754 0.0032 2500
300 RM 61 22.7 2.4 28.0 3055 0.0601 0.0030 2500
400 RM 61 25.7 2.6 31.5 3930 0.0470 0.0028 2500

Note *) RE : Round Solid Class 1


RM : Circular Stranded Class 2

Page - 5
Section 2 - PVC Insulated Cables
Unarmoured Cables

450/750 V PVC INSULATED WIRE


CU/PVC-Flexible (IEC 60227)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type C Operating Temperature
Colour Ident. : Red, White, Black, Green, Grey Maximum 70°C
Brown, Blue, Yellow, Green-yellow

Conductor Nominal Nominal Maximum Minimum AC


Nominal Maximum Diameter Thickness Overall Weight Conductor Insulation Test
Cross- Diameter of of Diameter of Resistance Resistance Voltage
section of wire Conductor Insulation wire at 20°C at 70°C
area (approx.) (Approx.) (Approx.)
mm² mm mm mm mm kg/km /km M.km V/5 min

1.5 0.26 1.6 0.7 3.2 25 13.30 0.010 2500


2.5 0.26 2.0 0.8 3.8 35 7.98 0.009 2500
4 0.31 2.6 0.8 4.4 50 4.95 0.007 2500
6 0.31 3.5 0.8 5.3 75 3.30 0.006 2500
10 0.41 4.6 1.0 6.8 130 1.91 0.0056 2500
16 0.41 5.7 1.0 7.9 190 1.21 0.0046 2500
25 0.41 7.1 1.2 9.7 290 0.78 0.0044 2500
35 0.41 8.4 1.2 11.0 395 0.554 0.0038 2500
50 0.41 10.1 1.4 13.5 550 0.386 0.0037 2500
70 0.51 12.0 1.4 15.0 760 0.272 0.0032 2500
95 0.51 13.7 1.6 17.5 1010 0.206 0.0032 2500
120 0.51 15.5 1.6 19.5 1270 0.161 0.0029 2500
150 0.51 17.6 1.8 22.0 1605 0.129 0.0029 2500
185 0.51 19.2 2.0 24.0 1915 0.106 0.0029 2500
240 0.51 22.0 2.2 27.0 2495 0.0801 0.0028 2500

Page - 6
Section 2 - PVC Insulated Cables
Unarmoured Cables

300/500 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (NYM) - IEC 60227 , SPLN 42-2

Conductor PVC Inner covering


PVC Insulation PVC Sheath

300/500 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC Flexible (NYMHY) - IEC 60227 , SPLN 42-2

Conductor
PVC Insulation PVC Sheath

450/750 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC Flexible (IEC 60227, SPLN 42-6-3)

Tape (manufacturer's option)


Conductor PVC Sheath
PVC Insulation
Filler (Polyprophylene yarn,or extruded filler up to request)

Page - 7
Section 2 - PVC Insulated Cables
Unarmoured Cables

300/500 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (NYM) - IEC 60227-4 , SPLN 42-2

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 and 2) Uo/U - 300/500 V
Insulation : PVC Compound Type C Operating Temperature
Inner covering : PVC Compound Maximum 70°C
Sheath : PVC Compound type ST4
Colour Ident. : Insulation : Two cores - Brown, Blue
Three cores - Brown, Black, Grey
Sheath - White

TWO AND THREE CORES


Conductor Nominal Nominal Overall Maximum

No. Nominal Shape Diameter Thickness Thickness Thickness diameter Weight Conductor

of Cross- of number of of of Inner of of of Resistance

Core section Cond. of wire Conductor Insulation covering Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
- mm² - Number mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 0.4 1.2 9.5 130 12.1
1.5 RM 7 1.6 0.7 0.4 1.2 10.0 140 12.1
2.5 RE 1 1.78 0.8 0.4 1.2 11.0 175 7.41
2.5 RM 7 2.0 0.8 0.4 1.2 11.0 185 7.41
4 RE 1 2.26 0.8 0.4 1.2 12.0 225 4.61
2 4 RM 7 2.6 0.8 0.4 1.2 12.5 240 4.61
6 RE 1 1 0.8 0.4 1.2 13.0 295 3.08
6 RM 7 3.1 0.8 0.4 1.2 14.0 315 3.08
10 RE 1 3.57 1.0 0.6 1.4 16.0 455 1.83
10 RM 7 4.1 1.0 0.6 1.4 17.0 495 1.83
16 RM 7 5.1 1.0 0.6 1.4 19.0 670 1.15
25 RM 7 6.4 1.2 0.8 1.4 23.0 1000 0.727
35 RM 7 7.6 1.2 1.0 1.6 26.0 1340 0.524
1.5 RE 1 1.38 0.7 0.4 1.2 10.0 150 12.1
1.5 RM 7 1.6 0.7 0.4 1.2 10.5 160 12.1
2.5 RE 1 1.78 0.8 0.4 1.2 11.5 205 7.41
2.5 RM 7 2.0 0.8 0.4 1.2 12.0 220 7.41
4 RE 1 2.26 0.8 0.4 1.2 12.5 270 4.61
3 4 RM 7 2.6 0.8 0.4 1.2 13.0 290 4.61
6 RE 1 2.77 0.8 0.4 1.4 14.0 360 3.08
6 RM 7 3.1 0.8 0.4 1.4 14.5 385 3.08
10 RE 1 3.57 1.0 0.6 1.4 17.0 560 1.83
10 RM 7 4.1 1.0 0.6 1.4 18.0 600 1.83
16 RM 7 5.1 1.0 0.8 1.4 20.5 850 1.15
25 RM 7 6.4 1.2 0.8 1.6 24.5 1270 0.727
35 RM 7 7.6 1.2 1.0 1.6 27.5 1680 0.524

Note *) : RE : Round Solid Class 1


Page - 8 RM : Circular Stranded Class 2
Section 2 - PVC Insulated Cables
Unarmoured Cables

300/500 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (NYM) - IEC 60227-4 , SPLN 42-2

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 and 2) Uo/U - 300/500 V
Insulation : PVC Compound Type C Operating Temperature
Inner covering : PVC Compound Maximum 70°C
Sheath : PVC Compound type ST4
Colour Ident. : Insulation : Four core - Brown, Black, Grey, Blue
Five core - Brown, Black, Grey, Blue, Green / Yellow stripe
Sheath - White

FOUR AND FIVE CORES


Conductor Nominal Nominal Overall Maximum

No. Nominal Shape Diameter Thickness Thickness Thickness diameter Weight Conductor

of Cross- of number of of of Inner of of of Resistance

Core section Cond. of wire Conductor Insulation covering Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
- mm² - Number mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 0.4 1.2 11.0 180 12.1
1.5 RM 7 1.6 0.7 0.4 1.2 11.5 190 12.1
2.5 RE 1 1.78 0.8 0.4 1.2 12.5 250 7.41
2.5 RM 7 2.0 0.8 0.4 1.2 13.0 265 7.41
4 RE 1 2.26 0.8 0.4 1.4 14.0 340 4.61
4 4 RM 7 2.6 0.8 0.4 1.4 14.5 365 4.61
6 RE 1 2.77 0.8 0.4 1.4 15.5 460 3.08
6 RM 7 3.1 0.8 0.4 1.4 16.0 485 3.08
10 RE 1 3.57 1.0 0.6 1.4 18.5 690 1.83
10 RM 7 4.1 1.0 0.6 1.4 19.5 745 1.83
16 RM 7 5.1 1.0 0.8 1.4 22.5 1060 1.15
25 RM 7 6.4 1.2 1.0 1.6 27.5 1620 0.727
35 RM 7 7.6 1.2 1.0 1.6 30.0 2110 0.524
1.5 RE 1 1.38 0.7 0.4 1.2 11.5 210 12.1
1.5 RM 7 1.6 0.7 0.4 1.2 12.0 225 12.1
2.5 RE 1 1.78 0.8 0.4 1.2 13.5 295 7.41
2.5 RM 7 2.0 0.8 0.4 1.2 14.0 315 7.41
4 RE 1 2.26 0.8 0.6 1.4 15.5 425 4.61
5 4 RM 7 2.6 0.8 0.6 1.4 16.5 455 4.61
6 RE 1 2.77 0.8 0.6 1.4 17.0 550 3.08
6 RM 7 3.1 0.8 0.6 1.4 17.5 580 3.08
10 RE 1 3.57 1.0 0.6 1.4 20.0 840 1.83
10 RM 7 4.1 1.0 0.6 1.4 21.5 900 1.83
16 RM 7 5.1 1.0 0.8 1.6 25.0 1310 1.15
25 RM 7 6.4 1.2 1.0 1.6 30.0 1970 0.727
35 RM 7 7.6 1.2 1.2 1.6 33.5 2620 0.524
Note *) : RE : Round Solid Class 1

RM : Circular Stranded Class 2 Page - 9


Section 2 - PVC Insulated Cables
Unarmoured Cables

300/500 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC Flexible (IEC 60227-5, SPLN 42-6-2)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 300/500 V
Insulation : PVC Compound type D Operating Temperature
Sheath : PVC Compound type ST5 Maximum 70°C
Colour Ident. : Insulation :Two core : Brown, Blue
Three core - Brown, Black, Grey
Four core - Brown, Black, Grey, Blue
Five core - Brown, Black, Grey, Blue, Green / Yellow stripe
Sheath - White

Conductor Nominal Nominal Overall Maximum

Number Nominal Maximum Diameter Thickness Thickness diameter Weight Conductor

of Cross- Diameter of of of of of Resistance

Core section of wire Conductor Insulation Sheath cable cable at 20°C


area (approx.) (approx.) (approx.)

- mm² mm mm mm mm mm kg/km /km


0.75 0.21 1.1 0.6 0.8 7.0 65 26.0

2 1 0.21 1.3 0.6 0.8 7.5 75 19.5


1.5 0.26 1.6 0.7 0.8 8.5 100 13.3
2.5 0.26 2.0 0.8 1.0 10.0 145 7.98
0.75 0.21 1.1 0.6 0.8 7.5 75 26.0

3 1 0.21 1.3 0.6 0.8 7.5 90 19.5


1.5 0.26 1.6 0.7 0.9 9.0 125 13.3
2.5 0.26 2.0 0.8 1.1 10.5 180 7.98
0.75 0.21 1.1 0.6 0.8 8.0 90 26.0

4 1 0.21 1.3 0.6 0.9 8.5 110 19.5


1.5 0.26 1.6 0.7 1.0 10.0 150 13.3
2.5 0.26 2.0 0.8 1.1 11.5 220 7.98
0.75 0.21 1.1 0.6 0.9 9.0 115 26.0

5 1 0.21 1.3 0.6 0.9 9.5 130 19.5


1.5 0.26 1.6 0.7 1.1 11.0 185 13.3
2.5 0.26 2.0 0.8 1.2 13.0 270 7.98

Note : Shape of conductor : Flexible stranded class 5

Page - 10
Section 2 - PVC Insulated Cables
Unarmoured Cables

450/750 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC Flexible (IEC 60227-5, SPLN 42-6-3)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Brown, Blue
Sheath - Black

TWO CORES
Conductor Nominal Nominal Overall Maximum
Nominal Maximum Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.)
mm² mm mm mm mm mm kg/km /km

1.5 0.26 1.6 0.7 1.8 10.5 126 13.3


2.5 0.26 2.0 0.8 1.8 12.0 166 7.98
4 0.31 2.6 1.0 1.8 14.0 230 4.95
6 0.31 3.5 1.0 1.8 15.5 297 3.30
10 0.41 4.6 1.0 1.8 18.0 422 1.91
16 0.41 5.7 1.0 1.8 20.0 562 1.21
25 0.41 7.1 1.2 1.8 23.5 809 0.780
35 0.41 8.4 1.2 1.8 26.0 1061 0.554
50 0.41 10.1 1.4 1.8 30.5 1451 0.386
70 0.51 12.0 1.4 1.9 34.5 1949 0.272
95 0.51 13.7 1.6 2.0 39.0 2546 0.206
120 0.51 15.5 1.6 2.1 43.0 3160 0.161

Note : Shape of conductor : Flexible stranded class 5

Page - 11
Section 2 - PVC Insulated Cables
Unarmoured Cables

450/750 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC Flexible (IEC 60227-5, SPLN 42-6-3)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Brown, Black, Grey
Sheath - Black

THREE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Maximum Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.)
mm² mm mm mm mm mm kg/km /km

1.5 0.26 1.6 0.7 1.8 11.0 153 13.3


2.5 0.26 2.0 0.8 1.8 12.5 204 7.98
4 0.31 2.6 1.0 1.8 14.5 287 4.95
6 0.31 3.5 1.0 1.8 16.5 380 3.30
10 0.41 4.6 1.0 1.8 19.0 552 1.91
16 0.41 5.7 1.0 1.8 21.0 744 1.21
25 0.41 7.1 1.2 1.8 25.0 1085 0.780
35 0.41 8.4 1.2 1.8 28.0 1443 0.554
50 0.41 10.1 1.4 1.8 32.5 1986 0.386
70 0.51 12.0 1.4 2.0 37.0 2702 0.272
95 0.51 13.7 1.6 2.1 42.0 3542 0.206
120 0.51 15.5 1.6 2.2 46.0 4408 0.161

Note : Shape of conductor : Flexible stranded class 5

Page - 12
Section 2 - PVC Insulated Cables
Unarmoured Cables

450/750 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC Flexible (IEC 60227-5, SPLN 42-6-3)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Brown, Black, Grey, Blue
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Overall Maximum
Nominal Maximum Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.)
mm² mm mm mm mm mm kg/km /km

1.5 0.26 1.6 0.7 1.8 12.0 181 13.3


2.5 0.26 2.0 0.8 1.8 13.5 247 7.98
4 0.31 2.6 1.0 1.8 16.0 353 4.95
6 0.31 3.5 1.0 1.8 18.0 471 3.30
10 0.41 4.6 1.0 1.8 20.5 696 1.91
16 0.41 5.7 1.0 1.8 23.5 942 1.21
25 0.41 7.1 1.2 1.8 27.5 1390 0.780
35 0.41 8.4 1.2 1.8 31.0 1856 0.554
50 0.41 10.1 1.4 1.9 36.0 2579 0.386
70 0.51 12.0 1.4 2.1 41.0 3517 0.272
95 0.51 13.7 1.6 2.2 47.0 4610 0.206
120 0.51 15.5 1.6 2.4 51.5 5769 0.161

Note : Shape of conductor : Flexible stranded class 5

Page - 13
Section 2 - PVC Insulated Cables
Unarmoured Cables

450/750 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC Flexible (IEC 60227-5, SPLN 42-6-3)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Brown, Black, Grey, Blue, Green / Yellow stripe
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Maximum Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² mm mm mm mm mm kg/km /km

1.5 0.26 1.6 0.7 1.8 13.0 215 13.3


2.5 0.26 2.0 0.8 1.8 14.5 290 7.98
4 0.31 2.6 1.0 1.8 17.0 425 4.95
6 0.31 3.5 1.0 1.8 19.5 567 3.30
10 0.41 4.6 1.0 1.8 22.5 847 1.91
16 0.41 5.7 1.0 1.8 25.5 1154 1.21
25 0.41 7.1 1.2 1.8 30.5 1703 0.780
35 0.41 8.4 1.2 1.9 34.0 2297 0.554
50 0.41 10.1 1.4 2.0 40.0 3200 0.386

Note : Shape of conductor : Flexible stranded class 5

Page - 14
Section 2 - PVC Insulated Cables
Unarmoured Cables

450/750 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC Flexible (IEC 60227-5, SPLN 42-6-3)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 1.5 mm²


Conductor Nominal Nominal Overall Maximum
Maximum Diameter Thickness Thickness diameter Weight Conductor
No Diameter of of of of of Resistance
of of wire Conductor Insulation Sheath cable cable at 20°C
core (approx.) (approx.) (approx.) (approx.)
mm mm mm mm mm kg/km /km

6 0.26 1.6 0.7 1.8 14.0 240 13.3


7 0.26 1.6 0.7 1.8 14.0 258 13.3
8 0.26 1.6 0.7 1.8 15.0 295 13.3
9 0.26 1.6 0.7 1.8 16.0 326 13.3
10 0.26 1.6 0.7 1.8 17.0 360 13.3
12 0.26 1.6 0.7 1.8 17.5 408 13.3
14 0.26 1.6 0.7 1.8 18.5 458 13.3
15 0.26 1.6 0.7 1.8 19.0 489 13.3
16 0.26 1.6 0.7 1.8 19.0 514 13.3
18 0.26 1.6 0.7 1.8 20.0 562 13.3
19 0.26 1.6 0.7 1.8 20.0 580 13.3
20 0.26 1.6 0.7 1.8 21.0 614 13.3
24 0.26 1.6 0.7 1.8 23.5 725 13.3
30 0.26 1.6 0.7 1.8 24.5 868 13.3
32 0.26 1.6 0.7 1.8 25.0 921 13.3
37 0.26 1.6 0.7 1.8 26.5 1034 13.3
40 0.26 1.6 0.7 1.8 27.5 1110 13.3
50 0.26 1.6 0.7 1.9 30.5 1374 13.3
52 0.26 1.6 0.7 1.9 31.5 1424 13.3
60 0.26 1.6 0.7 1.9 33.0 1617 13.3
61 0.26 1.6 0.7 1.9 33.0 1635 13.3

Note : Shape of conductor : Flexible stranded class 5

Page - 15
Section 2 - PVC Insulated Cables
Unarmoured Cables

450/750 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC Flexible (IEC 60227-5, SPLN 42-6-3)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 2.5 mm²


Conductor Nominal Nominal Overall Maximum
Maximum Diameter Thickness Thickness diameter Weight Conductor
No Diameter of of of of of Resistance
of of wire Conductor Insulation Sheath cable cable at 20°C
core (approx.) (approx.) (approx.) (approx.)
mm mm mm mm mm kg/km /km

6 0.26 2.0 0.8 1.8 15.5 331 7.98


7 0.26 2.0 0.8 1.8 15.5 358 7.98
8 0.26 2.0 0.8 1.8 17.0 406 7.98
9 0.26 2.0 0.8 1.8 18.0 455 7.98
10 0.26 2.0 0.8 1.8 19.5 505 7.98
12 0.26 2.0 0.8 1.8 20.0 577 7.98
14 0.26 2.0 0.8 1.8 21.0 654 7.98
15 0.26 2.0 0.8 1.8 21.5 697 7.98
16 0.26 2.0 0.8 1.8 22.0 732 7.98
18 0.26 2.0 0.8 1.8 23.0 806 7.98
19 0.26 2.0 0.8 1.8 23.0 834 7.98
20 0.26 2.0 0.8 1.8 24.0 887 7.98
24 0.26 2.0 0.8 1.8 27.0 1049 7.98
30 0.26 2.0 0.8 1.8 28.5 1266 7.98
32 0.26 2.0 0.8 1.8 29.0 1342 7.98
37 0.26 2.0 0.8 1.9 31.0 1527 7.98
40 0.26 2.0 0.8 1.9 32.0 1644 7.98
50 0.26 2.0 0.8 2.0 35.5 2037 7.98
52 0.26 2.0 0.8 2.0 36.5 2115 7.98
60 0.26 2.0 0.8 2.1 39.0 2423 7.98
61 0.26 2.0 0.8 2.1 39.0 2450 7.98

Note : Shape of conductor : Flexible stranded class 5

Page - 16
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (acc. to IEC 60502-1)

1 1

2 2

5 5

Constructions : Note : Special application upon request


1 Conductor (Annealed Copper) * Available product in accordance to : SPLN, ICEA/NEMA,
2 Insulation (PVC Compound) AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
3 Filler (Polyprophylene yarn,or extruded filler * Anti termite performance.
up to request) * Tin coated Copper conductor.
4 Binding tape (Manufacturer's option) * Polyethylene / Low smoke Halogen Free sheathed

5 Outer sheath (PVC Compound)

Page - 17
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Sheath : PVC Compound type ST1 Maximum 70°C
Colour Ident. : Insulation - Brown
Sheath - Black

SINGLE CORE
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of Resistance
section cond. of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.)
mm² - number mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.4 5.6 50 12.1
1.5 RM 7 1.6 0.8 1.4 5.8 50 12.1
2.5 RE 1 1.78 0.8 1.4 6.0 60 7.41
2.5 RM 7 2.0 0.8 1.4 6.2 65 7.41
4 RE 1 2.26 1.0 1.4 6.9 85 4.61
4 RM 7 2.6 1.0 1.4 7.2 90 4.61
6 RM 7 3.1 1.0 1.4 7.7 115 3.08
10 RM 7 4.1 1.0 1.4 8.7 160 1.83
16 RM 7 5.1 1.0 1.4 9.7 225 1.15
25 RM 7 6.4 1.2 1.4 11.5 335 0.727
35 RM 7 7.6 1.2 1.4 12.5 440 0.524
50 RM 19 9.2 1.4 1.4 14.5 600 0.387
70 RM 19 10.9 1.4 1.4 16.5 810 0.268
95 RM 19 12.6 1.6 1.5 19.0 1090 0.193
120 RM 37 14.2 1.6 1.5 20.5 1335 0.153
150 RM 37 15.9 1.8 1.6 22.5 1660 0.124
185 RM 37 17.6 2.0 1.7 25.0 2025 0.0991
240 RM 61 20.3 2.2 1.8 28.0 2650 0.0754
300 RM 61 22.7 2.4 1.9 31.0 3275 0.0601
400 RM 61 25.7 2.6 2.0 35.0 4190 0.0470
500 RM 61 28.8 2.8 2.1 38.5 5200 0.0366
630 RM 91 32.6 2.8 2.2 42.5 6505 0.0283
800 RM 127 37.1 2.8 2.3 47.5 8285 0.0221
1000 RM 127 41.6 3.0 2.5 52.5 10360 0.0176
Note *) RE : Round Solid Class 1
RM : Circular Stranded Class 2

Page - 18
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Blue
Sheath - Black

TWO CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of Resistance
section area Conductor of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.)
mm² - number mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.8 10.0 115 12.1
1.5 RM 7 1.6 0.8 1.8 10.5 125 12.1
2.5 RE 1 1.78 0.8 1.8 10.5 145 7.41
2.5 RM 7 2.0 0.8 1.8 11.0 155 7.41
4 RE 1 2.26 1.0 1.8 12.5 200 4.61
4 RM 7 2.6 1.0 1.8 13.0 215 4.61
6 RM 7 3.1 1.0 1.8 14.0 270 3.08
10 RM 7 4.1 1.0 1.8 16.0 375 1.83
16 RM 7 5.1 1.0 1.8 18.0 520 1.15
25 RM 7 6.4 1.2 1.8 21.5 765 0.727
35 RM 7 7.6 1.2 1.8 24.0 1000 0.524
50 RM 19 9.2 1.4 1.8 28.0 1370 0.387
70 RM 19 10.9 1.4 1.9 31.5 1825 0.268
95 RM 19 12.6 1.6 2.0 36.0 2440 0.193
120 RM 37 14.2 1.6 2.1 39.5 2990 0.153
150 RM 37 15.9 1.8 2.2 44.0 3715 0.124
185 RM 37 17.6 2.0 2.4 48.5 4545 0.0991
240 RM 61 20.3 2.2 2.6 55.0 5945 0.0754
300 RM 61 22.7 2.4 2.7 60.5 7325 0.0601

Note *) RE : Round Solid Class 1


RM : Circular Stranded Class 2

Page - 19
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey
Sheath - Black

THREE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of Resistance
section area conductor of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.8 10.5 140 12.1
1.5 RM 7 1.6 0.8 1.8 11.0 150 12.1
2.5 RE 1 1.78 0.8 1.8 11.5 180 7.41
2.5 RM 7 2.0 0.8 1.8 11.5 190 7.41
4 RE 1 2.26 1.0 1.8 13.0 260 4.61
4 RM 7 2.6 1.0 1.8 14.0 275 4.61
6 RM 7 3.1 1.0 1.8 15.0 350 3.08
10 RM 7 4.1 1.0 1.8 17.0 500 1.83
16 RM 7 5.1 1.0 1.8 19.0 700 1.15
25 RM 7 6.4 1.2 1.8 23.0 1045 0.727
35 RM 7 7.6 1.2 1.8 25.5 1380 0.524
50 SM 19 6.8 1.4 1.8 24.0 1710 0.387
70 SM 19 8.2 1.4 2.0 27.5 2365 0.268
95 SM 19 9.7 1.6 2.1 32.0 3265 0.193
120 SM 37 10.9 1.6 2.2 34.5 3905 0.153
150 SM 37 11.9 1.8 2.3 37.5 4785 0.124
185 SM 37 13.6 2.0 2.5 42.5 5965 0.0991
240 SM 37 15.8 2.2 2.7 48.0 7970 0.0754
300 SM 37 17.5 2.4 2.9 53.0 9920 0.0601

Note *) RE : Round Solid Class 1


RM : Circular Stranded Class 2
RM : Three Segmental Stranded Compacted Class 2

Page - 20
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey, Blue
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of Resistance
section area conductor of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.8 11.0 170 12.1
1.5 RM 7 1.6 0.8 1.8 11.5 180 12.1
2.5 RE 1 1.78 0.8 1.8 12.0 220 7.41
2.5 RM 7 2.0 0.8 1.8 12.5 235 7.41
4 RE 1 2.26 1.0 1.8 14.5 320 4.61
4 RM 7 2.6 1.0 1.8 15.0 340 4.61
6 RM 7 3.1 1.0 1.8 16.5 435 3.08
10 RM 7 4.1 1.0 1.8 18.5 635 1.83
16 RM 7 5.1 1.0 1.8 21.0 900 1.15
25 RM 7 6.4 1.2 1.8 25.0 1345 0.727
35 RM 7 7.6 1.2 1.8 28.0 1780 0.524
50 SM 19 8.1 1.4 1.9 27.5 2210 0.387
70 SM 19 9.7 1.4 2.1 31.5 3090 0.268
95 SM 19 11.4 1.6 2.2 36.5 4255 0.193
120 SM 37 12.9 1.6 2.4 40.0 5100 0.153
150 SM 37 14.2 1.8 2.5 43.5 6265 0.124
185 SM 37 16.0 2.0 2.7 49.0 7815 0.0991
240 SM 37 18.2 2.2 2.9 54.5 10425 0.0754
300 SM 37 20.6 2.4 3.1 61.0 12985 0.0601

Note *) RE : Round Solid Class 1


RM : Circular Stranded Class 2
RM : Four Segmental Stranded Compacted Class 2

Page - 21
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey, Blue, Green / Yellow Stripe
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of Resistance
section area conductor of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.8 12.0 200 12.1
1.5 RM 7 1.6 0.8 1.8 12.5 215 12.1
2.5 RE 1 1.78 0.8 1.8 13.0 265 7.41
2.5 RM 7 2.0 0.8 1.8 14.0 280 7.41
4 RE 1 2.26 1.0 1.8 15.5 385 4.61
4 RM 7 2.6 1.0 1.8 16.5 410 4.61
6 RM 7 3.1 1.0 1.8 18.0 530 3.08
10 RM 7 4.1 1.0 1.8 20.5 775 1.83
16 RM 7 5.1 1.0 1.8 23.0 1100 1.15
25 RM 7 6.4 1.2 1.8 28.0 1655 0.727
35 RM 7 7.6 1.2 1.9 31.0 2200 0.524
50 RM 19 9.2 1.4 2.1 37.0 3080 0.387

Note *) RE : Round Solid Class 1


RM : Circular Stranded Class 2

Page - 22
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 1.5 mm² (Solid conductor)


Conductor Nominal Nominal Overall Maximum
No Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
of Cross-section of Number of of of of of Resistance
core area conductor of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
6 1.5 RE 1 1.38 0.8 1.8 13.0 230 12.1
7 1.5 RE 1 1.38 0.8 1.8 13.0 245 12.1
8 1.5 RE 1 1.38 0.8 1.8 14.0 280 12.1
9 1.5 RE 1 1.38 0.8 1.8 15.0 310 12.1
10 1.5 RE 1 1.38 0.8 1.8 16.5 345 12.1
12 1.5 RE 1 1.38 0.8 1.8 17.0 395 12.1
14 1.5 RE 1 1.38 0.8 1.8 17.5 445 12.1
15 1.5 RE 1 1.38 0.8 1.8 18.0 470 12.1
16 1.5 RE 1 1.38 0.8 1.8 18.5 500 12.1
18 1.5 RE 1 1.38 0.8 1.8 19.5 550 12.1
19 1.5 RE 1 1.38 0.8 1.8 19.5 565 12.1
20 1.5 RE 1 1.38 0.8 1.8 20.0 600 12.1
21 1.5 RE 1 1.38 0.8 1.8 21.0 625 12.1
24 1.5 RE 1 1.38 0.8 1.8 22.5 710 12.1
30 1.5 RE 1 1.38 0.8 1.8 24.0 855 12.1
32 1.5 RE 1 1.38 0.8 1.8 24.5 905 12.1
37 1.5 RE 1 1.38 0.8 1.8 26.0 1025 12.1
40 1.5 RE 1 1.38 0.8 1.8 27.0 1105 12.1
50 1.5 RE 1 1.38 0.8 1.9 29.5 1350 12.1
52 1.5 RE 1 1.38 0.8 1.9 30.5 1405 12.1
60 1.5 RE 1 1.38 0.8 2.0 32.5 1615 12.1
61 1.5 RE 1 1.38 0.8 2.0 32.5 1635 12.1

Note RE : Round solid class 1

Page - 23
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 1.5 mm² (Stranded conductor)


Conductor Nominal Nominal Overall Maximum
No Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
of Cross-section of Number of of of of of Resistance
core area conductor of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
6 1.5 RM 7 1.6 0.8 1.8 13.5 240 12.1
7 1.5 RM 7 1.6 0.8 1.8 13.5 260 12.1
8 1.5 RM 7 1.6 0.8 1.8 14.5 295 12.1
9 1.5 RM 7 1.6 0.8 1.8 16.0 330 12.1
10 1.5 RM 7 1.6 0.8 1.8 17.0 365 12.1
12 1.5 RM 7 1.6 0.8 1.8 17.5 420 12.1
14 1.5 RM 7 1.6 0.8 1.8 18.5 475 12.1
15 1.5 RM 7 1.6 0.8 1.8 19.0 500 12.1
16 1.5 RM 7 1.6 0.8 1.8 19.5 530 12.1
18 1.5 RM 7 1.6 0.8 1.8 20.5 585 12.1
19 1.5 RM 7 1.6 0.8 1.8 20.5 600 12.1
20 1.5 RM 7 1.6 0.8 1.8 21.0 635 12.1
21 1.5 RM 7 1.6 0.8 1.8 22.0 665 12.1
24 1.5 RM 7 1.6 0.8 1.8 24.0 755 12.1
30 1.5 RM 7 1.6 0.8 1.8 25.5 910 12.1
32 1.5 RM 7 1.6 0.8 1.8 26.0 965 12.1
37 1.5 RM 7 1.6 0.8 1.8 27.5 1090 12.1
40 1.5 RM 7 1.6 0.8 1.8 28.5 1175 12.1
50 1.5 RM 7 1.6 0.8 1.9 31.0 1440 12.1
52 1.5 RM 7 1.6 0.8 1.9 32.0 1495 12.1
60 1.5 RM 7 1.6 0.8 2.0 34.5 1720 12.1
61 1.5 RM 7 1.6 0.8 2.0 34.5 1745 12.1

Note : RM : Circular Stranded Class 2

Page - 24
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 2.5 mm² (Solid conductor)


Conductor Nominal Nominal Overall Maximum
No Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
of Cross-section of Number of of of of of Resistance
core area conductor of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
6 2.5 RE 1 1.78 0.8 1.8 14.5 300 7.41
7 2.5 RE 1 1.78 0.8 1.8 14.5 330 7.41
8 2.5 RE 1 1.78 0.8 1.8 15.5 375 7.41
9 2.5 RE 1 1.78 0.8 1.8 16.5 420 7.41
10 2.5 RE 1 1.78 0.8 1.8 18.0 465 7.41
12 2.5 RE 1 1.78 0.8 1.8 18.5 535 7.41
14 2.5 RE 1 1.78 0.8 1.8 19.5 610 7.41
15 2.5 RE 1 1.78 0.8 1.8 20.0 645 7.41
16 2.5 RE 1 1.78 0.8 1.8 20.5 685 7.41
18 2.5 RE 1 1.78 0.8 1.8 21.5 755 7.41
19 2.5 RE 1 1.78 0.8 1.8 21.5 780 7.41
20 2.5 RE 1 1.78 0.8 1.8 22.0 825 7.41
21 2.5 RE 1 1.78 0.8 1.8 23.5 865 7.41
24 2.5 RE 1 1.78 0.8 1.8 25.0 985 7.41
30 2.5 RE 1 1.78 0.8 1.8 26.5 1195 7.41
32 2.5 RE 1 1.78 0.8 1.8 27.0 1265 7.41
37 2.5 RE 1 1.78 0.8 1.9 28.5 1435 7.41
40 2.5 RE 1 1.78 0.8 1.9 30.0 1545 7.41
50 2.5 RE 1 1.78 0.8 2.0 33.0 1920 7.41
52 2.5 RE 1 1.78 0.8 2.0 34.0 1995 7.41
60 2.5 RE 1 1.78 0.8 2.1 36.5 2295 7.41
61 2.5 RE 1 1.78 0.8 2.1 36.5 2325 7.41

Note : RE : Round Solid Class 1

Page - 25
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 2.5 mm² (Stranded conductor)


Conductor Nominal Nominal Overall Maximum
No Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
of Cross-section of Number of of of of of Resistance
core area conductor of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
6 2.5 RM 7 2.0 0.8 1.8 15.0 320 7.41
7 2.5 RM 7 2.0 0.8 1.8 15.0 345 7.41
8 2.5 RM 7 2.0 0.8 1.8 16.0 395 7.41
9 2.5 RM 7 2.0 0.8 1.8 17.0 440 7.41
10 2.5 RM 7 2.0 0.8 1.8 18.5 490 7.41
12 2.5 RM 7 2.0 0.8 1.8 19.5 565 7.41
14 2.5 RM 7 2.0 0.8 1.8 20.5 640 7.41
15 2.5 RM 7 2.0 0.8 1.8 21.0 680 7.41
16 2.5 RM 7 2.0 0.8 1.8 21.5 725 7.41
18 2.5 RM 7 2.0 0.8 1.8 22.5 795 7.41
19 2.5 RM 7 2.0 0.8 1.8 22.5 825 7.41
20 2.5 RM 7 2.0 0.8 1.8 23.0 870 7.41
21 2.5 RM 7 2.0 0.8 1.8 24.0 910 7.41
24 2.5 RM 7 2.0 0.8 1.8 26.5 1040 7.41
30 2.5 RM 7 2.0 0.8 1.8 28.0 1260 7.41
32 2.5 RM 7 2.0 0.8 1.8 28.5 1335 7.41
37 2.5 RM 7 2.0 0.8 1.9 30.0 1515 7.41
40 2.5 RM 7 2.0 0.8 1.9 31.5 1635 7.41
50 2.5 RM 7 2.0 0.8 2.0 34.5 2025 7.41
52 2.5 RM 7 2.0 0.8 2.0 35.5 2105 7.41
60 2.5 RM 7 2.0 0.8 2.1 38.0 2420 7.41
61 2.5 RM 7 2.0 0.8 2.1 38.0 2455 7.41

Note : RM : Circular Stranded Class 2

Page - 26
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 clas 1) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 4 mm² (Solid conductor)


Conductor Nominal Nominal Overall Maximum
No Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
of Cross-section of Number of of of of of Resistance
core area conductor of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
6 4 RE 1 2.26 1.0 1.8 17.0 440 4.61
7 4 RE 1 2.26 1.0 1.8 17.0 485 4.61
8 4 RE 1 2.26 1.0 1.8 18.5 555 4.61
9 4 RE 1 2.26 1.0 1.8 20.0 625 4.61
10 4 RE 1 2.26 1.0 1.8 21.5 690 4.61
12 4 RE 1 2.26 1.0 1.8 22.0 800 4.61
14 4 RE 1 2.26 1.0 1.8 23.5 915 4.61
15 4 RE 1 2.26 1.0 1.8 24.0 970 4.61
16 4 RE 1 2.26 1.0 1.8 24.5 1035 4.61
18 4 RE 1 2.26 1.0 1.8 26.0 1140 4.61
19 4 RE 1 2.26 1.0 1.8 26.0 1185 4.61
20 4 RE 1 2.26 1.0 1.8 27.0 1250 4.61
21 4 RE 1 2.26 1.0 1.8 28.0 1310 4.61
24 4 RE 1 2.26 1.0 1.9 30.5 1495 4.61
30 4 RE 1 2.26 1.0 2.0 32.5 1840 4.61
32 4 RE 1 2.26 1.0 2.0 33.0 1950 4.61
37 4 RE 1 2.26 1.0 2.1 35.5 2235 4.61
40 4 RE 1 2.26 1.0 2.1 37.0 2410 4.61
50 4 RE 1 2.26 1.0 2.3 41.0 3010 4.61
52 4 RE 1 2.26 1.0 2.3 42.0 3130 4.61
60 4 RE 1 2.26 1.0 2.4 45.0 3575 4.61
61 4 RE 1 2.26 1.0 2.4 45.0 3625 4.61

Note RE : Round Solid Class 1

Page - 27
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED AND PVC SHEATHED CABLES


PVC/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 clas 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 4 mm² (Stranded conductor)


Conductor Nominal Nominal Overall Maximum
No Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
of Cross-section of Number of of of of of Resistance
core area conductor of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
6 4 RM 7 2.6 1.0 1.8 18.0 470 4.61
7 4 RM 7 2.6 1.0 1.8 18.0 515 4.61
8 4 RM 7 2.6 1.0 1.8 19.5 585 4.61
9 4 RM 7 2.6 1.0 1.8 21.0 660 4.61
10 4 RM 7 2.6 1.0 1.8 22.5 735 4.61
12 4 RM 7 2.6 1.0 1.8 23.5 850 4.61
14 4 RM 7 2.6 1.0 1.8 24.5 970 4.61
15 4 RM 7 2.6 1.0 1.8 25.5 1030 4.61
16 4 RM 7 2.6 1.0 1.8 26.0 1095 4.61
18 4 RM 7 2.6 1.0 1.8 27.5 1210 4.61
19 4 RM 7 2.6 1.0 1.8 27.5 1255 4.61
20 4 RM 7 2.6 1.0 1.8 28.5 1325 4.61
21 4 RM 7 2.6 1.0 1.8 30.0 1390 4.61
24 4 RM 7 2.6 1.0 1.9 32.5 1585 4.61
30 4 RM 7 2.6 1.0 2.0 34.5 1950 4.61
32 4 RM 7 2.6 1.0 2.0 35.0 2070 4.61
37 4 RM 7 2.6 1.0 2.1 37.5 2365 4.61
40 4 RM 7 2.6 1.0 2.1 39.0 2555 4.61
50 4 RM 7 2.6 1.0 2.3 43.5 3190 4.61
52 4 RM 7 2.6 1.0 2.3 44.5 3315 4.61
60 4 RM 7 2.6 1.0 2.4 47.5 3790 4.61
61 4 RM 7 2.6 1.0 2.4 47.5 3845 4.61

Note RM : Circular Stranded Class 2

Page - 28
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES


PVC/PVC-S (IEC 60502-1)

Constructions : Note : Special application upon request


1 Conductor (Annealed Copper) * Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
2 Insulation (PVC Compound)
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
3 Filler (Polyprophylene yarn,or extruded filler * Anti termite performance.
up to request) * Tin coated Copper conductor.
4 * Copper wire screen.
Binding tape (Manufacturer's option)
* Polyethylene / Low smoke Halogen Free sheathed
5 Copper Tape screen
6 Binding tape (Manufacturer's option)
7 Outer sheath (PVC Compound)

Page - 29
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES


PVC/PVC-S (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Blue
Sheath - Black

TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of of Resistance
section area cond. of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm mm kg/km /km

1.5 RE 1 1.38 0.8 0.1 1.8 10.5 145 12.1


1.5 RM 7 1.6 0.8 0.1 1.8 11.0 150 12.1
2.5 RE 1 1.78 0.8 0.1 1.8 11.5 175 7.41
2.5 RM 7 2.0 0.8 0.1 1.8 11.5 180 7.41
4 RE 1 2.26 1.0 0.1 1.8 13.0 240 4.61
4 RM 7 2.6 1.0 0.1 1.8 13.5 245 4.61
6 RM 7 3.1 1.0 0.1 1.8 14.5 305 3.08
10 RM 7 4.1 1.0 0.1 1.8 16.5 420 1.83
16 RM 7 5.1 1.0 0.1 1.8 18.5 570 1.15
25 RM 7 6.4 1.2 0.1 1.8 22.0 825 0.727
35 RM 7 7.6 1.2 0.1 1.8 24.5 1065 0.524
50 RM 19 9.2 1.4 0.1 1.8 28.5 1450 0.387
70 RM 19 10.9 1.4 0.1 1.9 32.0 1910 0.268
95 RM 19 12.6 1.6 0.1 2.0 36.5 2545 0.193
120 RM 37 14.2 1.6 0.1 2.1 40.0 3105 0.153
150 RM 37 15.9 1.8 0.1 2.2 44.5 3840 0.124
185 RM 37 17.6 2.0 0.1 2.4 49.0 4680 0.0991
240 RM 61 20.3 2.2 0.1 2.6 55.5 6100 0.0754
300 RM 61 22.7 2.4 0.1 2.7 61.5 7525 0.0601
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2

Page - 30
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES


PVC/PVC-S (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey
Sheath - Black

THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of of Resistance
section area cond. of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 0.1 1.8 11.0 170 12.1
1.5 RM 7 1.6 0.8 0.1 1.8 11.5 175 12.1
2.5 RE 1 1.78 0.8 0.1 1.8 12.0 215 7.41
2.5 RM 7 2.0 0.8 0.1 1.8 12.5 220 7.41
4 RE 1 2.26 1.0 0.1 1.8 14.0 300 4.61
4 RM 7 2.6 1.0 0.1 1.8 14.5 305 4.61
6 RM 7 3.1 1.0 0.1 1.8 15.0 385 3.08
10 RM 7 4.1 1.0 0.1 1.8 17.5 545 1.83
16 RM 7 5.1 1.0 0.1 1.8 20.0 755 1.15
25 RM 7 6.4 1.2 0.1 1.8 23.5 1110 0.727
35 RM 7 7.6 1.2 0.1 1.8 26.0 1445 0.524
50 SM 19 6.8 1.4 0.1 1.9 25.0 1775 0.387
70 SM 19 8.2 1.4 0.1 2.0 28.0 2440 0.268
95 SM 19 9.7 1.6 0.1 2.1 32.5 3350 0.193
120 SM 37 10.9 1.6 0.1 2.2 35.0 3995 0.153
150 SM 37 11.9 1.8 0.1 2.4 38.5 4885 0.124
185 SM 37 13.6 2.0 0.1 2.5 43.0 6080 0.0991
240 SM 37 15.8 2.2 0.1 2.7 48.5 8095 0.0754
300 SM 37 17.5 2.4 0.1 2.9 53.5 10060 0.0601
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
SM : Three Segmental Stranded Compacted Class 2

Page - 31
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES


PVC/PVC-S (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey, Blue
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of of Resistance
section area cond. of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm mm kg/km /km

1.5 RE 1 1.38 0.8 0.1 1.8 12.0 205 12.1


1.5 RM 7 1.6 0.8 0.1 1.8 12.5 210 12.1
2.5 RE 1 1.78 0.8 0.1 1.8 13.0 260 7.41
2.5 RM 7 2.0 0.8 0.1 1.8 13.5 265 7.41
4 RE 1 2.26 1.0 0.1 1.8 15.0 370 4.61
4 RM 7 2.6 1.0 0.1 1.8 15.5 380 4.61
6 RM 7 3.1 1.0 0.1 1.8 17.0 485 3.08
10 RM 7 4.1 1.0 0.1 1.8 19.5 685 1.83
16 RM 7 5.1 1.0 0.1 1.8 21.5 960 1.15
25 RM 7 6.4 1.2 0.1 1.8 26.0 1415 0.727
35 RM 7 7.6 1.2 0.1 1.8 28.5 1860 0.524
50 SM 19 8.1 1.4 0.1 2.0 28.5 2305 0.387
70 SM 19 9.7 1.4 0.1 2.1 32.0 3180 0.268
95 SM 19 11.4 1.6 0.1 2.2 37.0 4360 0.193
120 SM 37 12.9 1.6 0.1 2.4 40.5 5220 0.153
150 SM 37 14.2 1.8 0.1 2.5 44.5 6395 0.124
185 SM 37 16.0 2.0 0.1 2.7 49.5 7965 0.0991
240 SM 37 18.2 2.2 0.1 2.9 55.5 10595 0.0754
300 SM 37 20.6 2.4 0.1 3.1 61.5 13180 0.0601
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
SM : Four Segmental Stranded Compacted Class 2

Page - 32
Section 2 - PVC Insulated Cables
Unarmoured Cables

600/1000 V PVC INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES


PVC/PVC-S (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey, Blue,, Green / Yellow Stripe
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of of Resistance
section area cond. of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm mm kg/km /km

1.5 RE 1 1.38 0.8 0.1 1.8 12.5 240 12.1


1.5 RM 7 1.6 0.8 0.1 1.8 13.5 245 12.1
2.5 RE 1 1.78 0.8 0.1 1.8 14.0 305 7.41
2.5 RM 7 2.0 0.8 0.1 1.8 14.5 315 7.41
4 RE 1 2.26 1.0 0.1 1.8 16.5 435 4.61
4 RM 7 2.6 1.0 0.1 1.8 17.0 450 4.61
6 RM 7 3.1 1.0 0.1 1.8 18.5 580 3.08
10 RM 7 4.1 1.0 0.1 1.8 21.0 830 1.83
16 RM 7 5.1 1.0 0.1 1.8 24.0 1170 1.15
25 RM 7 6.4 1.2 0.1 1.8 28.5 1730 0.727
35 RM 7 7.6 1.2 0.1 1.9 31.5 2290 0.524
50 RM 19 9.2 1.4 0.1 2.1 37.5 3060 0.387
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2

Page - 33
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, ALUMINIUM WIRE ARMOURED AND PVC SHEATHED CABLES
PVC / AWA / PVC (acc. to IEC 60502-1)

1
Constructions :
2 1 Conductor (Annealed Copper)
3 2 Insulation (PVC Compound)
3 Inner Covering (PVC Compound)
4
4 Round Aluminium Wire armour
5
5 Binding tape (Manufacturer's option)
6 Outer sheath (PVC Compound)
6

600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC / SWA / PVC (acc. to IEC 60502-1)

1 Constructions :
1 Conductor (Annealed Copper)
2
2 Insulation (PVC Compound)
3 3 Filler (Polyprophylene yarn,or extruded filler
4 up to request)
5 4 Binding tape (Manufacturer's option)
5 Inner Covering (PVC Compound)
6
6 Galvanized Round Steel Wire armour
7
7 Binding tape (Manufacturer's option)
8 Outer sheath (PVC Compound)
8

Note : Special application upon request


* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed

Page - 34
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED,ALUMINIUM WIRE ARMOURED AND PVC SHEATHED CABLES


PVC / AWA / PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Inner covering : PVC Compound ST1 Maximum 70°C
Armour : Aluminium Wire
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown
Sheath - Black

SINGLE CORE
Conductor Nominal Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter of Thickness diameter Weight Conductor
Cross- of number of of of inner Aluminium of of of Resistance
section Cond. of wire Conductor Insulation covering wire Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km

16 RM 7 5.1 1.0 1.0 0.8 1.8 14.5 370 1.15

25 RM 7 6.4 1.2 1.0 0.8 1.8 16.5 495 0.727

35 RM 7 7.6 1.2 1.0 0.8 1.8 17.5 620 0.524

50 RM 19 9.2 1.4 1.0 1.25 1.8 20.5 845 0.387

70 RM 19 10.9 1.4 1.0 1.25 1.8 22.0 1075 0.268

95 RM 19 12.6 1.6 1.0 1.25 1.8 24.5 1380 0.193

120 RM 37 14.2 1.6 1.0 1.6 1.8 27.0 1705 0.153

150 RM 37 15.9 1.8 1.0 1.6 1.8 29.0 2055 0.124

185 RM 37 17.6 2.0 1.0 1.6 1.8 31.0 2450 0.0991

240 RM 61 20.3 2.2 1.0 1.6 1.9 34.0 3110 0.0754

300 RM 61 22.7 2.4 1.0 2.0 2.0 38.0 3865 0.0601

400 RM 61 25.7 2.6 1.2 2.0 2.1 42.0 4885 0.0470

500 RM 61 28.8 2.8 1.2 2.0 2.2 46.0 5965 0.0366

630 RM 91 32.6 2.8 1.2 2.0 2.4 50.0 7335 0.0283

800 RM 127 37.1 2.8 1.4 2.5 2.5 56.0 9410 0.0221

1000 RM 127 41.6 3.0 1.4 2.5 2.7 61.0 11635 0.0176

Note : RM : Circular Stranded Class 2

Page - 35
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC / SWA / PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Blue
Sheath - Black

TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Diameter Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. of of of Resistance
section Cond. of wire Conductor Insulation covering Steel wire Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.8 1.8 14.0 335 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 1.8 14.5 350 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 1.8 15.0 380 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 1.8 15.5 395 7.41
4 RE 1 2.26 1.0 1.0 0.8 1.8 16.5 475 4.61
4 RM 7 2.6 1.0 1.0 0.8 1.8 17.5 495 4.61
6 RM 7 3.12 1.0 1.0 1.25 1.8 19.0 670 3.08
10 RM 7 4.1 1.0 1.0 1.25 1.8 21.0 840 1.83
16 RM 7 5.1 1.0 1.0 1.25 1.8 23.0 1020 1.15
25 RM 7 6.4 1.2 1.0 1.6 1.8 27.5 1510 0.727
35 RM 7 7.6 1.2 1.0 1.6 1.8 30.0 1810 0.524
50 RM 19 9.2 1.4 1.0 1.6 1.9 34.0 2320 0.387
70 RM 19 10.9 1.4 1.0 2.0 2.0 38.0 3125 0.268
95 RM 19 12.6 1.6 1.2 2.0 2.2 43.5 3990 0.193
120 RM 37 14.2 1.6 1.2 2.0 2.3 47.0 4695 0.153
150 RM 37 15.9 1.8 1.2 2.5 2.4 52.0 5995 0.124
185 RM 37 17.6 2.0 1.4 2.5 2.6 57.0 7110 0.0991
240 RM 61 20.3 2.2 1.4 2.5 2.8 63.5 8830 0.0754
300 RM 61 22.7 2.4 1.6 2.5 2.9 70.0 10575 0.0601

Note : RE : Round Solid Class 1


RM : Circular Stranded Class 2

Page - 36
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC / SWA / PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey
Sheath - Black

THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Diameter Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. of of of Resistance
section Cond. of wire Conductor Insulation covering Steel wire Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.8 1.8 14.5 375 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 1.8 15.0 385 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 1.8 15.5 430 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 1.8 16.0 450 7.41
4 RE 1 2.26 1.0 1.0 0.8 1.8 18.0 640 4.61
4 RM 7 2.6 1.0 1.0 1.25 1.8 18.5 660 4.61
6 RM 7 3.1 1.0 1.0 1.25 1.8 20.0 770 3.08
10 RM 7 4.1 1.0 1.0 1.25 1.8 22.0 975 1.83
16 RM 7 5.1 1.0 1.0 1.25 1.8 24.0 1230 1.15
25 RM 7 6.4 1.2 1.0 1.6 1.8 29.0 1820 0.727
35 RM 7 7.6 1.2 1.0 1.6 1.8 31.5 2230 0.524
50 SM 19 6.8 1.4 1.0 1.6 2.0 30.5 2560 0.387
70 SM 19 8.2 1.4 1.2 2.0 2.1 34.5 3580 0.268
95 SM 19 9.7 1.6 1.2 2.0 2.2 39.0 4655 0.193
120 SM 37 10.9 1.6 1.2 2.0 2.3 42.0 5410 0.153
150 SM 37 11.9 1.8 1.4 2.5 2.5 46.0 6830 0.124
185 SM 37 13.6 2.0 1.4 2.5 2.7 51.0 8260 0.0991
240 SM 37 15.8 2.2 1.6 2.5 2.9 57.0 10635 0.0754
300 SM 37 17.5 2.4 1.6 2.5 3.1 62.0 12795 0.0601

Note : RE : Round Solid Class 1


RM : Circular Stranded Class 2
SM : Three Segmental Stranded Compacted Class 2

Page - 37
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC / SWA / PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey, Blue
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Diameter Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. of of of Resistance
section Cond. of wire Conductor Insulation covering Steel wire Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.8 1.8 15.5 415 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 1.8 16.0 435 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 1.8 16.5 490 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 1.8 17.0 510 7.41
4 RE 1 2.26 1.0 1.0 0.8 1.8 19.5 740 4.61
4 RM 7 2.6 1.0 1.0 1.25 1.8 20.0 765 4.61
6 RM 7 3.1 1.0 1.0 1.25 1.8 21.0 895 3.08
10 RM 7 4.1 1.0 1.0 1.25 1.8 23.5 1145 1.83
16 RM 7 5.1 1.0 1.0 1.6 1.8 27.0 1625 1.15
25 RM 7 6.4 1.2 1.0 1.6 1.8 31.0 2185 0.727
35 RM 7 7.6 1.2 1.0 1.6 1.9 34.0 2700 0.524
50 SM 19 8.1 1.4 1.2 2.0 2.1 35.0 3470 0.387
70 SM 19 9.7 1.4 1.2 2.0 2.2 38.5 4455 0.268
95 SM 19 11.4 1.6 1.2 2.5 2.4 44.5 6225 0.193
120 SM 37 12.9 1.6 1.4 2.5 2.5 48.5 7250 0.153
150 SM 37 14.2 1.8 1.4 2.5 2.7 52.5 8665 0.124
185 SM 37 16.0 2.0 1.6 2.5 2.9 58.0 10505 0.0991
240 SM 37 18.2 2.2 1.6 2.5 3.1 63.5 13415 0.0754
300 SM 37 20.6 2.4 1.6 2.5 3.3 70.0 16300 0.0601

Note : RE : Round Solid Class 1


RM : Circular Stranded Class 2
SM : Four Segmental Stranded Compacted Class 2

Page - 38
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC / SWA / PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey, Blue, Green / Yellow Stripe
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Diameter Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. of of of Resistance
section Cond. of wire Conductor Insulation covering Steel wire Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.8 1.8 16.5 465 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 1.8 17.0 490 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 1.8 17.5 555 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 1.8 18.0 575 7.41
4 RE 1 2.26 1.0 1.0 0.8 1.8 20.5 835 4.61
4 RM 7 2.6 1.0 1.0 1.25 1.8 21.5 865 4.61
6 RM 7 3.1 1.0 1.0 1.25 1.8 22.5 1025 3.08
10 RM 7 4.1 1.0 1.0 1.6 1.8 26.5 1480 1.83
16 RM 7 5.1 1.0 1.0 1.60 1.8 29.0 1893 1.15
25 RM 7 6.4 1.2 1.0 1.6 1.9 33.5 2580 0.727
35 RM 7 7.6 1.2 1.0 2.0 2.0 38.0 3470 0.524
50 RM 19 9.2 1.4 1.2 2.0 2.2 44.0 4505 0.387

Note : RE : Round Solid Class 1


RM : Circular Stranded Class 2

Page - 39
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (acc. to IEC 60502-1)

Constructions :
1 Conductor (Annealed Copper) Note : Special application upon request
2 Insulation (PVC Compound) * Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
3 Filler (Polyprophylene yarn,or extruded filler
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
up to request) * Anti termite performance.
4 Binding tape (Manufacturer's option) * Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed
5 Inner Covering (PVC Compound)
6 Galvanized Flat Steel Wire armour
7 Galvanized Steel Tape binding
8 Outer sheath (PVC Compound)

Page - 40
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Blue
Sheath - Black

TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. thickness of of of Resistance
section Cond. of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² Number mm mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.8 0.3 1.8 14.0 410 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 0.3 1.8 14.5 420 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 0.3 1.8 15.0 445 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 0.3 1.8 15.5 480 7.41
4 RE 1 2.26 1.0 1.0 0.8 0.3 1.8 17.0 570 4.61
4 RM 7 2.6 1.0 1.0 0.8 0.3 1.8 17.5 585 4.61
6 RM 7 3.1 1.0 1.0 0.8 0.3 1.8 18.5 675 3.08
10 RM 7 4.1 1.0 1.0 0.8 0.3 1.8 20.5 830 1.83
16 RM 7 5.1 1.0 1.0 0.8 0.3 1.8 22.5 1040 1.15
25 RM 7 6.4 1.2 1.0 0.8 0.3 1.8 26.0 1365 0.727
35 RM 7 7.6 1.2 1.0 0.8 0.3 1.8 28.0 1675 0.524
50 RM 19 9.2 1.4 1.0 0.8 0.3 1.8 32.0 2135 0.387
70 RM 19 10.9 1.4 1.0 0.8 0.3 1.9 35.5 2695 0.268
95 RM 19 12.6 1.6 1.2 0.8 0.3 2.1 41.0 3485 0.193
120 RM 37 14.2 1.6 1.2 0.8 0.3 2.2 44.5 4150 0.153
150 RM 37 15.9 1.8 1.2 0.8 0.3 2.3 49.0 4995 0.124
185 RM 37 17.6 2.0 1.4 0.8 0.3 2.4 53.5 5970 0.0991
240 RM 61 20.3 2.2 1.4 0.8 0.3 2.6 60.0 7540 0.0754
300 RM 61 22.7 2.4 1.6 0.8 0.3 2.8 66.5 9180 0.0601

Note : RE : Round Solid Class 1


RM : Circular Stranded Class 2

Page - 41
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey
Sheath - Black

THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. thickness of of of Resistance
section Cond. of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.8 0.3 1.8 14.5 440 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 0.3 1.8 15.0 450 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 0.3 1.8 15.5 510 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 0.3 1.8 16.0 525 7.41
4 RE 1 2.26 1.0 1.0 0.8 0.3 1.8 17.5 635 4.61
4 RM 7 2.6 1.0 1.0 0.8 0.3 1.8 18.0 650 4.61
6 RM 7 3.1 1.0 1.0 0.8 0.3 1.8 19.0 760 3.08
10 RM 7 4.1 1.0 1.0 0.8 0.3 1.8 21.5 985 1.83
16 RM 7 5.1 1.0 1.0 0.8 0.3 1.8 23.5 1230 1.15
25 RM 7 6.4 1.2 1.0 0.8 0.3 1.8 27.0 1685 0.727
35 RM 7 7.6 1.2 1.0 0.8 0.3 1.8 30.0 2090 0.524
50 SM 19 6.8 1.4 1.0 0.8 0.3 1.9 28.5 2385 0.387
70 SM 19 8.2 1.4 1.2 0.8 0.3 2.0 32.0 3150 0.268
95 SM 19 9.7 1.6 1.2 0.8 0.3 2.2 37.0 4185 0.193
120 SM 37 10.9 1.6 1.2 0.8 0.3 2.3 39.5 4905 0.153
150 SM 37 11.9 1.8 1.4 0.8 0.3 2.4 43.0 5890 0.124
185 SM 37 13.6 2.0 1.4 0.8 0.3 2.6 47.5 7215 0.0991
240 SM 37 15.8 2.2 1.6 0.8 0.3 2.8 54.0 9460 0.0754
300 SM 37 17.5 2.4 1.6 0.8 0.3 2.9 58.5 11520 0.0601

Note : RE : Round Solid Class 1


RM : Circular Stranded Class 2
SM : Three Segmental Stranded Compacted Class 2

Page - 42
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey, Blue
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. thickness of of of Resistance
section Cond. of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.8 0.3 1.8 15.5 500 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 0.3 1.8 16.0 510 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 0.3 1.8 16.5 560 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 0.3 1.8 17.0 605 7.41
4 RE 1 2.26 1.0 1.0 0.8 0.3 1.8 18.5 735 4.61
4 RM 7 2.6 1.0 1.0 0.8 0.3 1.8 19.5 755 4.61
6 RM 7 3.1 1.0 1.0 0.8 0.3 1.8 20.5 890 3.08
10 RM 7 4.1 1.0 1.0 0.8 0.3 1.8 23.0 1160 1.83
16 RM 7 5.1 1.0 1.0 0.8 0.3 1.8 25.5 1500 1.15
25 RM 7 6.4 1.2 1.0 0.8 0.3 1.8 29.5 2055 0.727
35 RM 7 7.6 1.2 1.0 0.8 0.3 1.9 32.5 2570 0.524
50 SM 19 8.1 1.4 1.2 0.8 0.3 2.0 32.5 3045 0.387
70 SM 19 9.7 1.4 1.2 0.8 0.3 2.1 36.0 3995 0.268
95 SM 19 11.4 1.6 1.2 0.8 0.3 2.3 41.5 5310 0.193
120 SM 37 12.9 1.6 1.4 0.8 0.3 2.4 45.0 6290 0.153
150 SM 37 14.2 1.8 1.4 0.8 0.3 2.6 49.0 7570 0.124
185 SM 37 16.0 2.0 1.6 0.8 0.3 2.7 54.5 9310 0.0991
240 SM 37 18.2 2.2 1.6 0.8 0.3 3.0 60.5 12120 0.0754
300 SM 37 20.6 2.4 1.6 0.8 0.3 3.2 66.5 14865 0.0601

Note : RE : Round Solid Class 1


RM : Circular Stranded Class 2
SM : Four Segmental Stranded Compacted Class 2

Page - 43
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey, Blue, Green / Yellow Stripe
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. thickness of of of Resistance
section of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.8 0.3 1.8 16.5 540 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 0.3 1.8 17.0 580 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 0.3 1.8 17.5 635 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 0.3 1.8 18.0 655 7.41
4 RE 1 2.26 1.0 1.0 0.8 0.3 1.8 20.0 835 4.61
4 RM 7 2.6 1.0 1.0 0.8 0.3 1.8 21.0 860 4.61
6 RM 7 3.1 1.0 1.0 0.8 0.3 1.8 22.0 1025 3.08
10 RM 7 4.1 1.0 1.0 0.8 0.3 1.8 25.0 1340 1.83
16 RM 7 5.1 1.0 1.0 0.8 0.3 1.8 27.5 1745 1.15
25 RM 7 6.4 1.2 1.0 0.8 0.3 1.8 32.0 2415 0.727
35 RM 7 7.6 1.2 1.0 0.8 0.3 1.9 35.5 3070 0.524
50 RM 19 9.2 1.4 1.2 0.8 0.3 2.1 41.5 4015 0.387

Note : RE : Round Solid Class 1


RM : Circular Stranded Class 2

Page - 44
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, ALUMINIUM TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DATA/PVC (acc. to IEC 60502-1)

Constructions :
2
1 Conductor (Annealed Copper)
3 2 Insulation (PVC Compound)
4 3 Inner Covering (PVC Compound)
4 Double Aluminium Tape armour
5 Outer sheath (PVC Compound)
5

600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DSTA/PVC (acc. to IEC 60502-1)

Constructions :
1
1 Conductor (Annealed Copper)
2 Insulation (PVC Compound)
2
3 Filler (Polyprophylene yarn,or extruded filler
3
up to request)
4
4
Binding tape (Manufacturer's option)
5
5 Inner Covering (PVC Compound)
6 6 Double Galvanized Steel Tape armour
7 Outer sheath (PVC Compound)
6

Note : Special application upon request


7
6
* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed

Page - 45
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, ALUMINIUM TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DATA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Inner covering : PVC Compound Maximum 70°C
Armour : Double Aluminium tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown
Sheath - Black

SINGLE CORE
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- of number of of of Inner thickness of of of of Resistance
section Cond. of wire Conductor Insulation covering Aluminium Sheath cable cable at 20°C
area (approx.) (approx.) tape (approx.) (approx.)
mm² number mm mm mm mm mm mm kg/km /km
50 RM 19 9.2 1.4 1.0 0.5 1.8 19.5 820 0.387
70 RM 19 10.9 1.4 1.0 0.5 1.8 21.0 1045 0.268
95 RM 19 12.6 1.6 1.0 0.5 1.8 23.5 1345 0.193
120 RM 37 14.2 1.6 1.0 0.5 1.8 25.0 1610 0.153
150 RM 37 15.9 1.8 1.0 0.5 1.8 27.0 1950 0.124
185 RM 37 17.6 2.0 1.0 0.5 1.8 29.5 2340 0.0991
240 RM 61 20.3 2.2 1.0 0.5 1.9 32.5 2990 0.0754
300 RM 61 22.7 2.4 1.0 0.5 1.9 35.0 3630 0.0601
400 RM 61 25.7 2.6 1.2 0.5 2.1 39.5 4640 0.0470
500 RM 61 28.8 2.8 1.2 0.5 2.2 43.5 5695 0.0366

Note RM : Circular Stranded Class 2

Page - 46
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DSTA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Blue
Sheath - Black

TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. of of of Resistance
section Cond. of wire Conductor Insulation covering Steel tape Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.2 1.8 13.0 240 12.1
1.5 RM 7 1.6 0.8 1.0 0.2 1.8 13.0 250 12.1
2.5 RE 1 1.78 0.8 1.0 0.2 1.8 13.5 280 7.41
2.5 RM 7 2.0 0.8 1.0 0.2 1.8 14.0 290 7.41
4 RE 1 2.26 1.0 1.0 0.2 1.8 15.5 360 4.61
4 RM 7 2.6 1.0 1.0 0.2 1.8 16.0 375 4.61
6 RM 7 3.1 1.0 1.0 0.2 1.8 17.0 440 3.08
10 RM 7 4.1 1.0 1.0 0.2 1.8 19.0 575 1.83
16 RM 7 5.1 1.0 1.0 0.2 1.8 21.0 745 1.15
25 RM 7 6.4 1.2 1.0 0.2 1.8 24.5 1030 0.727
35 RM 7 7.6 1.2 1.0 0.2 1.8 27.0 1290 0.524
50 RM 19 9.2 1.4 1.0 0.2 1.8 31.0 1715 0.387
70 RM 19 10.9 1.4 1.0 0.2 1.9 34.0 2265 0.268
95 RM 19 12.6 1.6 1.2 0.2 2.1 39.0 2900 0.193
120 RM 37 14.2 1.6 1.2 0.5 2.2 43.5 3925 0.153
150 RM 37 15.9 1.8 1.2 0.5 2.3 48.0 4725 0.124
185 RM 37 17.6 2.0 1.4 0.5 2.4 52.5 5675 0.0991
240 RM 61 20.3 2.2 1.4 0.5 2.6 58.5 7170 0.0754
300 RM 61 22.7 2.4 1.6 0.5 2.8 64.5 8710 0.0601

Note RE : Round Solid Class 1


RM : Circular Stranded Class 2

Page - 47
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DSTA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey
Sheath - Black

THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. of of of Resistance
section Cond. of wire Conductor Insulation covering Steel tape Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.2 1.8 13.5 270 12.1
1.5 RM 7 1.6 0.8 1.0 0.2 1.8 13.5 285 12.1
2.5 RE 1 1.78 0.8 1.0 0.2 1.8 14.0 320 7.41
2.5 RM 7 2.0 0.8 1.0 0.2 1.8 14.5 335 7.41
4 RE 1 2.26 1.0 1.0 0.2 1.8 16.0 420 4.61
4 RM 7 2.6 1.0 1.0 0.2 1.8 16.5 445 4.61
6 RM 7 3.1 1.0 1.0 0.2 1.8 18.0 530 3.08
10 RM 7 4.1 1.0 1.0 0.2 1.8 20.0 710 1.83
16 RM 7 5.1 1.0 1.0 0.2 1.8 22.0 935 1.15
25 RM 7 6.4 1.2 1.0 0.2 1.8 26.0 1330 0.727
35 RM 7 7.6 1.2 1.0 0.2 1.8 28.5 1685 0.524
50 SM 19 6.8 1.4 1.0 0.2 1.9 27.0 2005 0.387
70 SM 19 8.2 1.4 1.2 0.2 2.0 30.5 2725 0.268
95 SM 19 9.7 1.6 1.2 0.5 2.2 36.5 4065 0.193
120 SM 37 10.9 1.6 1.2 0.5 2.3 39.5 4765 0.153
150 SM 37 11.9 1.8 1.4 0.5 2.4 42.5 5745 0.124
185 SM 37 13.6 2.0 1.4 0.5 2.6 47.5 7055 0.0991
240 SM 37 15.8 2.2 1.6 0.5 2.8 53.5 9255 0.0754
300 SM 37 17.5 2.4 1.6 0.5 2.9 58.0 11300 0.0601

Note : RE : Round Solid Class 1


RM : Circular Stranded Class 2
SM : Three Segmental Stranded Compacted Class 2

Page - 48
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC / DSTA / PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey, Blue
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. of of of Resistance
section Cond. of wire Conductor Insulation covering Steel tape Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.2 1.8 14.0 310 12.1
1.5 RM 7 1.6 0.8 1.0 0.2 1.8 14.5 325 12.1
2.5 RE 1 1.78 0.8 1.0 0.2 1.8 15.0 375 7.41
2.5 RM 7 2.0 0.8 1.0 0.2 1.8 15.5 390 7.41
4 RE 1 2.26 1.0 1.0 0.2 1.8 17.5 500 4.61
4 RM 7 2.6 1.0 1.0 0.2 1.8 18.0 525 4.61
6 RM 7 3.1 1.0 1.0 0.2 1.8 19.0 640 3.08
10 RM 7 4.1 1.0 1.0 0.2 1.8 21.5 860 1.83
16 RM 7 5.1 1.0 1.0 0.2 1.8 24.0 1160 1.15
25 RM 7 6.4 1.2 1.0 0.2 1.8 28.0 1650 0.727
35 RM 7 7.6 1.2 1.0 0.2 1.8 31.0 2120 0.524
50 SM 19 8.1 1.4 1.2 0.2 2.0 31.0 2595 0.387
70 SM 19 9.7 1.4 1.2 0.5 2.1 36.0 3865 0.268
95 SM 19 11.4 1.6 1.2 0.5 2.3 41.0 5175 0.193
120 SM 37 12.9 1.6 1.4 0.5 2.4 44.5 6125 0.153
150 SM 37 14.2 1.8 1.4 0.5 2.6 49.0 7405 0.124
185 SM 37 16.0 2.0 1.6 0.5 2.7 54.0 9115 0.0991
240 SM 37 18.2 2.2 1.6 0.5 3.0 60.0 11900 0.0754
300 SM 37 20.6 2.4 1.6 0.5 3.2 66.5 14625 0.0601

Note : RE : Round Solid Class 1


RM : Circular Stranded Class 2
SM : Three Segmental Stranded Compacted Class 2

Page - 49
Section 2 - PVC Insulated Cables
Armoured Cables

600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DSTA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey, Blue, Green / Yellow Stripe
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. of of of Resistance
section Cond. of wire Conductor Insulation covering Steel tape Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.2 1.8 15.0 350 12.1
1.5 RM 7 1.6 0.8 1.0 0.2 1.8 15.5 370 12.1
2.5 RE 1 1.78 0.8 1.0 0.2 1.8 16.0 425 7.41
2.5 RM 7 2.0 0.8 1.0 0.2 1.8 16.5 450 7.41
4 RE 1 2.26 1.0 1.0 0.2 1.8 18.5 580 4.61
4 RM 7 2.6 1.0 1.0 0.2 1.8 19.5 610 4.61
6 RM 7 3.1 1.0 1.0 0.2 1.8 20.5 750 3.08
10 RM 7 4.1 1.0 1.0 0.2 1.8 23.5 1025 1.83
16 RM 7 5.1 1.0 1.0 0.2 1.8 26.0 1390 1.15
25 RM 7 6.4 1.2 1.0 0.2 1.8 30.5 1995 0.727
35 RM 7 7.6 1.2 1.0 0.2 1.9 34.0 2580 0.524
50 RM 19 9.2 1.4 1.2 0.2 2.1 40.0 3400 0.387

Note : RE : Round Solid Class 1


RM : Circular Stranded Class 2

Page - 50
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES


XLPE/PVC (IEC 60502-1)

Constructions : Note : Special application upon request


1 Conductor (Annealed Copper) * Available product in accordance to : SPLN, ICEA/NEMA,
2 Insulation (XLPE Compound) AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
3 Filler (Polyprophylene yarn,or extruded filler * Anti termite performance.
up to request) * Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed
4 Binding tape (Manufacturer's option)
5 Outer sheath (PVC Compound)

Page - 51
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES


XLPE / PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Sheath : PVC Compound type ST2 Maximum 90°C
Colour Ident. : Insulation - Brown
Sheath - Black

SINGLE CORE
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of Resistance
section Cond. of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.4 5.4 45 12.1
1.5 RM 7 1.6 0.7 1.4 5.6 45 12.1
2.5 RE 1 1.78 0.7 1.4 5.8 55 7.41
2.5 RM 7 2.0 0.7 1.4 6.0 55 7.41
4 RE 1 2.26 0.7 1.4 6.3 75 4.61
4 RM 7 2.6 0.7 1.4 6.6 75 4.61
6 RM 7 3.1 0.7 1.4 7.1 100 3.08
10 RM 7 4.1 0.7 1.4 8.1 140 1.83
16 CM 7 4.7 0.7 1.4 8.7 195 1.15
25 CM 7 5.9 0.9 1.4 10.5 290 0.727
35 CM 7 7.1 0.9 1.4 11.5 385 0.524
50 CM 19 8.1 1.0 1.4 12.5 500 0.387
70 CM 19 9.7 1.1 1.4 14.5 700 0.268
95 CM 19 11.6 1.1 1.5 16.5 955 0.193
120 CM 37 12.9 1.2 1.5 18.0 1190 0.153
150 CM 37 14.3 1.4 1.6 20.0 1475 0.124
185 CM 37 16.0 1.6 1.6 22.5 1825 0.0991
240 CM 37 18.3 1.7 1.7 25.0 2360 0.0754
300 CM 61 20.7 1.8 1.8 27.5 2945 0.0601
400 CM 61 23.4 2.0 1.9 31.0 3740 0.0470
500 CM 61 26.5 2.2 2.0 34.5 4780 0.0366
630 CM 91 30.3 2.4 2.2 39.5 6165 0.0283
800 CM 91 34.3 2.6 2.3 44.0 7860 0.0221
1000 RM 127 41.6 2.8 2.4 52.0 10030 0.0176

Note RE : Round Solid Class 1, RM : Circular Stranded Class 2, CM : Circular Stranded Compacted Class 2
Page - 52
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES


XLPE / PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Blue
Sheath - Black

TWO CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of Resistance
section Cond. of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.8 9.5 105 12.1
1.5 RM 7 1.6 0.7 1.8 10.0 110 12.1
2.5 RE 1 1.78 0.7 1.8 10.5 130 7.41
2.5 RM 7 2.0 0.7 1.8 10.5 135 7.41
4 RE 1 2.26 0.7 1.8 11.5 170 4.61
4 RM 7 2.6 0.7 1.8 12.0 180 4.61
6 RM 7 3.1 0.7 1.8 13.0 230 3.08
10 RM 7 4.1 0.7 1.8 15.0 330 1.83
16 CM 7 4.7 0.7 1.8 16.0 445 1.15
25 CM 7 5.9 0.9 1.8 19.5 660 0.727
35 CM 7 7.1 0.9 1.8 21.5 870 0.524
50 CM 19 8.1 1.0 1.8 24.0 1130 0.387
70 CM 19 9.7 1.1 1.8 27.5 1570 0.268
95 CM 19 11.6 1.1 2.0 31.5 2125 0.193
120 CM 37 12.9 1.2 2.1 35.0 2645 0.153
150 CM 37 14.3 1.4 2.2 38.5 3275 0.124
185 CM 37 16.0 1.6 2.3 43.5 4075 0.0991
240 CM 37 18.3 1.7 2.5 48.5 5270 0.0754
300 CM 61 20.7 1.8 2.7 54.5 6575 0.0601
400 CM 61 23.4 2.0 2.9 61.0 8355 0.0470

Note RE : Round Solid Class 1


RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2

Page - 53
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES


XLPE / PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey
Sheath - Black

THREE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of Resistance
section Cond. of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.8 10.0 125 12.1
1.5 RM 7 1.6 0.7 1.8 10.5 130 12.1
2.5 RE 1 1.78 0.7 1.8 11.0 160 7.41
2.5 RM 7 2.0 0.7 1.8 11.5 170 7.41
4 RE 1 2.26 0.7 1.8 12.0 215 4.61
4 RM 7 2.6 0.7 1.8 12.5 230 4.61
6 RM 7 3.1 0.7 1.8 13.5 295 3.08
10 RM 7 4.1 0.7 1.8 16.0 435 1.83
16 CM 7 4.7 0.7 1.8 17.0 605 1.15
25 CM 7 5.9 0.9 1.8 20.5 900 0.727
35 CM 7 7.1 0.9 1.8 23.0 1200 0.524
50 CM 19 8.1 1.0 1.8 25.5 1570 0.387
70 CM 19 9.7 1.1 1.9 29.5 2200 0.268
95 CM 19 11.6 1.1 2.0 34.0 2995 0.193
120 CM 37 12.9 1.2 2.1 37.5 3735 0.153
150 CM 37 14.3 1.4 2.3 41.5 4650 0.124
185 CM 37 16.0 1.6 2.4 46.5 5760 0.0991
240 CM 37 18.3 1.7 2.6 52.5 7500 0.0754
300 CM 61 20.7 1.8 2.8 58.5 9360 0.0601
400 CM 61 23.4 2.0 3.1 65.5 11900 0.0470

Note RE : Round Solid Class 1


RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2

Page - 54
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES


XLPE / PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey, Blue
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of Resistance
section Cond. of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km

1.5 RE 1 1.38 0.7 1.8 10.5 150 12.1


1.5 RM 7 1.6 0.7 1.8 11.0 155 12.1
2.5 RE 1 1.78 0.7 1.8 11.5 195 7.41
2.5 RM 7 2.0 0.7 1.8 12.0 205 7.41
4 RE 1 2.26 0.7 1.8 13.0 270 4.61
4 RM 7 2.6 0.7 1.8 13.5 280 4.61
6 RM 7 3.1 0.7 1.8 15.0 370 3.08
10 RM 7 4.1 0.7 1.8 17.5 550 1.83
16 CM 7 4.7 0.7 1.8 18.5 770 1.15
25 CM 7 5.9 0.9 1.8 22.5 1160 0.727
35 CM 7 7.1 0.9 1.8 25.5 1550 0.524
50 CM 19 8.1 1.0 1.9 28.5 2040 0.387
70 CM 19 9.7 1.1 2.0 33.0 2880 0.268
95 CM 19 11.6 1.1 2.1 37.5 3925 0.193
120 CM 37 12.9 1.2 2.3 41.5 4920 0.153
150 CM 37 14.3 1.4 2.4 46.0 6075 0.124
185 CM 37 16.0 1.6 2.6 52.0 7585 0.0991
240 CM 37 18.3 1.7 2.8 58.5 9870 0.0754
300 CM 61 20.7 1.8 3.0 65.0 12320 0.0601

Note RE : Round Solid Class 1


RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2

Page - 55
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES


XLPE / PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey, Blue, Green / Yellow Stripe
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of Resistance
section Cond. of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.8 11.5 175 12.1
1.5 RM 7 1.6 0.7 1.8 12.0 185 12.1
2.5 RE 1 1.78 0.7 1.8 12.5 235 7.41
2.5 RM 7 2.0 0.7 1.8 13.0 245 7.41
4 RE 1 2.26 0.7 1.8 14.0 320 4.61
4 RM 7 2.6 0.7 1.8 15.0 340 4.61
6 RM 7 3.1 0.7 1.8 16.0 450 3.08
10 RM 7 4.1 0.7 1.8 19.0 675 1.83
16 CM 7 4.7 0.7 1.8 20.5 945 1.15
25 CM 7 5.9 0.9 1.8 25.0 1425 0.727
35 CM 7 7.1 0.9 1.8 28.0 1915 0.524
50 CM 19 8.1 1.0 2.0 31.5 2535 0.387

Note RE : Round Solid Class 1


RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2

Page - 56
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES


XLPE / PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 clas 1) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler (if necessary) : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 1.5 mm² (Solid conductor)


Conductor Nominal Nominal Overall Maximum
No Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
of Cross-section of number of of of of of Resistance
core area Cond. of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
6 1.5 RE 1 1.38 0.7 1.8 12.5 200 12.1
7 1.5 RE 1 1.38 0.7 1.8 12.5 210 12.1
8 1.5 RE 1 1.38 0.7 1.8 13.5 240 12.1
9 1.5 RE 1 1.38 0.7 1.8 14.3 265 12.1
10 1.5 RE 1 1.38 0.7 1.8 15.5 295 12.1
12 1.5 RE 1 1.38 0.7 1.8 16.0 335 12.1
14 1.5 RE 1 1.38 0.7 1.8 16.5 380 12.1
15 1.5 RE 1 1.38 0.7 1.8 17.0 400 12.1
16 1.5 RE 1 1.38 0.7 1.8 17.5 425 12.1
18 1.5 RE 1 1.38 0.7 1.8 18.5 465 12.1
19 1.5 RE 1 1.38 0.7 1.8 18.5 480 12.1
20 1.5 RE 1 1.38 0.7 1.8 19.0 505 12.1
24 1.5 RE 1 1.38 0.7 1.8 21.5 600 12.1
30 1.5 RE 1 1.38 0.7 1.8 22.5 720 12.1
32 1.5 RE 1 1.38 0.7 1.8 23.0 760 12.1
37 1.5 RE 1 1.38 0.7 1.8 24.5 855 12.1
40 1.5 RE 1 1.38 0.7 1.8 25.5 920 12.1
50 1.5 RE 1 1.38 0.7 1.9 28.0 1125 12.1
52 1.5 RE 1 1.38 0.7 1.9 29.5 1210 12.1
60 1.5 RE 1 1.38 0.7 1.9 30.5 1330 12.1
61 1.5 RE 1 1.38 0.7 1.9 30.5 1350 12.1

Note RE : Round Solid Class 1

Page - 57
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES


XLPE / PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 clas 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler (if necessary) : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 1.5 mm² (Stranded conductor)


Conductor Nominal Nominal Overall Maximum
No Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
of Cross-section of number of of of of of Resistance
core area Cond. of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
6 1.5 RM 7 1.6 0.7 1.8 13.0 210 12.1
7 1.5 RM 7 1.6 0.7 1.8 13.0 220 12.1
8 1.5 RM 7 1.6 0.7 1.8 14.0 250 12.1
9 1.5 RM 7 1.6 0.7 1.8 15.0 280 12.1
10 1.5 RM 7 1.6 0.7 1.8 16.5 310 12.1
12 1.5 RM 7 1.6 0.7 1.8 17.0 355 12.1
14 1.5 RM 7 1.6 0.7 1.8 17.5 400 12.1
15 1.5 RM 7 1.6 0.7 1.8 18.0 420 12.1
16 1.5 RM 7 1.6 0.7 1.8 18.5 445 12.1
18 1.5 RM 7 1.6 0.7 1.8 19.5 490 12.1
19 1.5 RM 7 1.6 0.7 1.8 19.5 500 12.1
20 1.5 RM 7 1.6 0.7 1.8 20.0 530 12.1
24 1.5 RM 7 1.6 0.7 1.8 22.5 630 12.1
30 1.5 RM 7 1.6 0.7 1.8 24.0 755 12.1
32 1.5 RM 7 1.6 0.7 1.8 24.5 795 12.1
37 1.5 RM 7 1.6 0.7 1.8 26.0 900 12.1
40 1.5 RM 7 1.6 0.7 1.8 27.0 965 12.1
50 1.5 RM 7 1.6 0.7 1.9 29.5 1185 12.1
52 1.5 RM 7 1.6 0.7 1.9 30.5 1230 12.1
60 1.5 RM 7 1.6 0.7 1.9 32.5 1395 12.1
61 1.5 RM 7 1.6 0.7 1.9 32.5 1415 12.1

Note RM : Circular Stranded Class 2

Page - 58
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES


XLPE / PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler (if necessary) : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 2.5 mm² (Solid conductor)


Conductor Nominal Nominal Overall Maximum
No Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
of Cross-section of number of of of of of Resistance
core area Cond. of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
6 2.5 RE 1 1.78 0.7 1.8 13.5 265 7.41
7 2.5 RE 1 1.78 0.7 1.8 13.5 290 7.41
8 2.5 RE 1 1.78 0.7 1.8 14.5 330 7.41
9 2.5 RE 1 1.78 0.7 1.8 16.0 370 7.41
10 2.5 RE 1 1.78 0.7 1.8 17.0 410 7.41
12 2.5 RE 1 1.78 0.7 1.8 17.5 465 7.41
14 2.5 RE 1 1.78 0.7 1.8 18.5 530 7.41
15 2.5 RE 1 1.78 0.7 1.8 19.0 565 7.41
16 2.5 RE 1 1.78 0.7 1.8 19.5 595 7.41
18 2.5 RE 1 1.78 0.7 1.8 20.5 655 7.41
19 2.5 RE 1 1.78 0.7 1.8 20.5 680 7.41
20 2.5 RE 1 1.78 0.7 1.8 21.0 715 7.41
24 2.5 RE 1 1.78 0.7 1.8 24.0 855 7.41
30 2.5 RE 1 1.78 0.7 1.8 25.5 1035 7.41
32 2.5 RE 1 1.78 0.7 1.8 26.0 1095 7.41
37 2.5 RE 1 1.78 0.7 1.8 27.5 1240 7.41
40 2.5 RE 1 1.78 0.7 1.9 28.5 1335 7.41
50 2.5 RE 1 1.78 0.7 2.0 31.5 1655 7.41
52 2.5 RE 1 1.78 0.7 2.0 32.5 1720 7.41
60 2.5 RE 1 1.78 0.7 2.0 34.5 1965 7.41
61 2.5 RE 1 1.78 0.7 2.0 34.5 1990 7.41

Note RE : Round Solid Class 1

Page - 59
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES


XLPE / PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler (if necessary) : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

CONTROL CABLE : 2.5 mm² (Stranded conductor)


Conductor Nominal Nominal Overall Maximum
No Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
of Cross-section of number of of of of of Resistance
core area Cond. of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
6 2.5 RM 7 2.0 0.7 1.8 14.5 280 7.41
7 2.5 RM 7 2.0 0.7 1.8 14.5 300 7.41
8 2.5 RM 7 2.0 0.7 1.8 15.5 340 7.41
9 2.5 RM 7 2.0 0.7 1.8 16.5 385 7.41
10 2.5 RM 7 2.0 0.7 1.8 18.0 425 7.41
12 2.5 RM 7 2.0 0.7 1.8 18.5 485 7.41
14 2.5 RM 7 2.0 0.7 1.8 19.5 555 7.41
15 2.5 RM 7 2.0 0.7 1.8 20.0 585 7.41
16 2.5 RM 7 2.0 0.7 1.8 20.5 620 7.41
18 2.5 RM 7 2.0 0.7 1.8 21.5 685 7.41
19 2.5 RM 7 2.0 0.7 1.8 21.5 705 7.41
20 2.5 RM 7 2.0 0.7 1.8 22.0 745 7.41
24 2.5 RM 7 2.0 0.7 1.8 25.0 890 7.41
30 2.5 RM 7 2.0 0.7 1.8 26.5 1075 7.41
32 2.5 RM 7 2.0 0.7 1.8 27.0 1140 7.41
37 2.5 RM 7 2.0 0.7 1.8 28.5 1290 7.41
40 2.5 RM 7 2.0 0.7 1.9 30.0 1390 7.41
50 2.5 RM 7 2.0 0.7 2.0 33.0 1710 7.41
52 2.5 RM 7 2.0 0.7 2.0 34.0 1790 7.41
60 2.5 RM 7 2.0 0.7 2.0 36.0 2040 7.41
61 2.5 RM 7 2.0 0.7 2.0 36.0 2070 7.41

Note RM : Circular Stranded Class 2

Page - 60
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES


XLPE / PVC-S (IEC 60502-1)

1 Constructions :
1 Conductor (Annealed Copper)
2 2 Insulation (XLPE Compound)
3 Filler (Polyprophylene yarn,or extruded filler
up to request)
3
4 Binding tape (Manufacturer's option)
4 5 Copper Tape screen
6 Binding tape (Manufacturer's option)
5
7 Outer sheath (PVC Compound)

7 Note : Special application upon request


* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Copper wire screen.
* Polyethylene / Low smoke Halogen Free sheathed

Page - 61
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES


XLPE / PVC-S (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Blue
Sheath - Black

TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of of Resistance
section area Cond. of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 0.1 1.8 10.0 125 12.1
1.5 RM 7 1.6 0.7 0.1 1.8 10.5 135 12.1
2.5 RE 1 1.78 0.7 0.1 1.8 11.0 155 7.41
2.5 RM 7 2.0 0.7 0.1 1.8 11.5 165 7.41
4 RE 1 2.26 0.7 0.1 1.8 12.0 200 4.61
4 RM 7 2.6 0.7 0.1 1.8 12.5 210 4.61
6 RE 1 2.77 0.7 0.1 1.8 13.0 250 3.08
6 RM 7 3.1 0.7 0.1 1.8 13.5 265 3.08
10 RM 7 4.1 0.7 0.1 1.8 15.5 370 1.83
16 CM 7 4.7 0.7 0.1 1.8 16.5 490 1.15
25 CM 7 5.9 0.9 0.1 1.8 20.0 715 0.727
35 CM 7 7.1 0.9 0.1 1.8 22.5 935 0.524
50 CM 19 8.1 1.0 0.1 1.8 24.5 1200 0.387
70 CM 19 9.7 1.1 0.1 1.9 28.5 1650 0.268
95 CM 19 11.6 1.1 0.1 2.0 32.5 2225 0.193
120 CM 37 12.9 1.2 0.1 2.1 35.5 2755 0.153
150 CM 37 14.3 1.4 0.1 2.2 39.5 3395 0.124
185 CM 37 16.0 1.6 0.1 2.3 44.0 4205 0.0991
240 CM 37 18.3 1.7 0.1 2.5 49.5 5425 0.0754
300 CM 61 20.7 1.8 0.1 2.7 55.0 6755 0.0601
400 CM 61 23.4 2.0 0.1 2.9 61.5 8545 0.0470

Note RE : Round Solid Class 1


RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Page - 62
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES


XLPE / PVC-S (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey
Sheath - Black

THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of of Resistance
section area Cond. of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 0.1 1.8 10.5 150 12.1
1.5 RM 7 1.6 0.7 0.1 1.8 11.0 155 12.1
2.5 RE 1 1.78 0.7 0.1 1.8 11.5 190 7.41
2.5 RM 7 2.0 0.7 0.1 1.8 12.0 195 7.41
4 RE 1 2.26 0.7 0.1 1.8 12.5 250 4.61
4 RM 7 2.6 0.7 0.1 1.8 13.0 260 4.61
6 RE 1 2.77 0.7 0.1 1.8 13.5 320 3.08
6 RM 7 3.1 0.7 0.1 1.8 14.0 330 3.08
10 RM 7 4.1 0.7 0.1 1.8 16.5 480 1.83
16 CM 7 4.7 0.7 0.1 1.8 17.5 650 1.15
25 CM 7 5.9 0.9 0.1 1.8 21.0 960 0.727
35 CM 7 7.1 0.9 0.1 1.8 23.5 1275 0.524
50 CM 19 8.1 1.0 0.1 1.8 26.5 1645 0.387
70 CM 19 9.7 1.1 0.1 1.9 30.0 2285 0.268
95 CM 19 11.6 1.1 0.1 2.0 34.5 3110 0.193
120 CM 37 12.9 1.2 0.1 2.2 38.0 3870 0.153
150 CM 37 14.3 1.4 0.1 2.3 42.0 4775 0.124
185 CM 37 16.0 1.6 0.1 2.4 47.0 5910 0.0991
240 CM 37 18.3 1.7 0.1 2.6 53.0 7675 0.0754
300 CM 61 20.7 1.8 0.1 2.8 59.0 9565 0.0601
400 CM 61 23.4 2.0 0.1 3.1 66.0 12110 0.0470

Note RE : Round Solid Class 1


RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Page - 63
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES


XLPE / PVC-S (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey, Blue
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of of Resistance
section area Cond. of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 0.1 1.8 11.5 175 12.1
1.5 RM 7 1.6 0.7 0.1 1.8 12.0 185 12.1
2.5 RE 1 1.78 0.7 0.1 1.8 12.5 230 7.41
2.5 RM 7 2.0 0.7 0.1 1.8 13.0 240 7.41
4 RE 1 2.26 0.7 0.1 1.8 13.5 300 4.61
4 RM 7 2.6 0.7 0.1 1.8 14.0 320 4.61
6 RE 1 2.77 0.7 0.1 1.8 14.5 395 3.08
6 RM 7 3.1 0.7 0.1 1.8 15.5 410 3.08
10 RM 7 4.1 0.7 0.1 1.8 18.0 600 1.83
16 CM 7 4.7 0.7 0.1 1.8 19.5 825 1.15
25 CM 7 5.9 0.9 0.1 1.8 23.0 1230 0.727
35 CM 7 7.1 0.9 0.1 1.8 26.0 1635 0.524
50 CM 19 8.1 1.0 0.1 1.9 29.0 2120 0.387
70 CM 19 9.7 1.1 0.1 2.0 33.5 2980 0.268
95 CM 19 11.6 1.1 0.1 2.2 38.5 4075 0.193
120 CM 37 12.9 1.2 0.1 2.3 42.5 5055 0.153
150 CM 37 14.3 1.4 0.1 2.5 47.0 6245 0.124
185 CM 37 16.0 1.6 0.1 2.6 52.5 7755 0.0991
240 CM 37 18.3 1.7 0.1 2.8 59.0 10070 0.0754
300 CM 61 20.7 1.8 0.1 3.0 65.5 12550 0.0601
400 CM 61 23.4 2.0 0.1 3.3 73.5 15900 0.0470

Note RE : Round Solid Class 1


RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Page - 64
Section 3 - XLPE Insulated Cables
Unarmoured Cables

600/1000 V XLPE INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES


XLPE / PVC-S (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of of Resistance
section area Cond. of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 0.1 1.8 12.0 205 12.1
1.5 RM 7 1.6 0.7 0.1 1.8 12.5 215 12.1
2.5 RE 1 1.78 0.7 0.1 1.8 13.5 265 7.41
2.5 RM 7 2.0 0.7 0.1 1.8 14.0 280 7.41
4 RE 1 2.26 0.7 0.1 1.8 14.5 360 4.61
4 RM 7 2.6 0.7 0.1 1.8 15.5 380 4.61
6 RE 1 2.77 0.7 0.1 1.8 16.0 475 3.08
6 RM 7 3.1 0.7 0.1 1.8 17.0 490 3.08
10 RM 7 4.1 0.7 0.1 1.8 19.5 720 1.83
16 CM 7 4.7 0.7 0.1 1.8 21.0 1005 1.15
25 CM 7 5.9 0.9 0.1 1.8 25.5 1495 0.727
35 CM 7 7.1 0.9 0.1 1.9 28.5 2005 0.524
50 CM 19 8.1 1.0 0.1 2.0 32.0 2620 0.387

Note RE : Round Solid Class 1


RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2

Page - 65
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, ALUMINIUM WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/AWA/PVC (acc. to IEC 60502-1)

1
Constructions :
2
1 Conductor (Annealed Copper)
3 2 Insulation (XLPE Compound)
4 3 Inner Covering (PVC Compound)

5 4 Round Aluminium Wire armour


5 Binding tape (Manufacturer's option)
6 6 Outer sheath (PVC Compound)

600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/SWA/PVC (acc. to IEC 60502-1)

Constructions :
1
1 Conductor (Annealed Copper)
2 2 Insulation (XLPE Compound)

3 3 Filler (Polyprophylene yarn,or extruded filler


up to request)
4
4 Binding tape (Manufacturer's option)
5
5 Inner Covering (PVC Compound)
6 6 Galvanized Round Steel Wire armour

7 7 Binding tape (Manufacturer's option)


8 Outer sheath (PVC Compound)

8
Note : Special application upon request
* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed

Page - 66
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, ALUMINIUM WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE / AWA / PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Inner covering : PVC Compound Maximum 90°C
Armour : Aluminium Wire
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown
Sheath - Black

SINGLE CORE
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- of number of of of Inner diameter of of of of Resistance
section Cond. of wire Conductor Insulation covering Aluminium Sheath cable cable at 20°C
area (approx.) (approx.) wire (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km

16 CM 7 4.7 0.7 1.0 0.8 1.8 13.5 325 1.15

25 CM 7 5.9 0.9 1.0 0.8 1.8 15.5 435 0.727

35 CM 7 7.1 0.9 1.0 0.8 1.8 16.5 545 0.524

50 CM 19 8.1 1.0 1.0 1.25 1.8 18.5 715 0.387

70 CM 19 9.7 1.1 1.0 1.25 1.8 20.0 940 0.268

95 CM 19 11.6 1.1 1.0 1.25 1.8 22.0 1215 0.193

120 CM 37 12.9 1.2 1.0 1.6 1.8 24.5 1565 0.153

150 CM 37 14.3 1.4 1.0 1.6 1.8 26.5 1865 0.124

185 CM 37 16.0 1.6 1.0 1.6 1.8 28.5 2270 0.0991

240 CM 37 18.3 1.7 1.0 1.6 1.9 31.0 2860 0.0754

300 CM 61 20.7 1.8 1.0 1.6 1.9 34.0 3490 0.0601

400 CM 61 23.4 2.0 1.2 2.0 2.1 38.5 4385 0.0470

500 CM 61 26.5 2.2 1.2 2.0 2.2 42.0 5485 0.0366

630 CM 91 30.3 2.4 1.2 2.0 2.3 46.5 6930 0.0283

800 CM 91 34.3 2.6 1.4 2.5 2.5 52.5 8915 0.0221

1000 RM 127 41.6 2.8 1.4 2.5 2.5 60.5 11315 0.0176

Note RM : Circular Stranded Class 2


CM : Circular Stranded Compacted Class 2

Page - 67
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE / SWA / PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Blue
Sheath - Black

TWO CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- of number of of of Inner diameter of of of Resistance
section Cond. of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.8 1.8 13.5 315 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 1.8 14.0 325 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 1.8 14.5 355 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 1.8 15.0 375 7.41
4 RE 1 2.26 0.7 1.0 0.8 1.8 15.5 425 4.61
4 RM 7 2.6 0.7 1.0 0.8 1.8 16.0 440 4.61
6 RE 1 2.77 0.7 1.0 0.8 1.8 16.5 485 3.08
6 RM 7 3.1 0.7 1.0 0.8 1.8 17.0 515 3.08
10 RM 7 4.1 0.7 1.0 1.25 1.8 20.0 760 1.83
16 CM 7 4.7 0.7 1.0 1.25 1.8 21.0 910 1.15
25 CM 7 5.9 0.9 1.0 1.6 1.8 25.0 1345 0.727
35 CM 7 7.1 0.9 1.0 1.6 1.8 27.5 1630 0.524
50 CM 19 8.1 1.0 1.0 1.6 1.8 30.0 1965 0.387
70 CM 19 9.7 1.1 1.0 1.6 2.0 34.0 2550 0.268
95 CM 19 11.6 1.1 1.2 2.0 2.1 39.0 3520 0.193
120 CM 37 12.9 1.2 1.2 2.0 2.2 42.0 4160 0.153
150 CM 37 14.3 1.4 1.2 2.0 2.3 46.0 4970 0.124
185 CM 37 16.0 1.6 1.4 2.5 2.5 52.0 6435 0.0991
240 CM 37 18.3 1.7 1.4 2.5 2.7 57.5 7895 0.0754
300 CM 61 20.7 1.8 1.6 2.5 2.8 63.0 9545 0.0601

Note RE : Round Solid Class 1


RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Page - 68
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE / SWA / PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey
Sheath - Black

THREE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- of number of of of Inner diameter of of of Resistance
section Cond. of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.8 1.8 14.0 345 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 1.8 14.5 360 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 1.8 15.0 400 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 1.8 15.5 420 7.41
4 RE 1 2.26 0.7 1.0 0.8 1.8 16.0 475 4.61
4 RM 7 2.6 0.7 1.0 0.8 1.8 17.0 505 4.61
6 RE 1 2.77 0.7 1.0 0.8 1.8 17.0 570 3.08
6 RM 7 3.1 0.7 1.0 0.8 1.8 18.0 595 3.08
10 RM 7 4.1 0.7 1.0 1.25 1.8 20.5 890 1.83
16 CM 7 4.7 0.7 1.0 1.25 1.8 22.0 1090 1.15
25 CM 7 5.9 0.9 1.0 1.6 1.8 26.5 1625 0.727
35 CM 7 7.1 0.9 1.0 1.6 1.8 29.0 2015 0.524
50 CM 19 8.1 1.0 1.0 1.6 1.9 31.5 2465 0.387
70 CM 19 9.7 1.1 1.2 2.0 2.0 37.0 3525 0.268
95 CM 19 11.6 1.1 1.2 2.0 2.2 41.5 4495 0.193
120 CM 37 12.9 1.2 1.2 2.0 2.3 45.0 5385 0.153
150 CM 37 14.3 1.4 1.4 2.5 2.5 50.0 6920 0.124
185 CM 37 16.0 1.6 1.4 2.5 2.6 55.0 8285 0.0991
240 CM 61 18.3 1.7 1.6 2.5 2.8 61.5 10400 0.0754
300 CM 61 20.7 1.8 1.6 2.5 3.0 67.5 12550 0.0601

Note RE : Round Solid Class 1


RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Page - 69
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE / SWA / PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey,, Blue
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- of number of of of Inner diameter of of of Resistance
section Cond. of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.8 1.8 15.0 385 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 1.8 15.5 400 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 1.8 16.0 455 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 1.8 16.5 475 7.41
4 RE 1 2.26 0.7 1.0 0.8 1.8 17.0 550 4.61
4 RM 7 2.6 0.7 1.0 0.8 1.8 18.0 575 4.61
6 RE 1 2.77 0.7 1.0 1.25 1.8 19.0 755 3.08
6 RM 7 3.1 0.7 1.0 1.25 1.8 19.5 795 3.08
10 RM 7 4.1 0.7 1.0 1.25 1.8 22.0 1040 1.83
16 CM 7 4.7 0.7 1.0 1.25 1.8 23.5 1295 1.15
25 CM 7 5.9 0.9 1.0 1.6 1.8 28.5 1955 0.727
35 CM 7 7.1 0.9 1.0 1.6 1.9 31.5 2440 0.524
50 CM 19 8.1 1.0 1.0 1.6 2.0 34.5 3040 0.387
70 CM 19 9.7 1.1 1.2 2.0 2.2 40.5 4345 0.268
95 CM 19 11.6 1.1 1.2 2.0 2.3 45.0 5580 0.193
120 CM 37 12.9 1.2 1.4 2.5 2.5 50.0 7195 0.153
150 CM 37 14.3 1.4 1.4 2.5 2.6 55.0 8600 0.124
185 CM 37 16.0 1.6 1.4 2.5 2.8 60.5 10390 0.0991
240 CM 37 18.3 1.7 1.6 2.5 3.0 67.5 13060 0.0754
300 CM 61 20.7 1.8 1.6 2.5 3.2 74.0 15810 0.0601

Note RE : Round Solid Class 1


RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Page - 70
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE / SWA / PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey, Blue, Green / Yellow Stripe
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- of number of of of Inner diameter of of of Resistance
section Cond. of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.8 1.8 16.0 430 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 1.8 16.5 450 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 1.8 17.0 510 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 1.8 17.5 535 7.41
4 RE 1 2.26 0.7 1.0 1.25 1.8 19.0 730 4.61
4 RM 7 2.6 0.7 1.0 1.25 1.8 19.5 765 4.61
6 RE 1 2.77 0.7 1.0 1.25 1.8 20.5 905 3.08
6 RM 7 3.1 0.7 1.0 1.25 1.8 21.0 910 3.08
10 RM 7 4.1 0.7 1.0 1.25 1.8 24.0 1205 1.83
16 CM 7 4.7 0.7 1.0 1.6 1.8 26.5 1670 1.15
25 CM 7 5.9 0.9 1.0 1.6 1.8 30.5 2290 0.727
35 CM 7 7.1 0.9 1.0 1.6 1.9 34.0 2880 0.524
50 CM 19 8.1 1.0 1.2 2.0 2.1 39.0 3920 0.387

Note RE : Round Solid Class 1


RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2

Page - 71
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (acc. to IEC 60502-1)

2
1 Conductor (Annealed Copper)
2 Insulation (XLPE Compound)
3 Filler (Polyprophylene yarn,or extruded filler
3
up to request)
4 4 Binding tape (Manufacturer's option)
5 Inner Covering (PVC Compound)
5
6 Galvanized Flat Steel Wire armour
6 7 Galvanized Steel Tape binding
7 8 Outer sheath (PVC Compound)

Note : Special application upon request


* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed

Page - 72
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Black
Sheath - Black

TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. thickness of of of Resistance
section Cond. of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.8 0.3 1.8 14.0 365 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 0.3 1.8 14.0 400 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 0.3 1.8 14.5 430 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 0.3 1.8 15.0 435 7.41
4 RE 1 2.26 0.7 1.0 0.8 0.3 1.8 15.5 505 4.61
4 RM 7 2.6 0.7 1.0 0.8 0.3 1.8 16.0 515 4.61
6 RE 1 2.77 0.7 1.0 0.8 0.3 1.8 16.5 575 3.08
6 RM 7 3.1 0.7 1.0 0.8 0.3 1.8 17.0 600 3.08
10 RE 1 4.1 0.7 1.0 0.8 0.3 1.8 19.0 745 1.83
16 CM 6 4.7 0.7 1.0 0.8 0.3 1.8 20.5 900 1.15
25 CM 6 5.9 0.9 1.0 0.8 0.3 1.8 23.5 1190 0.727
35 CM 6 7.1 0.9 1.0 0.8 0.3 1.8 26.0 1475 0.524
50 CM 6 8.1 1.0 1.0 0.8 0.3 1.8 28.5 1805 0.387
70 CM 12 9.7 1.1 1.0 0.8 0.3 1.9 32.0 2330 0.268
95 CM 15 11.6 1.1 1.2 0.8 0.3 2.0 36.5 3035 0.193
120 CM 18 12.9 1.2 1.2 0.8 0.3 2.1 39.5 3635 0.153
150 CM 18 14.3 1.4 1.2 0.8 0.3 2.2 43.5 4385 0.124
185 CM 30 16.0 1.6 1.4 0.8 0.3 2.4 48.5 5345 0.0991
240 CM 34 18.3 1.7 1.4 0.8 0.3 2.6 54.0 6725 0.0754
300 CM 34 20.7 1.8 1.6 0.8 0.3 2.7 60.0 8225 0.0601
400 CM 53 23.4 2.0 1.6 0.8 0.3 3.0 66.5 10210 0.0470

Note RE : Round Solid Class 1


RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2 Page - 73
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow, Blue
Sheath - Black

THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. thickness of of of Resistance
section Cond. of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.8 0.3 1.8 14.5 420 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 0.3 1.8 14.5 430 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 0.3 1.8 15.0 460 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 0.3 1.8 15.5 500 7.41
4 RE 1 2.26 0.7 1.0 0.8 0.3 1.8 16.0 555 4.61
4 RM 7 2.6 0.7 1.0 0.8 0.3 1.8 17.0 595 4.61
6 RE 1 2.77 0.7 1.0 0.8 0.3 1.8 17.5 665 3.08
6 RM 7 3.1 0.7 1.0 0.8 0.3 1.8 18.0 675 3.08
10 RE 1 4.1 0.7 1.0 0.8 0.3 1.8 20.0 885 1.83
16 CM 6 4.7 0.7 1.0 0.8 0.3 1.8 21.5 1090 1.15
25 CM 6 5.9 0.9 1.0 0.8 0.3 1.8 25.0 1470 0.727
35 CM 6 7.1 0.9 1.0 0.8 0.3 1.8 27.5 1845 0.524
50 CM 6 8.1 1.0 1.0 0.8 0.3 1.8 30.0 2285 0.387
70 CM 12 9.7 1.1 1.2 0.8 0.3 2.0 34.5 3070 0.268
95 CM 15 11.6 1.1 1.2 0.8 0.3 2.1 39.0 3990 0.193
120 CM 18 12.9 1.2 1.2 0.8 0.3 2.2 42.0 4820 0.153
150 CM 18 14.3 1.4 1.4 0.8 0.3 2.3 46.5 5875 0.124
185 CM 30 16.0 1.6 1.4 0.8 0.3 2.4 52.0 7165 0.0991
240 CM 34 18.3 1.7 1.6 0.8 0.3 2.7 58.0 9125 0.0754
300 CM 34 20.7 1.8 1.6 0.8 0.3 2.8 64.0 11130 0.0601

Note RE : Round Solid Class 1


RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Page - 74
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow, Blue, Black
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. thickness of of of Resistance
section Cond. of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.8 0.3 1.8 15.0 450 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 0.3 1.8 15.5 485 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 0.3 1.8 16.0 535 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 0.3 1.8 16.5 545 7.41
4 RE 1 2.26 0.7 1.0 0.8 0.3 1.8 17.0 640 4.61
4 RM 7 2.6 0.7 1.0 0.8 0.3 1.8 18.0 660 4.61
6 RE 1 2.77 0.7 1.0 0.8 0.3 1.8 18.5 645 3.08
6 RM 7 3.1 0.7 1.0 0.8 0.3 1.8 19.0 785 3.08
10 RE 1 4.1 0.7 1.0 0.8 0.3 1.8 21.5 1040 1.83
16 CM 6 4.7 0.7 1.0 0.8 0.3 1.8 23.0 1295 1.15
25 CM 6 5.9 0.9 1.0 0.8 0.3 1.8 27.0 1795 0.727
35 CM 6 7.1 0.9 1.0 0.8 0.3 1.8 30.0 2265 0.524
50 CM 6 8.1 1.0 1.0 0.8 0.3 1.9 32.5 2830 0.387
70 CM 12 9.7 1.1 1.2 0.8 0.3 2.1 38.0 3840 0.268
95 CM 15 11.6 1.1 1.2 0.8 0.3 2.2 42.5 5015 0.193
120 CM 18 12.9 1.2 1.4 0.8 0.3 2.3 47.0 6145 0.153
150 CM 18 14.3 1.4 1.4 0.8 0.3 2.5 51.5 7450 0.124
185 CM 30 16.0 1.6 1.4 0.8 0.3 2.7 57.5 9125 0.0991
240 CM 34 18.3 1.7 1.6 0.8 0.3 2.9 64.0 11670 0.0754
300 CM 34 20.7 1.8 1.6 0.8 0.3 3.1 70.5 14270 0.0601

Note RE : Round Solid Class 1


RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Page - 75
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : XLPE Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. thickness of of of Resistance
section Cond. of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.8 0.3 1.8 16.0 510 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 0.3 1.8 16.5 520 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 0.3 1.8 17.0 605 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 0.3 1.8 17.5 615 7.41
4 RE 1 2.26 0.7 1.0 0.8 0.3 1.8 18.5 730 4.61
4 RM 7 2.6 0.7 1.0 0.8 0.3 1.8 19.0 750 4.61
6 RE 1 2.77 0.7 1.0 0.8 0.3 1.8 20.0 875 3.08
6 RM 7 3.1 0.7 1.0 0.8 0.3 1.8 20.5 900 3.08
10 RE 1 4.1 0.7 1.0 0.8 0.3 1.8 23.0 1200 1.83
16 CM 6 4.7 0.7 1.0 0.8 0.3 1.8 25.0 1512 1.15
25 CM 6 5.9 0.9 1.0 0.8 0.3 1.8 29.0 2100 0.727
35 CM 6 7.1 0.9 1.0 0.8 0.3 1.9 32.5 2700 0.524
50 CM 6 8.1 1.0 1.2 0.8 0.3 2.0 36.0 3435 0.387

Note RE : Round Solid Class 1


RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2

Page - 76
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, ALUMINIUM TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DATA/PVC (acc. to IEC 60502-1)

1
Constructions :
2 1 Conductor (Annealed Copper)
2 Insulation (XLPE Compound)
3
3 Inner Covering (PVC Compound)
4
4 Double Aluminium Tape armour
5 Outer sheath (PVC Compound)
5

600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (acc. to IEC 60502-1)

Constructions :
1 1 Conductor (Annealed Copper)
2 2 Insulation (XLPE Compound)
3 Filler (Polyprophylene yarn,or extruded filler

3
up to request)
4 Binding tape (Manufacturer's option)
4
5 Inner Covering (PVC Compound)
5 6 Double Galvanized Steel Tape armour
7 Outer sheath (PVC Compound)
6

7 Note : Special application upon request


* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed

Page - 77
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, ALUMINIUM TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DATA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Inner covering : PVC Compound Maximum 90°C
Armour : Double Aluminium tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown
Sheath - Black

SINGLE CORE
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of Inner of of of of Resistance
section Cond. of wire Conductor Insulation covering Aluminium Sheath cable cable at 20°C
area (approx.) (approx.) tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km

16 CM 6 4.7 0.7 1.0 0.5 1.8 13.5 335 1.15


25 CM 6 5.9 0.9 1.0 0.5 1.8 15.0 455 0.727
35 CM 6 7.1 0.9 1.0 0.5 1.8 16.5 570 0.524
50 CM 6 8.1 1.0 1.0 0.5 1.8 17.5 705 0.387
70 CM 12 9.7 1.1 1.0 0.5 1.8 19.5 930 0.268
95 CM 15 11.6 1.1 1.0 0.5 1.8 21.5 1210 0.193
120 CM 15 12.9 1.2 1.0 0.5 1.8 23.0 1470 0.153
150 CM 15 14.3 1.4 1.0 0.5 1.8 24.5 1760 0.124
185 CM 30 16.0 1.6 1.0 0.5 1.8 27.0 2155 0.0991
240 CM 30 18.3 1.7 1.0 0.5 1.8 29.5 2735 0.0754
300 CM 30 20.7 1.8 1.0 0.5 1.9 32.0 3365 0.0601
400 CM 53 23.4 2.0 1.2 0.5 2.0 35.5 4240 0.0470
500 CM 53 26.5 2.2 1.2 0.5 2.1 39.5 5350 0.0366
630 CM 53 30.3 2.4 1.2 0.5 2.3 44.0 6670 0.0283

Page - 78
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Blue
Sheath - Black

TWO CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- of number of of of Inner thickness of of of Resistance
section Cond. of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) Steel tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.2 1.8 12.5 220 
1.5 RM 7 1.6 0.7 1.0 0.2 1.8 13.0 230 12.1
2.5 RE 1 1.78 0.7 1.0 0.2 1.8 13.0 260 7.41
2.5 RM 7 2.0 0.7 1.0 0.2 1.8 13.5 270 7.41
4 RE 1 2.26 0.7 1.0 0.2 1.8 14.0 315 4.61
4 RM 7 2.6 0.7 1.0 0.2 1.8 15.0 330 4.61
6 RE 1 2.77 0.7 1.0 0.2 1.8 15.0 375 3.08
6 RM 7 3.1 0.7 1.0 0.2 1.8 16.0 390 3.08
10 RM 7 4.1 0.7 1.0 0.2 1.8 18.0 515 1.83
16 CM 6 4.7 0.7 1.0 0.2 1.8 19.0 645 1.15
25 CM 6 5.9 0.9 1.0 0.2 1.8 23.0 895 0.727
35 CM 6 7.1 0.9 1.0 0.2 1.8 24.5 1135 0.524
50 CM 6 8.1 1.0 1.0 0.2 1.8 27.0 1425 0.387
70 CM 12 9.7 1.1 1.0 0.2 1.9 30.5 1905 0.268
95 CM 15 11.6 1.1 1.2 0.2 2.0 35.0 2545 0.193
120 CM 18 12.9 1.2 1.2 0.5 2.1 39.5 3505 0.153
150 CM 18 14.3 1.4 1.4 0.5 2.3 43.5 4245 0.124
185 CM 30 16.0 1.6 1.4 0.5 2.4 48.5 5180 0.0991
240 CM 34 18.3 1.7 1.6 0.5 2.6 54.0 6530 0.0754
300 CM 34 20.7 1.8 1.6 0.5 2.7 59.5 8005 0.0601

Note RE : Round Solid Class 1


RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Page - 79
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey
Sheath - Black

THREE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- of number of of of Inner thickness of of of Resistance
section Cond. of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) Steel tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.2 1.8 13.0 250 
1.5 RM 7 1.6 0.7 1.0 0.2 1.8 13.5 260 12.1
2.5 RE 1 1.78 0.7 1.0 0.2 1.8 13.5 295 7.41
2.5 RM 7 2.0 0.7 1.0 0.2 1.8 14.0 310 7.41
4 RE 1 2.26 0.7 1.0 0.2 1.8 15.0 265 4.61
4 RM 7 2.6 0.7 1.0 0.2 1.8 15.5 385 4.61
6 RE 1 2.77 0.7 1.0 0.2 1.8 16.0 445 3.08
6 RM 7 3.1 0.7 1.0 0.2 1.8 16.5 465 3.08
10 RM 7 4.1 0.7 1.0 0.2 1.8 18.5 630 1.83
16 CM 6 4.7 0.7 1.0 0.2 1.8 20.0 815 1.15
25 CM 6 5.9 0.9 1.0 0.2 1.8 23.5 1150 0.727
35 CM 6 7.1 0.9 1.0 0.2 1.8 26.0 1485 0.524
50 CM 6 8.1 1.0 1.0 0.2 1.8 28.5 1885 0.387
70 CM 12 9.7 1.1 1.2 0.2 1.9 33.0 2590 0.268
95 CM 15 11.6 1.1 1.2 0.2 2.1 37.5 3460 0.193
120 CM 18 12.9 1.2 1.2 0.5 2.2 42.0 4670 0.153
150 CM 18 14.3 1.4 1.4 0.5 2.4 46.5 5710 0.124
185 CM 30 16.0 1.6 1.4 0.5 2.5 51.5 6965 0.0991
240 CM 34 18.3 1.7 1.6 0.5 2.7 58.0 8905 0.0754
300 CM 34 20.7 1.8 1.6 0.5 2.9 64.0 10920 0.0601

Note RE : Round Solid Class 1


RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Page - 80
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey, Blue
Sheath - Black

FOUR CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- of number of of of Inner thickness of of of Resistance
section Cond. of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) Steel tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.2 1.8 13.5 280 
1.5 RM 7 1.6 0.7 1.0 0.2 1.8 14.0 295 12.1
2.5 RE 1 1.78 0.7 1.0 0.2 1.8 14.5 345 7.41
2.5 RM 7 2.0 0.7 1.0 0.2 1.8 15.0 360 7.41
4 RE 1 2.26 0.7 1.0 0.2 1.8 16.0 430 4.61
4 RM 7 2.6 0.7 1.0 0.2 1.8 16.5 450 4.61
6 RE 1 2.77 0.7 1.0 0.2 1.8 17.0 535 3.08
6 RM 7 3.1 0.7 1.0 0.2 1.8 17.5 555 3.08
10 RM 7 4.1 0.7 1.0 0.2 1.8 20.0 765 1.83
16 CM 6 4.7 0.7 1.0 0.2 1.8 21.5 1000 1.15
25 CM 6 5.9 0.9 1.0 0.2 1.8 25.5 1435 0.727
35 CM 6 7.1 0.9 1.0 0.2 1.8 28.5 1860 0.524
50 CM 6 8.1 1.0 1.0 0.2 1.9 31.5 2385 0.387
70 CM 12 9.7 1.1 1.2 0.2 2.0 36.0 3315 0.268
95 CM 15 11.6 1.1 1.2 0.5 2.2 42.5 4875 0.193
120 CM 18 12.9 1.2 1.4 0.5 2.4 46.5 5985 0.153
150 CM 18 14.3 1.4 1.4 0.5 2.5 51.0 7275 0.124
185 CM 30 16.0 1.6 1.4 0.5 2.7 57.0 8925 0.0991
240 CM 34 18.3 1.7 1.6 0.5 2.9 64.0 11430 0.0754
300 CM 34 20.7 1.8 1.6 0.5 3.1 70.5 14015 0.0601

Note RE : Round Solid Class 1


RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Page - 81
Section 3 - XLPE Insulated Cables
Armoured Cables

600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (IEC 60502-1)

CONSTRUCTION TECHNICAL DATA


Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey, Blue, Green / Yellow Stripe
Sheath - Black

FIVE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- of number of of of Inner thickness of of of Resistance
section Cond. of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) Steel tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.2 1.8 14.5 320 
1.5 RM 7 1.6 0.7 1.0 0.2 1.8 15.0 335 12.1
2.5 RE 1 1.78 0.7 1.0 0.2 1.8 15.5 390 7.41
2.5 RM 7 2.0 0.7 1.0 0.2 1.8 16.0 405 7.41
4 RE 1 2.26 0.7 1.0 0.2 1.8 17.0 500 4.61
4 RM 7 2.6 0.7 1.0 0.2 1.8 17.5 520 4.61
6 RE 1 2.77 0.7 1.0 0.2 1.8 18.5 620 3.08
6 RM 7 3.1 0.7 1.0 0.2 1.8 19.0 645 3.08
10 RM 7 4.1 0.7 1.0 0.2 1.8 22.0 900 1.83
16 CM 6 4.7 0.7 1.0 0.2 1.8 23.5 1200 1.15
25 CM 6 5.9 0.9 1.0 0.2 1.8 27.5 1720 0.727
35 CM 6 7.1 0.9 1.0 0.2 1.9 31.0 2255 0.524
50 CM 6 8.1 1.0 1.2 0.2 2.0 35.0 2950 0.387

Note RE : Round Solid Class 1


RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2

Page - 82
CURRENT CARRYING CAPACITY FOR SINGLE CORE XLPE INSULATED CABLE
Current Carrying Capacity DC Alternating 2) 2) Minimum Conductor
Reactance (50 Hz) Inductance (50 Hz)
Conductor In Air ( 30°C ) In Conductor Current Insulation Short
1)
Nominal In Tray In Ducts Air Ground Resistance resistance Trefoil Flat Trefoil Flat Nominal Resistance circuit
Flat / Trefoil
Area Flat Trefoil Trefoil
at 20°C at 90°C / 50 Hz Capacitance current /
core to core core to core 1 sec
Unarmour Armour Unarmour Armour Unarmour Armour Unarmour Armour Unarmour Armour

mm² A A A A Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km µF / km M Ω. km kA

1.5 re/rm 22 21 20 23 12.1 15.4 - 0.1395 - 0.1541 - 0.4442 - 0.4905 - 0.0520 3000 0.215
2.5 re/rm 30 29 28 30 7.41 9.45 - 0.1280 - 0.1425 - 0.4074 - 0.4536 - 0.0571 2500 0.358
4 re/rm 42 40 37 39 4.61 5.88 - 0.1190 - 0.1335 - 0.3788 - 0.4250 - 0.0621 2000 0.572
6 re/rm 55 53 48 49 3.08 3.93 - 0.1109 - 0.1254 - 0.3531 - 0.3993 - 0.0665 2000 0.858
10 re/rm 77 74 66 65 1.83 2.34 - 0.1028 - 0.1173 - 0.3273 - 0.3735 - 0.0721 1500 1.430

16 cm 105 101 88 84 1.15 1.47 1.47 0.0984 0.1264 0.1129 0.1409 0.3131 0.4024 0.3593 0.4486 0.0751 1500 2.288
25 cm 141 135 117 107 0.727 0.927 0.927 0.0946 0.1190 0.1091 0.1335 0.3011 0.3789 0.3473 0.4251 0.0752 1500 3.575
35 cm 176 169 144 129 0.524 0.669 0.668 0.0900 0.1123 0.1045 0.1268 0.2865 0.3575 0.3327 0.4037 0.0789 1000 5.005
50 cm 216 207 175 153 0.387 0.494 0.494 0.0879 0.1109 0.1024 0.1254 0.2798 0.3529 0.3260 0.3991 0.0796 1000 7.150
70 cm 279 268 222 188 0.268 0.342 0.342 0.0847 0.1052 0.0992 0.1198 0.2697 0.3350 0.3159 0.3812 0.0815 900 10.01

95 cm 342 328 269 226 0.193 0.247 0.247 0.0818 0.0995 0.0963 0.1140 0.2603 0.3166 0.3065 0.3628 0.0848 800 13.59
120 cm 400 383 312 257 0.153 0.196 0.196 0.0805 0.0996 0.0951 0.1141 0.2564 0.3169 0.3026 0.3631 0.0853 800 17.16
150 cm 464 444 342 287 0.124 0.159 0.159 0.0807 0.0975 0.0952 0.1121 0.2567 0.3105 0.3029 0.3567 0.0846 800 21.45
185 cm 533 510 384 324 0.0991 0.128 0.128 0.0804 0.0958 0.0949 0.1103 0.2559 0.3048 0.3021 0.3510 0.0833 900 26.46
240 cm 634 607 450 375 0.0754 0.0983 0.0978 0.0786 0.0926 0.0931 0.1071 0.2502 0.2947 0.2964 0.3409 0.0848 800 34.32

300 cm 736 703 514 419 0.0601 0.0794 0.0788 0.0776 0.0903 0.0921 0.1048 0.2469 0.2873 0.2931 0.3335 0.0860 800 42.90
400 cm 868 823 661 495 0.0470 0.0634 0.0627 0.0769 0.0904 0.0915 0.1049 0.2449 0.2877 0.2911 0.3339 0.0865 700 57.20

Section 4 - General Information


500 cm 998 946 760 559 0.0366 0.0511 0.0502 0.0762 0.0883 0.0907 0.1029 0.2425 0.2812 0.2888 0.3274 0.0871 700 71.50
630 cm 1151 1088 879 635 0.0283 0.0416 0.0411 0.0756 0.0862 0.0901 0.1007 0.2406 0.2743 0.2869 0.3205 0.0880 700 90.09
800 cm 1328 1252 1020 725 0.0221 0.0349 0.0337 0.0750 0.0860 0.0896 0.1005 0.2389 0.2738 0.2851 0.3200 0.0883 700 114.40
1000 rm 1511 1420 1173 819 0.0176 0.0305 0.0291 0.0730 0.0829 0.0876 0.0974 0.2325 0.2639 0.2787 0.3101 0.0902 600 143.00
Page - 83

1)
Note : re : Round solid conductor IEC 60228 class 1 Underground : Thermal resistivity of soil : 2.5 K.m / W Note : Reference methode of installation to be used to obtain current carrying
rm : Circular stranded conductor IEC 60228 class 2 Depth of laying : 80 cm capacity for : in cable ducting, in cables conduit, cables direct in the -
cm : Circular stranded compacted conductor IEC 60228 class 2 Base temperature : 20°C ground with / without added protection against mechanical damage
2)
The Inductance calculated for armour cable is Amuminium Wire Armour (AWA)
Page - 84

Section 4 - General Information


CURRENT CARRYING CAPACITY FOR MULTICORE XLPE INSULATED CABLE

Current Carrying Capacity DC Alternating Minimum Conductor


Reactance (50 Hz) Inductance (50 Hz)
Conductor In Air ( 30°C ) Underground at 20°C Conductor Current Insulation Short
Nominal In Tray In Ducts Direct Burried ground Burried ducts ground Resistance resistance Nominal Resistance circuit
Area 2 3/4* 2 3/4* 2 3/4* 2 3/4* at 20°C at 90°C / 2/3 4 2/3 4 Capacitance current /
Core Core Core Core Core Core Core Core 50 Hz Core Core Core Core core to core core to core 1 sec
mm² A A A A A A A A Ω / km Ω / km Ω / km Ω / km mH / km mH / km µF / km M Ω. km kA

1.5 re/rm 26 23 22 19.5 27 23 25 21 12.1 15.4 0.1044 0.1117 0.3323 0.3554 0.0520 3000 0.215
2.5 re/rm 36 32 30 26 35 30 33 28 7.41 9.45 0.0959 0.1031 0.3052 0.3283 0.0571 2500 0.358
4 re/rm 49 42 40 35 46 39 43 36 4.61 5.88 0.0906 0.0979 0.2884 0.3115 0.0621 2000 0.572
6 re/rm 63 54 51 44 58 49 53 44 3.08 3.93 0.0850 0.0923 0.2706 0.2937 0.0665 2000 0.858

10 re/rm 86 75 69 60 77 65 71 58 1.83 2.33 0.0807 0.0880 0.2570 0.2801 0.0721 1500 1.430
16 cm 115 100 91 80 100 84 91 75 1.15 1.47 0.0781 0.0853 0.2485 0.2716 0.0751 1500 2.288
25 cm 149 127 119 105 129 107 116 96 0.727 0.927 0.0779 0.0852 0.2480 0.2711 0.0752 1500 3.575
35 cm 185 158 146 128 155 129 139 115 0.524 0.669 0.0753 0.0826 0.2397 0.2628 0.0789 1000 5.005

50 cm 225 192 175 154 183 153 164 135 0.387 0.494 0.0747 0.0820 0.2379 0.2610 0.0796 1000 7.150
70 cm 289 246 221 194 225 188 203 167 0.268 0.342 0.0734 0.0806 0.2335 0.2566 0.0815 900 10.01
95 cm 352 298 265 233 270 226 239 197 0.193 0.247 0.0711 0.0783 0.2262 0.2493 0.0848 800 13.59
120 cm 410 346 305 268 306 257 271 223 0.153 0.196 0.0708 0.0781 0.2254 0.2485 0.0853 800 17.16

150 cm 473 399 334 300 343 287 306 251 0.124 0.160 0.0712 0.0785 0.2267 0.2498 0.0846 800 21.45
185 cm 542 456 384 340 387 324 343 281 0.0991 0.128 0.0720 0.0793 0.2292 0.2523 0.0833 900 26.46
240 cm 641 538 459 398 448 375 395 324 0.0754 0.0987 0.0711 0.0784 0.2264 0.2495 0.0848 800 34.32
300 cm 741 621 532 455 502 419 446 365 0.0601 0.0798 0.0704 0.0776 0.2240 0.2471 0.0860 800 42.90
400 cm 892 745 628 552 593 495 521 426 0.0470 0.0640 0.0701 0.0773 0.2231 0.2462 0.0865 700 57.20

Note : re : Round solid conductor IEC 60228 class 1 Underground : Thermal resistivity of soil : 2.5 K.m / W 4* : 3 Phasa + Netral / Ground
rm : Circular stranded conductor IEC 60228 class 2 Depth of laying : 80 cm
cm : Circular stranded compacted conductor IEC 60228 class 2 Base temperature : 20°C
CURRENT CARRYING CAPACITY FOR SINGLE CORE PVC INSULATED CABLE

Current Carrying Capacity DC Alternating 2) 2) Minimum Conductor


Reactance (50 Hz) Inductance (50 Hz)
Conductor In Air ( 30°C ) In Conductor Current Insulation Short
1)
Nominal In Tray In Ducts Air Ground Resistance resistance Trefoil Flat Trefoil Flat Nominal Resistance circuit
Flat / Trefoil
Area Flat Trefoil Trefoil
at 20°C at 70°C / 50 Hz Capacitance at 20°C current /
core to core core to core 1 sec
Unarmour Armour Unarmour Armour Unarmour Armour Unarmour Armour Unarmour Armour

mm² A A A A Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km µF / km M Ω. km kA

1.5 re/rm 18 17.5 15.5 19 12.1 14.5 - 0.1418 - 0.1563 - 0.4513 - 0.4975 - 0.1391 50 0.174
2.5 re/rm 25 24 21 24 7.41 8.87 - 0.1300 - 0.1445 - 0.4139 - 0.4601 - 0.1531 50 0.290
4 re/rm 34 33 28 33 4.61 5.52 - 0.1245 - 0.1390 - 0.3962 - 0.4424 - 0.1553 50 0.464
6 re/rm 45 43 36 41 3.08 3.69 - 0.1160 - 0.1305 - 0.3693 - 0.4155 - 0.1671 50 0.696
10 re/rm 63 60 50 54 1.83 2.19 - 0.1073 - 0.1218 - 0.3416 - 0.3878 - 0.1827 50 1.160

16 rm 85 82 68 70 1.15 1.376 1.376 0.0997 0.1253 0.1142 0.1399 0.3172 0.3990 0.3634 0.4452 0.1966 40 1.856
25 rm 114 110 89 92 0.727 0.870 0.870 0.0956 0.1181 0.1101 0.1326 0.3044 0.3759 0.3506 0.4221 0.2001 40 2.900
35 rm 143 137 110 110 0.524 0.627 0.627 0.0914 0.1145 0.1059 0.1290 0.2908 0.3643 0.3370 0.4105 0.2100 40 4.060
50 rm 174 167 134 130 0.387 0.463 0.463 0.0886 0.1090 0.1031 0.1235 0.2821 0.3470 0.3283 0.3932 0.2127 30 5.800
70 rm 225 216 171 162 0.268 0.321 0.321 0.0848 0.1034 0.0993 0.1179 0.2700 0.3291 0.3162 0.3753 0.2223 30 8.120

95 rm 275 264 207 193 0.193 0.232 0.232 0.0844 0.1028 0.0989 0.1173 0.2687 0.3273 0.3149 0.3735 0.2205 30 11.02
120 rm 321 308 239 220 0.153 0.184 0.184 0.0820 0.0991 0.0965 0.1136 0.2609 0.3155 0.3072 0.3617 0.2270 30 13.92
150 rm 372 356 262 246 0.124 0.150 0.149 0.0817 0.0968 0.0962 0.1114 0.2600 0.3083 0.3062 0.3545 0.2274 20 17.40
185 rm 427 409 296 278 0.0991 0.120 0.120 0.0807 0.0947 0.0952 0.1092 0.2568 0.3014 0.3030 0.3476 0.2279 20 21.46
240 rm 507 485 346 320 0.0754 0.0925 0.0920 0.0796 0.0917 0.0941 0.1062 0.2533 0.2920 0.2995 0.3382 0.2308 20 27.84
0.0000
300 rm 587 561 394 359 0.0601 0.0746 0.0742 0.0823 0.0915 0.0968 0.1060 0.2618 0.2913 0.3080 0.3375 0.2323 20 34.80
400 rm 689 656 510 428 0.0470 0.0598 0.0591 0.0784 0.0905 0.0929 0.1050 0.2495 0.2880 0.2957 0.3342 0.2387 20 46.40
500 rm 789 749 587 485 0.0366 0.0483 0.0475 0.0777 0.0887 0.0922 0.1032 0.2472 0.2823 0.2934 0.3285 0.2355 20 58.00

Section 4 - General Information


630 rm 905 855 678 552 0.0283 0.0396 0.0386 0.0761 0.0870 0.0907 0.1015 0.2424 0.2768 0.2886 0.3230 0.2416 20 73.08
800 rm 1037 1027 788 631 0.0221 0.0335 0.0323 0.0746 0.0849 0.0891 0.0994 0.2375 0.2702 0.2837 0.3164 0.2476 20 92.80
1000 rm 1167 1173 906 715 0.0176 0.0292 0.0279 0.0738 0.0833 0.0883 0.0978 0.2348 0.2652 0.2810 0.3114 0.2500 20 116.00

1)
Note : re : Round solid conductor IEC 60228 class 1 Underground : Thermal resistivity of soil : 2.5 K.m / W Note : Reference methode of installation to be used to obtain current carrying
rm : Circular stranded conductor IEC 60228 class 2
Page - 85

Depth of laying : 80 cm capacity for : in cable ducting, in cables conduit, cables direct in the -
Base temperature : 20°C ground with / without added protection against mechanical damage
2)
The Inductance calculated for armour cable is Amuminium Wire Armour (AWA)
Page - 86

Section 4 - General Information


CURRENT CARRYING CAPACITY FOR MULTICORE PVC INSULATED CABLE

Current Carrying Capacity DC Alternating Minimum Conductor


Reactance (50 Hz) Inductance (50 Hz)
Conductor In Air ( 30°C ) Underground at 20°C Conductor Current Insulation Short
Nominal In Tray In Ducts Direct Burried ground Burried ducts ground Resistance resistance Nominal Resistance circuit
Area 2 3/4* 2 3/4* 2 3/4* 2 3/4* at 20°C at 70°C / 2/3 4 2/3 4 Capacitance at 20°C current /
Core Core Core Core Core Core Core Core 50 Hz Core Core Core Core core to core core to core 1 sec
mm² A A A A A A A A Ω / km Ω / km Ω / km Ω / km mH / km mH / km µF / km M Ω. km kA

1.5 re/rm 22 18.5 16.5 15 22 19 22 18 12.1 14.5 0.1082 0.1155 0.3444 0.3676 0.1391 50 0.174
2.5 re/rm 30 25 23 20 28 24 29 24 7.41 8.87 0.0993 0.1065 0.3160 0.3391 0.1531 50 0.290
4 re/rm 40 34 30 27 38 33 37 30 4.61 5.52 0.0990 0.1062 0.3151 0.3382 0.1553 50 0.464
6 re/rm 51 43 38 34 48 41 46 38 3.08 3.69 0.0926 0.0998 0.2946 0.3177 0.1671 50 0.696

10 re/rm 70 60 52 46 64 54 60 50 1.83 2.19 0.0870 0.0943 0.2770 0.3001 0.1827 50 1.160


16 rm 94 80 69 62 83 70 78 64 1.15 1.38 0.0818 0.0891 0.2604 0.2835 0.1966 40 1.856
25 rm 119 101 90 80 110 92 99 82 0.727 0.870 0.0808 0.0880 0.2571 0.2802 0.2001 40 2.900
35 rm 148 126 111 99 132 110 119 98 0.524 0.627 0.0781 0.0853 0.2485 0.2716 0.2100 40 4.060

50 rm/sm 180 153 133 118 156 130 140 116 0.387 0.464 0.0773 0.0846 0.2462 0.2693 0.2127 30 5.800
70 rm/sm 232 196 168 149 192 162 173 143 0.268 0.321 0.0748 0.0821 0.2382 0.2613 0.2223 30 8.120
95 rm/sm 282 238 201 179 230 193 204 169 0.193 0.232 0.0751 0.0823 0.2389 0.2620 0.2205 30 11.020
120 rm/sm 328 276 232 206 261 220 231 192 0.153 0.184 0.0734 0.0807 0.2337 0.2568 0.2270 30 13.920

150 rm/sm 379 319 258 225 293 246 261 217 0.124 0.150 0.0734 0.0806 0.2336 0.2567 0.2274 20 17.400
185 rm/sm 434 364 294 255 331 278 292 243 0.0991 0.121 0.0731 0.0804 0.2328 0.2559 0.2279 20 21.460
240 rm/sm 514 430 344 297 382 320 336 280 0.0754 0.0928 0.0725 0.0797 0.2307 0.2538 0.2308 20 27.840
300 rm/sm 593 497 394 339 427 359 379 316 0.0601 0.0752 0.0723 0.0795 0.2301 0.2532 0.2323 20 34.80

Note : re : Round solid conductor IEC 60228 class 1 Underground : Thermal resistivity of soil : 2.5 K.m / W 4* : 3 Phasa + Netral / Ground
rm : Circular stranded conductor IEC 60228 class 2 Depth of laying : 80 cm
sm : Sector shape stranded conductor IEC 60228 class 2 Base temperature : 20°C
Correction factor of Curent carrying capacity

Rating factor relating to open air temperature


Air temperature°C 10 15 20 25 30 35 40 45 50 55 60 65 70 80

PVC Insulation 1.22 1.17 1.12 1.06 1.00 0.94 0.87 0.79 0.71 0.61 0.50 - - -

XLPE Insulation 1.15 1.12 1.08 1.04 1.00 0.96 0.91 0.87 0.82 0.76 0.71 0.65 0.58 0.41

Rating factor relating to Ground temperature


Ground temp °C 10 15 20 25 30 35 40 45 50 55 60 65 70 80

PVC Insulation 1.10 1.05 1.00 0.95 0.89 0.84 0.77 0.71 0.63 0.55 0.45 - - -

XLPE Insulation 1.07 1.04 1.00 0.96 0.93 0.89 0.85 0.80 0.76 0.71 0.65 0.60 0.53 0.38

Rating factor relating to themal ground resistivity


Thermal Resistivity of soil K.m / W 0.5 0.7 1 1.5 2 2.5 3.5

Corection factor for cables in buried ducts 1.28 1.20 1.18 1.10 1.05 1 0.96

Corection factor for direct buried cables 1.88 1.62 1.50 1.28 1.12 1 0.90

Rating factor based on 3 core cable for size 1.5 ~ 10 mm²


Number of core
Under ground In Air

5 0.70 0.75

7 0.60 0.65

10 0.50 0.55

14 0.45 0.50

Section 4 - General Information


19 0.40 0.45

24 0.35 0.40

40 0.30 0.35

61 0.25 0.30
Page - 87
Section 4 - General Information

Reduction factors for group of more than one multi-core cable


to be applied to reference current-carrying capacities for multi-core cables in free air
Number Number of cables per trays or ladder
Method of installation
of trays 1 2 3 4 6 9
Touching
1 1.00 0.88 0.82 0.79 0.76 0.73
2 1.00 0.87 0.80 0.77 0.73 0.68
3 1.00 0.86 0.79 0.76 0.71 0.66
Perforated Cable 6 1.00 0.84 0.77 0.73 0.68 0.64
tray systems
( note 3 )
Spaced
1 1.00 1.00 0.98 0.95 0.91 -
2 1.00 0.99 0.96 0.92 0.87 -
3 1.00 0.98 0.95 0.91 0.85 -

Touching

1 1.00 0.88 0.82 0.78 0.73 0.72


Vertical
Perforated 2 1.00 0.88 0.81 0.76 0.71 0.70
Cable tray
systems
Spaced
( note 4 )
1 1.00 0.91 0.89 0.88 0.87 -

2 1.00 0.91 0.88 0.87 0.85 -

Touching
1 0.97 0.84 0.78 0.75 0.71 0.68
Unperforated 2 0.97 0.83 0.76 0.72 0.68 0.63
Cable tray 3 0.97 0.82 0.75 0.71 0.66 0.61
systems 6 0.97 0.81 0.73 0.69 0.63 0.58

Touching
1 1.00 0.87 0.82 0.80 0.79 0.78
2 1.00 0.86 0.80 0.78 0.76 0.73
3 1.00 0.85 0.79 0.76 0.73 0.70
Cable ladder 6 1.00 0.84 0.77 0.73 0.68 0.64
systems
Spaced
cleats, etc 1 1.00 1.00 1.00 1.00 1.00 -
( note 3 ) 2 1.00 0.99 0.98 0.97 0.96 -
3 1.00 0.98 0.97 0.96 0.93 -

NOTE 1 Values given are averages for the cable types and range of conductor sizes considered. The spread of values is generally less than 5 %.

NOTE 2 Factor apply to single layer groups of cables as shown above and do not apply when cables are installed in more than one layer touching each
other. Values for such installations may be significantly lower and has to be determined by an appropriate method

NOTE 3 Values are given for vertical spacing between cable trays of 300 mm and at least 20 mm between cable trays and wall. For closer spacing the
factors should be reduced.

NOTE 4 Values are given for horizontal spacing between cable trays of 225 mm with cable trays mounted back to back. For closer spacing the factor
should be reduced.

Page - 88
Section 4 - General Information

Reduction factors for groups of one or more circuits of single-core cables


to be applied to reference current-carrying capacity for one circuit of single-core
Number of Use as a multiplier to
Method of installation
trays 1 2 3 Current carrying capacity for
Touching

Perforated cable 1 0.98 0.91 0.87 Three cables in


tray systems 2 0.96 0.87 0.81 horizontal formation
( Note 3 ) 3 0.95 0.85 0.78

Touching
Vertically perforated 1 0.96 0.86 - Three cables in
cable tray systems 2 0.95 0.84 - vertcal formation
( note 4 )

Touching

Cable ladder systems 1 1.00 0.97 0.96 Three cables in


cleats, etc 2 0.98 0.93 0.89 horizontal formation
( Note 3 ) 3 0.97 0.90 0.86

Perforated cable 1 1.00 0.98 0.96


tray systems 2 0.97 0.93 0.89
( Note 3 ) 3 0.96 0.92 0.86

Spaced

Vertical perforated 1 1.00 0.91 0.89


Cable tray systems 2 1.00 0.90 0.86 Three cables in
( Note 4 ) trefoil formation

Cable ladder systems, 1 1.00 1.00 1.00


cleats, etc 2 0.97 0.95 0.93
( Note 3 ) 3 0.96 0.94 0.90

NOTE 1 Value given are averages for the cable types and range of conductor sizes considered. The spread of values is generally less than ± 5 %.

NOTE 2 Factor aer given for single layers of cables ( or trefoil groups ) as shown in the table and do not apply when cables are installed in more than one
layer touching each other. Values for such installations may be significantly lower and should be determined by an appropriate method.
NOTE 3 Values are given for vertical spacing between cable trays of 300 mm and at least 20 mm between cable trays and wall. For closer spacing the
factor should be reduced.
NOTE 4 Values are given for horizontal spacings between cable trays of 225 mm with cable trays mounted back to back. For closer spacing the factors
should be reduced
NOTE 5 For circuits having more than one cable in parallel per phase, each three phase set of conductors should be considered as a circuit for the
purpose of this table
NOTE 6 If a circuit consists of m parallel conductors per phase, then for determining the erduction factor this circuit should be considered as m circuits

Page - 89
Section 4 - General Information

PERMISSIBLE PULLING TENSION


Pulling equipment Permissible pulling tension (kg)
PULLING EYE 7 x (Number of core) x (Cross section area of conductor)
CABLE NET About 500 kg, but the maximum tension shall not be more than one of
conductor (same calculation as using PULLING EYE)

Reference data on Aluminium conductor


Pulling equipment Permissible pulling tension (kg)
PULLING EYE 4 x (Number of core) x (Cross section area of conductor)
CABLE NET About 500 kg, but the maximum tension shall not be more than one of
conductor (same calculation as using PULLING EYE)
Note) Cable net shall be covered more than 500 mm in length

MINIMUM BENDING RADIUS


Reference data on other types of POWER cables D : Diameter of cable
Minimum bending radius
Single core cable
Type of cable
Round/Compacted Multi core cable
Sector conductor
conductor
Sheild cable ( XLPE/PVC-S etc ) 10D 12D 8D
Non Sheild cable ( XLPE/PVC etc ) 8D 12D 6D
Triplex type cable ( CVT etc ) - - 8D
Wire armored cable ( XLPE/SWA/PVC etc) 10D 12D 10D
Tape armored cable (XLPE/DSTA/PVC etc) 10D 12D 10D
Flat tape armored (XLPE/FSWA/PVC etc) 10D 12D 10D

Reference data on other types of INSTRUMENT cables


Minimum bending radius
Type of cable
Multi core cable
Non shield cable ( XLPE/PVC etc ) 6D Note) Sheild tape shall be
Sheild cable (XLPE/PVC-S etc) 6D AL mylar tape

PERMISSIBLE SIDE WALL PRESSURE


300kg/m is suggested as permissible side wall pressure to the cable during installation.
Side wall pressure (T1) can be calculated with below formula.
T kg
T1 = Pulling tension (T) / Bending radius (r) r

CALCULATION OF CABLE PULLING TENSION DURING INSTALLATION

The cable pulling tension (T2) during installation can be calculated with below formula.

1) Horizontal straight part : T2   * W * L W : Weight of cable (kg/m)


2) Horizontal curve part : T3  T4 * e     L : Length of cable with straight part (m)
θ : Angle of curve part (rad)
µ : Friction factor Friction factor T2 : Pulling tension (kg)
on pulley 0.2 T3 : Pulling tension before curve part (kg)
underground 0.2 - 0.3 T4 : Pulling tension after curve part (kg)
in pipe 0.5 - 0.7

Page - 90
Section 4 - Contents & Information

Fire Performance Tests


1. Flame Propagation Tests
IEC 60332-1
Part 1 - Test on a single vertical insulated wire or cable
This is a relatively simple method for providing adequate indication of the flame-retardant characteristics of a single cable.
A 600 mm long cable sample is verticatlly suspended, placed in the middle of a three-sided metal screen.
This is subjected to the regulated flame of one (up to a cable diameter of 50 mm) or two (above 50 mm diameter) gas burners at an
angle of 45° to the cable. The flame is applied for a continuous time calculated according to an increasing with the cable weight
(from around 1-minute for a small control cable to about 7 minutes for a 4 core 300 mm² power cable). The test is passed if the cable
has self-extinguished and the charred or flame affected portion of the cable has not reached the top of the sample.

IEC 60332-3
Part 3 - Test on bunched wire or cables
This test was developed to obtain a method to determine the flame propagation characteristics of bunched cables.
It can not be assumed that because a single vertical cable complies with the requirements of IEC 60332 part 1 it will also behave in 1
a similar manner when bunched with others cables.
The propagation of a flame along a bunch of cables depends on a number of features, such as :
The volume of combustible material exposed to the fire
The geometrical configuration of the cables
The temperature at which it is possible to ignite any gases emitted from the cables
The quantity of combustible gas released from the cables
The volume of air passing through the cable installation
The test consists of a vertical chamber, 1 x 2 x 4 m. Openings air inlet and outlet are provided in the base and the top of the test
chamber for a controlled air flow rate during the test. The cable samples to be tested are 3.5 m long and fixed to a steel ladder mounted
150 mm from the rear wall vertically with the test chamber. The number of lengths of cables in the test depends on the test categoty
based on the volume of combustible material.
Test Category Volume of combustible material Time of flame application
A 7 litres / m 40 Minutes
B 3.5 litres / m 40 Minutes
C 1.5 litres / m 20 Minutes
A ribbon gas burner of a set size and heat flow rate, operating at 800°C is mounted horizontally in front of the cable samples at a set
distance and height. The test is passed if the charred or affected portion of the samples have not reached a height exceeding 2.5 m
above the bottom edge of the burner.

2. Fire Resistant Tests


IEC 60331 - 21 ( 1999-04 )
Fire resisting characteristics of electric cables Circuit Integrity Test
This test determines the circuit integrity of a cable during and after a prolonged fire :
A horizontally suspended sample 1200 mm long is placed 75 mm above a 610 mm long ribbon type gas burner, the flame temperature
of which is regulated to 750°C. The conductors of the sample are connected to an AC voltage source, at the operating voltage, via fuses.
The flame and test voltage shall be applied continuously for a period of 90 min. 12 hours after the flame has been extinguished the cable
is energised again.
The test is passed if no failure of any of the fuses occurs.