Académique Documents
Professionnel Documents
Culture Documents
Jl. Gatot Subroto Km 7,8 Kel Pasir Jaya, Kec. Jati Uwung, Tangerang 15135-Indonesia
Phone : (62-21) 5922404, 5928066 (Hunting) Fax. : (62-21) 59301979, 5922576, 5901469
c
Copyright Sumi Indo Kabel 2012
All rights reserved. This catalogue is the copyright work of PT. Sumi Indo Kabel Tbk. No part of this publication may be reproduced, stored in a retrieval system, or transmitted,
in any form or by means, electronic, mechanical, photocopying, recording or otherwise, without prior permission of PT. Sumi Indo Kabel.
All information contained in this catalogue is believed to be accurate at the time issue. PT. Sumi Indo Kabel reserve the right to change information or specification at any time
in the light of technical developments or revisions.
600/1000 Volts PVC Insulated and PVC Sheathed Cables (PVC/PVC, NYY) 18
600/1000 Volts PVC Insulated, Copper Tape Shielded and PVC Sheathed Cables (PVC/PVC-S, NYSY) 30
Armoured Cables
600/1000 Volts PVC Insulated, Steel Wire Armoured and PVC Sheathed Cables (PVC/SWA/PVC, NYRY) 35
600/1000 Volts PVC Insulated, Flat Steel Wire Armoured and PVC Sheathed Cables (PVC/FSWA/PVC, NYFGbY) 41
600/1000 Volts PVC Insulated, Double Steel Tape Armoured and PVC Sheathed Cables (PVC/DSTA/PVC, NYBY) 46
Armoured Cables
600/1000 Volts XLPE Insulated, Steel Wire Armoured and PVC Sheathed Cables (XLPE/SWA/PVC, N2XRY) 67
600/1000 Volts XLPE Insulated, Flat Steel Wire Armoured and PVC Sheathed Cables (XLPE/FSWA/PVC, N2XFGbY) 73
600/1000 Volts XLPE Insulated, Double Steel Tape Armoured and PVC Sheathed Cables (XLPE/DSTA/PVC, N2XBY) 78
Page - 1
Section 1 - Contents & Information
1 Scope
These specification apply to material and constructions of cross-linked thermosetting polyethylene
(XLPE) or Polivinyl chloride (PVC) insulated wire and cables for rated voltages 0.3/0.5 kV up to
0.6/1(1.2) kV in accordance to IEC 60502-1, SNI or SPLN ( Standard of Indonesia Electric Power
Company )
2 Conductor
The conductor shall be formed from plain annealed copper or aluminium complying with IEC
60228
The conductor shall be solid, circular stranded, compacted stranded or sector shape
3 Insulation
The insulation shall be cross-linked polyethylene (XLPE) or Polivinyl chloride (PVC) in
accordance to IEC 60502-1.
4 Identification of cores
Below is standard reference for core identification :
A. IEC 60445 - 2010 Phasa / AC System : Black, Brown or Grey
Neutral : Blue 1
Grounding : Green and Yellow
Such that, the proposal cables shall be identified by color or numbered printed on the surface of
insulation in accordance with the following sequence or other sequence as follows *) :
Number of core Identification of cores
Single core Brown
Two cores Brown, Blue
Three cores Brown, Black, Grey
1
Four cores Brown, Black, Grey, Blue
Five cores Brown, Black, Grey, Blue, Green / Yellow stripe
Six core or more Black insulation with white numbered code.
Note : *) : Sumi Indo Kabel can comply for color identification as Request
Page - 2
Section 1 - Contents & Information
8 Metallic armour
The metallic armour shall consist of single layer of round galvanized steel wire or flat galvanized
steel wire and steel tape or double layer of galvanized steel tapes in accordance to IEC 60502-1.
The armour of single core cables shall consist of single layer of aluminium wire or double layers of
aluminium tape as non magnetic material.
9 Outer sheath
The outer sheath shall consist of a thermoplastic compound such as polyvinyl chloride (PVC),
polyethylene (PE), halogen free (LSOH), etc in accordance with IEC 60502-1.
Page - 3
Section 2 - PVC Insulated Cables
Unarmoured Cables
Colour of Insulation : Red, White, Black, Green, Brown, Blue, Yellow, Grey, Green-yellow
Colour of Insulation : Red, White, Black, Green, Brown, Blue, Yellow, Grey, Green-yellow
Page - 4
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 5
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 6
Section 2 - PVC Insulated Cables
Unarmoured Cables
Conductor
PVC Insulation PVC Sheath
Page - 7
Section 2 - PVC Insulated Cables
Unarmoured Cables
No. Nominal Shape Diameter Thickness Thickness Thickness diameter Weight Conductor
Core section Cond. of wire Conductor Insulation covering Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
- mm² - Number mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 0.4 1.2 9.5 130 12.1
1.5 RM 7 1.6 0.7 0.4 1.2 10.0 140 12.1
2.5 RE 1 1.78 0.8 0.4 1.2 11.0 175 7.41
2.5 RM 7 2.0 0.8 0.4 1.2 11.0 185 7.41
4 RE 1 2.26 0.8 0.4 1.2 12.0 225 4.61
2 4 RM 7 2.6 0.8 0.4 1.2 12.5 240 4.61
6 RE 1 1 0.8 0.4 1.2 13.0 295 3.08
6 RM 7 3.1 0.8 0.4 1.2 14.0 315 3.08
10 RE 1 3.57 1.0 0.6 1.4 16.0 455 1.83
10 RM 7 4.1 1.0 0.6 1.4 17.0 495 1.83
16 RM 7 5.1 1.0 0.6 1.4 19.0 670 1.15
25 RM 7 6.4 1.2 0.8 1.4 23.0 1000 0.727
35 RM 7 7.6 1.2 1.0 1.6 26.0 1340 0.524
1.5 RE 1 1.38 0.7 0.4 1.2 10.0 150 12.1
1.5 RM 7 1.6 0.7 0.4 1.2 10.5 160 12.1
2.5 RE 1 1.78 0.8 0.4 1.2 11.5 205 7.41
2.5 RM 7 2.0 0.8 0.4 1.2 12.0 220 7.41
4 RE 1 2.26 0.8 0.4 1.2 12.5 270 4.61
3 4 RM 7 2.6 0.8 0.4 1.2 13.0 290 4.61
6 RE 1 2.77 0.8 0.4 1.4 14.0 360 3.08
6 RM 7 3.1 0.8 0.4 1.4 14.5 385 3.08
10 RE 1 3.57 1.0 0.6 1.4 17.0 560 1.83
10 RM 7 4.1 1.0 0.6 1.4 18.0 600 1.83
16 RM 7 5.1 1.0 0.8 1.4 20.5 850 1.15
25 RM 7 6.4 1.2 0.8 1.6 24.5 1270 0.727
35 RM 7 7.6 1.2 1.0 1.6 27.5 1680 0.524
No. Nominal Shape Diameter Thickness Thickness Thickness diameter Weight Conductor
Core section Cond. of wire Conductor Insulation covering Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
- mm² - Number mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 0.4 1.2 11.0 180 12.1
1.5 RM 7 1.6 0.7 0.4 1.2 11.5 190 12.1
2.5 RE 1 1.78 0.8 0.4 1.2 12.5 250 7.41
2.5 RM 7 2.0 0.8 0.4 1.2 13.0 265 7.41
4 RE 1 2.26 0.8 0.4 1.4 14.0 340 4.61
4 4 RM 7 2.6 0.8 0.4 1.4 14.5 365 4.61
6 RE 1 2.77 0.8 0.4 1.4 15.5 460 3.08
6 RM 7 3.1 0.8 0.4 1.4 16.0 485 3.08
10 RE 1 3.57 1.0 0.6 1.4 18.5 690 1.83
10 RM 7 4.1 1.0 0.6 1.4 19.5 745 1.83
16 RM 7 5.1 1.0 0.8 1.4 22.5 1060 1.15
25 RM 7 6.4 1.2 1.0 1.6 27.5 1620 0.727
35 RM 7 7.6 1.2 1.0 1.6 30.0 2110 0.524
1.5 RE 1 1.38 0.7 0.4 1.2 11.5 210 12.1
1.5 RM 7 1.6 0.7 0.4 1.2 12.0 225 12.1
2.5 RE 1 1.78 0.8 0.4 1.2 13.5 295 7.41
2.5 RM 7 2.0 0.8 0.4 1.2 14.0 315 7.41
4 RE 1 2.26 0.8 0.6 1.4 15.5 425 4.61
5 4 RM 7 2.6 0.8 0.6 1.4 16.5 455 4.61
6 RE 1 2.77 0.8 0.6 1.4 17.0 550 3.08
6 RM 7 3.1 0.8 0.6 1.4 17.5 580 3.08
10 RE 1 3.57 1.0 0.6 1.4 20.0 840 1.83
10 RM 7 4.1 1.0 0.6 1.4 21.5 900 1.83
16 RM 7 5.1 1.0 0.8 1.6 25.0 1310 1.15
25 RM 7 6.4 1.2 1.0 1.6 30.0 1970 0.727
35 RM 7 7.6 1.2 1.2 1.6 33.5 2620 0.524
Note *) : RE : Round Solid Class 1
Page - 10
Section 2 - PVC Insulated Cables
Unarmoured Cables
TWO CORES
Conductor Nominal Nominal Overall Maximum
Nominal Maximum Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.)
mm² mm mm mm mm mm kg/km /km
Page - 11
Section 2 - PVC Insulated Cables
Unarmoured Cables
THREE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Maximum Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.)
mm² mm mm mm mm mm kg/km /km
Page - 12
Section 2 - PVC Insulated Cables
Unarmoured Cables
FOUR CORES
Conductor Nominal Nominal Overall Maximum
Nominal Maximum Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.)
mm² mm mm mm mm mm kg/km /km
Page - 13
Section 2 - PVC Insulated Cables
Unarmoured Cables
FIVE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Maximum Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² mm mm mm mm mm kg/km /km
Page - 14
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 15
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 16
Section 2 - PVC Insulated Cables
Unarmoured Cables
1 1
2 2
5 5
Page - 17
Section 2 - PVC Insulated Cables
Unarmoured Cables
SINGLE CORE
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of Resistance
section cond. of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.)
mm² - number mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.4 5.6 50 12.1
1.5 RM 7 1.6 0.8 1.4 5.8 50 12.1
2.5 RE 1 1.78 0.8 1.4 6.0 60 7.41
2.5 RM 7 2.0 0.8 1.4 6.2 65 7.41
4 RE 1 2.26 1.0 1.4 6.9 85 4.61
4 RM 7 2.6 1.0 1.4 7.2 90 4.61
6 RM 7 3.1 1.0 1.4 7.7 115 3.08
10 RM 7 4.1 1.0 1.4 8.7 160 1.83
16 RM 7 5.1 1.0 1.4 9.7 225 1.15
25 RM 7 6.4 1.2 1.4 11.5 335 0.727
35 RM 7 7.6 1.2 1.4 12.5 440 0.524
50 RM 19 9.2 1.4 1.4 14.5 600 0.387
70 RM 19 10.9 1.4 1.4 16.5 810 0.268
95 RM 19 12.6 1.6 1.5 19.0 1090 0.193
120 RM 37 14.2 1.6 1.5 20.5 1335 0.153
150 RM 37 15.9 1.8 1.6 22.5 1660 0.124
185 RM 37 17.6 2.0 1.7 25.0 2025 0.0991
240 RM 61 20.3 2.2 1.8 28.0 2650 0.0754
300 RM 61 22.7 2.4 1.9 31.0 3275 0.0601
400 RM 61 25.7 2.6 2.0 35.0 4190 0.0470
500 RM 61 28.8 2.8 2.1 38.5 5200 0.0366
630 RM 91 32.6 2.8 2.2 42.5 6505 0.0283
800 RM 127 37.1 2.8 2.3 47.5 8285 0.0221
1000 RM 127 41.6 3.0 2.5 52.5 10360 0.0176
Note *) RE : Round Solid Class 1
RM : Circular Stranded Class 2
Page - 18
Section 2 - PVC Insulated Cables
Unarmoured Cables
TWO CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of Resistance
section area Conductor of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.)
mm² - number mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.8 10.0 115 12.1
1.5 RM 7 1.6 0.8 1.8 10.5 125 12.1
2.5 RE 1 1.78 0.8 1.8 10.5 145 7.41
2.5 RM 7 2.0 0.8 1.8 11.0 155 7.41
4 RE 1 2.26 1.0 1.8 12.5 200 4.61
4 RM 7 2.6 1.0 1.8 13.0 215 4.61
6 RM 7 3.1 1.0 1.8 14.0 270 3.08
10 RM 7 4.1 1.0 1.8 16.0 375 1.83
16 RM 7 5.1 1.0 1.8 18.0 520 1.15
25 RM 7 6.4 1.2 1.8 21.5 765 0.727
35 RM 7 7.6 1.2 1.8 24.0 1000 0.524
50 RM 19 9.2 1.4 1.8 28.0 1370 0.387
70 RM 19 10.9 1.4 1.9 31.5 1825 0.268
95 RM 19 12.6 1.6 2.0 36.0 2440 0.193
120 RM 37 14.2 1.6 2.1 39.5 2990 0.153
150 RM 37 15.9 1.8 2.2 44.0 3715 0.124
185 RM 37 17.6 2.0 2.4 48.5 4545 0.0991
240 RM 61 20.3 2.2 2.6 55.0 5945 0.0754
300 RM 61 22.7 2.4 2.7 60.5 7325 0.0601
Page - 19
Section 2 - PVC Insulated Cables
Unarmoured Cables
THREE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of Resistance
section area conductor of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.8 10.5 140 12.1
1.5 RM 7 1.6 0.8 1.8 11.0 150 12.1
2.5 RE 1 1.78 0.8 1.8 11.5 180 7.41
2.5 RM 7 2.0 0.8 1.8 11.5 190 7.41
4 RE 1 2.26 1.0 1.8 13.0 260 4.61
4 RM 7 2.6 1.0 1.8 14.0 275 4.61
6 RM 7 3.1 1.0 1.8 15.0 350 3.08
10 RM 7 4.1 1.0 1.8 17.0 500 1.83
16 RM 7 5.1 1.0 1.8 19.0 700 1.15
25 RM 7 6.4 1.2 1.8 23.0 1045 0.727
35 RM 7 7.6 1.2 1.8 25.5 1380 0.524
50 SM 19 6.8 1.4 1.8 24.0 1710 0.387
70 SM 19 8.2 1.4 2.0 27.5 2365 0.268
95 SM 19 9.7 1.6 2.1 32.0 3265 0.193
120 SM 37 10.9 1.6 2.2 34.5 3905 0.153
150 SM 37 11.9 1.8 2.3 37.5 4785 0.124
185 SM 37 13.6 2.0 2.5 42.5 5965 0.0991
240 SM 37 15.8 2.2 2.7 48.0 7970 0.0754
300 SM 37 17.5 2.4 2.9 53.0 9920 0.0601
Page - 20
Section 2 - PVC Insulated Cables
Unarmoured Cables
FOUR CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of Resistance
section area conductor of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.8 11.0 170 12.1
1.5 RM 7 1.6 0.8 1.8 11.5 180 12.1
2.5 RE 1 1.78 0.8 1.8 12.0 220 7.41
2.5 RM 7 2.0 0.8 1.8 12.5 235 7.41
4 RE 1 2.26 1.0 1.8 14.5 320 4.61
4 RM 7 2.6 1.0 1.8 15.0 340 4.61
6 RM 7 3.1 1.0 1.8 16.5 435 3.08
10 RM 7 4.1 1.0 1.8 18.5 635 1.83
16 RM 7 5.1 1.0 1.8 21.0 900 1.15
25 RM 7 6.4 1.2 1.8 25.0 1345 0.727
35 RM 7 7.6 1.2 1.8 28.0 1780 0.524
50 SM 19 8.1 1.4 1.9 27.5 2210 0.387
70 SM 19 9.7 1.4 2.1 31.5 3090 0.268
95 SM 19 11.4 1.6 2.2 36.5 4255 0.193
120 SM 37 12.9 1.6 2.4 40.0 5100 0.153
150 SM 37 14.2 1.8 2.5 43.5 6265 0.124
185 SM 37 16.0 2.0 2.7 49.0 7815 0.0991
240 SM 37 18.2 2.2 2.9 54.5 10425 0.0754
300 SM 37 20.6 2.4 3.1 61.0 12985 0.0601
Page - 21
Section 2 - PVC Insulated Cables
Unarmoured Cables
FIVE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of Resistance
section area conductor of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.8 12.0 200 12.1
1.5 RM 7 1.6 0.8 1.8 12.5 215 12.1
2.5 RE 1 1.78 0.8 1.8 13.0 265 7.41
2.5 RM 7 2.0 0.8 1.8 14.0 280 7.41
4 RE 1 2.26 1.0 1.8 15.5 385 4.61
4 RM 7 2.6 1.0 1.8 16.5 410 4.61
6 RM 7 3.1 1.0 1.8 18.0 530 3.08
10 RM 7 4.1 1.0 1.8 20.5 775 1.83
16 RM 7 5.1 1.0 1.8 23.0 1100 1.15
25 RM 7 6.4 1.2 1.8 28.0 1655 0.727
35 RM 7 7.6 1.2 1.9 31.0 2200 0.524
50 RM 19 9.2 1.4 2.1 37.0 3080 0.387
Page - 22
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 23
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 24
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 25
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 26
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 27
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 28
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 29
Section 2 - PVC Insulated Cables
Unarmoured Cables
TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of of Resistance
section area cond. of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm mm kg/km /km
Page - 30
Section 2 - PVC Insulated Cables
Unarmoured Cables
THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of of Resistance
section area cond. of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 0.1 1.8 11.0 170 12.1
1.5 RM 7 1.6 0.8 0.1 1.8 11.5 175 12.1
2.5 RE 1 1.78 0.8 0.1 1.8 12.0 215 7.41
2.5 RM 7 2.0 0.8 0.1 1.8 12.5 220 7.41
4 RE 1 2.26 1.0 0.1 1.8 14.0 300 4.61
4 RM 7 2.6 1.0 0.1 1.8 14.5 305 4.61
6 RM 7 3.1 1.0 0.1 1.8 15.0 385 3.08
10 RM 7 4.1 1.0 0.1 1.8 17.5 545 1.83
16 RM 7 5.1 1.0 0.1 1.8 20.0 755 1.15
25 RM 7 6.4 1.2 0.1 1.8 23.5 1110 0.727
35 RM 7 7.6 1.2 0.1 1.8 26.0 1445 0.524
50 SM 19 6.8 1.4 0.1 1.9 25.0 1775 0.387
70 SM 19 8.2 1.4 0.1 2.0 28.0 2440 0.268
95 SM 19 9.7 1.6 0.1 2.1 32.5 3350 0.193
120 SM 37 10.9 1.6 0.1 2.2 35.0 3995 0.153
150 SM 37 11.9 1.8 0.1 2.4 38.5 4885 0.124
185 SM 37 13.6 2.0 0.1 2.5 43.0 6080 0.0991
240 SM 37 15.8 2.2 0.1 2.7 48.5 8095 0.0754
300 SM 37 17.5 2.4 0.1 2.9 53.5 10060 0.0601
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
SM : Three Segmental Stranded Compacted Class 2
Page - 31
Section 2 - PVC Insulated Cables
Unarmoured Cables
FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of of Resistance
section area cond. of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm mm kg/km /km
Page - 32
Section 2 - PVC Insulated Cables
Unarmoured Cables
FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of of Resistance
section area cond. of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm mm kg/km /km
Page - 33
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, ALUMINIUM WIRE ARMOURED AND PVC SHEATHED CABLES
PVC / AWA / PVC (acc. to IEC 60502-1)
1
Constructions :
2 1 Conductor (Annealed Copper)
3 2 Insulation (PVC Compound)
3 Inner Covering (PVC Compound)
4
4 Round Aluminium Wire armour
5
5 Binding tape (Manufacturer's option)
6 Outer sheath (PVC Compound)
6
600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC / SWA / PVC (acc. to IEC 60502-1)
1 Constructions :
1 Conductor (Annealed Copper)
2
2 Insulation (PVC Compound)
3 3 Filler (Polyprophylene yarn,or extruded filler
4 up to request)
5 4 Binding tape (Manufacturer's option)
5 Inner Covering (PVC Compound)
6
6 Galvanized Round Steel Wire armour
7
7 Binding tape (Manufacturer's option)
8 Outer sheath (PVC Compound)
8
Page - 34
Section 2 - PVC Insulated Cables
Armoured Cables
SINGLE CORE
Conductor Nominal Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter of Thickness diameter Weight Conductor
Cross- of number of of of inner Aluminium of of of Resistance
section Cond. of wire Conductor Insulation covering wire Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km
800 RM 127 37.1 2.8 1.4 2.5 2.5 56.0 9410 0.0221
1000 RM 127 41.6 3.0 1.4 2.5 2.7 61.0 11635 0.0176
Page - 35
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC / SWA / PVC (IEC 60502-1)
TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Diameter Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. of of of Resistance
section Cond. of wire Conductor Insulation covering Steel wire Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.8 1.8 14.0 335 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 1.8 14.5 350 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 1.8 15.0 380 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 1.8 15.5 395 7.41
4 RE 1 2.26 1.0 1.0 0.8 1.8 16.5 475 4.61
4 RM 7 2.6 1.0 1.0 0.8 1.8 17.5 495 4.61
6 RM 7 3.12 1.0 1.0 1.25 1.8 19.0 670 3.08
10 RM 7 4.1 1.0 1.0 1.25 1.8 21.0 840 1.83
16 RM 7 5.1 1.0 1.0 1.25 1.8 23.0 1020 1.15
25 RM 7 6.4 1.2 1.0 1.6 1.8 27.5 1510 0.727
35 RM 7 7.6 1.2 1.0 1.6 1.8 30.0 1810 0.524
50 RM 19 9.2 1.4 1.0 1.6 1.9 34.0 2320 0.387
70 RM 19 10.9 1.4 1.0 2.0 2.0 38.0 3125 0.268
95 RM 19 12.6 1.6 1.2 2.0 2.2 43.5 3990 0.193
120 RM 37 14.2 1.6 1.2 2.0 2.3 47.0 4695 0.153
150 RM 37 15.9 1.8 1.2 2.5 2.4 52.0 5995 0.124
185 RM 37 17.6 2.0 1.4 2.5 2.6 57.0 7110 0.0991
240 RM 61 20.3 2.2 1.4 2.5 2.8 63.5 8830 0.0754
300 RM 61 22.7 2.4 1.6 2.5 2.9 70.0 10575 0.0601
Page - 36
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC / SWA / PVC (IEC 60502-1)
THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Diameter Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. of of of Resistance
section Cond. of wire Conductor Insulation covering Steel wire Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.8 1.8 14.5 375 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 1.8 15.0 385 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 1.8 15.5 430 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 1.8 16.0 450 7.41
4 RE 1 2.26 1.0 1.0 0.8 1.8 18.0 640 4.61
4 RM 7 2.6 1.0 1.0 1.25 1.8 18.5 660 4.61
6 RM 7 3.1 1.0 1.0 1.25 1.8 20.0 770 3.08
10 RM 7 4.1 1.0 1.0 1.25 1.8 22.0 975 1.83
16 RM 7 5.1 1.0 1.0 1.25 1.8 24.0 1230 1.15
25 RM 7 6.4 1.2 1.0 1.6 1.8 29.0 1820 0.727
35 RM 7 7.6 1.2 1.0 1.6 1.8 31.5 2230 0.524
50 SM 19 6.8 1.4 1.0 1.6 2.0 30.5 2560 0.387
70 SM 19 8.2 1.4 1.2 2.0 2.1 34.5 3580 0.268
95 SM 19 9.7 1.6 1.2 2.0 2.2 39.0 4655 0.193
120 SM 37 10.9 1.6 1.2 2.0 2.3 42.0 5410 0.153
150 SM 37 11.9 1.8 1.4 2.5 2.5 46.0 6830 0.124
185 SM 37 13.6 2.0 1.4 2.5 2.7 51.0 8260 0.0991
240 SM 37 15.8 2.2 1.6 2.5 2.9 57.0 10635 0.0754
300 SM 37 17.5 2.4 1.6 2.5 3.1 62.0 12795 0.0601
Page - 37
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC / SWA / PVC (IEC 60502-1)
FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Diameter Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. of of of Resistance
section Cond. of wire Conductor Insulation covering Steel wire Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.8 1.8 15.5 415 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 1.8 16.0 435 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 1.8 16.5 490 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 1.8 17.0 510 7.41
4 RE 1 2.26 1.0 1.0 0.8 1.8 19.5 740 4.61
4 RM 7 2.6 1.0 1.0 1.25 1.8 20.0 765 4.61
6 RM 7 3.1 1.0 1.0 1.25 1.8 21.0 895 3.08
10 RM 7 4.1 1.0 1.0 1.25 1.8 23.5 1145 1.83
16 RM 7 5.1 1.0 1.0 1.6 1.8 27.0 1625 1.15
25 RM 7 6.4 1.2 1.0 1.6 1.8 31.0 2185 0.727
35 RM 7 7.6 1.2 1.0 1.6 1.9 34.0 2700 0.524
50 SM 19 8.1 1.4 1.2 2.0 2.1 35.0 3470 0.387
70 SM 19 9.7 1.4 1.2 2.0 2.2 38.5 4455 0.268
95 SM 19 11.4 1.6 1.2 2.5 2.4 44.5 6225 0.193
120 SM 37 12.9 1.6 1.4 2.5 2.5 48.5 7250 0.153
150 SM 37 14.2 1.8 1.4 2.5 2.7 52.5 8665 0.124
185 SM 37 16.0 2.0 1.6 2.5 2.9 58.0 10505 0.0991
240 SM 37 18.2 2.2 1.6 2.5 3.1 63.5 13415 0.0754
300 SM 37 20.6 2.4 1.6 2.5 3.3 70.0 16300 0.0601
Page - 38
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC / SWA / PVC (IEC 60502-1)
FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Diameter Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. of of of Resistance
section Cond. of wire Conductor Insulation covering Steel wire Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.8 1.8 16.5 465 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 1.8 17.0 490 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 1.8 17.5 555 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 1.8 18.0 575 7.41
4 RE 1 2.26 1.0 1.0 0.8 1.8 20.5 835 4.61
4 RM 7 2.6 1.0 1.0 1.25 1.8 21.5 865 4.61
6 RM 7 3.1 1.0 1.0 1.25 1.8 22.5 1025 3.08
10 RM 7 4.1 1.0 1.0 1.6 1.8 26.5 1480 1.83
16 RM 7 5.1 1.0 1.0 1.60 1.8 29.0 1893 1.15
25 RM 7 6.4 1.2 1.0 1.6 1.9 33.5 2580 0.727
35 RM 7 7.6 1.2 1.0 2.0 2.0 38.0 3470 0.524
50 RM 19 9.2 1.4 1.2 2.0 2.2 44.0 4505 0.387
Page - 39
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (acc. to IEC 60502-1)
Constructions :
1 Conductor (Annealed Copper) Note : Special application upon request
2 Insulation (PVC Compound) * Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
3 Filler (Polyprophylene yarn,or extruded filler
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
up to request) * Anti termite performance.
4 Binding tape (Manufacturer's option) * Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed
5 Inner Covering (PVC Compound)
6 Galvanized Flat Steel Wire armour
7 Galvanized Steel Tape binding
8 Outer sheath (PVC Compound)
Page - 40
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (IEC 60502-1)
TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. thickness of of of Resistance
section Cond. of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² Number mm mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.8 0.3 1.8 14.0 410 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 0.3 1.8 14.5 420 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 0.3 1.8 15.0 445 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 0.3 1.8 15.5 480 7.41
4 RE 1 2.26 1.0 1.0 0.8 0.3 1.8 17.0 570 4.61
4 RM 7 2.6 1.0 1.0 0.8 0.3 1.8 17.5 585 4.61
6 RM 7 3.1 1.0 1.0 0.8 0.3 1.8 18.5 675 3.08
10 RM 7 4.1 1.0 1.0 0.8 0.3 1.8 20.5 830 1.83
16 RM 7 5.1 1.0 1.0 0.8 0.3 1.8 22.5 1040 1.15
25 RM 7 6.4 1.2 1.0 0.8 0.3 1.8 26.0 1365 0.727
35 RM 7 7.6 1.2 1.0 0.8 0.3 1.8 28.0 1675 0.524
50 RM 19 9.2 1.4 1.0 0.8 0.3 1.8 32.0 2135 0.387
70 RM 19 10.9 1.4 1.0 0.8 0.3 1.9 35.5 2695 0.268
95 RM 19 12.6 1.6 1.2 0.8 0.3 2.1 41.0 3485 0.193
120 RM 37 14.2 1.6 1.2 0.8 0.3 2.2 44.5 4150 0.153
150 RM 37 15.9 1.8 1.2 0.8 0.3 2.3 49.0 4995 0.124
185 RM 37 17.6 2.0 1.4 0.8 0.3 2.4 53.5 5970 0.0991
240 RM 61 20.3 2.2 1.4 0.8 0.3 2.6 60.0 7540 0.0754
300 RM 61 22.7 2.4 1.6 0.8 0.3 2.8 66.5 9180 0.0601
Page - 41
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (IEC 60502-1)
THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. thickness of of of Resistance
section Cond. of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.8 0.3 1.8 14.5 440 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 0.3 1.8 15.0 450 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 0.3 1.8 15.5 510 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 0.3 1.8 16.0 525 7.41
4 RE 1 2.26 1.0 1.0 0.8 0.3 1.8 17.5 635 4.61
4 RM 7 2.6 1.0 1.0 0.8 0.3 1.8 18.0 650 4.61
6 RM 7 3.1 1.0 1.0 0.8 0.3 1.8 19.0 760 3.08
10 RM 7 4.1 1.0 1.0 0.8 0.3 1.8 21.5 985 1.83
16 RM 7 5.1 1.0 1.0 0.8 0.3 1.8 23.5 1230 1.15
25 RM 7 6.4 1.2 1.0 0.8 0.3 1.8 27.0 1685 0.727
35 RM 7 7.6 1.2 1.0 0.8 0.3 1.8 30.0 2090 0.524
50 SM 19 6.8 1.4 1.0 0.8 0.3 1.9 28.5 2385 0.387
70 SM 19 8.2 1.4 1.2 0.8 0.3 2.0 32.0 3150 0.268
95 SM 19 9.7 1.6 1.2 0.8 0.3 2.2 37.0 4185 0.193
120 SM 37 10.9 1.6 1.2 0.8 0.3 2.3 39.5 4905 0.153
150 SM 37 11.9 1.8 1.4 0.8 0.3 2.4 43.0 5890 0.124
185 SM 37 13.6 2.0 1.4 0.8 0.3 2.6 47.5 7215 0.0991
240 SM 37 15.8 2.2 1.6 0.8 0.3 2.8 54.0 9460 0.0754
300 SM 37 17.5 2.4 1.6 0.8 0.3 2.9 58.5 11520 0.0601
Page - 42
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (IEC 60502-1)
FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. thickness of of of Resistance
section Cond. of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.8 0.3 1.8 15.5 500 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 0.3 1.8 16.0 510 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 0.3 1.8 16.5 560 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 0.3 1.8 17.0 605 7.41
4 RE 1 2.26 1.0 1.0 0.8 0.3 1.8 18.5 735 4.61
4 RM 7 2.6 1.0 1.0 0.8 0.3 1.8 19.5 755 4.61
6 RM 7 3.1 1.0 1.0 0.8 0.3 1.8 20.5 890 3.08
10 RM 7 4.1 1.0 1.0 0.8 0.3 1.8 23.0 1160 1.83
16 RM 7 5.1 1.0 1.0 0.8 0.3 1.8 25.5 1500 1.15
25 RM 7 6.4 1.2 1.0 0.8 0.3 1.8 29.5 2055 0.727
35 RM 7 7.6 1.2 1.0 0.8 0.3 1.9 32.5 2570 0.524
50 SM 19 8.1 1.4 1.2 0.8 0.3 2.0 32.5 3045 0.387
70 SM 19 9.7 1.4 1.2 0.8 0.3 2.1 36.0 3995 0.268
95 SM 19 11.4 1.6 1.2 0.8 0.3 2.3 41.5 5310 0.193
120 SM 37 12.9 1.6 1.4 0.8 0.3 2.4 45.0 6290 0.153
150 SM 37 14.2 1.8 1.4 0.8 0.3 2.6 49.0 7570 0.124
185 SM 37 16.0 2.0 1.6 0.8 0.3 2.7 54.5 9310 0.0991
240 SM 37 18.2 2.2 1.6 0.8 0.3 3.0 60.5 12120 0.0754
300 SM 37 20.6 2.4 1.6 0.8 0.3 3.2 66.5 14865 0.0601
Page - 43
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (IEC 60502-1)
FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. thickness of of of Resistance
section of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.8 0.3 1.8 16.5 540 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 0.3 1.8 17.0 580 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 0.3 1.8 17.5 635 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 0.3 1.8 18.0 655 7.41
4 RE 1 2.26 1.0 1.0 0.8 0.3 1.8 20.0 835 4.61
4 RM 7 2.6 1.0 1.0 0.8 0.3 1.8 21.0 860 4.61
6 RM 7 3.1 1.0 1.0 0.8 0.3 1.8 22.0 1025 3.08
10 RM 7 4.1 1.0 1.0 0.8 0.3 1.8 25.0 1340 1.83
16 RM 7 5.1 1.0 1.0 0.8 0.3 1.8 27.5 1745 1.15
25 RM 7 6.4 1.2 1.0 0.8 0.3 1.8 32.0 2415 0.727
35 RM 7 7.6 1.2 1.0 0.8 0.3 1.9 35.5 3070 0.524
50 RM 19 9.2 1.4 1.2 0.8 0.3 2.1 41.5 4015 0.387
Page - 44
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, ALUMINIUM TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DATA/PVC (acc. to IEC 60502-1)
Constructions :
2
1 Conductor (Annealed Copper)
3 2 Insulation (PVC Compound)
4 3 Inner Covering (PVC Compound)
4 Double Aluminium Tape armour
5 Outer sheath (PVC Compound)
5
600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DSTA/PVC (acc. to IEC 60502-1)
Constructions :
1
1 Conductor (Annealed Copper)
2 Insulation (PVC Compound)
2
3 Filler (Polyprophylene yarn,or extruded filler
3
up to request)
4
4
Binding tape (Manufacturer's option)
5
5 Inner Covering (PVC Compound)
6 6 Double Galvanized Steel Tape armour
7 Outer sheath (PVC Compound)
6
Page - 45
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, ALUMINIUM TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DATA/PVC (IEC 60502-1)
SINGLE CORE
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- of number of of of Inner thickness of of of of Resistance
section Cond. of wire Conductor Insulation covering Aluminium Sheath cable cable at 20°C
area (approx.) (approx.) tape (approx.) (approx.)
mm² number mm mm mm mm mm mm kg/km /km
50 RM 19 9.2 1.4 1.0 0.5 1.8 19.5 820 0.387
70 RM 19 10.9 1.4 1.0 0.5 1.8 21.0 1045 0.268
95 RM 19 12.6 1.6 1.0 0.5 1.8 23.5 1345 0.193
120 RM 37 14.2 1.6 1.0 0.5 1.8 25.0 1610 0.153
150 RM 37 15.9 1.8 1.0 0.5 1.8 27.0 1950 0.124
185 RM 37 17.6 2.0 1.0 0.5 1.8 29.5 2340 0.0991
240 RM 61 20.3 2.2 1.0 0.5 1.9 32.5 2990 0.0754
300 RM 61 22.7 2.4 1.0 0.5 1.9 35.0 3630 0.0601
400 RM 61 25.7 2.6 1.2 0.5 2.1 39.5 4640 0.0470
500 RM 61 28.8 2.8 1.2 0.5 2.2 43.5 5695 0.0366
Page - 46
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DSTA/PVC (IEC 60502-1)
TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. of of of Resistance
section Cond. of wire Conductor Insulation covering Steel tape Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.2 1.8 13.0 240 12.1
1.5 RM 7 1.6 0.8 1.0 0.2 1.8 13.0 250 12.1
2.5 RE 1 1.78 0.8 1.0 0.2 1.8 13.5 280 7.41
2.5 RM 7 2.0 0.8 1.0 0.2 1.8 14.0 290 7.41
4 RE 1 2.26 1.0 1.0 0.2 1.8 15.5 360 4.61
4 RM 7 2.6 1.0 1.0 0.2 1.8 16.0 375 4.61
6 RM 7 3.1 1.0 1.0 0.2 1.8 17.0 440 3.08
10 RM 7 4.1 1.0 1.0 0.2 1.8 19.0 575 1.83
16 RM 7 5.1 1.0 1.0 0.2 1.8 21.0 745 1.15
25 RM 7 6.4 1.2 1.0 0.2 1.8 24.5 1030 0.727
35 RM 7 7.6 1.2 1.0 0.2 1.8 27.0 1290 0.524
50 RM 19 9.2 1.4 1.0 0.2 1.8 31.0 1715 0.387
70 RM 19 10.9 1.4 1.0 0.2 1.9 34.0 2265 0.268
95 RM 19 12.6 1.6 1.2 0.2 2.1 39.0 2900 0.193
120 RM 37 14.2 1.6 1.2 0.5 2.2 43.5 3925 0.153
150 RM 37 15.9 1.8 1.2 0.5 2.3 48.0 4725 0.124
185 RM 37 17.6 2.0 1.4 0.5 2.4 52.5 5675 0.0991
240 RM 61 20.3 2.2 1.4 0.5 2.6 58.5 7170 0.0754
300 RM 61 22.7 2.4 1.6 0.5 2.8 64.5 8710 0.0601
Page - 47
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DSTA/PVC (IEC 60502-1)
THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. of of of Resistance
section Cond. of wire Conductor Insulation covering Steel tape Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.2 1.8 13.5 270 12.1
1.5 RM 7 1.6 0.8 1.0 0.2 1.8 13.5 285 12.1
2.5 RE 1 1.78 0.8 1.0 0.2 1.8 14.0 320 7.41
2.5 RM 7 2.0 0.8 1.0 0.2 1.8 14.5 335 7.41
4 RE 1 2.26 1.0 1.0 0.2 1.8 16.0 420 4.61
4 RM 7 2.6 1.0 1.0 0.2 1.8 16.5 445 4.61
6 RM 7 3.1 1.0 1.0 0.2 1.8 18.0 530 3.08
10 RM 7 4.1 1.0 1.0 0.2 1.8 20.0 710 1.83
16 RM 7 5.1 1.0 1.0 0.2 1.8 22.0 935 1.15
25 RM 7 6.4 1.2 1.0 0.2 1.8 26.0 1330 0.727
35 RM 7 7.6 1.2 1.0 0.2 1.8 28.5 1685 0.524
50 SM 19 6.8 1.4 1.0 0.2 1.9 27.0 2005 0.387
70 SM 19 8.2 1.4 1.2 0.2 2.0 30.5 2725 0.268
95 SM 19 9.7 1.6 1.2 0.5 2.2 36.5 4065 0.193
120 SM 37 10.9 1.6 1.2 0.5 2.3 39.5 4765 0.153
150 SM 37 11.9 1.8 1.4 0.5 2.4 42.5 5745 0.124
185 SM 37 13.6 2.0 1.4 0.5 2.6 47.5 7055 0.0991
240 SM 37 15.8 2.2 1.6 0.5 2.8 53.5 9255 0.0754
300 SM 37 17.5 2.4 1.6 0.5 2.9 58.0 11300 0.0601
Page - 48
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC / DSTA / PVC (IEC 60502-1)
FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. of of of Resistance
section Cond. of wire Conductor Insulation covering Steel tape Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.2 1.8 14.0 310 12.1
1.5 RM 7 1.6 0.8 1.0 0.2 1.8 14.5 325 12.1
2.5 RE 1 1.78 0.8 1.0 0.2 1.8 15.0 375 7.41
2.5 RM 7 2.0 0.8 1.0 0.2 1.8 15.5 390 7.41
4 RE 1 2.26 1.0 1.0 0.2 1.8 17.5 500 4.61
4 RM 7 2.6 1.0 1.0 0.2 1.8 18.0 525 4.61
6 RM 7 3.1 1.0 1.0 0.2 1.8 19.0 640 3.08
10 RM 7 4.1 1.0 1.0 0.2 1.8 21.5 860 1.83
16 RM 7 5.1 1.0 1.0 0.2 1.8 24.0 1160 1.15
25 RM 7 6.4 1.2 1.0 0.2 1.8 28.0 1650 0.727
35 RM 7 7.6 1.2 1.0 0.2 1.8 31.0 2120 0.524
50 SM 19 8.1 1.4 1.2 0.2 2.0 31.0 2595 0.387
70 SM 19 9.7 1.4 1.2 0.5 2.1 36.0 3865 0.268
95 SM 19 11.4 1.6 1.2 0.5 2.3 41.0 5175 0.193
120 SM 37 12.9 1.6 1.4 0.5 2.4 44.5 6125 0.153
150 SM 37 14.2 1.8 1.4 0.5 2.6 49.0 7405 0.124
185 SM 37 16.0 2.0 1.6 0.5 2.7 54.0 9115 0.0991
240 SM 37 18.2 2.2 1.6 0.5 3.0 60.0 11900 0.0754
300 SM 37 20.6 2.4 1.6 0.5 3.2 66.5 14625 0.0601
Page - 49
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DSTA/PVC (IEC 60502-1)
FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. of of of Resistance
section Cond. of wire Conductor Insulation covering Steel tape Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.8 1.0 0.2 1.8 15.0 350 12.1
1.5 RM 7 1.6 0.8 1.0 0.2 1.8 15.5 370 12.1
2.5 RE 1 1.78 0.8 1.0 0.2 1.8 16.0 425 7.41
2.5 RM 7 2.0 0.8 1.0 0.2 1.8 16.5 450 7.41
4 RE 1 2.26 1.0 1.0 0.2 1.8 18.5 580 4.61
4 RM 7 2.6 1.0 1.0 0.2 1.8 19.5 610 4.61
6 RM 7 3.1 1.0 1.0 0.2 1.8 20.5 750 3.08
10 RM 7 4.1 1.0 1.0 0.2 1.8 23.5 1025 1.83
16 RM 7 5.1 1.0 1.0 0.2 1.8 26.0 1390 1.15
25 RM 7 6.4 1.2 1.0 0.2 1.8 30.5 1995 0.727
35 RM 7 7.6 1.2 1.0 0.2 1.9 34.0 2580 0.524
50 RM 19 9.2 1.4 1.2 0.2 2.1 40.0 3400 0.387
Page - 50
Section 3 - XLPE Insulated Cables
Unarmoured Cables
Page - 51
Section 3 - XLPE Insulated Cables
Unarmoured Cables
SINGLE CORE
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of Resistance
section Cond. of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.4 5.4 45 12.1
1.5 RM 7 1.6 0.7 1.4 5.6 45 12.1
2.5 RE 1 1.78 0.7 1.4 5.8 55 7.41
2.5 RM 7 2.0 0.7 1.4 6.0 55 7.41
4 RE 1 2.26 0.7 1.4 6.3 75 4.61
4 RM 7 2.6 0.7 1.4 6.6 75 4.61
6 RM 7 3.1 0.7 1.4 7.1 100 3.08
10 RM 7 4.1 0.7 1.4 8.1 140 1.83
16 CM 7 4.7 0.7 1.4 8.7 195 1.15
25 CM 7 5.9 0.9 1.4 10.5 290 0.727
35 CM 7 7.1 0.9 1.4 11.5 385 0.524
50 CM 19 8.1 1.0 1.4 12.5 500 0.387
70 CM 19 9.7 1.1 1.4 14.5 700 0.268
95 CM 19 11.6 1.1 1.5 16.5 955 0.193
120 CM 37 12.9 1.2 1.5 18.0 1190 0.153
150 CM 37 14.3 1.4 1.6 20.0 1475 0.124
185 CM 37 16.0 1.6 1.6 22.5 1825 0.0991
240 CM 37 18.3 1.7 1.7 25.0 2360 0.0754
300 CM 61 20.7 1.8 1.8 27.5 2945 0.0601
400 CM 61 23.4 2.0 1.9 31.0 3740 0.0470
500 CM 61 26.5 2.2 2.0 34.5 4780 0.0366
630 CM 91 30.3 2.4 2.2 39.5 6165 0.0283
800 CM 91 34.3 2.6 2.3 44.0 7860 0.0221
1000 RM 127 41.6 2.8 2.4 52.0 10030 0.0176
Note RE : Round Solid Class 1, RM : Circular Stranded Class 2, CM : Circular Stranded Compacted Class 2
Page - 52
Section 3 - XLPE Insulated Cables
Unarmoured Cables
TWO CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of Resistance
section Cond. of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.8 9.5 105 12.1
1.5 RM 7 1.6 0.7 1.8 10.0 110 12.1
2.5 RE 1 1.78 0.7 1.8 10.5 130 7.41
2.5 RM 7 2.0 0.7 1.8 10.5 135 7.41
4 RE 1 2.26 0.7 1.8 11.5 170 4.61
4 RM 7 2.6 0.7 1.8 12.0 180 4.61
6 RM 7 3.1 0.7 1.8 13.0 230 3.08
10 RM 7 4.1 0.7 1.8 15.0 330 1.83
16 CM 7 4.7 0.7 1.8 16.0 445 1.15
25 CM 7 5.9 0.9 1.8 19.5 660 0.727
35 CM 7 7.1 0.9 1.8 21.5 870 0.524
50 CM 19 8.1 1.0 1.8 24.0 1130 0.387
70 CM 19 9.7 1.1 1.8 27.5 1570 0.268
95 CM 19 11.6 1.1 2.0 31.5 2125 0.193
120 CM 37 12.9 1.2 2.1 35.0 2645 0.153
150 CM 37 14.3 1.4 2.2 38.5 3275 0.124
185 CM 37 16.0 1.6 2.3 43.5 4075 0.0991
240 CM 37 18.3 1.7 2.5 48.5 5270 0.0754
300 CM 61 20.7 1.8 2.7 54.5 6575 0.0601
400 CM 61 23.4 2.0 2.9 61.0 8355 0.0470
Page - 53
Section 3 - XLPE Insulated Cables
Unarmoured Cables
THREE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of Resistance
section Cond. of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.8 10.0 125 12.1
1.5 RM 7 1.6 0.7 1.8 10.5 130 12.1
2.5 RE 1 1.78 0.7 1.8 11.0 160 7.41
2.5 RM 7 2.0 0.7 1.8 11.5 170 7.41
4 RE 1 2.26 0.7 1.8 12.0 215 4.61
4 RM 7 2.6 0.7 1.8 12.5 230 4.61
6 RM 7 3.1 0.7 1.8 13.5 295 3.08
10 RM 7 4.1 0.7 1.8 16.0 435 1.83
16 CM 7 4.7 0.7 1.8 17.0 605 1.15
25 CM 7 5.9 0.9 1.8 20.5 900 0.727
35 CM 7 7.1 0.9 1.8 23.0 1200 0.524
50 CM 19 8.1 1.0 1.8 25.5 1570 0.387
70 CM 19 9.7 1.1 1.9 29.5 2200 0.268
95 CM 19 11.6 1.1 2.0 34.0 2995 0.193
120 CM 37 12.9 1.2 2.1 37.5 3735 0.153
150 CM 37 14.3 1.4 2.3 41.5 4650 0.124
185 CM 37 16.0 1.6 2.4 46.5 5760 0.0991
240 CM 37 18.3 1.7 2.6 52.5 7500 0.0754
300 CM 61 20.7 1.8 2.8 58.5 9360 0.0601
400 CM 61 23.4 2.0 3.1 65.5 11900 0.0470
Page - 54
Section 3 - XLPE Insulated Cables
Unarmoured Cables
FOUR CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of Resistance
section Cond. of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
Page - 55
Section 3 - XLPE Insulated Cables
Unarmoured Cables
FIVE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of Resistance
section Cond. of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.8 11.5 175 12.1
1.5 RM 7 1.6 0.7 1.8 12.0 185 12.1
2.5 RE 1 1.78 0.7 1.8 12.5 235 7.41
2.5 RM 7 2.0 0.7 1.8 13.0 245 7.41
4 RE 1 2.26 0.7 1.8 14.0 320 4.61
4 RM 7 2.6 0.7 1.8 15.0 340 4.61
6 RM 7 3.1 0.7 1.8 16.0 450 3.08
10 RM 7 4.1 0.7 1.8 19.0 675 1.83
16 CM 7 4.7 0.7 1.8 20.5 945 1.15
25 CM 7 5.9 0.9 1.8 25.0 1425 0.727
35 CM 7 7.1 0.9 1.8 28.0 1915 0.524
50 CM 19 8.1 1.0 2.0 31.5 2535 0.387
Page - 56
Section 3 - XLPE Insulated Cables
Unarmoured Cables
Page - 57
Section 3 - XLPE Insulated Cables
Unarmoured Cables
Page - 58
Section 3 - XLPE Insulated Cables
Unarmoured Cables
Page - 59
Section 3 - XLPE Insulated Cables
Unarmoured Cables
Page - 60
Section 3 - XLPE Insulated Cables
Unarmoured Cables
1 Constructions :
1 Conductor (Annealed Copper)
2 2 Insulation (XLPE Compound)
3 Filler (Polyprophylene yarn,or extruded filler
up to request)
3
4 Binding tape (Manufacturer's option)
4 5 Copper Tape screen
6 Binding tape (Manufacturer's option)
5
7 Outer sheath (PVC Compound)
Page - 61
Section 3 - XLPE Insulated Cables
Unarmoured Cables
TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of of Resistance
section area Cond. of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 0.1 1.8 10.0 125 12.1
1.5 RM 7 1.6 0.7 0.1 1.8 10.5 135 12.1
2.5 RE 1 1.78 0.7 0.1 1.8 11.0 155 7.41
2.5 RM 7 2.0 0.7 0.1 1.8 11.5 165 7.41
4 RE 1 2.26 0.7 0.1 1.8 12.0 200 4.61
4 RM 7 2.6 0.7 0.1 1.8 12.5 210 4.61
6 RE 1 2.77 0.7 0.1 1.8 13.0 250 3.08
6 RM 7 3.1 0.7 0.1 1.8 13.5 265 3.08
10 RM 7 4.1 0.7 0.1 1.8 15.5 370 1.83
16 CM 7 4.7 0.7 0.1 1.8 16.5 490 1.15
25 CM 7 5.9 0.9 0.1 1.8 20.0 715 0.727
35 CM 7 7.1 0.9 0.1 1.8 22.5 935 0.524
50 CM 19 8.1 1.0 0.1 1.8 24.5 1200 0.387
70 CM 19 9.7 1.1 0.1 1.9 28.5 1650 0.268
95 CM 19 11.6 1.1 0.1 2.0 32.5 2225 0.193
120 CM 37 12.9 1.2 0.1 2.1 35.5 2755 0.153
150 CM 37 14.3 1.4 0.1 2.2 39.5 3395 0.124
185 CM 37 16.0 1.6 0.1 2.3 44.0 4205 0.0991
240 CM 37 18.3 1.7 0.1 2.5 49.5 5425 0.0754
300 CM 61 20.7 1.8 0.1 2.7 55.0 6755 0.0601
400 CM 61 23.4 2.0 0.1 2.9 61.5 8545 0.0470
THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of of Resistance
section area Cond. of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 0.1 1.8 10.5 150 12.1
1.5 RM 7 1.6 0.7 0.1 1.8 11.0 155 12.1
2.5 RE 1 1.78 0.7 0.1 1.8 11.5 190 7.41
2.5 RM 7 2.0 0.7 0.1 1.8 12.0 195 7.41
4 RE 1 2.26 0.7 0.1 1.8 12.5 250 4.61
4 RM 7 2.6 0.7 0.1 1.8 13.0 260 4.61
6 RE 1 2.77 0.7 0.1 1.8 13.5 320 3.08
6 RM 7 3.1 0.7 0.1 1.8 14.0 330 3.08
10 RM 7 4.1 0.7 0.1 1.8 16.5 480 1.83
16 CM 7 4.7 0.7 0.1 1.8 17.5 650 1.15
25 CM 7 5.9 0.9 0.1 1.8 21.0 960 0.727
35 CM 7 7.1 0.9 0.1 1.8 23.5 1275 0.524
50 CM 19 8.1 1.0 0.1 1.8 26.5 1645 0.387
70 CM 19 9.7 1.1 0.1 1.9 30.0 2285 0.268
95 CM 19 11.6 1.1 0.1 2.0 34.5 3110 0.193
120 CM 37 12.9 1.2 0.1 2.2 38.0 3870 0.153
150 CM 37 14.3 1.4 0.1 2.3 42.0 4775 0.124
185 CM 37 16.0 1.6 0.1 2.4 47.0 5910 0.0991
240 CM 37 18.3 1.7 0.1 2.6 53.0 7675 0.0754
300 CM 61 20.7 1.8 0.1 2.8 59.0 9565 0.0601
400 CM 61 23.4 2.0 0.1 3.1 66.0 12110 0.0470
FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of of Resistance
section area Cond. of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 0.1 1.8 11.5 175 12.1
1.5 RM 7 1.6 0.7 0.1 1.8 12.0 185 12.1
2.5 RE 1 1.78 0.7 0.1 1.8 12.5 230 7.41
2.5 RM 7 2.0 0.7 0.1 1.8 13.0 240 7.41
4 RE 1 2.26 0.7 0.1 1.8 13.5 300 4.61
4 RM 7 2.6 0.7 0.1 1.8 14.0 320 4.61
6 RE 1 2.77 0.7 0.1 1.8 14.5 395 3.08
6 RM 7 3.1 0.7 0.1 1.8 15.5 410 3.08
10 RM 7 4.1 0.7 0.1 1.8 18.0 600 1.83
16 CM 7 4.7 0.7 0.1 1.8 19.5 825 1.15
25 CM 7 5.9 0.9 0.1 1.8 23.0 1230 0.727
35 CM 7 7.1 0.9 0.1 1.8 26.0 1635 0.524
50 CM 19 8.1 1.0 0.1 1.9 29.0 2120 0.387
70 CM 19 9.7 1.1 0.1 2.0 33.5 2980 0.268
95 CM 19 11.6 1.1 0.1 2.2 38.5 4075 0.193
120 CM 37 12.9 1.2 0.1 2.3 42.5 5055 0.153
150 CM 37 14.3 1.4 0.1 2.5 47.0 6245 0.124
185 CM 37 16.0 1.6 0.1 2.6 52.5 7755 0.0991
240 CM 37 18.3 1.7 0.1 2.8 59.0 10070 0.0754
300 CM 61 20.7 1.8 0.1 3.0 65.5 12550 0.0601
400 CM 61 23.4 2.0 0.1 3.3 73.5 15900 0.0470
FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of of of of Resistance
section area Cond. of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² - Number mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 0.1 1.8 12.0 205 12.1
1.5 RM 7 1.6 0.7 0.1 1.8 12.5 215 12.1
2.5 RE 1 1.78 0.7 0.1 1.8 13.5 265 7.41
2.5 RM 7 2.0 0.7 0.1 1.8 14.0 280 7.41
4 RE 1 2.26 0.7 0.1 1.8 14.5 360 4.61
4 RM 7 2.6 0.7 0.1 1.8 15.5 380 4.61
6 RE 1 2.77 0.7 0.1 1.8 16.0 475 3.08
6 RM 7 3.1 0.7 0.1 1.8 17.0 490 3.08
10 RM 7 4.1 0.7 0.1 1.8 19.5 720 1.83
16 CM 7 4.7 0.7 0.1 1.8 21.0 1005 1.15
25 CM 7 5.9 0.9 0.1 1.8 25.5 1495 0.727
35 CM 7 7.1 0.9 0.1 1.9 28.5 2005 0.524
50 CM 19 8.1 1.0 0.1 2.0 32.0 2620 0.387
Page - 65
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, ALUMINIUM WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/AWA/PVC (acc. to IEC 60502-1)
1
Constructions :
2
1 Conductor (Annealed Copper)
3 2 Insulation (XLPE Compound)
4 3 Inner Covering (PVC Compound)
600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/SWA/PVC (acc. to IEC 60502-1)
Constructions :
1
1 Conductor (Annealed Copper)
2 2 Insulation (XLPE Compound)
8
Note : Special application upon request
* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed
Page - 66
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, ALUMINIUM WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE / AWA / PVC (IEC 60502-1)
SINGLE CORE
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- of number of of of Inner diameter of of of of Resistance
section Cond. of wire Conductor Insulation covering Aluminium Sheath cable cable at 20°C
area (approx.) (approx.) wire (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km
1000 RM 127 41.6 2.8 1.4 2.5 2.5 60.5 11315 0.0176
Page - 67
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE / SWA / PVC (IEC 60502-1)
TWO CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- of number of of of Inner diameter of of of Resistance
section Cond. of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.8 1.8 13.5 315 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 1.8 14.0 325 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 1.8 14.5 355 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 1.8 15.0 375 7.41
4 RE 1 2.26 0.7 1.0 0.8 1.8 15.5 425 4.61
4 RM 7 2.6 0.7 1.0 0.8 1.8 16.0 440 4.61
6 RE 1 2.77 0.7 1.0 0.8 1.8 16.5 485 3.08
6 RM 7 3.1 0.7 1.0 0.8 1.8 17.0 515 3.08
10 RM 7 4.1 0.7 1.0 1.25 1.8 20.0 760 1.83
16 CM 7 4.7 0.7 1.0 1.25 1.8 21.0 910 1.15
25 CM 7 5.9 0.9 1.0 1.6 1.8 25.0 1345 0.727
35 CM 7 7.1 0.9 1.0 1.6 1.8 27.5 1630 0.524
50 CM 19 8.1 1.0 1.0 1.6 1.8 30.0 1965 0.387
70 CM 19 9.7 1.1 1.0 1.6 2.0 34.0 2550 0.268
95 CM 19 11.6 1.1 1.2 2.0 2.1 39.0 3520 0.193
120 CM 37 12.9 1.2 1.2 2.0 2.2 42.0 4160 0.153
150 CM 37 14.3 1.4 1.2 2.0 2.3 46.0 4970 0.124
185 CM 37 16.0 1.6 1.4 2.5 2.5 52.0 6435 0.0991
240 CM 37 18.3 1.7 1.4 2.5 2.7 57.5 7895 0.0754
300 CM 61 20.7 1.8 1.6 2.5 2.8 63.0 9545 0.0601
600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE / SWA / PVC (IEC 60502-1)
THREE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- of number of of of Inner diameter of of of Resistance
section Cond. of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.8 1.8 14.0 345 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 1.8 14.5 360 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 1.8 15.0 400 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 1.8 15.5 420 7.41
4 RE 1 2.26 0.7 1.0 0.8 1.8 16.0 475 4.61
4 RM 7 2.6 0.7 1.0 0.8 1.8 17.0 505 4.61
6 RE 1 2.77 0.7 1.0 0.8 1.8 17.0 570 3.08
6 RM 7 3.1 0.7 1.0 0.8 1.8 18.0 595 3.08
10 RM 7 4.1 0.7 1.0 1.25 1.8 20.5 890 1.83
16 CM 7 4.7 0.7 1.0 1.25 1.8 22.0 1090 1.15
25 CM 7 5.9 0.9 1.0 1.6 1.8 26.5 1625 0.727
35 CM 7 7.1 0.9 1.0 1.6 1.8 29.0 2015 0.524
50 CM 19 8.1 1.0 1.0 1.6 1.9 31.5 2465 0.387
70 CM 19 9.7 1.1 1.2 2.0 2.0 37.0 3525 0.268
95 CM 19 11.6 1.1 1.2 2.0 2.2 41.5 4495 0.193
120 CM 37 12.9 1.2 1.2 2.0 2.3 45.0 5385 0.153
150 CM 37 14.3 1.4 1.4 2.5 2.5 50.0 6920 0.124
185 CM 37 16.0 1.6 1.4 2.5 2.6 55.0 8285 0.0991
240 CM 61 18.3 1.7 1.6 2.5 2.8 61.5 10400 0.0754
300 CM 61 20.7 1.8 1.6 2.5 3.0 67.5 12550 0.0601
600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE / SWA / PVC (IEC 60502-1)
FOUR CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- of number of of of Inner diameter of of of Resistance
section Cond. of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.8 1.8 15.0 385 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 1.8 15.5 400 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 1.8 16.0 455 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 1.8 16.5 475 7.41
4 RE 1 2.26 0.7 1.0 0.8 1.8 17.0 550 4.61
4 RM 7 2.6 0.7 1.0 0.8 1.8 18.0 575 4.61
6 RE 1 2.77 0.7 1.0 1.25 1.8 19.0 755 3.08
6 RM 7 3.1 0.7 1.0 1.25 1.8 19.5 795 3.08
10 RM 7 4.1 0.7 1.0 1.25 1.8 22.0 1040 1.83
16 CM 7 4.7 0.7 1.0 1.25 1.8 23.5 1295 1.15
25 CM 7 5.9 0.9 1.0 1.6 1.8 28.5 1955 0.727
35 CM 7 7.1 0.9 1.0 1.6 1.9 31.5 2440 0.524
50 CM 19 8.1 1.0 1.0 1.6 2.0 34.5 3040 0.387
70 CM 19 9.7 1.1 1.2 2.0 2.2 40.5 4345 0.268
95 CM 19 11.6 1.1 1.2 2.0 2.3 45.0 5580 0.193
120 CM 37 12.9 1.2 1.4 2.5 2.5 50.0 7195 0.153
150 CM 37 14.3 1.4 1.4 2.5 2.6 55.0 8600 0.124
185 CM 37 16.0 1.6 1.4 2.5 2.8 60.5 10390 0.0991
240 CM 37 18.3 1.7 1.6 2.5 3.0 67.5 13060 0.0754
300 CM 61 20.7 1.8 1.6 2.5 3.2 74.0 15810 0.0601
600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE / SWA / PVC (IEC 60502-1)
FIVE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- of number of of of Inner diameter of of of Resistance
section Cond. of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.8 1.8 16.0 430 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 1.8 16.5 450 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 1.8 17.0 510 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 1.8 17.5 535 7.41
4 RE 1 2.26 0.7 1.0 1.25 1.8 19.0 730 4.61
4 RM 7 2.6 0.7 1.0 1.25 1.8 19.5 765 4.61
6 RE 1 2.77 0.7 1.0 1.25 1.8 20.5 905 3.08
6 RM 7 3.1 0.7 1.0 1.25 1.8 21.0 910 3.08
10 RM 7 4.1 0.7 1.0 1.25 1.8 24.0 1205 1.83
16 CM 7 4.7 0.7 1.0 1.6 1.8 26.5 1670 1.15
25 CM 7 5.9 0.9 1.0 1.6 1.8 30.5 2290 0.727
35 CM 7 7.1 0.9 1.0 1.6 1.9 34.0 2880 0.524
50 CM 19 8.1 1.0 1.2 2.0 2.1 39.0 3920 0.387
Page - 71
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (acc. to IEC 60502-1)
2
1 Conductor (Annealed Copper)
2 Insulation (XLPE Compound)
3 Filler (Polyprophylene yarn,or extruded filler
3
up to request)
4 4 Binding tape (Manufacturer's option)
5 Inner Covering (PVC Compound)
5
6 Galvanized Flat Steel Wire armour
6 7 Galvanized Steel Tape binding
7 8 Outer sheath (PVC Compound)
Page - 72
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (IEC 60502-1)
TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. thickness of of of Resistance
section Cond. of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.8 0.3 1.8 14.0 365 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 0.3 1.8 14.0 400 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 0.3 1.8 14.5 430 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 0.3 1.8 15.0 435 7.41
4 RE 1 2.26 0.7 1.0 0.8 0.3 1.8 15.5 505 4.61
4 RM 7 2.6 0.7 1.0 0.8 0.3 1.8 16.0 515 4.61
6 RE 1 2.77 0.7 1.0 0.8 0.3 1.8 16.5 575 3.08
6 RM 7 3.1 0.7 1.0 0.8 0.3 1.8 17.0 600 3.08
10 RE 1 4.1 0.7 1.0 0.8 0.3 1.8 19.0 745 1.83
16 CM 6 4.7 0.7 1.0 0.8 0.3 1.8 20.5 900 1.15
25 CM 6 5.9 0.9 1.0 0.8 0.3 1.8 23.5 1190 0.727
35 CM 6 7.1 0.9 1.0 0.8 0.3 1.8 26.0 1475 0.524
50 CM 6 8.1 1.0 1.0 0.8 0.3 1.8 28.5 1805 0.387
70 CM 12 9.7 1.1 1.0 0.8 0.3 1.9 32.0 2330 0.268
95 CM 15 11.6 1.1 1.2 0.8 0.3 2.0 36.5 3035 0.193
120 CM 18 12.9 1.2 1.2 0.8 0.3 2.1 39.5 3635 0.153
150 CM 18 14.3 1.4 1.2 0.8 0.3 2.2 43.5 4385 0.124
185 CM 30 16.0 1.6 1.4 0.8 0.3 2.4 48.5 5345 0.0991
240 CM 34 18.3 1.7 1.4 0.8 0.3 2.6 54.0 6725 0.0754
300 CM 34 20.7 1.8 1.6 0.8 0.3 2.7 60.0 8225 0.0601
400 CM 53 23.4 2.0 1.6 0.8 0.3 3.0 66.5 10210 0.0470
600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (IEC 60502-1)
THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. thickness of of of Resistance
section Cond. of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.8 0.3 1.8 14.5 420 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 0.3 1.8 14.5 430 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 0.3 1.8 15.0 460 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 0.3 1.8 15.5 500 7.41
4 RE 1 2.26 0.7 1.0 0.8 0.3 1.8 16.0 555 4.61
4 RM 7 2.6 0.7 1.0 0.8 0.3 1.8 17.0 595 4.61
6 RE 1 2.77 0.7 1.0 0.8 0.3 1.8 17.5 665 3.08
6 RM 7 3.1 0.7 1.0 0.8 0.3 1.8 18.0 675 3.08
10 RE 1 4.1 0.7 1.0 0.8 0.3 1.8 20.0 885 1.83
16 CM 6 4.7 0.7 1.0 0.8 0.3 1.8 21.5 1090 1.15
25 CM 6 5.9 0.9 1.0 0.8 0.3 1.8 25.0 1470 0.727
35 CM 6 7.1 0.9 1.0 0.8 0.3 1.8 27.5 1845 0.524
50 CM 6 8.1 1.0 1.0 0.8 0.3 1.8 30.0 2285 0.387
70 CM 12 9.7 1.1 1.2 0.8 0.3 2.0 34.5 3070 0.268
95 CM 15 11.6 1.1 1.2 0.8 0.3 2.1 39.0 3990 0.193
120 CM 18 12.9 1.2 1.2 0.8 0.3 2.2 42.0 4820 0.153
150 CM 18 14.3 1.4 1.4 0.8 0.3 2.3 46.5 5875 0.124
185 CM 30 16.0 1.6 1.4 0.8 0.3 2.4 52.0 7165 0.0991
240 CM 34 18.3 1.7 1.6 0.8 0.3 2.7 58.0 9125 0.0754
300 CM 34 20.7 1.8 1.6 0.8 0.3 2.8 64.0 11130 0.0601
600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (IEC 60502-1)
FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. thickness of of of Resistance
section Cond. of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.8 0.3 1.8 15.0 450 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 0.3 1.8 15.5 485 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 0.3 1.8 16.0 535 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 0.3 1.8 16.5 545 7.41
4 RE 1 2.26 0.7 1.0 0.8 0.3 1.8 17.0 640 4.61
4 RM 7 2.6 0.7 1.0 0.8 0.3 1.8 18.0 660 4.61
6 RE 1 2.77 0.7 1.0 0.8 0.3 1.8 18.5 645 3.08
6 RM 7 3.1 0.7 1.0 0.8 0.3 1.8 19.0 785 3.08
10 RE 1 4.1 0.7 1.0 0.8 0.3 1.8 21.5 1040 1.83
16 CM 6 4.7 0.7 1.0 0.8 0.3 1.8 23.0 1295 1.15
25 CM 6 5.9 0.9 1.0 0.8 0.3 1.8 27.0 1795 0.727
35 CM 6 7.1 0.9 1.0 0.8 0.3 1.8 30.0 2265 0.524
50 CM 6 8.1 1.0 1.0 0.8 0.3 1.9 32.5 2830 0.387
70 CM 12 9.7 1.1 1.2 0.8 0.3 2.1 38.0 3840 0.268
95 CM 15 11.6 1.1 1.2 0.8 0.3 2.2 42.5 5015 0.193
120 CM 18 12.9 1.2 1.4 0.8 0.3 2.3 47.0 6145 0.153
150 CM 18 14.3 1.4 1.4 0.8 0.3 2.5 51.5 7450 0.124
185 CM 30 16.0 1.6 1.4 0.8 0.3 2.7 57.5 9125 0.0991
240 CM 34 18.3 1.7 1.6 0.8 0.3 2.9 64.0 11670 0.0754
300 CM 34 20.7 1.8 1.6 0.8 0.3 3.1 70.5 14270 0.0601
600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (IEC 60502-1)
FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- of number of of of Inner of Galv. thickness of of of Resistance
section Cond. of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.8 0.3 1.8 16.0 510 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 0.3 1.8 16.5 520 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 0.3 1.8 17.0 605 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 0.3 1.8 17.5 615 7.41
4 RE 1 2.26 0.7 1.0 0.8 0.3 1.8 18.5 730 4.61
4 RM 7 2.6 0.7 1.0 0.8 0.3 1.8 19.0 750 4.61
6 RE 1 2.77 0.7 1.0 0.8 0.3 1.8 20.0 875 3.08
6 RM 7 3.1 0.7 1.0 0.8 0.3 1.8 20.5 900 3.08
10 RE 1 4.1 0.7 1.0 0.8 0.3 1.8 23.0 1200 1.83
16 CM 6 4.7 0.7 1.0 0.8 0.3 1.8 25.0 1512 1.15
25 CM 6 5.9 0.9 1.0 0.8 0.3 1.8 29.0 2100 0.727
35 CM 6 7.1 0.9 1.0 0.8 0.3 1.9 32.5 2700 0.524
50 CM 6 8.1 1.0 1.2 0.8 0.3 2.0 36.0 3435 0.387
Page - 76
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, ALUMINIUM TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DATA/PVC (acc. to IEC 60502-1)
1
Constructions :
2 1 Conductor (Annealed Copper)
2 Insulation (XLPE Compound)
3
3 Inner Covering (PVC Compound)
4
4 Double Aluminium Tape armour
5 Outer sheath (PVC Compound)
5
600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (acc. to IEC 60502-1)
Constructions :
1 1 Conductor (Annealed Copper)
2 2 Insulation (XLPE Compound)
3 Filler (Polyprophylene yarn,or extruded filler
3
up to request)
4 Binding tape (Manufacturer's option)
4
5 Inner Covering (PVC Compound)
5 6 Double Galvanized Steel Tape armour
7 Outer sheath (PVC Compound)
6
Page - 77
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, ALUMINIUM TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DATA/PVC (IEC 60502-1)
SINGLE CORE
Conductor Nominal Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness Thickness Thickness diameter Weight Conductor
Cross- of number of of of Inner of of of of Resistance
section Cond. of wire Conductor Insulation covering Aluminium Sheath cable cable at 20°C
area (approx.) (approx.) tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km
Page - 78
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (IEC 60502-1)
TWO CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- of number of of of Inner thickness of of of Resistance
section Cond. of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) Steel tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.2 1.8 12.5 220
1.5 RM 7 1.6 0.7 1.0 0.2 1.8 13.0 230 12.1
2.5 RE 1 1.78 0.7 1.0 0.2 1.8 13.0 260 7.41
2.5 RM 7 2.0 0.7 1.0 0.2 1.8 13.5 270 7.41
4 RE 1 2.26 0.7 1.0 0.2 1.8 14.0 315 4.61
4 RM 7 2.6 0.7 1.0 0.2 1.8 15.0 330 4.61
6 RE 1 2.77 0.7 1.0 0.2 1.8 15.0 375 3.08
6 RM 7 3.1 0.7 1.0 0.2 1.8 16.0 390 3.08
10 RM 7 4.1 0.7 1.0 0.2 1.8 18.0 515 1.83
16 CM 6 4.7 0.7 1.0 0.2 1.8 19.0 645 1.15
25 CM 6 5.9 0.9 1.0 0.2 1.8 23.0 895 0.727
35 CM 6 7.1 0.9 1.0 0.2 1.8 24.5 1135 0.524
50 CM 6 8.1 1.0 1.0 0.2 1.8 27.0 1425 0.387
70 CM 12 9.7 1.1 1.0 0.2 1.9 30.5 1905 0.268
95 CM 15 11.6 1.1 1.2 0.2 2.0 35.0 2545 0.193
120 CM 18 12.9 1.2 1.2 0.5 2.1 39.5 3505 0.153
150 CM 18 14.3 1.4 1.4 0.5 2.3 43.5 4245 0.124
185 CM 30 16.0 1.6 1.4 0.5 2.4 48.5 5180 0.0991
240 CM 34 18.3 1.7 1.6 0.5 2.6 54.0 6530 0.0754
300 CM 34 20.7 1.8 1.6 0.5 2.7 59.5 8005 0.0601
600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (IEC 60502-1)
THREE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- of number of of of Inner thickness of of of Resistance
section Cond. of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) Steel tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.2 1.8 13.0 250
1.5 RM 7 1.6 0.7 1.0 0.2 1.8 13.5 260 12.1
2.5 RE 1 1.78 0.7 1.0 0.2 1.8 13.5 295 7.41
2.5 RM 7 2.0 0.7 1.0 0.2 1.8 14.0 310 7.41
4 RE 1 2.26 0.7 1.0 0.2 1.8 15.0 265 4.61
4 RM 7 2.6 0.7 1.0 0.2 1.8 15.5 385 4.61
6 RE 1 2.77 0.7 1.0 0.2 1.8 16.0 445 3.08
6 RM 7 3.1 0.7 1.0 0.2 1.8 16.5 465 3.08
10 RM 7 4.1 0.7 1.0 0.2 1.8 18.5 630 1.83
16 CM 6 4.7 0.7 1.0 0.2 1.8 20.0 815 1.15
25 CM 6 5.9 0.9 1.0 0.2 1.8 23.5 1150 0.727
35 CM 6 7.1 0.9 1.0 0.2 1.8 26.0 1485 0.524
50 CM 6 8.1 1.0 1.0 0.2 1.8 28.5 1885 0.387
70 CM 12 9.7 1.1 1.2 0.2 1.9 33.0 2590 0.268
95 CM 15 11.6 1.1 1.2 0.2 2.1 37.5 3460 0.193
120 CM 18 12.9 1.2 1.2 0.5 2.2 42.0 4670 0.153
150 CM 18 14.3 1.4 1.4 0.5 2.4 46.5 5710 0.124
185 CM 30 16.0 1.6 1.4 0.5 2.5 51.5 6965 0.0991
240 CM 34 18.3 1.7 1.6 0.5 2.7 58.0 8905 0.0754
300 CM 34 20.7 1.8 1.6 0.5 2.9 64.0 10920 0.0601
600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (IEC 60502-1)
FOUR CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- of number of of of Inner thickness of of of Resistance
section Cond. of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) Steel tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.2 1.8 13.5 280
1.5 RM 7 1.6 0.7 1.0 0.2 1.8 14.0 295 12.1
2.5 RE 1 1.78 0.7 1.0 0.2 1.8 14.5 345 7.41
2.5 RM 7 2.0 0.7 1.0 0.2 1.8 15.0 360 7.41
4 RE 1 2.26 0.7 1.0 0.2 1.8 16.0 430 4.61
4 RM 7 2.6 0.7 1.0 0.2 1.8 16.5 450 4.61
6 RE 1 2.77 0.7 1.0 0.2 1.8 17.0 535 3.08
6 RM 7 3.1 0.7 1.0 0.2 1.8 17.5 555 3.08
10 RM 7 4.1 0.7 1.0 0.2 1.8 20.0 765 1.83
16 CM 6 4.7 0.7 1.0 0.2 1.8 21.5 1000 1.15
25 CM 6 5.9 0.9 1.0 0.2 1.8 25.5 1435 0.727
35 CM 6 7.1 0.9 1.0 0.2 1.8 28.5 1860 0.524
50 CM 6 8.1 1.0 1.0 0.2 1.9 31.5 2385 0.387
70 CM 12 9.7 1.1 1.2 0.2 2.0 36.0 3315 0.268
95 CM 15 11.6 1.1 1.2 0.5 2.2 42.5 4875 0.193
120 CM 18 12.9 1.2 1.4 0.5 2.4 46.5 5985 0.153
150 CM 18 14.3 1.4 1.4 0.5 2.5 51.0 7275 0.124
185 CM 30 16.0 1.6 1.4 0.5 2.7 57.0 8925 0.0991
240 CM 34 18.3 1.7 1.6 0.5 2.9 64.0 11430 0.0754
300 CM 34 20.7 1.8 1.6 0.5 3.1 70.5 14015 0.0601
600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (IEC 60502-1)
FIVE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Shape Minimum Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- of number of of of Inner thickness of of of Resistance
section Cond. of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) Steel tape (approx.) (approx.)
mm² - Number mm mm mm mm mm mm kg/km /km
1.5 RE 1 1.38 0.7 1.0 0.2 1.8 14.5 320
1.5 RM 7 1.6 0.7 1.0 0.2 1.8 15.0 335 12.1
2.5 RE 1 1.78 0.7 1.0 0.2 1.8 15.5 390 7.41
2.5 RM 7 2.0 0.7 1.0 0.2 1.8 16.0 405 7.41
4 RE 1 2.26 0.7 1.0 0.2 1.8 17.0 500 4.61
4 RM 7 2.6 0.7 1.0 0.2 1.8 17.5 520 4.61
6 RE 1 2.77 0.7 1.0 0.2 1.8 18.5 620 3.08
6 RM 7 3.1 0.7 1.0 0.2 1.8 19.0 645 3.08
10 RM 7 4.1 0.7 1.0 0.2 1.8 22.0 900 1.83
16 CM 6 4.7 0.7 1.0 0.2 1.8 23.5 1200 1.15
25 CM 6 5.9 0.9 1.0 0.2 1.8 27.5 1720 0.727
35 CM 6 7.1 0.9 1.0 0.2 1.9 31.0 2255 0.524
50 CM 6 8.1 1.0 1.2 0.2 2.0 35.0 2950 0.387
Page - 82
CURRENT CARRYING CAPACITY FOR SINGLE CORE XLPE INSULATED CABLE
Current Carrying Capacity DC Alternating 2) 2) Minimum Conductor
Reactance (50 Hz) Inductance (50 Hz)
Conductor In Air ( 30°C ) In Conductor Current Insulation Short
1)
Nominal In Tray In Ducts Air Ground Resistance resistance Trefoil Flat Trefoil Flat Nominal Resistance circuit
Flat / Trefoil
Area Flat Trefoil Trefoil
at 20°C at 90°C / 50 Hz Capacitance current /
core to core core to core 1 sec
Unarmour Armour Unarmour Armour Unarmour Armour Unarmour Armour Unarmour Armour
mm² A A A A Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km µF / km M Ω. km kA
1.5 re/rm 22 21 20 23 12.1 15.4 - 0.1395 - 0.1541 - 0.4442 - 0.4905 - 0.0520 3000 0.215
2.5 re/rm 30 29 28 30 7.41 9.45 - 0.1280 - 0.1425 - 0.4074 - 0.4536 - 0.0571 2500 0.358
4 re/rm 42 40 37 39 4.61 5.88 - 0.1190 - 0.1335 - 0.3788 - 0.4250 - 0.0621 2000 0.572
6 re/rm 55 53 48 49 3.08 3.93 - 0.1109 - 0.1254 - 0.3531 - 0.3993 - 0.0665 2000 0.858
10 re/rm 77 74 66 65 1.83 2.34 - 0.1028 - 0.1173 - 0.3273 - 0.3735 - 0.0721 1500 1.430
16 cm 105 101 88 84 1.15 1.47 1.47 0.0984 0.1264 0.1129 0.1409 0.3131 0.4024 0.3593 0.4486 0.0751 1500 2.288
25 cm 141 135 117 107 0.727 0.927 0.927 0.0946 0.1190 0.1091 0.1335 0.3011 0.3789 0.3473 0.4251 0.0752 1500 3.575
35 cm 176 169 144 129 0.524 0.669 0.668 0.0900 0.1123 0.1045 0.1268 0.2865 0.3575 0.3327 0.4037 0.0789 1000 5.005
50 cm 216 207 175 153 0.387 0.494 0.494 0.0879 0.1109 0.1024 0.1254 0.2798 0.3529 0.3260 0.3991 0.0796 1000 7.150
70 cm 279 268 222 188 0.268 0.342 0.342 0.0847 0.1052 0.0992 0.1198 0.2697 0.3350 0.3159 0.3812 0.0815 900 10.01
95 cm 342 328 269 226 0.193 0.247 0.247 0.0818 0.0995 0.0963 0.1140 0.2603 0.3166 0.3065 0.3628 0.0848 800 13.59
120 cm 400 383 312 257 0.153 0.196 0.196 0.0805 0.0996 0.0951 0.1141 0.2564 0.3169 0.3026 0.3631 0.0853 800 17.16
150 cm 464 444 342 287 0.124 0.159 0.159 0.0807 0.0975 0.0952 0.1121 0.2567 0.3105 0.3029 0.3567 0.0846 800 21.45
185 cm 533 510 384 324 0.0991 0.128 0.128 0.0804 0.0958 0.0949 0.1103 0.2559 0.3048 0.3021 0.3510 0.0833 900 26.46
240 cm 634 607 450 375 0.0754 0.0983 0.0978 0.0786 0.0926 0.0931 0.1071 0.2502 0.2947 0.2964 0.3409 0.0848 800 34.32
300 cm 736 703 514 419 0.0601 0.0794 0.0788 0.0776 0.0903 0.0921 0.1048 0.2469 0.2873 0.2931 0.3335 0.0860 800 42.90
400 cm 868 823 661 495 0.0470 0.0634 0.0627 0.0769 0.0904 0.0915 0.1049 0.2449 0.2877 0.2911 0.3339 0.0865 700 57.20
1)
Note : re : Round solid conductor IEC 60228 class 1 Underground : Thermal resistivity of soil : 2.5 K.m / W Note : Reference methode of installation to be used to obtain current carrying
rm : Circular stranded conductor IEC 60228 class 2 Depth of laying : 80 cm capacity for : in cable ducting, in cables conduit, cables direct in the -
cm : Circular stranded compacted conductor IEC 60228 class 2 Base temperature : 20°C ground with / without added protection against mechanical damage
2)
The Inductance calculated for armour cable is Amuminium Wire Armour (AWA)
Page - 84
1.5 re/rm 26 23 22 19.5 27 23 25 21 12.1 15.4 0.1044 0.1117 0.3323 0.3554 0.0520 3000 0.215
2.5 re/rm 36 32 30 26 35 30 33 28 7.41 9.45 0.0959 0.1031 0.3052 0.3283 0.0571 2500 0.358
4 re/rm 49 42 40 35 46 39 43 36 4.61 5.88 0.0906 0.0979 0.2884 0.3115 0.0621 2000 0.572
6 re/rm 63 54 51 44 58 49 53 44 3.08 3.93 0.0850 0.0923 0.2706 0.2937 0.0665 2000 0.858
10 re/rm 86 75 69 60 77 65 71 58 1.83 2.33 0.0807 0.0880 0.2570 0.2801 0.0721 1500 1.430
16 cm 115 100 91 80 100 84 91 75 1.15 1.47 0.0781 0.0853 0.2485 0.2716 0.0751 1500 2.288
25 cm 149 127 119 105 129 107 116 96 0.727 0.927 0.0779 0.0852 0.2480 0.2711 0.0752 1500 3.575
35 cm 185 158 146 128 155 129 139 115 0.524 0.669 0.0753 0.0826 0.2397 0.2628 0.0789 1000 5.005
50 cm 225 192 175 154 183 153 164 135 0.387 0.494 0.0747 0.0820 0.2379 0.2610 0.0796 1000 7.150
70 cm 289 246 221 194 225 188 203 167 0.268 0.342 0.0734 0.0806 0.2335 0.2566 0.0815 900 10.01
95 cm 352 298 265 233 270 226 239 197 0.193 0.247 0.0711 0.0783 0.2262 0.2493 0.0848 800 13.59
120 cm 410 346 305 268 306 257 271 223 0.153 0.196 0.0708 0.0781 0.2254 0.2485 0.0853 800 17.16
150 cm 473 399 334 300 343 287 306 251 0.124 0.160 0.0712 0.0785 0.2267 0.2498 0.0846 800 21.45
185 cm 542 456 384 340 387 324 343 281 0.0991 0.128 0.0720 0.0793 0.2292 0.2523 0.0833 900 26.46
240 cm 641 538 459 398 448 375 395 324 0.0754 0.0987 0.0711 0.0784 0.2264 0.2495 0.0848 800 34.32
300 cm 741 621 532 455 502 419 446 365 0.0601 0.0798 0.0704 0.0776 0.2240 0.2471 0.0860 800 42.90
400 cm 892 745 628 552 593 495 521 426 0.0470 0.0640 0.0701 0.0773 0.2231 0.2462 0.0865 700 57.20
Note : re : Round solid conductor IEC 60228 class 1 Underground : Thermal resistivity of soil : 2.5 K.m / W 4* : 3 Phasa + Netral / Ground
rm : Circular stranded conductor IEC 60228 class 2 Depth of laying : 80 cm
cm : Circular stranded compacted conductor IEC 60228 class 2 Base temperature : 20°C
CURRENT CARRYING CAPACITY FOR SINGLE CORE PVC INSULATED CABLE
mm² A A A A Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km Ω / km µF / km M Ω. km kA
1.5 re/rm 18 17.5 15.5 19 12.1 14.5 - 0.1418 - 0.1563 - 0.4513 - 0.4975 - 0.1391 50 0.174
2.5 re/rm 25 24 21 24 7.41 8.87 - 0.1300 - 0.1445 - 0.4139 - 0.4601 - 0.1531 50 0.290
4 re/rm 34 33 28 33 4.61 5.52 - 0.1245 - 0.1390 - 0.3962 - 0.4424 - 0.1553 50 0.464
6 re/rm 45 43 36 41 3.08 3.69 - 0.1160 - 0.1305 - 0.3693 - 0.4155 - 0.1671 50 0.696
10 re/rm 63 60 50 54 1.83 2.19 - 0.1073 - 0.1218 - 0.3416 - 0.3878 - 0.1827 50 1.160
16 rm 85 82 68 70 1.15 1.376 1.376 0.0997 0.1253 0.1142 0.1399 0.3172 0.3990 0.3634 0.4452 0.1966 40 1.856
25 rm 114 110 89 92 0.727 0.870 0.870 0.0956 0.1181 0.1101 0.1326 0.3044 0.3759 0.3506 0.4221 0.2001 40 2.900
35 rm 143 137 110 110 0.524 0.627 0.627 0.0914 0.1145 0.1059 0.1290 0.2908 0.3643 0.3370 0.4105 0.2100 40 4.060
50 rm 174 167 134 130 0.387 0.463 0.463 0.0886 0.1090 0.1031 0.1235 0.2821 0.3470 0.3283 0.3932 0.2127 30 5.800
70 rm 225 216 171 162 0.268 0.321 0.321 0.0848 0.1034 0.0993 0.1179 0.2700 0.3291 0.3162 0.3753 0.2223 30 8.120
95 rm 275 264 207 193 0.193 0.232 0.232 0.0844 0.1028 0.0989 0.1173 0.2687 0.3273 0.3149 0.3735 0.2205 30 11.02
120 rm 321 308 239 220 0.153 0.184 0.184 0.0820 0.0991 0.0965 0.1136 0.2609 0.3155 0.3072 0.3617 0.2270 30 13.92
150 rm 372 356 262 246 0.124 0.150 0.149 0.0817 0.0968 0.0962 0.1114 0.2600 0.3083 0.3062 0.3545 0.2274 20 17.40
185 rm 427 409 296 278 0.0991 0.120 0.120 0.0807 0.0947 0.0952 0.1092 0.2568 0.3014 0.3030 0.3476 0.2279 20 21.46
240 rm 507 485 346 320 0.0754 0.0925 0.0920 0.0796 0.0917 0.0941 0.1062 0.2533 0.2920 0.2995 0.3382 0.2308 20 27.84
0.0000
300 rm 587 561 394 359 0.0601 0.0746 0.0742 0.0823 0.0915 0.0968 0.1060 0.2618 0.2913 0.3080 0.3375 0.2323 20 34.80
400 rm 689 656 510 428 0.0470 0.0598 0.0591 0.0784 0.0905 0.0929 0.1050 0.2495 0.2880 0.2957 0.3342 0.2387 20 46.40
500 rm 789 749 587 485 0.0366 0.0483 0.0475 0.0777 0.0887 0.0922 0.1032 0.2472 0.2823 0.2934 0.3285 0.2355 20 58.00
1)
Note : re : Round solid conductor IEC 60228 class 1 Underground : Thermal resistivity of soil : 2.5 K.m / W Note : Reference methode of installation to be used to obtain current carrying
rm : Circular stranded conductor IEC 60228 class 2
Page - 85
Depth of laying : 80 cm capacity for : in cable ducting, in cables conduit, cables direct in the -
Base temperature : 20°C ground with / without added protection against mechanical damage
2)
The Inductance calculated for armour cable is Amuminium Wire Armour (AWA)
Page - 86
1.5 re/rm 22 18.5 16.5 15 22 19 22 18 12.1 14.5 0.1082 0.1155 0.3444 0.3676 0.1391 50 0.174
2.5 re/rm 30 25 23 20 28 24 29 24 7.41 8.87 0.0993 0.1065 0.3160 0.3391 0.1531 50 0.290
4 re/rm 40 34 30 27 38 33 37 30 4.61 5.52 0.0990 0.1062 0.3151 0.3382 0.1553 50 0.464
6 re/rm 51 43 38 34 48 41 46 38 3.08 3.69 0.0926 0.0998 0.2946 0.3177 0.1671 50 0.696
50 rm/sm 180 153 133 118 156 130 140 116 0.387 0.464 0.0773 0.0846 0.2462 0.2693 0.2127 30 5.800
70 rm/sm 232 196 168 149 192 162 173 143 0.268 0.321 0.0748 0.0821 0.2382 0.2613 0.2223 30 8.120
95 rm/sm 282 238 201 179 230 193 204 169 0.193 0.232 0.0751 0.0823 0.2389 0.2620 0.2205 30 11.020
120 rm/sm 328 276 232 206 261 220 231 192 0.153 0.184 0.0734 0.0807 0.2337 0.2568 0.2270 30 13.920
150 rm/sm 379 319 258 225 293 246 261 217 0.124 0.150 0.0734 0.0806 0.2336 0.2567 0.2274 20 17.400
185 rm/sm 434 364 294 255 331 278 292 243 0.0991 0.121 0.0731 0.0804 0.2328 0.2559 0.2279 20 21.460
240 rm/sm 514 430 344 297 382 320 336 280 0.0754 0.0928 0.0725 0.0797 0.2307 0.2538 0.2308 20 27.840
300 rm/sm 593 497 394 339 427 359 379 316 0.0601 0.0752 0.0723 0.0795 0.2301 0.2532 0.2323 20 34.80
Note : re : Round solid conductor IEC 60228 class 1 Underground : Thermal resistivity of soil : 2.5 K.m / W 4* : 3 Phasa + Netral / Ground
rm : Circular stranded conductor IEC 60228 class 2 Depth of laying : 80 cm
sm : Sector shape stranded conductor IEC 60228 class 2 Base temperature : 20°C
Correction factor of Curent carrying capacity
PVC Insulation 1.22 1.17 1.12 1.06 1.00 0.94 0.87 0.79 0.71 0.61 0.50 - - -
XLPE Insulation 1.15 1.12 1.08 1.04 1.00 0.96 0.91 0.87 0.82 0.76 0.71 0.65 0.58 0.41
PVC Insulation 1.10 1.05 1.00 0.95 0.89 0.84 0.77 0.71 0.63 0.55 0.45 - - -
XLPE Insulation 1.07 1.04 1.00 0.96 0.93 0.89 0.85 0.80 0.76 0.71 0.65 0.60 0.53 0.38
Corection factor for cables in buried ducts 1.28 1.20 1.18 1.10 1.05 1 0.96
Corection factor for direct buried cables 1.88 1.62 1.50 1.28 1.12 1 0.90
5 0.70 0.75
7 0.60 0.65
10 0.50 0.55
14 0.45 0.50
24 0.35 0.40
40 0.30 0.35
61 0.25 0.30
Page - 87
Section 4 - General Information
Touching
Touching
1 0.97 0.84 0.78 0.75 0.71 0.68
Unperforated 2 0.97 0.83 0.76 0.72 0.68 0.63
Cable tray 3 0.97 0.82 0.75 0.71 0.66 0.61
systems 6 0.97 0.81 0.73 0.69 0.63 0.58
Touching
1 1.00 0.87 0.82 0.80 0.79 0.78
2 1.00 0.86 0.80 0.78 0.76 0.73
3 1.00 0.85 0.79 0.76 0.73 0.70
Cable ladder 6 1.00 0.84 0.77 0.73 0.68 0.64
systems
Spaced
cleats, etc 1 1.00 1.00 1.00 1.00 1.00 -
( note 3 ) 2 1.00 0.99 0.98 0.97 0.96 -
3 1.00 0.98 0.97 0.96 0.93 -
NOTE 1 Values given are averages for the cable types and range of conductor sizes considered. The spread of values is generally less than 5 %.
NOTE 2 Factor apply to single layer groups of cables as shown above and do not apply when cables are installed in more than one layer touching each
other. Values for such installations may be significantly lower and has to be determined by an appropriate method
NOTE 3 Values are given for vertical spacing between cable trays of 300 mm and at least 20 mm between cable trays and wall. For closer spacing the
factors should be reduced.
NOTE 4 Values are given for horizontal spacing between cable trays of 225 mm with cable trays mounted back to back. For closer spacing the factor
should be reduced.
Page - 88
Section 4 - General Information
Touching
Vertically perforated 1 0.96 0.86 - Three cables in
cable tray systems 2 0.95 0.84 - vertcal formation
( note 4 )
Touching
Spaced
NOTE 1 Value given are averages for the cable types and range of conductor sizes considered. The spread of values is generally less than ± 5 %.
NOTE 2 Factor aer given for single layers of cables ( or trefoil groups ) as shown in the table and do not apply when cables are installed in more than one
layer touching each other. Values for such installations may be significantly lower and should be determined by an appropriate method.
NOTE 3 Values are given for vertical spacing between cable trays of 300 mm and at least 20 mm between cable trays and wall. For closer spacing the
factor should be reduced.
NOTE 4 Values are given for horizontal spacings between cable trays of 225 mm with cable trays mounted back to back. For closer spacing the factors
should be reduced
NOTE 5 For circuits having more than one cable in parallel per phase, each three phase set of conductors should be considered as a circuit for the
purpose of this table
NOTE 6 If a circuit consists of m parallel conductors per phase, then for determining the erduction factor this circuit should be considered as m circuits
Page - 89
Section 4 - General Information
The cable pulling tension (T2) during installation can be calculated with below formula.
Page - 90
Section 4 - Contents & Information
IEC 60332-3
Part 3 - Test on bunched wire or cables
This test was developed to obtain a method to determine the flame propagation characteristics of bunched cables.
It can not be assumed that because a single vertical cable complies with the requirements of IEC 60332 part 1 it will also behave in 1
a similar manner when bunched with others cables.
The propagation of a flame along a bunch of cables depends on a number of features, such as :
The volume of combustible material exposed to the fire
The geometrical configuration of the cables
The temperature at which it is possible to ignite any gases emitted from the cables
The quantity of combustible gas released from the cables
The volume of air passing through the cable installation
The test consists of a vertical chamber, 1 x 2 x 4 m. Openings air inlet and outlet are provided in the base and the top of the test
chamber for a controlled air flow rate during the test. The cable samples to be tested are 3.5 m long and fixed to a steel ladder mounted
150 mm from the rear wall vertically with the test chamber. The number of lengths of cables in the test depends on the test categoty
based on the volume of combustible material.
Test Category Volume of combustible material Time of flame application
A 7 litres / m 40 Minutes
B 3.5 litres / m 40 Minutes
C 1.5 litres / m 20 Minutes
A ribbon gas burner of a set size and heat flow rate, operating at 800°C is mounted horizontally in front of the cable samples at a set
distance and height. The test is passed if the charred or affected portion of the samples have not reached a height exceeding 2.5 m
above the bottom edge of the burner.
Page - 91