Application Mode of operation
Firing systems for steam boilers which The equipment operates using a so-
are operated as per TRD 604, Sheet 1 called holding circuit which must be
or 2 may only be started up in the unlocked manually. It also causes the
presence of a boilerman as per Article requested fast switch-off (< 1 s) when
Printed in Germany • Rösler Druck • Edition 08.00 • Nr. 225 899

4.4. This is normally achieved by a the safety chain and the fault lock are
"holding circuit" after the boilerman interrupted.
has pressed the Start pushbutton. A A capacitor relay with switch-off delay
further requirement is that switch-offs is integrated in the NAE and bridges
of the safety chain provided as pro- bypasses of a period of max. 30 s. It
tection against overheating and lack detects by means of an additional
of water must cause a fault lock which power voltage relay whether the event
can only be unlocked by pressing the is a power voltage interruption or an
Start pushbutton. interruption of the safety chain.
These power holding circuits have the
disadvantage that even short power If the holding circuit is switched off by
failures (< 30 s) cause unnecessary a power voltage interruption of less
fault switch-offs. More than 90% of all than 30 s, it is restarted after the power
power failures are short power inter- voltage is restored and an unneces-
1…4
ruptions. sary fault switch-off is avoided.
Safety systems Installation and mounting Electrical connection
The complete layout is designed in Any installation position of the NAE Perform wiring as per the locally pre-
such a way that failures are detected equipment is possible. vailing regulations and the wiring dia-
automatically and prevent start-up. A Before mounting, remove the top part gram. The wiring diagram is affixed to
fuse which is not accessible from the and attach the plug-in base using two the underside of the top part.
exterior is installed as protection screws. The maximum back-up fuse may be 6
against relay contacts welding. It can For the connection, 7 rubber cable A slow-blow or 10 A quick-acting.
only be exchanged after a safety check glands and 5 breakable PG* 9 open-
at the manufacturer. ings are provided on the plug-in base
(* = heavy-gauged conduit thread). Terminal wiring diagram
A blocking or bypassing of the Start Function of terminals 13 - 14 - 15
pushbutton does not impair the safety These terminals lead to a relay with
function of the equipment. switch-on delay which switches over
approx. 10 s after the power voltage is
applied.
This function is for unlocking a group
alarm after a power interruption.

Terminal wiring diagram


n !
i o
at
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16rm
n fo e!
r i or
o u NCm
Fault. STB WM
y Switch-over
NO COM
n y
r a delay
fo lecontact
ly ab
> 10 s

O n i l
- a
L N Safety chain external Output N
230 V
n
Start
a v max. 2 A

io ot
50 HZ
t
Back-up fuse max. 6 A slow-blow or 10 A quick-acting Anschlußplan Stecksockel NAE

n ta is n
e t
u m u c
o c od
d Pr
d
Ol

2…4
Function and program sequence

Normal start followed b voltage failure <15s


Supply voltage (T 1, 16)
Wiping contact (T 13, 14, 15)
Safety chain (T 5, 7)
Start (T 8, 9)
Output (T 11)
Fault (T 3)

>10s >60s <15s >10s

Normal start followed by voltage failure >30s


Supply voltage (T 1, 16)
Wiping contact (Kl. 13, 14, 15)
Safety chain (T 5, 7)
Start (T 8, 9)

!
Output (T 11)

n
Fault (T 3)

i o
at
>10s >30s >10s

r m
fo e!
Interruption of safety chain without voltage failure

n
i or Supply voltage (T 1, 16)

r
u m
Wiping contact (T 13, 14, 15)

o
Safety chain (T 5, 7)

r y ny Start (T 8, 9)

fo le a
Output (T 11)
Fault (T 3)

n ly ab
l
<1s

- O a i
n a v
Interruption of safety chain shortly before voltage failure

t io ot Supply voltage (T 1, 16)

ta is n
Wiping contact (T 13, 14, 15)

n
e t
Safety chain (T 5, 7)
Start (T 8, 9)

u m u c Output (T 11)

c od
Fault (T 3)

o
d Pr <1s <15s >10s

ld
O Interruption of safety chain shortly after voltage failure

Supply voltage (T 1, 16)


Wiping contact (T 13, 14, 15)
Safety chain (T 5, 7)
Start (T 8, 9)
Output (T 11)
Fault (T 3)

<15s >10s

3…4
Power failure detector
NAE

Dimensions [mm] Specifications

Nominal voltage
n
230 VAC + 10/-15%
!
ti o
a
Frequency 50/60 Hz

r m5 A
132

Power consumption approx.

n f2oA e!
Switching capacity
r i or
o u m
y 10 A quickacting
Back-up fuse max. 6 A slow-blow or
y n
orfacilityewitha 250 V DC, 1 A
150 75

f l
y pushbutton
Fault unlock
l a b
n ilprotection
100
ø 4,5 external ø 4,5

- O
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

a
v temperature
Degree of IP 40

o n t a
i
at no Weight
NAmbient -15° to +60°C
18

n t s
e ti
xx
approx. 0.5 kg
25 25

m uc
PG 9 ø 15,8

u
50 50

c od
75

o
d Pr
Order datald
O Type Order-No.

Power failure detector NAE 224 931

We reserve the right to make any changes in the interest of technical progress