Gefran 400 Temperature

Controller: Quick Start Guide

Tel: +27 11 966 9800 (JHB)


+27 21 762 8995 (CT)
sales@unitemp.com
www.unitemp.com/contact
Quick Start Guide
400-D-R-x Programmable PID Controller Heat & Alarm
GETTING STARTED 2 Program Your Gefran Controller 3 Connect Your Controller
• Unpack Contents
• Verify model numberand application • Press and hold F until InP appears Input Sensor 19 Additional wiring
• Power Controller
• Press F once, Ctr appears — ENTER 6
Sensor Type Sensor Type configurations
• Program for yourapplication 0 TC J °C 30 PT100 °C are available
• Press F once, tYP appears — ENTER the Input Sensor 1 TC J °F 31 PT100 °F
20 in the User’s
2 TC K °C 32 JPT100 °C
Note number from the list ALARM Manual and
3 TC K °F 33 JPT100 °F
Change all menu parameters by General Setup
• Press F repeatedly until Lo.S* appears — ENTER the
4 TC R °C 34 PTC °C
5 TC R °F 35 PTC °F - 21 Guide
using the front panel buttons
minimum Input Scale limit 6 TC S °C 36 NTC °C
7 TC S °F 37 NTC °F
• Press F once, H i.S* appears — ENTER the maximum Input 8 TC T °C 44 4...20 mA
9 TC T °F 46 0...10 V
+ 22
Scale limit HEATER
• Press F repeatedly until Lo.L* appears — ENTER the minimum Alarm Scale limit POWER CONTROL
1 What’s Included
• Press F once, H i.L* appears — ENTER the maximum Alarm Scale limit 23 2 -
• Press and hold F until CFG appears
24 1 +
• Press and hold F until you return to the main process display. This is the display after PAS
and will be indicated by the Process Variable if an input sensor is connected, or Sbr, Err, POWER THERMOCOUPLE
Lo, H i, if no input is connected.
If needed, automatic tuning (Self-Tune) can be enabled
• Press F once from the main display,_SP, appears to adjust the control setpoint (SV). with the following steps
• Press F twice from the main display, AL.1 appears to adjust the Alarm 1 setpoint. With the machine at ambient temperature and
the control setpoint (SV) set..
• Press F twice to return to the main display. • Press and hold F until CFG appears
• Press the button to switch between automatic and manual control modes from the • Press F once, S.Tu appears — ENTER 2
main display. The deviation LEDs ( ) will flash while in manual mode. • Press F once
• Cycle power to the controller
• Cycle power to the controllerThe right-most
decimal point will light during the tuning process
Self-Tune will automatically save new PID
• 48x48 DIN 400-D-R-x values once complete
Gefran Controller This Quick Start Guide provides basic information on setting
• Mounting Bracket up the Gefran 400 controller for the application referenced
• Panel Sealing Gasket above. Additional software and hardware configuration
• Screw Terminal Cover information can be found in the User’s Manual included
• Multi-Language Manual * Parameter may be left at default value for input types 0...37 with this controller or online at www.gefran.com

GEFRAN SpA
Via Sebina, 74 - 25050 PROVAGLIO D’ISEO (BS) ITALY
Quick Start Guide
401-R-R-R-x Programmable PID Controller Heat - Cool - Alarm
GETTING STARTED 2 Program Your Gefran Controller 3 Connect Your Controller
• Unpack Contents
• Verify model numberand application • Press and hold F until InP appears Input Sensor 19 Additional wiring
• Power Controller configurations are
• Press F once, Ctr appears — ENTER 8
Sensor Type Sensor Type
• Program for yourapplication 0 TC J °C 30 PT100 °C available in the User’s
• Press F once, tYP appears — ENTER the Input Sensor 1 TC J °F 31 PT100 °F
20 Manual and General
Note
2 TC K °C 32 JPT100 °C
Setup Guide
number from the list 3 TC K °F 33 JPT100 °F COOLING
Change all menu parameters by • Press F repeatedly until Lo.S* appears — ENTER the
4 TC R °C 34 PTC °C

using the front panel buttons


5 TC R °F 35 PTC °F 21 6
minimum Input Scale limit 6 TC S °C 36 NTC °C
7 TC S °F 37 NTC °F
• Press F once, H i.S* appears — ENTER the maximum Input 8 TC T °C 44 4...20 mA
9 TC T °F 46 0...10 V 22 5
Scale limit
HEATER ALARM
• Press F repeatedly until Lo.L* appears — ENTER the minimum Alarm Scale limit
1 What’s Included
• Press F once, H i.L* appears — ENTER the maximum Alarm Scale limit 23 2 -
• Press and hold F until Out appears
24 1 +
• Press F repeatedly until, r.o.2 appears — ENTER1
• Press F once, r.o.3 appears — ENTER 2 POWER THERMOCOUPLE

• Press and hold F until CFG appears If needed, automatic tuning (Self-Tune) can be enabled
• Press and hold F until you return to the main process display. This is the display after PAS with the following steps
and will be indicated by the Process Variable if an input sensor is connected, or Sbr, Err, With the machine at ambient temperature and
Lo, H i, if no input is connected. the control setpoint (SV) set..
• Press F once from the main display,_SP, appears to adjust the control setpoint (SV). • Press and hold F until CFG appears
• Press F once, S.Tu appears — ENTER 2
• Press F twice from the main display, AL.1 appears to adjust the Alarm 1 setpoint. • Press F once
• Press F twice to return to the main display.
• Cycle power to the controller
• Cycle power to the controllerThe right-most
• Press the button to switch between automatic and manual control modes from the decimal point will light during the tuning process
main display. The deviation LEDs ( ) will flash while in manual mode. Self-Tune will automatically save new PID
• 48x48 DIN 401-R-R-R-x values once complete
Gefran Controller This Quick Start Guide provides basic information on setting
• Mounting Bracket up the Gefran 400 controller for the application referenced
• Panel Sealing Gasket above. Additional software and hardware configuration
• Screw Terminal Cover information can be found in the User’s Manual included
• Multi-Language Manual * Parameter may be left at default value for input types 0...37 with this controller or online at www.gefran.com

GEFRAN SpA
Via Sebina, 74 - 25050 PROVAGLIO D’ISEO (BS) ITALY
Quick Start Guide
401-D-R-R-x Programmable PID Controller Heat - Cool - Alarm
GETTING STARTED 2 Program Your Gefran Controller 3 Connect Your Controller
• Unpack Contents
• Verify model numberand application • Press and hold F until InP appears Input Sensor 19 Additionalwiring
Additional wiring
• Power Controller configurationsare
configurations are
• Press F once, Ctr appears — ENTER 8
Sensor Type Sensor Type
• Program for yourapplication 0 TC J °C 30 PT100 °C availableininthe
available theUser’s
User’s
• Press F once, tYP appears — ENTER the Input Sensor 1 TC J °F 31 PT100 °F
20 Manualand
Manual andGeneral
General
Note
2 TC K °C 32 JPT100 °C
SetupGuide
Setup Guide
number from the list 3 TC K °F 33 JPT100 °F COOLING
Change all menu parameters by • Press F repeatedly until Lo.S* appears — ENTER the
4 TC R °C 34 PTC °C
5 TC R °F 35 PTC °F - 21 6
using the front panel buttons
minimum Input Scale limit 6 TC S °C 36 NTC °C
7 TC S °F 37 NTC °F
• Press F once, H i.S* appears — ENTER the maximum Input 8 TC T °C 44 4...20 mA
9 TC T °F 46 0...10 V
+ 22 5
Scale limit HEATER
POWER CONTROL ALARM
• Press F repeatedly until Lo.L* appears — ENTER the minimum Alarm Scale limit
1 What’s Included
• Press F once, H i.L* appears — ENTER the maximum Alarm Scale limit 23 2 -
• Press and hold F until Out appears
24 1 +
• Press F repeatedly until, r.o.2 appears — ENTER1
• Press F once, r.o.3 appears — ENTER 2 POWER THERMOCOUPLE

• Press and hold F until CFG appears If needed, automatic tuning (Self-Tune) can be enabled
• Press and hold F until you return to the main process display. This is the display after PAS with the following steps
and will be indicated by the Process Variable if an input sensor is connected, or Sbr, Err, With the machine at ambient temperature and
Lo, H i, if no input is connected. the control setpoint (SV) set..
• Press F once from the main display,_SP, appears to adjust the control setpoint (SV). • Press and hold F until CFG appears
• Press F once, S.Tu appears — ENTER 2
• Press F twice from the main display, AL.1 appears to adjust the Alarm 1 setpoint. • Press F once
• Press F twice to return to the main display.
• Cycle power to the controller
• Cycle power to the controllerThe right-most
• Press the button to switch between automatic and manual control modes from the decimal point will light during the tuning process
main display. The deviation LEDs ( ) will flash while in manual mode. Self-Tune will automatically save new PID
• 48x48 DIN 401-D-R-R-x values once complete
Gefran Controller This Quick Start Guide provides basic information on setting
• Mounting Bracket up the Gefran 400 controller for the application referenced
• Panel Sealing Gasket above. Additional software and hardware configuration
• Screw Terminal Cover information can be found in the User’s Manual included
• Multi-Language Manual * Parameter may be left at default value for input types 0...37 with this controller or online at www.gefran.com

GEFRAN SpA
Via Sebina, 74 - 25050 PROVAGLIO D’ISEO (BS) ITALY
Quick Start Guide
400-R-R-x Programmable PID Controller Heat - Cool
GETTING STARTED 2 Program Your Gefran Controller 3 Connect Your Controller
• Unpack Contents
• Verify model numberand application • Press and hold F until InP appears Input Sensor 19 Additional wiring
• Power Controller
• Press F once, Ctr appears — ENTER 8
Sensor Type Sensor Type configurations
• Program for yourapplication 0 TC J °C 30 PT100 °C are available
• Press F once, tYP appears — ENTER the Input Sensor 1 TC J °F 31 PT100 °F
20 in the User’s
2 TC K °C 32 JPT100 °C
Note number from the list COOLING Manual and
3 TC K °F 33 JPT100 °F
Change all menu parameters by General Setup
• Press F repeatedly until Lo.S* appears — ENTER the
4 TC R °C 34 PTC °C
5 TC R °F 35 PTC °F 21 Guide
using the front panel buttons
minimum Input Scale limit 6 TC S °C 36 NTC °C
7 TC S °F 37 NTC °F
• Press F once, H i.S* appears — ENTER the maximum Input 8 TC T °C 44 4...20 mA
9 TC T °F 46 0...10 V
22
Scale limit
HEATER
• Press F repeatedly until Lo.L* appears — ENTER the minimum Alarm Scale limit
1 What’s Included
• Press F once, H i.L* appears — ENTER the maximum Alarm Scale limit 23 2 -
• Press and hold F until Out appears
24 1 +
• Press F once, AL.n appears — ENTER 0
POWER THERMOCOUPLE
• Press F twice, r.o.2 appears — ENTER 1
• Press and hold F until you return to the main process display. This is the display after PAS If needed, automatic tuning (Self-Tune) can be enabled
and will be indicated by the Process Variable if an input sensor is connected, or Sbr, Err, with the following steps
Lo, H i, if no input is connected. With the machine at ambient temperature and
• Press F once from the main display,_SP, appears to adjust the control setpoint (SV). the control setpoint (SV) set..
• Press and hold F until CFG appears
• Press F twice to return to the main display.
• Press F once, S.Tu appears — ENTER 2
• Press the button to switch between automatic and manual control modes from the • Press F once
main display. The deviation LEDs ( ) will flash while in manual mode. • Cycle power to the controller
• Cycle power to the controllerThe right-most
decimal point will light during the tuning process
Self-Tune will automatically save new PID
• 48x48 DIN 400-R-R-x values once complete
Gefran Controller This Quick Start Guide provides basic information on setting
• Mounting Bracket up the Gefran 400 controller for the application referenced
• Panel Sealing Gasket above. Additional software and hardware configuration
• Screw Terminal Cover information can be found in the User’s Manual included
• Multi-Language Manual * Parameter may be left at default value for input types 0...37 with this controller or online at www.gefran.com

GEFRAN SpA
Via Sebina, 74 - 25050 PROVAGLIO D’ISEO (BS) ITALY
Quick Start Guide
400-R-R-x Programmable PID Controller Heat & Alarm
GETTING STARTED 2 Program Your Gefran Controller 3 Connect Your Controller
• Unpack Contents
• Verify model numberand application • Press and hold F until InP appears Input Sensor 19 Additional wiring
• Power Controller
• Press F once, Ctr appears — ENTER 6
Sensor Type Sensor Type configurations
• Program for yourapplication 0 TC J °C 30 PT100 °C are available
• Press F once, tYP appears — ENTER the Input Sensor 1 TC J °F 31 PT100 °F
20 in the User’s
2 TC K °C 32 JPT100 °C
Note number from the list ALARM Manual and
3 TC K °F 33 JPT100 °F
Change all menu parameters by General Setup
• Press F repeatedly until Lo.S* appears — ENTER the
4 TC R °C 34 PTC °C
5 TC R °F 35 PTC °F 21 Guide
using the front panel buttons
minimum Input Scale limit 6 TC S °C 36 NTC °C
7 TC S °F 37 NTC °F
• Press F once, H i.S* appears — ENTER the maximum Input 8 TC T °C 44 4...20 mA
9 TC T °F 46 0...10 V
22
Scale limit
HEATER
• Press F repeatedly until Lo.L* appears — ENTER the minimum Alarm Scale limit
1 What’s Included
• Press F once, H i.L* appears — ENTER the maximum Alarm Scale limit 23 2 -
• Press and hold F until CFG appears
24 1 +
• Press and hold F until you return to the main process display. This is the display after PAS
and will be indicated by the Process Variable if an input sensor is connected, or Sbr, Err, POWER THERMOCOUPLE
Lo, H i, if no input is connected.
If needed, automatic tuning (Self-Tune) can be enabled
• Press F once from the main display,_SP, appears to adjust the control setpoint (SV). with the following steps
• Press F twice from the main display, AL.1 appears to adjust the Alarm 1 setpoint. With the machine at ambient temperature and
the control setpoint (SV) set..
• Press F twice to return to the main display. • Press and hold F until CFG appears
• Press the button to switch between automatic and manual control modes from the • Press F once, S.Tu appears — ENTER 2
main display. The deviation LEDs ( ) will flash while in manual mode. • Press F once
• Cycle power to the controller
• Cycle power to the controllerThe right-most
decimal point will light during the tuning process
Self-Tune will automatically save new PID
• 48x48 DIN 400-R-R-x values once complete
Gefran Controller This Quick Start Guide provides basic information on setting
• Mounting Bracket up the Gefran 400 controller for the application referenced
• Panel Sealing Gasket above. Additional software and hardware configuration
• Screw Terminal Cover information can be found in the User’s Manual included
• Multi-Language Manual * Parameter may be left at default value for input types 0...37 with this controller or online at www.gefran.com

GEFRAN SpA
Via Sebina, 74 - 25050 PROVAGLIO D’ISEO (BS) ITALY
Quick Start Guide
400-D-R-x Programmable PID Controller Heat - Cool
GETTING STARTED 2 Program Your Gefran Controller 3 Connect Your Controller
• Unpack Contents
• Verify model numberand application • Press and hold F until InP appears Input Sensor 19 Additional wiring
• Power Controller
• Press F once, Ctr appears — ENTER 8
Sensor Type Sensor Type configurations
• Program for yourapplication 0 TC J °C 30 PT100 °C are available
• Press F once, tYP appears — ENTER the Input Sensor 1 TC J °F 31 PT100 °F
20 in the User’s
2 TC K °C 32 JPT100 °C
Note number from the list Manual and
3 TC K °F 33 JPT100 °F COOLING
Change all menu parameters by General Setup
• Press F repeatedly until Lo.S* appears — ENTER the
4 TC R °C 34 PTC °C
5 TC R °F 35 PTC °F - 21 Guide
using the front panel buttons
minimum Input Scale limit 6 TC S °C 36 NTC °C
7 TC S °F 37 NTC °F
• Press F once, H i.S* appears — ENTER the maximum Input 8 TC T °C 44 4...20 mA
9 TC T °F 46 0...10 V
+ 22
Scale limit HEATER
POWER CONTROL
• Press F repeatedly until Lo.L* appears — ENTER the minimum Alarm Scale limit
1 What’s Included
• Press F once, H i.L* appears — ENTER the maximum Alarm Scale limit 23 2 -
• Press and hold F until Out appears
24 1 +
• Press F once, AL.n appears — ENTER 0
• Press F twice, r.o.2 appears — ENTER1 POWER THERMOCOUPLE

• Press and hold F until you return to the main process display. This is the display after PAS If needed, automatic tuning (Self-Tune) can be enabled
and will be indicated by the Process Variable if an input sensor is connected, or Sbr, Err, with the following steps
Lo, H i, if no input is connected. With the machine at ambient temperature and
• Press F once from the main display,_SP, appears to adjust the control setpoint (SV). the control setpoint (SV) set..
• Press and hold F until CFG appears
• Press F twice to return to the main display.
• Press F once, S.Tu appears — ENTER 2
• Press the button to switch between automatic and manual control modes from the • Press F once
main display. The deviation LEDs ( ) will flash while in manual mode. • Cycle power to the controller
• Cycle power to the controllerThe right-most
decimal point will light during the tuning process
Self-Tune will automatically save new PID
• 48x48 DIN 400-D-R-x values once complete
Gefran Controller This Quick Start Guide provides basic information on setting
• Mounting Bracket up the Gefran 400 controller for the application referenced
• Panel Sealing Gasket above. Additional software and hardware configuration
• Screw Terminal Cover information can be found in the User’s Manual included
• Multi-Language Manual * Parameter may be left at default value for input types 0...37 with this controller or online at www.gefran.com