Vous êtes sur la page 1sur 55

Electricity and New Energy

Directional Protection
&RXUVHZDUH6DPSOH
52174-)0
Order no.: 52174-10
First Edition
Revision level: 11/2016

By the staff of Festo Didactic

© Festo Didactic Ltée/Ltd, Quebec, Canada 2016


Internet: www.festo-didactic.com
e-mail: did@de.festo.com

Printed in Canada
All rights reserved
ISBN 978-2-89747-560-4 (Printed version)
ISBN 978-2-89747-562-8 (CD-ROM)
Legal Deposit – Bibliothèque et Archives nationales du Québec, 2016
Legal Deposit – Library and Archives Canada, 2016

The purchaser shall receive a single right of use which is non-exclusive, non-time-limited and limited
geographically to use at the purchaser's site/location as follows.

The purchaser shall be entitled to use the work to train his/her staff at the purchaser’s site/location and
shall also be entitled to use parts of the copyright material as the basis for the production of his/her own
training documentation for the training of his/her staff at the purchaser’s site/location with
acknowledgement of source and to make copies for this purpose. In the case of schools/technical
colleges, training centers, and universities, the right of use shall also include use by school and college
students and trainees at the purchaser’s site/location for teaching purposes.

The right of use shall in all cases exclude the right to publish the copyright material or to make this
available for use on intranet, Internet and LMS platforms and databases such as Moodle, which allow
access by a wide variety of users, including those outside of the purchaser’s site/location.

Entitlement to other rights relating to reproductions, copies, adaptations, translations, microfilming and
transfer to and storage and processing in electronic systems, no matter whether in whole or in part, shall
require the prior consent of Festo Didactic.

Information in this document is subject to change without notice and does not represent a commitment on
the part of Festo Didactic. The Festo materials described in this document are furnished under a license
agreement or a nondisclosure agreement.

Festo Didactic recognizes product names as trademarks or registered trademarks of their respective
holders.

All other trademarks are the property of their respective owners. Other trademarks and trade names may
be used in this document to refer to either the entity claiming the marks and names or their products.
Festo Didactic disclaims any proprietary interest in trademarks and trade names other than its own.
Safety and Common Symbols
The following safety and common symbols may be used in this manual and on
the equipment:

Symbol Description

DANGER indicates a hazard with a high level of risk which, if not


avoided, will result in death or serious injury.

WARNING indicates a hazard with a medium level of risk which,


if not avoided, could result in death or serious injury.

CAUTION indicates a hazard with a low level of risk which, if not


avoided, could result in minor or moderate injury.

CAUTION used without the Caution, risk of danger sign ,


indicates a hazard with a potentially hazardous situation which,
if not avoided, may result in property damage.

Caution, risk of electric shock

Caution, hot surface

Caution, risk of danger. Consult the relevant user documentation.

Caution, lifting hazard

Caution, hand entanglement hazard

Notice, non-ionizing radiation

Direct current

Alternating current

Both direct and alternating current

Three-phase alternating current

Earth (ground) terminal

© Festo Didactic 52174-10 III


Safety and Common Symbols

Symbol Description

Protective conductor terminal

Frame or chassis terminal

Equipotentiality

On (supply)

Off (supply)

Equipment protected throughout by double insulation or


reinforced insulation

In position of a bi-stable push control

Out position of a bi-stable push control

IV © Festo Didactic 52174-10


Table of Contents
Preface .................................................................................................................. IX
About This Manual ................................................................................................ XI
To the Instructor .................................................................................................. XIII

Introduction Directional Protection .................................................................. 1


DISCUSSION OF FUNDAMENTALS ....................................................... 1
Overcurrent protection of radial feeders .................................. 1
Protection of parallel power lines using overcurrent relays ..... 2
Directional overcurrent protection............................................ 4
Directional comparison protection ........................................... 6
Directional power protection .................................................... 7

Exercise 1 Directional Overcurrent Protection ............................................ 9


DISCUSSION ..................................................................................... 9
Determining the direction in which an alternating current
flows ......................................................................................... 9
Operation of the directional overcurrent relay ....................... 11
Typical value (45°) of the characteristic angle used in
directional overcurrent relays ................................................ 13
PROCEDURE .................................................................................. 16
Set up and connections ......................................................... 16
Operation of a directional overcurrent relay .......................... 17
Forward direction zone............................................................. 17
Backward (reverse) direction zone ........................................... 23
Directional overcurrent protection of power lines
connected in parallel .............................................................. 25
Operation of the overcurrent relays at locations C and D......... 30
Operation of the directional overcurrent relays at
locations E and F ..................................................................... 32
Analysis of the relay responses ............................................... 35
Ending the exercise ............................................................... 37

Exercise 2 Directional Comparison Protection.......................................... 39


DISCUSSION ................................................................................... 39
Directional overcurrent protection with time coordination
or time-current coordination................................................... 39
Directional comparison protection ......................................... 43
Control logic of directional overcurrent relays used for
directional comparison protection .......................................... 46

© Festo Didactic 52174-10 V


Table of Contents

PROCEDURE .................................................................................. 49


Set up and connections ......................................................... 49
Directional overcurrent protection of a three-segment
ring bus .................................................................................. 50
Operation of the overcurrent relays at locations D and E ......... 56
Operation of the directional overcurrent relays at
locations F and G ..................................................................... 59
Operation of the directional overcurrent relays at
locations H and I....................................................................... 62
Analysis of the relay responses ................................................ 63
Directional comparison protection of a three-segment
ring bus .................................................................................. 66
Operation of the directional overcurrent relay at location D ...... 68
Operation of the directional overcurrent relay at location F ...... 71
Analysis of the relay responses on the faulty line ..................... 74
Operation of the directional overcurrent relays at
locations H and I....................................................................... 75
Analysis of the relay responses on a healthy line ..................... 79
Global analysis of the relay responses ..................................... 79
Ending the exercise ............................................................... 80

Exercise 3 Directional Power Protection .................................................... 83


DISCUSSION ................................................................................... 83
Determining the value of power and the direction of
power flow.............................................................................. 83
Active power ............................................................................. 84
Reactive power......................................................................... 85
Operation of the directional power relay ................................ 86
Motoring protection ................................................................ 88
Loss-of-excitation protection .................................................. 90
PROCEDURE .................................................................................. 93
Set up and connections ......................................................... 93
Directional power protection applied to a synchronous
generator ............................................................................... 94
Motoring protection................................................................... 96
Loss-of-excitation protection...................................................101
Ending the exercise ............................................................. 105

Appendix A Equipment Utilization Chart .................................................... 109

Appendix B Glossary of New Terms ........................................................... 111

VI © Festo Didactic 52174-10


Table of Contents

Appendix C Introduction to the DIGSI 5 Software from Siemens ............ 113


Setting the language used in DIGSI 5 ................................. 114
Opening a project file ........................................................... 114
Displaying the single-line diagram ....................................... 116
Setting the frequency of operation of the protective relay ... 116
Setting the language used in the front panel display of
the protective relay .............................................................. 118
Accessing the settings of a specific protection function of
the relay ............................................................................... 118
Accessing the parameters of a test sequence .................... 120
Changing the ratio of current (or voltage) transformers ...... 121
Enabling/disabling fault display ........................................... 123
Loading a new configuration to the protective relay ............ 124
Restarting the protective relay in the simulation (test)
mode .................................................................................... 126
Updating the test environment............................................. 129
Starting a test sequence ...................................................... 129
Downloading a fault record from the protective relay .......... 131
Displaying the signals stored in a fault record ..................... 132
Restarting the protective relay in the process (normal
operation) mode................................................................... 135

Appendix D Protective Relay LED Identification Labels ........................... 137

Appendix E Electrical Graphic Symbols (IEC and ANSI) .......................... 139

Index .................................................................................................................. 141


Bibliography ....................................................................................................... 143

© Festo Didactic 52174-10 VII


Preface
The production of energy using renewable natural resources such as wind,
sunlight, rain, tides, geothermal heat, etc., has gained much importance in recent
years as it is an effective means of reducing greenhouse gas (GHG) emissions.
The need for innovative technologies to make the grid smarter has recently
emerged as a major trend, as the increase in electrical power demand observed
worldwide makes it harder for the actual grid in many countries to keep up with
demand. Furthermore, electric vehicles (from bicycles to cars) are developed and
marketed with more and more success in many countries all over the world.

To answer the increasingly diversified needs for training in the wide field of
electrical energy, the Electric Power Technology Training Program was
developed as a modular study program for technical institutes, colleges, and
universities. The program is shown below as a flow chart, with each box in the
flow chart representing a course.

The Electric Power Technology Training Program.

© Festo Didactic 52174-10 IX


Preface

The program starts with a variety of courses providing in-depth coverage of basic
topics related to the field of electrical energy such as ac and dc power circuits,
power transformers, rotating machines, ac power transmission lines, and power
electronics. The program then builds on the knowledge gained by the student
through these basic courses to provide training in more advanced subjects such
as home energy production from renewable resources (wind and sunlight), large-
scale electricity production from hydropower, large-scale electricity production
from wind power (doubly-fed induction generator [DFIG], synchronous generator,
and asynchronous generator technologies), smart-grid technologies (SVC,
STATCOM, HVDC transmission, etc.), storage of electrical energy in batteries,
and drive systems for small electric vehicles and cars.

We invite readers of this manual to send us their tips, feedback, and


suggestions for improving the book.

Please send these to did@de.festo.com.


The authors and Festo Didactic look forward to your comments.

X © Festo Didactic 52174-10


About This Manual

Manual objectives

When you have completed this manual, you will be familiar with the operation
and settings of the directional overcurrent relay (ANSI device no. 67). You will
learn about directional overcurrent protection and directional comparison
protection, which are two ways to protect power lines connected in parallel or
forming a ring bus. You will understand how directional comparison protection
uses a communication link between two directional overcurrent relays to allow
fast clearing of faults. You will be familiar with the operation and settings of the
directional power relay (ANSI device no. 32). You will learn how directional power
protection can prevent damage to the prime mover of a synchronous generator
when it stops driving the generator. You will also see how directional power
protection can prevent damage to a synchronous generator resulting from
sustained operation as an asynchronous generator following a loss of excitation.

Safety considerations

Safety symbols that may be used in this manual and on the equipment are listed
in the Safety Symbols table at the beginning of the manual.

Safety procedures related to the tasks that you will be asked to perform are
indicated in each exercise.

Make sure that you are wearing appropriate protective equipment when
performing the tasks. You should never perform a task if you have any reason to
think that a manipulation could be dangerous for you or your teammates.

Prerequisite

As a prerequisite to this course, you should have read the manuals titled DC
Power Circuits, part number 86350, Single-Phase AC Power Circuits, part
number 86358, Single-Phase Power Transformers, part number 86377,
Three-Phase AC Power Circuits, part number 86360, Three-Phase Transformer
Banks, part number 86379, and Overcurrent and Overload Protection Using
Protective Relays, part number 52173.

Systems of units

Units are expressed using the International System of Units (SI) followed by units
expressed in the U.S. customary system of units (between parentheses).

Voltage symbol

Voltages are represented using the letter “E”. In certain countries, the letter “U” is
rather used to represent voltages.

© Festo Didactic 52174-10 XI


To the Instructor
You will find in this Instructor Guide all the elements included in the Student
Manual together with the answers to all questions, results of measurements,
graphs, explanations, suggestions, and, in some cases, instructions to help you
guide the students through their learning process. All the information that applies
to you is placed between markers and appears in red.

Accuracy of measurements

The numerical results of the hands-on exercises may differ from one student to
another. For this reason, the results and answers given in this manual should be
considered as a guide. Students who correctly performed the exercises should
expect to demonstrate the principles involved and make observations and
measurements similar to those given as answers.

Detailed procedure in Exercise 1

It is recommended to perform the exercises in the order proposed in this manual,


as Exercise 1 features more detailed explanations than the rest of the exercises.

© Festo Didactic 52174-10 XIII


Sample
Extracted from
Instructor Guide
Introduction

Directional Protection

MANUAL OBJECTIVE When you have completed this manual, you will be familiar with the operation
and settings of the directional overcurrent relay (ANSI device no. 67). You will
learn about directional overcurrent protection and directional comparison
protection, which are two ways to protect power lines connected in parallel or
forming a ring bus. You will understand how directional comparison protection
uses a communication link between two directional overcurrent relays to allow
fast clearing of faults. You will be familiar with the operation and settings of the
directional power relay (ANSI device no. 32). You will learn how directional power
protection can prevent damage to the prime mover of a synchronous generator
when it stops driving the generator. You will also see how directional power
protection can prevent damage to a synchronous generator resulting from
sustained operation as an asynchronous generator following a loss of excitation.

DISCUSSION OUTLINE The Discussion of Fundamentals covers the following points:

ƒ Overcurrent protection of radial feeders


ƒ Protection of parallel power lines using overcurrent relays
ƒ Directional overcurrent protection
ƒ Directional comparison protection
ƒ Directional power protection

DISCUSSION OF Overcurrent protection of radial feeders


FUNDAMENTALS
In a distribution network or an industrial application, a radial feeder is a line used
to convey electric power, which has a radial structure and is powered at one end
only. The power source side of the radial feeder generally consists of a single
power transformer or two or more power transformers connected in parallel.
Along the radial feeder, substation busses are present to which loads are
connected to provide power, for example, to a small town or village. The power
lines between the substations are called feeder segments. The infeed of a feeder
segment refers to its end on the source side.

It is common to use overcurrent protection to protect radial feeders against faults


that give rise to the flow of excessive currents. Protection of radial feeders is
commonly achieved by installing a circuit breaker and an overcurrent relay with
its associated current transformers at the infeed of each feeder segment.
Figure 1 shows a radial feeder protected this way. For the sake of simplicity, only
the circuit breaker at the infeed of each feeder segment is shown in this figure,
and the power transformers and fuses feeding the loads at substation
busses A, B, C, and D have been omitted.

© Festo Didactic 52174-10 1


Introduction – Directional Protection  Discussion of Fundamentals

A Feeder
Substation segment
Infeed bus Transformer
B C D Fuse
Load

Loads

Figure 1. Single-line diagram of a radial feeder with overcurrent protection.

Using circuit breakers and overcurrent relays at different locations along a radial
feeder is essential to achieve discriminative protection. This type of protection
disconnects the minimum amount of circuit to isolate the fault and thereby limits
the number of loads that lose power. To obtain proper discrimination when
protecting a radial feeder with several circuit breakers and overcurrent relays, the
operation of the overcurrent relays must be properly coordinated. This is referred
to as relay coordination or relay grading. Several methods exist to achieve relay
coordination. In short, one must determine the characteristics of the protected
radial feeder and adjust the time and/or current settings of the overcurrent relays
in such a manner that the relay closest to the fault trips first.

a The coordination of overcurrent relays is presented in Exercise 3 of the manual


Overcurrent and Overload Protection Using Protective Relays, p/n 52173.

Protection of parallel power lines using overcurrent relays

Equipment redundancy is common in electric power systems, since one piece of


equipment can fail without interrupting the supply of power. The use of multiple
generators, lines, and/or transformers thus improves the availability of power.
Similarly, equipment redundancy facilitates maintenance, since the piece of
equipment requiring maintenance can be put out of service temporarily without
interrupting the supply of power. Also, using multiple lines in parallel (see
Figure 2) is common, because it allows more power to be conveyed to a given
location. Equipment redundancy and the use of parallel power lines help in
making the power grid smart.

2 © Festo Didactic 52174-10


Introduction – Directional Protection  Discussion of Fundamentals

Power
source
Substation bus A

Line 1 Line 2

Substation bus B

Load

Figure 2. Two lines connected in parallel to convey power to a substation.

It is possible to protect the two parallel lines of Figure 2 the same way as in a
radial feeder protection system, i.e., by using an overcurrent relay (ANSI device
no. 51) and a circuit breaker at the source end of each line, as shown in Figure 3.
This protects the line properly, but results in a poor availability of power at the
load.

When a fault occurs on line 1, fault currents circulate in both lines, causing both
overcurrent relays to trip after 0.3 s, thereby opening circuit breakers C and D.
This opens both power lines. As a result, power is no longer available at
substation bus B.

Using overcurrent protection to protect power lines connected in parallel works,


but is not discriminative; even the healthy power line is opened. Consequently,
the supply of power to the load is interrupted for a fault on any one of the two
power lines. This results in twice as many chances to lose power at the load
compared to when a single line is used. In the end, this is likely to lead to lower
availability of power than when a single line is used.

© Festo Didactic 52174-10 3


Introduction – Directional Protection  Discussion of Fundamentals

Power
source

Substation bus A

Fault
currents

IF1 IF2
0.3 s 51 51 0.3 s
DT DT
C D
Line 1 Line 2

Fault

Substation bus B

Load

Figure 3. Protection of two parallel lines using overcurrent relays.

Directional overcurrent protection

ANSI is the common abbre- Directional overcurrent relays are required to achieve discriminative protection of
viation used to refer to the the two power lines in Figure 3. A directional overcurrent relay is referred to as
American National Stand- a device no. 67 as per ANSI standard C37.2. It is defined as “a relay that
ards Institute. functions on a desired value of ac overcurrent flowing in a predetermined
direction”. In other words, it is an overcurrent relay that trips only when the fault
current flows in a given direction. Exercise 1 of this manual covers the operation
of directional overcurrent relays in detail.

a In the context of alternating current (ac) power systems, the polarity of current
cannot be used to establish the direction of current flow. Instead, the phase
shift between current and voltage is used, as explained in the discussion of
Exercise 1.

Proper fault discrimination is achieved when one uses directional overcurrent


relays to protect parallel power lines, as shown in Figure 4.

a A directional overcurrent relay measures the circuit voltage via a voltage


transformer. The voltage transformers have been omitted in Figure 4 for the
sake of clarity.

4 © Festo Didactic 52174-10


Introduction – Directional Protection  Discussion of Fundamentals

Power
source

Substation bus A

Fault
currents

51 IF1 IF2 51
DT DT
0.4 s C D 0.4 s

Line 1 Line 2

Fault

0.1 s 0.1 s

67 67
E F

Substation bus B

Load

Figure 4. Directional overcurrent protection of two power lines connected in parallel.

When a fault occurs on line 1, fault current IF1 flows through line 1. Fault
current IF2 also flows through line 1, but in the opposite direction. The directional
overcurrent relay at location E trips and opens the corresponding circuit
breaker 0.1 s after the fault occurred, because fault current IF2 flows in the same
direction as the direction set in the relay (indicated in Figure 4 by the arrow
beside the directional overcurrent relay symbol). On the other hand, the
directional overcurrent relay at location F does not trip, because fault current IF2
flows in the direction opposite to the direction set in the relay. Consequently, fault
current IF2 is interrupted when the circuit breaker at location E opens, i.e., 0.1 s
after the fault occurred.

Fault current IF1 still flows through line 1 after the circuit breaker at location E
opened. However, the overcurrent relay at location C trips and opens the
corresponding circuit breaker 0.4 s after the fault occurred, thereby interrupting
fault current IF1.

As a result, the protection isolated the fault while achieving proper discrimination:
the faulty line (line 1) has been disconnected and the healthy line (line 2) has
been left in service. Consequently, power is still available at substation bus B,
thereby maintaining the availability of power at the load.

© Festo Didactic 52174-10 5


Introduction – Directional Protection  Discussion of Fundamentals

In this example of direction- A time setting of 0.4 s is used on the overcurrent relay at location D to allow the
al overcurrent protection of directional overcurrent relay at location E to trip first when a fault occurs on
two power lines in parallel, line 1. This ensures that line 2 is not disconnected when a fault occurs on line 1,
fault discrimination is based thereby achieving proper fault discrimination. Similarly, the same time setting
on time coordination of 0.4 s is used for the overcurrent relay at location C to allow the directional
achieved using definite time overcurrent relay at location F to trip first when a fault occurs on line 2. This
overcurrent relays. Inverse ensures that line 1 is not disconnected when a fault occurs on line 2.
definite minimum
time (IDMT) overcurrent When overcurrent protection is used to protect parallel power lines, both an
relays can also be used to overcurrent relay and a directional overcurrent relay are required on each line to
achieve time-current coor- achieve proper fault discrimination. This kind of protection is commonly referred
dination. to as directional overcurrent protection.

Exercise 1 of this manual deals with the operation of the directional overcurrent
relay and the directional overcurrent protection applied to power lines connected
in parallel.

Figure 5. Parallel power lines.

Directional comparison protection

Directional overcurrent protection, when applied to parallel power lines, remains


simple and allows faults to be cleared in relatively short times, while achieving
proper discrimination. However, when the topology of the power system
becomes more complex, relay coordination involves more than just two relays.
Unfortunately, the time required to clear faults increases with the number of
relays to be coordinated. Depending on the application, longer fault clearing
times may or may not be acceptable for various reasons. When the fault clearing
times achieved using directional overcurrent protection and relay coordination
based on either time alone or time and current are judged unacceptable,
directional comparison protection can be used to minimize fault clearing times.

6 © Festo Didactic 52174-10


Introduction – Directional Protection  Discussion of Fundamentals

Directional comparison protection uses a pair of directional overcurrent relays


to protect each segment of a power line, the relays being located at the two ends
of the protected line segment. Each directional overcurrent relay in a pair can
communicate with the relay at the other end of the protected line segment via a
communication link (optical fiber, microwave communication system, etc.). This
key feature allows the implementation of fast relay tripping schemes providing
short fault clearing times.

Exercise 2 of this manual explains how directional comparison protection works.

Directional power protection

A protective relay that measures the current and voltage at a given point of a
circuit, like a directional overcurrent relay, is also able to determine the value of
power at the point of measurement as well as the direction of power flow. Such a
protective relay is referred to as a directional power relay (ANSI device no. 32).
Directional power relays are used to implement directional power protection.

For instance, directional power protection can be implemented to prevent


damage to a prime mover (e.g., a steam turbine) when it stops driving a
synchronous generator connected to the power network. In short, this is achieved
by measuring active power at the generator stator and generating an alarm when
the direction of active power flow reverses, which means that the generator
begins to draw active power from the network because it begins to operate as a
synchronous motor. After a certain time delay, a trip command is generated to
disconnect the synchronous generator from the power network, thereby stopping
generator motoring and preventing damage to the prime mover. This type of
directional power protection is commonly referred to as motoring protection or
reverse power protection.

Directional power protection can also be used to protect a synchronous


generator against a loss of excitation (LOE). Losing excitation causes a
synchronous generator to operate as an asynchronous generator, a condition of
operation that can eventually result in damage to the synchronous generator. In
short, this protection is achieved by measuring the reactive power at the
generator stator and generating a trip command, either immediately or shortly
after the LOE event, to shutdown the synchronous generator before damage due
to sustained operation as an asynchronous generator occurs. This type of
directional power protection is commonly referred to as loss-of-excitation
protection or loss-of-field protection.

Exercise 3 of this manual deals with directional power protection.

© Festo Didactic 52174-10 7


Exercise 1

Directional Overcurrent Protection

EXERCISE OBJECTIVE In this exercise, you will learn how to determine the direction in which an
alternating current flows. You will become familiar with the operation of a
directional overcurrent relay, including its main settings. You will analyze the
phasors of fault currents on a given phase to understand why the characteristic
angle in a directional overcurrent relay is commonly set to 45°. You will verify the
angular limits of the forward and backward direction zones of a directional
overcurrent relay. You will learn how directional overcurrent protection achieves
discriminative protection of two power lines connected in parallel.

DISCUSSION OUTLINE The Discussion of this exercise covers the following points:

ƒ Determining the direction in which an alternating current flows


ƒ Operation of the directional overcurrent relay
ƒ Typical value (45°) of the characteristic angle used in directional
overcurrent relays

DISCUSSION Determining the direction in which an alternating current flows

Current in any conductor of an electric circuit can flow from left to right or from
right to left. This is commonly referred to as the direction of current flow. In dc
power circuits, the polarity of the current indicates the direction of current flow. In
ac power circuits, however, the polarity of the current alternates constantly.
Consequently, polarity cannot be used to determine the direction of current flow.

In an ac power circuit, one determines the direction of current flow from the
phase shift between the voltage E and the current I at any given point of the
circuit (refer to Figure 6a).

The term reverse direction When the current flows from left to right in the circuit, the absolute value of the
is commonly used to refer to phase shift between the voltage and current is 90° or less (Figure 6b), the exact
the backward direction. value of the phase shift being dependent on the value of the circuit impedance Z.
Both terms are used in this This direction is generally considered as the forward direction. On the other
manual. hand, when the current flows from right to left in the circuit, the absolute value of
the phase shift between the voltage and current is 90° or more (Figure 6c), the
exact value of the phase shift being dependent on the value of the circuit
impedance Z. This direction is generally considered as the reverse direction.

© Festo Didactic 52174-10 9


Exercise 1 – Directional Overcurrent Protection  Discussion

Forward

Reverse

Z Z

I
E

(a)
Circuit diagram

90° 90°

E E
180° 0° 180° 0°
(-180°) (-180°)

270° 270°
(-90°) (-90°)

(b) (c)
Current flows in forward direction Current flows in reverse direction

Figure 6. Determining the direction of current flow in an ac power circuit.

a Phase angle values can be expressed over a range of 0° to 360° or over a


range of -180° to 180°. In the phasor diagrams provided in this manual, phase
angle values are expressed over a range of 0° to 360°. For practicality,
however, phase angle values between -180° and 0° are also provided (shown
in parentheses).

In most power networks, the impedance is of resistive-inductive nature. In this


case, the expected range of phase angle values of the current is reduced to 90°
for each direction of current flow, as shown in Figure 7.

10 © Festo Didactic 52174-10


Exercise 1 – Directional Overcurrent Protection  Discussion

Forward

Reverse

Z Z

I
E

(a)
Circuit diagram

90° 90°

E E
180° 0° 180° 0°
(-180°) (-180°)

270° 270°
(-90°) (-90°)

(b) (c)
Current flows in forward direction Current flows in reverse direction

Figure 7. Determining the direction of current flow in an ac power circuit (resistive-inductive


impedance only).

Operation of the directional overcurrent relay

The directional overcurrent relay is the key component to achieve directional


overcurrent protection, as discussed in the Introduction of this manual. The
operation of the directional overcurrent relay (ANSI device no. 67) along with its
main parameters are explained below.
x A directional overcurrent relay (ANSI device no. 67) mainly consists of an
overcurrent relay plus a directional element that determines the direction of
current flow.
x A directional overcurrent relay measures current and voltage at a given point
of the circuit, as shown in Figure 8. From these measurements, the
directional element is able to determine the direction of current flow.

© Festo Didactic 52174-10 11


Exercise 1 – Directional Overcurrent Protection  Discussion

From
power To load
source

Current
input
Directional
overcurrent Trip
Voltage relay
input (ANSI device
no. 67)

Figure 8. Connection of a directional overcurrent relay and HV circuit breaker to an electric


power circuit.

x The directional element allows the operation (tripping) of the overcurrent


relay within the directional overcurrent relay only when the measured current
flows in the selected direction (forward or reverse) of current flow.
x A directional overcurrent relay can monitor line current on two phases, in
which case it measures two currents and two voltages. This allows detection
of any phase-to-phase fault. It can also monitor line current on all three
phases, in which case it measures three currents and three voltages. This
allows detection of any phase-to-phase fault as well as any phase-to-ground
fault.
x In electromechanical and static directional overcurrent relays, the reference
voltage for phase A is generally line voltage EBC, not phase voltage EA, as
one could expect. This is because voltage EBC is not affected when a ground
fault occurs on phase A, thereby providing a more stable reference voltage
(the same applies to phase B and phase C, i.e., line voltage ECA is used as
the reference voltage for phase B and line voltage EAB is used as the
reference voltage for phase C). On the other hand, modern directional
overcurrent relays (digital and numerical units) generally use phase
voltage EA as the reference voltage for phase A and other techniques to
obtain a reference voltage that is even more stable (these techniques are
beyond the scope of this manual). However, note that the settings in certain
modern directional overcurrent relays replicate the settings found in
electromechanical and static directional overcurrent relays even if a phase
voltage (e.g., voltage EA for phase A) is used as the reference voltage
instead of a phase-to-phase voltage (e.g., voltage EBC for phase A).
x The reference voltage may be rotated to properly align the forward and
reverse direction zones of the directional overcurrent relay. This rotation
angle is referred to as the characteristic angle. Figure 9 shows the forward
and reverse direction zones for two values of characteristic angle when line
voltage EBC is used as the reference voltage. The value at which the
characteristic angle is set in most applications is discussed in the next
section of this exercise.

12 © Festo Didactic 52174-10


Exercise 1 – Directional Overcurrent Protection  Discussion

Forward direction zone

Reverse direction zone

90° 90°

ERef
180° 0° 180° 0°
(-180°) EA (-180°) EA

EBC, ERef EBC

Characteristic
270° 270° angle
(-90°) (-90°)

(a) (b)
No rotation of reference voltage Rotated reference voltage
(characteristic angle = 0°) (characteristic angle = 90°)

Figure 9. Selecting a characteristic angle to properly align the forward and reverse direction
zones of the directional overcurrent relay.

x The main settings of a directional overcurrent relay are:


- Direction of current flow (forward or reverse)
- Current threshold, also referred to as the current setting. This is the
minimum current for which the directional overcurrent relay may trip.
- Time delay, also referred to as the time setting or the operate delay. This
is the operating time of the relay when a definite-time overcurrent relay
(ANSI device no. 51DT) is used in the directional overcurrent relay.
When an inverse definite minimum time overcurrent relay (ANSI device
no. 51I) is used, the operating time is calculated according to the chosen
time-current characteristic.
- Characteristic angle. Angle by which the reference voltage is rotated to
allow proper operation of the directional overcurrent relay. This angle is
generally set to 45°. This is explained in the following section.

Typical value (45°) of the characteristic angle used in directional


overcurrent relays

The range of phase angle values of current expected for faults on phase A
includes the ranges of phase angle values for a phase-to-ground fault, a phase-
to-phase fault between phase A and phase B, and a phase-to-phase fault

© Festo Didactic 52174-10 13


Exercise 1 – Directional Overcurrent Protection  Discussion

between phase A and phase C. These three cases are treated separately below
to ease understanding. The circuit impedance considered is of resistive-inductive
nature, as this is representative of actual circuit impedances.

When a phase-to-ground fault occurs on phase A, the range of phase angle


values of current IA that is expected is illustrated in Figure 10.

90°

EC

EA Purely-resistive
180° 0°
impedance
(-180°)

EB
IA

270°
(-90°)
Purely-inductive
impedance

Figure 10. Range of phase angle values of current IA expected for a phase-to-ground fault on
phase A.

The ranges of phase angle values of current IA expected for phase-to-phase


faults between phase A and phase B and between phase A and phase C are
shown in Figure 11.

90° 90°

Purely-resistive
impedance
EC EAB EC

EA EA
180° 0° 180° 0°
(-180°) (-180°)
EAC
IA
EB EB
Purely-resistive
impedance
IA

Purely-inductive
impedance
270° Purely-inductive 270°
(-90°) impedance (-90°)

Figure 11. Ranges of phase angle values of current IA expected for phase-to-phase faults
between phase A and phase B (left) and between phase A and phase C (right).

14 © Festo Didactic 52174-10


Exercise 1 – Directional Overcurrent Protection  Discussion

The superposition of the ranges of phase angle values of current IA involved in


Figure 10 and Figure 11 is presented in Figure 12. The total range covers 150°.
Similarly, the total range of phase angle values of the current is also 150° for
faults on phase B or phase C.

90°

EC

EA
180° 0°
(-180°)
EB

IA

270°
(-90°)

Figure 12. Range of phase angle values of current IA expected for faults on phase A.

Setting the characteristic angle to 45° properly aligns the forward and reverse
direction zones of the directional overcurrent relay with the vectors of fault
current expected for phase A, as illustrated in Figure 13. Notice that the forward
direction zone encloses every expected vector of fault current for phase A with a
safety margin of 15° on each side of the expected range of phase angle values of
current. This ensures optimal operation of the directional overcurrent relay.

90°
Forward direction zone

Reverse direction zone

15°

180° 0°
(-180°)
ERef

15° EBC

Characteristic
angle = 45°

270°
(-90°)

Figure 13. Setting the characteristic angle to 45° properly aligns the forward and reverse
direction zones of the directional overcurrent relay with the range of phase angle values
expected for the fault currents.

© Festo Didactic 52174-10 15


Exercise 1 – Directional Overcurrent Protection  Procedure Outline

PROCEDURE OUTLINE The Procedure is divided into the following sections:

ƒ Set up and connections


ƒ Operation of a directional overcurrent relay
Forward direction zone. Backward (reverse) direction zone.
ƒ Directional overcurrent protection of power lines connected in parallel
Operation of the overcurrent relays at locations C and D. Operation of the
directional overcurrent relays at locations E and F. Analysis of the relay
responses.
ƒ Ending the exercise

PROCEDURE a Appendix C of this manual provides information on how to use software


DIGSI ® 5 to perform various tasks related to SIPROTEC ® 5 protective relays.
You should read this appendix before performing the exercise procedure.

Set up and connections

In this section, you will set up a protective relay so that it can be programmed
and tested using a host computer.

1. Refer to the Equipment Utilization Chart in Appendix A to obtain the list of


equipment required to perform this exercise.

Install the Numerical Directional Overcurrent Relay (Model 3812) and the
host computer on your work surface.

a This exercise can also be performed using the Numerical Distance


Relay (Model 3813). The term protective relay is used throughout the
remainder of this exercise procedure to refer to the protective relay used to
perform the exercise.

Insert the LED identification label for Exercise 1 into the front panel of the
protective relay. The identification labels can be found in Appendix D.

2. Connect the protective relay and the host computer to an ac power wall
outlet.

Turn the protective relay on. Wait for the protective relay to complete its
initialization routine (this generally takes about 45 s).

3. Connect the USB port of the protective relay to a USB port of the host
computer.

4. Turn the host computer on, then start the DIGSI 5 software.

16 © Festo Didactic 52174-10


Exercise 1 – Directional Overcurrent Protection  Procedure

Operation of a directional overcurrent relay

In this section, you will establish the phase angle limits of the forward and
backward direction zones of a directional overcurrent relay (ANSI device no. 67).

Forward direction zone

5. In DIGSI 5, open project file Directional Overcurrent Protection.dp5v6


created for the protective relay that you are using to perform the exercise. A
project file contains the complete configuration of the protective relay for a
particular application. By default, the project files required to perform the
exercises in this manual should be located in the following folder:
C:\ProgramData\Festo Didactic\Manual 52174, Directional Protection\...

a Refer to Appendix C to learn how to perform various tasks in software DIGSI 5.

6. In DIGSI 5, display the single-line diagram showing the connection of the


protective relay to the electric power circuit. Observe that in this project, the
current inputs of the protective relay are connected to the electric power
circuit (a feeder in an electric power substation) via current transformers
having a 200 A/1 A ratio. Also, the voltage inputs of the protective relay are
connected to the electric power circuit via Y-connected (star-connected)
voltage transformers having a 100 kV/100 V ratio. For example, when the
bus voltage is 120 kV, the voltage at the primary windings of the voltage
transformers is 69.3 kV and the voltage at the secondary windings is 69.3 V.

a A ratio of 100 kV to 100 V eases calculations of voltage values at the


secondary windings of the voltage transformers. This ratio is not commonly
available in practice and is employed here strictly for educational purposes.

7. In DIGSI 5, set the frequency of operation (Rated frequency parameter) of


the protective relay to the frequency of your local ac power network.

Set the language used in the front panel display of the protective relay to the
language used in DIGSI 5.

8. In DIGSI 5, access the settings of the directional overcurrent protection


function of the protective relay. In the Project tree area of DIGSI 5, the
directional overcurrent protection function is called 67 Dir.OC-3ph-A1 and is
located in protection function group VI 3ph 1.

Make the following observations about the directional overcurrent protection


function:
x The characteristic angle (parameter Rotation angle of ref. volt. in the
General section) is set to 45°.
x The other parameters of the protection function are defined in time-
current characteristic Definite-T1. Note that the Mode parameter is set to
on, meaning that the protection function is activated.
x The direction of current flow (parameter Directional mode) is set to
forward.

© Festo Didactic 52174-10 17


Exercise 1 – Directional Overcurrent Protection  Procedure

x The protective relay has a definite-time characteristic, because the time


delay (parameter Operate delay) is set to 0.1 s.
x The current threshold of the protective relay (parameter Threshold) is set
to 400 A.
x Time-current characteristic Definite-T1 is displayed in the right region of
the working area of DIGSI 5.

a The x-axis in the diagram showing the time-current characteristic of the


protection function is graduated with values of current at the secondary
windings of the current transformers. These values of current must be
multiplied by the ratio of the current transformers (200 A/1 A in the currently-
open project) to obtain values of current at the primary windings of the current
transformers (i.e., values of current in the electric power circuit).

With voltage EBC as the reference voltage and the value of the characteristic
angle presented above, the forward and backward direction zones of the
directional overcurrent relay are the same as those shown in Figure 13.

9. In DIGSI 5, access the settings of the overcurrent protection function of the


protective relay. In the Project tree area of DIGSI 5, the directional
overcurrent protection function is called 50/51 OC-3ph-B1
or 50/51 OC-3ph-A and is located in protection function group VI 3ph 1.

This function is inactive (Mode parameter is set to off) for now, but will be
used later in this exercise procedure.

10. In DIGSI 5, access the parameters of test sequence Directional OC Relay


Operation. This test sequence is part of the project file currently open in
DIGSI 5 and can be used to test the directional overcurrent protection
function of the protective relay using its internal relay test system.

a In all test sequences, the magnitudes are expressed as secondary values, i.e.,
the values at the secondary windings of the current and voltage transformers.

Make the following observations about test sequence Directional OC Relay


Operation.
x The test sequence consists of two steps.
x The first step (step 1) has a duration of 5.0 s.
x During the first step, the internal relay test system emulates balanced
currents of 1.00 A at the current inputs of the relay. This is equivalent to
balanced currents of 200 A in the electric power circuit,
because 200 A/1 A current transformers are used in this project.
x During the first step, the internal relay test system emulates balanced
voltages of 69.3 V at the voltage inputs of the relay. This is equivalent to
balanced line-to-neutral voltages of 69.3 kV in the electric power circuit,
because 100 kV/100 V voltage transformers (Y-connected) are used in
this project.
x The second step (step 2) has a duration of 72.0 s.

18 © Festo Didactic 52174-10


Exercise 1 – Directional Overcurrent Protection  Procedure

x During the second step, the internal relay test system emulates a current
of 2.50 A at the phase-A current input of the relay. This is equivalent to a
current of 500 A in the electric power circuit. Also, the phase angle of this
current increases linearly from -180° to 180°, as shown in Figure 14,
thereby covering the entire range of possible phase angle values.

Phase angle

Time (seconds)

Figure 14. Phase angle of the current at phase A during step 2 of test sequence Directional
OC Relay Operation.

x During the second step, the currents emulated for phase B and phase C,
as well as all of the emulated voltages, are the same as those emulated
during step 1.
x By default, the frequency of the currents and voltages emulated by the
internal relay test system during both steps of the sequence is set
to 50 Hz.

Set the frequency of the currents and voltages emulated during both steps of
test sequence Directional OC Relay Operation to the frequency of your local
ac power network.

11. Load the configuration (i.e., the content of the project file currently open) to
the protective relay using DIGSI 5. This step generally takes some time.

12. In DIGSI 5, restart the protective relay in the simulation mode to allow the
directional overcurrent protection function of the protective relay (i.e.,
protection function 67 Dir.OC-3ph-A1 in protection function group VI 3ph 1)
to be tested using the internal relay test system. Once the restart process is
completed, the test environment should be displayed in DIGSI 5. Also, the
front panel display of the protective relay should indicate that the unit is
operating in the simulation mode (the words Simulation mode should appear
briefly on the display at regular intervals).

a The Error LED on the front panel of the protective relay lights up when the unit
is in simulation mode. This is normal. Do not be concerned about this error
indication.

© Festo Didactic 52174-10 19


Exercise 1 – Directional Overcurrent Protection  Procedure

a During this procedure, if you notice that DIGSI 5 lags relay operation, press the
Clear list button at the top of the test environment. This should restore normal
operation of DIGSI 5.

13. In DIGSI 5, start test sequence Directional OC Relay Operation, then


observe the front panel of the protective relay to see how it responds to the
currents and voltages emulated by its internal relay test system.

a The relay display refreshes every 1 or 2 seconds.

Note that the protective relay displays the magnitude and phase of the
measured currents and voltages. For 5 seconds, the values of the balanced
currents and voltages are displayed, then the magnitude of the current of
phase A increases to 500 A and its phase angle decreases to -180°. The
phase angle then slowly increases up to a value of 180°. Eventually, LED
indicators 1, 9, and 16 light up.

Table 1 provides the functions of the LED indicators of the protective relay
(i.e., the column of 16 LEDs located on the left-hand side of the front panel).
These functions are included in the configuration loaded to the protective
relay.

Table 1. Functions of the LED indicators on the front panel of the protective relay.

LED
indicator LED color Function
number

Pickup indication for phase A. The LED lights up when


1 Red either the overcurrent protection function or the directional
overcurrent protection function picks up.

2 Red Same as LED indicator 1 for phase B.

3 Red Same as LED indicator 1 for phase C.

Overcurrent protection function tripped indication. The LED


7 Red lights up when the overcurrent protection function trips the
protective relay.

Directional overcurrent protection function tripped


9 Red indication. The LED lights up when the directional
overcurrent protection function trips the protective relay.

Relay tripped indication. The LED lights up when the


16 Red
protective relay trips.

a The LED indicators are numbered 1 to 16 from the top to the bottom of the
column, respectively.

20 © Festo Didactic 52174-10


Exercise 1 – Directional Overcurrent Protection  Procedure

Explain why LED indicator 1 lit up during the simulation.

LED indicator 1 lit up because the relay picked up on phase A. This


happened because, during a certain time (about 36 s), the magnitude (500 A)
of the emulated current for phase A was higher than the current
threshold (400 A) of the protective relay while this current flowed in the
direction set in the relay (forward in this case).

Explain why LED indicators 9 and 16 lit up.

LED indicator 9 lit up to indicate that the directional overcurrent protection


function tripped. This happened because the magnitude (500 A) of the
emulated current for phase A was higher than the current threshold (400 A)
of the protective relay while this current flowed in the direction set in the relay
(forward in this case), for a time duration (about 36 s) much longer than the
relay time delay (0.1 s).

LED indicator 16 lit up because the protective relay tripped.

14. Whenever the protective relay is tested using its internal relay test system,
input signals (e.g., the currents at the three current inputs) as well as internal
signals (e.g., relay pickup occurrences, the circuit breaker trip command,
etc.) may be recorded in the relay. The signals recorded in the protective
relay are referred to as a fault record. DIGSI 5 can be used to download a
fault record from the protective relay and display the signals contained in the
fault record in SIGRA. SIGRA is a Siemens application that displays the
signals contained in a fault record on time charts. These time charts are
useful to analyze the protective relay response to the fault.

A fault record has been created in the protective relay during the previous
manipulation. Use DIGSI 5 to download the latest fault record from the
protective relay and display the signals contained in this fault record in
SIGRA. Figure 15 shows the signal representing the phase angle of the
phase-A current and the pickup signal of the protective relay that should be
displayed in SIGRA.

For optimal display of the signals, make the following settings:


x Select Instantaneous Values (and not R.M.S. Values).
x Under the Measuring Signal column, select the phase angle of phase A
(VI3ph1:FdSym:Fundam:Iph:phs A angle) for both cursors. The
Instantaneous column then displays the phase angle values of the
phase-A current at the time corresponding to cursors 1 and 2.
x Align the cursors with the beginning and end of the relay pickup signal.

© Festo Didactic 52174-10 21


Exercise 1 – Directional Overcurrent Protection  Procedure

Figure 15. Signals contained in the fault record downloaded from the protective relay
displayed in SIGRA.

For which range of phase angle values of the phase-A current did the relay
pick up? Explain below and draw the forward direction zone of the relay in
Figure 16.

90°

135° 45°

180° 0°
(-180°)

225° 315°
(-135°) (-45°)

270°
(-90°)
Figure 16. Experimental forward and backward direction zones of the directional overcurrent
relay.

22 © Festo Didactic 52174-10


Exercise 1 – Directional Overcurrent Protection  Procedure

The relay picked up when the phase angle of the phase-A current was
between about -133° (at t = 9.6 s) and 42.5° (at t = 44.6 s). This is a little
less (175.5°) than the theoretical range of 180°, which spreads from phase
angle values of -135° to 45° when the characteristic angle is set to 45°.

90°

135° 45°
Backward (reverse)
direction zone

180° 0°
(-180°)

Forward direction
zone
225° 315°
(-135°) (-45°)

270°
(-90°)
Figure 16. Experimental forward and backward direction zones of the directional overcurrent
relay.

a Similar results would be obtained if the phase angle of the phase-A current
decreased linearly from 180° to -180° in the test sequence.

15. Reset the protective relay by momentarily depressing the Reset button
located just below the 16 LED indicators on the left-hand side of the relay
front panel. The LED indicators should go out.

Backward (reverse) direction zone

16. In DIGSI 5, access the settings of the directional overcurrent protection


function of the protective relay. In the Project tree area of DIGSI 5, the
directional overcurrent protection function is called 67 Dir.OC-3ph-A1 and is
located in protection function group VI 3ph 1.

Change the direction of current flow (parameter Directional mode) to reverse.

17. Load the configuration to the protective relay using DIGSI 5.

© Festo Didactic 52174-10 23


Exercise 1 – Directional Overcurrent Protection  Procedure

18. In DIGSI 5, display the test environment of the protective relay. Start test
sequence Directional OC Relay Operation, then observe the front panel of
the protective relay to see how it responds to the currents and voltages
emulated by its internal relay test system.

19. A fault record has been created in the protection relay during the previous
manipulation. Use DIGSI 5 to download the latest fault record from the
protective relay and display the signals contained in this fault record in
SIGRA.

The following figure shows the signals that should be displayed in SIGRA.

Signals contained in the fault record downloaded from the protective relay displayed in
SIGRA.

For which range of phase angle values of the phase-A current did the relay
pick up? Explain below and draw the backward direction zone of the relay in
Figure 16.

The relay picked up when the phase angle of the phase-A current was
between -180° and about -138° (at t = 8.6 s) and between about 47.5°
(at t = 45.7 s) and 180°. Overall, the pickup range was approximately from
phase angle values of 47.5° to 222° (-138°). This is a little less (174.5°) than
the theoretical range of 180°, which spreads from phase angle values of 45°
to 225° (-135°) when the characteristic angle is set to 45°.

24 © Festo Didactic 52174-10


Exercise 1 – Directional Overcurrent Protection  Procedure

20. Referring to Figure 13 and Figure 16, summarize the limitations of the
directional overcurrent relay in determining the direction of current flow.

There are two small intervals (about 5° each) of phase angle of the
measured current, located at the limit between the forward and backward
direction zones, where the directional overcurrent relay considers that the
direction of current flow is neither forward nor backward. This is because the
relay is unable to determine the direction of current flow reliably when the
value of the phase angle of the measured current is in either one of these
two intervals of phase angle.

21. Reset the protective relay.

Directional overcurrent protection of power lines connected in parallel

In this section, you will assess how directional overcurrent protection can protect
two power lines connected in parallel.

22. Look at the single line diagram shown in Figure 17. It illustrates two
substations interconnected by two power lines connected in parallel. To
protect the power lines, directional overcurrent protection is used. Each line
is protected by an overcurrent relay close to substation A and a directional
overcurrent relay close to substation B.

a A directional overcurrent relay measures the circuit voltage via a voltage


transformer. The voltage transformers have been omitted in Figure 17 for the
sake of clarity. This applies to every other single line diagram in this exercise.

© Festo Didactic 52174-10 25


Exercise 1 – Directional Overcurrent Protection  Procedure

315 kV Power source

9.1 ȍ ‫ס‬85° Source impedance

315 kV/120 kV
300 MVA Y-Y
12% ‫ס‬85°

Substation bus A

51 51
DT DT
C D

Line 1 Line 2
50 km 50 km
0.45 ȍ/km ‫ס‬85° 0.45 ȍ/km ‫ס‬85°

67 67
E F

Substation bus B

Load Load

Figure 17. Substations interconnected by two power lines connected in parallel. Directional
overcurrent protection is used to protect the power lines.

The magnitude and phase angle of the currents and voltages measured by
the relays at locations C through F under normal operating conditions are
given in Table 2.

a All magnitudes are expressed as primary values, i.e., the values at the primary
windings of the current and voltage transformers. Also, all phase angle values
are referred to the phase angle of voltage EAN at the power source (i.e., the
phase angle of voltage EAN at the power source is 0°).

26 © Festo Didactic 52174-10


Exercise 1 – Directional Overcurrent Protection  Procedure

Table 2. Currents and voltages in the circuit of Figure 17 under normal operating conditions.

Relay C Relay D

Magnitude Phase angle Magnitude Phase angle

IA (A, ‫ס‬°) 196 -6 196 -6


IB (A, ‫ס‬°) 196 -126 196 -126
IC (A, ‫ס‬°) 196 114 196 114
EA (V, ‫ס‬°) 68809 -2 68809 -2
EB (V, ‫ס‬°) 68809 -122 68809 -122
EC (V, ‫ס‬°) 68809 118 68809 118

Relay E Ĺ Relay F Ĺ

Magnitude Phase angle Magnitude Phase angle

IA (A, ‫ס‬°) 196 174 196 174


IB (A, ‫ס‬°) 196 54 196 54
IC (A, ‫ס‬°) 196 -66 196 -66
EA (V, ‫ס‬°) 68283 -6 68283 -6
EB (V, ‫ס‬°) 68283 -126 68283 -126
EC (V, ‫ס‬°) 68283 114 68283 114

Observe that the current at location E is phase shifted by 180° with respect to
the current at location C. Also, the current at location F is phase shifted
by 180° with respect to the current at location D. This is because the polarity
of the current transformers at directional overcurrent relays E and F are
reversed with respect to the polarity of the current transformers at
overcurrent relays C and D. This practice is common when directional
overcurrent relays are used to protect power lines connected in parallel, as
explained later in this exercise.

Figure 18 shows the flow of the resulting fault currents for a ground fault on
phase A located at 10 km from the load end of line 1.

a When referring to Earth, the word “earth” is used in British English, whereas
the word “ground” is used in American English. The word “ground” is used
throughout this manual.

© Festo Didactic 52174-10 27


Exercise 1 – Directional Overcurrent Protection  Procedure

315 kV Power source

9.1 ȍ ‫ס‬85° Source impedance

315 kV/120 kV
300 MVA Y-Y
12% ‫ס‬85°

Substation bus A

IF1 IF2
51 51
DT DT
C D

Fault

67 67
E F

Substation bus B

Load Load

Figure 18. Flow of fault currents for a ground fault located at 10 km of the load end of line 1.

The magnitude and phase angle of the currents and voltages measured by
the relays at locations C through F, assuming that the ground fault shown in
Figure 18 occurs on phase A, are given in Table 3. Notice that a ground fault
on phase A only affects the magnitude and phase angle of the current and
voltage of phase A measured at locations C through F.

a It is assumed here that the ground impedance (i.e., the impedance of the
return path to the grounded terminal of the power transformer in Figure 18) is
null.

28 © Festo Didactic 52174-10


Exercise 1 – Directional Overcurrent Protection  Procedure

Table 3. Currents and voltages in the circuit of Figure 17 under the ground fault condition (on
phase A) shown in Figure 18.

Relay C Relay D

Magnitude Phase angle Magnitude Phase angle

IA (A, ‫ס‬°) 2324 -86 1550 -84


IB (A, ‫ס‬°) 196 -126 196 -126
IC (A, ‫ס‬°) 196 114 196 114
EA (V, ‫ס‬°) 41833 0 41833 0
EB (V, ‫ס‬°) 68809 -122 68809 -122
EC (V, ‫ס‬°) 68809 118 68809 118

Relay E Ĺ Relay F Ĺ

Magnitude Phase angle Magnitude Phase angle

IA (A, ‫ס‬°) 1546 -86 1550 96


IB (A, ‫ס‬°) 196 54 196 54
IC (A, ‫ס‬°) 196 -66 196 -66
EA (V, ‫ס‬°) 6958 -1 6958 -1
EB (V, ‫ס‬°) 68283 -126 68283 -126
EC (V, ‫ס‬°) 68283 114 68283 114

The settings of the definite-time overcurrent relays at locations C and D are


given in Table 4, whereas the settings of the directional overcurrent relays at
locations E and F are given in Table 5.

Table 4. Settings of the overcurrent relays at locations C and D.

Settings Value

Current threshold 400 A

Time delay 0.4 s

CT ratio 200 A / 1 A

Table 5. Settings of the directional overcurrent relays at locations E and F.

Settings Value

Characteristic angle 45°

Direction of current flow Forward

Current threshold 400 A

Time delay 0.1 s

CT ratio 200 A / 1 A

VT ratio 100 kV / 100 V

© Festo Didactic 52174-10 29


Exercise 1 – Directional Overcurrent Protection  Procedure

23. In DIGSI 5, display the single-line diagram showing the connection of the
protective relay to the electric power circuit.

Note the following very important point: the electric power circuit includes
only one protective relay, whereas the protection system of the parallel
power lines shown in Figure 17 includes four distinct protective relays.

To confirm that the protection system properly isolates the fault on line 1
(shown in Figure 18), you will:
x Program the protective relay in the DIGSI 5 project to act, in turn, as
each of the four protective relays in the circuit of Figure 17.
x Obtain the response (i.e., whether or not the relay tripped, and if so, the
trip time) of each relay under the ground fault condition shown in
Figure 18.
x Analyze the response of each of the four relays to reconstitute the
sequence of events that occurs when the relays at locations C through F
in the circuit of Figure 17 are all in operation at the same time.

In this exercise, you will first obtain the response of the overcurrent relay at
locations C and D. You will then obtain the response of the directional
overcurrent relay at locations E and F.

For each of the four relays to be tested, a two-step test sequence bearing the
name of the relay has been predefined in the DIGSI 5 project. The magnitude
and phase angle of the currents and voltages in these sequences represent
those given in Table 2 and Table 3.

24. In DIGSI 5, enable fault display on the relay.

a The above setting allows the pickup and trip times of the relay to be read
directly from the relay front panel display.

Operation of the overcurrent relays at locations C and D

25. In DIGSI 5, access the settings of the overcurrent protection function of the
protective relay. In the Project tree area of DIGSI 5, the overcurrent
protection function is called 50/51 OC-3ph-B1 or 50/51 OC-3ph-A1 and is
located in protection function group VI 3ph 1. Make sure the settings of the
overcurrent protection function (current threshold and time delay) match
those presented in Table 4.

Set the Mode parameter to on to activate the overcurrent protection function


of the protective relay.

26. In DIGSI 5, access the settings of the directional overcurrent protection


function of the protective relay. In the Project tree area of DIGSI 5, the
directional overcurrent protection function is called 67 Dir.OC-3ph-A1 and is
located in protection function group VI 3ph 1.

30 © Festo Didactic 52174-10


Exercise 1 – Directional Overcurrent Protection  Procedure

Set the Mode parameter to off to deactivate the directional overcurrent


protection function of the protective relay.

The protective relay is set to operate as the overcurrent relay at location C


or D.

27. In DIGSI 5, access the parameters of test sequence Testing of Relay C. This
test sequence is set so that the internal relay test system emulates the
currents and voltages that the overcurrent relay at location C measures when
the ground fault shown in Figure 18 occurs on phase A. The test sequence
consists of two steps. The first step (step 1) has a duration of 10.0 s and the
second step (step 2) has a duration of 2.0 s.

The magnitude and phase angle of the currents and voltages emulated
during step 1 represent those given in Table 2 (normal operating conditions).
The magnitude and phase angle of the currents and voltages emulated
during step 2 represent those given in Table 3 (ground fault condition shown
in Figure 18).

Note that the frequency of the currents and voltages emulated by the internal
relay test system during both steps of the sequence is set to 50 Hz.

Set the frequency of the currents and voltages emulated during both steps of
test sequence Testing of Relay C to the frequency of your local ac power
network.

28. Load the configuration to the protective relay. This is necessary because the
settings of the protection function have been modified to make the protective
relay operate as an overcurrent relay having the settings shown in Table 4.

29. In DIGSI 5, display the test environment of the protective relay. Start test
sequence Testing of Relay C, then observe the front panel of the protective
relay to see how it responds to the currents and voltages emulated by its
internal relay test system.

a You may notice that the phase angle values displayed on the protective relay
differ from those in the test sequence (presented in Table 2 and Table 3). This
is because the protective relay assumes that the phase angle of voltage EA
is 0°, the phase angle values of all other currents and voltages being adjusted
accordingly.

When the protective relay picks up or trips, information (protective function


that picked up and tripped the relay, relay pickup time, relay trip time, etc.)
about the response of the protective relay to the test sequence is displayed
on the front panel display. Use the up and down arrow buttons on the relay
front panel to scroll through this information.

© Festo Didactic 52174-10 31


Exercise 1 – Directional Overcurrent Protection  Procedure

Did the protective relay (i.e., the overcurrent relay at location C) operate? If
so, record the trip time of the relay. Explain briefly.

Yes. The protective relay (i.e., the overcurrent relay at location C) tripped in
about 400 ms because the magnitude of the emulated current for
phase A (2324 A) was higher than the relay current threshold (400 A) for a
time exceeding the relay time delay (0.4 s).

30. Reset the protective relay.

31. In DIGSI 5, access the parameters of test sequence Testing of Relay D. This
test sequence is set so that the internal relay test system emulates the
currents and voltages that the overcurrent relay at location D measures when
the ground fault shown in Figure 18 occurs on phase A. Test sequence
Testing of Relay D is built in the same manner as test sequence Testing of
Relay C.

Set the frequency of the currents and voltages emulated during both steps of
test sequence Testing of Relay D to the frequency of your local ac power
network.

32. In DIGSI 5, display the test environment of the protective relay. Start test
sequence Testing of Relay D, then observe the front panel of the protective
relay to see how it responds to the currents and voltages emulated by its
internal relay test system.

Did the protective relay (i.e., the overcurrent relay at location D) operate? If
so, record the trip time of the relay. Explain briefly.

Yes. The protective relay (i.e., the overcurrent relay at location D) tripped in
about 400 ms because the magnitude of the emulated current for
phase A (1550 A) was higher than the relay current threshold (400 A) for a
time exceeding the relay time delay (0.4 s).

33. Reset the protective relay.

Operation of the directional overcurrent relays at locations E and F

34. In DIGSI 5, access the settings of the directional overcurrent protection


function of the protective relay. In the Project tree area of DIGSI 5, the
directional overcurrent protection function is called 67 Dir.OC-3ph-A1 and is
located in protection function group VI 3ph 1. Make sure the settings of the
directional overcurrent protection function (characteristic angle, direction of
current flow, current threshold, and time delay) match those presented in
Table 5.

32 © Festo Didactic 52174-10


Exercise 1 – Directional Overcurrent Protection  Procedure

Set the Mode parameter to on to activate the directional overcurrent


protection function of the protective relay.

Observe that the direction of current flow (parameter Directional mode) is set
to forward, whereas Figure 17 shows that the directional overcurrent relay at
locations E and F look toward the power source, i.e., in the direction opposite
to the expected direction of current flow under normal operating conditions
(or reverse direction). This is because it is assumed that the polarity of the
current transformers at the directional overcurrent relays is arranged in such
a way that setting the direction of current flow to forward makes each relay
look toward the line segment that it protects. This practice is common when
directional overcurrent relays are used to protect power lines connected in
parallel.

35. In DIGSI 5, access the settings of the overcurrent protection function of the
protective relay. In the Project tree area of DIGSI 5, the overcurrent
protection function is called 50/51 OC-3ph-B1 or 50/51 OC-3ph-A1 and is
located in protection function group VI 3ph 1.

Set the Mode parameter to off to deactivate the overcurrent protection


function of the protective relay.

The protective relay is now set to operate as the directional overcurrent relay
at location E or F.

36. In DIGSI 5, access the parameters of test sequence Testing of Relay E. This
test sequence is set so that the internal relay test system emulates the
currents and voltages that the overcurrent relay at location E measures when
the ground fault shown in Figure 18 occurs on phase A. Test sequence
Testing of Relay E is built in the same manner as test sequence Testing of
Relay C.

Set the frequency of the currents and voltages emulated during both steps of
test sequence Testing of Relay E to the frequency of your local ac power
network.

37. Load the configuration to the protective relay. This is necessary because the
settings of the protection function have been modified to make the protective
relay operate as a directional overcurrent relay having the settings shown in
Table 5.

38. In DIGSI 5, display the test environment of the protective relay. Start test
sequence Testing of Relay E, then observe the front panel of the protective
relay to see how it responds to the currents and voltages emulated by its
internal relay test system.

© Festo Didactic 52174-10 33


Exercise 1 – Directional Overcurrent Protection  Procedure

Did the protective relay (i.e., the directional overcurrent relay at location E)
operate? If so, record the trip time of the relay. Explain briefly.

Yes. The protective relay (i.e., the directional overcurrent relay at location E)
tripped in about 100 ms, because:
x the magnitude of the emulated current for phase A (1546 A) was higher
than the relay current threshold (400 A).
x the emulated current for phase A was flowing in the same direction as
the direction of current flow set in the relay (i.e., the phase angle [-86°] of
the emulated current for phase A was in the forward direction zone of the
relay).
x these two conditions lasted for a time exceeding the relay time
delay (0.1 s).

39. Reset the protective relay.

40. In DIGSI 5, access the parameters of test sequence Testing of Relay F. This
test sequence is set so that the internal relay test system emulates the
currents and voltages that the overcurrent relay at location F measures when
the ground fault shown in Figure 18 occurs on phase A. Test sequence
Testing of Relay F is built in the same manner as test sequence Testing of
Relay C.

Set the frequency of the currents and voltages emulated during both steps of
test sequence Testing of Relay F to the frequency of your local ac power
network.

41. In DIGSI 5, display the test environment of the protective relay. Start test
sequence Testing of Relay F.

Did the protective relay (i.e., the directional overcurrent relay at location F)
operate? If so, record the trip time of the relay. Explain briefly.

No. The protective relay (i.e., the directional overcurrent relay at location F)
did not trip. Even if the magnitude of the emulated current for
phase A (1550 A) was higher than the relay current threshold (400 A), the
emulated current for phase A was flowing in the direction opposite to the
direction of current flow set in the relay (i.e., the phase angle [96°] of the
emulated current for phase A was not in the forward direction zone of the
relay).

42. Reset the protective relay.

34 © Festo Didactic 52174-10


Exercise 1 – Directional Overcurrent Protection  Procedure

Analysis of the relay responses

43. Regroup the responses of the relays at locations C through F in Figure 19.

Substation bus A

Relay C (51DT) Relay D (51DT)

Did the relay trip? ________ Did the relay trip? ________

Trip time: ________ Trip time: ________

Line 1 Line 2

Relay E (67) Ĺ Relay F (67) Ĺ

Did the relay trip? ________ Did the relay trip? ________

Trip time: ________ Trip time: ________

Substation bus B

Figure 19. Responses of the relays.

© Festo Didactic 52174-10 35


Exercise 1 – Directional Overcurrent Protection  Procedure

Substation bus A

Relay C (51DT) Relay D (51DT)

Did the relay trip? Yes Did the relay trip? Yes

Trip time: 400 ms Trip time: 400 ms

Line 1 Line 2

Relay E (67) Ĺ Relay F (67) Ĺ

Did the relay trip? Yes Did the relay trip? No

Trip time: 100 ms Trip time: N/A

Substation bus B

Figure 19. Responses of the relays.

Using the relay responses above, reconstitute the sequence of events that
should occur when the relays at locations C through F are all in operation at
the same time.

The directional overcurrent relay at location E trips about 100 ms after the
ground fault occurred on phase A of line 1, because fault current IF2 (refer to
Figure 18) flows in the same direction as the direction of current flow set in
the relay. On the other hand, the directional overcurrent relay at location F
does not trip, because fault current IF2 flows in the direction opposite to the
direction of current flow set in the relay.

Tripping of the directional overcurrent relay at location E immediately opens


the corresponding circuit breaker, thereby interrupting fault current IF2. This,
in turn, prevents the overcurrent relay at location D from tripping, because its
time delay (0.4 s) largely exceeds the duration (about 100 ms) of fault
current IF2.

Finally, the overcurrent relay at location C trips about 400 ms after the fault
occurred. This immediately opens the corresponding circuit breaker, thereby
interrupting fault current IF1.

36 © Festo Didactic 52174-10


Exercise 1 – Directional Overcurrent Protection  Conclusion

How is the fault on line 1 isolated?

The fault on line 1 is isolated by the tripping of the relays at locations C


and E.

How much time is required to clear the fault?

The directional overcurrent relay at location E operates in 100 ms, whereas


the overcurrent relay at location C operates in 400 ms. It thus takes 400 ms
to isolate the fault.

Does directional overcurrent protection isolate a fault on one of the two


parallel connected lines while achieving proper discrimination? Explain
briefly.

Yes. The protection isolates the fault while achieving proper discrimination.
The faulty line (line 1) is disconnected and the healthy line (line 2) is left in
service. Consequently, power is still available at substation bus B, thereby
maintaining the availability of power at the load.

Ending the exercise

44. In DIGSI 5, restart the protective relay in the process mode to allow normal
operation of the unit. Once the restart process is completed, the display of
the protective relay no longer indicates that the unit is operating in the
simulation mode (the words Simulation mode no longer appear on the
display).

45. Close the project open in DIGSI 5 without saving the changes you made to
this project.

Close DIGSI 5.

Turn the protective relay off, then disconnect it from the host computer.

Delete the copy of the project file that you opened at the beginning of this
exercise.

CONCLUSION In this exercise, you learned how to determine the direction in which an
alternating current flows. You became familiar with the operation of a directional
overcurrent relay, including its main settings: direction of current flow,
characteristic angle, current threshold, and time delay. You saw the range of
phase angle that is expected for fault currents on a given phase. You also saw
that setting the characteristic angle to 45° properly aligns the forward direction
and backward direction zones of a directional overcurrent relay with the expected
vectors of fault currents, thereby ensuring optimal detection of the direction of
current flow. You experimentally verified the angular limits of the forward and
backward direction zones of a directional overcurrent relay. You learned, and
experimentally verified, how directional overcurrent protection achieves
discriminative protection of two parallel-connected power lines.

© Festo Didactic 52174-10 37


Exercise 1 – Directional Overcurrent Protection  Review Questions

REVIEW QUESTIONS 1. Why is the characteristic angle generally set to 45° in a directional
overcurrent relay?

Setting the characteristic angle to 45° (typical value) properly aligns the
forward and reverse direction zones of the directional overcurrent relay with
the expected vectors of fault currents, thereby ensuring optimal detection of
the direction of current flow.

2. Name the four main settings of a directional overcurrent relay.

The four main settings of a directional overcurrent relay are:


x Direction of current flow (forward or reverse)
x Current threshold
x Time delay
x Characteristic angle

3. How is the direction of current flow evaluated in an ac power circuit?

In an ac power circuit, one determines the direction of current flow from the
phase shift between the voltage E and the current I at any given point of the
circuit.

4. In a directional overcurrent relay, why is a voltage input required in addition


to the current input?

In a directional overcurrent relay, a voltage input is required in addition to the


current input to determine the direction of current flow via the phase shift
between the voltage E and the current I.

5. Consider the two power lines connected in parallel as shown in Figure 17.
Suppose that the polarity of the current transformers at each directional
overcurrent relay is reversed, thereby causing each relay to look toward the
load instead of toward the line segment that it protects. How could you fix this
problem without changing the polarity of the current transformers?

This problem can be fixed by reversing the direction of current flow set in the
directional overcurrent relay (i.e., set it to reverse).

38 © Festo Didactic 52174-10


Bibliography
Russel Mason, C., The Art & Science or Protective Relaying, Wiley, 1964.

GEC Alsthom Measurements Limited, Protective Relays – Application Guide,


3rd ed., 1987.

Institution of Electrical Engineers, Power System Protection - Volume 2, Systems


and Methods, The Electricity Training Association, 1995, ISBN 0-85296-836-1.

Alstom Grid, Network Protection & Automation Guide, 1st ed., 2011,
ISBN 978-0-9568678-0-3.

Reimert, D., Protective Relaying for Power Generation Systems, 1st ed., Taylor
and Francis, 2006, ISBN 978-0-8247-0700-2.

Siemens, SIPROTEC 5 – Overcurrent Protection 7SJ82/7SJ85, V4.0, 2013.

© Festo Didactic 52174-10 143