Vous êtes sur la page 1sur 1

TECHNICAL PARAMETERS OF AL-QURNA SUBMERSIBLE WASTE

WATER PUMPING STATION (CENTER 2)

Parameter Value
Number of pumping units 3
3
Capacity of each pump (m /hr.), (L/sec.) 324 (90)
Capacity of both duty pumps in parallel 648 (180)
TDH, Demand (m) 10
TDH, Design (m) 14
T.W.L.3 (Alarm signal) 5.88
T.W.L.2(Second pump to operate) 5.21
T.W.L.1 (First pump to operate) 4.82
L.W.L (All pumps to stop) 4.05
Invert level of sump 3.75
Top level of sump 9.75
Invert level of inlet sewer 5.31
Diameter of inlet sewer (mm) 710
Length of Force main (m) 3000
Diameter of Force main (mm) 500
Diameter of riser (mm) 250
Existing ground level 9.20
Sump dimension (dry) (m*m) 6*2.5
Sump dimension (wait) (m*m) 4*4
*One pumping unit as stand by