FRAME HV 804 S
SPECIFICATIONS & OPTIONS
STAMFORD AC generators are designed to meet the All generator stators are wound to 2/3 pitch. This eliminates
performance requirements of IEC EN 60034-1. Other triplen (3rd, 9th, 15th …) harmonics on the voltage waveform
international standards, including BS5000, VDE 0530, and is found to be the optimum design for trouble-free supply
NEMA MG1-32, AS1359, CSA C22.2, UL and CE; as well of non-linear loads. The 2/3 pitch design avoids excessive
as a wide range of international Marine Certification neutral currents sometimes seen with higher winding pitches.
Approvals, can be met on request. For clarification A fully connected damper winding reduces oscillations during
regarding compliance please contact Cummins Generator paralleling. This winding, with the 2/3 pitch and carefully
Technologies. selected pole and tooth designs, ensures very low levels of
. voltage waveform distortion.
The STAMFORD PI range of synchronous ac generators Standard generators feature a main stator with 6 ends
are brushless with a rotating field. They are separately brought out to the terminals, which are mounted on the
excited by the STAMFORD Permanent Magnet Generator frame at the non-drive end of the generator. A sheet steel
(PMG). This is a shaft mounted, high frequency, pilot exciter terminal box contains the AVR and provides ample space for
which provides a constant supply of clean power via the the customers' wiring and gland arrangements. It has
Automatic Voltage Regulator (AVR) to the main exciter. removable panels for easy access.
The main exciter output is fed to the main rotor, through a
full wave bridge rectifier, protected by surge suppression. SHAFT & KEYS
VOLTAGE REGULATORS All generator rotors are dynamically balanced to better than
BS6861:Part 1 Grade 2.5 for minimum vibration in operation.
The P range generators complete with a PMG are available Two bearing generators are balanced with a half key.
with one AVR. The AVR has soft start voltage build up and
built in protection against sustained over-excitation, which INSULATION/IMPREGNATION
will de-excite the generator after a minimum of 8 seconds.
Underspeed protection (UFRO) is also provided on both The insulation system is class 'F'.
AVRs. The UFRO will reduce the generator output voltage All wound components are impregnated with materials and
proportional to the speed of the generator below a pre- processes designed specifically to provide the high build
settable level. required for static windings and the high mechanical strength
required for rotating components.
The MA330 AVR is 3 phase rms sensed with a voltage
regulation of 0.5% rms (see the note on regulation). The QUALITY ASSURANCE
UFRO circuit has adjustable slope and dwell for controlled
recovery from step loads. An over voltage protection circuit Generators are manufactured using production procedures
will shutdown the output device of the AVR, it can also trip having a quality assurance level to
an optional excitation circuit breaker if required. As an BS EN ISO 9001.
option, short circuit current limiting is available with the
addition of current transformers. NOTE ON REGULATION
The stated voltage regulation may not be maintained in the
The MA330 AVR needs a generator mounted current presence of certain radio transmitted signals. Any change in
transformer to provide quadrature droop characteristics for performance will fall within the limits of Criteria 'B' of EN
load sharing during parallel operation. 61000-6-2:2001. At no time will the steady-state voltage
Provision is also made for the connection of the regulation exceed 2%.
STAMFORD power factor controller, for embedded
applications, and a remote voltage trimmer. NB Continuous development of our products entitles us to change
specification details without notice, therefore they must not be
regarded as binding.
2
FRAME HV 804 S
WINDING 61
RATINGS REFER TO SALES AND SERVICE BRIEFING
MAXIMUM ALTITUDE 1000 METRES ABOVE SEA LEVEL
MAXIMUM AMBIENT TEMPERATURE 40º C
FREQUENCY 50Hz
TELEPHONE INTERFERENCE THF< 2%
COOLING AIR 3 m3/sec
VOLTAGE STAR (Y) 6300 6600 6900
kVA BASE RATING FOR
2405 2520 2520
REACTANCE VALUES
Xd DIRECT AXIS SYNCHRONOUS 2.62 2.50 2.29
X'd DIRECT AXIS TRANSIENT 0.217 0.207 0.189
X''d DIRECT AXIS SUB-TRANSIENT 0.161 0.154 0.141
Xq QUADRATURE AXIS REACTANCE 1.833 1.750 1.601
X''q QUAD. AXIS SUB-TRANSIENT 0.301 0.287 0.263
XL LEAKAGE REACTANCE 0.117 0.112 0.102
X2 NEGATIVE PHASE SEQUENCE 0.233 0.222 0.203
X0 ZERO PHASE SEQUENCE 0.036 0.034 0.031
REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
T'd TRANSIENT TIME CONSTANT 0.200
T''d SUB-TRANSIENT TIME CONSTANT 0.015
T'do O.C. FIELD TIME CONSTANT 4.15
Ta ARMATURE TIME CONSTANT 0.074
SHORT CIRCUIT RATIO 1/Xd
Continuous development of our products entitles us to change specification details without notice,
therefore they must not be regarded as binding.
3
FRAME HV 804 S WDG 61 50 Hz
THREE PHASE EFFICIENCY CURVES
6300 V
98.0
97.5
1.0
97.0
0.9
96.5
0.8
96.0
% P.F.
95.5
94.5
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
2405 kVA
6600 V
98.0
97.5
1.0
97.0
0.9
96.5
0.8
96.0
% P.F.
95.5
95.0
94.5
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
2520 kVA
6900 V
98.0
97.5
1.0
97.0
0.9
96.5
0.8
96.0
% P.F.
95.5
95.0
94.5
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
2520 kVA
4
FRAME HV 804 S WDG 61 50Hz
FULL WAVE RECTIFIED AVR
LOCKED ROTOR MOTOR STARTING CURVE
6300V 6600V 6900V
X
30.0
PER CENT TRANSIENT VOLTAGE DIP
25.0
20.0
15.0
10.0
5.0
0.0
0 500 1000 1500 2000 2500 3000 3500 4000 4500
LOCKED ROTOR kVA
x NOTE 1
10000
THE FOLLOWING MULTIPLICATION FACTORS SHOULD BE USED TO ADJUST THE VALUES
SYMMETRIC FROM CURVES BETWEEN THE 0.001 SECONDS AND THE MINIMUM CURRENT POINT IN
RESPECT OF NOMINAL OPERATING VOLTAGE
6300V X 1.00
6600V X 1.05
1000
NOTE 2
5
FRAME HV 804 S
WINDING 61 0.8 Power Factor
RATINGS
Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Class F Standby - 125/40°C Class F Standby - 138/27°C
50Hz Star (V) 6300 6600 6900 6300 6600 6900 6300 6600 6900 6300 6600 6900
kVA 2405 2520 2520 N/A N/A N/A 2573 2695 2695 2668 2795 2795
kW 1924 2016 2016 N/A N/A N/A 2058 2156 2156 2134 2236 2236
Efficiency (%) 96.3 96.3 96.4 N/A N/A N/A 96.2 96.2 96.3 96.1 96.2 96.3
kW Input 1998 2093 2091 N/A N/A N/A 2140 2241 2239 2220 2324 2323
60Hz Star (V) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
kVA N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
kW N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
Efficiency (%) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
kW Input N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
© 2009 TD_HV804S.61.GB_03.09_09_GB