Vous êtes sur la page 1sur 376

E10-3B1-2

Engineering Data Book


3 compressors & 3 inverters
Super Modular Multi System

Full set version,


without appendix

Notice: Toshiba is committed to continuously improving its products to ensure the highest
quality and reliability standards, and to meet local regulations and market requirements. All
features and specifications are subject to change without prior notice.
SMMS-i Data book

Contents
1 Foreword .................................................................................................1-1
2 Safety caution ..........................................................................................2-1
3 Introduction ..............................................................................................3-1
4 System overview .....................................................................................4-1
4-1. OUTLINE OF TOSHIBA SMMS-i
(Super Modular Multi System-i)..................................................................... 4-1
4-2. SUMMARY OF SYSTEM EQUIPMENTS........................................................... 4-2
4-3. List of product and combined model name......................................................... 4-3
4-4. Indoor unit........................................................................................................... 4-5
4-5. Remote controller ............................................................................................... 4-7
5 Basic system configuration ......................................................................5-1
5-1. Basic systems (examples) .................................................................................. 5-1
5-2. Fresh Air Intake Indoor Unit Type....................................................................... 5-5
6 Equipment selection procedure ...............................................................6-1
6-1. Selection flow chart............................................................................................. 6-1
6-2. Operational temperature range........................................................................... 6-2
6-3. Combination conditions for indoor unit and outdoor unit .................................... 6-3
6-4. Cooling/heating capacity characteristics............................................................. 6-4
6-5. Example of equipment selection......................................................................... 6-9
6-6. Selection procedure for fresh air intake indoor unit .......................................... 6-14
7 Refrigerant piping design .......................................................................7-1
7-1. WARNINGS ON REFRIGERANT LEAKAGE ..................................................... 7-1
7-2. Free branching system ....................................................................................... 7-2
7-3. Allowable length/height difference of refrigerant piping ...................................... 7-3
7-4. Selection of refrigerant piping ............................................................................. 7-4
7-5. Charging requirement with additional refrigerant................................................ 7-5
8 Refrigerant cycle diagram ........................................................................8-1
8-1. Outdoor Unit ....................................................................................................... 8-1
8-2. Explanation of Functional Parts .......................................................................... 8-4
8-3. Indoor Unit .......................................................................................................... 8-6
8-4. COMBINED REFRIGERATION CYCLE............................................................. 8-7
9 Wiring Design ..........................................................................................9-1
9-1. General ............................................................................................................... 9-1
9-2. Summary of wiring design .................................................................................. 9-1
9-3. Electrical wiring design ....................................................................................... 9-1
9-4. Outdoor unit power supply.................................................................................. 9-1
9-5. Indoor unit power supply..................................................................................... 9-3
9-6. Design of control wiring ...................................................................................... 9-5
10 Controls .................................................................................................10-1
10-1. Outline of application Control chart................................................................... 10-1
10-2. Applications for indoor remote controller .......................................................... 10-2
10-3. Application control for central remote controller ............................................... 10-3
10-4. Application controls by optional P.C. board of outdoor unit ............................. 10-6
10-5. Application control of optional devices connectable to indoor units................ 10-14
10-6. Application control for network........................................................................ 10-17
10-7. Dimensionel drawing ...................................................................................... 10-22
11 Technical Specifications ........................................................................11-1
11-1. Outdoor unit ...................................................................................................... 11-1
11-1-1. Specifications ........................................................................................................ 11-1
11-1-2. Dimensional drawing ........................................................................................... 11-16
11-1-3. Wiring diagram .................................................................................................... 11-23

i
Contents

11-1-4. Connecting diagram ............................................................................................ 11-26


11-1-5. Center of gravity ................................................................................................. 11-29
11-1-6. Branch header / branch joint .............................................................................. 11-30
11-1-7. Part Load performance....................................................................................... 11-33
11-1-8. Sound Pressure level data (NC CURVE) ............................................................ 11-70
11-2. Indoor unit....................................................................................................... 11-77
11-2-1. 4-way Air Discharge Cassette Type .................................................................... 11-77
11-2-2. Compact 4-way Cassette(600x600) Type ........................................................... 11-95
11-2-3. 2-way Air Discharge Cassette Type .................................................................. 11-107
11-2-4. 1-way Air Discharge Cassette Type .................................................................. 11-121
11-2-5. Concealed Duct Type........................................................................................ 11-135
11-2-6. Concealed Duct High Static Pressure Type ...................................................... 11-149
11-2-7. Slim Duct Type .................................................................................................. 11-163
11-2-8. Ceiling Type ...................................................................................................... 11-185
11-2-9. High-wall(3 series) Type.................................................................................... 11-195
11-2-10.Floor Standing Concealed Type........................................................................ 11-205
11-2-11.Floor Standing Cabinet Type............................................................................. 11-213
11-2-12.Floor Standing Type .......................................................................................... 11-223
11-2-13.Fresh Air Intake Indoor Unit Type ..................................................................... 11-233
11-2-14.Console Type .................................................................................................... 11-249
11-2-15.Air to Air Heat exchanger with DX-coil Type ..................................................... 11-263
Appendix Previous indoor unit ....................................................................... A-1
A-1. Compact 4-way Cassette(600x600) Type ...............................................................A-1
A-2. 1-way Air Discharge Cassette Type ......................................................................A-13
A-3. Concealed Duct Type............................................................................................A-27
A-4. Concealed Duct High Static Pressure Type ..........................................................A-41
A-5. Slim Duct Type ......................................................................................................A-55
A-6. Ceiling Type ..........................................................................................................A-77
A-7. High-wall(1 series) Type........................................................................................A-87
A-8. Floor Standing Concealed Type............................................................................A-97
A-9. Floor Standing Cabinet Type...............................................................................A-105
A-10. Floor Standing Type ............................................................................................A-115

ii
1
SMMS-i Data book

Foreword

The engineering data book details all relevant data, charts


and drawings to enable you to get the best performance
from the Toshiba Super Modular Multi System i for the
various applications.

The information is aimed to assist you by providing greater


detail of the system and the wider applications that the
system will cover.

1 -1
2
SMMS-i Data book

Safety caution
• Before use, read carefully through the “Safety caution” section to ensure correct operation.
• The important contents concerned to the safety are described in the “Safety Cautions”.
Be sure to keep them. For Indications and their meanings, see the following description.

Warning Indications on the Air Conditioner Unit


Warning indication Description

WARNING WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote ELECTRICAL SHOCK HAZARD
electric power supplies Disconnect all remote electric power supplies before servicing.

WARNING
WARNING

Moving parts. Moving parts.


Do not operate unit with
Do not operate unit with grille removed.
grille removed.
Stop the unit before the servicing.

CAUTION CAUTION
High temperature parts.
You might get burned when High temperature parts.
removing this panel. You might get burned when removing this panel.

CAUTION CAUTION
Do not touch the aluminum
fins of the unit. Do not touch the aluminium fins of the unit.
Doing so may result in injury. Doing so may result in injury.

CAUTION
CAUTION

BURST HAZARD BURST HAZARD


Open the service valves
Open the service valves before the operation, otherwise there might be the
before the operation,
burst.

CAUTION CAUTION
Do not climb onto the fan
guard. Do not climb onto the fan guard.
Doing so may result in Doing so may result in injury.

2 -1
2 Safety caution

Explanation of indications

WARNING
Indicates possibilities that a death or serious injury of personnel is caused by an incorrect handling.

CAUTION
Indicates contents that an injury (*1) or property damage (*2) only may be caused when an incorrect work has been executed.

*1: “Injury” means a hurt, a burn, or an electric shock which does not require hospitalization or a long-term going to the hospital.
*2: “Property damage means an enlarged damage concerned to property, or breakage of materials.

• After installation work has finished, check there is no trouble by a test operation, and explain using method and
maintenance method to the customers based on the Owner’s Manual.
Please ask the customers to keep this Installation Manual together with the Owner’s Manual.

WARNING
Ask a shop or a professional dealer to install the air conditioner.
If you will install by yourself, a fire, an electric shock, or water leak is caused.
Take measures so that the refrigerant does not exceed the limit concentration even if it leaks when installing the air conditioner
in a small room.
For the measures not to exceed the limit of concentration, contact the dealer. If the refrigerant leaks and it exceeds the limit of
concentration, an accident of oxygen shortage is caused.
Install the air conditioner at a place which is satisfactorily bearable to weight.
If strength is insufficient, the unit may fall down resulting in human injury.
Perform a specified installation work against a strong wind such as typhoon or earthquake.
If the air conditioner is imperfectly installed, an accident by falling or dropping may be caused.
If refrigerant gas leaks during installation work, ventilate the room.
If the leaked refrigerant gas approaches to fire, noxious gas may generate.
After installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks in the room, and approaches to fire such as fan heater, stove or kitchen range, generation of noxious gas may be
caused.
Never recover refrigerant in the outdoor unit.
Be sure to use a refrigerant recovery device to recover refrigerant in reinstallation or repair work.
Recovery of refrigerant in the outdoor unit is unavailable; otherwise a serious accident such as crack or human injury is caused.
A person qualified for the electric work should deal with the electric construction conforming to the regulations of the local
electric company and the Installation Manual. Be sure to use the exclusive circuit.
If there is capacity shortage of the power supply circuit or incomplete installation, a fire or an electric shock is caused.
For cabling, use the specified cables and connect them securely so that external force of cable does not transmit to the
terminal connecting section.
If connection or fixing is incomplete, a fire, etc. may be caused.
Be sure to connect earth wire.
Do not connect earth wire to gas pipe, water pipe, lightning rod, nor earth wire of telephone.
If grounding is incomplete, an electric shock is caused.

CAUTION
Do not install the air conditioner at a place where combustible gas may leak.
If gas leaks and is collected at surrounding the unit, the production of fire may be caused.
Be sure to attach an earth leakage breaker; otherwise an electric shock may be caused.
Using a torque wrench, tighten the flare nut in the specified method.
If the flare nut is exceedingly tightened, the flare nut is broken and a refrigerant leakage may be caused after a long time has passed.

2 -2
2 Safety caution

WARNINGS ON REFRIGERANT LEAKAGE


Check of Concentration Limit Important
The room in which the air conditioner is to be NOTE 2:
installed requires a design that in the event of The standards for minimum room volume are as follows.
refrigerant gas leaking out, its concentration will not
exceed a set limit. (1) No partition (shaded portion)
The refrigerant R410A which is used in the air
conditioner is safe, without the toxicity or combustibility
of ammonia, and is not restricted by laws to be imposed
which protect the ozone layer. However, since it
contains more than air, it poses the risk of suffocation if
(2) When there is an effective opening with the adjacent
its concentration should rise excessively.
room for ventilation of leaking refrigerant gas
Suffocation from leakage of R410A is almost
(opening without a door, or an opening 0.15% or
nonexistent. With the recent increase in the number of
larger than the respective floor spaces at the top or
high concentration buildings, however, the installation of
bottom of the door).
multi air conditioner systems is on the increase because
Outdoor unit
of the need for effective use of floor space, individual
control, energy conservation by curtailing heat and Refrigerant piping
carrying power etc.
Indoor unit
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared
with conventional individual air conditioners. If a single
unit of the multi conditioner system is to be (3) If an indoor unit is installed in each partitioned room
installed in a small room, select a suitable model and and the refrigerant tubing is interconnected, the
installation procedure so that if the refrigerant smallest room of course becomes the object. But
accidentally leaks out, its concentration does not reach when a mechanical ventilation is installed
the limit (and in the event of an emergency, measures interlocked with a gas leakage detector in the
can be made before injury can occur). smallest room where the density limit is exceeded,
In a room where the concentration may exceed the limit, the volume of the next smallest room becomes the
create an opening with adjacent rooms, or install object.
mechanical ventilation combined with a gas leak Refrigerant piping
detection device.
The concentration is as given below.
Total amount of refrigerant (kg) Outdoor unit
Min. volume of the indoor unit installed room (m3) Very
≤ Concentration limit (kg/m3) small
room Indoor unit

The concentration limit of R410A which is used in multi Small Medium


room room Large room
air conditioners is 0.3kg/m3.
Mechanical ventilation device - Gas leak detector
NOTE 1:
If there are 2 or more refrigerating systems in a single NOTE 3:
refrigerating device, the amounts of refrigerant should The minimum indoor floor area compared with the
be as charged in each independent device. amount of refrigerant is roughly as follows: (When the
Outdoor unit ceiling is 2.7m high)
e.g., charged
amount (10kg) e.g.,
40 Range below the
charged amount (15kg)
density limit of 0.3
m² 35 kg/m3
30 (countermeasures
not needed)
25
Min. indoor floor area

20
Range above the
Room A Room B Room C Room D Room E Room F 15 density limit of 0.3
Indoor unit 10 kg/m3
(countermeasures
For the amount of charge in this example: 5 needed)
The possible amount of leaked refrigerant gas in
rooms A, B and C is 10kg. 0
10 20 30
The possible amount of leaked refrigerant gas in Total amount of refrigerant kg
rooms D, E and F is 15kg.

2 -3
3
SMMS-i Data book

Introduction

The next-generation ‘ -quality’ trio


Dedication to innovation and advanced intelligence fosters the imaginative
creativity with which we deliver total value in air conditioning systems.

innovation, intelligence and imagination


Industry leading energy savings
Energy-efficient performance for greater eco-consciousness

Adopting the highly efficient new DC twin-rotary compressors and advanced vector-controlled inverters realizes
a COP of 6.41 (under 50% partial load). Greater operating performance is now possible when operating under
a constant load.
2 3 4 5 6 7

6.41
4.52
COP

5.50
3.52

6.26
4.15
EER

5.60
3.28

Industry leading pipe length for greater flexibility


Layout flexibility with few design limitations

System layouts can use a maximum equivalent distance of up to 235 metres. This makes it much easier to
design for floors with many small rooms, or for tenants who often rearrange their floor layouts.

d’s
Wortl in *
bes lass
its c

Farthest equivalent length 235m *

Main piping length

120 m

1st branching piping length 90 m


* As of December 2009 (according to independent Toshiba testing)

3 -1
3 Introduction

Greater support for height differences between indoor units


Toshiba SMMS-i leads the industry with support for height differences of up to 40 metres between indoor units
on a single system. For instance, in an 11-story building, this is enough height to fully cover the entire floor as
well as the elevator halls.

’s
Wortldin *1
bes lass
its c

Height between Single


indoor units system

*Calculated at 3.5 meters per floor *As of December 2009 (according to independent Toshiba testing)

Industry leading installation flexibility


The outdoor units improve performance to achieve greater space efficiency that defies their compact module
size to deliver greater freedom in layout design. This minimizes weight-related restrictions and allows for
quicker installation.

(16HP) (32HP) 40% reduction


8HP 8HP 8HP 8HP 8HP 8HP
SMMS

2,000 4,020

16HP 16HP 16HP


SMMS-i

A 16HP system installation now


occupies only 2/3 the footprint
1,210 2,440 and weight of two units
previously required.

Infinity variable control


Ultra-precise 0.1 Hz control over compressor rotation speed

Infinity variable control adjusts compressor rotation speed in near-seamless 0.1 Hz steps. Responding precisely
to the capacity needs of the moment, this fine control minimizes energy loss when changing frequencies, and
also creates a comfortable environment subject to minimal temperature variations.

d’s
SMMS SMMS-i Wortl in *
bes lass
its c

0.1Hz
0.6Hz
Compressor Hz

Compressor Hz

y y
Capacit Capacit

*As of December 2009 (according to independent Toshiba testing)

3 -2
3 Introduction

Optimal refrigerant control


– When a multiple number of indoor units are connected, an insufficient or excess amount of refrigerant may be
supplied to indoor units depending on the difference in length of the connection pipe from the outdoor unit.
– This is caused by pressure loss and heat leaks as the refrigerant travels through the pipes, resulting in
incorrect amounts of refrigerant being supplied to the indoor units.
– Optimal refrigerant flow control featuring intelligent control over the refrigerant sensors and opening rate of
individual pulse motor valves realizes stable indoor temperatures throughout a building with height
differences of up to 40m between indoor units.
Outdoor unit

Pulse motor valve

D
Heat
exchanger
TC2 TCJ TC1
A B C
Indoor unit Refrigerant Refrigerant
sensor (In) sensor (Out)

The surplus represented by


The surplus represented by (B) is diminished (A) is diminished and the
and the deficiency represented by (C) is deficiency represented by
compensated for. (D) is compensated for.
Capacity

Target capacity

(A) (B) (C) (D)

Introducing high-performance outdoor units


with 3 compressors and 3 inverters*1

1New DC twin-rotary compressor


Leading the world with Toshiba’s
own new DC twin-rotary Improved motor
compressor
Newly designed
Three new DC twin-rotary compression path

compressors that feature outstanding More precise


components
capacity under partial load drive the
New DC twin-rotary compressor Twin-rotary
14 and 16HP outdoor unit models, Optimization of discharge port positioning Each motor employs a compact 2 1 (14HP, 16HP)
while two are used by the other and blade thickness reduces compression loss and powerful magnetic rotor (rare
earth magnet) and features
and friction resistance. Increasing the surface
outdoor unit models. These new area of the rotor magnets and the addition of reduced eddy-current loss.

compressors improve both energy noise.


efficiency and comfort levels.

2Fast-calculating vector-controlled inverter


All-inverter control realizes finer
control over operation to match
the load on the system

Toshiba SMMS-i leads the industry in


controlling all 3 compressors with a
dedicated inverter board that taps the Smooth sine curve Circuit board
compressor’s full potential to provide The fast-calculating vector-controlled The vector-controlled inverter quickly
inverter produces a smooth sine curve that converts current into a smooth sine
smoother operation. curve to achieve smoother operation
*1 14 and 16HP models
of the compressor’s DC motor.

3 -3
4
SMMS-i Data book

System overview
4-1. OUTLINE OF TOSHIBA SMMS-i
(Super Modular Multi System-i)

Shortest route design by free branching


The Combination of line and header branching is highly flexible.
Following the shortest design route possible, thereby saving
on installation time and cost. Line/header branching after the
header branching is only available with TOSHIBA SMMS-i.

Line branching
Outdoor unit
Branching joint
8F

Indoor unit

Header branching
Outdoor unit
Branching 7F
header

Indoor unit

Line + Header branching Header


Outdoor unit 2F

Indoor
Branching joint
unit

Line branching after header branching 1F


Outdoor unit
Allowable pipe length:
Branching joint Outdoor 235m equivalent length
Header
unit
TOSHIBA
Only 1st branching
unit and outdoor unit: 70m (*1)

section
Height difference between

Indoor unit
unit and indoor unit:
Height difference

Header branching after header branching


between indoor

Outdoor unit
indoor

40m

Header
TOSHIBA
Only From 1st branching to the furthest
indoor unit: 90m (*2)
*1: If the height different between(H2) indoor
Header units exceeds 3m, set below 50m.
*2 : If the height different between(H1) indoor
and outdoor units exceeds 3m, set below
Indoor unit 65m.

4 -1
4 System overview

4-2. SUMMARY OF SYSTEM EQUIPMENTS


Equipment
Outdoor units
* SMMS outdoor unit
Inverter unit
Corresponding HP Appearance
5HP* 6HP* 8HP 10HP 12HP 14HP 16HP
Heat
MMY- MAP0501HT8 MAP0601HT8 MAP0804HT8 MAP1004HT8 MAP1204HT8 MAP1404HT8 MAP1604HT8
Model pump
name Cooling
MMY- MAP0501T8 MAP0601T8 MAP0804T8 MAP1004T8 MAP1204T8 MAP1404T8 MAP1604T8
only
Cooling capacity (kW) 14.0 16.0 22.4 28.0 33.5 40.0 45.0
Heating capacity (kW) 16.0 18.0 25.0 31.5 37.5 45.0 50.0
No. of connectable
8 10 13 16 20 23 27
indoor units

Combination of outdoor units


Standard model
Corresponding HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP 32HP
Combined MMY- AP1814HT8 AP2014HT8 AP2214HT8 AP2414HT8 AP2614HT8 AP2814HT8 AP3014HT8 AP3214HT8
Model MMY- AP1814T8 AP2014T8 AP2214T8 AP2414T8 AP2614T8 AP2814T8 AP3014T8 AP3214T8
Cooling capacity (kW) 50.4 56.0 61.5 68.0 73.0 78.5 85.0 90.0
Heating capacity (kW) 56.5 63.0 69.0 76.5 81.5 88.0 95.0 100.0
10HP 10HP 12HP 12HP 16HP 16HP 16HP 16HP
8HP 10HP 10HP 12HP 10HP 12HP 14HP 16HP
Combined outdoor units
– – – – – – – –
– – – – – – – –
No. of connectable
30 33 37 40 43 47 48 48
indoor units
Corresponding HP 34HP 36HP 38HP 40HP 42HP 44HP 46HP 48HP
Combined MMY- AP3414HT8 AP3614HT8 AP3814HT8 AP4014HT8 AP4214HT8 AP4414HT8 AP4614HT8 AP4814HT8
Model MMY- AP3414T8 AP3614HT8 AP3814T8 AP4014T8 AP4214T8 AP4414T8 AP4614T8 AP4814T8
Cooling capacity (kW) 96.0 101.0 106.5 112.0 118.0 123.5 130.0 135.0
Heating capacity (kW) 108.0 113.0 119.5 127.0 132.0 138.0 145.0 150.0
12HP 12HP 16HP 16HP 16HP 16HP 16HP 16HP
12HP 12HP 12HP 12HP 14HP 16HP 16HP 16HP
Combined outdoor units
10HP 12HP 10HP 12HP 12HP 12HP 14HP 16HP
– – – – – – – –
No. of connectable
48 48 48 48 48 48 48 48
indoor units
High efficiency model
Corresponding HP 16HP 24HP 26HP 28HP 30HP 32HP 34HP 36HP
Combined MMY- AP1624HT8 AP2424HT8 AP2624HT8 AP2824HT8 AP3024HT8 AP3224HT8 AP3424HT8 AP3624HT8
Model MMY- AP1624T8 AP2424T8 AP2624T8 AP2824T8 AP3024T8 AP3224T8 AP3424T8 AP3624T8
Cooling capacity (kW) 45.0 68.0 73.0 78.5 85.0 90.0 96.0 101.0
Heating capacity (kW) 50.0 76.5 81.5 88.0 95.0 100.0 108.0 113.0
8HP 8HP 10HP 10HP 10HP 8HP 10HP 10HP
8HP 8HP 8HP 10HP 10HP 8HP 8HP 10HP
Combined outdoor units
– 8HP 8HP 8HP 10HP 8HP 8HP 8HP
– – – – – 8HP 8HP 8HP
No. of connectable
27 40 43 47 48 48 48 48
indoor units
Corresponding HP 38HP 40HP 42HP 44HP 46HP 48HP
Combined MMY- AP3824HT8 AP4024HT8 AP4224HT8 AP4424HT8 AP4624HT8 AP4824HT8
Model MMY- AP3824T8 AP4024T8 AP4224T8 AP4424T8 AP4624T8 AP4824T8
Cooling capacity (kW) 106.5 112.0 118.0 123.5 130.0 135.0
Heating capacity (kW) 119.5 127.0 132.0 138.0 145.0 150.0
10HP 10HP 12HP 12HP 12HP 12HP
10HP 10HP 10HP 12HP 12HP 12HP
Combined outdoor units
10HP 10HP 10HP 10HP 12HP 12HP
8HP 10HP 10HP 10HP 10HP 12HP
No. of connectable
48 48 48 48 48 48
indoor units

Branching joints and headers


Model name Usage (Classification according to capacity code (*1)) Appearance
RBM-BY55E Indoor unit: Total below 6.4
RBM-BY105E Indoor unit: Total 6.4 or more and below 14.2 (*2)
Y-shape branching joint (*3)
RBM-BY205E Indoor unit: Total 14.2 or more and below 25.2 (*2)
RBM-BY305E Indoor unit: Total 25.2 or more (*2)
4-branching header RBM-HY1043E Indoor unit: Total below 14.2
Max.4 branches
(*3)(*4)(*5) RBM-HY2043E Indoor unit: Total 14.2 or more and below 25.2
8-branching header RBM-HY1083E Indoor unit: Total below 14.2
Max.8 branches
(*3)(*4)(*5) RBM-HY2083E Indoor unit: Total 14.2 or more and below 25.2
Capacity code Piping at gas side (Y-shape) Piping at liquid side (T-shape) Balance pipe (T-shape)
Branching joint for connection ø19.1 ø9.5
RBM-BT14E ø28.6
of outdoor units Total below 26 ø31.8 ø25.4
(1set of 1type of Y-shape joint ø19.1 ø19.1 ø9.5 ø9.5
pipe and 2types of T-joint pipes ø22.2 ø9.5
ø38.1
as described right.) RBM-BT24E Total 26 or more ø38.1 ø28.6
ø22.2 ø22.2 ø9.5 ø9.5
*1 “Capacity code” can be obtained by the lists in chapter 4-3 and 4-4.(Capacity code is not actual capacity.)
*2 If total capacity code value of indoor unit exceeds that of outdoor unit, apply capacity code of outdoor unit.
*3 In 1st branching, select according to the capacity code of the outdoor unit.
*4 Max capacity code of 6.0 in total is connectable to one line after branching header.
*5 When capacity code of outdoor units is 12 or more and using of 1st branching , use RBM-HY-2043E or RBM-HY-2083E. And if the code is 26 or more, it is not
used for 1st branching.

4 -2
4 System overview

4-3. List of product and combined model name

Heat Pump model


HP No. of
Model name Inverter 5HP Used Inverter 6HP Used Inverter 8HP Used Inverter 10HP Used Inverter 12HP Used Inverter 14HP Used Inverter 16HP Used
(Capacity combined
MMY- MMY- Qty MMY- Qty MMY- Qty MMY- Qty MMY- Qty MMY- Qty MMY- Qty
code) units
Standard model
5HP(5)* MAP0501HT8 1 MAP0501HT8 1
6HP(6)* MAP0601HT8 1 MAP0601HT8 1
8HP(8) MAP0804HT8 1 MAP0804HT8 1
10HP(10) MAP1004HT8 1 MAP1004HT8 1
12HP(12) MAP1204HT8 1 MAP1204HT8 1
14HP(14) MAP1404HT8 1 MAP1404HT8 1
16HP(16) MAP1604HT8 1 MAP1604HT8 1
18HP(18) AP1814HT8 2 MAP0804HT8 1 MAP1004HT8 1
20HP(20) AP2014HT8 2 MAP1004HT8 2
22HP(22) AP2214HT8 2 MAP1004HT8 1 MAP1204HT8 1
24HP(24) AP2414HT8 2 MAP1204HT8 2
26HP(26) AP2614HT8 2 MAP1004HT8 1 MAP1604HT8 1
28HP(28) AP2814HT8 2 MAP1204HT8 1 MAP1604HT8 1
30HP(30) AP3014HT8 2 MAP1404HT8 1 MAP1604HT8 1
32HP(32) AP3214HT8 2 MAP1604HT8 2
34HP(34) AP3414HT8 3 MAP1004HT8 1 MAP1204HT8 2
36HP(36) AP3614HT8 3 MAP1204HT8 3
38HP(38) AP3814HT8 3 MAP1004HT8 1 MAP1204HT8 1 MAP1604HT8 1
40HP(40) AP4014HT8 3 MAP1204HT8 2 MAP1604HT8 1
42HP(42) AP4214HT8 3 MAP1204HT8 1 MAP1404HT8 1 MAP1604HT8 1
44HP(44) AP4414HT8 3 MAP1204HT8 1 MAP1604HT8 2
46HP(46) AP4614HT8 3 MAP1404HT8 1 MAP1604HT8 2
48HP(48) AP4814HT8 3 MAP1604HT8 3
High efficiency model
16HP(16) AP1624HT8 2 MAP0804HT8 2
24HP(24) AP2424HT8 3 MAP0804HT8 3
26HP(26) AP2624HT8 3 MAP0804HT8 2 MAP1004HT8 1
28HP(28) AP2824HT8 3 MAP0804HT8 1 MAP1004HT8 2
30HP(30) AP3024HT8 3 MAP1004HT8 3
32HP(32) AP3224HT8 4 MAP0804HT8 4
34HP(34) AP3424HT8 4 MAP0804HT8 3 MAP1004HT8 1
36HP(36) AP3624HT8 4 MAP0804HT8 2 MAP1004HT8 2
38HP(38) AP3824HT8 4 MAP0804HT8 1 MAP1004HT8 3
40HP(40) AP4024HT8 4 MAP1004HT8 4
42HP(42) AP4224HT8 4 MAP1004HT8 3 MAP1204HT8 1
44HP(44) AP4424HT8 4 MAP1004HT8 2 MAP1204HT8 2
46HP(46) AP4624HT8 4 MAP1004HT8 1 MAP1204HT8 3
48HP(48) AP4824HT8 4 MAP1204HT8 4
* : SMMS outdoor unit

1. Allocation standard of model name


MMY_ M AP H T 8

Power supply specifications, 3Ø 380-400-415V, 50Hz ....... 8


T: Capacity variable unit
H: Heat pump
Development series No.
0 : Single model, 1: Standard model, 2 : High efficiency model
Capacity rank HP
Refrigerant R410A
M: Single module unit, No mark: Combined Model name
Modular Multi

2. Rang of combined capacity


No. of combined units: 1 to 4 units
Capacity of combined units: 16 HP(16type) to 48 HP(48type)

3. Rated conditions
Cooling: Indoor air temperature 27ºC DB/19ºC WB, Outdoor air temperature 35ºC DB
Heating: Indoor air temperature 20ºC DB, Outdoor air temperature 7ºC DB/6ºC WB

4 -3
4 System overview

Cooling Only model


No. of
HP(Capacity Model name Inverter 5HP Used Inverter 6HP Used Inverter 8HP Used Inverter 10HP Used Inverter 12HP Used Inverter 14HP Used Inverter 16HP Used
combined
code) MMY- MMY- Qty MMY- Qty MMY- Qty MMY- Qty MMY- Qty MMY- Qty MMY- Qty
units
Standard model
5HP(5)* MAP0501T8 1 MAP0501T8 1
6HP(6)* MAP0601T8 1 MAP0601T8 1
8HP(8) MAP0804T8 1 MAP0804T8 1
10HP(10) MAP1004T8 1 MAP1004T8 1
12HP(12) MAP1204T8 1 MAP1204T8 1
14HP(14) MAP1404T8 1 MAP1404T8 1
16HP(16) MAP1604T8 1 MAP1604T8 1
18HP(18) AP1814T8 2 MAP0804T8 1 MAP1004T8 1
20HP(20) AP2014T8 2 MAP1004T8 2
22HP(22) AP2214T8 2 MAP1004T8 1 MAP1204T8 1
24HP(24) AP2414T8 2 MAP1204T8 2
26HP(26) AP2614T8 2 MAP1004T8 1 MAP1604T8 1
28HP(28) AP2814T8 2 MAP1204T8 1 MAP1604T8 1
30HP(30) AP3014T8 2 MAP1404T8 1 MAP1604T8 1
32HP(32) AP3214T8 2 MAP1604T8 2
34HP(34) AP3414T8 3 MAP1004T8 1 MAP1204T8 2
36HP(36) AP3614T8 3 MAP1204T8 3
38HP(38) AP3814T8 3 MAP1004T8 1 MAP1204T8 1 MAP1604T8 1
40HP(40) AP4014T8 3 MAP1204T8 2 MAP1604T8 1
42HP(42) AP4214T8 3 MAP1204T8 1 MAP1404T8 1 MAP1604T8 1
44HP(44) AP4414T8 3 MAP1204T8 1 MAP1604T8 2
46HP(46) AP4614T8 3 MAP1404T8 1 MAP1604T8 2
48HP(48) AP4814T8 3 MAP1604T8 3
High efficiency model
16HP(16) AP1624T8 2 MAP0804T8 2
24HP(24) AP2424T8 3 MAP0804T8 3
26HP(26) AP2624T8 3 MAP0804T8 2 MAP1004T8 1
28HP(28) AP2824T8 3 MAP0804T8 1 MAP1004T8 2
30HP(30) AP3024T8 3 MAP1004T8 3
32HP(32) AP3224T8 4 MAP0804T8 4
34HP(34) AP3424T8 4 MAP0804T8 3 MAP1004T8 1
36HP(36) AP3624T8 4 MAP0804T8 2 MAP1004T8 2
38HP(38) AP3824T8 4 MAP0804T8 1 MAP1004T8 3
40HP(40) AP4024T8 4 MAP1004T8 4
42HP(42) AP4224T8 4 MAP1004T8 3 MAP1204T8 1
44HP(44) AP4424T8 4 MAP1004T8 2 MAP1204T8 2
46HP(46) AP4624T8 4 MAP1004T8 1 MAP1204T8 3
48HP(48) AP4824T8 4 MAP1204T8 4
* : SMMS outdoor unit

1. Allocation standard of model name


MMY_ M AP T 8

Power supply specifications, 3Ø 380-400-415V, 50Hz ....... 8


T: Capacity variable unit
Development series No.
0 : Single model, 1: Standard model, 2 : High efficiency model
Capacity rank HP
Refrigerant R410A
M: Single module unit, No mark: Combined Model name
Modular Multi

2. Rang of combined capacity


No. of combined units: 1 to 4 units
Capacity of combined units: 16 HP(16type) to 48 HP(48type)

3. Rated conditions
Cooling: Indoor air temperature 27ºC DB/19ºC WB, Outdoor air temperature 35ºC DB

4 -4
4 System overview

4-4. Indoor unit


Cooling Heating
Type Appearance Model name Capacity rank Capacity code capacity (kW) capacity (kW)
MMU-AP0092H 009 type 1.00 2.8 3.2
MMU-AP0122H 012 type 1.25 3.6 4.0
MMU-AP0152H 015 type 1.70 4.5 5.0
MMU-AP0182H 018 type 2.00 5.6 6.3
4-way Air Discharge MMU-AP0242H 024 type 2.50 7.1 8.0
Cassette Type MMU-AP0272H 027 type 3.00 8.0 9.0
MMU-AP0302H 030 type 3.20 9.0 10.0
MMU-AP0362H 036 type 4.00 11.2 12.5
MMU-AP0482H 048 type 5.00 14.0 16.0
MMU-AP0562H 056 type 6.00 16.0 18.0
MMU-AP0074MH-E 007 type 0.80 2.2 2.5

Compact 4-way MMU-AP0094MH-E 009 type 1.00 2.8 3.2


Cassette (600 × 600) MMU-AP0124MH-E 012 type 1.25 3.6 4.0
Type MMU-AP0154MH-E 015 type 1.70 4.5 5.0
MMU-AP0184MH-E 018 type 2.00 5.6 6.3
MMU-AP0072WH 007 type 0.80 2.2 2.5
MMU-AP0092WH 009 type 1.00 2.8 3.2
MMU-AP0122WH 012 type 1.25 3.6 4.0
MMU-AP0152WH 015 type 1.70 4.5 5.0
MMU-AP0182WH 018 type 2.00 5.6 6.3
2-way Air Discharge
MMU-AP0242WH 024 type 2.50 7.1 8.0
Cassette Type
MMU-AP0272WH 027 type 3.00 8.0 9.0
MMU-AP0302WH 030 type 3.20 9.0 10.0
MMU-AP0362WH 036 type 4.00 11.2 12.5
MMU-AP0482WH 048 type 5.00 14.0 16.0
MMU-AP0562WH 056 type 6.00 16.0 18.0
MMU-AP0074YH-E 007 type 0.80 2.2 2.5
MMU-AP0094YH-E 009 type 1.00 2.8 3.2
1-way Air Discharge MMU-AP0124YH-E 012 type 1.25 3.6 4.0
Cassette Type MMU-AP0154SH-E 015 type 1.70 4.5 5.0
MMU-AP0184SH-E 018 type 2.00 5.6 6.3
MMU-AP0244SH-E 024 type 2.50 7.1 8.0
MMD-AP0074BH-E 007 type 0.80 2.2 2.5
MMD-AP0094BH-E 009 type 1.00 2.8 3.2
MMD-AP0124BH-E 012 type 1.25 3.6 4.0
MMD-AP0154BH-E 015 type 1.70 4.5 5.0
MMD-AP0184BH-E 018 type 2.00 5.6 6.3
Concealed Duct
MMD-AP0244BH-E 024 type 2.50 7.1 8.0
Type
MMD-AP0274BH-E 027 type 3.00 8.0 9.0
MMD-AP0304BH-E 030 type 3.20 9.0 10.0
MMD-AP0364BH-E 036 type 4.00 11.2 12.5
MMD-AP0484BH-E 048 type 5.00 14.0 16.0
MMD-AP0564BH-E 056 type 6.00 16.0 18.0
MMD-AP0184H-E 018 type 2.00 5.6 6.3
MMD-AP0244H-E 024 type 2.50 7.1 8.0

Concealed Duct MMD-AP0274H-E 027 type 3.00 8.0 9.0


High Static MMD-AP0364H-E 036 type 4.00 11.2 10.0
Pressure Type MMD-AP0484H-E 048 type 5.00 14.0 16.0
MMD-AP0724H-E 072 type 8.00 22.4 25.0
MMD-AP0964H-E 096 type 10.00 28.0 31.5
MMD-AP0074SPH-E 007 type 0.80 2.2 2.5
MMD-AP0094SPH-E 009 type 1.00 2.8 3.2
Slim Duct Type MMD-AP0124SPH-E 012 type 1.25 3.6 4.0
MMD-AP0154SPH-E 015 type 1.70 4.5 5.0
MMD-AP0184SPH-E 018 type 2.00 5.6 6.3
MMC-AP0154H-E 015 type 1.70 4.5 5.0
MMC-AP0184H-E 018 type 2.00 5.6 6.3
MMC-AP0244H-E 024 type 2.50 7.1 8.0
Ceiling Type
MMC-AP0274H-E 027 type 3.00 8.0 9.0
MMC-AP0364H-E 036 type 4.00 11.2 12.5
MMC-AP0484H-E 048 type 5.00 14.0 16.0

4 -5
4 System overview

Cooling Heating
Type Appearance Model name Capacity rank Capacity code capacity (kW) capacity (kW)
MMK-AP0073H 007 type 0.80 2.2 2.5
MMK-AP0093H 009 type 1.00 2.8 3.2
High-wall Type MMK-AP0123H 012 type 1.25 3.6 4.0
3 series MMK-AP0153H 015 type 1.70 4.5 5.0
MMK-AP0183H 018 type 2.00 5.6 6.3
MMK-AP0243H 024 type 2.50 7.1 8.0
MML-AP0074BH-E 007 type 0.80 2.2 2.5
MML-AP0094BH-E 009 type 1.00 2.8 3.2
Floor Standing MML-AP0124BH-E 012 type 1.25 3.6 4.0
Concealed Type MML-AP0154BH-E 015 type 1.70 4.5 5.0
MML-AP0184BH-E 018 type 2.00 5.6 6.3
MML-AP0244BH-E 024 type 2.50 7.1 8.0
MML-AP0074H-E 007 type 0.80 2.2 2.5
MML-AP0094H-E 009 type 1.00 2.8 3.2
Floor Standing MML-AP0124H-E 012 type 1.25 3.6 4.0
Cabinet Type MML-AP0154H-E 015 type 1.70 4.5 5.0
MML-AP0184H-E 018 type 2.00 5.6 6.3
MML-AP0244H-E 024 type 2.50 7.1 8.0
MMF-AP0154H-E 015 type 1.70 4.5 5.0
MMF-AP0184H-E 018 type 2.00 5.6 6.3
MMF-AP0244H-E 024 type 2.50 7.1 8.0
Floor Standing Type MMF-AP0274H-E 027 type 3.00 8.0 9.0
MMF-AP0364H-E 036 type 4.00 11.2 10.0
MMF-AP0484H-E 048 type 5.00 14.0 16.0
MMF-AP0564H-E 056 type 6.00 16.0 18.0
MMD-AP0481HFE 048 type 5.00 14.0 8.9
Fresh Air Intake
MMD-AP0721HFE 072 type 8.00 22.4 13.9
Indoor Unit Type
MMD-AP0961HFE 096 type 10.00 28.0 17.4
MML-AP0074NH-E 007 type 0.80 2.2 2.5
MML-AP0094NH-E 009 type 1.00 2.8 3.2
Console Type MML-AP0124NH-E 012 type 1.25 3.6 4.0
MML-AP0154NH-E 015 type 1.70 4.5 5.0
MML-AP0184NH-E 018 type 2.00 5.6 6.3

Air to Air Heat MMD-VN502HEXE 009 type 1.00 4.10(1.30) * 5.53(2.33) *


exchanger with DX-coil MMD-VN802HEXE 015 type 1.70 6.56(2.06) * 8.61(3.61) *
Type MMD-VN1002HEXE 018 type 2.00 8.25(2.32) * 10.92(4.32) *

* : The figures in ( ) indicate the heat reclaimed from the heat recovery ventilator.

4 -6
4 System overview

4-5. Remote controller


Model
Name Appearance Application Function
name
Connected to indoor unit • Start/Stop
• Mode change
• Temperature setting
Wired remote controller

• Change of air flow


• Timer function
RBC-AMT32E

• Filter sign
• Self-diagnosis function
TIMER SET • Control by 2 remote controllers is available.
TIME

FILTER
L
RESET TEST SET CL

Wired remote Wired remote controller


controller (In case of control by 2
remote controllers)

Connected to indoor unit • Start/Stop


• Temperature setting
Simple wired remote controller

• Change of air flow


• Check code display
RBC-AS21E2

Simple remote controller

• Start/Stop
RBC-AX31U(WS)-E
RBC-AX31U(W)-E

• Mode change
• Temperature setting
• Change of air flow
• Timer function
• Control by 2 remote controllers is available.
Wireless remote controller kit

• Check code display


Connected to indoor unit
RBC-AX22CE2

RBC-AX31U(W)-E
RBC-AX31U(WS)-E
(For 4-way Air Discharge Cassette)

RBC-AX22CE2
(For Under Ceiling, 1-way Air Discharge
Cassette SH)
TCB-AX21E2

TCB-AX21E2
(For Compact 4-way Cassette, 2-way Air
Discharge Cassette, 1-way Air Discharge
Cassette YH, Concealed Duct Standard, Slim
Duct, Floor Standing Cabinet, Floor Standing)
Connected to outdoor unit, • Individual control up to 16 indoor units.
indoor unit
• Setting of simultaneous ON/OFF 3 times for
Header Follower each day of the week when combined with
schedule timer.
• Connected to 2 remote controllers is available.
ON-OFF controller

TCB-CC163TLE2

Outdoor unit

ON-OFF
controller

ON-OFF Indoor
controller remote controller

4 -7
4 System overview

Model
Name Appearance Application Function
name
• Individual control up to 64 indoor units.
• Individual control for max. 64 indoor units
divided into 4 zones.
Up to 16 indoor units
for each zone
ALL
ZONE
ZONE • Up to 16 outdoor header units are connectable.
• 4 type central control setting to inhibit individual
GROUP
Connected to outdoor unit,
TCB-SC642TLE2

CODE
No.

indoor unit operation by remote controller can be selected.


1234 UNIT No. TEST

SET DATA
SETTING R.C. No.
Header Follower

GROUP • Setting for one of 1 to 4 zones is available.


SELECT ZONE
• Can be used with other central control devices
(Up to 10 central control devices and BMS I/F in
CL SET one control circuit)
• Two selectable control modes
Central controller mode
Remote controller mode
Outdoor unit
Central remote controller

• Operating with Shedule Timer TCB-EX21TLE.


• Individual control of up to (64 indoor units) x 2
TCC-LINK buses
• Individual control of up to (64 indoor units
Central divided 1 to 64 zone) x 2 TCC-LINK buses (Up
remote controller to 64 indoor units for each zone)
• Up to 16 outdoor header units are connectable
per 1 TCC-LINK bus
• 4 types of central control settings of inhibit
individual operation by remote controller can be
BMS-CM1280TLE

selected.
• Setting for (one of 1 to 64 zones) x 2ch is
available.
• Setting for (one of 1 to 64 groups) x 2ch is
Central available.
remote
controller • Usable and BMS I/F other central control
Indoor devices
remote controller (Up to 10 central control devices in one TCC-
LINK bus).
• Two control mode selectively
(contral controller mode)
(Remote controller mode) by SW01 bit6.
• Operating with Shedule Timer TCB-EX21TLE.
• Return back setting
Schedule timer mode Schedule timer mode
• 6 programmings per day
• Enabling 8 groups to be programmed
Outdoor unit • A maximum of 64 indoor units can be controlled
• A maximum of 100 hours back-up power supply

Indoor unit Weekly timer mode


• 7 types of weekly schedule and 3
programmings per day
• Can set ON/OFF by one-minute interval
TCB-EXS21TLE
Schedule timer

Wekly timer mode


TCC-LINK
Connected to central remote controller or
wired remote controller

Central Schedule
remote controller timer

Wired Schedule
remote controller timer

4 -8
4 System overview

Model
Name Appearance Application Function
name
• Clock display
Remote controller with schedule timer

Connected to indoor unit • Schedule timer:


Possible to program schedule timer (7-day
timer) function
(7-day timer function)

Possible to program 8 functions for each day of


RBC-AMS41E

the week

* The following items can be set in program:


Operation time, Operation start/stop, Operation
mode, Temperature setting, Restriction on
button operation.
Simple remote controller

Display
• Full dot display with back light
• Multilingual language(11 languages)
-EN : English, Italian, Polish, Greece, Russian,
Turkish
Connected to indoor unit -ES : English, Spanish, Portuguese, French,
Dutch, German
Lite-Vision plus Remote Controller

• Indoor unit & outdoor unit temperature


Room A 12:00
• Filter remaining hour, Total operation running
RBC-AMS51E-EN/ES

hour
24 • Name of room
Cool
Mode Fan Speed
Energy Saving
• Schdule timer with Energy save operation
4 pattern per day
• Save ratio : 3 steps of 0%(thermo off) / 50% /
Lite-Vision plus Another wired 75%
remote controller remote controller
as follower
• Return back : Setting range 10 to 120min
(including Lite- Schedule timer
Vision plus) • 8 programs per day
• Off reminder timer
Others
• Easy to use by simple button
• Night operation mode
• Key Lock
Ventilation
• Ventilation srart/stop
• Ventilation mode change
Wired remote controller for Air to Air Heat Exchanger

• Change of ventilation fan speed


Basic function
• Start/Stop
• Mode change
• Temperature setting
• Change of air flow
with DX coil unit

• Timer function
NRC-01HE

• Filter sign

Air to Air Heat Exchanger with


DX-coil unit

Wired remote Wired remote controller


controller NRC-01HE

When all A2A HEXs with DX-coil or group operation


with standard indoor units, use NRC-01HE.

4 -9
5
SMMS-i Data book

Basic system configuration


5-1. Basic systems (examples)
8 HP system Capacity code
• Max. indoor unit : 13 units
• Capacity code of indoor unit : Min. : 4 Total 10.4
Max. : 10.8
No. of total units

13

Outdoor unit Capacity code


over the branch
(0.8 + 0.8 = 1.6)
8HP Indoor unit
designation
10.4 4.8 4.0 3.2 2.4 1.6 Capacity
Code

007 007 007 007 007 007


(0.8) (0.8) (0.8) (0.8) (0.8) (0.8)

5.6 4.8 4.0 3.2 2.4 1.6 0.8

Indoor unit 007 007 007 007 007 007 007


Remote (0.8) (0.8) (0.8) (0.8) (0.8) (0.8) (0.8)
controller

5 -1
5 Basic system configuration

20 HP system Capacity code


• Max. indoor unit : 33 units
• Capacity code of indoor unit : Min. : 10 Total 26.75
Max. : 27
No. of total units

19

Outdoor unit

10HP 10HP

10
26.75 10.25 8.25 6.25 5.0 3.75 2.5

018 018 012 012 012 012 012


(2.0) (2.0) (1.25) (1.25) (1.25) (1.25) (1.25)

16.5 8.25 6.25 5.0 3.75 2.5

018 012 012 012 012 012


(2.0) (1.25) (1.25) (1.25) (1.25) (1.25)

8.25 6.25 5.0 3.75 2.5

Indoor unit 018 012 012 012 012 012


Remote (2.0) (1.25) (1.25) (1.25) (1.25) (1.25)
controller

5 -2
5 Basic system configuration

40 HP system (Standard model) Capacity code


• Max. indoor unit : 48 units
• Capacity code of indoor unit : Min. : 20 Total 53.75
Max. : 54
No. of total units

32

Outdoor unit

16HP 12HP 12HP

40 24 12

53.75 14.0 13.0 12.0 11.0 9.75 8.5 6.5

009 009 009 012 012 018 024 036


(1) (1) (1) (1.25) (1.25) (2.0) (2.5) (4)

39.75 13.25 12.25 11.25 10.25 9.0 7.75 6.5

009 009 009 012 012 012 024 036


(1) (1) (1) (1.25) (1.25) (1.25) (2.5) (4)

26.5 13.25 12.25 11.25 10.25 9.0 7.75 6.5

009 009 009 012 012 012 024 036


(1) (1) (1) (1.25) (1.25) (1.25) (2.5) (4)

13.25 12.25 11.25 10.25 9.0 7.75 6.5

Indoor unit 009 009 009 012 012 012 024 036
Remote (1) (1) (1) (1.25) (1.25) (1.25) (2.5) (4)
controller

5 -3
5 Basic system configuration

48HP systems (High efficiency model) Capacity code


• Max. indoor unit : 48 units
• Capacity code of indoor unit : Min.: 24 Total 61.9
Max.: 64.8
No. of total units

40

Outdoor unit

12HP 12HP 12HP 12HP

48 36 24 12

61.9 16.55 15.75 14.5 13.25 12.25 11.25 9.25 7.25 5.25

007 012 012 009 009 018 018 018 012 036
(0.8) (1.25) (1.25) (1.0) (1.0) (2) (2) (2) (1.25) (4)

45.35 16.3 15.5 14.25 13.25 12.25 11.25 9.25 7.25 5.25

007 012 009 009 009 018 018 018 012 036
(0.8) (1.25) (1.0) (1.0) (1.0) (2.0) (2.0) (2.0) (1.25) (4)

29.05 14.3 13.5 12.25 11.25 10.25 9.25 7.25 5.25 3.25

007 012 009 009 009 018 018 018 012 018
(0.8) (1.25) (1.0) (1.0) (1.0) (2.0) (2.0) (2.0) (1.25) (2.0)

14.75 13.5 12.25 11.25 10.25 9.25 7.25 5.25 3.25

Indoor unit 012 012 009 009 009 018 018 018 012 018

Remote (1.25) (1.25) (1.0) (1.0) (1.0) (2.0) (2.0) (2.0) (1.25) (2.0)
controller

5 -4
5 Basic system configuration

5-2. Fresh Air Intake Indoor Unit Type


34 HP system Capacity code
Connecting limitation
• The total capacity of the fresh air intake units and the indoor units is restricted to 80 Total 34
to 100% against the capacity of the outdoor units.
• Up to two fresh air intake units can be connected on one line of the multi system. No. of total units
• The allowable total capacity of fresh air intake units shall be 30% or less against
8
the total capacity of the indoor units (including the fresh air intake units).
• The fresh air intake units only cannot connected.

Outdoor unit 12HP 12HP 10HP

34
24 20 16 12 8

036 036 036 036 036 036 Indoor unit


(4) (4) (4) (4) (4) (4)

Remote
controller
10

024 024 Fresh Air Intake Indoor unit


(5) (5)
Remote
controller

5 -5
6
SMMS-i Data book

Equipment selection procedure


6-1. Selection flow chart
1 Determination of indoor air-conditioning load at each room.

2 Preliminary selection of indoor units in the standard capacity no less


than air-conditioning load at each room.

3 Calculate corrected capacity A of each indoor unit by correcting of


indoor temperature for the standard capacity of each indoor unit.(Refer
to Chart [1])

4 Preliminary selection of outdoor unit in the standard capacity no less


than total values of corrected capacity A in indoor units. At the same time,
check both connectable indoor units number and the outdoor unit
diversity(Connected ratio of indoor units to outdoor units) for the 2' Increase of indoor
specifications. unit capacity at object
room against
air-conditioning load
5 Calculate corrected capacity B of each indoor unit by following 2 steps.
Step1:Find the correction value of "Connecting pipe length and lift" by
both the longest length and the largest height with selected piping
condition at 4 or 4'.(Refer to Chatrt [3])
Step2:Calculate capacity B by multiplying the value of step1 by corrected
capacity A.

6 Corrected capacity B of indoor NG


unit >= air-conditioning load (for All
rooms)
YES

OK

7 Find correction values of below items for the standard capacity of


outdoor unit selected at 4 or 4'. 5' <Only cooling>
Then determination of total corrected capacity of the selected outdoor unit The correction characteristic
by all multiplying. NO of "connecting pipe length and
-Correction of indoor temperature condition(Refer to Chart [1]) lift"(Graph [3]) between
-Correction of outdoor temperature condition(Refer to Chart [2]) increased outdoor unit at 4'
-Correction of connecting pipe length and lift between indoor and outdoor
and preliminary selected
units by both the longest length and the largest height (Refer to Chart [3])
outdoor unit at 4 is different.
-Correction of outdoor unit diversity in only over 100%(Refer to Chart [4])
(The both graphs are
-Correction of frost condition on outdoor heat exchanger when in heating
different.)
(Refer to Chart [5])

8 Calculate corrected capacity C of each indoor unit by multiplying the


total corrected capacity of outdoor unit at 7by proportional division of
each indoor unit standard capacity for total standard capacity of all indoor 5' Increase of outdoor unit capacity.
units. At the same time, check both
connectable indoor units number
and the outdoor unit diversity

9 Corrected capacity C of indoor NG


unit >= air-conditioning load (for All
rooms)

OK

end

6 -1
6 Equipment selection procedure

6-2. Operational temperature range


Cooling Heating
45 20

40

Outdoor air wet bulb temp. (°C)


Outdoor air dry bulb temp. (°C)

15
35

30 10

down operation
25

Range for pull


Continuously
5
operable
20

Range for warming


range Continuously
0 operable

up operation
15 range

10 -5

5 -10
0
-15
-5

-10 -20
10 15 20 25 28 30 5 10 15 20 25 30
Indoor air wet bulb temp. (°C) Indoor air dry bulb temp. (°C)

The unit will operate down to an outdoor


temperature of -20°C, however
considerable performance decrease will
be expected below -15°C.
Therefore please consider installation
location/surroundings and system design
when expected to operate between -15°C
and -20°C.

6 -2
6 Equipment selection procedure

6-3. Combination conditions for indoor unit and outdoor unit


6-3-1.For indoor unit, the capacity code is decided for each capacity rank.
Capacity rank type 007 009 012 015 018 024 027 030 036 048 056 072 096
Capacity code 0.8 1 1.25 1.7 2 2.5 3 3.2 4 5 6 8 10

NOTE:
Capacity rank: Correspondence to Btu/h. Capacity code: Correspondence to Horsepower.
6-3-2.For outdoor unit, maximum No. of connectable indoor units and total capacity code of indoor units are decided.
Total capacity code of
Outdoor unit (Heat pump) Outdoor unit (Cooling only) Capacity code of outdoor unit Max. No. of indoor units
indoor units
Standard model
MMY-MAP0501HT8* MMY-MAP0501T8* 5 8 2.5 to 6.75
MMY-MAP0601HT8* MMY-MAP0601T8* 6 10 3 to 8.1
MMY-MAP0804HT8 MMY-MAP0804T8 8 13 4 to 10.8
MMY-MAP1004HT8 MMY-MAP1004T8 10 16 5 to 13.5
MMY-MAP1204HT8 MMY-MAP1204T8 12 20 6 to 16.2
MMY-MAP1404HT8 MMY-MAP1404T8 14 23 7 to 18.9
MMY-MAP1604HT8 MMY-MAP1604T8 16 27 8 to 21.6
MMY-AP1814HT8 MMY-AP1814T8 18 30 9 to 24.3
MMY-AP2014HT8 MMY-AP2014T8 20 33 10 to 27
MMY-AP2214HT8 MMY-AP2214T8 22 37 11 to 29.7
MMY-AP2414HT8 MMY-AP2414T8 24 40 12 to 32.4
MMY-AP2614HT8 MMY-AP2614T8 26 43 13 to 35.1
MMY-AP2814HT8 MMY-AP2814T8 28 47 14 to 37.8
MMY-AP3014HT8 MMY-AP3014T8 30 48 15 to 40.5
MMY-AP3214HT8 MMY-AP3214T8 32 48 16 to 43.2
MMY-AP3414HT8 MMY-AP3414T8 34 48 17 to 45.9
MMY-AP3614HT8 MMY-AP3614T8 36 48 18 to 48.6
MMY-AP3814HT8 MMY-AP3814T8 38 48 19 to 51.3
MMY-AP4014HT8 MMY-AP4014T8 40 48 20 to 54
MMY-AP4214HT8 MMY-AP4214T8 42 48 21 to 56.7
MMY-AP4414HT8 MMY-AP4414T8 44 48 22 to 59.4
MMY-AP4614HT8 MMY-AP4614T8 46 48 23 to 62.1
MMY-AP4814HT8 MMY-AP4814T8 48 48 24 to 64.8
High efficiency model
MMY-AP1624HT8 MMY-AP1624T8 16 27 8 to 21.6
MMY-AP2424HT8 MMY-AP2424T8 24 40 12 to 32.4
MMY-AP2624HT8 MMY-AP2624T8 26 43 13 to 35.1
MMY-AP2824HT8 MMY-AP2824T8 28 47 14 to 37.8
MMY-AP3024HT8 MMY-AP3024T8 30 48 15 to 40.5
MMY-AP3224HT8 MMY-AP3224T8 32 48 16 to 43.2
MMY-AP3424HT8 MMY-AP3424T8 34 48 17 to 45.9
MMY-AP3624HT8 MMY-AP3624T8 36 48 18 to 48.6
MMY-AP3824HT8 MMY-AP3824T8 38 48 19 to 51.3
MMY-AP4024HT8 MMY-AP4024T8 40 48 20 to 54
MMY-AP4224HT8 MMY-AP4224T8 42 48 21 to 56.7
MMY-AP4424HT8 MMY-AP4424T8 44 48 22 to 59.4
MMY-AP4624HT8 MMY-AP4624T8 46 48 23 to 62.1
MMY-AP4824HT8 MMY-AP4824T8 48 48 24 to 64.8

* : SMMS 50 to 135% of outdoor unit capacity

6 -3
6 Equipment selection procedure

6-4. Cooling/heating capacity characteristics


6-4-1.Correction charts for cooling capacity calculation
[1] Indoor air wet bulb temperature vs. capacity correction value
t

1.2
Capacity correction value
1.1

1.0

0.9

0.8
15 20 24
Indoor air wet bulb temp. (°C)

[2] Outdoor air dry bulb temperature vs.capacity correction value


1.2
Capacity correction value

1.1

1.0

0.9

-10 -5 0 10 15 20 25 30 35 40 43
Outdoor air dry bulb temp. (°C)

[3] Connecting pipe length and lift difference between indoor Standard model High efficiency model
HP
and outdoor units vs. capacity correction value Pipe length Graph Pipe length Graph
8 210 A1
10 210 B1
12 210 A1
Outdoor unit 14 210 A1
16 210 A1 220 A2
L' is the longest one of 18 220 B2
20 220 B2
(l'o + l'a, l'o + l'b, l'o + l'c) 22 220 A2
ho l'o 24 220 A2 235 A3
H = ho + 26 220 B2 235 B3
28 220 B2 235 B3
(Largest one of ha, hb, and hc) 30 220 B2 235 B3
32 220 B2 235 B3
34 235 B3 235 B3
ha 36 235 A3 235 A3
hb l'a 38 235 B3 235 B3
hc A 40 235 B3 235 B3
l'b 42 235 B3 235 B3
B Indoor unit 44 235 B3 235 B3
l'c 46 185 C1 185 C1
C 48 185 C1 185 C1

6 -4
6 Equipment selection procedure

Outdoor unit (A1)

Height of outdoor unit H (m)


70
60
50
40

97.5%
30

100%
20

87.5%

77.5%
82.5%
92.5%

72.5%
75%
90%
95%

85%

80%
10
0
-10
-20
-30
-40
0 10 20 30 40 50 60 70 80 90100 110 120130 140 150160 170 180190 200 210
Pipe length (Equivalent length) L’ (m)

Outdoor unit (A2)


Height of outdoor unit H (m)

70
60
50
97.5%

40
30
100%

77.5%
92.5%

72.5%
87.5%

82.5%
20
95%

75%
90%

85%

80%
10
0
-10
-20

70%
-30
-40
0 10 20 30 40 50 60 70 80 90 100 110 120130 140 150160 170 180190 200 210 220
Pipe length (Equivalent length) L’ (m)

Outdoor unit (A3)


Height of outdoor unit H (m)

70
60
50
40
97.5%

30
100%

20
77.5%
92.5%

72.5%
87.5%

82.5%

10
95%

75%
90%

85%

80%

70%

0
-10
-20
-30
-40
0 10 20 30 40 50 60 70 80 90 100 110 120130 140 150160 170 180190 200 210 220 230
Pipe length (Equivalent length) L’ (m)

Outdoor unit (B1)


Height of outdoor unit H (m)

70
60
50
40
97.5%

30
100%

87.5%

82.5%
92.5%

20
77.5%

67.5%
72.5%
85%

80%

75%
90%
95%

70%

10
0
-10
-20
-30
-40
0 10 20 30 40 50 60 70 80 90100 110 120130 140 150160 170 180190 200 210
Pipe length (Equivalent length) L’ (m)

6 -5
6 Equipment selection procedure

Outdoor unit (B2)

Height of outdoor unit H (m)


70
60
50
40

97.5%
30

100%

87.5%

82.5%
92.5%

77.5%

67.5%
72.5%
20

95%

85%

80%

75%
90%

70%
10
0
-10
-20
-30
-40
0 10 20 30 40 50 60 70 80 90 100 110 120130 140 150160 170 180190 200 210 220
Pipe length (Equivalent length) L’ (m)

Outdoor unit (B3)


Height of outdoor unit H (m)

70
60
50
40
97.5%

30
100%

20
87.5%

77.5%
82.5%

72.5%
92.5%

67.5%
95%

85%

80%

65%
75%
90%

70%
10
0
-10
-20
-30
-40
0 10 20 30 40 50 60 70 80 90 100 110 120130 140 150160 170 180190 200 210 220 230
Pipe length (Equivalent length) L’ (m)

Outdoor unit (C)


Height of outdoor unit H (m)

70
60
50
40
97.5%

30
100%

20
87.5%

82.5%
92.5%

77.5%

72.5%

67.5%
85%

80%

75%
90%
95%

70%

10
0
-10
-20
-30
-40
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180
Pipe length (Equivalent length) L’ (m)

[4]* Correction of outdoor unit diversity


1.2

1.0

0.8
Correction

0.6

0.4

0.2

0 20 40 60 80 100 120 135

Standard capacity ratio


Indoor units total capacity ratio (%)

*: Coefficient to use for the correction of the outdoor unit capacity when the total capacity of the indoor units are not equal to the
outdoor unit capacity.

6 -6
6 Equipment selection procedure

6-4-2.Correction charts for heating capacity calculation


[1] Indoor air dry bulb temperature vs. capacity correction value
1.2

Capacity correction value


1.1

1.0

0.9

0.8
15 20 24
Indoor air dry bulb temp. (°C)

[2] Outdoor air wet bulb temperature vs. capacity correction value
1.2
Capacity correction value

1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
-20 -15 -10 -5 0 5 10 15
Outdoor air wet bulb temp. (°C)

[3] Connecting pipe length and lift difference between indoor and outdoor units vs. capacity correction value

Outdoor unit

L' is the longest one of


(l'o + l'a, l'o + l'b, l'o + l'c)
ho l'o
H = ho + (Largest one of ha, hb, and hc)

ha
hb l'a
hc A
l'b
B Indoor unit
l'c
C

Outdoor unit (8 to 48HP)


Height of outdoor unit H (m)

70
60
50
40
99%

30
100%

20
10
0
98%

94%
95%

92%

91%

86%

85%
93%

89%
97%

90%
96%

88%
87%

-10
-20
-30
-40
0 10 20 30 40 50 60 70 80 90 100 110 120130 140 150160 170 180190 200 210 220 230
Pipe length (Equivalent length) L’ (m)

6 -7
6 Equipment selection procedure

[4]* Correction of outdoor unit diversity


1.2

1.0

Correction
0.8

0.6

0.4

0.2

0 20 40 60 80 100 120 135

Standard capacity ratio


Indoor units total capacity ratio (%)

*: Coefficient to use for the correction of the outdoor unit capacity when the total capacity of the indoor units are
not equal to the outdoor unit capacity.

6-4-3.Capacity correction in case of frost on the outdoor heat exchanger when in heating
Correct the heating capacity when frost can be found on the outdoor heat exchanger.
Heating capacity = Capacity after correction of outdoor unit x Correction value of capacity resulted from frost
(Capacity after correction of outdoor unit: Heating capacity calculated in the above item 2.)

[5] Capacity correction in case of frost on the outdoor heat exchanger


1.0
Capacity correction value

0.9

0.8
-15 -10 -5 0 5 10
Outdoor air wet bulb temp. (°C)

6-4-4.Rated conditions
Cooling: Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating: Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB

6 -8
6 Equipment selection procedure

6-5. Example of equipment selection


Selection condition
Indoor temperature Outdoor temperature Indoor Temperature Piping
When cooling : 27.0 CDB/19.0 CWB When cooling : 35.0 CDB/ - correction correctinon correction
When heating : 20.0 CDB/ - When heating : 6.0 CDB/3.0 CWB Cooling 1.0 0.92
Equivalent pipe length : 46m Height of outdoor unit : 20m(Outdoor unit upper) Heating 1.0 0.97
(From charts)

6-5-1.Capacity correction and selection for indoor unit


1 Determinate of indoor air-condition load at each room as shown below table.
2 Preliminary select indoor units in standard capacity exceeding air-condition load at each room.
3 Find the correction values from indoor correction charts for both cooling and heating with temperature
conditions. (Refer to Chart [1].)
JIn this case, get correction values, Cooling 1.0 / Heating 1.0
Then calculate Capacity A of each indoor unit.
Capacity A = Standard capacity x the correction value by indoor unit condition
4 Preliminary select outdoor unit in standard capacity exceeding total values of Capacity A.
At that time, check connectable indoor units number and the outdoor unit diversity (connecting ratio of indoor
units HP to outdoor unit HP.)
JIn this case, select MMY-MAP2214HT* (22HP)
Cooling capacity : 61.3 < 61.5 OK, Heating capacity : 68.9 < 69.0 OK,
Number of connectable indoor units : 11 < 37 OK,
Outdoor unit diversity (H2 < 15m) : 100% matchs "50 to 135%". OK
5 This part has two steps.
Step1 : Find the correction values of "Connecting pipe length and lift" by both the longest pipe length and the
largest height
with selected piping condition at 4 both cooling and heating. (Refer to Chart [3].)
JIn this case, get correction values , Cooling 0.92 / Heating 0.97.
Step2 : Calculate Capacity B by multiplying the value of step1 by corrected Capacity A.
Capacity B = Capacity A x the correction value by piping condition of length/lift
6 Comperae Capacity B of indoor unit with air-conditioning load (for all rooms)
Capacity B >= Air-conditioing load (for all room)
JIn this case, all Capacity B are bigger than air-conditioning load for both cooling and heating. Go to 7.

6 -9
6 Equipment selection procedure

1 2 3 5
Condition of indoors Capacity correction and selection for indoor unit
Air-conditioning load Standard capacity Corrected Capacity A Corrected Capacity B
Floor Room name Cooling Heatiing Model name Cooling Heatiing Cooling Heatiing Cooling Heatiing
(kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
Office 1 6.0 6.2 MMU-AP0242H 7.1 8.0 7.1 8.0 6.5 7.8
Meeting rroom 1 4.6 5.0 MMU-AP0182H 5.6 6.3 5.6 6.3 5.2 6.1
Office 2 3.8 3.3 MMU-AP0152H 4.5 5.0 4.5 5.0 4.1 4.9
Locker room 1 3.0 3.1 MMU-AP0122H 3.6 4.0 3.6 4.0 3.3 3.9
Meeting room 2 11.8 12.0 MMU-AP0482H 14.0 16.0 14.0 16.0 12.9 15.5
Locker room 2 3.0 3.0 MMU-AP0122H 3.6 4.0 3.6 4.0 3.3 3.9
1
Rest room 4.6 4.8 MMU-AP0182H 5.6 6.3 5.6 6.3 5.2 6.1
Smoking room 3.0 3.1 MMU-AP0122H 3.6 4.0 3.6 4.0 3.3 3.9
Reception room 3.8 3.9 MMU-AP0152H 4.5 5.0 4.5 5.0 4.1 4.9
Office 3 4.8 4.5 MMU-AP0182H 5.6 6.3 5.6 6.3 5.2 6.1
Reception area 3.0 3.1 MMU-AP0122H 3.6 4.0 3.6 4.0 3.3 3.9

Total 51.4 52.0 61.3 68.9 61.3 68.9 56.4 66.8

Cooling charts Heating charts


[1] Indoor air wet bulb temperature vs. [1] Inddor air dry bulb temperature vs.
capacity correction value capacity correction value

3
3

Selection of piping chart by selecting


outdoor unit

19
⑤- 1

[3] connecting pipe length and lift between indoor [3] Connecting pipe length and lift betweenindoor
and outdoor units vs. capacity correction value and outdo units vs. capacity correction value

5-1
5-1

0.92 0.97

46 46

6 -10
6 Equipment selection procedure

6-5-2.Capacity correction and selection for oudoor unit


7 Find the correction values of following five items for the standard capacity of outdoor unit selected at 4.
Then determination of total corrected capacity of the selected outdoor unit by all multiplying.
Corrected capacity of outdoor unit = Standard capacity of selected outdoor unit
x Correction value by the indoor temperature condition (Refer to Chart [1].)
x Correction value by the outdoor temperature condition (Refer to Chart [2].)
x Correction value by connecting pipe length and lift between indoor and outdoor units
(Refer to Chart [3].)
x Correction value by outdoor unit diversity in only over 100% (Refer to Chart [4].)
x Correction value by frost condition on outdoor heating exchanger in heating
(Refer to Chart [5].)
JIn this case, these five correction values are bewlow.
Correction value by the indoor temperature condition : Cooling 1.0 / Heating 1.0 (sama as 3)
Correction value by the outdoor temperature condition :
Cooling 1.0 / Heating 0.95 (Find both values by chart [2])
Correction value by connecting pipe length and lift between indoor and outdoor units :
Cooling 0.92 / Heating 0.97 (sama as 5-1.)
Correction value by outdoor unit diversity : Cooling 1.0 / Heating 1.0 (Find both values by chart [4])
Correction value by frost condition on outdoor heating exchanger in only heating :
Cooling - / Heating 0.95 (Find the value by chart [5])
Corrected capacity of outdoor unit : Cooling 61.5kW x 1.0 x 1.0 x 0.92 x 1.0 = 56.6kW
Heating 69.0kW x 1.0 x 0.95 x 0.97 x 1.0 x 0.95 = 60.4k
8 Calculate Capacity C of each indoor unit by multiplying the corrected capacity of outdoor unit at 7 by
proportinal division of each indoor unit standard capacity for total standard capacity of all indoor units.
Capacity C = Corrected capacity of outdoor unit x (Each indoor unit standard capacity / total standard
capacity of all indoor units)
JIn this case, the example of "Office 1" is the following.
Cooling : Capacity C = 56.6kW x (7.1kW / 61.3kW) = 6.6kW
Heating : Capacity C = 60.4kW x (8.0kW / 68.9kW) = 7.0kW
Calculate Capacity C of remain rooms by the similar method.
9 Comperae Capacity C of indoor unit with air-conditioning load (for all rooms)
Capacity C >= Air-conditioing load (for all room)
JIn this case, all Capacity C are bigger than air-conditioning load for both cooling and heating. All rooms
are OK and selection ends.
Cooling charts Heating charts
[2] Outdoor air dry bulb temperature vs. [2] Outdoor air wet bulb temperature vs.
capacity correction value capacity correction value
7
0.95
7

[4] Correction of outdoor unit diversity [4] Correction of outdoor unit diversity
7 7

[5] Frost on the outdoor heating exchanger in


heating
0.95
7

6 -11
6 Equipment selection procedure

6-5-3.Result of selection example


Selection condition
Indoor temperature Outdoor temperature Indoor Temperature Piping
When cooling : 27.0 CDB/19.0 CWB When cooling : 35.0 CDB/ - correction correctinon correction
When heating : 20.0 CDB/ - When heating : 6.0 CDB/3.0 CWB Cooling 1.0 0.92
Equivalent pipe length : 46m Height of outdoor unit : 20m(Outdoor unit upper) Heating 1.0 0.97
(From charts)

Preliminary selection of indoor units(with outdoor unit) by each air-conditioning load


Condition of indoors Capacity correction and selection for indoor unit
Air-conditioning load Standard capacity Corrected Capacity A Corrected Capacity B
Floor Room name Cooling Heating Model name Cooling Heating Cooling Heating Cooling Heating
(kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
Office 1 6.0 6.2 MMU-AP0242H 7.1 8.0 7.1 8.0 6.5 7.8
Meeting room 1 4.6 5.0 MMU-AP0182H 5.6 6.3 5.6 6.3 5.2 6.1
Office 2 3.8 3.3 MMU-AP0152H 4.5 5.0 4.5 5.0 4.1 4.9
Locker room 1 3.0 3.1 MMU-AP0122H 3.6 4.0 3.6 4.0 3.3 3.9
Meeting room 2 11.8 12.0 MMU-AP0482H 14.0 16.0 14.0 16.0 12.9 15.5
Locker room 2 3.0 3.0 MMU-AP0122H 3.6 4.0 3.6 4.0 3.3 3.9
1
Rest room 4.6 4.8 MMU-AP0182H 5.6 6.3 5.6 6.3 5.2 6.1
Smoking room 3.0 3.1 MMU-AP0122H 3.6 4.0 3.6 4.0 3.3 3.9
Reception room 3.8 3.9 MMU-AP0152H 4.5 5.0 4.5 5.0 4.1 4.9
Office 3 4.8 4.5 MMU-AP0182H 5.6 6.3 5.6 6.3 5.2 6.1
Reception area 3.0 3.1 MMU-AP0122H 3.6 4.0 3.6 4.0 3.3 3.9

Total 51.4 52.0 61.3 68.9 61.3 68.9 56.4 66.8

Preliminary selection of outdoor unit


Cooling Heatiing
Model name
(kW) (kW)
MMY-APMAP2214HT*
61.5 69.0
(Standard model 22HP)

8
Selection of outdoor unit / indoor units
Pipe length(m) Corrected capacity of outdoor unit (kW) Corrected Capacity C
Floor Room name Correction of cooling Correction of heating Cooling Heating
Equivalent length & lift Item
capacity capacity (kW) (kW)
Office 1 6.6 7.0
Standard capacity 61.5 69.0
Meeting room 1 5.2 5.5
Office 2 4.2 4.4
Indoor temperature 1.0 1.0
Locker room 1 3.3 3.5
Meeting room 2 12.9 14.0
Outdoor temperature 1.0 0.95
Locker room 2 46 / 20 3.3 3.5
1
Rest room (Outdoor unit upper) Connecting pipe 5.2 5.5
0.92 0.97
Smoking room length and lift 3.3 3.5
Reception room 4.2 4.4
Outdoor unit diversity 1.0 1.0
Office 3 5.2 5.5
Reception area Frost on heating 3.3 3.5
- 0.95
exchanger
Total 56.6 60.4 56.6 60.4

7 7

9
Judgment result
Condition of indoors Equipment Selection
Judgment result
Air-conditioning load Corrected Capacity C
Floor Room name Cooling Heating Model name Cooling Heating
Cooling Heating
(kW) (kW) (kW) (kW)
Office 1 6.0 6.2 MMU-AP0242H 6.6 7.0 OK OK
Meeting room 1 4.6 5.0 MMU-AP0182H 5.2 5.5 OK OK
Office 2 3.8 3.3 MMU-AP0152H 4.2 4.4 OK OK
Locker room 1 3.0 3.1 MMU-AP0122H 3.3 3.5 OK OK
Meeting room 2 11.8 12.0 MMU-AP0482H 12.9 14.0 OK OK
Locker room 2 3.0 3.0 MMU-AP0122H 3.3 3.5 OK OK
1
Rest room 4.6 4.8 MMU-AP0182H 5.2 5.5 OK OK
Smoking room 3.0 3.1 MMU-AP0122H 3.3 3.5 OK OK
Reception room 3.8 3.9 MMU-AP0152H 4.2 4.4 OK OK
Office 3 4.8 4.5 MMU-AP0182H 5.2 5.5 OK OK
Reception area 3.0 3.1 MMU-AP0122H 3.3 3.5 OK OK

Total 51.4 52.0 MMY-APMAP2214HT* 56.6 60.4 OK OK

6 -12
6 Equipment selection procedure

Example: Equipment selection based on system load profile


Since the five rooms on the floor face different directions, their hourly cooling load profile will be also
different.
We select each indoor unit based on the individual room peak load. However, we need to use the total load
profile on the floor as a base to choose the outdoor module.

• Load in each room • Total load in all rooms

8 22
Room1
6 20
Load (kW)

4 18

2 16

0 14

Total Load (kW)


0 8 12 16 20 Hour

12
8
Room2 10
6
Load (kW)

8
4

6
2

4
0
0 8 12 16 20 Hour
2

8
0
Room3 0 8 12 16 20 Hour
6
Load (kW)

0
0 8 12 16 20 Hour

1. The total load on the floor is calculated by adding


8
Room4 the hourly cooling loads of the five rooms.
6 2. The maximum value of total load is used to select
Load (kW)

outdoor module.
4

0
0 8 12 16 20 Hour

8
Room5
6
Load (kW)

0
0 8 12 16 20 Hour

6 -13
6 Equipment selection procedure

6-6. Selection procedure for fresh air intake indoor unit


6-6-1.Selection flow chart

1. Decisions of both air volume for fresh air intake and static pressure of duct
It is necessary to calculate “required ventilatory volume” to decide the air volume.
Be sure to consider the balance of air supply and exhaust.

2. Decisions of fresh air intake indoor unit by necessary air volume and external
static pressure

3. Temporary grouping of outdoor units and normal indoor units + fresh air intake
indoor units
Grouping limitation
*1 : The system is SMMS, is not SHRM SHRM(heat
(heatrecovery).
recovery).
*2 : Up to two fresh air intake indoor units on one line of the multi system.
*3 : The allowable total capacity of fresh air intake units shall be 30% or less against the total
capacity of the indoor units(including
units (includingthe
thefresh
freshair
airintake
intakeunits).
units).
*4 : The total capacity of the fresh air intake units and the indoor units is restricted to 80 to
100% against the capacity
capacith of the outdoor units.
*5 : The fresh air intake units only cannot connected.

4. Check of piping length and the height difference for between outdoor units and
normal indoor units + fresh air intake indoor units.

5. Capacity correction with design indoor temperature and outdoor temperature

6. Check of temporary grouping No good


outdoor units and normal indoor
units + fresh air intake indoor units

OK

7. Decision of combination between outdoor units and normal indoor units + fresh
air intake indoor units

end

6 -14
6 Equipment selection procedure

6-6-2.Operatable temperature range and discharge temperature set up

Operatable temperature range

Ts : Setup Temp.
Operable mode and sidecharge temp setup range
Fresh air temp.°C Operation mode At shipment from factory Setup range
–10 0 10 20 30 40 50 COOL 18°C 16 to 27°C
5
Ts
40 HEAT 25°C 16 to 27°C
COOL mode FAN COOL

Ts + 3°C

Ts
–5 43

HEAT mode HEAT FAN

Ts – 3°C

• In cooling operation, if the temperature is below 5°C, the operation stops automatically. (FAN stop)
• In heating operation, if the temperature is below –5°C, the operation stops automatically. (FAN stop)
(To protect the refrigerant cycle)

6-6-3.Calculation of required ventilatory volume


The required ventilatory volume (air supply quantity) is calculated depending on the ventilation purpose or the
number of ventilation ducts.

Ex. Calculation method based on a general living room under Japanese Building Standard Law
Available amount of ventilation V [m3/h]
V = 20 Af/N
Af : Floor space of the living room m2
N : Occupation area per room m2
If N > 10, please set N to 10.
(In the case of a living room of the special building, please change 10m2 to 3m2 as N.)
Af/N means number of people in the living room.
So if “X” as number of people in the living room is settled, V is able to define by the below expression
V = 20 x X
This expression is based on Japanese Building Standard Law and the coefficient “20” (unit : m3/h) is based on
exhaust volume of carbon dioxide by breathing per person who is quietly sitting adult male.
Although the coefficient is not always enough ventilatory volume.

In fact in ASHRAE (American Society of Heating Refrigerating and Air-Conditioning Engineers),


it shows 30 m3/h per person as its guideline in consideration of smells of the cigarette and so on.

Please calculate the required ventilatory volume with meeting for local regulations, market requirements
and customer’s purpose.

6 -15
7
SMMS-i Data book

Refrigerant piping design

7-1. WARNINGS ON REFRIGERANT LEAKAGE


Check of Concentration Limit Important
The room in which the air conditioner is to be installed NOTE 2:
requires a design that in the event of refrigerant gas The standards for minimum room volume are as follows.
leaking out, its concentration will not exceed a set limit.
The refrigerant R410A which is used in the air (1) No partition (shaded portion)
conditioner is safe, without the toxicity or combustibility
of ammonia, and is not restricted by laws to be imposed
which protect the ozone layer. However, since it
contains more than air, it poses the risk of suffocation if
its concentration should rise excessively.
(2) When there is an effective opening with the adjacent
Suffocation from leakage of R410A is almost
room for ventilation of leaking refrigerant gas
nonexistent. With the recent increase in the number of
(opening without a door, or an opening 0.15% or
high concentration buildings, however, the installation of
larger than the respective floor spaces at the top or
multi air conditioner systems is on the increase because
bottom of the door).
of the need for effective use of floor space, individual
Outdoor unit
control, energy conservation by curtailing heat and
carrying power etc. Refrigerant piping
Most importantly, the multi air conditioner system is able
Indoor unit
to replenish a large amount of refrigerant compared
with conventional individual air conditioners. If a single
unit of the multi conditioner system is to be
installed in a small room, select a suitable model and (3) If an indoor unit is installed in each partitioned room
installation procedure so that if the refrigerant and the refrigerant tubing is interconnected, the
accidentally leaks out, its concentration does not reach smallest room of course becomes the object. But
the limit (and in the event of an emergency, measures when a mechanical ventilation is installed
can be made before injury can occur). interlocked with a gas leakage detector in the
In a room where the concentration may exceed the limit, smallest room where the density limit is exceeded,
create an opening with adjacent rooms, or install the volume of the next smallest room becomes the
mechanical ventilation combined with a gas leak object.
detection device. Refrigerant piping
The concentration is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m3) Outdoor unit
≤ Concentration limit (kg/m3) Very
small
room Indoor unit
The concentration limit of R410A which is used in multi
air conditioners is 0.3kg/m3. Small Medium
room room Large room

NOTE 1: Mechanical ventilation device - Gas leak detector


If there are 2 or more refrigerating systems in a single
refrigerating device, the amounts of refrigerant should NOTE 3:
be as charged in each independent device. The minimum indoor floor area compared with the
Outdoor unit amount of refrigerant is roughly as follows: (When the
e.g., charged ceiling is 2.7m high)
amount (10kg) e.g.,
charged amount (15kg)
40 Range below the
density limit of
m² 35 0.3 kg/m3
Min. indoor floor area

30 (countermeasur
es not needed)
25

Room A Room B Room C Room D Room E Room F 20


Range above
Indoor unit 15 the density limit
For the amount of charge in this example: 10 of 0.3 kg/m3
(countermeasur
The possible amount of leaked refrigerant gas in 5 es needed)
rooms A, B and C is 10kg.
The possible amount of leaked refrigerant gas in 0
10 20 30
rooms D, E and F is 15kg. kg
Total amount of refrigerant

7 -1
7 Refrigerant piping design

7-2. Free branching system


[1] Line branching system
[2] Header branching system
[3] Header branching system after line branching
[4] Line branching system after header branching
[5] Header branching system after header branching
The above five branching systems enable to dramatically increase the flexibility of refrigerant piping design.

Outdoor unit

Branching joint

Line branching
system
Indoor unit

Remote
controller

Outdoor unit

Header Branching header


branching
system
Indoor unit
Remote controller

Outdoor unit

Branching joint
Header
branching
system after line
branching
Indoor unit
Remote
controller

Line branching Outdoor unit


system after
header
branching Branching header

Header Branching
joint
branching
system after Indoor
unit
header Remote
branching controller

7 -2
7 Refrigerant piping design

7-3. Allowable length/height difference of refrigerant piping


T-shape branching joint for liquid pipe Y-shape branching joint for gas pipe
D
Follower <Ex.1> <Ex.1>
unit 3

Height A B C
difference Header Follower Follower
unit unit 1 unit 2
between
outdoor Outdoor unit
Connecting
piping of
( Horizontal
posture )
units outdoor unit OK OK
H3 5m
<Ex.2> <Ex.2>
La Lb Lc Ld

LA LB
Equivalent length corresponded to farthest piping
Main between outdoor unit LO <25m
Height piping
difference Y-shape branching T-shape branching NO GOOD
L1 NO GOOD
between joint for gas pipe joint for liquid pipe
outdoor
units Branching
H1 70m Branching piping L2 header

Connecting piping of indoor unit L7


1st branching
section
a b c d e

L3 Indoor unit

Equivalent length corresponded to farthest piping L 235 m


Height difference
Equivalent length corresponded to farthest piping after 1st branching Li 90 m
between indoor
units
L6
L4 L5 H2 40m
Y-joint

f g h i j

Indoor unit

System restrictions
Max. No. of combined outdoor units 4 units Note 1) Combination of outdoor units: Header unit (1 unit) + Follower units (0 to 3 units).
Header unit is the outdoor unit nearest to the connected indoor units.
Max. capacity of combined outdoor units 48 HP Note 2) Install the outdoor units in order of capacity.
Max. No. of connected indoor units 48 units (Header unit ≥ Follower unit 1 ≥ Follower unit 2 ≥ Follower unit 3)
Note 3) Use Y-shape branching joint in connecting of gas pipe for outdoor unit, and install horizontally.
Max. capacity of combined H2 15 135% Note 4) Piping to indoor units shall be perpendicular to piping to the header outdoor unit as <Ex.1>.
indoor units H2 > 15 Do not connect piping to indoor units in the same direction of header outdoor unit as T-shape
105% branching joint for liquid pipe of <Ex.2>.
Farthest piping length L(*1) by capacity of outdoor units
Standard model High efficiency model
Capacity (HP) 5,6 8 ∼ 16 18 ∼ 32 34 ∼ 44 46 , 48 16 24 ∼ 44 46 , 48
Equivalent length (m) 175 210 220 235 185 210 235 185
Real length (m) 150 170 180 190 155 180 190 155
Note : All values of above table decrease 25m when H1 exceeds 3m, except 5HP& 6HP.

Allowable length and height difference of refrigerant piping


Allowable value Piping section
Total extension of pipe Below 34HP 300m LA + LB + La + Lb + Lc + Ld + L1 + L2 + L3 + L4+ L5 +
(Liquid pipe, real length) 34HP or more 500m L6 + L7 + a + b + c + d + e + f + g + h + i + j
Equivalent length 235m
Farthest piping Length L (*1) LA + LB + Ld + L1 + L3 + L4 + L5 + L6 + j
Real length 190m
Equivalent length of farthest piping from 1st branching Li (*1) 90m (*2) L3 + L4 + L5 + L6 + j
Piping length Equivalent length of farthest piping between outdoor units LO (*1) 25m LA + LB + Ld(LA + Lb, LA + LB + Ld)
Equivalent length 120m (*3)
Max. equivalent length of main piping L1
Real length 100m (*3)
Max. equivalent length of outdoor unit connecting piping 10m Ld(La, Lb, Lc)
Max. real length of indoor unit connecting piping 30m a, b, c, d, e, f, g, h, i, j
Max. equivalent length between branches 50m L2, L3, L4, L5, L6, L7
Upper outdoor unit 70m (*4) –
Height between indoor and outdoor units H1
Difference in Lower outdoor unit 40m (*5) –
height Height between indoor units H2 40m (*6) –
Height between outdoor units H3 5m –
(*1) : (D) is outdoor unit furthest from the 1st branch and (j) is the indoor unit furthest from the 1st branch.
(*2) : If the height difference (H1) between indoor and outdoor unit exceeds 3m, set 65m or less. In case of 5HP & 6HP, it is 65m or less
regardless of H1.
(*3) : If the max. combined outdoor unit capacity is 46HP or more, then max. equivalent length is 70m or less (real length is 50m or less).
In case of 5HP & 6HP, the equivalent length is 85m or less when under 46HP, and 70m or less when 46HP or more.
(*4) : If the height difference (H2) between indoor units exceeds 3m, set 50m or less. In case of 5HP & 6HP, it is 50m or less regardless of H2.
(*5) : If the height difference (H2) between indoor units exceeds 3m, set 30m or less.
(*6) : In case of 5HP & 6HP, it is 30m or less.

7 -3
7 Refrigerant piping design

7-4. Selection of refrigerant piping


6 Header branching pipe
Branching piping

Follower Follower Follower Indoor unit connecting piping 4


unit 3 unit 2 unit 1 Header unit

Outdoor 5 5 5 5 5
unit 4

Balance pipe
ø9.5
1st branching Indoor unit
1 section
1 1 1 1 6 Y-shape
2 2 branching 4
7 3 Main piping joint 4 4

2 2 7 Branching joint for 4


1 Outdoor unit outdoor unit 5 5 5 5 5
connecting Main connecting
piping piping between Indoor unit
outdoor units connecting piping

Indoor unit
1 Pipe size of outdoor unit (Table 1) 5 Piping of indoor unit (Table 5)
Model name MMY- Gas side Liquid side Capacity rank Gas side Liquid side
MAP0501* ø15.9 ø9.5 007 type to Actual length 15m or less ø9.5 ø6.4
MAP0601* ø19.1 ø9.5 012 type Actual length exceeds 15m ø12.7 ø6.4
MAP0804* ø22.2 ø12.7 015 type to 018 type ø12.7 ø6.4
MAP1004* ø22.2 ø12.7 024 type to 056 type ø15.9 ø9.5
MAP1204* ø28.6 ø12.7 072 type to 096 type ø22.2 ø12.7
MAP1404* ø28.6 ø15.9
MAP1604* ø28.6 ø15.9 6 Selection of branching section (Table 6)
2 Connecting pipe size between outdoor units (Table 2) Total capacity code of indoor unit *1 Model name
Below 6.4 RBM-BY55E
Total capacity code of outdoor units at Liquid Balance
Gas side Y-shape branching 6.4 to below 14.2 RBM-BY105E
downstream side *1 side pipe
joint *2 *3 *8 14.2 to below 25.2 RBM-BY205E
16 to below 22 ø28.6 ø15.9
25.2 or more RBM-BY305E
22 to below 26 ø34.9 ø15.9
ø9.5 For 4 Below 14.2 RBM-HY1043E
26 to below 36 ø34.9 ø19.1
Branching header branching 14.2 to below 25.2 RBM-HY2043E
36 or more ø41.3 ø22.2
*2 *3 *6 *8 For 8 Below 14.2 RBM-HY1083E
3 Size of main pipe (Table 3) branching 14.2 to below 25.2 RBM-HY2083E
Total capacity code of all
Gas side Liquid side
outdoor units *1 7 Selection of branching joint for outdoor unit (Table 7)
Below 6 ø15.9 ø9.5 Total Joints
6 to below 8 ø19.1 ø9.5 capacity Model
8 to below 12 ø22.2 ø12.7 Gas Liquid Balance
code of name
12 to below 14 ø28.6 ø12.7 (Y-shape) (T-shape) (T-shape)
outdoor unit
14 to below 22 ø28.6 ø15.9
ø28.6 ø19.1 ø9.5
22 to below 36 ø34.9 ø19.1 ø31.8 RBM-
36 to below 46 ø41.3 ø22.2 Branching Below 26 BT14E
46 or more *7 ø41.3 ø22.2 ø25.4 ø19.1 ø19.1 ø9.5 ø9.5
joint for
Determine thickness of the main pipe according to capacity of the outdoor units. outdoor ø38.1
ø38.1 ø22.2 ø9.5
unit RBM-
4 Pipe size between branching sections (Table 4)*5 26 or more
ø28.6 ø22.2 ø22.2 ø9.5 ø9.5 BT24E
SMMS-i 8HP to 48HP
Total capacity code of indoor
Gas side Liquid side
units at downstream side *1 8 Minimum wall thickness for R410A application (Table 8)
2.4 or less ø12.7 ø9.5
Minimum wall
2.4 to below 6.4 ø15.9 ø9.5 Soft Half hard or hard OD (Inch) OD (mm)
6.4 to below 12.2 ø22.2 ø12.7 thickness (mm)
12.2 to below 20.2 ø28.6 ø15.9 OK OK 1/4'' 6.35 0.80
20.2 to below 35.2 ø34.9 ø19.1 OK OK 3/8'' 9.52 0.80
35.2 or more ø41.3 ø22.2 OK OK 1/2'' 12.70 0.80
OK OK 5/8'' 15.88 1.00
SMMS 5HP & 6HP NG*4 OK 3/4'' 19.05 1.00
Total capacity code of indoor NG*4 OK 7/8'' 22.20 1.00
Gas side Liquid side
units at downstream side *1 NG*4 OK 1.1/8'' 28.58 1.00
2.8 or less ø12.7 ø9.5 NG*4 OK 1.3/8'' 34.92 1.10
2.8 to below 6.4 ø15.9 ø9.5 NG*4 OK 1.5/8'' 41.28 1.25
6.4 or more ø22.2 ø12.7
If the total capacity code value of indoor units exceeds that of the outdoor units,
apply the capacity code of outdoor units.

*1 Code is determined according to the capacity rank.


*2 When using a branching joint for the 1st branch, select according to capacity code of the outdoor unit.
*3 For 1 line after branching header indoor units with a maximum capacity code of 6.0 in total can be connected.
*4 If the pipe size is Ø19.0 or more, use a suitable material as detailed in the installation manual.
*5 If the piping size becomes over main piping size, select the size same as main piping.
*6 When the first branch is a header with the outdoor total capacity codes of 12 to 26, apply the model RBM- HY2043E(4-branch) or RBM-
HY2083E(8-branch) regardless of the total capacity codes of the down-stream indoor units.
*7 The maximum equivalent length of main pipe should be 70m or shorter.
*8 When the sum of capacity code of indoor units exceeds the capacity code of outdoor units, select according to capacity code of the outdoor units.

7 -4
7 Refrigerant piping design

7-5. Charging requirement with additional refrigerant


After the system has been vacuumed, replace the vacuum pump with a refrigerant cylinder and system with
additional refrigerant.

Calculating the amount of additional refrigerant required


R410A
Refrigerant in the system when shipped from the factory
*SMMS
5HP* 6HP* 8HP 10HP 12HP 14HP 16HP
Refrigerant amount Heat pump model 8.5kg 8.5kg 11.5kg 11.5kg 11.5kg 11.5kg 11.5kg
charged in factory Cooling only model 8.0kg 8.0kg 10.5kg 10.5kg 10.5kg 11.5kg 11.5kg

When the system is charged with refrigerant at the factory, the amount of refrigerant needed for the pipes at the site
is not included. Therefore, calculate the additional amount needed and add the required amount to the system.
(Calculation)
Additional refrigerant charge amount is calculated based on the size of liquid pipe at site and its real length.

Additional refrigerant charge amount at site =


Additional refrigerant charge amount
Real length of liquid pipe × per liquid pipe 1m (Table 1) + Compensation by system HP (Table 2)

Example : Additional charge amount R (kg) = (L1 x 0.025kg/m) + (L2 x 0.055kg/m) + (L3 x 0.105kg/m) + (3.0kg)
L1 : Real total length of liquid pipe ø6.4 (m)
L2 : Real total length of liquid pipe ø9.5 (m)
L3 : Real total length of liquid pipe ø12.7 (m)
Table 1
Pipe dia. at liquid side ø6.4 ø9.5 ø12.7 ø15.9 ø19.0 ø22.2
Additional refrigerant amount/1m 0.025kg 0.055kg 0.105kg 0.160kg 0.250kg 0.350kg

Table 2
Standard model High efficiency model
Combined Compensation Combined Compensation
horse power Outdoor by System HP horse power Outdoor by System HP
combination(HP) combination(HP)
(HP) (kg) (HP) (kg)
5* 5 0.0 - -
6* 6 0.0 - -
8 8 1.5 - -
10 10 2.5 - -
12 12 3.5 - -
14 14 8.5 - -
16 16 10.5 16 8 8 0.0
18 10 8 0.0 - -
20 10 10 3.0 - -
22 12 10 5.0 - -
24 12 12 7.5 24 8 8 8 -4.0
26 16 10 8.5 26 10 8 8 -4.0
28 16 12 9.5 28 10 10 8 -2.0
30 16 14 11.5 30 10 10 10 0.0
32 16 16 12.5 32 8 8 8 8 -6.0
34 12 12 10 3.0 34 10 8 8 8 -6.0
36 12 12 12 4.0 36 10 10 8 8 -6.0
38 16 12 10 6.0 38 10 10 10 8 -6.0
40 16 12 12 7.0 40 10 10 10 10 -5.0
42 16 14 12 8.0 42 12 10 10 10 -4.0
44 16 16 12 10.0 44 12 12 10 10 -2.0
46 16 16 14 12.0 46 12 12 12 10 0.0
48 16 16 16 14.0 48 12 12 12 12 2.0
*SMMS
7 -5
8
SMMS-i Data book

Refrigerant cycle diagram


8-1. Outdoor Unit
Inverter Driven Unit (5, 6HP)
Model : MMY-MAP0501, MAP0601

Propeller fan

M Fan motor

Sensor (Right side)


(TE1)
Sensor
Air heat exchanger at outdoor side (TO)
Strainer
(Left side)
Pulse motor
valve (PMV) Air heat exchanger at outdoor side
(5, 6HP)

(PMV1)
Strainer Solenoid valve (SV5) 4-Way valve

Check valve Solenoid valve Sensor (TS1)


High-pressure (SV2)
sensor Capillary tube
Sensor
(TL) Check joint
Low-pressure
Capillary tube sensor
Check joint
Solenoid valve Strainer Oil
(SV3D) separator
Capillary tube
Liquid
tank Strainer
Solenoid valve
Solenoid valve (SV42)
(SV41)

Check Check High-pressure


Check High-pressure valve valve
switch switch
joint Accumulator
Capillary Solenoid
Sensor valve Sensor
(TD1) tube (TD2)
(SV3C)
Compressor 1

Compressor 2

Sensor
(TK3)
(Inverter)

(Inverter)

Strainer Strainer

Check Check
valve valve

Capillary tube Capillary tube


Sensor Sensor
(TK1) (TK2)
Solenoid
valve Sensor
(SV3E) (TK4)

Capillary tube Capillary tube

Solenoid
Strainer Strainer valve
(SV3A)
Check Solenoid
Strainer valve valve
(SV3B)

Check
valve

Balance Liquid Gas


pipe side side
servise service service
value value value

8 -1
8 Refrigerant cycle diagram

Inverter Driven Unit (8, 10, 12HP)


Model Name : MMY-MAP0804*, MMY-MAP1004*, MMY-MAP1204*

Fan
M Fan Motor

(Right side)

(TO)
Heat Exchanger

(Left side)

Heat Exchanger
(TE1)
SV

(SV5) Reducer

PMV1
PMV2 4- way Valve

(TS1)

Check Valve

High Low
Pressure Pressure
Sensor
SV
(TL)

(SV2)
(SV3D) Oil
Fusible FP
Plug SV

SV (SV41) Check valve Check Valve SV (SV42)

High-
(TD1) High-pressure pressur (TD2)
Liquid switch switch
Accumlator
Tank (SV3C
SV

Compressor 2
Compressor 1
(Inverter )

(Inverter )

A3 (TK4)

Check Check
Valve Valve

(TK1) (TK2)

Oil Header
SV

(SV3E) (TK5)
SV

(SV3A)

Check Valve SV (SV3B)

Check Valve

Liquid side
Gas side Balance pipe
service valve
service valve packed valve
SV

Solenoid Capillary Check Check Strainer Temperature Distributor


Valve Tube Valve Joint Sensor

8 -2
8 Refrigerant cycle diagram

Inverter Driven Unit (14,16HP)


Model Name : MMY-MAP1404*, MMY-MAP1604*

Fan
M Fan Motor

(Right Side)

Main Heat Exchanger (TO)

PMV1 Sub Heat Exchanger (Right side)


PMV2
(Left side)

(TE1) Main Heat Exchanger


Check Valve
PMV4 (TE2)
SubHeat Exchanger (Left side) Check Valve

4- way Valve

High
Pressure (TS1)
(SV6)
SV
Low
Pressure
SV
Sensor

Fusible
FP (SV2)
Plug (TL) (SV3D) Oil
SV

Liquid (SV41)
Tank Check Valve
SV SV (SV42) SV Accumlator

High (SV3C) High (SV43)


(TD1) pressure High
pressure (TD2) pressure (TD3)
SV

switch switch switch


Compressor 1

(TK4)
Compressor 2

Compressor 3
(Inverter)

(Inverter)

(Inverter)

(TK2)
(TK1) (TK3)

(TK5) Oil Header


SV

(SV3E)

SV (SV3F)
SV

(SV3A)

Check Valve SV (SV3B)

Check Valve

Liquid side Gas side Balance pipe


Service Valve service valve service valve

SV

Solenoid Capillary Check Check Strainer Temperature Distributor


Valve Tube Valve Joint Sensor

8 -3
8 Refrigerant cycle diagram

8-2. Explanation of Functional Parts


Model : MMY-MAP0501*, MMY-MAP0601* (SMMS)
Functional part name Functional outline
Solenoid valve 1. SV3A (Connector CN324: Red)
1) Collects oil in the oil tank during OFF time.
2) Supplies oil reserved in the oil tank during ON time.
2. SV3B (Connector CN313: Yellow)
1) Returns oil supplied in the balance pipe to the compressor.
3. SV3C (Connector CN314: Black)
1) Pressurizes oil reserved in the oil tank during ON time.
4. SV3D (Connector CN323: White)
1) Reserves oil in the oil separator during OFF time, and supplies oil during ON time.
5. SV3E (Connector CN323: White)
1) Turns on during operation and balances oil between the compressors.
6. SV2 (Hot gas bypass) (Connector CN312: White)
1) Low pressure release function
2) High pressure release function
3) Gas balance during stop time
7. SV4 (n) (Start compensation valve of compressor)
(Connector CN311: Blue)
1) For gas balance start
2) High pressure release function
3) Low pressure release function
8. SV5 (Connector CN310: White) (for Heating model only)
1) Preventive function for high-pressure rising in heating operation
4-way valve (Connector CN317: Blue)
1) Cooling/heating exchange
2) Reverse defrost
Pulse motor valve PMV1, 2 (Connector CN300, 301: White)
1) Super heat control function in heating operation
2) Liquid line shut-down function while follower unit stops
3) Sub-cool adjustment function in cooling operation
Oil separator 1) Prevention for rapid decreasing of oil (Decreases oil flowing to the cycle)
2) Reserve function of surplus oil
Temp. sensor 1. TD1 (TD1: Connector, CN502: White, TD2: Connector, CN503: Pink)
TD2 1) Protection of compressor discharge temp. Used for release
2. TS1 (Connector CN504: White)
1) Controls super heat in heating operation
3. TE1 (Connector CN505: Green)
1) Controls defrost in heating operation
2) Controls outdoor fan in heating operation
4. TK1, TK2, TK3, TK4 TK1 Connector CN514: Black, TK2 Connector CN515: Green,
TK3 Connector CN516: Red, TK4 Connector CN523: Yellow
1) Judges oil level of the compressor
5. TL (Connector CN521: White)
1) Detects under cool in cooling operation
6. TO (Connector CN507: Yellow)
1) Detects outside temperature
Pressure sensor 1. High pressure sensor (Connector CN501: Red)
1) Detects high pressure and controls compressor capacity
2) Detects high pressure in cooling operation, and controls the fan in low ambient cooling operation
2. Low pressure sensor (Connector CN500: White)
1) Detects low pressure in cooling operation and controls compressor capacity
2) Detects low pressure in heating operation, and controls the super heat
Heater Compressor case heater (Compressor 1 Connector CN316: White, Compressor 2 Connector CN315: Blue)
1) Prevents liquid accumulation to compressor
Accumulator case heater (Connector CN321: Red)
1) Prevents liquid accumulation to accumulator
Balance pipe 1) Oil balancing in each outdoor unit

8 -4
8 Refrigerant cycle diagram

Model : MMY-MAP0804*, MAP1004*, MAP1204*, MAP1404*, MAP1604*


Functional part name Functional outline
Solenoid valve 1. SV3A (Connector CN321: White)
1) Supplies oil reserved in the oil tank during ON time.
2. SV3B (Connector CN321: White)
1) Returns oil supplied in the balance pipe to the compressor.
3. SV3C (Connector CN321: White)
1) Pressurizes oil reserved in the oil tank during ON time.
4. SV3D (Connector CN322: White)
1) Reserves oil in the oil separator during OFF time.
2) Returns oil reserved in the oil separator to the compressor during ON time.
5. SV3E (Connector CN322: White)
1) Turns on during operation and balances oil between the compressors.
6. SV3F (Connector CN323: White)
1) Controls oil level balances between compressors.
7. SV2 (Hot gas bypass) (Connector CN311: White)
1) Low pressure release function
2) High pressure release function
3) Gas balance during stop time
8. SV41 (Start compensation valve of compressor)
SV42 (Connector : SV41->CN312: Bule, SV42->CN312: Bule, SV43->CN313: Red)
SV43 1) For gas balance start
SV44 2) High pressure release function
3) Low pressure release function
9. SV5 (Connector CN314: White)
1) Preventive function for high-pressure rising in heating operation
10. SV6 (Connector CN315: White)
1) Liquid bypass function for discharge temperature release (Green bypass function)
4-way valve (Connector CN317: Blue)
1) Cooling/heating exchange
2) Reverse defrost
Pulse motor valve PMV1, 2 (Connector CN300, 301: White)
1) Super heat control function in heating operation
2) Liquid line shut-down function while follower unit stops.
3) Under-cool adjustment function in cooling operation
4) Exchange function between main and sub exchangers in cooling operation
PMV4 (Connector CN303: Red)
1) Switching function for between sub and main heat exchanger in cooling operation
2) Preventive function for high-pressure rising in heating operation
Oil separator 1) Prevention for rapid decreasing of oil (Decreases oil flowing to the cycle)
2) Reserve function of surplus oil
Temp. sensor 1. TD1 (TD1 Connector CN502: White, TD2 Connector CN503: Pink, TD3 Connector CN504: Bule)
TD2 1) Protection of compressor discharge temperature
TD3 2) Use for discharge temperature release
2. TS1 (Connector CN505: White)
1) Controls super heat in heating operation
3. TE1 (Connector CN520: Green)
1) Controls defrost in heating operation
2) Controls outdoor fan in heating operation
4. TE2 (Connector CN521: Red)
1) Controls exchange function between main and sub exchangers
5. TK1, TK2, TK3, (TK1 Connector CN531: Black, TK2 Connector CN532: Green, TK3 Connector CN533: Red,
TK4, TK5 TK4 Connector CN534: Yellow, TK5 Connector CN535: Red)
1) Judges oil level of the compressor
6. TL (Connector CN523: White)
1) Detects under cool in cooling operation
7. TO (Connector CN507: Yellow)
1)Detects outside temperature
Pressure sensor 1. High pressure sensor (Connector CN501: Red)
1) Detects high pressure and controls compressor capacity
2) Detects high pressure in cooling operation, and controls the fan in low ambient cooling operation
3) Detects under cool of indoor unit in heating operation
2. Low pressure sensor (Connector CN500: White)
1) Detects low pressure in cooling operation and controls compressor capacity
2) Detects low pressure in heating operation, and controls the super heat
Heater Compressor case heater (Compressure 1 Connector CN331: White, Compressure 2 Connector CN332: Bule,
Compressure 3 Connector CN333: Black)
1) Prevents liquid accumulation to compressure
Accumulator case heater (Connector CN334: Red)
1) Prevents liquid accumulation to accumulator
Balance pipe 1) Oil balancing in each outdoor unit

8 -5
8 Refrigerant cycle diagram

8-3. Indoor Unit


Liquid side Gas side

Strainer
Capillary Tube

Air heat exchager


at indoor side

Pulse
Motor
Valve
Sensor
Fan
Sensor (TCJ)
(TC2)
Sensor
(TC1)
㧹 Fan Motor
Sensor
(TA)

(Note) MMU-AP0074YH-E to AP0124YH-E type iar conditioners have no TC2 sensor.

Functional part name Functional outline


Pulse Motor Valve PMV (Connector CN082 (6P): Blue)
1) Controls super heat in cooling operation
2) Controls under cool in heating operation
3) Recovers refrigerant oil in cooling operation
4) Recovers refrigerant oil in heating operation
Temp. sensor 1.TA (Connector CN104 (2P): Yellow)
1) Detects indoor suction temperature
2.TC1 (Connector CN100 (3P): Brown)
1) Controls PMV super heat in cooling operation
3.TC2 (Connector CN101 (2P): Black)
1) Controls PMV under cool in heating operation
4.TCJ (Connector CN102 (2P): Red)
1) Controls PMV super heat in cooling operation
2) [MMU-AP0071 to AP0121YH only]
Controls PMV under cool in heating operation

8 -6
8 Refrigerant cycle diagram

8-4. COMBINED REFRIGERATION CYCLE


(Please refer to SMMS's manual for 5HP and 6HP units of SMMS.)
8-4-1. Normal Operation (COOLING mode, DEFROST mode)
High Outside Air Temperature (Roughly 20 °C or Above)

Pressure sensor
(low pressure)

Pressure sensor
(low pressure)

Tank

Tank

2
1

Note : In DEFROST mode, PMV4 also opens.

Normal refrigerant line

The "header unit" is the outdoor unit to which the indoor-outdoor communication line is con-
nected. All other outdoor units are called "follower units".

8 -7
8 Refrigerant cycle diagram

8-4-2.Normal Operation (COOLING mode, DEFROST mode)


Low Outside Air Temperature (Roughly Below 20 °C)
Header Unit (MMY-MAP1604*) Follower Unit (MMY-MAP1204*)

FM FM

TO TO

PMV1
PMV2

TE1
TE1
PMV4 TE2 SV

SV5
PMV1
4- way Valve PMV2 4- way Valve

Pd sensor
TS1 TS1

SV6 SV
Pd sensor Pressure sensor
(low pressure)
SV
SV
TL

SV2 Pressure sensor


TL SV3D O. S. (low pressure) SV2
O. S.
SV SV3D
SV

SV41 SV SV4 SV SV42


Liquid
Tank SV SV SV42 SV Accumlator
TD1 TD2
Liquid HPS HPS
SV3C SV43 Accumlator
Tank SV3C
TD1 HPS HPS TD2 TD3
SV

SV
HPS

Compressor
Compressor
A3 TK4

2
1
TK4
Compressor

Compressor

Compressor
1

TK1 TK2

TK1 TK2
TK3

SV
SV3E TK5

TK5
SV

SV3E
SV SV3F SV3A SV

SV SV3B
SV

SV3A
SV SV3B

Balance Pipe
Liquid Pipe

Gas Pipe

Gas Pipe

Liquid Pipe

PMV PMV PMV PMV

TC1 TC1 TC1 TC1


TC2 TC2 TC2 TC2
TCJ TCJ TCJ TCJ

Indoor Unit
NOTE
The "header unit" is the outdoor unit to which the indoor-outdoor
High pressure gas or condensate liquid refrigerant communication line is connected. All other outdoor units are
called "follower units".
Evaporative gas refrigerant (Low pressure gas)

Normal refrigerant line

(Example : 28HP system (16HP+12HP))

8 -8
8 Refrigerant cycle diagram

8-4-3.Normal Operation (HEAT mode)

Header Unit (MMY-MAP1604*) Follower Unit (MMY-MAP1204*)

FM FM

TO TO

PMV1
PMV

TE1
TE1
PMV4 TE2 SV

PMV1 SV5

4- way Valve PMV2 4- way Valve

Pd sensor
TS1 TS1

SV6 SV

Pd sensor Pressure sensor


(low pressure)
SV
SV
TL
SV2 Pressure sensor
TL SV3D O. S.
(low pressure) SV2
SV
SV3D O. S.

SV

SV41
SV SV41 SV SV42
Liquid
Tank SV SV SV42 SV Accumlator
TD1 TD2
Liquid HPS HPS
SV3C SV43 SV3C Accumlator
TD1 HPS HPS TD2 TD3 Tank
SV

SV
HPS

Compressor
Compressor
A3 TK4

2
1
TK4
Compressor

Compressor

Compressor
1

TK1 TK2

TK1 TK2
TK3

SV
SV3E TK5

TK5
SV3E
SV

SV SV3F
SV
SV3A
SV SV3B
SV

SV3A
SV SV3B

Balance Pipe
Liquid Pipe

Gas Pipe

Gas Pipe

Liquid Pipe

PMV PMV PMV PMV

TC1 TC1 TC1 TC1


TC2 TC2 TC2 TC
TC TCJ TCJ TCJ

Indoor Unit

High pressure gas or condensate liquid refrigerant


Evaporative gas refrigerant (Low pressure gas)

Normal refrigerant line

NOTE
The "header unit" is the outdoor unit to which the indoor-outdoor communication line is con-
nected. All other outdoor units are called "follower units".
(Example : 28HP system (16HP+12HP))

8 -9
8 Refrigerant cycle diagram

8-4-4. Emergency Operation (Cooling Operation under Header Outdoor Unit Backup Scenario)

Set Up as Temporary
Header Unit during
Emergency Operation
Leakage from PMV :
Liquid-side service
valve = Full closure. Header Unit (MMY-MAP1604*) Failure Follower Unit (MMY-MAP1604*)

FM FM

TO TO

PMV1 PMV1
PMV2 PMV2

TE1 TE1
PMV4 TE2 PMV4 TE2

4- way Valve 4- way Valve

Pd sensor Pd sensor
TS1 TS1
SV6 SV SV6 SV

SV SV

SV2 Pressure sensor Pressure sensor


TL (low pressure) TL SV2 (low pressure)
SV3D O. S. SV3D O. S.
SV SV

SV41 SV41
Liquid Liquid
Tank SV SV
SV42 SV Accumlator Tank SV SV SV42 SV Accumlator
SV3C SV3C
SV43 SV43
TD1 HPS HPS TD2 TD3 TD1 HPS HPS TD2 TD3
SV

SV
HPS HPS

TK4
Compressor
TK4

Compressor
Compressor

Compressor

Compressor

Compressor
2
1
1

3
TK1 TK2 TK1 TK2 TK3
TK3

TK5 TK5
SV

SV

SV3E SV3E
SV SV3F SV SV3F
SV

SV

SV3A SV3A
SV SV3B SV SV3B

Balance Pipe
Liquid Pipe

Gas Pipe
Gas-side service Balance pipe packed
valve = Full closure valve = Full closure Ga Pipe

Liquid Pipe

PMV PMV PMV PMV

TC1 TC1 TC1 TC1


TC2 TC2 TC2 TC2
TCJ TCJ TCJ TCJ

Indoor Unit

High pressure gas or condensate liquid refrigerant


Evaporative gas refrigerant (Low pressure gas)
Normal refrigerant line
Refrigerant recovery line

NOTE
The "header unit" is the outdoor unit to which the indoor-outdoor communication line is con-
nected. All other outdoor units are called "follower units".
(Example :32HP system (16HP+16HP))

8 -10
8 Refrigerant cycle diagram

8-4-5. Emergency Operation (Heating Operation under Header Outdoor Unit Backup Scenario)

Set Up as Temporary
Header Unit during
Emergency Operation
Leakage from PMV :
Liquid-side service
valve = Full closure. Header Unit (MMY-MAP1604*) Failure Follower Unit (MMY-MAP1604*)

FM FM

TO TO

PMV1 PMV1
PMV2 PMV

TE1 TE1
PMV4 TE2 PMV TE2

4- way Valve 4- way Valve

Pd sensor Pd sensor
TS1 TS1
SV6 SV SV6 SV

SV SV

SV2 Pressure sensor SV2 Pressure sensor


TL SV3D O. S.
(low pressure) TL SV3D O. S.
(low pressure)
SV SV

SV41 SV41
Liquid
Tank SV SV SV42 SV Accumlator SV SV SV42 SV Accumlator
SV3C Liquid SV3C
SV43 SV43
TD1 HPS HPS TD2 Tank TD1 HPS HPS TD2
TD3 TD3
SV

SV
HPS HPS

Compressor
TK4
Compressor

Compressor

Compressor
TK4

Compressor
Compressor
1

2
3

3
TK1 TK2 TK3 TK1 TK2
TK3

TK5 TK5
SV

SV

SV3 SV3E
SV SV3F SV SV3F
SV

SV

SV3A SV3A
SV SV3B SV SV3B

Balance Pipe
Liquid Pipe

Gas Pipe
Gas-side service Balance pipe packed
valve = Full closure valve = Full closure Gas Pipe

Liquid Pipe

PMV PMV PMV PMV

TC1 TC1 TC1 TC1


TC2 TC2 TC2 TC2
TCJ TCJ TCJ TCJ

Indoor Unit

High pressure gas or condensate liquid refrigerant


Evaporative gas refrigerant (Low pressure gas)
Normal refrigerant line
Refrigerant recovery line

NOTE
The "header unit" is the outdoor unit to which the indoor-outdoor communication line is con-
nected. All other outdoor units are called "follower units".
(Example :32HP system (16HP+16HP))

8 -11
8 Refrigerant cycle diagram

8-4-6. Refrigerant Recovery from Failed Outdoor Unit (Pump-Down Operation under Follower Out-
door Unit Backup Scenario)

Header Unit (MMY-MAP1604*)


Failure Follower Unit (MMY-MAP1204*)

FM FM

TO TO

PMV1
PMV2

TE1
TE1
PMV4 TE2 SV

SV5
PMV1
4- way Valve PMV2 4- way Valve

Pd sensor TS1
TS1
SV6 Bypass line
SV

Pd sensor Pressure sensor


SV (low pressure)
SV
TL

SV2 Pressure sensor


TL SV3D O. S.
(low pressure) SV2
SV3D O. S.
SV
SV

SV41 SV SV41 SV SV42


Liquid
Tank SV SV SV42 SV Accumlator
TD1 TD2
SV3 Liquid HPS HPS
SV43 SV3C Accumlator
TD1 HPS HPS TD2 Tank
TD3
SV

SV
HPS

Compressor
Compressor
A3 TK4

2
TK
Compressor

Compressor

Compressor
1

TK1 TK2

TK1 TK2
TK3
SV

SV3E TK5

TK5
SV

SV3E
SV SV3F
SV

SV3A
SV SV3B
SV

SV3A
SV SV3B

Balance pipe packed valve = Full opening


Balance Pipe
Liquid Pipe
Gas-side service valve = Full opening
→ Full closure 10 minutes after system startup
Gas Pipe
liquid-side service valve = Full closure
Gas Pipe

Liquid Pipe

PMV PMV PMV PMV

TC1 TC1 TC1 TC1


TC2 TC2 TC2 TC2
TCJ TCJ TCJ TCJ

Indoor Unit

High pressure gas or condensate liquid refrigerant


Evaporative gas refrigerant (Low pressure gas)
Normal refrigerant line
Refrigerant recovery line

NOTE
The "header unit" is the outdoor unit to which the indoor-outdoor communication line is con-
nected. All other outdoor units are called "follower units".
(Example : 28HP system (16HP+12HP))

8 -12
9
SMMS-i Data book

Wiring Design
9-1.General
• Perform wiring of the power supply in conformance with the regulations of the local electric company.
• For cabling of the power supply of the indoor unit and the inter-unit cabling between indoor and outdoor units,
refer to the Installation Manual of indoor unit.
• Never connect power supply to the terminal block (U1, U2, U3, U4, U5, U6) for control wiring.
(The equipment breaks down.)
• Arrange the cables so that the electric wires do not come to contact with high-temperature part of the pipe;
otherwise coating melts and an accident may be caused.
• After connecting cable to the terminal block, take off the trap and then fix the cable with cable clamp.
• Do not turn on power of the indoor unit until vacuuming of the refrigerant pipe will finish.
9-2.Summary of wiring design
Design of outdoor unit power supply • Select the wiring depending on MCA.
• Be sure to set the earth leakage breaker from the viewpoint of safety.

Design of indoor unit power supply • Select the wiring depending on total current of indoor units.
• Determine the wire size for the length rules.
• Be sure to set the earth leakage breaker from the viewpoint of safety.

Design of control wiring • Design each control wiring.


Between outdoor and indoor units,
Between indoor units/outdoor units
Between indoor unit and remote controller, central control, BMS
• Select the wire size and type depending on the length rules.

9-3.Electrical wiring design

Earth
3-phase
380-415V, 50Hz
or 380V, 60Hz
Earth leakage breaker
hand switch
Outdoor
power source
Pull box
Indoor
power source
Single phase
220-240V 50Hz
or 220V 60Hz
Earth leakage breaker
Model Outdoor power supply power switch
MMY-MAP/AP XXXX HT8,
3phese, 380-415V, 50Hz
HT8, T8, T8
MMY-MAP/AP XXXX HT7 3phese, 380V, 60Hz

• Wiring size must comply with the applicable local and national code.
• Determine the wire size for the indoor unit according to the number of connected indoor units downstream.

9-4.Outdoor unit power supply


• Select the power supply cabling and fuse of each
outdoor unit from the following specifications: NO GOOD
cable 4-core, in conformance with Design 60245
IEC 66
• Do not connect the outdoor units by crossing
outside of them, but connect them via the terminal L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3

block (L1, L2, L3, N). Outdoor power supply


3-phase 380-415V, 50Hz
380V 60Hz

9 -1
Outdoor unit data
Standard model * : SMMS model
Power Supply Voltage Range Compressor
Heat Pump Model Cooling Only Model Fan Motor MCA MOCP
Type HP Phase and Min. Max Unit No.1 Unit No.2 Unit No.3 Unit No.4
MMY- MMY- Nominal Voltage
frequency (V) (V) (kW) (kW) (kW) (kW) (kW) (A) (A)
5* MAP0501HT8* MAP0501T8* 3N~ 50Hz 380-400-415V 342 456 1.1 x 2 0.6 16.5 20
6* MAP0601HT8* MAP0601T8* 3N~ 50Hz 380-400-415V 342 456 1.4 x 2 0.6 16.5 20
8 MAP0804HT8 MAP0804T8 3N~ 50Hz 380-400-415V 342 456 2.3 x 2 1.0 23.5 32
10 MAP1004HT8 MAP1004T8 3N~ 50Hz 380-400-415V 342 456 3.1 x 2 1.0 25.5 32
12 MAP1204HT8 MAP1204T8 3N~ 50Hz 380-400-415V 342 456 4.2 x 2 1.0 28.5 40

Single unit
14 MAP1404HT8 MAP1404T8 3N~ 50Hz 380-400-415V 342 456 3.0 x 3 1.0 33.2 40
16 MAP1604HT8 MAP1604T8 3N~ 50Hz 380-400-415V 342 456 3.6 x 3 1.0 36.5 50
18 AP1814HT8 AP1814T8 3N~ 50Hz 380-400-415V 342 456 3.1 x 2 2.3 x 2 1.0 x 2 49.0 63
9 Wiring Design

20 AP2014HT8 AP2014T8 3N~ 50Hz 380-400-415V 342 456 3.1 x 2 3.1 x 2 1.0 x 2 51.0 63
22 AP2214HT8 AP2214T8 3N~ 50Hz 380-400-415V 342 456 4.2 x 2 3.1 x 2 1.0 x 2 54.0 63
24 AP2414HT8 AP2414T8 3N~ 50Hz 380-400-415V 342 456 4.2 x 2 4.2 x 2 1.0 x 2 57.0 63
26 AP2614HT8 AP2614T8 3N~ 50Hz 380-400-415V 342 456 3.6 x 3 3.1 x 2 1.0 x 2 62.0 80
28 AP2814HT8 AP2814T8 3N~ 50Hz 380-400-415V 342 456 3.6 x 3 4.2 x 2 1.0 x 2 65.0 80
30 AP3014HT8 AP3014T8 3N~ 50Hz 380-400-415V 342 456 3.6 x 3 3.0 x 3 1.0 x 2 69.7 80
32 AP3214HT8 AP3214T8 3N~ 50Hz 380-400-415V 342 456 3.6 x 3 3.6 x 3 1.0 x 2 73.0 100
34 AP3414HT8 AP3414T8 3N~ 50Hz 380-400-415V 342 456 4.2 x 2 4.2 x 2 3.1 x 2 1.0 x 3 82.5 100
36 AP3614HT8 AP3614T8 3N~ 50Hz 380-400-415V 342 456 4.2 x 2 4.2 x 2 4.2 x 2 1.0 x 3 85.5 100
38 AP3814HT8 AP3814T8 3N~ 50Hz 380-400-415V 342 456 3.6 x 3 4.2 x 2 3.1 x 2 1.0 x 3 90.5 100
40 AP4014HT8 AP4014T8 3N~ 50Hz 380-400-415V 342 456 3.6 x 3 4.2 x 2 4.2 x 2 1.0 x 3 93.5 125
42 AP4214HT8 AP4214T8 3N~ 50Hz 380-400-415V 342 456 3.6 x 3 3.0 x 3 4.2 x 2 1.0 x 3 98.2 125

Combination of outdoor unit


44 AP4414HT8 AP4414T8 3N~ 50Hz 380-400-415V 342 456 3.6 x 3 3.6 x 3 4.2 x 2 1.0 x 3 101.5 125
46 AP4614HT8 AP4614T8 3N~ 50Hz 380-400-415V 342 456 3.6 x 3 3.6 x 3 3.0 x 3 1.0 x 3 106.2 125
48 AP4814HT8 AP4814T8 3N~ 50Hz 380-400-415V 342 456 3.6 x 3 3.6 x 3 3.6 x 3 1.0 x 3 109.5 125

9 -2
High efficiency model
Power Supply Voltage Range Compressor
Heat Pump Model Cooling Only Model Fan Motor MCA MOCP
Type HP Phase and Nominal Min. Max Unit No.1 Unit No.2 Unit No.3 Unit No.4
MMY- MMY-
frequency Voltage (V) (V) (kW) (kW) (kW) (kW) (kW) (A) (A)
16 AP1624HT8 AP1624T8 3N~ 50Hz 380-400-415V 342 456 2.3 x 2 2.3 x 2 1.0 x 2 46.9 63
24 AP2424HT8 AP2424T8 3N~ 50Hz 380-400-415V 342 456 2.3 x 2 2.3 x 2 2.3 x 2 1.0 x 3 70.4 80
26 AP2624HT8 AP2624T8 3N~ 50Hz 380-400-415V 342 456 3.1 x 2 2.3 x 2 2.3 x 2 1.0 x 3 72.4 80
28 AP2824HT8 AP2824T8 3N~ 50Hz 380-400-415V 342 456 3.1 x 2 3.1 x 2 2.3 x 2 1.0 x 3 74.5 100
30 AP3024HT8 AP3024T8 3N~ 50Hz 380-400-415V 342 456 3.1 x 2 3.1 x 2 3.1 x 2 1.0 x 3 76.5 100
32 AP3224HT8 AP324T8 3N~ 50Hz 380-400-415V 342 456 2.3 x 2 2.3 x 2 2.3 x 2 2.3 x 2 1.0 x 4 93.8 125
34 AP3424HT8 AP3424T8 3N~ 50Hz 380-400-415V 342 456 3.1 x 2 2.3 x 2 2.3 x 2 2.3 x 2 1.0 x 4 95.9 125
36 AP3624HT8 AP3624T8 3N~ 50Hz 380-400-415V 342 456 3.1 x 2 3.1 x 2 2.3 x 2 2.3 x 2 1.0 x 4 97.9 125
38 AP3824HT8 AP3824T8 3N~ 50Hz 380-400-415V 342 456 3.1 x 2 3.1 x 2 3.1 x 2 2.3 x 2 1.0 x 4 100 125
40 AP4024HT8 AP4024T8 3N~ 50Hz 380-400-415V 342 456 3.1 x 2 3.1 x 2 3.1 x 2 3.1 x 2 1.0 x 4 102 125
42 AP4224HT8 AP4224T8 3N~ 50Hz 380-400-415V 342 456 4.2 x 2 3.1 x 2 3.1 x 2 3.1 x 2 1.0 x 4 105 125
44 AP4424HT8 AP4424T8 3N~ 50Hz 380-400-415V 342 456 4.2 x 2 4.2 x 2 3.1 x 2 3.1 x 2 1.0 x 4 108 125

Combination of outdoor unit


46 AP4624HT8 AP4624T8 3N~ 50Hz 380-400-415V 342 456 4.2 x 2 4.2 x 2 4.2 x 2 3.1 x 2 1.0 x 4 111 125
48 AP4824HT8 AP4824T8 3N~ 50Hz 380-400-415V 342 456 4.2 x 2 4.2 x 2 4.2 x 2 4.2 x 2 1.0 x 4 114 125

Notes MCA : Minimum Circuit Amps


MOCP : Maximum Overcurrent Protection (Amps)
9 Wiring Design

9-5.Indoor unit power supply


• Electrical characteristics
Nominal Voltage Voltage Range Fan Motor Power Supply
Type Model
(V-Ph-Hz) Min Max kW FLA MCA MOCP
MMU-AP0092H 230-1-50 198 264 0.014 0.63 0.79 15
MMU-AP0122H 230-1-50 198 264 0.014 0.63 0.79 15
MMU-AP0152H 230-1-50 198 264 0.014 0.80 1.00 15
MMU-AP0182H 230-1-50 198 264 0.014 0.80 1.00 15
4-Way Air MMU-AP0242H 230-1-50 198 264 0.020 0.87 1.09 15
Discharge
Cassette Type MMU-AP0272H 230-1-50 198 264 0.020 0.87 1.09 15
MMU-AP0302H 230-1-50 198 264 0.020 0.87 1.09 15
MMU-AP0362H 230-1-50 198 264 0.068 1.15 1.44 15
MMU-AP0482H 230-1-50 198 264 0.072 1.15 1.44 15
MMU-AP0562H 230-1-50 198 264 0.072 1.15 1.44 15
MMU-AP0074MH-E 230-1-50 198 264 0.060 0.32 0.40 15
MMU-AP0094MH-E 230-1-50 198 264 0.060 0.35 0.44 15
Compact 4-way Cassette
MMU-AP0124MH-E 230-1-50 198 264 0.060 0.36 0.45 15
(600 x 600) Type
MMU-AP0154MH-E 230-1-50 198 264 0.060 0.48 0.60 15
MMU-AP0184MH-E 230-1-50 198 264 0.060 0.48 0.60 15
MMU-AP0072WH 230-1-50 198 264 0.020 0.32 0.40 15
MMU-AP0092WH 230-1-50 198 264 0.020 0.32 0.40 15
MMU-AP0122WH 230-1-50 198 264 0.020 0.32 0.40 15
MMU-AP0152WH 230-1-50 198 264 0.020 0.32 0.40 15
MMU-AP0182WH 230-1-50 198 264 0.030 0.70 0.88 15
2-Way Air
Discharge MMU-AP0242WH 230-1-50 198 264 0.040 0.81 1.01 15
Cassette Type
MMU-AP0272WH 230-1-50 198 264 0.040 0.81 1.01 15
MMU-AP0302WH 230-1-50 198 264 0.050 0.81 1.01 15
MMU-AP0362WH 230-1-50 198 264 0.070 0.87 1.09 15
MMU-AP0485WH 230-1-50 198 264 0.070 0.87 1.09 15
MMU-AP0562WH 230-1-50 198 264 0.070 0.87 1.09 15
MMU-AP0074YH-E 230-1-50 198 264 0.022 0.28 0.35 15
MMU-AP0094YH-E 230-1-50 198 264 0.022 0.28 0.35 15
1-Way Air MMU-AP0124YH-E 230-1-50 198 264 0.022 0.28 0.35 15
Discharge
Cassette Type MMU-AP0154SH-E 230-1-50 198 264 0.030 0.40 0.49 15
MMU-AP0184SH-E 230-1-50 198 264 0.030 0.42 0.53 15
MMU-AP0244SH-E 230-1-50 198 264 0.030 0.71 0.88 15
MMD-AP0074BH-E 230-1-50 198 264 0.120 0.33 0.41 15
MMD-AP0094BH-E 230-1-50 198 264 0.120 0.33 0.41 15
MMD-AP0124BH-E 230-1-50 198 264 0.120 0.39 0.49 15
MMD-AP0154BH-E 230-1-50 198 264 0.120 0.39 0.49 15
MMD-AP0184BH-E 230-1-50 198 264 0.120 0.50 0.62 15
Concealed Duct Type MMD-AP0244BH-E 230-1-50 198 264 0.120 0.60 0.75 15
MMD-AP0274BH-E 230-1-50 198 264 0.120 0.60 0.75 15
MMD-AP0304BH-E 230-1-50 198 264 0.120 0.70 0.88 15
MMD-AP0364BH-E 230-1-50 198 264 0.120 0.96 1.20 15
MMD-AP0484BH-E 230-1-50 198 264 0.120 1.13 1.41 15
MMD-AP0564BH-E 230-1-50 198 264 0.120 1.13 1.41 15
MMD-AP0184H-E 230-1-50 198 264 0.160 0.93 1.16 15
MMD-AP0244H-E 230-1-50 198 264 0.160 1.55 1.94 15
MMD-AP0274H-E 230-1-50 198 264 0.160 1.55 1.94 15
Concealed Duct
High Static MMD-AP0364H-E 230-1-50 198 264 0.260 1.87 2.34 15
Pressure Type
MMD-AP0484H-E 230-1-50 198 264 0.260 2.12 2.65 15
MMD-AP0724H-E 230-1-50 198 264 0.370 x 3 6.04 7.55 15
MMD-AP0964H-E 230-1-50 198 264 0.370 x 3 6.35 7.94 15
MMD-AP0074SPH-E 230-1-50 198 264 0.060 0.35 0.44 15
MMD-AP0094SPH-E 230-1-50 198 264 0.060 0.35 0.44 15
Slim Duct Type MMD-AP0124SPH-E 230-1-50 198 264 0.060 0.37 0.47 15
MMD-AP0154SPH-E 230-1-50 198 264 0.060 0.38 0.48 15
MMD-AP0184SPH-E 230-1-50 198 264 0.060 0.47 0.59 15
MMC-AP0154H-E 230-1-50 198 264 0.030 0.33 0.41 15
MMC-AP0184H-E 230-1-50 198 264 0.030 0.37 0.46 15
MMC-AP0244H-E 230-1-50 198 264 0.040 0.48 0.60 15
Ceiling Type
MMC-AP0274H-E 230-1-50 198 264 0.040 0.48 0.60 15
MMC-AP0364H-E 230-1-50 198 264 0.080 0.90 1.13 15
MMC-AP0484H-E 230-1-50 198 264 0.080 0.96 1.20 15

9 -3
9 Wiring Design

Nominal Voltage Voltage Range Fan Motor Power Supply


Type Model
(V-Ph-Hz) Min Max kW FLA MCA MOCP
MMK-AP0073H 230-1-50 198 264 0.030 0.20 0.22 15
MMK-AP0093H 230-1-50 198 264 0.030 0.22 0.24 15

High-wall Type MMK-AP0123H 230-1-50 198 264 0.030 0.22 0.24 15


(3 series) MMK-AP0153H 230-1-50 198 264 0.030 0.37 0.40 15
MMK-AP0183H 230-1-50 198 264 0.030 0.37 0.40 15
MMK-AP0243H 230-1-50 198 264 0.030 0.43 0.47 15
MML-AP0074H-E 230-1-50 198 264 0.045 0.30 0.37 15
MML-AP0094H-E 230-1-50 198 264 0.045 0.30 0.37 15

Floor Standing MML-AP0124H-E 230-1-50 198 264 0.045 0.49 0.62 15


Cabinet Type MML-AP0154H-E 230-1-50 198 264 0.045 0.49 0.62 15
MML-AP0184H-E 230-1-50 198 264 0.070 0.54 0.68 15
MML-AP0244H-E 230-1-50 198 264 0.070 0.54 0.68 15
MML-AP0074BH-E 230-1-50 198 264 0.019 0.29 0.36 15
MML-AP0094BH-E 230-1-50 198 264 0.019 0.29 0.36 15

Floor Standing MML-AP0124BH-E 230-1-50 198 264 0.019 0.29 0.36 15


Concealed Type MML-AP0154BH-E 230-1-50 198 264 0.070 0.52 0.65 15
MML-AP0184BH-E 230-1-50 198 264 0.070 0.52 0.65 15
MML-AP0244BH-E 230-1-50 198 264 0.070 0.53 0.66 15
MMF-AP0154H-E 230-1-50 198 264 0.037 0.77 0.96 15
MMF-AP0184H-E 230-1-50 198 264 0.037 0.77 0.96 15
MMF-AP0244H-E 230-1-50 198 264 0.063 1.01 1.27 15
Floor Standing Type MMF-AP0274H-E 230-1-50 198 264 0.063 1.01 1.27 15
MMF-AP0364H-E 230-1-50 198 264 0.110 1.48 1.85 15
MMF-AP0484H-E 230-1-50 198 264 0.160 1.84 2.30 15
MMF-AP0564H-E 230-1-50 198 264 0.160 1.84 2.30 15
MMD-AP0481HFE 230-1-50 198 264 0.160 0.28 0.35 15
Fresh Air Intake Indoor Unit
MMD-AP0721HFE 230-1-50 198 264 0.16 x 2 0.45 0.56 15
Type
MMD-AP0961HFE 230-1-50 198 264 0.16 x 2 0.52 0.65 15
MML-AP0074NH-E 230-1-50 198 264 0.041 0.21 0.26 15
MML-AP0094NH-E 230-1-50 198 264 0.041 0.21 0.26 15
Console Type MML-AP0124NH-E 230-1-50 198 264 0.041 0.25 0.31 15
MML-AP0154NH-E 230-1-50 198 264 0.041 0.32 0.40 15
MML-AP0184NH-E 230-1-50 198 264 0.041 0.46 0.58 15
MMD-VN502HEXE 230-1-50 198 264 0.124 x 2 1.5 1.7 15
Air to Air Heat exchanger with
MMD-VN802HEXE 230-1-50 198 264 0.217 x 2 2.6 3.0 15
DX-coil Type
MMD-VN1002HEXE 230-1-50 198 264 0.284 x 2 2.9 3.5 15

9 -4
9 Wiring Design

• Wiring size
Must be independent from the outdoor unit power supply
Item Power supply wiring
Model Wire size
All models of indoor units 2.0mm2 (AWG#14) Max. 20m 3.5mm2 (AWG#12) Max. 50m

NOTE:
The above connecting lengths stated in the table, indicate the length from the isolator to the outdoor unit. When the
power supply of the indoor units are connected in parallel, it is assumed that no more than a 2% voltage drop will occur. If
the connecting length is to exceed the stated lengths, select a suitable wire in accordance with the local wiring standards.

9-6.Design of control wiring


• Summary of control wiring
Header outdoor Follower outdoor

Central control U1 U2 U3 U4 U5 U6 U1 U2 U3 U4 U5 U6

device

U1 U2
U3 U4
Control wiring between outdoor units (Shield wire)

Control wiring between indoor and outdoor units (Shield wire)

Control wiring between indoor units (Shield wire)

U1 U2 A B U1 U2 A B U1 U2 A B U1 U2 A B

Indoor unit Indoor unit Indoor unit Indoor unit

A B A B A B

Remote controller Remote controller Remote controller


(Group control)

9 -5
9 Wiring Design

• Restriction of control wiring


Be sure to keep the rule of below tables about size and length of control wiring.
Central control
device
U1 U2 Super modular multi system
U3 U4
Table-1
L4
Header Header Follower Follower Follower Header Follower
unit unit unit unit unit unit unit
U3 U4 U3 U4 U3 U4 U3 U4 U3 U4 U3 U4 U3 U4
Outdoor unit
U1 U2 U5 U6 U1 U2 U5 U6 U1 U2 U5 U6 U1 U2 U5 U6 U1 U2 U5 U6 U1 U2 U5 U6 U1 U2 U5 U6

L1 L5 Table-1 Table-2

L2 L3

U1 U2 U1 U2 U1 U2 U1 U2 U1 U2 U1 U2 U1 U2 U1 U2
Indoor unit
A B A B A B A B A B A B A B A B

Table-3
L7
L6
Remote Remote controller
controller Remote controller

Table-1 Control wiring between indoor and outdoor units (L1, L2, L3),
Central control wiring (L4)
Wiring 2-core, non-polarity
Type Shield wire
Size/Length 1.25 mm2: Up to 1000 m/2.0 mm2: Up to 2000 m (*1)

Note (*1): Total length of control wiring length for all refrigerant circuits ( L1 + L2 + L3 + L4)
Table-2 Control wiring between outdoor units (L5)
Wiring 2-core, non-polarity
Type Shield wire
Size/Length 1.25 mm2 to 2.0 mm2/Up to 100 m (L5)

Table-3 Remote controller wiring (L6, L7)


Wire 2-core
Size 0.5 mm2 to 2.0 mm2
• Up to 500 m (L6 + L7)
Length • Up 400 m in case of wireless remote controller in group control.
• Up to 200 m total length of control wiring between indoor units (L6)

• Group Operation through a Remote Controller


Group operation of multiple indoor units (8 units) through a single remote controller switch
Indoor unit No.1 No.2 No.3 No.4 No.7 No.8

AB AB AB AB AB AB

(A.B)
Remote
controller

9 -6
TCB-IFCB640TLE
Analog I/F (DC voltage) DC line Daiseikai
TCB-IFLN642TLE/T
10
TP
Open System TCB-IFMB640TLE TCC-LINK General Purpose I/F
TCB-IFCG1TLE
RS485 Sensors/switch/key/actuator
TCS-Net Relay Interface
RS485

BMS-LSV6E BACnet Server BMS-LSV4E


BMS-STBN08E BACnet Server Software TCB-KBOS1E
Power peak-out control board TCB-PCOS1E2
RS485 Energy monitoring TCB-PCDM4E SMMS-i for SDI4 only Super Digital Inverter
Relay I/F Power Meter Digital Inverter
External sw
*Monitoring Touch-screen Controller
Controls
SMMS-i Data book

Mini-SMMS
*Remote control BMS-TP0641ACE Snowfall /External master ON/OFF/ /Night
*Schedule operation BMS-TP5121ACE operation/Operation mode selection board
Digital I/O Relay I/F Cable for connector
BMS-TP0641PWE TCB-PCMO4E
*Error code indication I/O CN32(TCB-KBCN32VEE)
BMS-TP5121PWE “1:1 model” connection
Device CN60(TCB-KBCN60OPE)
*Alarm list indication TCC-Link Interface CN61(TCB-KBCN61HAE)
*Monthly report Smart Manager Energy monitoring Relay I/F TCB-PCNT30TLE2 CN70(TCB-KBCN70OAE)
*Energy monitoring data etc. BMS-SM1280HTLE BMS-IFWH5E Power Error output control board Compressor CN73(TCB-KBCN73DEE)
Meter operation /system operation ratio(SMMS-i only) CN80(TCB-KBCN80EXE)
RS485 TCB-PCIN4E

TCC-LINK
Digital I/O Relay I/F
Intranet BMS-IFDD03E TCC-LINK

RS485 I/O
Device
TCC-LINK Alarm Status output Remote ON/OFF Air to Air
Webserver RS485 ON/OFF Command TCB IFCB-4E2 Heat
Exchanger

10 -1
BMS-WB2561PWE TCC-LINK
10-1. Outline of application Control chart

with DX coil

Cable for connector


CN32(TCB-KBCN32VEE)
Energy monitoring Relay I/F CN60(TCB-KBCN60OPE)
Digital I/O Relay I/F GSM Modem
CN61(TCB-KBCN61HAE)
TCC-LINK CN70(TCB-KBCN70OAE)
CN73(TCB-KBCN73DEE)
CN80(TCB-KBCN80EXE)
RS485 GSM REMOTE CONTROL
Batch drive, error output TCB-IFGSM1E
BMS-WB01GTE Master Server Follower
remote Header
BMS-WB2561PWE Gateway Master ON/OFF signal remote
RS485

RS485
TCC-LINK Central remote controller
TCB-SC642TLE2
BMS-WB2561PWE Gateway

Energy monitoring Relay I/F


Digital I/O Relay I/F ON-OFF controller Compliant Manager
Wired remote controller Wired remote controller Simple remote controller Wireless remote Remote Sensor
TCB-CC163TLE2 BMS-CM1280TLE
Power peak-out control signal with schedule timer RBC-AMT32E RBC-AS21E2 controller TCB-TC21LE2
Master ON/OFF signal RBC-AMS41E
Error/operation output
Compressor operation /system
operation ratio (SMMS-i only)

Air-conditioning Management System Schedule timer


TCB-EXS21TLE
Lite-Vision plus Wired remote controller for Air to
Remote Controller Air Heat Exchanger and Air to Air
RBC-AMS51E-EN/ES Heat Exchanger with DX coil unit
NRC-01HE
10 Controls

10-2. Applications for indoor remote controller


Basic function System diagram Model

Main remote Wireless remote • Wired remote controller


controller controller RBC-AMT32E
• Wired remote controller with
schedule timer
RBC-AMS41E
Individual control
Indoor Indoor RBC-AMS51E-EN/ES
10- Air conditioner is
unit unit • Simple wired remote controller
2-1 individually operated
RBC-AS21E2
at a distance.

(((
Receiver unit • Wireless remote controller kit
RBC-AX31U(W)-E
Remote Wireless RBC-AX31U(WS)-E
controller remote
RBC-AX22CE2
controller
TCB-AX21E2

Max.8 indoor units • Wired remote controller


RBC-AMT32E
• Wired remote controller with
GROUP control schedule timer
One remote Indoor Indoor Indoor Indoor RBC-AMS41E
controller can control unit unit unit unit RBC-AMS51E-EN/ES
10-
a group of up to a • Simple wired remote controller
2-2
max. 8 indoor units. RBC-AS21E2
Operating on the Remote • Wireless remote controller kit
same setting. controller RBC-AX31U(W)-E
RBC-AX31U(WS)-E
RBC-AX22CE2
TCB-AX21E2

Wired system Wired & Wireless combination


control
(Either one of the two controllers
can be set as side control.)
Indoor
unit • Wired remote controller
Indoor RBC-AMT32E
unit • Wired remote controller with
Remote Remote schedule timer
Two remote control RBC-AMS41E
((

controller controller
(

Air conditioner is Remote Wireless RBC-AMS51E-EN/ES


10- Header Follower
controlled by two controller remote • Simple wired remote controller
2-3 Wireless system controller
remote controllers in RBC-AS21E2
two locations. • Wireless remote controller kit
RBC-AX31U(W)-E
Indoor When two wireless RBC-AX31U(WS)-E
unit remote controllers are RBC-AX22CE2
operated at the same TCB-AX21E2
(((

((

time, the communication


(

Wireless Wireless are not done by


remote remote interference of both
controller 1 controller 2
infrared rays.
Header Follower
Schedule timer mode Weekly timer mode

SW setting at • Wired remote controller


Control by Indoor Indoor
schedule timer RBC-AMT32E
schedule timer unit unit
10- is necessary. • Central remote controller
Schedule timer mode
2-4 TCC-LINK TCB-SC642TLE2
and Weekly timer
• Schedule timer
mode
TCB-EXS21TLE
Central Schedule Wired Schedule
remote timer remote timer
controller controller

10 -2
10 Controls

10-3. Application control for central remote controller


Basic function System diagram Model
• Central remote
Header
unit controller
Outdoor unit
U3, U4
TCB-SC642TLE2
Line-3
U5, U6 Indoor unit BMS-CM1280TLE
U1, U2
• ON-OFF controller
Zone
4 TCB-CC163TLE2
Header Indoor remote controller
unit
U3, U4 Outdoor unit

U5, U6 Line-2 Indoor unit

Zone U1, U2
3

Zone
2

Header Indoor remote controller


unit
U3, U4 Outdoor unit
Line-1 Indoor unit

Zone U1, U2
1

Power Central Indoor remote controller Indoor remote


supply remote controller
Single phase
controller
220/230/240V • Wired remote controller
RBC-AMT32E
Central management Function of central remote controller • Wired remote controller
10-
controllers for with schedule timer
3-1 TCB-SC642TLE2
64/128 units RBC-AMS41E
• Individual control up to 64 indoor units
RBC-AMS51E-EN/ES
• Individual control for max. 64 indoor units divided in to 4 zones
• Simple wired remote
(Up to 16 indoor units for each zone)
controller
• Up to 16 outdoor header units are connectable.
RBC-AS21E2
• Setting for one of 1 to 4 zones is available.
• Wireless remote
controller kit
BMS-CM1280TLE
• Individual control of up to (64 indoor units)*2 TCC-LINK buses
• Individual control of up to (64 indoor units divided 1 to 64
zone)*2 TCC-LINK buses (Up to 64 indoor units for each zone)
• Up to 16 outdoor header units are connectable per 1 TCC-LINK
bus
• Setting for (one of 1 to 64 zones)*2ch is available.
• Setting for (one of 1 to 64 groups)*2ch is available.
• Return back setting

Common
• Usable with other central control devices (Up to 10 central
control devices in one control circuit)
• Central control 4 mode
4 selectable settings to restrict individual operation of remote
controller.
• Two selectable mode
Central controller mode/Remote controller mode
• Master/Sub setting possible

10 -3
10 Controls

Basic function System diagram Model


• Central remote
controller
U3, U4 Outdoor unit TCB-SC642TLE
Indoor unit
U1, U2 BMS-CM1280TLE
• ON-OFF controller
TCB-CC163TLE2
+
Central remote controller • Schedule timer
Indoor remote controller
+ TBC-EXS21TLE
Schedule timer Single phase
TCC LINK line
Weekly operation 220/230/240V Indoor remote
10-
schedule can be set Power Schedule timer controller
3-2 supply
by connecting a Central Power line • Wired remote controller
schedule timer to remote controller RBC-AMT32E
the central remote • Wired remote controller
controller with schedule timer
RBC-AMS41E
RBC-AMS51E-EN/ES
• Simple wired remote
controller
RBC-AS21E2
• Wireless remote
controller kit
• Central remote
U3, U4
Outdoor unit controller
U1, U2 TCB-SC642TLE2
BMS-CM1280TLE
Power • ON-OFF controller
Indoor unit
supply TCB-CC163TLE2
Central remote controller
Single phase Indoor remote
220/230/240V Even when grouping operation is performed by controller
connecting multiple indoor units to 1 line, the • Wired remote controller
indoor remote controller is required. RBC-AMT32E
Either one of the two Example of grouping operation
• Wired remote controller
controllers can be set as U3, U4
Outdoor unit with schedule timer
side control without indoor
U1, U2 RBC-AMS41E
remote controller.
RBC-AMS51E-EN/ES
10- Please prepare a
• Wireless remote
3-3 wired remote
controller kit
controller for Power (Group)
supply
operation confirming Indoor remote controller is
of indoor unit in required Available
Single phase Central remote controller
advance.
220/230/240V

U3, U4
Outdoor unit
U1, U2

Power (Group)
supply
Available
Single phase Central remote controller
220/230/240

10 -4
10 Controls

Basic function System diagram Model


• Central remote
controller
TCB-SC642TLE2
BMS-CM1280TLE
• ON-OFF controller
Power Central remote controller TCB-CC163TLE2
supply • ‘‘1 : 1 model’’
Single phase connection interface
U3, U4
220/230/240V TCB-PCNT30TLE2
High-wall type for
Header unit SMMS-i
*1 SDI/DI is not
necessary this.
U1, U2 Indoor unit “1 : 1 model” 4-way 4series and
connection
interface compact 4-way
cassette type for
10- Central management SDI/DI need the
3-4 control with ‘‘1 : 1 model’’ metal fitting kit
Indoor remote controller (TCB-PX30MUE).

Indoor remote
controller
* TOSHIBA Digital Inverter System and Super Digital Inverter • Wired remote controller
System RBC-AMT32E
• Wired remote controller
with schedule timer
RBC-AMS41E
RBC-AMS51E-EN/ES
• Simple wired remote
controller
RBC-AS21E2
• Wireless remote
controller kit

10 -5
10 Controls

10-4. Application controls by optional P.C. board of outdoor unit


Model
Appearance Function
name
[1] Power peak-cut Control

• Purpose: Limiting air conditioning performance with external signals and


decreasing the peak power consumption.
• Feature
The upper limit capacity of the outdoor unit is restricted based on the outdoor power
peak selected setting.

Standard Specifications
(Wiring example)
Size : 71 x 85 (mm) L1: Display lamp suring power peak cut control
Header outdoor unit
Application Locally procured

Optional PCB Power


Outdoor unit Display supply
relay TB1 L1
interface PCB

[OPERATION] Shield
TB2 wire
CN513 PJ17
SW07 COM
[ON] SW1
ON ON SW 1
OFF
COM SW2
TCB-PCDM4E

1 2 3 4 [OFF] SW2
Bit 2 OFF OFF
Shield
Connection cable (attached in this optional PCB) wire
For SW1 and SW2, be sure to provide no-voltage
contacts for each terminal.
The input signals of SW1 and SW2 may be pulse
input (100 msec or more) or continuous make.
Do not turn on [SW1] and [SW2] simultaneously.

<SW07 (bit 2) OFF [2-stage switching]>


Input SW07 (bit 1)
Display relay (L1)
SW1 SW2 Bit 1 OFF Bit 1 ON
100% 100%
OFF ON OFF
(normal operation) (normal operation)
Approx. 60%
ON OFF 0% (forced stop) ON
(upper limit regulated)
* Install the optional P.C.
board in the outdoor header
unit.

10 -6
10 Controls

Model
Appearance Function
name
For one input function (only SMMS- i)

Size : 55.5 x 60 (mm)

Application
TCB-PCMO4E

* Install the optional P.C.


board in the outdoor header
unit.

10 -7
10 Controls

Model
Appearance Function
name
[2] External master ON/OFF control
• Feature
The outdoor unit starts or stop the system.
• Function
By connecting the cable (attached in this optional PCB) to the interface PC
board on an outdoor unit, all indoor units connected to the outdoor unit enable
to operate simultaneously.
• Operation
Size : 55.5 x 60 (mm) The outdoor unit connection is for the header unit (U1).
Header outdoor unit
Application Connection cable Locally procured
Outdoor unit (attached in this
Optional PCB
interface PCB optional PCB) TB1
COM
CN512 PJ17 COOL
SW1
HEAT
SW2

Shield
wire
SW1: Operation input switch
SW2: Stop input switch
TCB-PCMO4E

Terminal Input signal Operation


ON
COOL (SW1) All indoor units operate together
OFF
ON
HEAT (SW2) All indoor units stop together
OFF
Provide no-voltage pulse contacts for each terminal.
Hold the ON state for at least 100 msec.
Do not turn SW1 and SW2 ON simultaneously
[3] Night time operation(sound reduction) control
* Install the optional P.C. • Purpose : Reducing noise from an outdoor unit
board in the outdoor header • Feature
unit. Sound level can be reduced by restricting the compressor and fan speed
• Function
As the cable (attached in this optional PCB) is connected to the “Interface
PCB” on an outdoor unit, both compressor speed and fan speed are restricted
while the signal of the night operation control is input. It makes the noise
reduction during the night time operation.
• Operation
The outdoor unit connection is for the header unit (U1).
Header outdoor unit
Connection cable Locally procured
(attached in this Optional PCB
Outdoor unit
interface PCB optional PCB) TB1
COM
CN508 PJ17 COOL
SW1
HEAT
Shield
wire

SW1: Night time signal switch

Terminal Input signal Operation


ON
All indoor units operate together
OFF
COOL (SW1)
ON
All indoor units stop together
OFF
Each terminal should be connected to dry contact.
The input signal is recognized during its rising/falling phase.
(After reaching the top/buttom of the rising/falling edge, the signal must remain there for
at least 100 ms.)

10 -8
10 Controls

Model
Appearance Function
name
Sound reduction and approximation capacity(reference)

Night operation sound Capacity


reduction dB(A) COOL HEAT
1604 type 53 Approx. 70% Approx. 70%
1404 type 53 Approx. 80% Approx. 80%
1204 type 50 Approx. 60% Approx. 55%
1004 type 50 Approx. 70% Approx. 65%
Size : 55.5 x 60 (mm) 0804 type 50 Approx. 85% Approx. 80%
0601 type 50 Approx. 75% Approx. 70%
Application 0501 type 50 Approx. 85% Approx. 80%
Condition
Cooling : (Indoor 27deg DB, 19deg WB)
(Outdoor temperature 25deg DB)
Heating : (Indoor 20 deg DB)
(Outdoor temperature 7deg DB, 6 deg WB)

[4] Snowfall fan control

• Purpose : Rotating the fan to prevent snow accumulation


• Feature
Outdoor fan is operated from the snowfall signal received from the outside.
TCB-PCMO4E

* Install the optional P.C.


board in the outdoor header
unit.

Be sure to provide no-voltage continous contacts for each terminal.

10 -9
10 Controls

Model
Appearance Function
name
[5] Operation mode selection control
• Purpose: Limiting operation modes to cooling and heating only
• Feature
This control can restrict the selectable operation mode.

Size : 55.5 x 60 (mm)

Application
TCB-PCIN4E

* Install the optional P.C.


board in the outdoor header
unit.

10 -10
10 Controls

Model
Appearance Function
name
[6] Error / Operation Output

• Feature
Operation and error monitoring is possible.

Size: 73 x 79 (mm)
TCB-PCIN4E

Application

* [OUTPUT3] is normally output when power is turned out.

* Install the optional P.C.


board in the outdoor header
unit.

10 -11
10 Controls

Model
Appearance Function
name
[7] Compressor Operation Output (only SMMS-i)

• Feature
Outputs the operation status of the compressors in each outdoor unit.

Size: 73 x 79 (mm)

Application
TCB-PCIN4E

* Install the optional P.C.


board in individual outdoor
unit

10 -12
10 Controls

Model
Appearance Function
name
[8] Operating Rate Output (only SMMS-i)

• Feature
Relay turn ON/OFF depending on the running rate of the system.

Size: 73 x 79 (mm)
TCB-PCIN4E

Application

* Install the optional P.C.


board in the outdoor header
unit.

10 -13
10 Controls

10-5. Application control of optional devices connectable to indoor units


10-5-1. Remote location ON/OFF control box
Model
Appearance Function
name
• Start and stop of the air conditioner is possible by a external
signal and indication of operation/alarm externally.
TCB-IFCB-4E2

Appearance Function
• Monitoring
ON/OFF status (for indoor unit)
Operation
Alarm status (system & indoor unit stop)
• ON/OFF command
Air conditioner can be turned ON/OFF by the external signals.
The external ON/OFF signals will initiate the signals shown
Interface below.
Display

Remote ON/OFF
Controller Non-voltage
ON /OFF continuous signal
COM

10-5-2. “1:1 model” connection interface


Model
Appearance Function
name
• Link adapter for “1:1 model” to enable connection to VRF
system network

1:1 model :Super digital inverter


Digital inverter
• High-wall type does not need this interface.
• Some types of indoor units (2 series compact 4-way, 4-way
cassette 4series, etc.) need the metal case TCB-PX30MUE to
use this interface. Refer to the Installation manual of each unit
(85 x 52 mm) for details.
Install optional P.C. board in E-parts of the indoor unit. Connection of cables
Appearance
Central
ON-OFF control
control devices
TCB-PCNT30TLE2

Central Remote Controller Indoor unit Indoor unit Indoor unit


TCB-SC642TLE2
ON-OFF Controller or BMS-CM1280TLE U3 U4
TCB-CC163TLE2 or other BMS
Indoor Indoor Indoor
or Adaptor control control control
P.C.board P.C.board P.C.board

A B A B A B

Control wiring

1:1 model Remote


controller
connection
interface

Indoor units Wiring diagram of indoor P.C. board

Digital Inverter
U3 U4 Connecting
Super Digital Inverter terminal block
BLU BLU

1 2
Outdoor unit
1 2
CN40 (BIU)
CN51 (RED) WHI CN50 (WHI)
1 1 1 1
RED
2 2 2 2
adapter RED Indoor control
3 3 3 3
RED P.C.board
4 4 4 4
RED
5 5 5 5

10 -14
10 Controls

10-5-3. General purpose Interface


Model
Appearance Function
name
Provide various applied controls that enable connection between
the indoor unit and external equipments.
• Equipped with 4 Relay contact outputs, 2 Analogue Outputs
through which a central controller can send commands, and 4
Analogue Inputs/6 Digital Inputs through which the Central
controller can read data.
• Equipment with the HA terminal (DAISEIKAI, IMS, etc.) can be
connected to the TCC-LINK central control network (DI/SDI,S-
MMS,Mini-SMMS,S-HRM) for ON/OFF Control & Monitoring via
this device.
• Full Central Control by Modbus System TCB-IFMB640TLE and
ON/OFF Control by Central Control by TCB-SC642TLE2 and
Compliant Manager (Multi languagge).
Programmable Control by Special Tool
• Operation of specified indoor units can be programmed on site
with input ports level change.
Appearance Function
Connection to Tcc-link Interlocking operation with indoors and
input ports.
TCB-IFCG1TLE

• 2 Analog/5 Digital inputs can interlock with 64 indoors and 4


Relays.
• 12 programs possible.

Central control via tcc-link Port specification


Connectable with HA terminal
(4pin input/output), alarm input Input/
Channel Connected Device/
Interlocking Operation (below) output Main spec
number Apparatus example
ports
TCC-LI NK Output Temperature
2 measurement: Thermistor
TCB-IFCG1TLE
Analog -10~90°C±0.4°C
TCC-LINK
Input Analog Input:
Input
Trigger
Relay #1 #2
2 0~10V 10bits Sensor, etc
Output
resolution
Analog Output: 0-10V Actuator, Motors,
Example of 2
Human Window
Switches peripheral Output 8bits resolution Pumps, etc
detection equipment
Photo coupler type: HA in
open/close Temperature
sensor lights
Digital
senser Pump/motor

6 ON level 2mA, (Daiseikai, IMS),


Input
max 30mA Fan Sensor, etc
Actuator, Motors,
Relay contacts:
Digital Pumps HA out
4 Max 1A 42VAC/
Output (Daiseikai, IMS),
30VDC
Fan, light, etc

10 -15
10 Controls

10-5-4. GSM Phone control Interface


Model
Appearance Function
name
Controlling and Monitoring Toshiba air conditioning from
registered mobile phone.
• Stand alone, simple, cheap system without LAN
• Possible on/off control and status monitoring of the air
conditioner by the SMS mail system of GSM mobile phone
• Auto alarm transfer function for S-MMS,SDI,DI
• Triple “Security” is assured by SMS system, secret telephone
numbers and PIN on TCB-IFGSM1E
• Can register 5 Phone numbers which can control an air
conditioner and 5 Phone numbers which can receive response
TCB-IFGSM1E

from an air conditioner


• Can register the name of air conditioner (max 19 characters)
• Not necessary for Power Supply in case of CN61
Appearance Function

Set from SMS mail

Non LAN / Internet area


GSM Modem
Secured Remote control or monitoring of air-conditioner ON/OFF
TCB-IFGSM1E
control/monitoring
• Control : write ON or OFF, then send mail
RS232C • Status : write STATUS, then send mail
Cable
• “Alarm” is automatically sent from the site (CN61)
ACAdaptor

10-5-5. Network adapter


Model
Appearance Function
name
• Indoor units of VRF system are controlled by AI-NETWORK
central remote controller.Connectable indoor units per group.
Connection of cables

Central remote controller


Non polarity cable

XY Indoor unit
CN03 control Indoor unit Indoor unit Indoor unit
12 P.C.board
1 1 1 Indoor Indoor Indoor
CN041
2 3 3 control control control
13 13 P.C.board P.C.board P.C.board
CN309
CN02 CN01 Indoor
TCB-PCNT20E

unit A B A B A B A B

Install optional P.C. board in E-parts of indoor unit. Non polarity cable
Remote controller
Appearance
Wiring diagram of indoor P.C. board
Power
Supply Al Network
CN040(Blue) Indoor control P.C.board CN300(Yellow)
1 2 3 1 3
1 2 3 1 3
Black Black
Terminal block
Central Remote Network Adapter for connecting
Network
remote controller Black
Controller 3 3 adapter CN01(White) Power
TCB-SC641E A B 2 2 P.C. board 2 2 Supply
CN02(Blue) 1 1
White 1 1
transformer
CN03(Red)
1 2
1 2
Gray Gray
Indoor unit
Remote
X Y
Controller Network connection terminal block

10 -16
10 Controls

10-6. Application control for network


10-6-1. LONWORKS
System diagram Model
• LON Interface
Max 64 Indoors/groups/IF TCB-IFLN642TLE
TCC-link bus 1:1model • “1:1model” connection
TCC-Link Interface
Connection TCB-PCNT30TLE2
I/F
• Wired Remote controller
LON I/F
Twisted pair line RBC-AMT32E
Free/Bus topology • Wireless Remote controller
RBC-AX31U(W)-E
LONWORKS TCC-link bus RBC-AX31U(WS)-E
Controller
RBC-AX22CE2
TCB-AX21E2
LON I/F
• Wired Remote controller with
schedule timer
RBC-AMS41E
RBC-AMS51E-EN/ES
traffic or points numbers.
[Note] Xif file:
• controller commissioning without
LON Interface
Other system (security, etc)

10-6-2. BACnet
System diagram Model
• BACnet server
/CZ+PFQQTU BMS-LSV6E
6%%NKPMDWU OQFGN • BACnet Server Software
$#%PGVUGTXGT
BMS-STBN08E
45 %QPPGEVKQP+(
• Setting file creation software
Relay I/F
• “1:1model” connection
TCC-Link Interface
$#%PGV5GTXGT
TCB-PCNT30TLE2
'VJGTPGV
5QHVYCTG • Relay Interface
/CZ
6%%NKPMDWU
BMS-LSV4E
/CZPWODGTQH$#%PGVUGTXGT
FGRGPFUQP+2PGVQYQM CPF BMS-LSV3E
WRRGTU[UVGO • Wired Remote controller
Relay I/F
RBC-AMT32E
• Wireless Remote controller
RBC-AX31U(W)-E
+PECUGQH$#5'6%CVGIQT[QT RBC-AX31U(WS)-E
%CVGIQT[ RBC-AX22CE2
+PECUGQH$#5'6:%CVGIQT[

$#%PGV+2
#PPGZ, TCB-AX21E2
• Wired Remote controller with
schedule timer
'VJGTPGV
1VJGTU[UVGO
RBC-AMS41E
RBC-AMS51E-EN/ES

[Note] Pc BACnet explorer:


• Commissioning for BACnet
server (lacal supply)

%GPVTCNOCPCIGOGPVEQPVTQNNGT

10 -17
10 Controls

10-6-3. Modbus
System diagram Model
• Modbus I/F
Modbus TCB-IFMB640TLE
Master Max 64 Indoors/groups/IF
Modbus I/F
TCC-link bus 1:1model • “1:1model” connection
• TCC-Link Interface
Connection
TCB-PCNT30TLE2
RS-485 I/F
• Wired Remote controller
RBC-AMT32E
• Wireless Remote controller
Modbus I/F RBC-AX31U(W)-E
T C C link bus RBC-AX31U(WS)-E
RBC-AX22CE2
TCB-AX21E2
• Wired Remote controller with
schedule timer
RBC-AMS41E
RBC-AMS51E-EN/ES

[Note]
• Pc master dummy program:
Commissioning for Modbus I/F
Other system (security, etc)

10-6-4. Smart Manager


System diagram Model
Power unit
• Smart Manager
Smart Manager AC BMS-SM1280HTLE
Max 128 indoors
Power supply
• Setting file creation software
TCC-link bus 1:1model • Monthly report creation software
• “1:1model” connection
RS-485 Connection I/F
TCC-Link Interface
Digital I/O signal TCB-PCNT30TLE2
• Energy monitoring Relay I/F
Max In3 /Out2
BMS-IFWH5E
Ethernet • Digital I/ORelay I/F
Fire alarm
Key lock
BMS-IFDD03E
TCC-link bus
• Wired Remote controller
RBC-AMT32E
• Wireless Remote controller
RBC-AX31U(W)-E,
RBC-AX31U(WS)-E,
RBC-AX22CE2
TCB-AX21E2
• Wired Remote controller with
Energy monitoring Relay I/F
Power Meter
schedule timer
Max4 Pulse signal RBC-AMS41E
RBC-AMS51E-EN/ES
Max8
Monitor/Control Monthly report
/Setting creation software Digital I/O Relay I/F

Digital I/O signal Fire alarm


Max4
Max4 PC simultaneous access Door key
Error

Max In 8 /Out 4

Power meter:
Pulse width:50-1000ms
Pulse generator constants (kWh/pulse) 0.1-99.9

10 -18
10 Controls

10-6-5. Touch Screen Controller


System diagram Model
• Touch Screen Controller
Max 64/512 Indoors
Touch Screen Controller
BMS-TP0641ACE
1:1model
BMS-TP5121ACE
TCC-link bus
BMS-TP0641PWE
RS-485 Connection I/F BMS-TP5121PWE
Relay I/F • Setting file creation software
Digital Input • Monthly report creation software
Digital
3ch • “1:1model” connection
output
3ch
TCC-Link Interface
Ethernet
Fire alarm
Key lock
TCB-PCNT30TLE2
Max12 TCC-link bus
• Relay Interface
BMS-LSV4E
Relay I/F • Energy monitoring Relay I/F
BMS-IFWH5E
• Digital I/O Relay I/F
BMS-IFDD03E
Monthly report creation software
• Wired Remote controller
Energy monitoring Relay I/F
Power Meter RBC-AMT32E
Max8 Pulse signal
• Wireless Remote controller
RBC-AX31U(W)-E
Max8 RBC-AX31U(WS)-E
RBC-AX22CE2
Digital I/O Relay I/F TCB-AX21E2
Fire alarm
• Wired Remote controller with
Digital I/O signal
Door key schedule timer
Max8
Error RBC-AMS41E
Max In 8 /Out 4
RBC-AMS51E-EN/ES

Power meter:
Pulse width:50-1000ms
Pulse generator constants (kWh/pulse) 0.1-99.9

10 -19
10 Controls

10-6-6. WEB Based Controller


System diagram Model
BMS-WB2561PWE
BMS-WB2561PWE
(Web Server)
TCS-Net Relay I/F
TCC-LINK
BMS-WB2561PWE
BMS-WB01GTE
Ethernet BMS-IFLSV4E

SMMS-i SMMS-i
RS-485 • Setting file creation software
• Monthly report creation software
HUB • “1:1mode” connection
TCC-Link Interface
TCS-Net Relay I/F
TCC-LINK
TCB-PCNT30TLE2
• Relay Interface
MiNi-SMMS
BMS-IFLSV4E

SMMS-i BMS-IFLSV4E
I/F for Power Meter
PC (WINDOWS) *Local supply (BMS-IFWH5E)

I/F for I/O signal


Network, Intranet, connection (BMS-IFDD03E)
through LAN port
• Energy monitoring Relay I/F
BMS-IFWH5E
System product configuration table
Web Server System • Digital I/O
Product name
Model name Max. connectable units Relay I/F
Web Server BMS-WB2561PWE 1 BMS-IFDD03E
Indoor Unit (TCC-LINK integrated model) Max. 256
• Wired Remote controller
TCS-NET Relay Interface BMS-IFLSV4E Max. 8
Energy Monitoring Relay Interface BMS-IFWH5E Max. 4
RBC-AMT32E
Digital Input/Output Relay Interface BMS-IFDD03E Max. 4 • Wireless Remote controller
Central Remote Controller
TCB-SC642TLE
Max. 10 RBC-AX31U(W)-E
BMS-CM1280TLE
RBC-AX31U(WS)-E
OS Windows XP,Vista RBC-AX22CE2
Client PC specification Browser Internet Explorer 6.0 or 7.0 TCB-AX21E2
Display 1,024 X 768 more • Wired Remote controller with
Max 257 Indoors or more
schedule timer
TCS-Net
Relay I/F RBC-AMS41E
TCC-LINK
BMS-WB01GTE
(Master Server) SMMS-i
RBC-AMS51E-EN/ES
Ethernet BMS-WB2561PWE SMMS-i
(Gateway)

TCS-Net
RS-485 Relay I/F
TCC-LINK

MiNi-SMMS
SMMS-i

HUB TCS-Net
Relay I/F
TCC-LINK

SMMS-i
SMMS-i
BMS-WB2561PWE
(Gateway)
RS-485 TCS-Net
Relay I/F
TCC-LINK
PC (WINDOWS) *Local supply
MiNi-SMMS
I/F for Power Meter SMMS-i
(BMS-IFWH4E2)

I/F for I/O signal


(BMS-IFDD02E2)

Network, Intranet, connection through LAN port


Enable to connector up to 2,048 FCUs

System product configuration table


Master Server System
Product name Max.
Model name Notes
connectable units
Master Server BMS- WB01GTE 1
Gateway BMS- WB2561PWE Max. 8
Indoor Unit (TCC-LINK integrated model) Max. 2048 Max. 256 units per Gateway
TCS-NET Relay Interface BMS-IFLSV4E Max. 64 Max. 8 units per Gateway
Energy Monitoring Relay Interface BMS-IFWH5E Max. 32 Max. 4 units per Gateway
Digital Input/Output Relay Interface BMS-IFDD03E Max. 32 Max. 4 units per Gateway
TCB-SC642TLE
Central Remote Controller Max. 80 Max. 10 units per Gateway
BMS-CM1280TLE

OS Windows XP,Vista
Client PC specification Browser Internet Explorer 6.0 or 7.0
Display 1,024 X 768 more
Power meter:
Pulse width:50-1000ms
Pulse generator constants (kWh/pulse)0.1-99.9

10 -20
10 Controls

10-6-7. Analog Interface


System diagram Model
• Analog Interface
TCB-IFCB640TLE
• 1:1model connection
B uffer

1:1model
TCC-Link Interface
TCC-link bus
R otary
S witcher 0-10VDC TCB-PCNT30TLE2
switch
Connection • General purposeI/F
Rotary B uffer

I/F
Switch
TCB-IFCG1TLE
• Wired Remote controller
R otary
switch
Analog I/F
or RBC-AMT32E
Max 64 Indoors/groups • Wireless Remote controller
PLC (Programmable
Logic Controler)
RBC-AX31U(W)-E
RBC-AX31U(WS)-E
Analog RBC-AX22CE2
Unit TCB-AX21E2
General purpose I/F • Wired Remote controller with
schedule timer
RBC-AMS41E
RBC-AMS51E-EN/ES

10 -21
10 Controls

10-7. Dimensionel drawing


Wired remote controller
RBC-AMT32E / NRC-01HE

120
120 16

Simple wired remote controller


RBC-AS21E2
120
80

13
60
16
70

10 -22
10 Controls

Wireless remote controller kit


RBC-AX31U(W)-E/RBC-AX31U(WS)-E
66.6

66.6

Wireless remote controller kit


RBC-AX22CE2

130
58 19.5
65
177

61

10 -23
10 Controls

Wireless remote controller kit


TCB-AX21E2

58 19.5

4.4 x 9.4 long hole


13

83.5

120
177

70 4.4 x 5.4 long hole

61

Wireless remote controller (High-wall 3 series)


WH-L11SE
204 157

56 24 120

10 -24
10 Controls

Wired remote controller with schedule timer


RBC-AMS41E

120
120 16

Schedule timer
TCB-EXS21TLE
4
2.7

120

16
120

10 -25
10 Controls

Central remote controller


TCB-SC642TLE2 116
47

15
13
160 21 69
6 148 (6)

115
121
160
148

121
(6)

128
80
13

47
36
128
80

Z-view

ON-OFF controller
TCB-CC163TLE2 116

160
148 (6) 14 69
6
6

<
115
121
160
148 (6)

122

128
80
13
36

47
128
80

10 -26
10 Controls

Remote sensor
TCB-TC21LE2

120
80

13
60
16
70

Remote location ON/OFF control box


TCB-IFCB-4E2

200

6- 5.5 mounting hole


22 78 78 22 Approx. 300 66
63.6

Approx.
1500
146.9

170
156

22 78 78 22

10 -27
10 Controls

General Purpose Interface/Analog Interface


TCB-IFCG1TLE/TCB-IFCB640TLE

200

6-Ø5 mounting holes 66


22 78 78 22 63.6

Bottom side
Top side
147

156
170
22 78 78 22

GSM Mobile Phone control interface


TCB-IFGSM1E

80

125 32

10 -28
10 Controls

Modbus Interface
TCB-IFMB640TLE

200

6- 5.5 mounting holes 66


22 78 78 22 63.6

Bottom side
Top side
147

156
170
22 78 78 22

LON Gateway
TCB-IFLN642TLE

246
234

6- 5.5 mounting holes

246
66
219 63.6
77

193.4
193

193
77

10 -29
10 Controls

BACnet server
BMS-LSV6E 9

19
145
105
125

70
11

3.2
250 69.5

4-Ø4.6

280
292

Compliant manager
BMS-CM1280TLE
8.5 155 8.5 5Ø
17.9
106.6

76

Dimensions of unit fixing holes in the wall, etc.

142
12.7

172

140
108

90
70

19 69
180

158
66
42

120

90
8
46

*
* Reserve space of 10mm or more
when installing the unit.

10 -30
10 Controls

Smart Manager
BMS-SM1280HTLE
Central control
140

180 19 45

120

90

Power Unit

182.7
177

6-Ø5.5 52.4
12 153 12 50
102
114
90

153
12 12

10 -31
10 Controls

Touch Screen Controller


BMS-TP0641ACE
BMS-TP5121ACE
BMS-TP0641PWE
BMS-TP5121PWE

316
54 249
5 49 75

95.75
242

256
75

91.75
99.3

70

82.5
302
48 55.5
16

19 30

[mm]

Web Based Controller


BMS-WB2561PWE/BMS-WB01GTE
9

19
145
105
125

70
210
11
65

4-Ø4.6

171
71.6

250

280
292

10 -32
10 Controls

TCS-Net Relay Interface


BMS-IFLSV4E

200

6- 5.5 mounting holes 66


22 78 78 22 63.6

Bottom side
Top side
147

156
170
22 78 78 22

Digital I/O Relay Interface/Energy Monitoring Relay Interface


BMS-IFDD03E
BMS-IFWH5E

246
234

6- 5.5 mounting holes


246
66
219 63.6
77
120

193.4
193

193
77
34

10 -33
10 Controls

Wired remote controller with schedule timer


RBC-AMS51E-EN/ES

120
120 20

10 -34
10 Controls

Dimensions of P.C. board


TCB-PCDM4E
Terminal
Screw M3 6
71 4-4ø hole
61

TOSHIBA

OFF
NCC-1212

OFF
TCB-PCOM1

COM
TCB-PCOM1E

8 ICI
ON
ON

5
COM

OFF ON
MS MS

5
T82

PJ17
85

75

T81
OPERATION/

10
K100

Terminal
Screw M4 8

TCB-PCMO4E
55.5 4-4ø hole
Terminal
45.5
Screw M3 6

TOSHIBA
NCC-1214 TCB-PCMO1
TCB-PCMO1E
HEAT COOL

10
1

4
60

50

PJ17
ICI

1
4

5
COM

COM

TB1
D2

TCB-PCIN4E
73
63
1 PJ20 5

C2
MCC-1613-02

C4
1 D 2 D 3 D

C3
69
79

Terminal block (M3)


K1 K2 K3

4-4 mm dia. mounting holes


1 2 3 4 5 6 TB1

OUTPUT1 OUTPUT2 OUTPUT3

TCB-PCNT30TLE2

10 -35
10 Controls

10 -36
11
SMMS-i Data book

Technical Specifications
11-1. Outdoor unit
11-1-1 Specifications
Standard model (Single unit)
Equivalent HP 5HP (*) 6HP (*) 8HP 10HP 12HP
Heat Pump MMY- MAP0501HT8 MAP0601HT8 MAP0804HT8 MAP1004HT8 MAP1204HT8
Model name
Cooling Only MMY- MAP0501T8 MAP0601T8 MAP0804T8 MAP1004T8 MAP1204T8
Outdoor unit type Inverter unit
Cooling capacity (*1) (kW) 14.0 16.0 22.4 28.0 33.5
Heating capacity (*1) (kW) 16.0 18.0 25.0 31.5 37.5
Power supply (*2) 3phase 4wires 50Hz 400V (380-415V)
Running current (A) 5.85 7.28 8.50 11.4 14.7
Power consumption (kW) 3.65 4.64 5.40 7.41 9.55
Cooling
Power factor (%) 90 92 92 94 94
Electrical EER (Energy Efficiency Ratio) (kW/kW)) 3.84 3.45 4.15 3.78 3.51
characteristics Running current (A) 6.09 7.08 8.8 11.80 16.0
(*1) Power consumption (kW) 3.84 4.56 5.53 7.50 10.2
Heating
Power factor (%) 91 93 91 92 92
EER (Energy Efficiency Ratio) (kW/kW)) 4.17 3.95 4.52 4.20 3.68
Starting Current (A) Soft Start
Height (mm) 1,857 1,857 1,887 1,887 1,887
Packing Width (mm) 1062 1062 1062 1062 1062
Depth (mm) 798 798 828 828 828
Dimension
Height (mm) 1,800 1,800 1,800 1,800 1,800
Unit Width (mm) 990 990 990 990 990
Depth (mm) 750 750 780 780 780
Heat Pump (kg) 241 241 257 257 257
Packing
Cooling only (kg) 240 240 256 256 256
Weight
Heat Pump (kg) 228 228 242 242 242
Unit
Cooling only (kg) 227 227 241 241 241
Colour Silky shade (Munsell 1Y8.5/0.5)
Type Hermetic twin rotary compressor
Compressor
Motor output (kW) 1.1 x 2 1.4 x 2 2.3 x 2 3.1 x 2 4.2 x 2
Fan Propeller fan
Fan unit Motor output (kW) 0.60 1.0
Air volume (m3/h) 9,000 9,900 10,500 11,600
Heat exchanger Finned tube
R410A
Refrigerant Charged Heat Pump (kg) 8.5 11.5
refrigerant
amount(*3) Cooling Only (kg) 8.0 10.5
High-pressure switch (Pa) OFF: 2.9 ON: 3.73
Protective devices (**) (*4)
MCA(*5) (A) 16.5 23.5 25.5 28.5
Power supply wiring Unit
MOCP(*6) (A) 20 32 40
Connecting Gas side (mm) ø 15.9 ø 19.1 ø 22.2 ø 28.6
port Liquid side (mm) ø 9.5 ø 12.7
diameter Balance side (mm) ø 9.5
Gas side Flare Brazing
Connecting Liquid side Flare
method
Refrigerant piping Balance side Flare
Max. equivation length (mm) 175 210
Max. real length (mm) 150 170
Max. total pipe length (Real length) (*7) (mm) 300
(mm) Outdoor unit is higher than indoor unit : 50 Outdoor unit is higher than indoor unit : 70(*8)
Max. height difference
(*9) (mm) Outdoor unit is lower than indoor unit: 40
Control wiring between indoor and (Up to 1000m) Shield wire 1.25mm2 x 2 cores
outdoor units + Central controller wiring (Up to 2000m) Shield wire 2.0mm2 x 2 cores
Max. No. of connected indoor units 8 10 13 16 20
Cooling (dB(A)) 55.0 56.0 55.0 57.0 59.0
Sound pressure level
Heating (dB(A)) 55.0 56.0 56.0 58.0 61.0
Cooling (dB(A)) 75 76 77 78 82
Sound power level
Heating (dB(A)) 75 76 78 79 83
Max. external static pressure (Pa) 35 60 50
Cooling CDB -5 to 43
Operation temperature range
Heating CWB -15 to 15.5 -20 to 15.5

Note
* :SMMS model
** : Discharge temp. sensor / Suction temp. sensor / High-pressure sensor / Low-pressure sensor / High-pressure switch / Over-current relay
*1 :Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
The standard piping means that mian pipe length is 5m, branching pipe length is 2.5m of branch piping connected with a 0 meter height.
*2 :The source voltage must not fluctuate more than ±10%.
*3 :The amount does not consider extra piping length. Refrigerant must be added on site in accordance with the actual piping length.
*4 :Discharge temp. sensor / Suction temp. sensor / High-pressure sensor / Low-pressure sensor / High-pressure switch / PC board fuse
*5 :Select wire size base on the larger value of MCA.
MCA : Minimum Circuit Amps
*6 :MOCP : Maximum Overcurrent Protection(Amps)
*7 :The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.
*8 :Set 50m or less if the height difference between indoor units exceeds 3m.
*9 :Set 30m or less if the height difference between indoor units exceeds 3m.

11 -1
11 Technical Specifications

Equivalent HP 14HP 16HP


Heat Pump MMY- MAP1404HT8 MAP1604HT8
Model name
Cooling Only MMY- MAP1404T8 MAP1604T8
Outdoor unit type Inverter unit
Cooling capacity (*1) (kW) 40.0 45.0
Heating capacity (*1) (kW) 45.0 50.0
Power supply (*2) 3phase 4wires 50Hz 400V (380-415V)
Running current (A) 17.7 20.8
Power consumption (kW) 11.5 13.7
Cooling
Power factor (%) 94 95
Electrical EER (Energy Efficiency Ratio) (kW/kW)) 3.48 3.28
characteristics Running current (A) 17.6 22.0
(*1) Power consumption (kW) 11.2 14.2
Heating
Power factor (%) 92 93
EER (Energy Efficiency Ratio) (kW/kW)) 4.02 3.52
Starting Current (A) Soft Start
Height (mm) 1,887 1,887
Packing Width (mm) 1282 1282
Depth (mm) 828 828
Dimension
Height (mm) 1,800 1,800
Unit Width (mm) 1210 1210
Depth (mm) 780 780
Heat Pump (kg) 347 347
Packing
Cooling only (kg) 347 347
Weight
Heat Pump (kg) 330 330
Unit
Cooling only (kg) 330 330
Colour Silky shade (Munsell 1Y8.5/0.5)
Type Hermetic twin rotary compressor
Compressor
Motor output (kW) 3.0 x 3 3.6 x 3
Fan Propeller fan
Fan unit Motor output (kW) 1.0
Air volume (m3/h) 12,000 13,000
Heat exchanger Finned tube
R410A
Refrigerant Charged Heat Pump (kg) 11.5
refrigerant
amount(*3) Cooling Only (kg) 11.5
High-pressure switch (Pa) OFF: 2.9 ON: 3.73
Protective devices (*4)
MCA(*5) (A) 33.2 36.5
Power supply wiring Unit
MOCP(*6) (A) 40 50
Connecting Gas side (mm) ø 28.6
port Liquid side (mm) ø 15.9
diameter Balance side (mm) ø 9.5
Gas side Brazing
Connecting
Liquid side Flare
method
Refrigerant piping Balance side Flare
Max. equivation length (mm) 210
Max. real length (mm) 170
Max. total pipe length (Real length) (*7) (mm) 300
(*8) (mm) Outdoor unit is higher than indoor unit : 70
Max. height difference
(*9) (mm) Outdoor unit is lower than indoor unit: 40
Control wiring between indoor and (Up to 1000m) Shield wire 1.25mm2 x 2 cores
outdoor units + Central controller wiring (Up to 2000m) Shield wire 2.0mm2 x 2 cores
Max. No. of connected indoor units 23 27
Cooling (dB(A)) 60.0 61.0
Sound pressure level
Heating (dB(A)) 62.0 63.0
Cooling (dB(A)) 82 83
Sound power level
Heating (dB(A)) 83 84
Max. external static pressure (Pa) 40
Cooling CDB -5 to 43
Operation temperature range
Heating CWB -20 to 15.5

Note
*1 :Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
The standard piping means that mian pipe length is 5m, branching pipe length is 2.5m of branch piping connected with a 0 meter height.
*2 :The source voltage must not fluctuate more than ±10%.
*3 :The amount does not consider extra piping length. Refrigerant must be added on site in accordance with the actual piping length.
*4 :Discharge temp. sensor / Suction temp. sensor / High-pressure sensor / Low-pressure sensor / High-pressure switch / PC board fuse
*5 :Select wire size base on the larger value of MCA.
MCA : Minimum Circuit Amps
*6 :MOCP : Maximum Overcurrent Protection(Amps)
*7 :The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.
*8 :Set 50m or less if the height difference between indoor units exceeds 3m.
*9 :Set 30m or less if the height difference between indoor units exceeds 3m.

11 -2
11 Technical Specifications

Standard model (Combination)


Equivalent HP Equivalent to 18HP Equivalent to 20HP Equivalent to 22HP
Heat Pump MMY- AP1814HT8 AP2014HT8 AP2214HT8
Model name
Cooling Only MMY- AP1814T8 AP2014T8 AP2214T8
Outdoor unit type Inverter unit
Heat Pump MMY- MAP1004HT8 MAP0804HT8 MAP1004HT8 MAP1004HT8 MAP1204HT8 MAP1004HT8
Outdoor unit model
Cooling Only MMY- MAP1004T8 MAP0804T8 MAP1004T8 MAP1004T8 MAP1204T8 MAP1004T8
Cooling capacity (*1) (kW) 50.4 56.0 61.5
Heating capacity (*1) (kW) 56.5 63.0 69.0
Power supply (*2) 3phase 4wires 50Hz 400V (380-415V)
Running current (A) 19.9 22.8 26.0
Power consumption (kW) 12.81 14.82 16.96
Cooling
Power factor (%) 93 94 94
Electrical EER (Energy Efficiency Ratio) (kW/kW)) 3.93 3.78 3.63
characteristics Running current (A) 20.5 23.5 27.8
(*1) Power consumption (kW) 13.03 15.00 17.70
Heating
Power factor (%) 92 92 92
EER (Energy Efficiency Ratio) (kW/kW)) 4.34 4.20 3.90
Starting Current (A) Soft Start
Height (mm) 1,887 1,887 1,887 1,887 1,887 1,887
Packing Width (mm) 1,062 1,062 1,062 1,062 1,062 1,062
Depth (mm) 828 828 828 828 828 828
Dimension
Height (mm) 1,800 1,800 1,800 1,800 1,800 1,800
Unit Width (mm) 990 990 990 990 990 990
Depth (mm) 780 780 780 780 780 780
Heat Pump (kg) 257 257 257 257 257 257
Packing
Cooling only (kg) 256 256 256 256 256 256
Weight
Heat Pump (kg) 242 242 242 242 242 242
Unit
Cooling only (kg) 241 241 241 241 241 241
Appearance (Colour) Silky shade (Munsell 1Y8.5/0.5)
Type Hermetic twin rotary compressor
Compressor
Motor output (kW) 3.1 x 2 2.3 x 2 3.1 x 2 3.1 x 2 4.2 x 2 3.1 x 2
Fan Propeller fan
Fan unit Motor output (kW) 1.0 1.0 1.0 1.0 1.0 1.0
Air volume (m3/h) 10,500 9,900 10,500 10,500 11,600 10,500
Heat exchanger Finned tube
R410A
Refrigerant Charged Heat Pump (kg) 11.5 11.5 11.5 11.5 11.5 11.5
refrigerant
amount(*3) Cooling Only (kg) 10.5 10.5 10.5 10.5 10.5 10.5
High-pressure switch (Pa) OFF: 2.9 ON: 3.73
Protective devices (*4)
MCA(*5) (A) 49.0 51.0 54.0
Power supply wiring Unit
MOCP(*6) (A) 63 63 63
Connecting Gas side (mm) ø 28.6 ø 34.9
port Liquid side (mm) ø 15.9 ø 19.1
diameter Balance side (mm) ø 9.5
Gas side Brazing
Connecting Liquid side Flare
method
Refrigerant piping Balance side Flare
Max. equivation length (mm) 220
Max. real length (mm) 180
Max. total pipe length (Real length) (*7) (mm) 300
(*8) (mm) Outdoor unit is higher than indoor unit : 70
Max. height difference
(*9) (mm) Outdoor unit is lower than indoor unit: 40
Control wiring between indoor and (Up to 1000m) Shield wire 1.25mm2 x 2 cores
outdoor units + Central controller wiring (Up to 2000m) Shield wire 2.0mm2 x 2 cores
Max. No. of connected indoor units 30 33 37
Cooling (dB(A)) 59.5 60.0 61.5
Sound pressure level
Heating (dB(A)) 60.5 61.0 63.0
Max. external static pressure (Pa) 60 60 60 60 50 60
Cooling CDB -5 to 43
Operation temperature range
Heating CWB -20 to 15.5

Note
*1 :Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
The standard piping means that mian pipe length is 5m, branching pipe length is 2.5m of branch piping connected with a 0 meter height.
*2 :The source voltage must not fluctuate more than ±10%.
*3 :The amount does not consider extra piping length. Refrigerant must be added on site in accordance with the actual piping length.
*4 :Discharge temp. sensor / Suction temp. sensor / High-pressure sensor / Low-pressure sensor / High-pressure switch / PC board fuse
*5 :Select wire size base on the larger value of MCA.
MCA : Minimum Circuit Amps
*6 :MOCP : Maximum Overcurrent Protection(Amps)
*7 :The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.
*8 :Set 50m or less if the height difference between indoor units exceeds 3m.
*9 :Set 30m or less if the height difference between indoor units exceeds 3m.

11 -3
11 Technical Specifications

Equivalent HP Equivalent to 24HP Equivalent to 26HP Equivalent to 28HP


Heat Pump MMY- AP2414HT8 AP2614HT8 AP2814HT8
Model name
Cooling Only MMY- AP2414T8 AP2614T8 AP2814T8
Outdoor unit type Inverter unit
Heat Pump MMY- MAP1204HT8 MAP1204HT8 MAP1604HT8 MAP1004HT8 MAP1604HT8 MAP1204HT8
Outdoor unit model
Cooling Only MMY- MAP1204T8 MAP1204T8 MAP1604T8 MAP1004T8 MAP1604T8 MAP1204T8
Cooling capacity (*1) (kW) 68.0 73.0 78.5
Heating capacity (*1) (kW) 76.5 81.5 88.0
Power supply (*2) 3phase 4wires 50Hz 400V (380-415V)
Running current (A) 30.2 32.2 35.5
Power consumption (kW) 19.66 21.11 23.25
Cooling
Power factor (%) 94 95 95
Electrical EER (Energy Efficiency Ratio) (kW/kW)) 3.46 3.46 3.38
characteristics Running current (A) 33.2 33.8 38.4
(*1) Power consumption (kW) 21.13 21.70 24.65
Heating
Power factor (%) 92 93 92.6
EER (Energy Efficiency Ratio) (kW/kW)) 3.62 3.76 3.57
Starting Current (A) Soft Start
Height (mm) 1,887 1,887 1,887 1,887 1,887 1,887
Packing Width (mm) 1,062 1,062 1,282 1,062 1,282 1,062
Depth (mm) 828 828 828 828 828 828
Dimension
Height (mm) 1,800 1,800 1,800 1,800 1,800 1,800
Unit Width (mm) 990 990 1,210 990 1,210 990
Depth (mm) 780 780 780 780 780 780
Heat Pump (kg) 257 257 347 257 347 257
Packing
Cooling only (kg) 256 256 347 256 347 256
Weight
Heat Pump (kg) 242 242 330 242 330 242
Unit
Cooling only (kg) 241 241 330 241 330 241
Colour Silky shade (Munsell 1Y8.5/0.5)
Type Hermetic twin rotary compressor
Compressor
Motor output (kW) 4.2 x 2 4.2 x 2 3.6 x 3 3.1 x 2 3.6 x 3 4.2 x 2
Fan Propeller fan
Fan unit Motor output (kW) 1.0 1.0 1.0 1.0 1.0 1.0
Air volume (m3/h) 11,600 11,600 13,000 10,500 13,000 11,600
Heat exchanger Finned tube
R410A
Refrigerant Charged Heat Pump (kg) 11.5 11.5 11.5 11.5 11.5 11.5
refrigerant
amount(*3) Cooling Only (kg) 10.5 10.5 11.5 10.5 11.5 10.5
High-pressure switch (Pa) OFF: 2.9 ON: 3.73
Protective devices (*4)
MCA(*5) (A) 57.0 62.0 65.0
Power supply wiring Unit
MOCP(*6) (A) 63 80 80
Connecting Gas side (mm) ø 34.9
port Liquid side (mm) ø 19.1
diameter Balance side (mm) ø 9.5
Gas side Brazing
Connecting Liquid side Flare
method
Refrigerant piping Balance side Flare
Max. equivation length (mm) 220
Max. real length (mm) 180
Max. total pipe length (Real length) (*7) (mm) 300
(*8) (mm) Outdoor unit is higher than indoor unit : 70
Max. height difference
(*9) (mm) Outdoor unit is lower than indoor unit: 40
Control wiring between indoor and (Up to 1000m) Shield wire 1.25mm2 x 2 cores
outdoor units + Central controller wiring (Up to 2000m) Shield wire 2.0mm2 x 2 cores
Max. No. of connected indoor units 40 43 47
Cooling (dB(A)) 62.0 62.5 63.5
Sound pressure level
Heating (dB(A)) 64.0 64.5 65.5
Max. external static pressure (Pa) 50 50 40 60 40 50
Cooling CDB -5 to 43
Operation temperature range
Heating CWB -20 to 15.5

Note
*1 :Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
The standard piping means that mian pipe length is 5m, branching pipe length is 2.5m of branch piping connected with a 0 meter height.
*2 :The source voltage must not fluctuate more than ±10%.
*3 :The amount does not consider extra piping length. Refrigerant must be added on site in accordance with the actual piping length.
*4 :Discharge temp. sensor / Suction temp. sensor / High-pressure sensor / Low-pressure sensor / High-pressure switch / PC board fuse
*5 :Select wire size base on the larger value of MCA.
MCA : Minimum Circuit Amps
*6 :MOCP : Maximum Overcurrent Protection(Amps)
*7 :The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.
*8 :Set 50m or less if the height difference between indoor units exceeds 3m.
*9 :Set 30m or less if the height difference between indoor units exceeds 3m.

11 -4
11 Technical Specifications

Equivalent HP Equivalent to 30HP Equivalent to 32HP Equivalent to 34HP


Heat Pump MMY- AP3014HT8 AP3214HT8 AP3414HT8
Model name
Cooling Only MMY- AP3014T8 AP3214T8 AP3414T8
Outdoor unit type Inverter unit
Heat Pump MMY- MAP1604HT8 MAP1404HT8 MAP1604HT8 MAP1604HT8 MAP1204HT8 MAP1204HT8 MAP1004HT8
Outdoor unit model
Cooling Only MMY- MAP1604T8 MAP1404T8 MAP1604T8 MAP1604T8 MAP1204T8 MAP1204T8 MAP1004T8
Cooling capacity (*1) (kW) 85.0 90.0 96.0
Heating capacity (*1) (kW) 95.0 100.0 108.0
Power supply (*2) 3phase 4wires 50Hz 400V (380-415V)
Running current (A) 38.5 41.6 41.5
Power consumption (kW) 25.20 27.40 27.06
Cooling
Power factor (%) 95 95 94
Electrical EER (Energy Efficiency Ratio) (kW/kW)) 3.37 3.28 3.55
characteristics Running current (A) 39.6 44.1 44.9
(*1) Power consumption (kW) 25.40 28.40 28.60
Heating
Power factor (%) 93 93 92
EER (Energy Efficiency Ratio) (kW/kW)) 3.74 3.52 3.78
Starting Current (A) Soft Start
Height (mm) 1,887 1,887 1,887 1,887 1,887 1,887 1,887
Packing Width (mm) 1,282 1,282 1,282 1,282 1,062 1,062 1,062
Depth (mm) 828 828 828 828 828 828 828
Dimension
Height (mm) 1,800 1,800 1,800 1,800 1,800 1,800 1,800
Unit Width (mm) 1,210 1,210 1,210 1,210 990 990 990
Depth (mm) 780 780 780 780 780 780 780
Heat Pump (kg) 347 347 347 347 257 257 257
Packing
Cooling only (kg) 347 347 347 347 256 256 256
Weight
Heat Pump (kg) 330 330 330 330 242 242 242
Unit
Cooling only (kg) 330 330 330 330 241 241 241
Colour Silky shade (Munsell 1Y8.5/0.5)
Type Hermetic twin rotary compressor
Compressor
Motor output (kW) 3.6 x 3 3.0 x 3 3.6 x 3 3.6 x 3 4.2 x 2 4.2 x 2 3.1 x 2
Fan Propeller fan
Fan unit Motor output (kW) 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Air volume (m3/h) 13,000 12,000 13,000 13,000 11,600 11,600 10,500
Heat exchanger Finned tube
R410A
Refrigerant Charged Heat Pump (kg) 11.5 11.5 11.5 11.5 11.5 11.5 11.5
refrigerant
amount(*3) Cooling Only (kg) 11.5 11.5 11.5 11.5 10.5 10.5 10.5
High-pressure switch (Pa) OFF: 2.9 ON: 3.73
Protective devices (*4)
MCA(*5) (A) 69.7 73.0 82.5
Power supply wiring Unit
MOCP(*6) (A) 80 100 100
Connecting Gas side (mm) ø 34.9
port Liquid side (mm) ø 19.1
diameter Balance side (mm) ø 9.5
Gas side Brazing
Connecting Liquid side Flare
method
Refrigerant piping Balance side Flare
Max. equivation length (mm) 220 235
Max. real length (mm) 180 190
Max. total pipe length (Real length) (*7) (mm) 300 500
(*8) (mm) Outdoor unit is higher than indoor unit : 70
Max. height difference
(*9) (mm) Outdoor unit is lower than indoor unit: 40
Control wiring between indoor and (Up to 1000m) Shield wire 1.25mm2 x 2 cores
outdoor units + Central controller wiring (Up to 2000m) Shield wire 2.0mm2 x 2 cores
Max. No. of connected indoor units 48 48 48
Cooling (dB(A)) 63.5 64.0 63.5
Sound pressure level
Heating (dB(A)) 65.5 66.0 65.0
Max. external static pressure (Pa) 40 40 40 40 50 50 60
Cooling CDB -5 to 43
Operation temperature range
Heating CWB -20 to 15.5

Note
*1 :Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
The standard piping means that mian pipe length is 5m, branching pipe length is 2.5m of branch piping connected with a 0 meter height.
*2 :The source voltage must not fluctuate more than ±10%.
*3 :The amount does not consider extra piping length. Refrigerant must be added on site in accordance with the actual piping length.
*4 :Discharge temp. sensor / Suction temp. sensor / High-pressure sensor / Low-pressure sensor / High-pressure switch / PC board fuse
*5 :Select wire size base on the larger value of MCA.
MCA : Minimum Circuit Amps
*6 :MOCP : Maximum Overcurrent Protection(Amps)
*7 :The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.
*8 :Set 50m or less if the height difference between indoor units exceeds 3m.
*9 :Set 30m or less if the height difference between indoor units exceeds 3m.

11 -5
11 Technical Specifications

Equivalent HP Equivalent to 36HP Equivalent to 38HP Equivalent to 40HP


Heat Pump MMY- AP3614HT8 AP3814HT8 AP4014HT8
Model name
Cooling Only MMY- AP3614T8 AP3814T8 AP4014T8
Outdoor unit type Inverter unit
Heat Pump MMY- MAP1204HT8 MAP1204HT8 MAP1204HT8 MAP1604HT8 MAP1204HT8 MAP1004HT8 MAP1604HT8 MAP1204HT8 MAP1204HT8
Outdoor unit model
Cooling Only MMY- MAP1204T8 MAP1204T8 MAP1204T8 MAP1604T8 MAP1204T8 MAP1004T8 MAP1604T8 MAP1204T8 MAP1204T8
Cooling capacity (*1) (kW) 101.0 106.0 112.0
Heating capacity (*1) (kW) 113.0 119.5 127.0
Power supply (*2) 3phase 4wires 50Hz 400V (380-415V)
Running current (A) 44.4 46.9 50.1
Power consumption (kW) 28.93 30.66 32.80
Cooling
Power factor (%) 94 94 94
Electrical EER (Energy Efficiency Ratio) (kW/kW)) 3.49 3.47 3.41
characteristics Running current (A) 48.4 50.2 55.1
(*1) Power consumption (kW) 30.84 32.14 35.29
Heating
Power factor (%) 92 92 92
EER (Energy Efficiency Ratio) (kW/kW)) 3.66 3.72 3.60
Starting Current (A) Soft Start
Height (mm) 1,887 1,887 1,887 1,887 1,887 1,887 1,887 1,887 1,887
Packing Width (mm) 1,062 1,062 1,062 1,282 1,062 1,062 1,282 1,062 1,062
Depth (mm) 828 828 828 828 828 828 828 828 828
Dimension
Height (mm) 1,800 1,800 1,800 1,800 1,800 1,800 1,800 1,800 1,800
Unit Width (mm) 990 990 990 1,210 990 990 1,210 990 990
Depth (mm) 780 780 780 780 780 780 780 780 780
Heat Pump (kg) 257 257 257 347 257 257 347 257 257
Packing
Cooling only (kg) 256 256 256 347 256 256 347 256 256
Weight
Heat Pump (kg) 242 242 242 330 242 242 330 242 242
Unit
Cooling only (kg) 241 241 241 330 241 241 330 241 241
Colour Silky shade (Munsell 1Y8.5/0.5)
Type Hermetic twin rotary compressor
Compressor
Motor output (kW) 4.2 x 2 4.2 x 2 4.2 x 2 3.6 x 3 4.2 x 2 3.1 x 2 3.6 x 3 4.2 x 2 4.2 x 2
Fan Propeller fan
Fan unit Motor output (kW) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Air volume (m3/h) 11,600 11,600 11,600 13,000 11,600 10,500 13,000 11,600 11,600
Heat exchanger Finned tube
R410A
Refrigerant Charged Heat Pump (kg) 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5
refrigerant
amount(*3) Cooling Only (kg) 10.5 10.5 10.5 11.5 10.5 10.5 11.5 10.5 10.5
High-pressure switch (Pa) OFF: 2.9 ON: 3.73
Protective devices (*4)
MCA(*5) (A) 85.5 90.5 93.5
Power supply wiring Unit
MOCP(*6) (A) 100 100 125
Connecting Gas side (mm) ø 41.3
port Liquid side (mm) ø 22.2
diameter Balance side (mm) ø 9.5
Gas side Brazing
Connecting Liquid side Flare
method
Refrigerant piping Balance side Flare
Max. equivation length (mm) 235
Max. real length (mm) 190
Max. total pipe length (Real length) (*7) (mm) 500
(*8) (mm) Outdoor unit is higher than indoor unit : 70
Max. height difference
(*9) (mm) Outdoor unit is lower than indoor unit: 40
Control wiring between indoor and (Up to 1000m) Shield wire 1.25mm2 x 2 cores
outdoor units + Central controller wiring (Up to 2000m) Shield wire 2.0mm2 x 2 cores
Max. No. of connected indoor units 48 48 48
Cooling (dB(A)) 64.0 64.5 64.5
Sound pressure level
Heating (dB(A)) 66.0 66.0 66.5
Max. external static pressure (Pa) 50 50 50 40 50 60 40 50 50
Cooling CDB -5 to 43
Operation temperature range
Heating CWB -20 to 15.5

Note
*1 :Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
The standard piping means that mian pipe length is 5m, branching pipe length is 2.5m of branch piping connected with a 0 meter height.
*2 :The source voltage must not fluctuate more than ±10%.
*3 :The amount does not consider extra piping length. Refrigerant must be added on site in accordance with the actual piping length.
*4 :Discharge temp. sensor / Suction temp. sensor / High-pressure sensor / Low-pressure sensor / High-pressure switch / PC board fuse
*5 :Select wire size base on the larger value of MCA.
MCA : Minimum Circuit Amps
*6 :MOCP : Maximum Overcurrent Protection(Amps)
*7 :The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.
*8 :Set 50m or less if the height difference between indoor units exceeds 3m.
*9 :Set 30m or less if the height difference between indoor units exceeds 3m.

11 -6
11 Technical Specifications

Equivalent HP Equivalent to 42HP Equivalent to 44HP


Heat Pump MMY- AP4214HT8 AP4414HT8
Model name
Cooling Only MMY- AP4214T8 AP4414T8
Outdoor unit type Inverter unit
Heat Pump MMY- MAP1604HT8 MAP1404HT8 MAP1204HT8 MAP1604HT8 MAP1604HT8 MAP1204HT8
Outdoor unit model
Cooling Only MMY- MAP1604T8 MAP1404T8 MAP1204T8 MAP1604T8 MAP1604T8 MAP1204T8
Cooling capacity (*1) (kW) 118.0 123.5
Heating capacity (*1) (kW) 132.0 138.0
Power supply (*2) 3phase 4wires 50Hz 400V (380-415V)
Running current (A) 53.1 56.3
Power consumption (kW) 34.47 36.95
Cooling
Power factor (%) 94 95
Electrical EER (Energy Efficiency Ratio) (kW/kW)) 3.42 3.34
characteristics Running current (A) 55.4 60.5
(*1) Power consumption (kW) 35.46 38.85
Heating
Power factor (%) 92 93
EER (Energy Efficiency Ratio) (kW/kW)) 3.72 3.55
Starting Current (A) Soft Start
Height (mm) 1,887 1,887 1,887 1,887 1,887 1,887
Packing Width (mm) 1,282 1,282 1,062 1,282 1,282 1,062
Depth (mm) 828 828 828 828 828 828
Dimension
Height (mm) 1,800 1,800 1,800 1,800 1,800 1,800
Unit Width (mm) 1,210 1,210 990 1,210 1,210 990
Depth (mm) 780 780 780 780 780 780
Heat Pump (kg) 347 347 257 347 347 257
Packing
Cooling only (kg) 347 347 256 347 347 256
Weight
Heat Pump (kg) 330 330 242 330 330 242
Unit
Cooling only (kg) 330 330 241 330 330 241
Colour Silky shade (Munsell 1Y8.5/0.5)
Type Hermetic twin rotary compressor
Compressor
Motor output (kW) 3.6 x 3 3.0 x 3 4.2 x 2 3.6 x 3 3.6 x 3 4.2 x 2
Fan Propeller fan
Fan unit Motor output (kW) 1.0 1.0 1.0 1.0 1.0 1.0
Air volume (m3/h) 13,000 12,000 11,600 13,000 13,000 11,600
Heat exchanger Finned tube
R410A
Refrigerant Charged Heat Pump (kg) 11.5 11.5 11.5 11.5 11.5 11.5
refrigerant
amount(*3) Cooling Only (kg) 11.5 11.5 10.5 11.5 11.5 10.5
High-pressure switch (Pa) OFF: 2.9 ON: 3.73
Protective devices (*4)
MCA(*5) (A) 98.2 101.5
Power supply wiring Unit
MOCP(*6) (A) 125 125
Connecting Gas side (mm) ø 41.3
port Liquid side (mm) ø 22.2
diameter Balance side (mm) ø 9.5
Gas side Brazing
Connecting Liquid side Flare
method
Refrigerant piping Balance side Flare
Max. equivation length (mm) 235
Max. real length (mm) 190
Max. total pipe length (Real length) (*7) (mm) 500
(*8) (mm) Outdoor unit is higher than indoor unit : 70
Max. height difference
(*9) (mm) Outdoor unit is lower than indoor unit: 40
Control wiring between indoor and (Up to 1000m) Shield wire 1.25mm2 x 2 cores
outdoor units + Central controller wiring (Up to 2000m) Shield wire 2.0mm2 x 2 cores
Max. No. of connected indoor units 48 48
Cooling (dB(A)) 65.0 65.5
Sound pressure level
Heating (dB(A)) 67.0 67.5
Max. external static pressure (Pa) 40 40 50 40 40 50
Cooling CDB -5 to 43
Operation temperature range
Heating CWB -20 to 15.5

Note
*1 :Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
The standard piping means that mian pipe length is 5m, branching pipe length is 2.5m of branch piping connected with a 0 meter height.
*2 :The source voltage must not fluctuate more than ±10%.
*3 :The amount does not consider extra piping length. Refrigerant must be added on site in accordance with the actual piping length.
*4 :Discharge temp. sensor / Suction temp. sensor / High-pressure sensor / Low-pressure sensor / High-pressure switch / PC board fuse
*5 :Select wire size base on the larger value of MCA.
MCA : Minimum Circuit Amps
*6 :MOCP : Maximum Overcurrent Protection(Amps)
*7 :The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.
*8 :Set 50m or less if the height difference between indoor units exceeds 3m.
*9 :Set 30m or less if the height difference between indoor units exceeds 3m.

11 -7
11 Technical Specifications

Equivalent HP Equivalent to 46HP Equivalent to 48HP


Heat Pump MMY- AP4614HT8 AP4814HT8
Model name
Cooling Only MMY- AP4614T8 AP4814T8
Outdoor unit type Inverter unit
Heat Pump MMY- MAP1604HT8 MAP1604HT8 MAP1404HT8 MAP1604HT8 MAP1604HT8 MAP1604HT8
Outdoor unit model
Cooling Only MMY- MAP1604T8 MAP1604T8 MAP1404T8 MAP1604T8 MAP1604T8 MAP1604T8
Cooling capacity (*1) (kW) 130.0 135.0
Heating capacity (*1) (kW) 145.0 150.0
Power supply (*2) 3phase 4wires 50Hz 400V (380-415V)
Running current (A) 59.3 62.4
Power consumption (kW) 38.90 41.10
Cooling
Power factor (%) 95 95
Electrical EER (Energy Efficiency Ratio) (kW/kW)) 3.34 3.28
characteristics Running current (A) 61.7 66.1
(*1) Power consumption (kW) 39.60 42.60
Heating
Power factor (%) 93 93
EER (Energy Efficiency Ratio) (kW/kW)) 3.66 3.52
Starting Current (A) Soft Start
Height (mm) 1,887 1,887 1,887 1,887 1,887 1,887
Packing Width (mm) 1,282 1,282 1,282 1,282 1,282 1,282
Depth (mm) 828 828 828 828 828 828
Dimension
Height (mm) 1,800 1,800 1,800 1,800 1,800 1,800
Unit Width (mm) 1,210 1,210 1,210 1,210 1,210 1,210
Depth (mm) 780 780 780 780 780 780
Heat Pump (kg) 347 347 347 347 347 347
Packing
Cooling only (kg) 347 347 347 347 347 347
Weight
Heat Pump (kg) 330 330 330 330 330 330
Unit
Cooling only (kg) 330 330 330 330 330 330
Colour Silky shade (Munsell 1Y8.5/0.5)
Type Hermetic twin rotary compressor
Compressor
Motor output (kW) 3.6 x 3 3.6 x 3 3.0 x 3 3.6 x 3 3.6 x 3 3.6 x 3
Fan Propeller fan
Fan unit Motor output (kW) 1.0 1.0 1.0 1.0 1.0 1.0
Air volume (m3/h) 13,000 13,000 12,000 13,000 13,000 13,000
Heat exchanger Finned tube
R410A
Refrigerant Charged Heat Pump (kg) 11.5 11.5 11.5 11.5 11.5 11.5
refrigerant
amount(*3) Cooling Only (kg) 11.5 11.5 11.5 11.5 11.5 11.5
High-pressure switch (Pa) OFF: 2.9 ON: 3.73
Protective devices (*4)
MCA(*5) (A) 106.2 109.5
Power supply wiring Unit
MOCP(*6) (A) 125 125
Connecting Gas side (mm) ø 41.3
port Liquid side (mm) ø 22.2
diameter Balance side (mm) ø 9.5
Gas side Brazing
Connecting Liquid side Flare
method
Refrigerant piping Balance side Flare
Max. equivation length (mm) 185
Max. real length (mm) 155
Max. total pipe length (Real length) (*7) (mm) 500
(*8) (mm) Outdoor unit is higher than indoor unit : 70
Max. height difference
(*9) (mm) Outdoor unit is lower than indoor unit: 40
Control wiring between indoor and (Up to 1000m) Shield wire 1.25mm2 x 2 cores
outdoor units + Central controller wiring (Up to 2000m) Shield wire 2.0mm2 x 2 cores
Max. No. of connected indoor units 48 48
Cooling (dB(A)) 65.5 66.0
Sound pressure level
Heating (dB(A)) 67.5 68.0
Max. external static pressure (Pa) 40 40 40 40 40 40
Cooling CDB -5 to 43
Operation temperature range
Heating CWB -20 to 15.5

Note
*1 :Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
The standard piping means that mian pipe length is 5m, branching pipe length is 2.5m of branch piping connected with a 0 meter height.
*2 :The source voltage must not fluctuate more than ±10%.
*3 :The amount does not consider extra piping length. Refrigerant must be added on site in accordance with the actual piping length.
*4 :Discharge temp. sensor / Suction temp. sensor / High-pressure sensor / Low-pressure sensor / High-pressure switch / PC board fuse
*5 :Select wire size base on the larger value of MCA.
MCA : Minimum Circuit Amps
*6 :MOCP : Maximum Overcurrent Protection(Amps)
*7 :The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.
*8 :Set 50m or less if the height difference between indoor units exceeds 3m.
*9 :Set 30m or less if the height difference between indoor units exceeds 3m.

11 -8
11 Technical Specifications

High efficiency model (Combination)


Equivalent HP Equivalent to 16HP Equivalent to 24HP
Heat Pump MMY- AP1624HT8 AP2424HT8
Model name
Cooling Only MMY- AP1624T8 AP2424T8
Outdoor unit type Inverter unit
Heat Pump MMY- MAP0804HT8 MAP0804HT8 MAP0804HT8 MAP0804HT8 MAP0804HT8
Outdoor unit model
Cooling Only MMY- MAP0804T8 MAP0804T8 MAP0804T8 MAP0804T8 MAP0804T8
Cooling capacity (*1) (kW) 45.0 68.0
Heating capacity (*1) (kW) 50.0 76.5
Power supply (*2) 3phase 4wires 50Hz 400V (380-415V)
Running current (A) 17.1 26.0
Power consumption (kW) 10.89 16.58
Cooling
Power factor (%) 92 92
Electrical EER (Energy Efficiency Ratio) (kW/kW)) 4.13 4.10
characteristics Running current (A) 17.5 27.3
(*1) Power consumption (kW) 11.06 17.18
Heating
Power factor (%) 91 91
EER (Energy Efficiency Ratio) (kW/kW)) 4.52 4.45
Starting Current (A) Soft Start
Height (mm) 1,887 1,887 1,887 1,887 1,887
Packing Width (mm) 1,062 1,062 1,062 1,062 1,062
Depth (mm) 828 828 828 828 828
Dimension
Height (mm) 1,800 1,800 1,800 1,800 1,800
Unit Width (mm) 990 990 990 990 990
Depth (mm) 780 780 780 780 780
Heat Pump (kg) 257 257 257 257 257
Packing
Cooling only (kg) 256 256 256 256 256
Weight
Heat Pump (kg) 242 242 242 242 242
Unit
Cooling only (kg) 241 241 241 241 241
Colour Silky shade (Munsell 1Y8.5/0.5)
Type Hermetic twin rotary compressor
Compressor
Motor output (kW) 2.3 x 2 2.3 x 2 2.3 x 2 2.3 x 2 2.3 x 2
Fan Propeller fan
Fan unit Motor output (kW) 1.0 1.0 1.0 1.0 1.0
Air volume (m3/h) 9,900 9,900 9,900 9,900 9,900
Heat exchanger Finned tube
R410A
Refrigerant Charged Heat Pump (kg) 11.5 11.5 11.5 11.5 11.5
refrigerant
amount(*3) Cooling Only (kg) 10.5 10.5 10.5 10.5 10.5
High-pressure switch (Pa) OFF: 2.9 ON: 3.73
Protective devices (*4)
MCA(*5) (A) 46.9 70.4
Power supply wiring Unit
MOCP(*6) (A) 63 80
Connecting Gas side (mm) ø 28.6 ø 34.9
port Liquid side (mm) ø 15.9 ø 19.1
diameter Balance side (mm) ø 9.5
Gas side Brazing
Connecting Liquid side Flare
method
Refrigerant piping Balance side Flare
Max. equivation length (mm) 220 235
Max. real length (mm) 180 190
Max. total pipe length (Real length) (*7) (mm) 300
(*8) (mm) Outdoor unit is higher than indoor unit : 70
Max. height difference
(*9) (mm) Outdoor unit is lower than indoor unit: 40
Control wiring between indoor and (Up to 1000m) Shield wire 1.25mm2 x 2 cores
outdoor units + Central controller wiring (Up to 2000m) Shield wire 2.0mm2 x 2 cores
Max. No. of connected indoor units 27 40
Cooling (dB(A)) 58.0 60.0
Sound pressure level
Heating (dB(A)) 59.0 61.0
Max. external static pressure (Pa) 60 60 60 60 60
Cooling CDB -5 to 43
Operation temperature range
Heating CWB -20 to 15.5

Note
*1 :Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
The standard piping means that mian pipe length is 5m, branching pipe length is 2.5m of branch piping connected with a 0 meter height.
*2 :The source voltage must not fluctuate more than ±10%.
*3 :The amount does not consider extra piping length. Refrigerant must be added on site in accordance with the actual piping length.
*4 :Discharge temp. sensor / Suction temp. sensor / High-pressure sensor / Low-pressure sensor / High-pressure switch / PC board fuse
*5 :Select wire size base on the larger value of MCA.
MCA : Minimum Circuit Amps
*6 :MOCP : Maximum Overcurrent Protection(Amps)
*7 :The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.
*8 :Set 50m or less if the height difference between indoor units exceeds 3m.
*9 :Set 30m or less if the height difference between indoor units exceeds 3m.

11 -9
11 Technical Specifications

Equivalent HP Equivalent to 26HP Equivalent to 28HP


Heat Pump MMY- AP2624HT8 AP2824HT8
Model name
Cooling Only MMY- AP2624T8 AP2824T8
Outdoor unit type Inverter unit
Heat Pump MMY- MAP1004HT8 MAP0804HT8 MAP0804HT8 MAP1004HT8 MAP1004HT8 MAP0804HT8
Outdoor unit model
Cooling Only MMY- MAP1004T8 MAP0804T8 MAP0804T8 MAP1004T8 MAP1004T8 MAP0804T8
Cooling capacity (*1) (kW) 73.0 78.5
Heating capacity (*1) (kW) 81.5 88.0
Power supply (*2) 3phase 4wires 50Hz 400V (380-415V)
Running current (A) 28.5 31.3
Power consumption (kW) 18.31 20.27
Cooling
Power factor (%) 93 94
Electrical EER (Energy Efficiency Ratio) (kW/kW)) 3.99 3.87
characteristics Running current (A) 29.3 32.3
(*1) Power consumption (kW) 18.56 20.53
Heating
Power factor (%) 91 92
EER (Energy Efficiency Ratio) (kW/kW)) 4.39 4.29
Starting Current (A) Soft Start
Height (mm) 1,887 1,887 1,887 1,887 1,887 1,887
Packing Width (mm) 1,062 1,062 1,062 1,062 1,062 1,062
Depth (mm) 828 828 828 828 828 828
Dimension
Height (mm) 1,800 1,800 1,800 1,800 1,800 1,800
Unit Width (mm) 990 990 990 990 990 990
Depth (mm) 780 780 780 780 780 780
Heat Pump (kg) 257 257 257 257 257 257
Packing
Cooling only (kg) 256 256 256 256 256 256
Weight
Heat Pump (kg) 242 242 242 242 242 242
Unit
Cooling only (kg) 241 241 241 241 241 241
Colour Silky shade (Munsell 1Y8.5/0.5)
Type Hermetic twin rotary compressor
Compressor
Motor output (kW) 3.1 x 2 2.3 x 2 2.3 x 2 3.1 x 2 3.1 x 2 2.3 x 2
Fan Propeller fan
Fan unit Motor output (kW) 1.0 1.0 1.0 1.0 1.0 1.0
Air volume (m3/h) 10,500 9,900 9,900 10,500 10,500 9,900
Heat exchanger Finned tube
R410A
Refrigerant Charged Heat Pump (kg) 11.5 11.5 11.5 11.5 11.5 11.5
refrigerant
amount(*3) Cooling Only (kg) 10.5 10.5 10.5 10.5 10.5 10.5
High-pressure switch (Pa) OFF: 2.9 ON: 3.73
Protective devices (*4)
MCA(*5) (A) 72.4 74.5
Power supply wiring Unit
MOCP(*6) (A) 80 100
Connecting Gas side (mm) ø 34.9
port Liquid side (mm) ø 19.1
diameter Balance side (mm) ø 9.5
Gas side Brazing
Connecting Liquid side Flare
method
Refrigerant piping Balance side Flare
Max. equivation length (mm) 235
Max. real length (mm) 190
Max. total pipe length (Real length) (*7) (mm) 300
(*8) (mm) Outdoor unit is higher than indoor unit : 70
Max. height difference
(*9) (mm) Outdoor unit is lower than indoor unit: 40
Control wiring between indoor and (Up to 1000m) Shield wire 1.25mm2 x 2 cores
outdoor units + Central controller wiring (Up to 2000m) Shield wire 2.0mm2 x 2 cores
Max. No. of connected indoor units 43 47
Cooling (dB(A)) 60.5 61.5
Sound pressure level
Heating (dB(A)) 61.5 62.5
Max. external static pressure (Pa) 60 60 60 60 60 60
Cooling CDB -5 to 43
Operation temperature range
Heating CWB -20 to 15.5

Note
*1 :Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
The standard piping means that mian pipe length is 5m, branching pipe length is 2.5m of branch piping connected with a 0 meter height.
*2 :The source voltage must not fluctuate more than ±10%.
*3 :The amount does not consider extra piping length. Refrigerant must be added on site in accordance with the actual piping length.
*4 :Discharge temp. sensor / Suction temp. sensor / High-pressure sensor / Low-pressure sensor / High-pressure switch / PC board fuse
*5 :Select wire size base on the larger value of MCA.
MCA : Minimum Circuit Amps
*6 :MOCP : Maximum Overcurrent Protection(Amps)
*7 :The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.
*8 :Set 50m or less if the height difference between indoor units exceeds 3m.
*9 :Set 30m or less if the height difference between indoor units exceeds 3m.

11 -10
11 Technical Specifications

Equivalent HP Equivalent to 30HP Equivalent to 32HP


Heat Pump MMY- AP3024HT8 AP3224HT8
Model name
Cooling Only MMY- AP3024T8 AP3224T8
Outdoor unit type Inverter unit
Heat Pump MMY- MAP1004HT8 MAP1004HT8 MAP1004HT8 MAP0804HT8 MAP0804HT8 MAP0804HT8 MAP0804HT8
Outdoor unit model
Cooling Only MMY- MAP1004T8 MAP1004T8 MAP1004T8 MAP0804T8 MAP0804T8 MAP0804T8 MAP0804T8
Cooling capacity (*1) (kW) 85.0 90.0
Heating capacity (*1) (kW) 95.0 100.0
Power supply (*2) 3phase 4wires 50Hz 400V (380-415V)
Running current (A) 34.9 34.2
Power consumption (kW) 22.75 21.79
Cooling
Power factor (%) 94 92
Electrical EER (Energy Efficiency Ratio) (kW/kW)) 3.74 4.13
characteristics Running current (A) 35.6 35.1
(*1) Power consumption (kW) 22.71 22.12
Heating
Power factor (%) 92 91
EER (Energy Efficiency Ratio) (kW/kW)) 4.18 4.52
Starting Current (A) Soft Start
Height (mm) 1,887 1,887 1,887 1,887 1,887 1,887 1,887
Packing Width (mm) 1,062 1,062 1,062 1,062 1,062 1,062 1,062
Depth (mm) 828 828 828 828 828 828 828
Dimension
Height (mm) 1,800 1,800 1,800 1,800 1,800 1,800 1,800
Unit Width (mm) 990 990 990 990 990 990 990
Depth (mm) 780 780 780 780 780 780 780
Heat Pump (kg) 257 257 257 257 257 257 257
Packing
Cooling only (kg) 256 256 256 256 256 256 256
Weight
Heat Pump (kg) 242 242 242 242 242 242 242
Unit
Cooling only (kg) 241 241 241 241 241 241 241
Colour Silky shade (Munsell 1Y8.5/0.5)
Type Hermetic twin rotary compressor
Compressor
Motor output (kW) 3.1 x 2 3.1 x 2 3.1 x 2 2.3 x 2 2.3 x 2 2.3 x 2 2.3 x 2
Fan Propeller fan
Fan unit Motor output (kW) 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Air volume (m3/h) 10,500 10,500 10,500 9,900 9,900 9,900 9,900
Heat exchanger Finned tube
R410A
Refrigerant Charged Heat Pump (kg) 11.5 11.5 11.5 11.5 11.5 11.5 11.5
refrigerant
amount(*3) Cooling Only (kg) 10.5 10.5 10.5 10.5 10.5 10.5 10.5
High-pressure switch (Pa) OFF: 2.9 ON: 3.73
Protective devices (*4)
MCA(*5) (A) 76.5 93.8
Power supply wiring Unit
MOCP(*6) (A) 100 125
Connecting Gas side (mm) ø 34.9
port Liquid side (mm) ø 19.1
diameter Balance side (mm) ø 9.5
Gas side Brazing
Connecting Liquid side Flare
method
Refrigerant piping Balance side Flare
Max. equivation length (mm) 235
Max. real length (mm) 190
Max. total pipe length (Real length) (*7) (mm) 300
(*8) (mm) Outdoor unit is higher than indoor unit : 70
Max. height difference
(*9) (mm) Outdoor unit is lower than indoor unit: 40
Control wiring between indoor and (Up to 1000m) Shield wire 1.25mm2 x 2 cores
outdoor units + Central controller wiring (Up to 2000m) Shield wire 2.0mm2 x 2 cores
Max. No. of connected indoor units 48 48
Cooling (dB(A)) 62.0 61.0
Sound pressure level
Heating (dB(A)) 63.0 62.0
Max. external static pressure (Pa) 60 60 60 60 60 60 60
Cooling CDB -5 to 43
Operation temperature range
Heating CWB -20 to 15.5

Note
*1 :Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
The standard piping means that mian pipe length is 5m, branching pipe length is 2.5m of branch piping connected with a 0 meter height.
*2 :The source voltage must not fluctuate more than ±10%.
*3 :The amount does not consider extra piping length. Refrigerant must be added on site in accordance with the actual piping length.
*4 :Discharge temp. sensor / Suction temp. sensor / High-pressure sensor / Low-pressure sensor / High-pressure switch / PC board fuse
*5 :Select wire size base on the larger value of MCA.
MCA : Minimum Circuit Amps
*6 :MOCP : Maximum Overcurrent Protection(Amps)
*7 :The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.
*8 :Set 50m or less if the height difference between indoor units exceeds 3m.
*9 :Set 30m or less if the height difference between indoor units exceeds 3m.

11 -11
11 Technical Specifications

Equivalent HP Equivalent to 34HP Equivalent to 36HP


Heat Pump MMY- AP3424HT8 AP3624HT8
Model name
Cooling Only MMY- AP3424T8 AP3624T8
Outdoor unit type Inverter unit
Heat Pump MMY- MAP1004HT8 MAP0804HT8 MAP0804HT8 MAP0804HT8 MAP1004HT8 MAP1004HT8 MAP0804HT8 MAP0804HT8
Outdoor unit model
Cooling Only MMY- MAP1004T8 MAP0804T8 MAP0804T8 MAP0804T8 MAP1004T8 MAP1004T8 MAP0804T8 MAP0804T8
Cooling capacity (*1) (kW) 96.0 101.0
Heating capacity (*1) (kW) 108.0 113.0
Power supply (*2) 3phase 4wires 50Hz 400V (380-415V)
Running current (A) 37.4 39.9
Power consumption (kW) 24.00 25.72
Cooling
Power factor (%) 93 93
Electrical EER (Energy Efficiency Ratio) (kW/kW)) 4.00 3.93
characteristics Running current (A) 39.0 41.1
(*1) Power consumption (kW) 24.70 26.06
Heating
Power factor (%) 91 92
EER (Energy Efficiency Ratio) (kW/kW)) 4.37 4.34
Starting Current (A) Soft Start
Height (mm) 1,887 1,887 1,887 1,887 1,887 1,887 1,887 1,887
Packing Width (mm) 1,062 1,062 1,062 1,062 1,062 1,062 1,062 1,062
Depth (mm) 828 828 828 828 828 828 828 828
Dimension
Height (mm) 1,800 1,800 1,800 1,800 1,800 1,800 1,800 1,800
Unit Width (mm) 990 990 990 990 990 990 990 990
Depth (mm) 780 780 780 780 780 780 780 780
Heat Pump (kg) 257 257 257 257 257 257 257 257
Packing
Cooling only (kg) 256 256 256 256 256 256 256 256
Weight
Heat Pump (kg) 242 242 242 242 242 242 242 242
Unit
Cooling only (kg) 241 241 241 241 241 241 241 241
Colour Silky shade (Munsell 1Y8.5/0.5)
Type Hermetic twin rotary compressor
Compressor
Motor output (kW) 3.1 x 2 2.3 x 2 2.3 x 2 2.3 x 2 3.1 x 2 3.1 x 2 2.3 x 2 2.3 x 2
Fan Propeller fan
Fan unit Motor output (kW) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Air volume (m3/h) 10,500 9,900 9,900 9,900 10,500 10,500 9,900 9,900
Heat exchanger Finned tube
R410A
Refrigerant Charged Heat Pump (kg) 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5
refrigerant
amount(*3) Cooling Only (kg) 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5
High-pressure switch (Pa) OFF: 2.9 ON: 3.73
Protective devices (*4)
MCA(*5) (A) 95.9 97.9
Power supply wiring Unit
MOCP(*6) (A) 125 125
Connecting Gas side (mm) ø 34.9 ø 41.3
port Liquid side (mm) ø 19.1 ø 22.2
diameter Balance side (mm) ø 9.5
Gas side Brazing
Connecting Liquid side Flare
method
Refrigerant piping Balance side Flare
Max. equivation length (mm) 235
Max. real length (mm) 190
Max. total pipe length (Real length) (*7) (mm) 500
(*8) (mm) Outdoor unit is higher than indoor unit : 70
Max. height difference
(*9) (mm) Outdoor unit is lower than indoor unit: 40
Control wiring between indoor and (Up to 1000m) Shield wire 1.25mm2 x 2 cores
outdoor units + Central controller wiring (Up to 2000m) Shield wire 2.0mm2 x 2 cores
Max. No. of connected indoor units 48 48
Cooling (dB(A)) 62.0 62.5
Sound pressure level
Heating (dB(A)) 63.0 63.5
Max. external static pressure (Pa) 60 60 60 60 60 60 60 60
Cooling CDB -5 to 43
Operation temperature range
Heating CWB -20 to 15.5

Note
*1 :Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
The standard piping means that mian pipe length is 5m, branching pipe length is 2.5m of branch piping connected with a 0 meter height.
*2 :The source voltage must not fluctuate more than ±10%.
*3 :The amount does not consider extra piping length. Refrigerant must be added on site in accordance with the actual piping length.
*4 :Discharge temp. sensor / Suction temp. sensor / High-pressure sensor / Low-pressure sensor / High-pressure switch / PC board fuse
*5 :Select wire size base on the larger value of MCA.
MCA : Minimum Circuit Amps
*6 :MOCP : Maximum Overcurrent Protection(Amps)
*7 :The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.
*8 :Set 50m or less if the height difference between indoor units exceeds 3m.
*9 :Set 30m or less if the height difference between indoor units exceeds 3m.

11 -12
11 Technical Specifications

Equivalent HP Equivalent to 38HP Equivalent to 40HP


Heat Pump MMY- AP3824HT8 AP4024HT8
Model name
Cooling Only MMY- AP3824T8 AP4024T8
Outdoor unit type Inverter unit
Heat Pump MMY- MAP1004HT8 MAP1004HT8 MAP1004HT8 MAP0804HT8 MAP1004HT8 MAP1004HT8 MAP1004HT8 MAP1004HT8
Outdoor unit model
Cooling Only MMY- MAP1004T8 MAP1004T8 MAP1004T8 MAP0804T8 MAP1004T8 MAP1004T8 MAP1004T8 MAP1004T8
Cooling capacity (*1) (kW) 106.5 112.0
Heating capacity (*1) (kW) 119.5 127.0
Power supply (*2) 3phase 4wires 50Hz 400V (380-415V)
Running current (A) 42.7 45.5
Power consumption (kW) 27.68 29.64
Cooling
Power factor (%) 94 94
Electrical EER (Energy Efficiency Ratio) (kW/kW)) 3.85 3.78
characteristics Running current (A) 44.1 47.7
(*1) Power consumption (kW) 28.03 30.42
Heating
Power factor (%) 92 92
EER (Energy Efficiency Ratio) (kW/kW)) 4.26 4.17
Starting Current (A) Soft Start
Height (mm) 1,887 1,887 1,887 1,887 1,887 1,887 1,887 1,887
Packing Width (mm) 1,062 1,062 1,062 1,062 1,062 1,062 1,062 1,062
Depth (mm) 828 828 828 828 828 828 828 828
Dimension
Height (mm) 1,800 1,800 1,800 1,800 1,800 1,800 1,800 1,800
Unit Width (mm) 990 990 990 990 990 990 990 990
Depth (mm) 780 780 780 780 780 780 780 780
Heat Pump (kg) 257 257 257 257 257 257 257 257
Packing
Cooling only (kg) 256 256 256 256 256 256 256 256
Weight
Heat Pump (kg) 242 242 242 242 242 242 242 242
Unit
Cooling only (kg) 241 241 241 241 241 241 241 241
Colour Silky shade (Munsell 1Y8.5/0.5)
Type Hermetic twin rotary compressor
Compressor
Motor output (kW) 3.1 x 2 3.1 x 2 3.1 x 2 2.3 x 2 3.1 x 2 3.1 x 2 3.1 x 2 3.1 x 2
Fan Propeller fan
Fan unit Motor output (kW) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Air volume (m3/h) 10,500 10,500 10,500 9,900 10,500 10,500 10,500 10,500
Heat exchanger Finned tube
R410A
Refrigerant Charged Heat Pump (kg) 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5
refrigerant
amount(*3) Cooling Only (kg) 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5
High-pressure switch (Pa) OFF: 2.9 ON: 3.73
Protective devices (*4)
MCA(*5) (A) 100.0 102.0
Power supply wiring Unit
MOCP(*6) (A) 125 125
Connecting Gas side (mm) ø 41.3
port Liquid side (mm) ø 22.2
diameter Balance side (mm) ø 9.5
Gas side Brazing
Connecting Liquid side Flare
method
Refrigerant piping Balance side Flare
Max. equivation length (mm) 235
Max. real length (mm) 190
Max. total pipe length (Real length) (*7) (mm) 500
(*8) (mm) Outdoor unit is higher than indoor unit : 70
Max. height difference
(*9) (mm) Outdoor unit is lower than indoor unit: 40
Control wiring between indoor and (Up to 1000m) Shield wire 1.25mm2 x 2 cores
outdoor units + Central controller wiring (Up to 2000m) Shield wire 2.0mm2 x 2 cores
Max. No. of connected indoor units 48 48
Cooling (dB(A)) 63.0 63.0
Sound pressure level
Heating (dB(A)) 64.0 64.0
Max. external static pressure (Pa) 60 60 60 60 60 60 60 60
Cooling CDB -5 to 43
Operation temperature range
Heating CWB -20 to 15.5

Note
*1 :Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
The standard piping means that mian pipe length is 5m, branching pipe length is 2.5m of branch piping connected with a 0 meter height.
*2 :The source voltage must not fluctuate more than ±10%.
*3 :The amount does not consider extra piping length. Refrigerant must be added on site in accordance with the actual piping length.
*4 :Discharge temp. sensor / Suction temp. sensor / High-pressure sensor / Low-pressure sensor / High-pressure switch / PC board fuse
*5 :Select wire size base on the larger value of MCA.
MCA : Minimum Circuit Amps
*6 :MOCP : Maximum Overcurrent Protection(Amps)
*7 :The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.
*8 :Set 50m or less if the height difference between indoor units exceeds 3m.
*9 :Set 30m or less if the height difference between indoor units exceeds 3m.

11 -13
11 Technical Specifications

Equivalent HP Equivalent to 42HP Equivalent to 44HP


Heat Pump MMY- AP4224HT8 AP4424HT8
Model name
Cooling Only MMY- AP4224T8 AP4424T8
Outdoor unit type Inverter unit
Heat Pump MMY- MAP1204HT8 MAP1004HT8 MAP1004HT8 MAP1004HT8 MAP1204HT8 MAP1204HT8 MAP1004HT8 MAP1004HT8
Outdoor unit model
Cooling Only MMY- MAP1204T8 MAP1004T8 MAP1004T8 MAP1004T8 MAP1204T8 MAP1204T8 MAP1004T8 MAP1004T8
Cooling capacity (*1) (kW) 118.0 123.5
Heating capacity (*1) (kW) 132.0 138.0
Power supply (*2) 3phase 4wires 50Hz 400V (380-415V)
Running current (A) 49.2 52.5
Power consumption (kW) 32.04 34.19
Cooling
Power factor (%) 94 94
Electrical EER (Energy Efficiency Ratio) (kW/kW)) 3.68 3.61
characteristics Running current (A) 51.3 55.5
(*1) Power consumption (kW) 32.70 35.40
Heating
Power factor (%) 92 92
EER (Energy Efficiency Ratio) (kW/kW)) 4.04 3.90
Starting Current (A) Soft Start
Height (mm) 1,887 1,887 1,887 1,887 1,887 1,887 1,887 1,887
Packing Width (mm) 1,062 1,062 1,062 1,062 1,062 1,062 1,062 1,062
Depth (mm) 828 828 828 828 828 828 828 828
Dimension
Height (mm) 1,800 1,800 1,800 1,800 1,800 1,800 1,800 1,800
Unit Width (mm) 990 990 990 990 990 990 990 990
Depth (mm) 780 780 780 780 780 780 780 780
Heat Pump (kg) 257 257 257 257 257 257 257 257
Packing
Cooling only (kg) 256 256 256 256 256 256 256 256
Weight
Heat Pump (kg) 242 242 242 242 242 242 242 242
Unit
Cooling only (kg) 241 241 241 241 241 241 241 241
Colour Silky shade (Munsell 1Y8.5/0.5)
Type Hermetic twin rotary compressor
Compressor
Motor output (kW) 4.2 x 2 3.1 x 2 3.1 x 2 3.1 x 2 4.2 x 2 4.2 x 2 3.1 x 2 3.1 x 2
Fan Propeller fan
Fan unit Motor output (kW) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Air volume (m3/h) 11,600 10,500 10,500 10,500 11,600 11,600 10,500 10,500
Heat exchanger Finned tube
R410A
Refrigerant Charged Heat Pump (kg) 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5
refrigerant
amount(*3) Cooling Only (kg) 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5
High-pressure switch (Pa) OFF: 2.9 ON: 3.73
Protective devices (*4)
MCA(*5) (A) 105.0 108.0
Power supply wiring Unit
MOCP(*6) (A) 125 125
Connecting Gas side (mm) ø 41.3
port Liquid side (mm) ø 22.2
diameter Balance side (mm) ø 9.5
Gas side Brazing
Connecting Liquid side Flare
method
Refrigerant piping Balance side Flare
Max. equivation length (mm) 235
Max. real length (mm) 190
Max. total pipe length (Real length) (*7) (mm) 500
(*8) (mm) Outdoor unit is higher than indoor unit : 70
Max. height difference
(*9) (mm) Outdoor unit is lower than indoor unit: 40
Control wiring between indoor and (Up to 1000m) Shield wire 1.25mm2 x 2 cores
outdoor units + Central controller wiring (Up to 2000m) Shield wire 2.0mm2 x 2 cores
Max. No. of connected indoor units 48 48
Cooling (dB(A)) 64.0 64.5
Sound pressure level
Heating (dB(A)) 65.0 66.0
Max. external static pressure (Pa) 50 60 60 60 50 50 60 60
Cooling CDB -5 to 43
Operation temperature range
Heating CWB -20 to 15.5

Note
*1 :Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
The standard piping means that mian pipe length is 5m, branching pipe length is 2.5m of branch piping connected with a 0 meter height.
*2 :The source voltage must not fluctuate more than ±10%.
*3 :The amount does not consider extra piping length. Refrigerant must be added on site in accordance with the actual piping length.
*4 :Discharge temp. sensor / Suction temp. sensor / High-pressure sensor / Low-pressure sensor / High-pressure switch / PC board fuse
*5 :Select wire size base on the larger value of MCA.
MCA : Minimum Circuit Amps
*6 :MOCP : Maximum Overcurrent Protection(Amps)
*7 :The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.
*8 :Set 50m or less if the height difference between indoor units exceeds 3m.
*9 :Set 30m or less if the height difference between indoor units exceeds 3m.

11 -14
11 Technical Specifications

Equivalent HP Equivalent to 46HP Equivalent to 48HP


Heat Pump MMY- AP4624HT8 AP4824HT8
Model name
Cooling Only MMY- AP4624T8 AP4824T8
Outdoor unit type Inverter unit
Heat Pump MMY- MAP1204HT8 MAP1204HT8 MAP1204HT8 MAP1004HT8 MAP1204HT8 MAP1204HT8 MAP1204HT8 MAP1204HT8
Outdoor unit model
Cooling Only MMY- MAP1204T8 MAP1204T8 MAP1204T8 MAP1004T8 MAP1204T8 MAP1204T8 MAP1204T8 MAP1204T8
Cooling capacity (*1) (kW) 130.0 135.0
Heating capacity (*1) (kW) 145.0 150.0
Power supply (*2) 3phase 4wires 50Hz 400V (380-415V)
Running current (A) 56.6 59.5
Power consumption (kW) 36.88 38.76
Cooling
Power factor (%) 94 94
Electrical EER (Energy Efficiency Ratio) (kW/kW)) 3.52 3.48
characteristics Running current (A) 60.5 64.0
(*1) Power consumption (kW) 38.57 40.80
Heating
Power factor (%) 92 92
EER (Energy Efficiency Ratio) (kW/kW)) 3.76 3.68
Starting Current (A) Soft Start
Height (mm) 1,887 1,887 1,887 1,887 1,887 1,887 1,887 1,887
Packing Width (mm) 1,062 1,062 1,062 1,062 1,062 1,062 1,062 1,062
Depth (mm) 828 828 828 828 828 828 828 828
Dimension
Height (mm) 1,800 1,800 1,800 1,800 1,800 1,800 1,800 1,800
Unit Width (mm) 990 990 990 990 990 990 990 990
Depth (mm) 780 780 780 780 780 780 780 780
Heat Pump (kg) 257 257 257 257 257 257 257 257
Packing
Cooling only (kg) 256 256 256 256 256 256 256 256
Weight
Heat Pump (kg) 242 242 242 242 242 242 242 242
Unit
Cooling only (kg) 241 241 241 241 241 241 241 241
Colour Silky shade (Munsell 1Y8.5/0.5)
Type Hermetic twin rotary compressor
Compressor
Motor output (kW) 4.2 x 2 4.2 x 2 4.2 x 2 3.1 x 2 4.2 x 2 4.2 x 2 4.2 x 2 4.2 x 2
Fan Propeller fan
Fan unit Motor output (kW) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Air volume (m3/h) 11,600 11,600 11,600 10,500 11,600 11,600 11,600 11,600
Heat exchanger Finned tube
R410A
Refrigerant Charged Heat Pump (kg) 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5
refrigerant
amount(*3) Cooling Only (kg) 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5
High-pressure switch (Pa) OFF: 2.9 ON: 3.73
Protective devices (*4)
MCA(*5) (A) 111.0 114.0
Power supply wiring Unit
MOCP(*6) (A) 125 125
Connecting Gas side (mm) ø 41.3
port Liquid side (mm) ø 22.2
diameter Balance side (mm) ø 9.5
Gas side Brazing
Connecting Liquid side Flare
method
Refrigerant piping Balance side Flare
Max. equivation length (mm) 185
Max. real length (mm) 155
Max. total pipe length (Real length) (*7) (mm) 500
(*8) (mm) Outdoor unit is higher than indoor unit : 70
Max. height difference
(*9) (mm) Outdoor unit is lower than indoor unit: 40
Control wiring between indoor and (Up to 1000m) Shield wire 1.25mm2 x 2 cores
outdoor units + Central controller wiring (Up to 2000m) Shield wire 2.0mm2 x 2 cores
Max. No. of connected indoor units 48 48
Cooling (dB(A)) 65.0 65.0
Sound pressure level
Heating (dB(A)) 66.5 67.0
Max. external static pressure (Pa) 50 50 50 60 50 50 50 50
Cooling CDB -5 to 43
Operation temperature range
Heating CWB -20 to 15.5

Note
*1 :Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
The standard piping means that mian pipe length is 5m, branching pipe length is 2.5m of branch piping connected with a 0 meter height.
*2 :The source voltage must not fluctuate more than ±10%.
*3 :The amount does not consider extra piping length. Refrigerant must be added on site in accordance with the actual piping length.
*4 :Discharge temp. sensor / Suction temp. sensor / High-pressure sensor / Low-pressure sensor / High-pressure switch / PC board fuse
*5 :Select wire size base on the larger value of MCA.
MCA : Minimum Circuit Amps
*6 :MOCP : Maximum Overcurrent Protection(Amps)
*7 :The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.
*8 :Set 50m or less if the height difference between indoor units exceeds 3m.
*9 :Set 30m or less if the height difference between indoor units exceeds 3m.

11 -15
11 Technical Specifications

11-1-2. Dimensional drawing


Single unit
Model : MMY-MAP0501HT8, MAP0501T8 (SMMS)
MMY-MAP0601HT8, MAP0601T8
MMY-MAP0801HT8, MAP0801T8
MMY-MAP1001HT8, MAP1001T8
MMY-MAP1201HT8, MAP1201T8
Applied model A B C
MMY-MAP0501HT7/HT8 ø 15.9 ø 9.5 280
MMY-MAP0601HT7/HT8 ø 19.1 ø 9.5 280
MMY-MAP0801HT7/HT8 ø 22.2 ø 12.7 (205)
MMY-MAP1001HT7/HT8 ø 22.2 ø 12.7 (205)
MMY-MAP1201HT7/HT8 ø 28.6 ø 12.7 (205)
MMY-MAP0501T8 ø 15.9 ø 9.5 280
MMY-MAP0601T8 ø 19.1 ø 9.5 280
MMY-MAP0801T8 ø 22.2 ø 12.7 (205)
MMY-MAP1001T8 ø 22.2 ø 12.7 (205)
MMY-MAP1201T8 ø 28.6 ø 12.7 (205)

11 -16
11 Technical Specifications

Model : MMY-MAP0804HT8, MAP0804T8


MMY-MAP1004HT8, MAP1004T8
MMY-MAP1204HT8, MAP1204T8
Applied model A
MMY-MAP0804 type ø 22.2
MMY-MAP1004 type ø 22.2
MMY-MAP1204 type ø 28.6

11 -17
11 Technical Specifications

Model : MMY-MAP1404HT8, MAP1404T8


MMY-MAP1604HT8, MAP1604T8

11 -18
11 Technical Specifications

Combination
Outdoor unit
Model
(1) Header unit (2) Follower unit
MMY-AP1814HT8 MMY-MAP1004HT8 MMY-MAP0804HT8
MMY-AP2014HT8 MMY-MAP1004HT8 MMY-MAP1004HT8
MMY-AP2214HT8 MMY-MAP1204HT8 MMY-MAP1004HT8
MMY-AP2414HT8 MMY-MAP1204HT8 MMY-MAP1204HT8
MMY-AP1624HT8 MMY-MAP0804HT8 MMY-MAP0801HT8

Outdoor unit
Model
(1) Header unit (2) Follower unit
MMY-AP2614HT8 MMY-MAP1604HT8 MMY-MAP1004HT8
MMY-AP2814HT8 MMY-MAP1604HT8 MMY-MAP1204HT8

11 -19
11 Technical Specifications

Outdoor unit
Model
(1) Header unit (2) Follower unit
MMY-AP3014HT8 MMY-MAP1604HT8 MMY-MAP1404HT8
MMY-AP3214HT8 MMY-MAP1604HT8 MMY-MAP1604HT8

Outdoor unit
Model
(1) Header unit (2) Follower unit (3) Header unit
MMY-AP3414HT8 MMY-MAP1204HT8 MMY-MAP1204HT8 MMY-MAP1004HT8
MMY-AP3614HT8 MMY-MAP1204HT8 MMY-MAP1004HT8 MMY-MAP1204HT8
MMY-AP2424HT8 MMY-MAP0804HT8 MMY-MAP0804HT8 MMY-MAP0804HT8
MMY-AP2624HT8 MMY-MAP1004HT8 MMY-MAP0804HT8 MMY-MAP0804HT8
MMY-AP2824HT8 MMY-MAP1004HT8 MMY-MAP1004HT8 MMY-MAP0804HT8
MMY-AP3024HT8 MMY-MAP1004HT8 MMY-MAP1004HT8 MMY-MAP1004HT8

11 -20
11 Technical Specifications

Outdoor unit
Model
(1) Header unit (2) Follower unit (3) Follower unit
MMY-AP3814HT8 MMY-MAP1604HT8 MMY-MAP1204HT8 MMY-MAP1004HT8
MMY-AP4014HT8 MMY-MAP1604HT8 MMY-MAP1204HT8 MMY-MAP1204HT8

Outdoor unit
Model
(1) Header unit (2) Follower unit (3) Follower unit
MMY-AP4214HT8 MMY-MAP1604HT8 MMY-MAP1404HT8 MMY-MAP1204HT8
MMY-AP4414HT8 MMY-MAP1604HT8 MMY-MAP1604HT8 MMY-MAP1204HT8

11 -21
11 Technical Specifications

Outdoor unit
Model
(1) Header unit (2) Follower unit (3) Follower unit
MMY-AP4614HT8 MMY-MAP1604HT8 MMY-MAP1604HT8 MMY-MAP1404HT8
MMY-AP4814HT8 MMY-MAP1604HT8 MMY-MAP1604HT8 MMY-MAP1604HT8

Outdoor unit
Model
(1) Header unit (2) Follower unit (3) Follower unit (4) Header unit
MMY-AP3224HT8 MMY-MAP0804HT8 MMY-MAP0804HT8 MMY-MAP0804HT8 MMY-MAP0804HT8
MMY-AP3424HT8 MMY-MAP1004HT8 MMY-MAP0804HT8 MMY-MAP0804HT8 MMY-MAP0804HT8
MMY-AP3624HT8 MMY-MAP1004HT8 MMY-MAP1004HT8 MMY-MAP0804HT8 MMY-MAP0804HT8
MMY-AP3824HT8 MMY-MAP1004HT8 MMY-MAP1004HT8 MMY-MAP1004HT8 MMY-MAP0804HT8
MMY-AP4024HT8 MMY-MAP1004HT8 MMY-MAP1004HT8 MMY-MAP1004HT8 MMY-MAP1004HT8
MMY-AP4224HT8 MMY-MAP1204HT8 MMY-MAP1004HT8 MMY-MAP1004HT8 MMY-MAP1004HT8
MMY-AP4424HT8 MMY-MAP1204HT8 MMY-MAP1204HT8 MMY-MAP1004HT8 MMY-MAP1004HT8
MMY-AP4624HT8 MMY-MAP1204HT8 MMY-MAP1204HT8 MMY-MAP1204HT8 MMY-MAP1004HT8
MMY-AP4824HT8 MMY-MAP1204HT8 MMY-MAP1204HT8 MMY-MAP1204HT8 MMY-MAP1204HT8

11 -22
11 Technical Specifications

11-1-3. Wiring diagram


Model : MMY-MAP0501*, MAP0601* (SMMS)

11 -23
11 Technical Specifications

Model : MMY-MAP0804*, MAP1004*, MAP1204*

11 -24
11 Technical Specifications

Model : MAP1404*, MAP1604*

11 -25
Outdoor unit
power supply
3N~ 380-415V 50Hz
3N~ 380V 60Hz

Earth leakage breaker


power switch

Header
outdoor unit A
11-1-4. Connecting diagram

In using central controller,


L1 L2 L3 N Earth
Model : MMY-MAP0501*, 0601*

connect it with indoor/outdoor units


screw
after address setting of both units.

U1 U2 U3 U4 U5 U6
11 Technical Specifications

Central remote controller


(SMMS)

(Option)
L
U1/U3
Connection of shield wire closed terminal
U2/U4 (Connected to all connecting sections in each indoor unit.)
N Outdoor unit side
Indoor unit side
Earth leakage breaker

11 -26
power switch
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
Central controler power supply A A A A A A A A A A
1~ 50Hz 220~240V U1 U2 B B U1 U2 B B U1 U2 B B U1 U2 B B U1 U2 B B
1~ 60Hz 220V

L N Remote controller L N Remote controller L N Remote controller L N Remote controller L N Remote


Earth Earth Earth Earth controller
screw Earth
screw screw screw screw

Indoor nuit
Pull box Pull box Pull box Pull box
power supply
1~ 50Hz 220~240V
1~ 60Hz 220V
Earth leakage breaker
Power switch

Note)1.In using central controller,connect it with indoor/outdoor units after address setting of both units.
2.Select the power supply cabling size and fuse of outdoor/indoor units from each model's specification.
Model name Voltage frequency
Perform wiring of the power supplies in conformance with the regulation of the local electrical authorities.
MMY-MAP**01 HT8, HT8-E, T8, T8-E 3N~ 380-415V 50Hz
3.For the control wires connecting indoor units,outdoor units,and between indoor and outdoor units,
use of double-core and non-polarity shield wires. MMY-MAP**01 HT7 3N~ 380V 60Hz
4.Select the internal wiring of outdoor units and indoor units from the wiring diagrams.
11 Technical Specifications

SMMS-i Single unit


Model name
MMY-MAP0804*
MMY-MAP1004*
MMY-MAP1204*
MMY-MAP1404*
MMY-MAP1604*
3N~ 60Hz 380V

1~ 60Hz 220V

1~ 60Hz 220V

SMMS-i Combination unit


Model name
<Two connection> MMY-AP1814* MMY-AP2814*
MMY-AP2014* MMY-AP3014*
MMY-AP2214* MMY-AP3214*
MMY-AP2414* MMY-AP1624*
MMY-AP2614*
3N~60Hz 380V

1~ 60Hz 220V

1~ 60Hz 220V

11 -27
11 Technical Specifications

Model name
<Three connection> MMY-AP3414* MMY-AP4414* MMY-AP2824*
MMY-AP3614* MMY-AP4614* MMY-AP3024*
MMY-AP3814* MMY-AP4814*
MMY-AP4014* MMY-AP2424*
3N~ 60Hz 380V
MMY-AP4214* MMY-AP2624*

1~ 60Hz 220V

1~ 60Hz 220V

Model name
<Four connection> MMY-AP3224* MMY-AP4224*
MMY-AP3424* MMY-AP4424*
MMY-AP3624* MMY-AP4624*
MMY-AP3824* MMY-AP4824*
3N~ 60Hz 380V
MMY-AP4024*

1~ 60Hz 220V

1~ 60Hz 220V

11 -28
11 Technical Specifications

11-1-5. Center of gravity

(A) (B) (C)


Anchor bolt position Anchor bolt position Anchor bolt position
700 700 920
Anchor bolt position

Anchor bolt position

Anchor bolt position


755

755

755
Y

Y
X X X
Z
Z
Z

No. Model type X (mm) Y (mm) Z (mm) Mass (kg)


MMY-MAP0501 * 228
(A) 515 383 365
MMY-MAP0601 * (cooling only : 227)
MMY-MAP0804 *
242
(B) MMY-MAP1004 * 500 390 645
(cooling only : 241)
MMY-MAP1204 *
MMY-MAP1404 *
(C) 605 350 700 330
MMY-MAP1604 *

11 -29
11 Technical Specifications

11-1-6. Branch header / branch joint


• Branch header
RBM-HY1043E, HY1083E, HY2043E, HY2083E
Gas side

Insulator

Liquid side

Insulator

Model A B C øD øE n Accessory socket Q’ty


Gas side 380 90 83.6 22.2 15.9 3 6 x 4, 9 x 4, 14 x 1, 18 x 1, 70 x 1
RBM-HY1043E
Liquid side 360 60 - 15.9 9.5 3 1 x 4, 6 x 1, 9 x 1

Gas side 700 90 83.6 22.2 15.9 7 6 x 8, 9 x 8, 14 x 1, 18 x 1, 70 x 1


RBM-HY1083E
Liquid side 680 60 - 15.9 9.5 7 1 x 8, 6 x 1, 9 x 1

Gas side 385.5 95.5 89.3 31.8 15.9 3 6 x 2, 9 x 2, 27 x 1, 59 x 1


RBM-HY2043E
Liquid side 360 60 - 15.9 9.5 3 1 x2

Gas side 705.5 95.5 89.3 31.8 15.9 7 6 x 7, 9 x 7, 27 x 1, 59 x 1


RBM-HY2083E
Liquid side 680 60 - 15.9 9.5 7 1 x7

• Y-shape branch joint


RBM-BY55E, BY105E, BY205E, BY305E
Gas side Liquid side

Insulator
Insulator

RBM- A B øC øD Accessory socket Q'ty


Gas side 160 80 15.9 15.9 9 x 1, 51 x 2, 91 x 2
BY55E
Liquid side 130 70 9.5 9.5 1 x 2te

Gas side 170 80 22.2 22.2 14 x 2, 70 x 2, 91 x 1


BY105E
Liquid side 160 80 15.9 15.9 9 x 1, 91 x 1, 92 x 1

Gas side 200 80 31.8 28.6 16 x 1, 27 x 1, 43 x 2, 58 x 1, 59 x 1, 91 x 1


BY205E
Liquid side 160 80 15.9 15.9 9 x 1, 51 x 2, 92 x 1

Gas side 220 80 38.1 38.1 43 x 1, 61 x 3, 62 x 2, 71 x 2, 75 x 1, 91 x 1


BY305E
Liquid side 170 80 22.2 22.2 92 x 1, 94 x 3

11 -30
11 Technical Specifications

• Branching joint for connection of outdoor units(Set of three kinds of joint)


RBM-BT14E
Gas side

Liquid side Balance pipe

RBM-BT14E
Accessory socket Q'ty
Gas side 27 x 1, 43 x 2, 59 x 1

Liquid side 10 x 2, 13 x 1

RBM-BT24E
Gas side

Liquid side Balance pipe

RBM-BT24E
Accessory socket Q'ty
Gas side 43 x1, 61 x2, 62 x2, 71 x1, 73 x1

Liquid side 14 x2, 18 x2, 85 x1

11 -31
11 Technical Specifications

• Accessory socket
1 2 5 54 84 3 6 9 51 4 7 10 13 52 67
A øB A øB A øB
2 29 6.4 3 35 6.4 4 39 6.4
5 26 9.5 6 32 9.5 7 39 9.5
54 31 15.9 9 28 12.7 10 36 12.7
84 40 19.1 51 37.5 19.1 13 33 15.9
52 42.5 22.2
Outer dia. Outer dia. Outer dia. Outer dia.
67 49 25.4

25 27 55 59
14 18 69 70 85 86 16 20 24 43 48 49 53 58
A øB
A øB A øB
25 53 25.4
14 40 15.9 16 50 15.9
27 49 28.6
18 40 19.1 20 52 19.1
55 64 38.1
69 48 25.4 24 48 25.4
59 59 34.9
70 54 28.6 43 50 22.2
85 41 12.7 48 54 9.5
Outer dia. Outer dia. Outer dia.
86 44 9.5 49 52 12.7
53 55 31.8
58 62 34.9

28 61 62 71 72 73 74 75 76 77 91 94 95 96 97 92
A øB A øB øC øD
28 58 31.8 91 58 9.5 12.7 15.9
61 55 34.9 94 71 15.9 19.1 22.2
62 66 41.3 95 80 22.2 25.4 28.6
71 66 28.6 96 87 25.4 28.6 31.8
72 66 25.4 97 95 28.6 31.8 38.1
73 66 22.2
Outer dia. Outer dia.
74 66 19.1
75 64 15.9 Outer dia.
76 62 12.7
77 62 9.5

Closure tube

Outer dia. Outer dia.

11 -32
11 Technical Specifications

11-1-7. Part Load performance


Single unit
MMY-MAP0501HT8, MAP0501T8 (5HP, 14kW system) <SMMS>

Cooling Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 13.0 13.0 3.86 11.7 3.16 10.4 2.54 9.10 2.02
39 °C 13.2 13.2 3.81 11.9 3.11 10.6 2.51 9.24 1.99
37 °C 13.6 13.6 3.73 12.2 3.05 10.9 2.45 9.52 1.95
35 °C 14.0 14.0 3.65 12.6 2.98 11.2 2.40 9.80 1.90
33 °C 14.0 14.0 3.38 12.6 2.77 11.2 2.23 9.80 1.77
31 °C 14.0 14.0 3.14 12.6 2.57 11.2 2.08 9.80 1.66
30 °C 14.0 14.0 3.02 12.6 2.48 11.2 2.00 9.80 1.60
29 °C 14.0 14.0 2.91 12.6 2.39 11.2 1.93 9.80 1.55
27 °C 14.0 14.0 2.79 12.6 2.29 11.2 1.85 9.80 1.49
25 °C 14.0 14.0 2.71 12.6 2.22 11.2 1.80 9.80 1.45
23 °C 14.0 14.0 2.63 12.6 2.16 11.2 1.75 9.80 1.41
21 °C 14.0 14.0 2.55 12.6 2.10 11.2 1.71 9.80 1.37
20 °C 14.0 14.0 2.52 12.6 2.07 11.2 1.68 9.80 1.35
19 °C 14.0 14.0 2.48 12.6 2.04 11.2 1.66 9.80 1.33
17 °C 14.0 14.0 2.41 12.6 1.98 11.2 1.61 9.80 1.30
15 °C 14.0 14.0 2.34 12.6 1.93 11.2 1.57 9.80 1.26

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 13.0 7.80 1.59 6.50 1.24 5.20 1.03 3.90 0.88
39 °C 13.2 7.92 1.56 6.60 1.23 5.28 1.02 3.96 0.87
37 °C 13.6 8.16 1.53 6.80 1.20 5.44 0.99 4.08 0.84
35 °C 14.0 8.40 1.49 7.00 1.16 5.60 0.96 4.20 0.82
33 °C 14.0 8.40 1.40 7.00 1.10 5.60 0.91 4.20 0.78
31 °C 14.0 8.40 1.31 7.00 1.03 5.60 0.87 4.20 0.75
30 °C 14.0 8.40 1.27 7.00 1.00 5.60 0.84 4.20 0.73
29 °C 14.0 8.40 1.23 7.00 0.97 5.60 0.82 4.20 0.71
27 °C 14.0 8.40 1.18 7.00 0.94 5.60 0.80 4.20 0.69
25 °C 14.0 8.40 1.15 7.00 0.92 5.60 0.78 4.20 0.68
23 °C 14.0 8.40 1.12 7.00 0.90 5.60 0.76 4.20 0.66
21 °C 14.0 8.40 1.09 7.00 0.88 5.60 0.75 4.20 0.65
20 °C 14.0 8.40 1.08 7.00 0.87 5.60 0.74 4.20 0.65
19 °C 14.0 8.40 1.07 7.00 0.86 5.60 0.73 4.20 0.64
17 °C 14.0 8.40 1.04 7.00 0.84 5.60 0.71 4.20 0.63
15 °C 14.0 8.40 1.01 7.00 0.82 5.60 0.70 4.20 0.61
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 16.0 16.0 3.35 14.4 2.80 12.8 2.32 11.2 1.90
13.0 11.8 16.0 16.0 3.45 14.4 2.89 12.8 2.38 11.2 1.94
11.0 9.8 16.0 16.0 3.61 14.4 3.01 12.8 2.48 11.2 2.01
9.0 7.9 16.0 16.0 3.72 14.4 3.10 12.8 2.55 11.2 2.06
7.0 6.0 16.0 16.0 3.84 14.4 3.19 12.8 2.62 11.2 2.12
5.0 4.1 15.7 15.7 3.90 14.1 3.24 12.5 2.66 11.0 2.15
3.0 2.2 15.2 15.2 3.91 13.7 3.25 12.2 2.66 10.6 2.14
0.0 -0.7 14.1 14.1 3.74 12.7 3.11 11.3 2.55 9.86 2.06
-3.0 -3.7 13.1 13.1 3.64 11.8 3.03 10.5 2.48 9.18 2.00
-5.0 -5.6 12.8 12.8 3.63 11.5 3.02 10.2 2.47 8.96 1.99
-7.0 -7.6 11.8 11.8 3.37 10.7 2.80 9.47 2.30 8.29 1.86
-10 -10.5 10.9 10.9 3.26 9.79 2.72 8.70 2.23 7.62 1.81
-14.5 -15.0 8.0 8.00 2.56 7.20 2.15 6.40 1.78 5.60 1.46

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 16.0 9.60 1.53 8.00 1.23 6.40 0.99 4.80 0.80
13.0 11.8 16.0 9.60 1.57 8.00 1.25 6.40 1.00 4.80 0.81
11.0 9.8 16.0 9.60 1.61 8.00 1.28 6.40 1.01 4.80 0.81
9.0 7.9 16.0 9.60 1.65 8.00 1.30 6.40 1.02 4.80 0.81
7.0 6.0 16.0 9.60 1.69 8.00 1.32 6.40 1.03 4.80 0.81
5.0 4.1 15.7 9.41 1.70 7.84 1.33 6.27 1.04 4.70 0.81
3.0 2.2 15.2 9.12 1.70 7.60 1.33 6.08 1.03 4.56 0.81
0.0 -0.7 14.1 8.45 1.64 7.04 1.28 5.63 1.00 4.22 0.78
-3.0 -3.7 13.1 7.87 1.59 6.56 1.25 5.25 0.97 3.94 0.76
-5.0 -5.6 12.8 7.68 1.58 6.40 1.24 5.12 0.96 3.84 0.75
-7.0 -7.6 11.8 7.10 1.49 5.92 1.17 4.74 0.92 3.55 0.73
-10 -10.5 10.9 6.53 1.44 5.44 1.14 4.35 0.89 3.26 0.71
-14.5 -15.0 8.0 4.80 1.18 4.00 0.95 3.20 0.77 2.40 0.63
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -33
11 Technical Specifications

MMY-MAP0601HT8, MAP0601T8 (6HP, 16kW system) <SMMS>


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 14.9 14.9 4.91 13.4 4.01 11.9 3.23 10.43 2.57
39 °C 15.1 15.1 4.86 13.6 3.98 12.1 3.20 10.58 2.54
37 °C 15.6 15.6 4.75 14.0 3.88 12.4 3.13 10.89 2.48
35 °C 16.0 16.0 4.64 14.4 3.79 12.8 3.05 11.20 2.42
33 °C 16.0 16.0 4.30 14.4 3.52 12.8 2.84 11.20 2.26
31 °C 16.0 16.0 3.99 14.4 3.27 12.8 2.64 11.20 2.11
30 °C 16.0 16.0 3.84 14.4 3.15 12.8 2.55 11.20 2.03
29 °C 16.0 16.0 3.70 14.4 3.04 12.8 2.46 11.20 1.97
27 °C 16.0 16.0 3.49 14.4 2.87 12.8 2.33 11.20 1.87
25 °C 16.0 16.0 3.44 14.4 2.83 12.8 2.29 11.20 1.84
23 °C 16.0 16.0 3.34 14.4 2.75 12.8 2.23 11.20 1.79
21 °C 16.0 16.0 3.24 14.4 2.67 12.8 2.17 11.20 1.74
20 °C 16.0 16.0 3.20 14.4 2.63 12.8 2.14 11.20 1.72
19 °C 16.0 16.0 3.15 14.4 2.59 12.8 2.11 11.20 1.70
17 °C 16.0 16.0 3.06 14.4 2.52 12.8 2.05 11.20 1.65
15 °C 16.0 16.0 2.97 14.4 2.45 12.8 1.99 11.20 1.61

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 14.9 8.94 2.02 7.45 1.58 5.96 1.26 4.47 1.05
39 °C 15.1 9.07 2.00 7.56 1.56 6.05 1.24 4.54 1.03
37 °C 15.6 9.34 1.95 7.78 1.52 6.22 1.21 4.67 1.00
35 °C 16.0 9.60 1.90 8.00 1.48 6.40 1.17 4.80 0.97
33 °C 16.0 9.60 1.77 8.00 1.39 6.40 1.11 4.80 0.93
31 °C 16.0 9.60 1.66 8.00 1.31 6.40 1.06 4.80 0.89
30 °C 16.0 9.60 1.61 8.00 1.28 6.40 1.03 4.80 0.87
29 °C 16.0 9.60 1.56 8.00 1.24 6.40 1.00 4.80 0.85
27 °C 16.0 9.60 1.49 8.00 1.19 6.40 0.97 4.80 0.83
25 °C 16.0 9.60 1.46 8.00 1.17 6.40 0.95 4.80 0.82
23 °C 16.0 9.60 1.43 8.00 1.14 6.40 0.93 4.80 0.80
21 °C 16.0 9.60 1.39 8.00 1.11 6.40 0.91 4.80 0.79
20 °C 16.0 9.60 1.37 8.00 1.10 6.40 0.90 4.80 0.78
19 °C 16.0 9.60 1.36 8.00 1.09 6.40 0.89 4.80 0.77
17 °C 16.0 9.60 1.32 8.00 1.06 6.40 0.87 4.80 0.76
15 °C 16.0 9.60 1.29 8.00 1.04 6.40 0.86 4.80 0.74
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 18.0 18.0 3.97 16.2 3.33 14.4 2.76 12.6 2.25
13.0 11.8 18.0 18.0 4.10 16.2 3.43 14.4 2.83 12.6 2.31
11.0 9.8 18.0 18.0 4.28 16.2 3.57 14.4 2.94 12.6 2.39
9.0 7.9 18.0 18.0 4.41 16.2 3.68 14.4 3.02 12.6 2.45
7.0 6.0 18.0 18.0 4.56 16.2 3.79 14.4 3.11 12.6 2.52
5.0 4.1 17.6 17.6 4.63 15.9 3.85 14.1 3.16 12.3 2.55
3.0 2.2 17.1 17.1 4.64 15.4 3.85 13.7 3.16 12.0 2.55
0.0 -0.7 15.8 15.8 4.44 14.3 3.70 12.7 3.03 11.09 2.44
-3.0 -3.7 14.8 14.8 4.33 13.3 3.60 11.8 2.95 10.33 2.38
-5.0 -5.6 14.4 14.4 4.31 13.0 3.58 11.5 2.93 10.08 2.37
-7.0 -7.6 13.3 13.3 4.00 12.0 3.33 10.66 2.73 9.32 2.21
-10 -10.5 12.2 12.2 3.87 11.02 3.23 9.79 2.65 8.57 2.15
-14.5 -15.0 9.0 9.00 3.04 8.10 2.55 7.20 2.11 6.30 1.73

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 18.0 10.80 1.82 9.00 1.46 7.20 1.17 5.40 0.96
13.0 11.8 18.0 10.80 1.86 9.00 1.48 7.20 1.18 5.40 0.96
11.0 9.8 18.0 10.80 1.92 9.00 1.52 7.20 1.20 5.40 0.96
9.0 7.9 18.0 10.80 1.96 9.00 1.54 7.20 1.21 5.40 0.96
7.0 6.0 18.0 10.80 2.00 9.00 1.57 7.20 1.23 5.40 0.97
5.0 4.1 17.6 10.58 2.02 8.82 1.59 7.06 1.23 5.29 0.97
3.0 2.2 17.1 10.26 2.02 8.55 1.58 6.84 1.23 5.13 0.96
0.0 -0.7 15.8 9.50 1.94 7.92 1.52 6.34 1.18 4.75 0.93
-3.0 -3.7 14.8 8.86 1.89 7.38 1.48 5.90 1.15 4.43 0.90
-5.0 -5.6 14.4 8.64 1.88 7.20 1.47 5.76 1.14 4.32 0.89
-7.0 -7.6 13.3 7.99 1.76 6.66 1.39 5.33 1.09 4.00 0.86
-10 -10.5 12.2 7.34 1.71 6.12 1.35 4.90 1.06 3.67 0.84
-14.5 -15.0 9.0 5.40 1.41 4.50 1.13 3.60 0.91 2.70 0.75
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -34
11 Technical Specifications

MMY-MAP0804HT8, MAP0804T8 (8HP, 22.4kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 20.8 20.8 5.83 18.8 4.79 16.7 3.89 14.6 3.11
39 °C 21.2 21.2 5.75 19.1 4.72 17.0 3.83 14.8 3.06
37 °C 21.8 21.8 5.57 19.6 4.58 17.4 3.71 15.3 2.97
35 °C 22.4 22.4 5.40 20.2 4.44 17.9 3.60 15.7 2.87
33 °C 22.4 22.4 4.99 20.2 4.11 17.9 3.34 15.7 2.68
31 °C 22.4 22.4 4.63 20.2 3.82 17.9 3.11 15.7 2.50
30 °C 22.4 22.4 4.46 20.2 3.68 17.9 3.00 15.7 2.42
29 °C 22.4 22.4 4.31 20.2 3.56 17.9 2.90 15.7 2.34
27 °C 22.4 22.4 4.02 20.2 3.32 17.9 2.71 15.7 2.19
25 °C 22.4 22.4 3.75 20.2 3.10 17.9 2.54 15.7 2.06
23 °C 22.4 22.4 3.50 20.2 2.90 17.9 2.38 15.7 1.93
21 °C 22.4 22.4 3.43 20.2 2.84 17.9 2.33 15.7 1.90
20 °C 22.4 22.4 3.40 20.2 2.82 17.9 2.31 15.7 1.88
19 °C 22.4 22.4 3.36 20.2 2.79 17.9 2.29 15.7 1.87
17 °C 22.4 22.4 3.31 20.2 2.75 17.9 2.26 15.7 1.84
15 °C 22.4 22.4 3.26 20.2 2.71 17.9 2.23 15.7 1.82

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 20.8 12.5 2.46 10.4 1.94 8.34 1.55 6.25 1.29
39 °C 21.2 12.7 2.42 10.6 1.91 8.48 1.52 6.36 1.27
37 °C 21.8 13.1 2.35 10.9 1.85 8.72 1.48 6.54 1.23
35 °C 22.4 13.4 2.27 11.2 1.79 8.96 1.43 6.72 1.19
33 °C 22.4 13.4 2.13 11.2 1.69 8.96 1.36 6.72 1.14
31 °C 22.4 13.4 1.99 11.2 1.59 8.96 1.29 6.72 1.09
30 °C 22.4 13.4 1.93 11.2 1.54 8.96 1.26 6.72 1.07
29 °C 22.4 13.4 1.87 11.2 1.50 8.96 1.22 6.72 1.04
27 °C 22.4 13.4 1.76 11.2 1.42 8.96 1.16 6.72 1.00
25 °C 22.4 13.4 1.66 11.2 1.34 8.96 1.10 6.72 0.95
23 °C 22.4 13.4 1.56 11.2 1.27 8.96 1.05 6.72 0.91
21 °C 22.4 13.4 1.54 11.2 1.25 8.96 1.04 6.72 0.90
20 °C 22.4 13.4 1.53 11.2 1.24 8.96 1.04 6.72 0.90
19 °C 22.4 13.4 1.52 11.2 1.24 8.96 1.03 6.72 0.90
17 °C 22.4 13.4 1.50 11.2 1.23 8.96 1.03 6.72 0.90
15 °C 22.4 13.4 1.48 11.2 1.22 8.96 1.02 6.72 0.89
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 25.0 25.0 4.60 22.5 3.82 20.0 3.18 17.5 2.65
13.0 11.8 25.0 25.0 4.78 22.5 3.95 20.0 3.26 17.5 2.70
11.0 9.8 25.0 25.0 5.00 22.5 4.11 20.0 3.37 17.5 2.78
9.0 7.9 25.0 25.0 5.25 22.5 4.28 20.0 3.49 17.5 2.85
7.0 6.0 25.0 25.0 5.53 22.5 4.48 20.0 3.63 17.5 2.95
5.0 4.1 24.2 24.2 5.44 21.7 4.41 19.3 3.57 16.9 2.90
3.0 2.2 23.3 23.3 5.36 21.0 4.34 18.6 3.52 16.3 2.86
0.0 -0.7 21.9 21.9 5.23 19.7 4.24 17.5 3.43 15.4 2.79
-3.0 -3.7 20.5 20.5 5.10 18.4 4.13 16.4 3.35 14.3 2.72
-5.0 -5.6 19.6 19.6 5.02 17.6 4.06 15.6 3.29 13.7 2.67
-7.0 -7.6 18.6 18.6 4.93 16.7 3.99 14.8 3.23 13.0 2.63
-10 -10.5 17.1 17.1 4.80 15.4 3.89 13.7 3.15 12.0 2.56
-14.5 -15.0 14.7 14.7 4.60 13.2 3.73 11.8 3.02 10.3 2.45

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 25.0 15.0 2.21 12.5 1.83 10.0 1.51 7.50 1.20
13.0 11.8 25.0 15.0 2.24 12.5 1.86 10.0 1.52 7.50 1.21
11.0 9.8 25.0 15.0 2.29 12.5 1.88 10.0 1.54 7.50 1.22
9.0 7.9 25.0 15.0 2.34 12.5 1.92 10.0 1.55 7.50 1.23
7.0 6.0 25.0 15.0 2.40 12.5 1.95 10.0 1.58 7.50 1.24
5.0 4.1 24.2 14.5 2.36 12.1 1.92 9.66 1.55 7.25 1.22
3.0 2.2 23.3 14.0 2.32 11.6 1.89 9.31 1.53 6.99 1.20
0.0 -0.7 21.9 13.2 2.27 11.0 1.85 8.77 1.49 6.58 1.17
-3.0 -3.7 20.5 12.3 2.21 10.2 1.80 8.20 1.45 6.15 1.14
-5.0 -5.6 19.6 11.7 2.17 9.78 1.77 7.82 1.43 5.87 1.13
-7.0 -7.6 18.6 11.1 2.14 9.28 1.74 7.42 1.40 5.57 1.11
-10 -10.5 17.1 10.2 2.08 8.54 1.69 6.83 1.37 5.12 1.08
-14.5 -15.0 14.7 8.82 1.99 7.35 1.62 5.88 1.31 4.41 1.03
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -35
11 Technical Specifications

MMY-MAP1004HT8, MAP1004T8 (10HP, 28kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 26.1 26.1 8.00 23.5 6.58 20.8 5.33 18.2 4.26
39 °C 26.5 26.5 7.88 23.8 6.48 21.2 5.25 18.5 4.20
37 °C 27.3 27.3 7.65 24.5 6.28 21.8 5.09 19.1 4.07
35 °C 28.0 28.0 7.41 25.2 6.09 22.4 4.93 19.6 3.95
33 °C 28.0 28.0 6.85 25.2 5.64 22.4 4.58 19.6 3.67
31 °C 28.0 28.0 6.35 25.2 5.24 22.4 4.26 19.6 3.43
30 °C 28.0 28.0 6.13 25.2 5.06 22.4 4.12 19.6 3.32
29 °C 28.0 28.0 5.91 25.2 4.88 22.4 3.98 19.6 3.21
27 °C 28.0 28.0 5.51 25.2 4.56 22.4 3.72 19.6 3.01
25 °C 28.0 28.0 5.14 25.2 4.26 22.4 3.48 19.6 2.82
23 °C 28.0 28.0 4.81 25.2 3.98 22.4 3.26 19.6 2.65
21 °C 28.0 28.0 4.71 25.2 3.90 22.4 3.20 19.6 2.60
20 °C 28.0 28.0 4.66 25.2 3.87 22.4 3.17 19.6 2.58
19 °C 28.0 28.0 4.62 25.2 3.83 22.4 3.15 19.6 2.56
17 °C 28.0 28.0 4.54 25.2 3.77 22.4 3.10 19.6 2.53
15 °C 28.0 28.0 4.48 25.2 3.72 22.4 3.06 19.6 2.50

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 26.1 15.6 3.37 13.0 2.66 10.42 2.12 7.82 1.76
39 °C 26.5 15.9 3.32 13.2 2.62 10.59 2.09 7.94 1.74
37 °C 27.3 16.4 3.22 13.6 2.54 10.91 2.03 8.18 1.69
35 °C 28.0 16.8 3.12 14.0 2.46 11.20 1.96 8.40 1.63
33 °C 28.0 16.8 2.92 14.0 2.31 11.20 1.86 8.40 1.56
31 °C 28.0 16.8 2.74 14.0 2.18 11.20 1.77 8.40 1.49
30 °C 28.0 16.8 2.65 14.0 2.12 11.20 1.72 8.40 1.46
29 °C 28.0 16.8 2.57 14.0 2.06 11.20 1.68 8.40 1.43
27 °C 28.0 16.8 2.42 14.0 1.95 11.20 1.60 8.40 1.37
25 °C 28.0 16.8 2.27 14.0 1.84 11.20 1.51 8.40 1.30
23 °C 28.0 16.8 2.14 14.0 1.74 11.20 1.44 8.40 1.24
21 °C 28.0 16.8 2.11 14.0 1.72 11.20 1.43 8.40 1.24
20 °C 28.0 16.8 2.09 14.0 1.71 11.20 1.42 8.40 1.24
19 °C 28.0 16.8 2.08 14.0 1.70 11.20 1.42 8.40 1.23
17 °C 28.0 16.8 2.06 14.0 1.68 11.20 1.41 8.40 1.23
15 °C 28.0 16.8 2.04 14.0 1.67 11.20 1.40 8.40 1.23
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 31.5 31.5 6.24 28.4 5.18 25.2 4.31 22.1 3.59
13.0 11.8 31.5 31.5 6.49 28.4 5.36 25.2 4.43 22.1 3.67
11.0 9.8 31.5 31.5 6.79 28.4 5.57 25.2 4.57 22.1 3.76
9.0 7.9 31.5 31.5 7.12 28.4 5.80 25.2 4.73 22.1 3.87
7.0 6.0 31.5 31.5 7.50 28.4 6.08 25.2 4.92 22.1 4.00
5.0 4.1 30.4 30.4 7.38 27.4 5.98 24.3 4.85 21.3 3.93
3.0 2.2 29.3 29.3 7.27 26.4 5.89 23.5 4.77 20.5 3.87
0.0 -0.7 27.6 27.6 7.10 24.9 5.75 22.1 4.66 19.3 3.78
-3.0 -3.7 25.8 25.8 6.92 23.2 5.60 20.7 4.54 18.1 3.68
-5.0 -5.6 24.6 24.6 6.80 22.2 5.51 19.7 4.47 17.3 3.62
-7.0 -7.6 23.4 23.4 6.68 21.0 5.41 18.7 4.39 16.4 3.56
-10 -10.5 21.5 21.5 6.51 19.4 5.27 17.2 4.27 15.1 3.47
-14.5 -15.0 18.5 18.5 6.24 16.7 5.05 14.8 4.10 13.0 3.32

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 31.5 18.9 2.99 15.8 2.49 12.6 2.04 9.45 1.62
13.0 11.8 31.5 18.9 3.04 15.8 2.52 12.6 2.06 9.45 1.63
11.0 9.8 31.5 18.9 3.10 15.8 2.56 12.6 2.08 9.45 1.65
9.0 7.9 31.5 18.9 3.17 15.8 2.60 12.6 2.11 9.45 1.66
7.0 6.0 31.5 18.9 3.25 15.8 2.65 12.6 2.14 9.45 1.68
5.0 4.1 30.4 18.3 3.20 15.2 2.61 12.2 2.10 9.13 1.66
3.0 2.2 29.3 17.6 3.15 14.7 2.57 11.7 2.07 8.80 1.63
0.0 -0.7 27.6 16.6 3.08 13.8 2.50 11.1 2.02 8.29 1.59
-3.0 -3.7 25.8 15.5 3.00 12.9 2.44 10.3 1.97 7.75 1.55
-5.0 -5.6 24.6 14.8 2.95 12.3 2.40 9.86 1.94 7.39 1.53
-7.0 -7.6 23.4 14.0 2.90 11.7 2.36 9.35 1.90 7.01 1.50
-10 -10.5 21.5 12.9 2.82 10.8 2.30 8.61 1.86 6.45 1.46
-14.5 -15.0 18.5 11.1 2.70 9.26 2.20 7.41 1.78 5.55 1.40
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -36
11 Technical Specifications

MMY-MAP1204HT8, MAP1204T8 (12HP, 33.5kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 31.2 31.2 10.3 28.1 8.41 24.9 6.76 21.8 5.36
39 °C 31.7 31.7 10.2 28.5 8.28 25.3 6.66 22.2 5.28
37 °C 32.6 32.6 9.85 29.4 8.03 26.1 6.45 22.8 5.12
35 °C 33.5 33.5 9.55 30.2 7.78 26.8 6.25 23.5 4.96
33 °C 33.5 33.5 8.81 30.2 7.19 26.8 5.79 23.5 4.61
31 °C 33.5 33.5 8.16 30.2 6.67 26.8 5.39 23.5 4.30
30 °C 33.5 33.5 7.86 30.2 6.43 26.8 5.20 23.5 4.16
29 °C 33.5 33.5 7.58 30.2 6.21 26.8 5.02 23.5 4.02
27 °C 33.5 33.5 7.05 30.2 5.79 26.8 4.69 23.5 3.77
25 °C 33.5 33.5 6.58 30.2 5.40 26.8 4.39 23.5 3.53
23 °C 33.5 33.5 6.14 30.2 5.05 26.8 4.11 23.5 3.31
21 °C 33.5 33.5 6.01 30.2 4.94 26.8 4.03 23.5 3.25
20 °C 33.5 33.5 5.94 30.2 4.90 26.8 3.99 23.5 3.23
19 °C 33.5 33.5 5.89 30.2 4.85 26.8 3.96 23.5 3.20
17 °C 33.5 33.5 5.79 30.2 4.77 26.8 3.90 23.5 3.16
15 °C 33.5 33.5 5.70 30.2 4.71 26.8 3.85 23.5 3.12

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 31.2 18.7 4.21 15.6 3.30 12.5 2.63 9.35 2.20
39 °C 31.7 19.0 4.15 15.8 3.25 12.67 2.59 9.50 2.16
37 °C 32.6 19.6 4.02 16.3 3.15 13.05 2.51 9.79 2.10
35 °C 33.5 20.1 3.89 16.8 3.05 13.40 2.44 10.05 2.03
33 °C 33.5 20.1 3.64 16.8 2.87 13.40 2.31 10.05 1.94
31 °C 33.5 20.1 3.41 16.8 2.71 13.40 2.19 10.05 1.86
30 °C 33.5 20.1 3.30 16.8 2.63 13.40 2.14 10.05 1.82
29 °C 33.5 20.1 3.20 16.8 2.55 13.40 2.08 10.05 1.78
27 °C 33.5 20.1 3.01 16.8 2.41 13.40 1.98 10.05 1.70
25 °C 33.5 20.1 2.83 16.8 2.28 13.40 1.88 10.05 1.63
23 °C 33.5 20.1 2.66 16.8 2.15 13.40 1.78 10.05 1.55
21 °C 33.5 20.1 2.62 16.8 2.13 13.40 1.77 10.05 1.55
20 °C 33.5 20.1 2.60 16.8 2.12 13.40 1.76 10.05 1.54
19 °C 33.5 20.1 2.59 16.8 2.11 13.40 1.76 10.05 1.54
17 °C 33.5 20.1 2.56 16.8 2.09 13.40 1.75 10.05 1.54
15 °C 33.5 20.1 2.53 16.8 2.07 13.40 1.74 10.05 1.53
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 37.5 37.5 8.51 33.8 7.04 30.0 5.80 26.3 4.78
13.0 11.8 37.5 37.5 8.85 33.8 7.29 30.0 5.98 26.3 4.90
11.0 9.8 37.5 37.5 9.25 33.8 7.59 30.0 6.19 26.3 5.04
9.0 7.9 37.5 37.5 9.69 33.8 7.91 30.0 6.42 26.3 5.20
7.0 6.0 37.5 37.5 10.2 33.8 8.29 30.0 6.69 26.3 5.38
5.0 4.1 36.2 36.2 10.0 32.6 8.16 29.0 6.59 25.4 5.30
3.0 2.2 34.9 34.9 9.89 31.4 8.03 27.9 6.49 24.4 5.21
0.0 -0.7 32.9 32.9 9.65 29.6 7.84 26.3 6.33 23.0 5.09
-3.0 -3.7 30.7 30.7 9.41 27.7 7.64 24.6 6.17 21.5 4.96
-5.0 -5.6 29.3 29.3 9.25 26.4 7.52 23.5 6.07 20.5 4.88
-7.0 -7.6 27.8 27.8 9.09 25.1 7.38 22.3 5.96 19.5 4.79
-10 -10.5 25.6 25.6 8.85 23.0 7.19 20.5 5.81 17.9 4.67
-14.5 -15.0 22.0 22.0 8.49 19.8 6.89 17.6 5.57 15.4 4.47

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 37.5 22.5 3.93 18.8 3.25 15.0 2.70 11.3 2.27
13.0 11.8 37.5 22.5 4.01 18.8 3.29 15.0 2.72 11.3 2.27
11.0 9.8 37.5 22.5 4.10 18.8 3.34 15.0 2.74 11.3 2.27
9.0 7.9 37.5 22.5 4.20 18.8 3.40 15.0 2.77 11.3 2.28
7.0 6.0 37.5 22.5 4.32 18.8 3.47 15.0 2.80 11.3 2.28
5.0 4.1 36.2 21.7 4.25 18.1 3.42 14.5 2.76 10.9 2.25
3.0 2.2 34.9 21.0 4.18 17.5 3.36 14.0 2.72 10.5 2.22
0.0 -0.7 32.9 19.7 4.08 16.4 3.28 13.2 2.65 9.87 2.16
-3.0 -3.7 30.7 18.4 3.98 15.4 3.20 12.3 2.58 9.22 2.11
-5.0 -5.6 29.3 17.6 3.91 14.67 3.15 11.7 2.54 8.80 2.07
-7.0 -7.6 27.8 16.7 3.85 13.92 3.09 11.1 2.50 8.35 2.04
-10 -10.5 25.6 15.4 3.75 12.81 3.01 10.2 2.43 7.68 1.98
-14.5 -15.0 22.0 13.2 3.59 11.02 2.89 8.82 2.33 6.61 1.90
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -37
11 Technical Specifications

MMY-MAP1404HT8, MAP1404T8 (14HP, 40kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 37.2 37.2 12.4 33.5 10.1 29.8 8.14 26.1 6.40
39 °C 37.8 37.8 12.2 34.0 10.00 30.3 8.01 26.5 6.30
37 °C 39.0 39.0 11.9 35.1 9.70 31.2 7.77 27.3 6.11
35 °C 40.0 40.0 11.5 36.0 9.39 32.0 7.53 28.0 5.92
33 °C 40.0 40.0 10.6 36.0 8.68 32.0 6.97 28.0 5.49
31 °C 40.0 40.0 9.84 36.0 8.05 32.0 6.47 28.0 5.12
30 °C 40.0 40.0 9.48 36.0 7.76 32.0 6.24 28.0 4.94
29 °C 40.0 40.0 9.15 36.0 7.49 32.0 6.03 28.0 4.77
27 °C 40.0 40.0 8.52 36.0 6.98 32.0 5.62 28.0 4.46
25 °C 40.0 40.0 7.94 36.0 6.51 32.0 5.25 28.0 4.18
23 °C 40.0 40.0 7.42 36.0 6.08 32.0 4.91 28.0 3.92
21 °C 40.0 40.0 7.25 36.0 5.95 32.0 4.81 28.0 3.84
20 °C 40.0 40.0 7.18 36.0 5.89 32.0 4.77 28.0 3.81
19 °C 40.0 40.0 7.11 36.0 5.84 32.0 4.73 28.0 3.78
17 °C 40.0 40.0 6.99 36.0 5.74 32.0 4.65 28.0 3.72
15 °C 40.0 40.0 6.88 36.0 5.66 32.0 4.59 28.0 3.68

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 37.2 22.3 4.95 18.6 3.82 14.9 3.02 11.2 2.57
39 °C 37.8 22.7 4.88 18.9 3.77 15.1 2.98 11.3 2.54
37 °C 39.0 23.4 4.73 19.5 3.65 15.6 2.89 11.7 2.46
35 °C 40.0 24.0 4.58 20.0 3.54 16.0 2.80 12.0 2.38
33 °C 40.0 24.0 4.27 20.0 3.32 16.0 2.65 12.0 2.29
31 °C 40.0 24.0 4.00 20.0 3.13 16.0 2.52 12.0 2.19
30 °C 40.0 24.0 3.87 20.0 3.03 16.0 2.46 12.0 2.15
29 °C 40.0 24.0 3.74 20.0 2.95 16.0 2.40 12.0 2.11
27 °C 40.0 24.0 3.51 20.0 2.78 16.0 2.28 12.0 2.02
25 °C 40.0 24.0 3.30 20.0 2.63 16.0 2.17 12.0 1.93
23 °C 40.0 24.0 3.10 20.0 2.48 16.0 2.06 12.0 1.85
21 °C 40.0 24.0 3.05 20.0 2.45 16.0 2.04 12.0 1.84
20 °C 40.0 24.0 3.03 20.0 2.43 16.0 2.04 12.0 1.84
19 °C 40.0 24.0 3.01 20.0 2.42 16.0 2.03 12.0 1.84
17 °C 40.0 24.0 2.97 20.0 2.40 16.0 2.02 12.0 1.84
15 °C 40.0 24.0 2.94 20.0 2.38 16.0 2.01 12.0 1.84
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 45.0 45.0 9.32 40.5 7.74 36.0 6.43 31.5 5.36
13.0 11.8 45.0 45.0 9.69 40.5 8.00 36.0 6.61 31.5 5.48
11.0 9.8 45.0 45.0 10.1 40.5 8.31 36.0 6.83 31.5 5.62
9.0 7.9 45.0 45.0 10.6 40.5 8.67 36.0 7.07 31.5 5.78
7.0 6.0 45.0 45.0 11.2 40.5 9.07 36.0 7.35 31.5 5.97
5.0 4.1 43.5 43.5 11.0 39.1 8.93 34.8 7.24 30.4 5.87
3.0 2.2 41.9 41.9 10.9 37.7 8.80 33.5 7.13 29.3 5.78
0.0 -0.7 39.5 39.5 10.6 35.5 8.59 31.6 6.96 27.6 5.65
-3.0 -3.7 36.9 36.9 10.3 33.2 8.37 29.5 6.78 25.8 5.50
-5.0 -5.6 35.2 35.2 10.2 31.7 8.23 28.2 6.67 24.6 5.41
-7.0 -7.6 33.4 33.4 9.98 30.1 8.09 26.7 6.55 23.4 5.32
-10 -10.5 30.7 30.7 9.72 27.7 7.88 24.6 6.38 21.5 5.18
-14.5 -15.0 26.4 26.4 9.32 23.8 7.55 21.2 6.12 18.5 4.96

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 45.0 27.0 4.47 22.5 3.71 18.0 3.05 13.5 2.42
13.0 11.8 45.0 27.0 4.54 22.5 3.76 18.0 3.08 13.5 2.44
11.0 9.8 45.0 27.0 4.64 22.5 3.82 18.0 3.11 13.5 2.46
9.0 7.9 45.0 27.0 4.74 22.5 3.88 18.0 3.15 13.5 2.49
7.0 6.0 45.0 27.0 4.85 22.5 3.95 18.0 3.19 13.5 2.51
5.0 4.1 43.5 26.1 4.78 21.7 3.89 17.4 3.14 13.0 2.47
3.0 2.2 41.9 25.1 4.71 21.0 3.83 16.8 3.09 12.6 2.44
0.0 -0.7 39.5 23.7 4.59 19.7 3.74 15.8 3.02 11.8 2.38
-3.0 -3.7 36.9 22.1 4.48 18.4 3.64 14.8 2.94 11.1 2.32
-5.0 -5.6 35.2 21.1 4.40 17.6 3.58 14.1 2.90 10.6 2.28
-7.0 -7.6 33.4 20.0 4.33 16.7 3.52 13.4 2.84 10.0 2.24
-10 -10.5 30.7 18.4 4.21 15.4 3.43 12.3 2.77 9.22 2.18
-14.5 -15.0 26.4 15.9 4.04 13.2 3.29 10.6 2.66 7.93 2.09
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -38
11 Technical Specifications

MMY-MAP1604HT8, MAP1604T8 (16HP, 45kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 41.9 41.9 14.8 37.7 12.1 33.5 9.69 29.3 7.54
39 °C 42.5 42.5 14.6 38.3 11.9 34.0 9.55 29.8 7.43
37 °C 43.8 43.8 14.1 39.4 11.6 35.1 9.26 30.7 7.21
35 °C 45.0 45.0 13.7 40.5 11.2 36.0 8.97 31.5 6.98
33 °C 45.0 45.0 12.7 40.5 10.4 36.0 8.29 31.5 6.46
31 °C 45.0 45.0 11.7 40.5 9.62 36.0 7.69 31.5 6.00
30 °C 45.0 45.0 11.3 40.5 9.27 36.0 7.41 31.5 5.79
29 °C 45.0 45.0 10.9 40.5 8.94 36.0 7.15 31.5 5.59
27 °C 45.0 45.0 10.2 40.5 8.33 36.0 6.66 31.5 5.22
25 °C 45.0 45.0 9.49 40.5 7.77 36.0 6.22 31.5 4.88
23 °C 45.0 45.0 8.86 40.5 7.25 36.0 5.81 31.5 4.56
21 °C 45.0 45.0 8.66 40.5 7.09 36.0 5.68 31.5 4.47
20 °C 45.0 45.0 8.58 40.5 7.02 36.0 5.63 31.5 4.43
19 °C 45.0 45.0 8.49 40.5 6.95 36.0 5.57 31.5 4.39
17 °C 45.0 45.0 8.35 40.5 6.83 36.0 5.48 31.5 4.32
15 °C 45.0 45.0 8.22 40.5 6.73 36.0 5.40 31.5 4.27

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 41.9 25.1 5.74 20.9 4.34 16.8 3.40 12.6 2.97
39 °C 42.5 25.5 5.66 21.3 4.28 17.0 3.35 12.8 2.92
37 °C 43.8 26.3 5.48 21.9 4.15 17.5 3.24 13.1 2.83
35 °C 45.0 27.0 5.31 22.5 4.02 18.0 3.14 13.5 2.74
33 °C 45.0 27.0 4.94 22.5 3.76 18.0 2.98 13.5 2.64
31 °C 45.0 27.0 4.60 22.5 3.53 18.0 2.83 13.5 2.55
30 °C 45.0 27.0 4.45 22.5 3.43 18.0 2.76 13.5 2.50
29 °C 45.0 27.0 4.30 22.5 3.33 18.0 2.70 13.5 2.45
27 °C 45.0 27.0 4.03 22.5 3.14 18.0 2.57 13.5 2.36
25 °C 45.0 27.0 3.78 22.5 2.96 18.0 2.44 13.5 2.26
23 °C 45.0 27.0 3.55 22.5 2.79 18.0 2.32 13.5 2.17
21 °C 45.0 27.0 3.49 22.5 2.75 18.0 2.31 13.5 2.17
20 °C 45.0 27.0 3.46 22.5 2.74 18.0 2.30 13.5 2.17
19 °C 45.0 27.0 3.43 22.5 2.72 18.0 2.29 13.5 2.17
17 °C 45.0 27.0 3.39 22.5 2.70 18.0 2.28 13.5 2.17
15 °C 45.0 27.0 3.35 22.5 2.68 18.0 2.28 13.5 2.17
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 50.0 50.0 11.9 45.0 9.74 40.0 7.92 35.0 6.40
13.0 11.8 50.0 50.0 12.3 45.0 10.1 40.0 8.19 35.0 6.58
11.0 9.8 50.0 50.0 12.9 45.0 10.5 40.0 8.51 35.0 6.81
9.0 7.9 50.0 50.0 13.5 45.0 11.0 40.0 8.86 35.0 7.05
7.0 6.0 50.0 50.0 14.2 45.0 11.5 40.0 9.26 35.0 7.33
5.0 4.1 48.3 48.3 14.0 43.5 11.4 38.6 9.12 33.8 7.22
3.0 2.2 46.6 46.6 13.8 41.9 11.2 37.3 8.98 32.6 7.11
0.0 -0.7 43.9 43.9 13.4 39.5 10.9 35.1 8.76 30.7 6.94
-3.0 -3.7 41.0 41.0 13.1 36.9 10.7 32.8 8.54 28.7 6.76
-5.0 -5.6 39.1 39.1 12.9 35.2 10.5 31.3 8.40 27.4 6.65
-7.0 -7.6 37.1 37.1 12.7 33.4 10.3 29.7 8.25 26.0 6.53
-10 -10.5 34.1 34.1 12.3 30.7 10.0 27.3 8.04 23.9 6.36
-14.5 -15.0 29.4 29.4 11.8 26.4 9.61 23.5 7.70 20.6 6.10

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 50.0 30.0 5.18 25.0 4.25 20.0 3.63 15.0 3.30
13.0 11.8 50.0 30.0 5.29 25.0 4.30 20.0 3.63 15.0 3.27
11.0 9.8 50.0 30.0 5.43 25.0 4.37 20.0 3.64 15.0 3.24
9.0 7.9 50.0 30.0 5.58 25.0 4.45 20.0 3.66 15.0 3.21
7.0 6.0 48.3 30.0 5.76 25.0 4.54 20.0 3.69 15.0 3.19
5.0 4.1 46.6 29.0 5.67 24.2 4.47 19.3 3.63 14.5 3.15
3.0 2.2 43.9 27.9 5.58 23.3 4.41 18.6 3.58 14.0 3.10
0.0 -0.7 41.0 26.3 5.45 21.9 4.30 17.5 3.49 13.2 3.02
-3.0 -3.7 39.1 24.6 5.31 20.5 4.19 16.4 3.40 12.3 2.95
-5.0 -5.6 37.1 23.5 5.22 19.6 4.12 15.6 3.35 11.7 2.90
-7.0 -7.6 34.1 22.3 5.13 18.6 4.05 14.8 3.29 11.1 2.85
-10 -10.5 29.4 20.5 5.00 17.1 3.94 13.7 3.20 10.2 2.77
-14.5 -15.0 50.0 17.6 4.79 14.7 3.78 11.8 3.07 8.82 2.66
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -39
11 Technical Specifications

Combination
• Standard model
MMY-AP1814HT8, AP1814T8 (18HP, 50.4kW system)
Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 46.9 46.9 13.8 42.2 11.4 37.5 9.22 32.8 7.37
39 °C 47.7 47.7 13.6 42.9 11.2 38.1 9.08 33.4 7.26
37 °C 49.1 49.1 13.2 44.2 10.9 39.3 8.81 34.4 7.04
35 °C 50.4 50.4 12.8 45.4 10.5 40.3 8.53 35.3 6.82
33 °C 50.4 50.4 11.8 45.4 9.75 40.3 7.92 35.3 6.35
31 °C 50.4 50.4 11.0 45.4 9.06 40.3 7.37 35.3 5.93
30 °C 50.4 50.4 10.6 45.4 8.74 40.3 7.12 35.3 5.73
29 °C 50.4 50.4 10.2 45.4 8.44 40.3 6.88 35.3 5.55
27 °C 50.4 50.4 9.53 45.4 7.88 40.3 6.43 35.3 5.20
25 °C 50.4 50.4 8.89 45.4 7.36 40.3 6.02 35.3 4.88
23 °C 50.4 50.4 8.31 45.4 6.89 40.3 5.64 35.3 4.58
21 °C 50.4 50.4 8.14 45.4 6.75 40.3 5.54 35.3 4.50
20 °C 50.4 50.4 8.06 45.4 6.68 40.3 5.49 35.3 4.47
19 °C 50.4 50.4 7.98 45.4 6.63 40.3 5.44 35.3 4.43
17 °C 50.4 50.4 7.85 45.4 6.52 40.3 5.36 35.3 4.37
15 °C 50.4 50.4 7.74 45.4 6.43 40.3 5.30 35.3 4.33

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 46.9 28.1 5.83 23.5 4.60 18.8 3.67 14.1 3.05
39 °C 47.7 28.6 5.74 23.8 4.53 19.1 3.61 14.3 3.00
37 °C 49.1 29.4 5.57 24.5 4.39 19.6 3.51 14.7 2.91
35 °C 50.4 30.2 5.39 25.2 4.25 20.2 3.39 15.1 2.82
33 °C 50.4 30.2 5.04 25.2 4.00 20.2 3.22 15.1 2.70
31 °C 50.4 30.2 4.73 25.2 3.77 20.2 3.06 15.1 2.58
30 °C 50.4 30.2 4.58 25.2 3.66 20.2 2.98 15.1 2.53
29 °C 50.4 30.2 4.44 25.2 3.56 20.2 2.90 15.1 2.47
27 °C 50.4 30.2 4.18 25.2 3.36 20.2 2.76 15.1 2.36
25 °C 50.4 30.2 3.93 25.2 3.18 20.2 2.62 15.1 2.25
23 °C 50.4 30.2 3.70 25.2 3.00 20.2 2.48 15.1 2.15
21 °C 50.4 30.2 3.65 25.2 2.97 20.2 2.46 15.1 2.14
20 °C 50.4 30.2 3.62 25.2 2.95 20.2 2.46 15.1 2.14
19 °C 50.4 30.2 3.60 25.2 2.94 20.2 2.45 15.1 2.13
17 °C 50.4 30.2 3.56 25.2 2.91 20.2 2.43 15.1 2.13
15 °C 50.4 30.2 3.52 25.2 2.89 20.2 2.42 15.1 2.12
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 56.5 56.5 10.8 50.9 9.00 45.2 7.48 39.6 6.23
13.0 11.8 56.5 56.5 11.3 50.9 9.30 45.2 7.69 39.6 6.37
11.0 9.8 56.5 56.5 11.8 50.9 9.67 45.2 7.94 39.6 6.54
9.0 7.9 56.5 56.5 12.4 50.9 10.1 45.2 8.23 39.6 6.72
7.0 6.0 56.5 56.5 13.0 50.9 10.6 45.2 8.55 39.6 6.94
5.0 4.1 54.6 54.6 12.8 49.1 10.4 43.7 8.42 38.2 6.83
3.0 2.2 52.6 52.6 12.6 47.4 10.2 42.1 8.29 36.8 6.73
0.0 -0.7 49.6 49.6 12.3 44.6 9.99 39.7 8.09 34.7 6.57
-3.0 -3.7 46.3 46.3 12.0 41.7 9.74 37.0 7.89 32.4 6.40
-5.0 -5.6 44.2 44.2 11.8 39.8 9.58 35.4 7.76 30.9 6.30
-7.0 -7.6 41.9 41.9 11.6 37.7 9.41 33.6 7.62 29.4 6.19
-10 -10.5 38.6 38.6 11.3 34.7 9.16 30.9 7.42 27.0 6.02
-14.5 -15.0 33.2 33.2 10.8 29.9 8.78 26.6 7.11 23.2 5.77

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 56.5 33.9 5.20 28.3 4.32 22.6 3.55 17.0 2.82
13.0 11.8 56.5 33.9 5.29 28.3 4.37 22.6 3.58 17.0 2.84
11.0 9.8 56.5 33.9 5.39 28.3 4.44 22.6 3.62 17.0 2.86
9.0 7.9 56.5 33.9 5.51 28.3 4.51 22.6 3.66 17.0 2.89
7.0 6.0 56.5 33.9 5.65 28.3 4.60 22.6 3.71 17.0 2.92
5.0 4.1 54.6 32.7 5.56 27.3 4.53 21.8 3.66 16.4 2.88
3.0 2.2 52.6 31.6 5.48 26.3 4.46 21.0 3.60 15.8 2.83
0.0 -0.7 49.6 29.7 5.34 24.8 4.35 19.8 3.51 14.9 2.77
-3.0 -3.7 46.3 27.8 5.21 23.2 4.24 18.5 3.43 13.9 2.70
-5.0 -5.6 44.2 26.5 5.12 22.1 4.17 17.7 3.37 13.3 2.65
-7.0 -7.6 41.9 25.2 5.03 21.0 4.10 16.8 3.31 12.6 2.60
-10 -10.5 38.6 23.2 4.90 19.3 3.99 15.4 3.22 11.6 2.54
-14.5 -15.0 33.2 19.9 4.70 16.6 3.82 13.3 3.09 9.96 2.43
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -40
11 Technical Specifications

MMY-AP2014HT8, AP2014T8 (20HP, 56kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 52.1 52.1 15.8 46.9 13.0 41.7 10.5 36.5 8.40
39 °C 52.9 52.9 15.8 47.7 13.0 42.4 10.5 37.1 8.40
37 °C 54.5 54.5 15.3 49.1 12.6 43.6 10.2 38.2 8.15
35 °C 56.0 56.0 14.8 50.4 12.2 44.8 9.87 39.2 7.89
33 °C 56.0 56.0 13.7 50.4 11.3 44.8 9.16 39.2 7.35
31 °C 56.0 56.0 12.7 50.4 10.5 44.8 8.53 39.2 6.86
30 °C 56.0 56.0 12.3 50.4 10.1 44.8 8.24 39.2 6.63
29 °C 56.0 56.0 11.8 50.4 9.76 44.8 7.96 39.2 6.42
27 °C 56.0 56.0 11.0 50.4 9.11 44.8 7.44 39.2 6.02
25 °C 56.0 56.0 10.3 50.4 8.52 44.8 6.97 39.2 5.65
23 °C 56.0 56.0 9.62 50.4 7.97 44.8 6.53 39.2 5.30
21 °C 56.0 56.0 9.41 50.4 7.80 44.8 6.40 39.2 5.21
20 °C 56.0 56.0 9.32 50.4 7.73 44.8 6.35 39.2 5.17
19 °C 56.0 56.0 9.24 50.4 7.67 44.8 6.30 39.2 5.13
17 °C 56.0 56.0 9.08 50.4 7.55 44.8 6.20 39.2 5.06
15 °C 56.0 56.0 8.96 50.4 7.44 44.8 6.13 39.2 5.00

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 52.1 31.3 6.64 26.1 5.24 20.8 4.18 15.6 3.48
39 °C 52.9 31.8 6.64 26.5 5.24 21.2 4.18 15.9 3.48
37 °C 54.5 32.7 6.44 27.3 5.08 21.8 4.06 16.4 3.37
35 °C 56.0 33.6 6.24 28.0 4.92 22.4 3.93 16.8 3.26
33 °C 56.0 33.6 5.84 28.0 4.63 22.4 3.72 16.8 3.12
31 °C 56.0 33.6 5.47 28.0 4.36 22.4 3.54 16.8 2.99
30 °C 56.0 33.6 5.30 28.0 4.24 22.4 3.45 16.8 2.92
29 °C 56.0 33.6 5.14 28.0 4.12 22.4 3.36 16.8 2.86
27 °C 56.0 33.6 4.83 28.0 3.89 22.4 3.19 16.8 2.73
25 °C 56.0 33.6 4.55 28.0 3.68 22.4 3.03 16.8 2.61
23 °C 56.0 33.6 4.28 28.0 3.47 22.4 2.87 16.8 2.49
21 °C 56.0 33.6 4.22 28.0 3.43 22.4 2.85 16.8 2.48
20 °C 56.0 33.6 4.19 28.0 3.41 22.4 2.84 16.8 2.47
19 °C 56.0 33.6 4.16 28.0 3.40 22.4 2.83 16.8 2.47
17 °C 56.0 33.6 4.12 28.0 3.37 22.4 2.82 16.8 2.46
15 °C 56.0 33.6 4.08 28.0 3.34 22.4 2.80 16.8 2.46
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 63.0 63.0 12.5 56.7 10.4 50.4 8.62 44.1 7.18
13.0 11.8 63.0 63.0 13.0 56.7 10.7 50.4 8.85 44.1 7.34
11.0 9.8 63.0 63.0 13.6 56.7 11.1 50.4 9.15 44.1 7.53
9.0 7.9 63.0 63.0 14.2 56.7 11.6 50.4 9.47 44.1 7.74
7.0 6.0 63.0 63.0 15.0 56.7 12.2 50.4 9.84 44.1 7.99
5.0 4.1 60.9 60.9 14.8 54.8 12.0 48.7 9.69 42.6 7.87
3.0 2.2 58.7 58.7 14.5 52.8 11.8 46.9 9.54 41.1 7.75
0.0 -0.7 55.3 55.3 14.2 49.7 11.5 44.2 9.32 38.7 7.56
-3.0 -3.7 51.6 51.6 13.8 46.5 11.2 41.3 9.08 36.1 7.37
-5.0 -5.6 49.3 49.3 13.6 44.4 11.0 39.4 8.93 34.5 7.25
-7.0 -7.6 46.8 46.8 13.4 42.1 10.8 37.4 8.77 32.7 7.12
-10 -10.5 43.0 43.0 13.0 38.7 10.5 34.4 8.54 30.1 6.93
-14.5 -15.0 37.0 37.0 12.5 33.3 10.1 29.6 8.19 25.9 6.65

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 63.0 37.8 5.98 31.5 4.97 25.2 4.08 18.9 3.25
13.0 11.8 63.0 37.8 6.09 31.5 5.04 25.2 4.12 18.9 3.27
11.0 9.8 63.0 37.8 6.21 31.5 5.11 25.2 4.17 18.9 3.30
9.0 7.9 63.0 37.8 6.34 31.5 5.20 25.2 4.22 18.9 3.33
7.0 6.0 63.0 37.8 6.50 31.5 5.29 25.2 4.28 18.9 3.36
5.0 4.1 60.9 36.5 6.40 30.4 5.21 24.3 4.21 18.3 3.31
3.0 2.2 58.7 35.2 6.30 29.3 5.13 23.5 4.14 17.6 3.26
0.0 -0.7 55.3 33.2 6.15 27.6 5.01 22.1 4.05 16.6 3.18
-3.0 -3.7 51.6 31.0 6.00 25.8 4.88 20.7 3.94 15.5 3.10
-5.0 -5.6 49.3 29.6 5.90 24.6 4.80 19.7 3.88 14.8 3.05
-7.0 -7.6 46.8 28.1 5.79 23.4 4.72 18.7 3.81 14.0 3.00
-10 -10.5 43.0 25.8 5.64 21.5 4.59 17.2 3.71 12.9 2.92
-14.5 -15.0 37.0 22.2 5.41 18.5 4.40 14.8 3.56 11.1 2.80
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -41
11 Technical Specifications

MMY-AP2214HT8, AP2214T8 (22HP, 61.5kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 57.2 57.2 18.3 51.5 15.0 45.8 12.1 40.1 9.64
39 °C 58.2 58.2 18.0 52.3 14.8 46.5 11.9 40.7 9.49
37 °C 59.9 59.9 17.5 53.9 14.3 47.9 11.6 41.9 9.21
35 °C 61.5 61.5 17.0 55.4 13.9 49.2 11.2 43.1 8.92
33 °C 61.5 61.5 15.7 55.4 12.8 49.2 10.4 43.1 8.30
31 °C 61.5 61.5 14.5 55.4 11.9 49.2 9.66 43.1 7.74
30 °C 61.5 61.5 14.0 55.4 11.5 49.2 9.33 43.1 7.49
29 °C 61.5 61.5 13.5 55.4 11.1 49.2 9.01 43.1 7.24
27 °C 61.5 61.5 12.6 55.4 10.4 49.2 8.42 43.1 6.79
25 °C 61.5 61.5 11.7 55.4 9.67 49.2 7.88 43.1 6.37
23 °C 61.5 61.5 11.0 55.4 9.04 49.2 7.38 43.1 5.97
21 °C 61.5 61.5 10.7 55.4 8.86 49.2 7.24 43.1 5.87
20 °C 61.5 61.5 10.6 55.4 8.77 49.2 7.18 43.1 5.82
19 °C 61.5 61.5 10.5 55.4 8.69 49.2 7.12 43.1 5.78
17 °C 61.5 61.5 10.3 55.4 8.56 49.2 7.01 43.1 5.70
15 °C 61.5 61.5 10.2 55.4 8.44 49.2 6.92 43.1 5.64

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 57.2 34.3 7.60 28.6 5.97 22.9 4.77 17.2 3.97
39 °C 58.2 34.9 7.48 29.1 5.88 23.3 4.70 17.4 3.91
37 °C 59.9 35.9 7.26 29.9 5.71 24.0 4.55 18.0 3.79
35 °C 61.5 36.9 7.03 30.8 5.53 24.6 4.41 18.5 3.67
33 °C 61.5 36.9 6.57 30.8 5.20 24.6 4.18 18.5 3.51
31 °C 61.5 36.9 6.16 30.8 4.90 24.6 3.97 18.5 3.36
30 °C 61.5 36.9 5.96 30.8 4.76 24.6 3.87 18.5 3.29
29 °C 61.5 36.9 5.78 30.8 4.62 24.6 3.77 18.5 3.22
27 °C 61.5 36.9 5.44 30.8 4.37 24.6 3.58 18.5 3.08
25 °C 61.5 36.9 5.11 30.8 4.13 24.6 3.40 18.5 2.94
23 °C 61.5 36.9 4.81 30.8 3.90 24.6 3.23 18.5 2.80
21 °C 61.5 36.9 4.74 30.8 3.85 24.6 3.20 18.5 2.79
20 °C 61.5 36.9 4.71 30.8 3.83 24.6 3.19 18.5 2.78
19 °C 61.5 36.9 4.68 30.8 3.81 24.6 3.18 18.5 2.78
17 °C 61.5 36.9 4.63 30.8 3.78 24.6 3.16 18.5 2.77
15 °C 61.5 36.9 4.58 30.8 3.75 24.6 3.15 18.5 2.77
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 69.0 69.0 14.7 62.1 12.2 55.2 10.1 48.3 8.38
13.0 11.8 69.0 69.0 15.3 62.1 12.6 55.2 10.4 48.3 8.57
11.0 9.8 69.0 69.0 16.0 62.1 13.2 55.2 10.8 48.3 8.81
9.0 7.9 69.0 69.0 16.8 62.1 13.7 55.2 11.2 48.3 9.08
7.0 6.0 69.0 69.0 17.7 62.1 14.4 55.2 11.6 48.3 9.38
5.0 4.1 66.7 66.7 17.4 60.0 14.1 53.3 11.4 46.7 9.24
3.0 2.2 64.3 64.3 17.2 57.8 13.9 51.4 11.3 45.0 9.10
0.0 -0.7 60.5 60.5 16.7 54.5 13.6 48.4 11.0 42.4 8.88
-3.0 -3.7 56.6 56.6 16.3 50.9 13.2 45.2 10.7 39.6 8.65
-5.0 -5.6 54.0 54.0 16.1 48.6 13.0 43.2 10.5 37.8 8.51
-7.0 -7.6 51.2 51.2 15.8 46.1 12.8 41.0 10.3 35.9 8.36
-10 -10.5 47.1 47.1 15.4 42.4 12.5 37.7 10.1 33.0 8.14
-14.5 -15.0 40.6 40.6 14.7 36.5 11.9 32.4 9.66 28.4 7.80

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 69.0 41.4 6.94 34.5 5.76 27.6 4.75 20.7 3.88
13.0 11.8 69.0 41.4 7.07 34.5 5.83 27.6 4.79 20.7 3.90
11.0 9.8 69.0 41.4 7.22 34.5 5.92 27.6 4.84 20.7 3.91
9.0 7.9 69.0 41.4 7.39 34.5 6.02 27.6 4.89 20.7 3.94
7.0 6.0 69.0 41.4 7.58 34.5 6.13 27.6 4.95 20.7 3.97
5.0 4.1 66.7 40.0 7.46 33.3 6.04 26.7 4.88 20.0 3.91
3.0 2.2 64.3 38.6 7.35 32.1 5.94 25.7 4.80 19.3 3.85
0.0 -0.7 60.5 36.3 7.17 30.3 5.80 24.2 4.69 18.2 3.75
-3.0 -3.7 56.6 33.9 6.99 28.3 5.65 22.6 4.57 17.0 3.66
-5.0 -5.6 54.0 32.4 6.88 27.0 5.56 21.6 4.49 16.2 3.60
-7.0 -7.6 51.2 30.7 6.75 25.6 5.46 20.5 4.41 15.4 3.54
-10 -10.5 47.1 28.3 6.58 23.6 5.32 18.8 4.30 14.1 3.44
-14.5 -15.0 40.6 24.3 6.31 20.3 5.10 16.2 4.12 12.2 3.30
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -42
11 Technical Specifications

MMY-AP2414HT8, AP2414T8 (24HP, 68kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 63.3 63.3 21.2 57.0 17.3 50.6 13.9 44.3 11.0
39 °C 64.3 64.3 20.9 57.9 17.0 51.4 13.7 45.0 10.9
37 °C 66.2 66.2 20.3 59.6 16.5 53.0 13.3 46.4 10.5
35 °C 68.0 68.0 19.7 61.2 16.0 54.4 12.9 47.6 10.2
33 °C 68.0 68.0 18.1 61.2 14.8 54.4 11.9 47.6 9.49
31 °C 68.0 68.0 16.8 61.2 13.7 54.4 11.1 47.6 8.85
30 °C 68.0 68.0 16.2 61.2 13.2 54.4 10.7 47.6 8.56
29 °C 68.0 68.0 15.6 61.2 12.8 54.4 10.3 47.6 8.28
27 °C 68.0 68.0 14.5 61.2 11.9 54.4 9.66 47.6 7.75
25 °C 68.0 68.0 13.5 61.2 11.1 54.4 9.03 47.6 7.27
23 °C 68.0 68.0 12.6 61.2 10.4 54.4 8.46 47.6 6.82
21 °C 68.0 68.0 12.4 61.2 10.2 54.4 8.29 47.6 6.70
20 °C 68.0 68.0 12.2 61.2 10.1 54.4 8.22 47.6 6.64
19 °C 68.0 68.0 12.1 61.2 9.99 54.4 8.15 47.6 6.59
17 °C 68.0 68.0 11.9 61.2 9.83 54.4 8.02 47.6 6.50
15 °C 68.0 68.0 11.7 61.2 9.69 54.4 7.92 47.6 6.43

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 64.3 38.0 8.66 31.6 6.80 25.3 5.42 19.0 4.52
39 °C 66.2 38.6 8.53 32.1 6.69 25.7 5.34 19.3 4.45
37 °C 68.0 39.7 8.28 33.1 6.49 26.5 5.18 19.9 4.32
35 °C 68.0 40.8 8.02 34.0 6.29 27.2 5.01 20.4 4.18
33 °C 68.0 40.8 7.49 34.0 5.91 27.2 4.75 20.4 4.00
31 °C 68.0 40.8 7.02 34.0 5.57 27.2 4.51 20.4 3.83
30 °C 68.0 40.8 6.80 34.0 5.41 27.2 4.40 20.4 3.75
29 °C 68.0 40.8 6.59 34.0 5.26 27.2 4.29 20.4 3.67
27 °C 68.0 40.8 6.19 34.0 4.97 27.2 4.07 20.4 3.51
25 °C 68.0 40.8 5.82 34.0 4.69 27.2 3.87 20.4 3.35
23 °C 68.0 40.8 5.48 34.0 4.43 27.2 3.67 20.4 3.19
21 °C 68.0 40.8 5.40 34.0 4.38 27.2 3.64 20.4 3.18
20 °C 68.0 40.8 5.36 34.0 4.36 27.2 3.63 20.4 3.18
19 °C 68.0 40.8 5.33 34.0 4.34 27.2 3.62 20.4 3.17
17 °C 68.0 40.8 5.26 34.0 4.30 27.2 3.60 20.4 3.16
15 °C 63.3 40.8 5.21 34.0 4.26 27.2 3.58 20.4 3.16
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 76.5 76.5 17.6 68.9 14.6 61.2 12.0 53.6 9.90
13.0 11.8 76.5 76.5 18.3 68.9 15.1 61.2 12.4 53.6 10.1
11.0 9.8 76.5 76.5 19.2 68.9 15.7 61.2 12.8 53.6 10.4
9.0 7.9 76.5 76.5 20.1 68.9 16.4 61.2 13.3 53.6 10.8
7.0 6.0 76.5 76.5 21.1 68.9 17.2 61.2 13.9 53.6 11.1
5.0 4.1 73.9 73.9 20.8 66.5 16.9 59.1 13.6 51.7 11.0
3.0 2.2 71.3 71.3 20.5 64.1 16.6 57.0 13.4 49.9 10.8
0.0 -0.7 67.1 67.1 20.0 60.4 16.2 53.7 13.1 47.0 10.5
-3.0 -3.7 62.7 62.7 19.5 56.4 15.8 50.2 12.8 43.9 10.3
-5.0 -5.6 59.8 59.8 19.2 53.9 15.6 47.9 12.6 41.9 10.1
-7.0 -7.6 56.8 56.8 18.8 51.1 15.3 45.4 12.4 39.8 9.93
-10 -10.5 52.2 52.2 18.3 47.0 14.9 41.8 12.0 36.6 9.67
-14.5 -15.0 45.0 45.0 17.6 40.5 14.3 36.0 11.53 31.5 9.27

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 76.5 45.9 8.15 38.3 6.74 30.6 5.60 23.0 4.69
13.0 11.8 76.5 45.9 8.30 38.3 6.82 30.6 5.64 23.0 4.69
11.0 9.8 76.5 45.9 8.49 38.3 6.93 30.6 5.68 23.0 4.70
9.0 7.9 76.5 45.9 8.70 38.3 7.04 30.6 5.74 23.0 4.71
7.0 6.0 76.5 45.9 8.94 38.3 7.18 30.6 5.81 23.0 4.73
5.0 4.1 73.9 44.3 8.80 37.0 7.07 29.6 5.72 22.2 4.66
3.0 2.2 71.3 42.8 8.67 35.6 6.97 28.5 5.63 21.4 4.59
0.0 -0.7 67.1 40.3 8.46 33.6 6.80 26.8 5.49 20.1 4.48
-3.0 -3.7 62.7 37.6 8.25 31.4 6.63 25.1 5.35 18.8 4.37
-5.0 -5.6 59.8 35.9 8.11 29.9 6.52 23.9 5.27 18.0 4.29
-7.0 -7.6 56.8 34.1 7.97 28.4 6.40 22.7 5.17 17.0 4.22
-10 -10.5 52.2 31.3 7.76 26.1 6.24 20.9 5.04 15.7 4.11
-14.5 -15.0 45.0 27.0 7.44 22.5 5.98 18.0 4.83 13.5 3.94
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -43
11 Technical Specifications

MMY-AP2614HT8, AP2614T8 (26HP, 73kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 67.9 67.9 22.8 61.1 18.7 54.3 15.1 47.6 11.9
39 °C 69.0 69.0 22.5 62.1 18.4 55.2 14.8 48.3 11.7
37 °C 71.1 71.1 21.8 64.0 17.9 56.9 14.4 49.8 11.4
35 °C 73.0 73.0 21.1 65.7 17.3 58.4 13.9 51.1 11.0
33 °C 73.0 73.0 19.5 65.7 16.0 58.4 12.9 51.1 10.2
31 °C 73.0 73.0 18.1 65.7 14.9 58.4 12.0 51.1 9.51
30 °C 73.0 73.0 17.5 65.7 14.3 58.4 11.6 51.1 9.19
29 °C 73.0 73.0 16.8 65.7 13.8 58.4 11.2 51.1 8.88
27 °C 73.0 73.0 15.7 65.7 12.9 58.4 10.4 51.1 8.31
25 °C 73.0 73.0 14.6 65.7 12.0 58.4 9.75 51.1 7.78
23 °C 73.0 73.0 13.7 65.7 11.3 58.4 9.12 51.1 7.29
21 °C 73.0 73.0 13.4 65.7 11.0 58.4 8.94 51.1 7.15
20 °C 73.0 73.0 13.2 65.7 10.9 58.4 8.86 51.1 7.09
19 °C 73.0 73.0 13.1 65.7 10.8 58.4 8.78 51.1 7.04
17 °C 73.0 73.0 12.9 65.7 10.6 58.4 8.64 51.1 6.94
15 °C 73.0 73.0 12.7 65.7 10.5 58.4 8.52 51.1 6.85

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 67.9 40.8 9.23 34.0 7.13 27.2 5.64 20.4 4.80
39 °C 69.0 41.4 9.09 34.5 7.02 27.6 5.56 20.7 4.73
37 °C 71.1 42.7 8.81 35.5 6.81 28.4 5.39 21.3 4.58
35 °C 73.0 43.8 8.54 36.5 6.60 29.2 5.22 21.9 4.44
33 °C 73.0 43.8 7.96 36.5 6.19 29.2 4.95 21.9 4.26
31 °C 73.0 43.8 7.44 36.5 5.83 29.2 4.70 21.9 4.09
30 °C 73.0 43.8 7.20 36.5 5.66 29.2 4.58 21.9 4.01
29 °C 73.0 43.8 6.98 36.5 5.50 29.2 4.47 21.9 3.93
27 °C 73.0 43.8 6.55 36.5 5.19 29.2 4.25 21.9 3.76
25 °C 73.0 43.8 6.15 36.5 4.90 29.2 4.04 21.9 3.60
23 °C 73.0 43.8 5.78 36.5 4.62 29.2 3.84 21.9 3.44
21 °C 73.0 43.8 5.69 36.5 4.57 29.2 3.81 21.9 3.44
20 °C 73.0 43.8 5.65 36.5 4.54 29.2 3.80 21.9 3.43
19 °C 73.0 43.8 5.61 36.5 4.52 29.2 3.78 21.9 3.43
17 °C 73.0 43.8 5.54 36.5 4.48 29.2 3.76 21.9 3.43
15 °C 73.0 43.8 5.48 36.5 4.44 29.2 3.75 21.9 3.42
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 81.5 81.5 18.1 73.4 14.9 65.2 12.3 57.1 10.1
13.0 11.8 81.5 81.5 18.8 73.4 15.5 65.2 12.7 57.1 10.3
11.0 9.8 81.5 81.5 19.7 73.4 16.1 65.2 13.1 57.1 10.6
9.0 7.9 81.5 81.5 20.6 73.4 16.8 65.2 13.6 57.1 11.0
7.0 6.0 81.5 81.5 21.7 73.4 17.6 65.2 14.2 57.1 11.4
5.0 4.1 78.7 78.7 21.4 70.9 17.3 63.0 14.0 55.1 11.2
3.0 2.2 75.9 75.9 21.0 68.3 17.1 60.7 13.8 53.1 11.0
0.0 -0.7 71.5 71.5 20.5 64.3 16.7 57.2 13.4 50.0 10.8
-3.0 -3.7 66.8 66.8 20.0 60.1 16.2 53.4 13.1 46.8 10.5
-5.0 -5.6 63.8 63.8 19.7 57.4 16.0 51.0 12.9 44.6 10.3
-7.0 -7.6 60.5 60.5 19.3 54.4 15.7 48.4 12.7 42.3 10.1
-10 -10.5 55.7 55.7 18.8 50.1 15.3 44.5 12.3 39.0 9.88
-14.5 -15.0 47.9 47.9 18.1 43.1 14.7 38.3 11.8 33.5 9.47

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 81.5 48.9 8.29 40.8 6.85 32.6 5.72 24.5 4.87
13.0 11.8 81.5 48.9 8.44 40.8 6.93 32.6 5.75 24.5 4.86
11.0 9.8 81.5 48.9 8.64 40.8 7.04 32.6 5.80 24.5 4.86
9.0 7.9 81.5 48.9 8.85 40.8 7.16 32.6 5.85 24.5 4.86
7.0 6.0 81.5 48.9 9.10 40.8 7.30 32.6 5.91 24.5 4.88
5.0 4.1 78.7 47.2 8.96 39.4 7.19 31.5 5.82 23.6 4.80
3.0 2.2 75.9 45.5 8.82 38.0 7.08 30.4 5.73 22.8 4.73
0.0 -0.7 71.5 42.9 8.61 35.7 6.91 28.6 5.59 21.4 4.61
-3.0 -3.7 66.8 40.1 8.39 33.4 6.73 26.7 5.45 20.0 4.50
-5.0 -5.6 63.8 38.3 8.26 31.9 6.62 25.5 5.36 19.1 4.42
-7.0 -7.6 60.5 36.3 8.11 30.2 6.51 24.2 5.27 18.1 4.34
-10 -10.5 55.7 33.4 7.90 27.8 6.34 22.3 5.13 16.7 4.23
-14.5 -15.0 47.9 28.7 7.57 24.0 6.07 19.2 4.92 14.4 4.06
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -44
11 Technical Specifications

MMY-AP2814HT8, AP2814T8 (28HP, 78.5kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 73.1 73.1 25.1 65.7 20.5 58.4 16.4 51.1 12.9
39 °C 74.2 74.2 24.7 66.8 20.2 59.4 16.2 52.0 12.7
37 °C 76.4 76.4 24.0 68.8 19.6 61.2 15.7 53.5 12.3
35 °C 78.5 78.5 23.3 70.7 19.0 62.8 15.2 55.0 12.0
33 °C 78.5 78.5 21.5 70.7 17.6 62.8 14.1 55.0 11.1
31 °C 78.5 78.5 19.9 70.7 16.3 62.8 13.1 55.0 10.33
30 °C 78.5 78.5 19.2 70.7 15.7 62.8 12.6 55.0 9.98
29 °C 78.5 78.5 18.5 70.7 15.1 62.8 12.2 55.0 9.64
27 °C 78.5 78.5 17.2 70.7 14.1 62.8 11.4 55.0 9.01
25 °C 78.5 78.5 16.1 70.7 13.2 62.8 10.6 55.0 8.44
23 °C 78.5 78.5 15.0 70.7 12.3 62.8 9.93 55.0 7.91
21 °C 78.5 78.5 14.7 70.7 12.0 62.8 9.72 55.0 7.75
20 °C 78.5 78.5 14.5 70.7 11.9 62.8 9.63 55.0 7.69
19 °C 78.5 78.5 14.4 70.7 11.8 62.8 9.55 55.0 7.63
17 °C 78.5 78.5 14.1 70.7 11.6 62.8 9.40 55.0 7.52
15 °C 78.5 78.5 13.9 70.7 11.4 62.8 9.27 55.0 7.42

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 73.1 43.8 9.99 36.5 7.70 29.2 6.08 21.9 5.19
39 °C 74.2 44.5 9.85 37.1 7.59 29.7 5.99 22.3 5.11
37 °C 76.4 45.9 9.55 38.2 7.36 30.6 5.81 22.9 4.96
35 °C 78.5 47.1 9.25 39.3 7.13 31.4 5.63 23.6 4.80
33 °C 78.5 47.1 8.62 39.3 6.69 31.4 5.34 23.6 4.61
31 °C 78.5 47.1 8.06 39.3 6.29 31.4 5.07 23.6 4.43
30 °C 78.5 47.1 7.80 39.3 6.11 31.4 4.95 23.6 4.34
29 °C 78.5 47.1 7.55 39.3 5.93 31.4 4.82 23.6 4.25
27 °C 78.5 47.1 7.08 39.3 5.60 31.4 4.59 23.6 4.07
25 °C 78.5 47.1 6.65 39.3 5.28 31.4 4.36 23.6 3.90
23 °C 78.5 47.1 6.25 39.3 4.99 31.4 4.14 23.6 3.73
21 °C 78.5 47.1 6.15 39.3 4.93 31.4 4.11 23.6 3.72
20 °C 78.5 47.1 6.10 39.3 4.90 31.4 4.10 23.6 3.72
19 °C 78.5 47.1 6.06 39.3 4.87 31.4 4.09 23.6 3.72
17 °C 78.5 47.1 5.99 39.3 4.83 31.4 4.07 23.6 3.71
15 °C 78.5 47.1 5.92 39.3 4.79 31.4 4.05 23.6 3.71
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 88.0 88.0 20.6 79.2 17.0 70.4 13.9 61.6 11.3
13.0 11.8 88.0 88.0 21.4 79.2 17.6 70.4 14.3 61.6 11.6
11.0 9.8 88.0 88.0 22.4 79.2 18.3 70.4 14.9 61.6 12.0
9.0 7.9 88.0 88.0 23.4 79.2 19.1 70.4 15.5 61.6 12.4
7.0 6.0 88.0 88.0 24.7 79.2 20.0 70.4 16.1 61.6 12.9
5.0 4.1 85.0 85.0 24.3 76.5 19.7 68.0 15.9 59.5 12.7
3.0 2.2 82.0 82.0 23.9 73.8 19.4 65.6 15.6 57.4 12.5
0.0 -0.7 77.2 77.2 23.3 69.5 19.0 61.8 15.3 54.0 12.2
-3.0 -3.7 72.1 72.1 22.7 64.9 18.5 57.7 14.9 50.5 11.9
-5.0 -5.6 68.8 68.8 22.4 62.0 18.2 55.1 14.6 48.2 11.7
-7.0 -7.6 65.3 65.3 22.0 58.8 17.9 52.3 14.4 45.7 11.5
-10 -10.5 60.1 60.1 21.4 54.1 17.4 48.1 14.0 42.1 11.16
-14.5 -15.0 51.7 51.7 20.5 46.6 16.7 41.4 13.4 36.2 10.70

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 88.0 52.8 9.25 44.0 7.62 35.2 6.41 26.4 5.60
13.0 11.8 88.0 52.8 9.43 44.0 7.71 35.2 6.44 26.4 5.57
11.0 9.8 88.0 52.8 9.66 44.0 7.83 35.2 6.47 26.4 5.55
9.0 7.9 88.0 52.8 9.91 44.0 7.97 35.2 6.52 26.4 5.54
7.0 6.0 88.0 52.8 10.2 44.0 8.13 35.2 6.59 26.4 5.53
5.0 4.1 85.0 51.0 10.1 42.5 8.01 34.0 6.49 25.5 5.45
3.0 2.2 82.0 49.2 9.90 41.0 7.89 32.8 6.39 24.6 5.37
0.0 -0.7 77.2 46.3 9.66 38.6 7.70 30.9 6.24 23.2 5.24
-3.0 -3.7 72.1 43.3 9.42 36.1 7.50 28.9 6.08 21.6 5.10
-5.0 -5.6 68.8 41.3 9.26 34.4 7.38 27.5 5.98 20.7 5.02
-7.0 -7.6 65.3 39.2 9.10 32.7 7.25 26.1 5.87 19.6 4.93
-10 -10.5 60.1 36.1 8.86 30.0 7.06 24.0 5.72 18.0 4.80
-14.5 -15.0 51.7 31.0 8.50 25.9 6.77 20.7 5.48 15.5 4.60
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -45
11 Technical Specifications

MMY-AP3014HT8, AP3014T8 (30HP, 85kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 79.1 79.1 27.2 71.2 22.3 63.3 17.8 55.4 13.9
39 °C 80.4 80.4 26.8 72.3 21.9 64.3 17.6 56.3 13.7
37 °C 82.8 82.8 26.0 74.5 21.3 66.2 17.0 57.9 13.3
35 °C 85.0 85.0 25.2 76.5 20.6 68.0 16.5 59.5 12.9
33 °C 85.0 85.0 23.3 76.5 19.1 68.0 15.3 59.5 12.0
31 °C 85.0 85.0 21.6 76.5 17.7 68.0 14.2 59.5 11.1
30 °C 85.0 85.0 20.8 76.5 17.0 68.0 13.7 59.5 10.7
29 °C 85.0 85.0 20.1 76.5 16.4 68.0 13.2 59.5 10.4
27 °C 85.0 85.0 18.7 76.5 15.3 68.0 12.3 59.5 9.69
25 °C 85.0 85.0 17.4 76.5 14.3 68.0 11.5 59.5 9.07
23 °C 85.0 85.0 16.3 76.5 13.3 68.0 10.7 59.5 8.49
21 °C 85.0 85.0 15.9 76.5 13.0 68.0 10.5 59.5 8.32
20 °C 85.0 85.0 15.8 76.5 12.9 68.0 10.4 59.5 8.25
19 °C 85.0 85.0 15.6 76.5 12.8 68.0 10.3 59.5 8.18
17 °C 85.0 85.0 15.3 76.5 12.6 68.0 10.1 59.5 8.06
15 °C 85.0 85.0 15.1 76.5 12.4 68.0 9.99 59.5 7.95

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 79.1 47.5 10.7 39.5 8.18 31.6 6.44 23.7 5.55
39 °C 80.4 48.2 10.5 40.2 8.06 32.1 6.34 24.1 5.46
37 °C 82.8 49.7 10.2 41.4 7.82 33.1 6.15 24.8 5.30
35 °C 85.0 51.0 9.91 42.5 7.57 34.0 5.95 25.5 5.13
33 °C 85.0 51.0 9.22 42.5 7.10 34.0 5.65 25.5 4.94
31 °C 85.0 51.0 8.61 42.5 6.67 34.0 5.37 25.5 4.75
30 °C 85.0 51.0 8.33 42.5 6.48 34.0 5.23 25.5 4.65
29 °C 85.0 51.0 8.06 42.5 6.29 34.0 5.11 25.5 4.56
27 °C 85.0 51.0 7.56 42.5 5.93 34.0 4.86 25.5 4.38
25 °C 85.0 51.0 7.09 42.5 5.60 34.0 4.62 25.5 4.20
23 °C 85.0 51.0 6.66 42.5 5.28 34.0 4.39 25.5 4.02
21 °C 85.0 51.0 6.55 42.5 5.22 34.0 4.36 25.5 4.01
20 °C 85.0 51.0 6.50 42.5 5.19 34.0 4.34 25.5 4.01
19 °C 85.0 51.0 6.45 42.5 5.16 34.0 4.33 25.5 4.01
17 °C 85.0 51.0 6.37 42.5 5.11 34.0 4.31 25.5 4.01
15 °C 85.0 51.0 6.30 42.5 5.07 34.0 4.30 25.5 4.01
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 95.0 95.0 21.2 85.5 17.5 76.0 14.4 66.5 11.8
13.0 11.8 95.0 95.0 22.0 85.5 18.1 76.0 14.8 66.5 12.1
11.0 9.8 95.0 95.0 23.0 85.5 18.9 76.0 15.4 66.5 12.5
9.0 7.9 95.0 95.0 24.1 85.5 19.7 76.0 15.9 66.5 12.9
7.0 6.0 95.0 95.0 25.4 85.5 20.6 76.0 16.6 66.5 13.3
5.0 4.1 91.8 91.8 25.0 82.6 20.3 73.4 16.4 64.2 13.1
3.0 2.2 88.5 88.5 24.6 79.6 20.0 70.8 16.1 61.9 12.9
0.0 -0.7 83.3 83.3 24.0 75.0 19.5 66.7 15.7 58.3 12.6
-3.0 -3.7 77.9 77.9 23.4 70.1 19.0 62.3 15.3 54.5 12.3
-5.0 -5.6 74.3 74.3 23.0 66.9 18.7 59.5 15.1 52.0 12.1
-7.0 -7.6 70.5 70.5 22.6 63.5 18.4 56.4 14.8 49.4 11.9
-10 -10.5 64.9 64.9 22.0 58.4 17.9 51.9 14.4 45.4 11.6
-14.5 -15.0 55.8 55.8 21.1 50.3 17.2 44.7 13.8 39.1 11.1

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 95.0 57.0 9.70 47.5 8.02 38.0 6.70 28.5 5.70
13.0 11.8 95.0 57.0 9.88 47.5 8.11 38.0 6.74 28.5 5.69
11.0 9.8 95.0 57.0 10.1 47.5 8.24 38.0 6.78 28.5 5.69
9.0 7.9 95.0 57.0 10.4 47.5 8.38 38.0 6.84 28.5 5.69
7.0 6.0 95.0 57.0 10.7 47.5 8.54 38.0 6.92 28.5 5.71
5.0 4.1 91.8 55.1 10.5 45.9 8.41 36.7 6.81 27.5 5.62
3.0 2.2 88.5 53.1 10.3 44.2 8.28 35.4 6.71 26.5 5.53
0.0 -0.7 83.3 50.0 10.1 41.7 8.09 33.3 6.55 25.0 5.40
-3.0 -3.7 77.9 46.7 9.83 38.9 7.88 31.1 6.38 23.4 5.26
-5.0 -5.6 74.3 44.6 9.66 37.2 7.75 29.7 6.28 22.3 5.18
-7.0 -7.6 70.5 42.3 9.49 35.3 7.61 28.2 6.17 21.2 5.09
-10 -10.5 64.9 38.9 9.25 32.4 7.42 26.0 6.01 19.5 4.95
-14.5 -15.0 55.8 33.5 8.86 27.9 7.11 22.3 5.76 16.8 4.75
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -46
11 Technical Specifications

MMY-AP3214HT8, AP3214T8 (32HP, 90kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 83.8 83.8 29.6 75.4 24.3 67.0 19.4 58.6 15.1
39 °C 85.1 85.1 29.2 76.6 23.9 68.1 19.1 59.6 14.9
37 °C 87.6 87.6 28.3 78.9 23.2 70.1 18.5 61.3 14.4
35 °C 90.0 90.0 27.4 81.0 22.4 72.0 17.9 63.0 14.0
33 °C 90.0 90.0 25.3 81.0 20.7 72.0 16.6 63.0 12.9
31 °C 90.0 90.0 23.5 81.0 19.2 72.0 15.4 63.0 12.0
30 °C 90.0 90.0 22.6 81.0 18.5 72.0 14.8 63.0 11.6
29 °C 90.0 90.0 21.8 81.0 17.9 72.0 14.3 63.0 11.2
27 °C 90.0 90.0 20.3 81.0 16.7 72.0 13.3 63.0 10.4
25 °C 90.0 90.0 19.0 81.0 15.5 72.0 12.4 63.0 9.76
23 °C 90.0 90.0 17.7 81.0 14.5 72.0 11.6 63.0 9.13
21 °C 90.0 90.0 17.3 81.0 14.2 72.0 11.4 63.0 8.94
20 °C 90.0 90.0 17.2 81.0 14.0 72.0 11.3 63.0 8.86
19 °C 90.0 90.0 17.0 81.0 13.9 72.0 11.1 63.0 8.78
17 °C 90.0 90.0 16.7 81.0 13.7 72.0 11.0 63.0 8.65
15 °C 90.0 90.0 16.4 81.0 13.5 72.0 10.80 63.0 8.53

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 83.8 50.3 11.5 41.9 8.68 33.5 6.79 25.1 5.93
39 °C 85.1 51.1 11.3 42.5 8.55 34.0 6.69 25.5 5.84
37 °C 87.6 52.6 11.0 43.8 8.29 35.1 6.49 26.3 5.67
35 °C 90.0 54.0 10.6 45.0 8.03 36.0 6.28 27.0 5.49
33 °C 90.0 54.0 9.88 45.0 7.52 36.0 5.96 27.0 5.29
31 °C 90.0 54.0 9.21 45.0 7.07 36.0 5.67 27.0 5.10
30 °C 90.0 54.0 8.90 45.0 6.86 36.0 5.53 27.0 5.00
29 °C 90.0 54.0 8.61 45.0 6.65 36.0 5.39 27.0 4.90
27 °C 90.0 54.0 8.06 45.0 6.27 36.0 5.13 27.0 4.72
25 °C 90.0 54.0 7.56 45.0 5.92 36.0 4.88 27.0 4.53
23 °C 90.0 54.0 7.10 45.0 5.58 36.0 4.64 27.0 4.34
21 °C 90.0 54.0 6.97 45.0 5.51 36.0 4.61 27.0 4.34
20 °C 90.0 54.0 6.92 45.0 5.48 36.0 4.60 27.0 4.34
19 °C 90.0 54.0 6.86 45.0 5.45 36.0 4.59 27.0 4.34
17 °C 90.0 54.0 6.77 45.0 5.40 36.0 4.57 27.0 4.34
15 °C 90.0 54.0 6.70 45.0 5.35 36.0 4.55 27.0 4.34
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 100.0 100.0 23.7 90.0 19.5 80.0 15.8 70.0 12.8
13.0 11.8 100.0 100.0 24.7 90.0 20.2 80.0 16.4 70.0 13.2
11.0 9.8 100.0 100.0 25.8 90.0 21.1 80.0 17.0 70.0 13.6
9.0 7.9 100.0 100.0 27.0 90.0 22.0 80.0 17.7 70.0 14.1
7.0 6.0 100.0 100.0 28.4 90.0 23.1 80.0 18.5 70.0 14.7
5.0 4.1 96.6 96.6 28.0 86.9 22.7 77.3 18.2 67.6 14.4
3.0 2.2 93.1 93.1 27.5 83.8 22.4 74.5 18.0 65.2 14.2
0.0 -0.7 87.7 87.7 26.9 79.0 21.9 70.2 17.5 61.4 13.9
-3.0 -3.7 82.0 82.0 26.2 73.8 21.3 65.6 17.1 57.4 13.5
-5.0 -5.6 78.2 78.2 25.8 70.4 21.0 62.6 16.8 54.8 13.3
-7.0 -7.6 74.2 74.2 25.3 66.8 20.6 59.4 16.5 52.0 13.1
-10 -10.5 68.3 68.3 24.6 61.5 20.0 54.6 16.1 47.8 12.7
-14.5 -15.0 58.8 58.8 23.6 52.9 19.2 47.0 15.4 41.1 12.2

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 100.0 60.0 10.4 50.0 8.51 40.0 7.25 30.0 6.60
13.0 11.8 100.0 60.0 10.6 50.0 8.61 40.0 7.26 30.0 6.53
11.0 9.8 100.0 60.0 10.9 50.0 8.74 40.0 7.28 30.0 6.48
9.0 7.9 100.0 60.0 11.2 50.0 8.90 40.0 7.32 30.0 6.43
7.0 6.0 100.0 60.0 11.5 50.0 9.09 40.0 7.38 30.0 6.39
5.0 4.1 96.6 58.0 11.3 48.3 8.95 38.6 7.27 29.0 6.29
3.0 2.2 93.1 55.9 11.2 46.6 8.81 37.3 7.16 27.9 6.20
0.0 -0.7 87.7 52.6 10.9 43.9 8.60 35.1 6.98 26.3 6.05
-3.0 -3.7 82.0 49.2 10.6 41.0 8.38 32.8 6.81 24.6 5.89
-5.0 -5.6 78.2 46.9 10.4 39.1 8.24 31.3 6.69 23.5 5.80
-7.0 -7.6 74.2 44.5 10.3 37.1 8.10 29.7 6.58 22.3 5.69
-10 -10.5 68.3 41.0 9.99 34.1 7.89 27.3 6.41 20.5 5.55
-14.5 -15.0 58.8 35.3 9.58 29.4 7.56 23.5 6.14 17.6 5.32
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -47
11 Technical Specifications

MMY-AP3414HT8, AP3414T8 (34HP, 96kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 89.3 89.3 29.2 80.4 23.9 71.5 19.3 62.5 15.3
39 °C 90.8 90.8 28.8 81.7 23.6 72.6 19.0 63.5 15.1
37 °C 93.5 93.5 27.9 84.1 22.8 74.8 18.4 65.4 14.7
35 °C 96.0 96.0 27.1 86.4 22.1 76.8 17.8 67.2 14.2
33 °C 96.0 96.0 25.0 86.4 20.5 76.8 16.5 67.2 13.2
31 °C 96.0 96.0 23.1 86.4 19.0 76.8 15.4 67.2 12.3
30 °C 96.0 96.0 22.3 86.4 18.3 76.8 14.9 67.2 11.9
29 °C 96.0 96.0 21.5 86.4 17.7 76.8 14.4 67.2 11.5
27 °C 96.0 96.0 20.0 86.4 16.5 76.8 13.4 67.2 10.8
25 °C 96.0 96.0 18.7 86.4 15.4 76.8 12.6 67.2 10.1
23 °C 96.0 96.0 17.5 86.4 14.4 76.8 11.8 67.2 9.49
21 °C 96.0 96.0 17.1 86.4 14.1 76.8 11.5 67.2 9.32
20 °C 96.0 96.0 16.9 86.4 14.0 76.8 11.4 67.2 9.25
19 °C 96.0 96.0 16.8 86.4 13.9 76.8 11.3 67.2 9.18
17 °C 96.0 96.0 16.5 86.4 13.6 76.8 11.2 67.2 9.06
15 °C 96.0 96.0 16.2 86.4 13.4 76.8 11.0 67.2 8.95

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 89.3 53.6 12.1 44.7 9.46 35.7 7.53 26.8 6.28
39 °C 90.8 54.5 11.9 45.4 9.32 36.3 7.42 27.2 6.19
37 °C 93.5 56.1 11.5 46.7 9.04 37.4 7.20 28.0 6.00
35 °C 96.0 57.6 11.2 48.0 8.75 38.4 6.97 28.8 5.81
33 °C 96.0 57.6 10.4 48.0 8.23 38.4 6.61 28.8 5.56
31 °C 96.0 57.6 9.77 48.0 7.76 38.4 6.28 28.8 5.33
30 °C 96.0 57.6 9.46 48.0 7.53 38.4 6.12 28.8 5.21
29 °C 96.0 57.6 9.17 48.0 7.32 38.4 5.96 28.8 5.10
27 °C 96.0 57.6 8.62 48.0 6.91 38.4 5.66 28.8 4.87
25 °C 96.0 57.6 8.11 48.0 6.53 38.4 5.38 28.8 4.66
23 °C 96.0 57.6 7.63 48.0 6.17 38.4 5.10 28.8 4.44
21 °C 96.0 57.6 7.51 48.0 6.09 38.4 5.06 28.8 4.42
20 °C 96.0 57.6 7.46 48.0 6.06 38.4 5.05 28.8 4.42
19 °C 96.0 57.6 7.41 48.0 6.03 38.4 5.03 28.8 4.41
17 °C 96.0 57.6 7.33 48.0 5.98 38.4 5.00 28.8 4.40
15 °C 96.0 57.6 7.26 48.0 5.93 38.4 4.98 28.8 4.39
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 108.0 108.0 23.8 97.2 19.7 86.4 16.3 75.6 13.5
13.0 11.8 108.0 108.0 24.8 97.2 20.4 86.4 16.8 75.6 13.8
11.0 9.8 108.0 108.0 25.9 97.2 21.3 86.4 17.4 75.6 14.2
9.0 7.9 108.0 108.0 27.2 97.2 22.2 86.4 18.0 75.6 14.6
7.0 6.0 108.0 108.0 28.6 97.2 23.2 86.4 18.8 75.6 15.1
5.0 4.1 104.3 104.3 28.2 93.9 22.9 83.5 18.5 73.0 14.9
3.0 2.2 100.6 100.6 27.7 90.5 22.5 80.5 18.2 70.4 14.7
0.0 -0.7 94.7 94.7 27.1 85.3 22.0 75.8 17.8 66.3 14.3
-3.0 -3.7 88.5 88.5 26.4 79.7 21.4 70.8 17.3 62.0 14.0
-5.0 -5.6 84.5 84.5 25.9 76.0 21.1 67.6 17.0 59.1 13.7
-7.0 -7.6 80.2 80.2 25.5 72.2 20.7 64.1 16.7 56.1 13.5
-10 -10.5 73.8 73.8 24.8 66.4 20.1 59.0 16.3 51.6 13.1
-14.5 -15.0 63.5 63.5 23.8 57.1 19.3 50.8 15.6 44.4 12.6

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 108.0 64.8 11.2 54.0 9.24 43.2 7.65 32.4 6.30
13.0 11.8 108.0 64.8 11.4 54.0 9.35 43.2 7.70 32.4 6.31
11.0 9.8 108.0 64.8 11.6 54.0 9.50 43.2 7.77 32.4 6.34
9.0 7.9 108.0 64.8 11.9 54.0 9.66 43.2 7.86 32.4 6.37
7.0 6.0 108.0 64.8 12.2 54.0 9.85 43.2 7.96 32.4 6.41
5.0 4.1 104.3 62.6 12.0 52.2 9.70 41.7 7.83 31.3 6.31
3.0 2.2 100.6 60.4 11.8 50.3 9.55 40.2 7.71 30.2 6.21
0.0 -0.7 94.7 56.8 11.5 47.4 9.32 37.9 7.53 28.4 6.07
-3.0 -3.7 88.5 53.1 11.3 44.3 9.08 35.4 7.34 26.6 5.91
-5.0 -5.6 84.5 50.7 11.1 42.2 8.93 33.8 7.22 25.3 5.81
-7.0 -7.6 80.2 48.1 10.9 40.1 8.77 32.1 7.09 24.1 5.71
-10 -10.5 73.8 44.3 10.6 36.9 8.55 29.5 6.90 22.1 5.56
-14.5 -15.0 63.5 38.1 10.1 31.7 8.19 25.4 6.62 19.0 5.33
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -48
11 Technical Specifications

MMY-AP3614HT8, AP3614T8 (36HP, 101kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 94.0 94.0 31.2 84.6 25.5 75.2 20.5 65.8 16.2
39 °C 95.5 95.5 30.8 85.9 25.1 76.4 20.2 66.8 16.0
37 °C 98.3 98.3 29.8 88.5 24.3 78.7 19.6 68.8 15.5
35 °C 101.0 101.0 28.9 90.9 23.6 80.8 18.9 70.7 15.0
33 °C 101.0 101.0 26.7 90.9 21.8 80.8 17.6 70.7 14.0
31 °C 101.0 101.0 24.7 90.9 20.2 80.8 16.3 70.7 13.0
30 °C 101.0 101.0 23.8 90.9 19.5 80.8 15.8 70.7 12.6
29 °C 101.0 101.0 23.0 90.9 18.8 80.8 15.2 70.7 12.2
27 °C 101.0 101.0 21.4 90.9 17.5 80.8 14.2 70.7 11.4
25 °C 101.0 101.0 19.9 90.9 16.4 80.8 13.3 70.7 10.7
23 °C 101.0 101.0 18.6 90.9 15.3 80.8 12.4 70.7 10.0
21 °C 101.0 101.0 18.2 90.9 15.0 80.8 12.2 70.7 9.86
20 °C 101.0 101.0 18.0 90.9 14.8 80.8 12.1 70.7 9.78
19 °C 101.0 101.0 17.8 90.9 14.7 80.8 12.0 70.7 9.70
17 °C 101.0 101.0 17.5 90.9 14.5 80.8 11.8 70.7 9.57
15 °C 101.0 101.0 17.3 90.9 14.3 80.8 11.7 70.7 9.46

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 94.0 56.4 12.7 47.0 10.0 37.6 7.97 28.2 6.65
39 °C 95.5 57.3 12.6 47.7 9.85 38.2 7.85 28.6 6.55
37 °C 98.3 59.0 12.2 49.2 9.55 39.3 7.62 29.5 6.35
35 °C 101.0 60.6 11.8 50.5 9.25 40.4 7.38 30.3 6.15
33 °C 101.0 60.6 11.0 50.5 8.70 40.4 7.00 30.3 5.89
31 °C 101.0 60.6 10.3 50.5 8.20 40.4 6.64 30.3 5.64
30 °C 101.0 60.6 10.0 50.5 7.96 40.4 6.47 30.3 5.52
29 °C 101.0 60.6 9.69 50.5 7.74 40.4 6.31 30.3 5.40
27 °C 101.0 60.6 9.11 50.5 7.31 40.4 5.99 30.3 5.16
25 °C 101.0 60.6 8.57 50.5 6.91 40.4 5.69 30.3 4.93
23 °C 101.0 60.6 8.06 50.5 6.52 40.4 5.40 30.3 4.70
21 °C 101.0 60.6 7.94 50.5 6.45 40.4 5.36 30.3 4.68
20 °C 101.0 60.6 7.89 50.5 6.41 40.4 5.34 30.3 4.67
19 °C 101.0 60.6 7.84 50.5 6.38 40.4 5.33 30.3 4.67
17 °C 101.0 60.6 7.75 50.5 6.32 40.4 5.29 30.3 4.65
15 °C 101.0 60.6 7.67 50.5 6.27 40.4 5.27 30.3 4.64
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 113.0 113.0 25.7 101.7 21.3 90.4 17.6 79.1 14.4
13.0 11.8 113.0 113.0 26.7 101.7 22.0 90.4 18.1 79.1 14.8
11.0 9.8 113.0 113.0 28.0 101.7 22.9 90.4 18.7 79.1 15.2
9.0 7.9 113.0 113.0 29.3 101.7 23.9 90.4 19.4 79.1 15.7
7.0 6.0 113.0 113.0 30.8 101.7 25.1 90.4 20.2 79.1 16.3
5.0 4.1 109.2 109.2 30.4 98.2 24.7 87.3 19.9 76.4 16.0
3.0 2.2 105.2 105.2 29.9 94.7 24.3 84.2 19.6 73.7 15.8
0.0 -0.7 99.1 99.1 29.2 89.2 23.7 79.3 19.1 69.4 15.4
-3.0 -3.7 92.6 92.6 28.4 83.4 23.1 74.1 18.7 64.8 15.0
-5.0 -5.6 88.4 88.4 28.0 79.6 22.7 70.7 18.4 61.9 14.8
-7.0 -7.6 83.9 83.9 27.5 75.5 22.3 67.1 18.0 58.7 14.5
-10 -10.5 77.2 77.2 26.8 69.5 21.7 61.7 17.6 54.0 14.1
-14.5 -15.0 66.4 66.4 25.7 59.8 20.8 53.1 16.8 46.5 13.5

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 113.0 67.8 11.9 56.5 9.83 45.2 8.17 33.9 6.85
13.0 11.8 113.0 67.8 12.1 56.5 9.95 45.2 8.22 33.9 6.85
11.0 9.8 113.0 67.8 12.4 56.5 10.1 45.2 8.29 33.9 6.86
9.0 7.9 113.0 67.8 12.7 56.5 10.3 45.2 8.37 33.9 6.88
7.0 6.0 113.0 67.8 13.0 56.5 10.5 45.2 8.47 33.9 6.91
5.0 4.1 109.2 65.5 12.8 54.6 10.3 43.7 8.34 32.7 6.80
3.0 2.2 105.2 63.1 12.7 52.6 10.2 42.1 8.21 31.6 6.70
0.0 -0.7 99.1 59.5 12.3 49.6 9.92 39.7 8.02 29.7 6.54
-3.0 -3.7 92.6 55.6 12.0 46.3 9.67 37.0 7.82 27.8 6.37
-5.0 -5.6 88.4 53.0 11.8 44.2 9.51 35.4 7.69 26.5 6.27
-7.0 -7.6 83.9 50.3 11.6 41.9 9.34 33.6 7.55 25.2 6.16
-10 -10.5 77.2 46.3 11.3 38.6 9.10 30.9 7.35 23.2 6.00
-14.5 -15.0 66.4 39.9 10.9 33.2 8.72 26.6 7.05 19.9 5.75
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -49
11 Technical Specifications

MMY-AP3814HT8, AP3814T8 (38HP, 106.5kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 99.1 99.1 33.1 89.2 27.1 79.3 21.8 69.4 17.2
39 °C 100.7 100.7 32.6 90.6 26.7 80.6 21.5 70.5 17.0
37 °C 103.7 103.7 31.6 93.3 25.9 83.0 20.8 72.6 16.5
35 °C 106.5 106.5 30.7 95.9 25.1 85.2 20.2 74.6 16.0
33 °C 106.5 106.5 28.3 95.9 23.2 85.2 18.7 74.6 14.8
31 °C 106.5 106.5 26.3 95.9 21.5 85.2 17.4 74.6 13.8
30 °C 106.5 106.5 25.3 95.9 20.8 85.2 16.8 74.6 13.3
29 °C 106.5 106.5 24.4 95.9 20.0 85.2 16.2 74.6 12.9
27 °C 106.5 106.5 22.7 95.9 18.7 85.2 15.1 74.6 12.1
25 °C 106.5 106.5 21.2 95.9 17.4 85.2 14.1 74.6 11.3
23 °C 106.5 106.5 19.8 95.9 16.3 85.2 13.2 74.6 10.6
21 °C 106.5 106.5 19.4 95.9 16.0 85.2 13.0 74.6 10.4
20 °C 106.5 106.5 19.2 95.9 15.8 85.2 12.8 74.6 10.3
19 °C 106.5 106.5 19.0 95.9 15.7 85.2 12.7 74.6 10.2
17 °C 106.5 106.5 18.7 95.9 15.4 85.2 12.5 74.6 10.1
15 °C 106.5 106.5 18.4 95.9 15.2 85.2 12.4 74.6 9.97

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 99.1 59.5 13.4 49.6 10.4 39.6 8.28 29.7 6.99
39 °C 100.7 60.4 13.2 50.3 10.3 40.3 8.15 30.2 6.89
37 °C 103.7 62.2 12.8 51.9 9.97 41.5 7.91 31.1 6.68
35 °C 106.5 63.9 12.4 53.3 9.66 42.6 7.66 32.0 6.47
33 °C 106.5 63.9 11.6 53.3 9.07 42.6 7.26 32.0 6.21
31 °C 106.5 63.9 10.9 53.3 8.54 42.6 6.90 32.0 5.95
30 °C 106.5 63.9 10.5 53.3 8.29 42.6 6.72 32.0 5.83
29 °C 106.5 63.9 10.2 53.3 8.05 42.6 6.56 32.0 5.71
27 °C 106.5 63.9 9.56 53.3 7.60 42.6 6.23 32.0 5.47
25 °C 106.5 63.9 8.98 53.3 7.18 42.6 5.92 32.0 5.23
23 °C 106.5 63.9 8.45 53.3 6.78 42.6 5.62 32.0 4.99
21 °C 106.5 63.9 8.31 53.3 6.70 42.6 5.58 32.0 4.98
20 °C 106.5 63.9 8.25 53.3 6.66 42.6 5.56 32.0 4.97
19 °C 106.5 63.9 8.20 53.3 6.63 42.6 5.55 32.0 4.97
17 °C 106.5 63.9 8.10 53.3 6.57 42.6 5.52 32.0 4.96
15 °C 106.5 63.9 8.02 53.3 6.52 42.6 5.49 32.0 4.95
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 119.5 119.5 26.8 107.6 22.1 95.6 18.2 83.7 15.0
13.0 11.8 119.5 119.5 27.9 107.6 22.9 95.6 18.8 83.7 15.3
11.0 9.8 119.5 119.5 29.1 107.6 23.9 95.6 19.5 83.7 15.8
9.0 7.9 119.5 119.5 30.5 107.6 24.9 95.6 20.2 83.7 16.3
7.0 6.0 119.5 119.5 32.1 107.6 26.1 95.6 21.0 83.7 16.9
5.0 4.1 115.4 115.4 31.6 103.9 25.7 92.4 20.7 80.8 16.6
3.0 2.2 111.3 111.3 31.2 100.2 25.3 89.0 20.4 77.9 16.4
0.0 -0.7 104.8 104.8 30.4 94.4 24.7 83.9 19.9 73.4 16.0
-3.0 -3.7 98.0 98.0 29.6 88.2 24.1 78.4 19.4 68.6 15.6
-5.0 -5.6 93.5 93.5 29.2 84.1 23.7 74.8 19.1 65.4 15.3
-7.0 -7.6 88.7 88.7 28.6 79.8 23.3 71.0 18.8 62.1 15.0
-10 -10.5 81.6 81.6 27.9 73.5 22.7 65.3 18.3 57.1 14.7
-14.5 -15.0 70.2 70.2 26.7 63.2 21.7 56.2 17.5 49.2 14.0

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 119.5 71.7 12.3 59.8 10.2 47.8 8.49 35.9 7.19
13.0 11.8 119.5 71.7 12.5 59.8 10.3 47.8 8.54 35.9 7.18
11.0 9.8 119.5 71.7 12.8 59.8 10.5 47.8 8.60 35.9 7.18
9.0 7.9 119.5 71.7 13.1 59.8 10.6 47.8 8.68 35.9 7.19
7.0 6.0 119.5 71.7 13.5 59.8 10.8 47.8 8.78 35.9 7.21
5.0 4.1 115.4 69.3 13.3 57.7 10.7 46.2 8.65 34.6 7.10
3.0 2.2 111.3 66.8 13.1 55.7 10.5 44.5 8.51 33.4 6.99
0.0 -0.7 104.8 62.9 12.8 52.4 10.3 41.9 8.31 31.5 6.83
-3.0 -3.7 98.0 58.8 12.5 49.0 10.0 39.2 8.10 29.4 6.65
-5.0 -5.6 93.5 56.1 12.3 46.7 9.84 37.4 7.97 28.0 6.54
-7.0 -7.6 88.7 53.2 12.0 44.4 9.67 35.5 7.82 26.6 6.43
-10 -10.5 81.6 49.0 11.7 40.8 9.42 32.6 7.62 24.5 6.26
-14.5 -15.0 70.2 42.1 11.2 35.1 9.03 28.1 7.31 21.1 6.00
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -50
11 Technical Specifications

MMY-AP4014HT8, AP4014T8 (40HP, 112kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 104.2 104.2 35.4 93.8 28.9 83.4 23.2 73.0 18.3
39 °C 105.9 105.9 34.9 95.3 28.5 84.7 22.9 74.1 18.0
37 °C 109.1 109.1 33.8 98.2 27.6 87.2 22.2 76.3 17.5
35 °C 112.0 112.0 32.8 100.8 26.8 89.6 21.5 78.4 16.9
33 °C 112.0 112.0 30.3 100.8 24.7 89.6 19.9 78.4 15.7
31 °C 112.0 112.0 28.1 100.8 23.0 89.6 18.5 78.4 14.6
30 °C 112.0 112.0 27.0 100.8 22.1 89.6 17.8 78.4 14.1
29 °C 112.0 112.0 26.1 100.8 21.3 89.6 17.2 78.4 13.7
27 °C 112.0 112.0 24.3 100.8 19.9 89.6 16.1 78.4 12.8
25 °C 112.0 112.0 22.6 100.8 18.6 89.6 15.0 78.4 12.0
23 °C 112.0 112.0 21.1 100.8 17.4 89.6 14.0 78.4 11.2
21 °C 112.0 112.0 20.7 100.8 17.0 89.6 13.8 78.4 11.0
20 °C 112.0 112.0 20.5 100.8 16.8 89.6 13.6 78.4 10.9
19 °C 112.0 112.0 20.3 100.8 16.7 89.6 13.5 78.4 10.8
17 °C 112.0 112.0 19.9 100.8 16.4 89.6 13.3 78.4 10.7
15 °C 112.0 112.0 19.6 100.8 16.15 89.6 13.1 78.4 10.6

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 104.2 62.5 14.2 52.1 11.0 41.7 8.74 31.3 7.39
39 °C 105.9 63.5 14.0 52.9 10.9 42.4 8.6 31.8 7.28
37 °C 109.1 65.4 13.6 54.5 10.5 43.6 8.35 32.7 7.06
35 °C 112.0 67.2 13.2 56.0 10.2 44.8 8.08 33.6 6.84
33 °C 112.0 67.2 12.3 56.0 9.58 44.8 7.67 33.6 6.56
31 °C 112.0 67.2 11.5 56.0 9.02 44.8 7.28 33.6 6.30
30 °C 112.0 67.2 11.1 56.0 8.76 44.8 7.10 33.6 6.16
29 °C 112.0 67.2 10.8 56.0 8.50 44.8 6.92 33.6 6.04
27 °C 112.0 67.2 10.1 56.0 8.03 44.8 6.58 33.6 5.78
25 °C 112.0 67.2 9.49 56.0 7.58 44.8 6.25 33.6 5.53
23 °C 112.0 67.2 8.93 56.0 7.16 44.8 5.94 33.6 5.28
21 °C 112.0 67.2 8.78 56.0 7.07 44.8 5.89 33.6 5.27
20 °C 112.0 67.2 8.72 56.0 7.03 44.8 5.87 33.6 5.26
19 °C 112.0 67.2 8.66 56.0 7.00 44.8 5.86 33.6 5.26
17 °C 112.0 67.2 8.56 56.0 6.93 44.8 5.82 33.6 5.25
15 °C 112.0 67.2 8.47 56.0 6.88 44.8 5.80 33.6 5.24
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 127.0 127.0 29.5 114.3 24.3 101.6 20.0 88.9 16.3
13.0 11.8 127.0 127.0 30.6 114.3 25.2 101.6 20.6 88.9 16.7
11.0 9.8 127.0 127.0 32.0 114.3 26.2 101.6 21.3 88.9 17.3
9.0 7.9 127.0 127.0 33.5 114.3 27.4 101.6 22.2 88.9 17.8
7.0 6.0 127.0 127.0 35.3 114.3 28.7 101.6 23.1 88.9 18.5
5.0 4.1 122.7 122.7 34.8 110.4 28.2 98.1 22.8 85.9 18.2
3.0 2.2 118.3 118.3 34.2 106.5 27.8 94.6 22.4 82.8 17.9
0.0 -0.7 111.4 111.4 33.4 100.3 27.1 89.1 21.9 78.0 17.5
-3.0 -3.7 104.1 104.1 32.5 93.7 26.5 83.3 21.3 72.9 17.0
-5.0 -5.6 99.4 99.4 32.0 89.4 26.0 79.5 21.0 69.5 16.8
-7.0 -7.6 94.3 94.3 31.4 84.8 25.6 75.4 20.6 66.0 16.5
-10 -10.5 86.7 86.7 30.6 78.1 24.9 69.4 20.1 60.7 16.0
-14.5 -15.0 74.6 74.6 29.4 67.2 23.9 59.7 19.2 52.3 15.4

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 127.0 76.2 13.4 63.5 11.0 50.8 9.24 38.1 7.96
13.0 11.8 127.0 76.2 13.6 63.5 11.2 50.8 9.28 38.1 7.93
11.0 9.8 127.0 76.2 13.9 63.5 11.3 50.8 9.34 38.1 7.92
9.0 7.9 127.0 76.2 14.3 63.5 11.5 50.8 9.42 38.1 7.91
7.0 6.0 127.0 76.2 14.7 63.5 11.8 50.8 9.52 38.1 7.92
5.0 4.1 122.7 73.6 14.5 61.3 11.6 49.1 9.38 36.8 7.80
3.0 2.2 118.3 71.0 14.3 59.1 11.4 47.3 9.23 35.5 7.68
0.0 -0.7 111.4 66.8 13.9 55.7 11.1 44.6 9.01 33.4 7.49
-3.0 -3.7 104.1 62.5 13.6 52.0 10.9 41.6 8.78 31.2 7.30
-5.0 -5.6 99.4 59.6 13.4 49.7 10.7 39.7 8.64 29.8 7.18
-7.0 -7.6 94.3 56.6 13.1 47.1 10.5 37.7 8.48 28.3 7.06
-10 -10.5 86.7 52.0 12.8 43.4 10.2 34.7 8.26 26.0 6.87
-14.5 -15.0 74.6 44.8 12.25 37.3 9.79 29.9 7.92 22.4 6.59
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -51
11 Technical Specifications

MMY-AP4214HT8, AP4214T8 (42HP, 118kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 109.8 109.8 37.2 98.8 30.4 87.8 24.4 76.9 19.2
39 °C 111.6 111.6 36.7 100.4 30.0 89.3 24.0 78.1 18.9
37 °C 114.9 114.9 35.6 103.4 29.1 91.9 23.3 80.4 18.3
35 °C 118.0 118.0 34.5 106.2 28.2 94.4 22.6 82.6 17.7
33 °C 118.0 118.0 31.8 106.2 26.0 94.4 20.9 82.6 16.5
31 °C 118.0 118.0 29.5 106.2 24.1 94.4 19.4 82.6 15.3
30 °C 118.0 118.0 28.4 106.2 23.3 94.4 18.7 82.6 14.8
29 °C 118.0 118.0 27.4 106.2 22.4 94.4 18.1 82.6 14.3
27 °C 118.0 118.0 25.5 106.2 20.9 94.4 16.8 82.6 13.4
25 °C 118.0 118.0 23.8 106.2 19.5 94.4 15.7 82.6 12.5
23 °C 118.0 118.0 22.2 106.2 18.2 94.4 14.7 82.6 11.7
21 °C 118.0 118.0 21.7 106.2 17.8 94.4 14.4 82.6 11.5
20 °C 118.0 118.0 21.5 106.2 17.7 94.4 14.3 82.6 11.4
19 °C 118.0 118.0 21.3 106.2 17.5 94.4 14.2 82.6 11.3
17 °C 118.0 118.0 20.9 106.2 17.2 94.4 13.9 82.6 11.1
15 °C 118.0 118.0 20.6 106.2 17.0 94.4 13.7 82.6 11.0

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 109.8 65.9 14.8 54.9 11.4 43.9 9.03 32.9 7.70
39 °C 111.6 66.9 14.6 55.8 11.3 44.6 8.90 33.5 7.59
37 °C 114.9 68.9 14.2 57.5 10.9 46.0 8.63 34.5 7.36
35 °C 118.0 70.8 13.7 59.0 10.6 47.2 8.36 35.4 7.12
33 °C 118.0 70.8 12.8 59.0 9.93 47.2 7.93 35.4 6.84
31 °C 118.0 70.8 12.0 59.0 9.34 47.2 7.53 35.4 6.57
30 °C 118.0 70.8 11.6 59.0 9.07 47.2 7.34 35.4 6.44
29 °C 118.0 70.8 11.2 59.0 8.81 47.2 7.16 35.4 6.30
27 °C 118.0 70.8 10.5 59.0 8.31 47.2 6.81 35.4 6.04
25 °C 118.0 70.8 9.87 59.0 7.85 47.2 6.47 35.4 5.78
23 °C 118.0 70.8 9.28 59.0 7.41 47.2 6.15 35.4 5.53
21 °C 118.0 70.8 9.13 59.0 7.32 47.2 6.10 35.4 5.52
20 °C 118.0 70.8 9.06 59.0 7.28 47.2 6.08 35.4 5.51
19 °C 118.0 70.8 9.00 59.0 7.24 47.2 6.07 35.4 5.51
17 °C 118.0 70.8 8.89 59.0 7.17 47.2 6.04 35.4 5.51
15 °C 118.0 70.8 8.79 59.0 7.12 47.2 6.01 35.4 5.50
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 132.0 132.0 29.6 118.8 24.4 105.6 20.1 92.4 16.5
13.0 11.8 132.0 132.0 30.7 118.8 25.3 105.6 20.7 92.4 16.9
11.0 9.8 132.0 132.0 32.2 118.8 26.3 105.6 21.5 92.4 17.4
9.0 7.9 132.0 132.0 33.7 118.8 27.5 105.6 22.3 92.4 18.0
7.0 6.0 132.0 132.0 35.5 118.8 28.8 105.6 23.2 92.4 18.6
5.0 4.1 127.5 127.5 34.9 114.8 28.4 102.0 22.9 89.3 18.3
3.0 2.2 122.9 122.9 34.4 110.7 27.9 98.4 22.5 86.1 18.1
0.0 -0.7 115.8 115.8 33.6 104.2 27.2 92.6 22.0 81.1 17.6
-3.0 -3.7 108.2 108.2 32.7 97.4 26.6 86.6 21.4 75.7 17.2
-5.0 -5.6 103.3 103.3 32.2 92.9 26.1 82.6 21.1 72.3 16.9
-7.0 -7.6 98.0 98.0 31.6 88.2 25.7 78.4 20.7 68.6 16.6
-10 -10.5 90.1 90.1 30.8 81.1 25.0 72.1 20.2 63.1 16.2
-14.5 -15.0 77.6 77.6 29.5 69.8 24.0 62.1 19.3 54.3 15.5

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 132.0 79.2 13.6 66.0 11.2 52.8 9.37 39.6 7.93
13.0 11.8 132.0 79.2 13.8 66.0 11.4 52.8 9.42 39.6 7.92
11.0 9.8 132.0 79.2 14.2 66.0 11.5 52.8 9.49 39.6 7.92
9.0 7.9 132.0 79.2 14.5 66.0 11.7 52.8 9.58 39.6 7.94
7.0 6.0 132.0 79.2 14.9 66.0 12.0 52.8 9.69 39.6 7.96
5.0 4.1 127.5 76.5 14.7 63.8 11.8 51.0 9.54 38.3 7.84
3.0 2.2 122.9 73.8 14.5 61.5 11.6 49.2 9.39 36.9 7.72
0.0 -0.7 115.8 69.5 14.1 57.9 11.3 46.3 9.17 34.7 7.53
-3.0 -3.7 108.2 64.9 13.8 54.1 11.0 43.3 8.94 32.5 7.34
-5.0 -5.6 103.3 62.0 13.5 51.6 10.9 41.3 8.79 31.0 7.22
-7.0 -7.6 98.0 58.8 13.3 49.0 10.7 39.2 8.63 29.4 7.09
-10 -10.5 90.1 54.1 12.9 45.1 10.4 36.1 8.41 27.0 6.91
-14.5 -15.0 77.6 46.6 12.4 38.8 9.96 31.0 8.06 23.3 6.62
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -52
11 Technical Specifications

MMY-AP4414HT8, AP4414T8 (44HP, 123.5kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 114.9 114.9 39.3 103.4 32.2 91.9 25.8 80.4 20.2
39 °C 116.8 116.8 39.3 105.1 32.2 93.4 25.8 81.7 20.2
37 °C 120.3 120.3 38.1 108.2 31.2 96.2 25.0 84.2 19.6
35 °C 123.5 123.5 37.0 111.2 30.2 98.8 24.2 86.5 18.9
33 °C 123.5 123.5 34.1 111.2 27.9 98.8 22.4 86.5 17.6
31 °C 123.5 123.5 31.6 111.2 25.9 98.8 20.8 86.5 16.3
30 °C 123.5 123.5 30.5 111.2 25.0 98.8 20.0 86.5 15.8
29 °C 123.5 123.5 29.4 111.2 24.1 98.8 19.3 86.5 15.2
27 °C 123.5 123.5 27.4 111.2 22.4 98.8 18.0 86.5 14.2
25 °C 123.5 123.5 25.6 111.2 20.9 98.8 16.8 86.5 13.3
23 °C 123.5 123.5 23.9 111.2 19.6 98.8 15.7 86.5 12.5
21 °C 123.5 123.5 23.3 111.2 19.1 98.8 15.4 86.5 12.2
20 °C 123.5 123.5 23.1 111.2 18.9 98.8 15.3 86.5 12.1
19 °C 123.5 123.5 22.9 111.2 18.8 98.8 15.1 86.5 12.0
17 °C 123.5 123.5 22.5 111.2 18.4 98.8 14.9 86.5 11.8
15 °C 123.5 123.5 22.1 111.2 18.2 98.8 14.7 86.5 11.7

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 114.9 69.0 15.5 57.5 11.9 46.0 9.36 34.5 8.04
39 °C 116.8 70.1 15.5 58.4 11.9 46.7 9.36 35.0 8.04
37 °C 120.3 72.2 15.0 60.1 11.5 48.1 9.08 36.1 7.80
35 °C 123.5 74.1 14.6 61.8 11.2 49.4 8.79 37.1 7.55
33 °C 123.5 74.1 13.6 61.8 10.5 49.4 8.34 37.1 7.26
31 °C 123.5 74.1 12.7 61.8 9.85 49.4 7.92 37.1 6.98
30 °C 123.5 74.1 12.3 61.8 9.55 49.4 7.73 37.1 6.84
29 °C 123.5 74.1 11.9 61.8 9.28 49.4 7.53 37.1 6.71
27 °C 123.5 74.1 11.1 61.8 8.75 49.4 7.17 37.1 6.44
25 °C 123.5 74.1 10.4 61.8 8.26 49.4 6.81 37.1 6.17
23 °C 123.5 74.1 9.81 61.8 7.79 49.4 6.47 37.1 5.90
21 °C 123.5 74.1 9.65 61.8 7.70 49.4 6.43 37.1 5.89
20 °C 123.5 74.1 9.58 61.8 7.65 49.4 6.41 37.1 5.89
19 °C 123.5 74.1 9.51 61.8 7.61 49.4 6.39 37.1 5.89
17 °C 123.5 74.1 9.39 61.8 7.54 49.4 6.36 37.1 5.89
15 °C 123.5 74.1 9.29 61.8 7.48 49.4 6.33 37.1 5.88
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 138.0 138.0 32.4 124.2 26.7 110.4 21.8 96.6 17.7
13.0 11.8 138.0 138.0 33.7 124.2 27.7 110.4 22.5 96.6 18.2
11.0 9.8 138.0 138.0 35.3 124.2 28.9 110.4 23.4 96.6 18.8
9.0 7.9 138.0 138.0 36.9 124.2 30.1 110.4 24.3 96.6 19.5
7.0 6.0 138.0 138.0 38.9 124.2 31.6 110.4 25.4 96.6 20.2
5.0 4.1 133.3 133.3 38.3 120.0 31.1 106.6 25.0 93.3 19.9
3.0 2.2 128.5 128.5 37.7 115.7 30.6 102.8 24.6 90.0 19.6
0.0 -0.7 121.1 121.1 36.8 109.0 29.9 96.9 24.0 84.7 19.1
-3.0 -3.7 113.1 113.1 35.8 101.8 29.1 90.5 23.4 79.2 18.6
-5.0 -5.6 108.0 108.0 35.2 97.2 28.7 86.4 23.0 75.6 18.3
-7.0 -7.6 102.4 102.4 34.6 92.2 28.1 82.0 22.6 71.7 18.0
-10 -10.5 94.2 94.2 33.7 84.8 27.4 75.4 22.0 66.0 17.5
-14.5 -15.0 81.1 81.1 32.3 73.0 26.3 64.9 21.1 56.8 16.8

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 138.0 82.8 14.4 69.0 11.9 55.2 10.0 41.4 8.89
13.0 11.8 138.0 82.8 14.7 69.0 12.0 55.2 10.1 41.4 8.84
11.0 9.8 138.0 82.8 15.1 69.0 12.2 55.2 10.1 41.4 8.79
9.0 7.9 138.0 82.8 15.5 69.0 12.4 55.2 10.2 41.4 8.75
7.0 6.0 138.0 82.8 16.0 69.0 12.7 55.2 10.3 41.4 8.73
5.0 4.1 133.3 80.0 15.7 66.7 12.5 53.3 10.13 40.0 8.60
3.0 2.2 128.5 77.1 15.5 64.3 12.3 51.4 9.97 38.6 8.46
0.0 -0.7 121.1 72.6 15.1 60.5 12.0 48.4 9.74 36.3 8.26
-3.0 -3.7 113.1 67.9 14.7 56.6 11.7 45.2 9.49 33.9 8.05
-5.0 -5.6 108.0 64.8 14.5 54.0 11.5 43.2 9.33 32.4 7.92
-7.0 -7.6 102.4 61.5 14.2 51.2 11.3 41.0 9.17 30.7 7.78
-10 -10.5 94.2 56.5 13.9 47.1 11.0 37.7 8.93 28.3 7.58
-14.5 -15.0 81.1 48.7 13.3 40.6 10.6 32.4 8.56 24.3 7.26
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -53
11 Technical Specifications

MMY-AP4614HT8, AP4614T8 (46HP, 130kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 121.0 121.0 42.0 108.9 34.4 96.8 27.5 84.7 21.5
39 °C 122.9 122.9 41.4 110.6 33.9 98.3 27.1 86.0 21.2
37 °C 126.6 126.6 40.1 113.9 32.9 101.3 26.3 88.6 20.5
35 °C 130.0 130.0 38.9 117.0 31.8 104.0 25.5 91.0 19.9
33 °C 130.0 130.0 35.9 117.0 29.4 104.0 23.6 91.0 18.4
31 °C 130.0 130.0 33.3 117.0 27.3 104.0 21.9 91.0 17.1
30 °C 130.0 130.0 32.1 117.0 26.3 104.0 21.1 91.0 16.5
29 °C 130.0 130.0 31.0 117.0 25.4 104.0 20.3 91.0 16.0
27 °C 130.0 130.0 28.9 117.0 23.6 104.0 19.0 91.0 14.9
25 °C 130.0 130.0 26.9 117.0 22.0 104.0 17.7 91.0 13.9
23 °C 130.0 130.0 25.1 117.0 20.6 104.0 16.5 91.0 13.1
21 °C 130.0 130.0 24.6 117.0 20.1 104.0 16.2 91.0 12.8
20 °C 130.0 130.0 24.3 117.0 19.9 104.0 16.0 91.0 12.7
19 °C 130.0 130.0 24.1 117.0 19.7 104.0 15.9 91.0 12.6
17 °C 130.0 130.0 23.7 117.0 19.4 104.0 15.6 91.0 12.4
15 °C 130.0 130.0 23.3 117.0 19.1 104.0 15.4 91.0 12.2

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 121.0 72.6 16.5 60.5 12.5 48.4 9.84 36.3 8.51
39 °C 122.9 73.8 16.2 61.5 12.3 49.2 9.69 36.9 8.39
37 °C 126.6 76.0 15.7 63.3 12.0 50.6 9.40 38.0 8.13
35 °C 130.0 78.0 15.2 65.0 11.6 52.0 9.10 39.0 7.88
33 °C 130.0 78.0 14.2 65.0 10.9 52.0 8.64 39.0 7.58
31 °C 130.0 78.0 13.2 65.0 10.2 52.0 8.21 39.0 7.30
30 °C 130.0 78.0 12.8 65.0 9.91 52.0 8.00 39.0 7.16
29 °C 130.0 78.0 12.4 65.0 9.62 52.0 7.81 39.0 7.02
27 °C 130.0 78.0 11.6 65.0 9.07 52.0 7.43 39.0 6.74
25 °C 130.0 78.0 10.9 65.0 8.56 52.0 7.06 39.0 6.46
23 °C 130.0 78.0 10.2 65.0 8.08 52.0 6.71 39.0 6.19
21 °C 130.0 78.0 10.0 65.0 7.97 52.0 6.67 39.0 6.18
20 °C 130.0 78.0 9.96 65.0 7.93 52.0 6.65 39.0 6.18
19 °C 130.0 78.0 9.89 65.0 7.89 52.0 6.63 39.0 6.18
17 °C 130.0 78.0 9.76 65.0 7.81 52.0 6.60 39.0 6.18
15 °C 130.0 78.0 9.65 65.0 7.75 52.0 6.57 39.0 6.18
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 145.0 145.0 33.0 130.5 27.2 116.0 22.3 101.5 18.2
13.0 11.8 145.0 145.0 34.3 130.5 28.2 116.0 23.0 101.5 18.7
11.0 9.8 145.0 145.0 35.9 130.5 29.4 116.0 23.9 101.5 19.3
9.0 7.9 145.0 145.0 37.6 130.5 30.7 116.0 24.8 101.5 19.9
7.0 6.0 145.0 145.0 39.6 130.5 32.2 116.0 25.9 101.5 20.7
5.0 4.1 140.1 140.1 39.0 126.1 31.7 112.1 25.5 98.1 20.3
3.0 2.2 135.1 135.1 38.4 121.5 31.2 108.0 25.1 94.5 20.0
0.0 -0.7 127.2 127.2 37.5 114.5 30.4 101.8 24.5 89.0 19.5
-3.0 -3.7 118.9 118.9 36.5 107.0 29.7 95.1 23.9 83.2 19.1
-5.0 -5.6 113.4 113.4 35.9 102.1 29.2 90.8 23.5 79.4 18.7
-7.0 -7.6 107.6 107.6 35.3 96.9 28.7 86.1 23.1 75.3 18.4
-10 -10.5 99.0 99.0 34.4 89.1 27.9 79.2 22.5 69.3 17.9
-14.5 -15.0 85.2 85.2 32.9 76.7 26.8 68.2 21.5 59.7 17.2

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 145.0 87.0 14.9 72.5 12.3 58.0 10.3 43.5 8.99
13.0 11.8 145.0 87.0 15.2 72.5 12.4 58.0 10.4 43.5 8.95
11.0 9.8 145.0 87.0 15.5 72.5 12.6 58.0 10.4 43.5 8.92
9.0 7.9 145.0 87.0 16.0 72.5 12.8 58.0 10.5 43.5 8.91
7.0 6.0 145.0 87.0 16.4 72.5 13.1 58.0 10.6 43.5 8.90
5.0 4.1 140.1 84.0 16.2 70.0 12.9 56.0 10.5 42.0 8.77
3.0 2.2 135.1 81.0 15.9 67.5 12.7 54.0 10.3 40.5 8.63
0.0 -0.7 127.2 76.3 15.5 63.6 12.4 50.9 10.1 38.2 8.42
-3.0 -3.7 118.9 71.3 15.1 59.4 12.1 47.5 9.80 35.7 8.21
-5.0 -5.6 113.4 68.1 14.9 56.7 11.9 45.4 9.64 34.0 8.07
-7.0 -7.6 107.6 64.6 14.6 53.8 11.7 43.1 9.47 32.3 7.93
-10 -10.5 99.0 59.4 14.3 49.5 11.4 39.6 9.22 29.7 7.73
-14.5 -15.0 85.2 51.1 13.7 42.6 10.9 34.1 8.84 25.6 7.41
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -54
11 Technical Specifications

MMY-AP4814HT8, AP4814T8 (48HP, 135kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 125.6 125.6 44.4 113.1 36.4 100.5 29.1 87.9 22.7
39 °C 127.6 127.6 43.7 114.9 35.8 102.1 28.6 89.4 22.4
37 °C 131.5 131.5 42.4 118.3 34.7 105.2 27.8 92.0 21.7
35 °C 135.0 135.0 41.1 121.5 33.6 108.0 26.9 94.5 21.0
33 °C 135.0 135.0 38.0 121.5 31.1 108.0 24.9 94.5 19.5
31 °C 135.0 135.0 35.2 121.5 28.8 108.0 23.1 94.5 18.1
30 °C 135.0 135.0 34.0 121.5 27.8 108.0 22.3 94.5 17.5
29 °C 135.0 135.0 32.7 121.5 26.8 108.0 21.5 94.5 16.9
27 °C 135.0 135.0 30.5 121.5 25.0 108.0 20.0 94.5 15.7
25 °C 135.0 135.0 28.5 121.5 23.3 108.0 18.7 94.5 14.7
23 °C 135.0 135.0 26.6 121.5 21.8 108.0 17.5 94.5 13.8
21 °C 135.0 135.0 26.0 121.5 21.3 108.0 17.1 94.5 13.5
20 °C 135.0 135.0 25.7 121.5 21.1 108.0 16.9 94.5 13.4
19 °C 135.0 135.0 25.5 121.5 20.9 108.0 16.8 94.5 13.3
17 °C 135.0 135.0 25.0 121.5 20.5 108.0 16.5 94.5 13.1
15 °C 135.0 135.0 24.6 121.5 20.2 108.0 16.3 94.5 12.9

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 125.6 75.4 17.4 62.8 13.2 50.3 10.4 37.7 9.06
39 °C 127.6 76.6 17.1 63.8 13.0 51.1 10.3 38.3 8.92
37 °C 131.5 78.9 16.6 65.7 12.6 52.6 9.95 39.4 8.65
35 °C 135.0 81.0 16.1 67.5 12.2 54.0 9.63 40.5 8.38
33 °C 135.0 81.0 15.0 67.5 11.5 54.0 9.14 40.5 8.07
31 °C 135.0 81.0 14.0 67.5 10.8 54.0 8.69 40.5 7.77
30 °C 135.0 81.0 13.5 67.5 10.5 54.0 8.48 40.5 7.62
29 °C 135.0 81.0 13.1 67.5 10.2 54.0 8.27 40.5 7.47
27 °C 135.0 81.0 12.2 67.5 9.59 54.0 7.87 40.5 7.18
25 °C 135.0 81.0 11.5 67.5 9.05 54.0 7.49 40.5 6.89
23 °C 135.0 81.0 10.8 67.5 8.54 54.0 7.12 40.5 6.59
21 °C 135.0 81.0 10.6 67.5 8.43 54.0 7.07 40.5 6.59
20 °C 135.0 81.0 10.5 67.5 8.38 54.0 7.05 40.5 6.59
19 °C 135.0 81.0 10.4 67.5 8.34 54.0 7.03 40.5 6.59
17 °C 135.0 81.0 10.3 67.5 8.26 54.0 7.00 40.5 6.59
15 °C 135.0 81.0 10.2 67.5 8.20 54.0 6.97 40.5 6.59
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 150.0 150.0 35.6 135.0 29.2 120.0 23.8 105.0 19.2
13.0 11.8 150.0 150.0 37.0 135.0 30.3 120.0 24.6 105.0 19.7
11.0 9.8 150.0 150.0 38.7 135.0 31.6 120.0 25.5 105.0 20.4
9.0 7.9 150.0 150.0 40.5 135.0 33.0 120.0 26.6 105.0 21.1
7.0 6.0 150.0 150.0 42.6 135.0 34.6 120.0 27.8 105.0 22.0
5.0 4.1 144.9 144.9 41.9 130.4 34.1 115.9 27.4 101.4 21.7
3.0 2.2 139.7 139.7 41.3 125.7 33.6 111.8 26.9 97.8 21.3
0.0 -0.7 131.6 131.6 40.3 118.4 32.8 105.3 26.3 92.1 20.8
-3.0 -3.7 123.0 123.0 39.3 110.7 32.0 98.4 25.6 86.1 20.3
-5.0 -5.6 117.4 117.4 38.6 105.6 31.4 93.9 25.2 82.1 19.9
-7.0 -7.6 111.3 111.3 38.0 100.2 30.9 89.1 24.8 77.9 19.6
-10 -10.5 102.4 102.4 37.0 92.2 30.1 82.0 24.1 71.7 19.1
-14.5 -15.0 88.2 88.2 35.4 79.3 28.8 70.5 23.1 61.7 18.3

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 150.0 90.0 15.5 75.0 12.8 60.0 10.9 45.0 9.90
13.0 11.8 150.0 90.0 15.9 75.0 12.9 60.0 10.9 45.0 9.80
11.0 9.8 150.0 90.0 16.3 75.0 13.1 60.0 10.9 45.0 9.71
9.0 7.9 150.0 90.0 16.7 75.0 13.3 60.0 11.0 45.0 9.64
7.0 6.0 150.0 90.0 17.3 75.0 13.6 60.0 11.1 45.0 9.58
5.0 4.1 144.9 86.9 17.0 72.5 13.4 58.0 10.9 43.5 9.44
3.0 2.2 139.7 83.8 16.7 69.9 13.2 55.9 10.7 41.9 9.29
0.0 -0.7 131.6 79.0 16.3 65.8 12.9 52.6 10.5 39.5 9.07
-3.0 -3.7 123.0 73.8 15.9 61.5 12.6 49.2 10.2 36.9 8.84
-5.0 -5.6 117.4 70.4 15.7 58.7 12.4 46.9 10.0 35.2 8.70
-7.0 -7.6 111.3 66.8 15.4 55.7 12.1 44.5 9.87 33.4 8.54
-10 -10.5 102.4 61.5 15.0 51.2 11.8 41.0 9.61 30.7 8.32
-14.5 -15.0 88.2 52.9 14.4 44.1 11.3 35.3 9.21 26.4 7.97
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -55
11 Technical Specifications

• High efficiency model


MMY-AP1624HT8, AP1624T8 (16HP, 45kW system)
Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 41.9 41.9 11.8 37.7 9.67 33.5 7.84 29.3 6.27
39 °C 42.5 42.5 11.6 38.3 9.53 34.0 7.72 29.8 6.17
37 °C 43.8 43.8 11.2 39.4 9.24 35.1 7.49 30.7 5.99
35 °C 45.0 45.0 10.9 40.5 8.95 36.0 7.25 31.5 5.80
33 °C 45.0 45.0 10.1 40.5 8.29 36.0 6.73 31.5 5.40
31 °C 45.0 45.0 9.34 40.5 7.70 36.0 6.27 31.5 5.04
30 °C 45.0 45.0 9.00 40.5 7.43 36.0 6.1 31.5 4.87
29 °C 45.0 45.0 8.69 40.5 7.17 36.0 5.85 31.5 4.72
27 °C 45.0 45.0 8.10 40.5 6.69 36.0 5.47 31.5 4.42
25 °C 45.0 45.0 7.56 40.5 6.26 36.0 5.12 31.5 4.15
23 °C 45.0 45.0 7.07 40.5 5.85 36.0 4.80 31.5 3.89
21 °C 45.0 45.0 6.92 40.5 5.74 36.0 4.71 31.5 3.83
20 °C 45.0 45.0 6.85 40.5 5.68 36.0 4.66 31.5 3.80
19 °C 45.0 45.0 6.79 40.5 5.63 36.0 4.63 31.5 3.77
17 °C 45.0 45.0 6.68 40.5 5.54 36.0 4.56 31.5 3.72
15 °C 45.0 45.0 6.58 40.5 5.47 36.0 4.50 31.5 3.68

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 41.9 25.1 4.96 20.9 3.91 16.8 3.12 12.6 2.59
39 °C 42.5 25.5 4.88 21.3 3.85 17.0 3.07 12.8 2.55
37 °C 43.8 26.3 4.73 21.9 3.73 17.5 2.98 13.1 2.48
35 °C 45.0 27.0 4.59 22.5 3.61 18.0 2.89 13.5 2.40
33 °C 45.0 27.0 4.29 22.5 3.40 18.0 2.74 13.5 2.30
31 °C 45.0 27.0 4.02 22.5 3.21 18.0 2.60 13.5 2.20
30 °C 45.0 27.0 3.90 22.5 3.11 18.0 2.53 13.5 2.15
29 °C 45.0 27.0 3.78 22.5 3.03 18.0 2.47 13.5 2.10
27 °C 45.0 27.0 3.55 22.5 2.86 18.0 2.34 13.5 2.01
25 °C 45.0 27.0 3.34 22.5 2.70 18.0 2.23 13.5 1.92
23 °C 45.0 27.0 3.15 22.5 2.55 18.0 2.11 13.5 1.83
21 °C 45.0 27.0 3.10 22.5 2.52 18.0 2.10 13.5 1.82
20 °C 45.0 27.0 3.08 22.5 2.51 18.0 2.09 13.5 1.82
19 °C 45.0 27.0 3.06 22.5 2.50 18.0 2.08 13.5 1.81
17 °C 45.0 27.0 3.02 22.5 2.47 18.0 2.07 13.5 1.81
15 °C 45.0 27.0 2.99 22.5 2.46 18.0 2.06 13.5 1.80
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 50.0 50.0 9.20 45.0 7.64 40.0 6.35 35.0 5.29
13.0 11.8 50.0 50.0 9.57 45.0 7.90 40.0 6.53 35.0 5.41
11.0 9.8 50.0 50.0 10.0 45.0 8.21 40.0 6.74 35.0 5.55
9.0 7.9 50.0 50.0 10.5 45.0 8.56 40.0 6.98 35.0 5.71
7.0 6.0 50.0 50.0 11.1 45.0 8.96 40.0 7.26 35.0 5.89
5.0 4.1 48.3 48.3 10.9 43.5 8.82 38.6 7.15 33.8 5.80
3.0 2.2 46.6 46.6 10.7 41.9 8.69 37.3 7.04 32.6 5.71
0.0 -0.7 43.9 43.9 10.5 39.5 8.48 35.1 6.87 30.7 5.58
-3.0 -3.7 41.0 41.0 10.2 36.9 8.26 32.8 6.70 28.7 5.43
-5.0 -5.6 39.1 39.1 10.0 35.2 8.13 31.3 6.58 27.4 5.34
-7.0 -7.6 37.1 37.1 9.85 33.4 7.98 29.7 6.47 26.0 5.25
-10 -10.5 34.1 34.1 9.60 30.7 7.78 27.3 6.30 23.9 5.11
-14.5 -15.0 29.4 29.4 9.20 26.4 7.45 23.5 6.04 20.6 4.90

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 50.0 30.0 4.41 25.0 3.67 20.0 3.01 15.0 2.39
13.0 11.8 50.0 30.0 4.49 25.0 3.71 20.0 3.04 15.0 2.41
11.0 9.8 50.0 30.0 4.58 25.0 3.77 20.0 3.07 15.0 2.43
9.0 7.9 50.0 30.0 4.68 25.0 3.83 20.0 3.11 15.0 2.45
7.0 6.0 50.0 30.0 4.79 25.0 3.90 20.0 3.15 15.0 2.48
5.0 4.1 48.3 29.0 4.72 24.2 3.84 19.3 3.10 14.5 2.44
3.0 2.2 46.6 27.9 4.65 23.3 3.78 18.6 3.06 14.0 2.41
0.0 -0.7 43.9 26.3 4.54 21.9 3.69 17.5 2.98 13.2 2.35
-3.0 -3.7 41.0 24.6 4.42 20.5 3.60 16.4 2.91 12.3 2.29
-5.0 -5.6 39.1 23.5 4.35 19.6 3.54 15.6 2.86 11.7 2.25
-7.0 -7.6 37.1 22.3 4.27 18.6 3.48 14.8 2.81 11.1 2.21
-10 -10.5 34.1 20.5 4.16 17.1 3.39 13.7 2.74 10.2 2.15
-14.5 -15.0 29.4 17.6 3.99 14.7 3.25 11.8 2.62 8.82 2.06
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -56
11 Technical Specifications

MMY-AP2424HT8, AP2424T8 (24HP, 68kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 63.3 63.3 17.9 57.0 14.7 50.6 11.9 44.3 9.54
39 °C 64.3 64.3 17.6 57.9 14.5 51.4 11.8 45.0 9.40
37 °C 66.2 66.2 17.1 59.6 14.1 53.0 11.4 46.4 9.11
35 °C 68.0 68.0 16.6 61.2 13.6 54.4 11.0 47.6 8.83
33 °C 68.0 68.0 15.3 61.2 12.6 54.4 10.2 47.6 8.22
31 °C 68.0 68.0 14.2 61.2 11.7 54.4 9.54 47.6 7.67
30 °C 68.0 68.0 13.7 61.2 11.3 54.4 9.22 47.6 7.42
29 °C 68.0 68.0 13.2 61.2 10.9 54.4 8.90 47.6 7.18
27 °C 68.0 68.0 12.3 61.2 10.2 54.4 8.33 47.6 6.73
25 °C 68.0 68.0 11.5 61.2 9.53 54.4 7.80 47.6 6.32
23 °C 68.0 68.0 10.8 61.2 8.91 54.4 7.30 47.6 5.93
21 °C 68.0 68.0 10.5 61.2 8.73 54.4 7.16 47.6 5.83
20 °C 68.0 68.0 10.4 61.2 8.65 54.4 7.10 47.6 5.78
19 °C 68.0 68.0 10.3 61.2 8.58 54.4 7.04 47.6 5.74
17 °C 68.0 68.0 10.2 61.2 8.44 54.4 6.94 47.6 5.66
15 °C 68.0 68.0 10.0 61.2 8.33 54.4 6.85 47.6 5.60

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 63.3 38.0 7.54 31.6 5.95 25.3 4.75 19.0 3.95
39 °C 64.3 38.6 7.43 32.1 5.86 25.7 4.68 19.3 3.89
37 °C 66.2 39.7 7.21 33.1 5.68 26.5 4.54 19.9 3.77
35 °C 68.0 40.8 6.98 34.0 5.50 27.2 4.39 20.4 3.65
33 °C 68.0 40.8 6.53 34.0 5.18 27.2 4.17 20.4 3.49
31 °C 68.0 40.8 6.12 34.0 4.88 27.2 3.96 20.4 3.34
30 °C 68.0 40.8 5.93 34.0 4.74 27.2 3.85 20.4 3.27
29 °C 68.0 40.8 5.75 34.0 4.61 27.2 3.76 20.4 3.20
27 °C 68.0 40.8 5.41 34.0 4.35 27.2 3.57 20.4 3.06
25 °C 68.0 40.8 5.09 34.0 4.11 27.2 3.39 20.4 2.92
23 °C 68.0 40.8 4.79 34.0 3.89 27.2 3.22 20.4 2.78
21 °C 68.0 40.8 4.72 34.0 3.84 27.2 3.19 20.4 2.77
20 °C 68.0 40.8 4.69 34.0 3.82 27.2 3.18 20.4 2.77
19 °C 68.0 40.8 4.66 34.0 3.80 27.2 3.17 20.4 2.76
17 °C 68.0 40.8 4.60 34.0 3.77 27.2 3.15 20.4 2.75
15 °C 68.0 40.8 4.56 34.0 3.74 27.2 3.13 20.4 2.75
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 76.5 76.5 14.3 68.9 11.9 61.2 9.87 53.6 8.22
13.0 11.8 76.5 76.5 14.9 68.9 12.3 61.2 10.1 53.6 8.40
11.0 9.8 76.5 76.5 15.5 68.9 12.8 61.2 10.5 53.6 8.62
9.0 7.9 76.5 76.5 16.3 68.9 13.3 61.2 10.8 53.6 8.87
7.0 6.0 76.5 76.5 17.2 68.9 13.9 61.2 11.3 53.6 9.15
5.0 4.1 73.9 73.9 16.9 66.5 13.7 59.1 11.1 51.7 9.01
3.0 2.2 71.3 71.3 16.7 64.1 13.5 57.0 10.9 49.9 8.87
0.0 -0.7 67.1 67.1 16.3 60.4 13.2 53.7 10.7 47.0 8.66
-3.0 -3.7 62.7 62.7 15.8 56.4 12.8 50.2 10.4 43.9 8.44
-5.0 -5.6 59.8 59.8 15.6 53.9 12.6 47.9 10.2 41.9 8.30
-7.0 -7.6 56.8 56.8 15.3 51.1 12.4 45.4 10.0 39.8 8.16
-10 -10.5 52.2 52.2 14.9 47.0 12.1 41.8 9.79 36.6 7.94
-14.5 -15.0 45.0 45.0 14.3 40.5 11.6 36.0 9.38 31.5 7.61

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 76.5 45.9 6.85 38.3 5.70 30.6 4.68 23.0 3.72
13.0 11.8 76.5 45.9 6.97 38.3 5.77 30.6 4.72 23.0 3.74
11.0 9.8 76.5 45.9 7.11 38.3 5.85 30.6 4.77 23.0 3.78
9.0 7.9 76.5 45.9 7.27 38.3 5.95 30.6 4.83 23.0 3.81
7.0 6.0 76.5 45.9 7.45 38.3 6.06 30.6 4.90 23.0 3.85
5.0 4.1 73.9 44.3 7.33 37.0 5.97 29.6 4.82 22.2 3.79
3.0 2.2 71.3 42.8 7.22 35.6 5.88 28.5 4.75 21.4 3.74
0.0 -0.7 67.1 40.3 7.05 33.6 5.74 26.8 4.63 20.1 3.65
-3.0 -3.7 62.7 37.6 6.87 31.4 5.59 25.1 4.52 18.8 3.55
-5.0 -5.6 59.8 35.9 6.75 29.9 5.50 23.9 4.44 18.0 3.50
-7.0 -7.6 56.8 34.1 6.64 28.4 5.40 22.7 4.36 17.0 3.43
-10 -10.5 52.2 31.3 6.46 26.1 5.26 20.9 4.25 15.7 3.34
-14.5 -15.0 45.0 27.0 6.19 22.5 5.04 18.0 4.07 13.5 3.21
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -57
11 Technical Specifications

MMY-AP2624HT8, AP2624T8 (26HP, 73kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 67.9 67.9 19.8 61.1 16.3 54.3 13.2 47.6 10.5
39 °C 69.0 69.0 19.5 62.1 16.0 55.2 13.0 48.3 10.4
37 °C 71.1 71.1 18.9 64.0 15.5 56.9 12.6 49.8 10.1
35 °C 73.0 73.0 18.3 65.7 15.0 58.4 12.2 51.1 9.75
33 °C 73.0 73.0 16.9 65.7 13.9 58.4 11.3 51.1 9.08
31 °C 73.0 73.0 15.7 65.7 12.9 58.4 10.54 51.1 8.47
30 °C 73.0 73.0 15.1 65.7 12.5 58.4 10.2 51.1 8.20
29 °C 73.0 73.0 14.6 65.7 12.1 58.4 9.83 51.1 7.93
27 °C 73.0 73.0 13.6 65.7 11.3 58.4 9.20 51.1 7.43
25 °C 73.0 73.0 12.7 65.7 10.5 58.4 8.61 51.1 6.97
23 °C 73.0 73.0 11.9 65.7 9.84 58.4 8.07 51.1 6.55
21 °C 73.0 73.0 11.6 65.7 9.64 58.4 7.91 51.1 6.43
20 °C 73.0 73.0 11.5 65.7 9.55 58.4 7.84 51.1 6.38
19 °C 73.0 73.0 11.4 65.7 9.47 58.4 7.78 51.1 6.34
17 °C 73.0 73.0 11.2 65.7 9.32 58.4 7.67 51.1 6.25
15 °C 73.0 73.0 11.1 65.7 9.20 58.4 7.57 51.1 6.18

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 67.9 40.8 8.33 34.0 6.57 27.2 5.24 20.4 4.36
39 °C 69.0 41.4 8.21 34.5 6.47 27.6 5.17 20.7 4.29
37 °C 71.1 42.7 7.96 35.5 6.28 28.4 5.01 21.3 4.16
35 °C 73.0 43.8 7.71 36.5 6.08 29.2 4.85 21.9 4.03
33 °C 73.0 43.8 7.21 36.5 5.72 29.2 4.60 21.9 3.86
31 °C 73.0 43.8 6.76 36.5 5.39 29.2 4.37 21.9 3.69
30 °C 73.0 43.8 6.55 36.5 5.24 29.2 4.26 21.9 3.61
29 °C 73.0 43.8 6.35 36.5 5.09 29.2 4.15 21.9 3.53
27 °C 73.0 43.8 5.97 36.5 4.81 29.2 3.94 21.9 3.38
25 °C 73.0 43.8 5.62 36.5 4.54 29.2 3.74 21.9 3.22
23 °C 73.0 43.8 5.29 36.5 4.29 29.2 3.55 21.9 3.07
21 °C 73.0 43.8 5.21 36.5 4.24 29.2 3.52 21.9 3.06
20 °C 73.0 43.8 5.17 36.5 4.22 29.2 3.51 21.9 3.06
19 °C 73.0 43.8 5.14 36.5 4.20 29.2 3.50 21.9 3.05
17 °C 73.0 43.8 5.08 36.5 4.16 29.2 3.48 21.9 3.04
15 °C 73.0 43.8 5.03 36.5 4.13 29.2 3.46 21.9 3.03
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 81.5 81.5 15.4 73.4 12.8 65.2 10.7 57.1 8.88
13.0 11.8 81.5 81.5 16.1 73.4 13.3 65.2 11.0 57.1 9.08
11.0 9.8 81.5 81.5 16.8 73.4 13.8 65.2 11.3 57.1 9.31
9.0 7.9 81.5 81.5 17.6 73.4 14.4 65.2 11.7 57.1 9.58
7.0 6.0 81.5 81.5 18.6 73.4 15.0 65.2 12.2 57.1 9.89
5.0 4.1 78.7 78.7 18.3 70.9 14.8 63.0 12.0 55.1 9.74
3.0 2.2 75.9 75.9 18.0 68.3 14.6 60.7 11.8 53.1 9.59
0.0 -0.7 71.5 71.5 17.6 64.3 14.2 57.2 11.5 50.0 9.36
-3.0 -3.7 66.8 66.8 17.1 60.1 13.9 53.4 11.2 46.8 9.12
-5.0 -5.6 63.8 63.8 16.8 57.4 13.6 51.0 11.1 44.6 8.97
-7.0 -7.6 60.5 60.5 16.5 54.4 13.4 48.4 10.9 42.3 8.81
-10 -10.5 55.7 55.7 16.1 50.1 13.1 44.5 10.6 39.0 8.58
-14.5 -15.0 47.9 47.9 15.4 43.1 12.5 38.3 10.1 33.5 8.23

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 81.5 48.9 7.41 40.8 6.16 32.6 5.05 24.5 4.02
13.0 11.8 81.5 48.9 7.53 40.8 6.23 32.6 5.10 24.5 4.04
11.0 9.8 81.5 48.9 7.68 40.8 6.33 32.6 5.16 24.5 4.08
9.0 7.9 81.5 48.9 7.85 40.8 6.43 32.6 5.22 24.5 4.12
7.0 6.0 81.5 48.9 8.04 40.8 6.55 32.6 5.29 24.5 4.16
5.0 4.1 78.7 47.2 7.92 39.4 6.45 31.5 5.21 23.6 4.10
3.0 2.2 75.9 45.5 7.80 38.0 6.35 30.4 5.13 22.8 4.04
0.0 -0.7 71.5 42.9 7.61 35.7 6.20 28.6 5.01 21.4 3.94
-3.0 -3.7 66.8 40.1 7.42 33.4 6.04 26.7 4.88 20.0 3.84
-5.0 -5.6 63.8 38.3 7.30 31.9 5.94 25.5 4.80 19.1 3.78
-7.0 -7.6 60.5 36.3 7.17 30.2 5.84 24.2 4.71 18.1 3.71
-10 -10.5 55.7 33.4 6.98 27.8 5.68 22.3 4.59 16.7 3.61
-14.5 -15.0 47.9 28.7 6.69 24.0 5.45 19.2 4.40 14.4 3.46
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -58
11 Technical Specifications

MMY-AP2824HT8, AP2824T8 (28HP, 78.5kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 73.1 73.1 21.9 65.7 18.0 58.4 14.6 51.1 11.7
39 °C 74.2 74.2 21.6 66.8 17.7 59.4 14.4 52.0 11.5
37 °C 76.4 76.4 20.9 68.8 17.2 61.2 13.9 53.5 11.1
35 °C 78.5 78.5 20.3 70.7 16.7 62.8 13.5 55.0 10.8
33 °C 78.5 78.5 18.7 70.7 15.4 62.8 12.5 55.0 10.0
31 °C 78.5 78.5 17.4 70.7 14.3 62.8 11.7 55.0 9.38
30 °C 78.5 78.5 16.8 70.7 13.8 62.8 11.3 55.0 9.07
29 °C 78.5 78.5 16.2 70.7 13.4 62.8 10.9 55.0 8.78
27 °C 78.5 78.5 15.1 70.7 12.5 62.8 10.2 55.0 8.23
25 °C 78.5 78.5 14.1 70.7 11.6 62.8 9.53 55.0 7.72
23 °C 78.5 78.5 13.2 70.7 10.9 62.8 8.93 55.0 7.25
21 °C 78.5 78.5 12.9 70.7 10.7 62.8 8.76 55.0 7.12
20 °C 78.5 78.5 12.7 70.7 10.6 62.8 8.68 55.0 7.07
19 °C 78.5 78.5 12.6 70.7 10.5 62.8 8.61 55.0 7.01
17 °C 78.5 78.5 12.4 70.7 10.3 62.8 8.49 55.0 6.92
15 °C 78.5 78.5 12.2 70.7 10.2 62.8 8.38 55.0 6.84

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 73.1 43.8 9.22 36.5 7.27 29.2 5.81 21.9 4.83
39 °C 74.2 44.5 9.09 37.1 7.16 29.7 5.72 22.3 4.75
37 °C 76.4 45.9 8.81 38.2 6.95 30.6 5.55 22.9 4.61
35 °C 78.5 47.1 8.54 39.3 6.73 31.4 5.37 23.6 4.46
33 °C 78.5 47.1 7.98 39.3 6.33 31.4 5.09 23.6 4.27
31 °C 78.5 47.1 7.48 39.3 5.97 31.4 4.84 23.6 4.09
30 °C 78.5 47.1 7.25 39.3 5.80 31.4 4.71 23.6 4.00
29 °C 78.5 47.1 7.03 39.3 5.63 31.4 4.59 23.6 3.91
27 °C 78.5 47.1 6.61 39.3 5.32 31.4 4.36 23.6 3.74
25 °C 78.5 47.1 6.22 39.3 5.03 31.4 4.14 23.6 3.57
23 °C 78.5 47.1 5.86 39.3 4.75 31.4 3.93 23.6 3.40
21 °C 78.5 47.1 5.77 39.3 4.69 31.4 3.90 23.6 3.39
20 °C 78.5 47.1 5.73 39.3 4.67 31.4 3.89 23.6 3.38
19 °C 78.5 47.1 5.69 39.3 4.65 31.4 3.87 23.6 3.38
17 °C 78.5 47.1 5.63 39.3 4.60 31.4 3.85 23.6 3.37
15 °C 78.5 47.1 5.57 39.3 4.57 31.4 3.83 23.6 3.36
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 88.0 88.0 17.1 79.2 14.2 70.4 11.8 61.6 9.82
13.0 11.8 88.0 88.0 17.8 79.2 14.7 70.4 12.1 61.6 10.0
11.0 9.8 88.0 88.0 18.6 79.2 15.2 70.4 12.5 61.6 10.3
9.0 7.9 88.0 88.0 19.5 79.2 15.9 70.4 13.0 61.6 10.6
7.0 6.0 88.0 88.0 20.5 79.2 16.6 70.4 13.5 61.6 10.9
5.0 4.1 85.0 85.0 20.2 76.5 16.4 68.0 13.3 59.5 10.8
3.0 2.2 82.0 82.0 19.9 73.8 16.1 65.6 13.1 57.4 10.6
0.0 -0.7 77.2 77.2 19.4 69.5 15.7 61.8 12.8 54.0 10.3
-3.0 -3.7 72.1 72.1 18.9 64.9 15.3 57.7 12.4 50.5 10.1
-5.0 -5.6 68.8 68.8 18.6 62.0 15.1 55.1 12.2 48.2 9.92
-7.0 -7.6 65.3 65.3 18.3 58.8 14.8 52.3 12.0 45.7 9.75
-10 -10.5 60.1 60.1 17.8 54.1 14.4 48.1 11.7 42.1 9.49
-14.5 -15.0 51.7 51.7 17.1 46.6 13.8 41.4 11.2 36.2 9.10

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 88.0 52.8 8.19 44.0 6.81 35.2 5.59 26.4 4.44
13.0 11.8 88.0 52.8 8.33 44.0 6.89 35.2 5.64 26.4 4.47
11.0 9.8 88.0 52.8 8.50 44.0 7.00 35.2 5.70 26.4 4.51
9.0 7.9 88.0 52.8 8.68 44.0 7.11 35.2 5.77 26.4 4.56
7.0 6.0 88.0 52.8 8.90 44.0 7.24 35.2 5.85 26.4 4.60
5.0 4.1 85.0 51.0 8.76 42.5 7.13 34.0 5.76 25.5 4.53
3.0 2.2 82.0 49.2 8.63 41.0 7.02 32.8 5.67 24.6 4.46
0.0 -0.7 77.2 46.3 8.42 38.6 6.85 30.9 5.54 23.2 4.36
-3.0 -3.7 72.1 43.3 8.21 36.1 6.68 28.9 5.40 21.6 4.25
-5.0 -5.6 68.8 41.3 8.07 34.4 6.57 27.5 5.31 20.7 4.18
-7.0 -7.6 65.3 39.2 7.93 32.7 6.45 26.1 5.21 19.6 4.10
-10 -10.5 60.1 36.1 7.72 30.0 6.29 24.0 5.08 18.0 4.00
-14.5 -15.0 51.7 31.0 7.40 25.9 6.03 20.7 4.87 15.5 3.83
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -59
11 Technical Specifications

MMY-AP3024HT8, AP3024T8 (30HP, 85kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 79.1 79.1 24.6 71.2 20.2 63.3 16.4 55.4 13.1
39 °C 80.4 80.4 24.2 72.3 19.9 64.3 16.1 56.3 12.9
37 °C 82.8 82.8 23.5 74.5 19.3 66.2 15.6 57.9 12.5
35 °C 85.0 85.0 22.8 76.5 18.7 68.0 15.1 59.5 12.1
33 °C 85.0 85.0 21.0 76.5 17.3 68.0 14.1 59.5 11.3
31 °C 85.0 85.0 19.5 76.5 16.1 68.0 13.1 59.5 10.5
30 °C 85.0 85.0 18.8 76.5 15.5 68.0 12.6 59.5 10.2
29 °C 85.0 85.0 18.1 76.5 15.0 68.0 12.2 59.5 9.85
27 °C 85.0 85.0 16.9 76.5 14.0 68.0 11.4 59.5 9.24
25 °C 85.0 85.0 15.8 76.5 13.1 68.0 10.7 59.5 8.67
23 °C 85.0 85.0 14.8 76.5 12.2 68.0 10.0 59.5 8.14
21 °C 85.0 85.0 14.4 76.5 12.0 68.0 9.83 59.5 7.99
20 °C 85.0 85.0 14.3 76.5 11.9 68.0 9.74 59.5 7.93
19 °C 85.0 85.0 14.2 76.5 11.8 68.0 9.67 59.5 7.87
17 °C 85.0 85.0 13.9 76.5 11.6 68.0 9.52 59.5 7.77
15 °C 85.0 85.0 13.7 76.5 11.4 68.0 9.40 59.5 7.68

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 79.1 47.5 10.4 39.5 8.16 31.6 6.52 23.7 5.42
39 °C 80.4 48.2 10.2 40.2 8.04 32.1 6.42 24.1 5.34
37 °C 82.8 49.7 9.89 41.4 7.80 33.1 6.23 24.8 5.17
35 °C 85.0 51.0 9.58 42.5 7.55 34.0 6.03 25.5 5.01
33 °C 85.0 51.0 8.96 42.5 7.10 34.0 5.72 25.5 4.79
31 °C 85.0 51.0 8.40 42.5 6.70 34.0 5.43 25.5 4.59
30 °C 85.0 51.0 8.14 42.5 6.51 34.0 5.29 25.5 4.49
29 °C 85.0 51.0 7.89 42.5 6.32 34.0 5.15 25.5 4.39
27 °C 85.0 51.0 7.42 42.5 5.97 34.0 4.90 25.5 4.19
25 °C 85.0 51.0 6.98 42.5 5.64 34.0 4.65 25.5 4.00
23 °C 85.0 51.0 6.57 42.5 5.33 34.0 4.41 25.5 3.82
21 °C 85.0 51.0 6.47 42.5 5.27 34.0 4.38 25.5 3.80
20 °C 85.0 51.0 6.43 42.5 5.24 34.0 4.36 25.5 3.80
19 °C 85.0 51.0 6.39 42.5 5.21 34.0 4.35 25.5 3.79
17 °C 85.0 51.0 6.32 42.5 5.17 34.0 4.32 25.5 3.78
15 °C 85.0 51.0 6.26 42.5 5.13 34.0 4.30 25.5 3.77
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 95.0 95.0 18.9 85.5 15.7 76.0 13.0 66.5 10.9
13.0 11.8 95.0 95.0 19.6 85.5 16.2 76.0 13.4 66.5 11.1
11.0 9.8 95.0 95.0 20.5 85.5 16.9 76.0 13.8 66.5 11.4
9.0 7.9 95.0 95.0 21.5 85.5 17.6 76.0 14.3 66.5 11.7
7.0 6.0 95.0 95.0 22.7 85.5 18.4 76.0 14.9 66.5 12.1
5.0 4.1 91.8 91.8 22.4 82.6 18.1 73.4 14.7 64.2 11.9
3.0 2.2 88.5 88.5 22.0 79.6 17.8 70.8 14.5 61.9 11.7
0.0 -0.7 83.3 83.3 21.5 75.0 17.4 66.7 14.1 58.3 11.4
-3.0 -3.7 77.9 77.9 20.9 70.1 17.0 62.3 13.7 54.5 11.2
-5.0 -5.6 74.3 74.3 20.6 66.9 16.7 59.5 13.5 52.0 11.0
-7.0 -7.6 70.5 70.5 20.2 63.5 16.4 56.4 13.3 49.4 10.8
-10 -10.5 64.9 64.9 19.7 58.4 16.0 51.9 12.9 45.4 10.5
-14.5 -15.0 55.8 55.8 18.9 50.3 15.3 44.7 12.4 39.1 10.1

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 95.0 57.0 9.06 47.5 7.53 38.0 6.18 28.5 4.91
13.0 11.8 95.0 57.0 9.21 47.5 7.63 38.0 6.24 28.5 4.95
11.0 9.8 95.0 57.0 9.40 47.5 7.74 38.0 6.31 28.5 4.99
9.0 7.9 95.0 57.0 9.60 47.5 7.87 38.0 6.38 28.5 5.04
7.0 6.0 95.0 57.0 9.84 47.5 8.01 38.0 6.47 28.5 5.09
5.0 4.1 91.8 55.1 9.69 45.9 7.89 36.7 6.37 27.5 5.02
3.0 2.2 88.5 53.1 9.54 44.2 7.77 35.4 6.28 26.5 4.94
0.0 -0.7 83.3 50.0 9.31 41.7 7.58 33.3 6.13 25.0 4.82
-3.0 -3.7 77.9 46.7 9.08 38.9 7.39 31.1 5.97 23.4 4.70
-5.0 -5.6 74.3 44.6 8.93 37.2 7.27 29.7 5.87 22.3 4.62
-7.0 -7.6 70.5 42.3 8.77 35.3 7.14 28.2 5.77 21.2 4.54
-10 -10.5 64.9 38.9 8.54 32.4 6.95 26.0 5.62 19.5 4.42
-14.5 -15.0 55.8 33.5 8.19 27.9 6.67 22.3 5.38 16.8 4.24
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -60
11 Technical Specifications

MMY-AP3224HT8, AP3224T8 (32HP, 90kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 83.8 83.8 23.5 75.4 19.3 67.0 15.7 58.6 12.5
39 °C 85.1 85.1 23.2 76.6 19.1 68.1 15.4 59.6 12.4
37 °C 87.6 87.6 22.5 78.9 18.5 70.1 15.0 61.3 12.0
35 °C 90.0 90.0 21.8 81.0 17.9 72.0 14.5 63.0 11.6
33 °C 90.0 90.0 20.1 81.0 16.6 72.0 13.5 63.0 10.8
31 °C 90.0 90.0 18.7 81.0 15.4 72.0 12.5 63.0 10.1
30 °C 90.0 90.0 18.0 81.0 14.9 72.0 12.1 63.0 9.75
29 °C 90.0 90.0 17.4 81.0 14.4 72.0 11.7 63.0 9.44
27 °C 90.0 90.0 16.2 81.0 13.4 72.0 10.9 63.0 8.85
25 °C 90.0 90.0 15.1 81.0 12.5 72.0 10.2 63.0 8.30
23 °C 90.0 90.0 14.1 81.0 11.7 72.0 9.60 63.0 7.79
21 °C 90.0 90.0 13.8 81.0 11.5 72.0 9.42 63.0 7.66
20 °C 90.0 90.0 13.7 81.0 11.4 72.0 9.33 63.0 7.60
19 °C 90.0 90.0 13.6 81.0 11.3 72.0 9.26 63.0 7.54
17 °C 90.0 90.0 13.4 81.0 11.1 72.0 9.12 63.0 7.44
15 °C 90.0 90.0 13.2 81.0 10.9 72.0 9.01 63.0 7.36

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 83.8 50.3 9.92 41.9 7.82 33.5 6.24 25.1 5.19
39 °C 85.1 51.1 9.77 42.5 7.70 34.0 6.15 25.5 5.11
37 °C 87.6 52.6 9.47 43.8 7.47 35.1 5.96 26.3 4.96
35 °C 90.0 54.0 9.18 45.0 7.23 36.0 5.77 27.0 4.80
33 °C 90.0 54.0 8.58 45.0 6.80 36.0 5.48 27.0 4.59
31 °C 90.0 54.0 8.04 45.0 6.41 36.0 5.20 27.0 4.39
30 °C 90.0 54.0 7.79 45.0 6.23 36.0 5.07 27.0 4.30
29 °C 90.0 54.0 7.55 45.0 6.05 36.0 4.94 27.0 4.20
27 °C 90.0 54.0 7.10 45.0 5.72 36.0 4.69 27.0 4.02
25 °C 90.0 54.0 6.69 45.0 5.40 36.0 4.45 27.0 3.84
23 °C 90.0 54.0 6.29 45.0 5.11 36.0 4.23 27.0 3.66
21 °C 90.0 54.0 6.20 45.0 5.05 36.0 4.19 27.0 3.64
20 °C 90.0 54.0 6.16 45.0 5.02 36.0 4.18 27.0 3.64
19 °C 90.0 54.0 6.12 45.0 4.99 36.0 4.16 27.0 3.63
17 °C 90.0 54.0 6.05 45.0 4.95 36.0 4.14 27.0 3.62
15 °C 90.0 54.0 5.99 45.0 4.91 36.0 4.12 27.0 3.61
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 100.0 100.0 18.4 90.0 15.3 80.0 12.7 70.0 10.6
13.0 11.8 100.0 100.0 19.1 90.0 15.8 80.0 13.1 70.0 10.8
11.0 9.8 100.0 100.0 20.0 90.0 16.4 80.0 13.5 70.0 11.1
9.0 7.9 100.0 100.0 21.0 90.0 17.1 80.0 14.0 70.0 11.4
7.0 6.0 100.0 100.0 22.1 90.0 17.9 80.0 14.5 70.0 11.8
5.0 4.1 96.6 96.6 21.8 86.9 17.6 77.3 14.3 67.6 11.6
3.0 2.2 93.1 93.1 21.4 83.8 17.4 74.5 14.1 65.2 11.4
0.0 -0.7 87.7 87.7 20.9 79.0 17.0 70.2 13.7 61.4 11.2
-3.0 -3.7 82.0 82.0 20.4 73.8 16.5 65.6 13.4 57.4 10.9
-5.0 -5.6 78.2 78.2 20.1 70.4 16.3 62.6 13.2 54.8 10.7
-7.0 -7.6 74.2 74.2 19.7 66.8 16.0 59.4 12.9 52.0 10.5
-10 -10.5 68.3 68.3 19.2 61.5 15.6 54.6 12.6 47.8 10.2
-14.5 -15.0 58.8 58.8 18.4 52.9 14.9 47.0 12.1 41.1 9.80

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 100.0 60.0 8.83 50.0 7.34 40.0 6.02 30.0 4.79
13.0 11.8 100.0 60.0 8.97 50.0 7.43 40.0 6.08 30.0 4.82
11.0 9.8 100.0 60.0 9.15 50.0 7.54 40.0 6.14 30.0 4.86
9.0 7.9 100.0 60.0 9.35 50.0 7.66 40.0 6.22 30.0 4.91
7.0 6.0 100.0 60.0 9.59 50.0 7.80 40.0 6.30 30.0 4.96
5.0 4.1 96.6 58.0 9.44 48.3 7.68 38.6 6.21 29.0 4.89
3.0 2.2 93.1 55.9 9.30 46.6 7.57 37.3 6.11 27.9 4.81
0.0 -0.7 87.7 52.6 9.07 43.9 7.39 35.1 5.97 26.3 4.70
-3.0 -3.7 82.0 49.2 8.84 41.0 7.20 32.8 5.81 24.6 4.58
-5.0 -5.6 78.2 46.9 8.70 39.1 7.08 31.3 5.72 23.5 4.50
-7.0 -7.6 74.2 44.5 8.54 37.1 6.95 29.7 5.62 22.3 4.42
-10 -10.5 68.3 41.0 8.32 34.1 6.77 27.3 5.47 20.5 4.31
-14.5 -15.0 58.8 35.3 7.98 29.4 6.49 23.5 5.25 17.6 4.13
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -61
11 Technical Specifications

MMY-AP3424HT8, AP3424T8 (34HP, 96kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 89.3 89.3 25.9 80.4 21.3 71.5 17.3 62.5 13.8
39 °C 90.8 90.8 25.5 81.7 21.0 72.6 17.0 63.5 13.6
37 °C 93.5 93.5 24.8 84.1 20.4 74.8 16.5 65.4 13.2
35 °C 96.0 96.0 24.0 86.4 19.7 76.8 16.0 67.2 12.8
33 °C 96.0 96.0 22.2 86.4 18.3 76.8 14.8 67.2 11.9
31 °C 96.0 96.0 20.6 86.4 17.0 76.8 13.8 67.2 11.1
30 °C 96.0 96.0 19.8 86.4 16.4 76.8 13.3 67.2 10.7
29 °C 96.0 96.0 19.1 86.4 15.8 76.8 12.9 67.2 10.4
27 °C 96.0 96.0 17.8 86.4 14.8 76.8 12.1 67.2 9.74
25 °C 96.0 96.0 16.7 86.4 13.8 76.8 11.3 67.2 9.14
23 °C 96.0 96.0 15.6 86.4 12.9 76.8 10.6 67.2 8.58
21 °C 96.0 96.0 15.2 86.4 12.6 76.8 10.4 67.2 8.43
20 °C 96.0 96.0 15.1 86.4 12.5 76.8 10.3 67.2 8.37
19 °C 96.0 96.0 15.0 86.4 12.4 76.8 10.2 67.2 8.31
17 °C 96.0 96.0 14.7 86.4 12.2 76.8 10.0 67.2 8.20
15 °C 96.0 96.0 14.5 86.4 12.1 76.8 9.92 67.2 8.10

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 89.3 53.6 10.9 44.7 8.61 35.7 6.87 26.8 5.71
39 °C 90.8 54.5 10.8 45.4 8.48 36.3 6.77 27.2 5.63
37 °C 93.5 56.1 10.4 46.7 8.23 37.4 6.57 28.0 5.46
35 °C 96.0 57.6 10.1 48.0 7.97 38.4 6.36 28.8 5.29
33 °C 96.0 57.6 9.45 48.0 7.50 38.4 6.03 28.8 5.06
31 °C 96.0 57.6 8.86 48.0 7.07 38.4 5.73 28.8 4.84
30 °C 96.0 57.6 8.58 48.0 6.86 38.4 5.58 28.8 4.73
29 °C 96.0 57.6 8.32 48.0 6.67 38.4 5.44 28.8 4.63
27 °C 96.0 57.6 7.83 48.0 6.30 38.4 5.17 28.8 4.42
25 °C 96.0 57.6 7.36 48.0 5.95 38.4 4.91 28.8 4.22
23 °C 96.0 57.6 6.93 48.0 5.62 38.4 4.66 28.8 4.03
21 °C 96.0 57.6 6.83 48.0 5.56 38.4 4.62 28.8 4.01
20 °C 96.0 57.6 6.78 48.0 5.53 38.4 4.60 28.8 4.00
19 °C 96.0 57.6 6.74 48.0 5.50 38.4 4.59 28.8 4.00
17 °C 96.0 57.6 6.66 48.0 5.45 38.4 4.56 28.8 3.99
15 °C 96.0 57.6 6.60 48.0 5.41 38.4 4.54 28.8 3.98
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 108.0 108.0 20.6 97.2 17.1 86.4 14.2 75.6 11.8
13.0 11.8 108.0 108.0 21.4 97.2 17.6 86.4 14.6 75.6 12.1
11.0 9.8 108.0 108.0 22.3 97.2 18.3 86.4 15.1 75.6 12.4
9.0 7.9 108.0 108.0 23.4 97.2 19.1 86.4 15.6 75.6 12.7
7.0 6.0 108.0 108.0 24.7 97.2 20.0 86.4 16.2 75.6 13.2
5.0 4.1 104.3 104.3 24.3 93.9 19.7 83.5 16.0 73.0 13.0
3.0 2.2 100.6 100.6 23.9 90.5 19.4 80.5 15.7 70.4 12.8
0.0 -0.7 94.7 94.7 23.4 85.3 18.9 75.8 15.3 66.3 12.5
-3.0 -3.7 88.5 88.5 22.8 79.7 18.5 70.8 15.0 62.0 12.1
-5.0 -5.6 84.5 84.5 22.4 76.0 18.2 67.6 14.7 59.1 11.9
-7.0 -7.6 80.2 80.2 22.0 72.2 17.8 64.1 14.4 56.1 11.7
-10 -10.5 73.8 73.8 21.4 66.4 17.4 59.0 14.1 51.6 11.4
-14.5 -15.0 63.5 63.5 20.5 57.1 16.6 50.8 13.5 44.4 10.9

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 108.0 64.8 9.86 54.0 8.19 43.2 6.72 32.4 5.34
13.0 11.8 108.0 64.8 10.0 54.0 8.29 43.2 6.78 32.4 5.38
11.0 9.8 108.0 64.8 10.2 54.0 8.42 43.2 6.86 32.4 5.43
9.0 7.9 108.0 64.8 10.4 54.0 8.55 43.2 6.94 32.4 5.48
7.0 6.0 108.0 64.8 10.7 54.0 8.71 43.2 7.04 32.4 5.54
5.0 4.1 104.3 62.6 10.5 52.2 8.58 41.7 6.93 31.3 5.46
3.0 2.2 100.6 60.4 10.4 50.3 8.45 40.2 6.83 30.2 5.37
0.0 -0.7 94.7 56.8 10.1 47.4 8.25 37.9 6.66 28.4 5.24
-3.0 -3.7 88.5 53.1 9.87 44.3 8.04 35.4 6.49 26.6 5.11
-5.0 -5.6 84.5 50.7 9.71 42.2 7.90 33.8 6.39 25.3 5.03
-7.0 -7.6 80.2 48.1 9.54 40.1 7.77 32.1 6.27 24.1 4.94
-10 -10.5 73.8 44.3 9.29 36.9 7.56 29.5 6.11 22.1 4.81
-14.5 -15.0 63.5 38.1 8.91 31.7 7.25 25.4 5.86 19.0 4.61
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -62
11 Technical Specifications

MMY-AP3624HT8, AP3624T8 (36HP, 101kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 94.0 94.0 27.8 84.6 22.8 75.2 18.5 65.8 14.8
39 °C 95.5 95.5 27.4 85.9 22.5 76.4 18.2 66.8 14.6
37 °C 98.3 98.3 26.5 88.5 21.8 78.7 17.7 68.8 14.1
35 °C 101.0 101.0 25.7 90.9 21.1 80.8 17.1 70.7 13.7
33 °C 101.0 101.0 23.8 90.9 19.6 80.8 15.9 70.7 12.7
31 °C 101.0 101.0 22.1 90.9 18.2 80.8 14.8 70.7 11.9
30 °C 101.0 101.0 21.3 90.9 17.5 80.8 14.3 70.7 11.5
29 °C 101.0 101.0 20.5 90.9 16.9 80.8 13.8 70.7 11.1
27 °C 101.0 101.0 19.1 90.9 15.8 80.8 12.9 70.7 10.4
25 °C 101.0 101.0 17.9 90.9 14.8 80.8 12.1 70.7 9.80
23 °C 101.0 101.0 16.7 90.9 13.8 80.8 11.3 70.7 9.20
21 °C 101.0 101.0 16.3 90.9 13.5 80.8 11.1 70.7 9.04
20 °C 101.0 101.0 16.2 90.9 13.4 80.8 11.0 70.7 8.97
19 °C 101.0 101.0 16.0 90.9 13.3 80.8 10.9 70.7 8.90
17 °C 101.0 101.0 15.8 90.9 13.1 80.8 10.8 70.7 8.78
15 °C 101.0 101.0 15.5 90.9 12.9 80.8 10.6 70.7 8.68

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 94.0 56.4 11.7 47.0 9.23 37.6 7.37 28.2 6.12
39 °C 95.5 57.3 11.5 47.7 9.09 38.2 7.26 28.6 6.03
37 °C 98.3 59.0 11.2 49.2 8.81 39.3 7.04 29.5 5.85
35 °C 101.0 60.6 10.8 50.5 8.54 40.4 6.82 30.3 5.67
33 °C 101.0 60.6 10.1 50.5 8.03 40.4 6.46 30.3 5.42
31 °C 101.0 60.6 9.49 50.5 7.57 40.4 6.14 30.3 5.19
30 °C 101.0 60.6 9.20 50.5 7.35 40.4 5.98 30.3 5.07
29 °C 101.0 60.6 8.92 50.5 7.15 40.4 5.83 30.3 4.96
27 °C 101.0 60.6 8.39 50.5 6.75 40.4 5.54 30.3 4.74
25 °C 101.0 60.6 7.89 50.5 6.38 40.4 5.26 30.3 4.53
23 °C 101.0 60.6 7.43 50.5 6.03 40.4 4.99 30.3 4.32
21 °C 101.0 60.6 7.32 50.5 5.96 40.4 4.95 30.3 4.30
20 °C 101.0 60.6 7.27 50.5 5.92 40.4 4.93 30.3 4.29
19 °C 101.0 60.6 7.22 50.5 5.89 40.4 4.92 30.3 4.28
17 °C 101.0 60.6 7.14 50.5 5.84 40.4 4.89 30.3 4.27
15 °C 101.0 60.6 7.07 50.5 5.80 40.4 4.86 30.3 4.26
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 113.0 113.0 21.7 101.7 18.0 90.4 15.0 79.1 12.5
13.0 11.8 113.0 113.0 22.5 101.7 18.6 90.4 15.4 79.1 12.7
11.0 9.8 113.0 113.0 23.6 101.7 19.3 90.4 15.9 79.1 13.1
9.0 7.9 113.0 113.0 24.7 101.7 20.2 90.4 16.5 79.1 13.4
7.0 6.0 113.0 113.0 26.1 101.7 21.1 90.4 17.1 79.1 13.9
5.0 4.1 109.2 109.2 25.7 98.2 20.8 87.3 16.8 76.4 13.7
3.0 2.2 105.2 105.2 25.3 94.7 20.5 84.2 16.6 73.7 13.5
0.0 -0.7 99.1 99.1 24.7 89.2 20.0 79.3 16.2 69.4 13.1
-3.0 -3.7 92.6 92.6 24.0 83.4 19.5 74.1 15.8 64.8 12.8
-5.0 -5.6 88.4 88.4 23.6 79.6 19.2 70.7 15.5 61.9 12.6
-7.0 -7.6 83.9 83.9 23.2 75.5 18.8 67.1 15.2 58.7 12.4
-10 -10.5 77.2 77.2 22.6 69.5 18.3 61.7 14.8 54.0 12.0
-14.5 -15.0 66.4 66.4 21.7 59.8 17.6 53.1 14.2 46.5 11.5

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 113.0 67.8 10.4 56.5 8.64 45.2 7.09 33.9 5.64
13.0 11.8 113.0 67.8 10.6 56.5 8.75 45.2 7.16 33.9 5.68
11.0 9.8 113.0 67.8 10.8 56.5 8.88 45.2 7.24 33.9 5.73
9.0 7.9 113.0 67.8 11.0 56.5 9.03 45.2 7.33 33.9 5.78
7.0 6.0 113.0 67.8 11.3 56.5 9.19 45.2 7.43 33.9 5.84
5.0 4.1 109.2 65.5 11.1 54.6 9.05 43.7 7.31 32.7 5.76
3.0 2.2 105.2 63.1 11.0 52.6 8.91 42.1 7.20 31.6 5.67
0.0 -0.7 99.1 59.5 10.7 49.6 8.70 39.7 7.03 29.7 5.53
-3.0 -3.7 92.6 55.6 10.4 46.3 8.48 37.0 6.85 27.8 5.39
-5.0 -5.6 88.4 53.0 10.2 44.2 8.34 35.4 6.74 26.5 5.30
-7.0 -7.6 83.9 50.3 10.1 41.9 8.19 33.6 6.62 25.2 5.21
-10 -10.5 77.2 46.3 9.80 38.6 7.98 30.9 6.45 23.2 5.07
-14.5 -15.0 66.4 39.9 9.40 33.2 7.65 26.6 6.18 19.9 4.86
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -63
11 Technical Specifications

MMY-AP3824HT8, AP3824T8 (38HP, 106.5kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 99.1 99.1 29.9 89.2 24.6 79.3 19.9 69.4 15.9
39 °C 100.7 100.7 29.5 90.6 24.2 80.6 19.6 70.5 15.7
37 °C 103.7 103.7 28.6 93.3 23.5 83.0 19.0 72.6 15.2
35 °C 106.5 106.5 27.7 95.9 22.7 85.2 18.4 74.6 14.7
33 °C 106.5 106.5 25.6 95.9 21.1 85.2 17.1 74.6 13.7
31 °C 106.5 106.5 23.7 95.9 19.6 85.2 15.9 74.6 12.8
30 °C 106.5 106.5 22.9 95.9 18.9 85.2 15.4 74.6 12.4
29 °C 106.5 106.5 22.1 95.9 18.2 85.2 14.9 74.6 12.0
27 °C 106.5 106.5 20.6 95.9 17.0 85.2 13.9 74.6 11.2
25 °C 106.5 106.5 19.2 95.9 15.9 85.2 13.0 74.6 10.5
23 °C 106.5 106.5 18.0 95.9 14.9 85.2 12.2 74.6 9.9
21 °C 106.5 106.5 17.6 95.9 14.6 85.2 12.0 74.6 9.73
20 °C 106.5 106.5 17.4 95.9 14.4 85.2 11.9 74.6 9.65
19 °C 106.5 106.5 17.2 95.9 14.3 85.2 11.8 74.6 9.58
17 °C 106.5 106.5 17.0 95.9 14.1 85.2 11.6 74.6 9.45
15 °C 106.5 106.5 16.7 95.9 13.9 85.2 11.4 74.6 9.35

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 99.1 59.5 12.6 49.6 9.9 39.6 7.93 29.7 6.59
39 °C 100.7 60.4 12.4 50.3 9.78 40.3 7.81 30.2 6.49
37 °C 103.7 62.2 12.0 51.9 9.49 41.5 7.57 31.1 6.30
35 °C 106.5 63.9 11.7 53.3 9.19 42.6 7.34 32.0 6.10
33 °C 106.5 63.9 10.9 53.3 8.64 42.6 6.96 32.0 5.83
31 °C 106.5 63.9 10.2 53.3 8.15 42.6 6.60 32.0 5.58
30 °C 106.5 63.9 9.9 53.3 7.92 42.6 6.44 32.0 5.46
29 °C 106.5 63.9 9.60 53.3 7.69 42.6 6.27 32.0 5.34
27 °C 106.5 63.9 9.03 53.3 7.27 42.6 5.96 32.0 5.10
25 °C 106.5 63.9 8.49 53.3 6.87 42.6 5.66 32.0 4.87
23 °C 106.5 63.9 8.00 53.3 6.49 42.6 5.37 32.0 4.65
21 °C 106.5 63.9 7.88 53.3 6.41 42.6 5.33 32.0 4.63
20 °C 106.5 63.9 7.82 53.3 6.38 42.6 5.31 32.0 4.62
19 °C 106.5 63.9 7.77 53.3 6.34 42.6 5.29 32.0 4.61
17 °C 106.5 63.9 7.69 53.3 6.29 42.6 5.26 32.0 4.60
15 °C 106.5 63.9 7.61 53.3 6.24 42.6 5.23 32.0 4.59
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 119.5 119.5 23.3 107.6 19.4 95.6 16.1 83.7 13.4
13.0 11.8 119.5 119.5 24.2 107.6 20.0 95.6 16.5 83.7 13.7
11.0 9.8 119.5 119.5 25.4 107.6 20.8 95.6 17.1 83.7 14.1
9.0 7.9 119.5 119.5 26.6 107.6 21.7 95.6 17.7 83.7 14.5
7.0 6.0 119.5 119.5 28.0 107.6 22.7 95.6 18.4 83.7 14.9
5.0 4.1 115.4 115.4 27.6 103.9 22.4 92.4 18.1 80.8 14.7
3.0 2.2 111.3 111.3 27.2 100.2 22.0 89.0 17.8 77.9 14.5
0.0 -0.7 104.8 104.8 26.5 94.4 21.5 83.9 17.4 73.4 14.1
-3.0 -3.7 98.0 98.0 25.9 88.2 20.9 78.4 17.0 68.6 13.8
-5.0 -5.6 93.5 93.5 25.4 84.1 20.6 74.8 16.7 65.4 13.5
-7.0 -7.6 88.7 88.7 25.0 79.8 20.2 71.0 16.4 62.1 13.3
-10 -10.5 81.6 81.6 24.3 73.5 19.7 65.3 16.0 57.1 13.0
-14.5 -15.0 70.2 70.2 23.3 63.2 18.9 56.2 15.3 49.2 12.4

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 119.5 71.7 11.2 59.8 9.30 47.8 7.63 35.9 6.06
13.0 11.8 119.5 71.7 11.4 59.8 9.41 47.8 7.70 35.9 6.11
11.0 9.8 119.5 71.7 11.6 59.8 9.55 47.8 7.79 35.9 6.16
9.0 7.9 119.5 71.7 11.9 59.8 9.71 47.8 7.88 35.9 6.22
7.0 6.0 119.5 71.7 12.1 59.8 9.89 47.8 7.99 35.9 6.29
5.0 4.1 115.4 69.3 12.0 57.7 9.74 46.2 7.87 34.6 6.19
3.0 2.2 111.3 66.8 11.8 55.7 9.59 44.5 7.75 33.4 6.10
0.0 -0.7 104.8 62.9 11.5 52.4 9.36 41.9 7.56 31.5 5.95
-3.0 -3.7 98.0 58.8 11.2 49.0 9.12 39.2 7.37 29.4 5.80
-5.0 -5.6 93.5 56.1 11.0 46.7 8.97 37.4 7.25 28.0 5.70
-7.0 -7.6 88.7 53.2 10.8 44.4 8.81 35.5 7.12 26.6 5.60
-10 -10.5 81.6 49.0 10.5 40.8 8.58 32.6 6.93 24.5 5.46
-14.5 -15.0 70.2 42.1 10.1 35.1 8.23 28.1 6.65 21.1 5.23
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -64
11 Technical Specifications

MMY-AP4024HT8, AP4024T8 (40HP, 112kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 104.2 104.2 32.0 93.8 26.3 83.4 21.3 73.0 17.1
39 °C 105.9 105.9 31.5 95.3 25.9 84.7 21.0 74.1 16.8
37 °C 109.1 109.1 30.6 98.2 25.1 87.2 20.4 76.3 16.3
35 °C 112.0 112.0 29.6 100.8 24.4 89.6 19.7 78.4 15.8
33 °C 112.0 112.0 27.4 100.8 22.6 89.6 18.3 78.4 14.7
31 °C 112.0 112.0 25.4 100.8 21.0 89.6 17.1 78.4 13.7
30 °C 112.0 112.0 24.5 100.8 20.2 89.6 16.5 78.4 13.3
29 °C 112.0 112.0 23.6 100.8 19.5 89.6 15.9 78.4 12.8
27 °C 112.0 112.0 22.0 100.8 18.2 89.6 14.9 78.4 12.0
25 °C 112.0 112.0 20.6 100.8 17.0 89.6 13.9 78.4 11.3
23 °C 112.0 112.0 19.2 100.8 15.9 89.6 13.1 78.4 10.6
21 °C 112.0 112.0 18.8 100.8 15.6 89.6 12.8 78.4 10.4
20 °C 112.0 112.0 18.6 100.8 15.5 89.6 12.7 78.4 10.3
19 °C 112.0 112.0 18.5 100.8 15.3 89.6 12.6 78.4 10.3
17 °C 112.0 112.0 18.2 100.8 15.1 89.6 12.4 78.4 10.1
15 °C 112.0 112.0 17.9 100.8 14.9 89.6 12.3 78.4 10.0

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 104.2 62.5 13.5 52.1 10.6 41.7 8.49 31.3 7.06
39 °C 105.9 63.5 13.3 52.9 10.5 42.4 8.36 31.8 6.95
37 °C 109.1 65.4 12.9 54.5 10.2 43.6 8.11 32.7 6.74
35 °C 112.0 67.2 12.5 56.0 9.84 44.8 7.86 33.6 6.53
33 °C 112.0 67.2 11.7 56.0 9.26 44.8 7.45 33.6 6.25
31 °C 112.0 67.2 10.9 56.0 8.73 44.8 7.07 33.6 5.98
30 °C 112.0 67.2 10.6 56.0 8.48 44.8 6.89 33.6 5.85
29 °C 112.0 67.2 10.3 56.0 8.24 44.8 6.72 33.6 5.72
27 °C 112.0 67.2 9.7 56.0 7.78 44.8 6.38 33.6 5.46
25 °C 112.0 67.2 9.1 56.0 7.35 44.8 6.06 33.6 5.22
23 °C 112.0 67.2 8.6 56.0 6.95 44.8 5.75 33.6 4.97
21 °C 112.0 67.2 8.4 56.0 6.86 44.8 5.70 33.6 4.95
20 °C 112.0 67.2 8.4 56.0 6.83 44.8 5.68 33.6 4.95
19 °C 112.0 67.2 8.3 56.0 6.79 44.8 5.66 33.6 4.94
17 °C 112.0 67.2 8.2 56.0 6.73 44.8 5.63 33.6 4.92
15 °C 112.0 67.2 8.2 56.0 6.68 44.8 5.60 33.6 4.91
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 127.0 127.0 25.3 114.3 21.0 101.6 17.5 88.9 14.6
13.0 11.8 127.0 127.0 26.3 114.3 21.7 101.6 18.0 88.9 14.9
11.0 9.8 127.0 127.0 27.5 114.3 22.6 101.6 18.5 88.9 15.3
9.0 7.9 127.0 127.0 28.9 114.3 23.5 101.6 19.2 88.9 15.7
7.0 6.0 127.0 127.0 30.4 114.3 24.6 101.6 20.0 88.9 16.2
5.0 4.1 122.7 122.7 30.0 110.4 24.3 98.1 19.7 85.9 16.0
3.0 2.2 118.3 118.3 29.5 106.5 23.9 94.6 19.4 82.8 15.7
0.0 -0.7 111.4 111.4 28.8 100.3 23.3 89.1 18.9 78.0 15.3
-3.0 -3.7 104.1 104.1 28.1 93.7 22.7 83.3 18.4 72.9 14.9
-5.0 -5.6 99.4 99.4 27.6 89.4 22.4 79.5 18.1 69.5 14.7
-7.0 -7.6 94.3 94.3 27.1 84.8 22.0 75.4 17.8 66.0 14.4
-10 -10.5 86.7 86.7 26.4 78.1 21.4 69.4 17.3 60.7 14.1
-14.5 -15.0 74.6 74.6 25.3 67.2 20.5 59.7 16.6 52.3 13.5

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 127.0 76.2 12.1 63.5 10.1 50.8 8.28 38.1 6.58
13.0 11.8 127.0 76.2 12.3 63.5 10.2 50.8 8.36 38.1 6.63
11.0 9.8 127.0 76.2 12.6 63.5 10.4 50.8 8.45 38.1 6.69
9.0 7.9 127.0 76.2 12.9 63.5 10.5 50.8 8.55 38.1 6.75
7.0 6.0 127.0 76.2 13.2 63.5 10.7 50.8 8.67 38.1 6.82
5.0 4.1 122.7 73.6 13.0 61.3 10.6 49.1 8.54 36.8 6.72
3.0 2.2 118.3 71.0 12.8 59.1 10.4 47.3 8.41 35.5 6.62
0.0 -0.7 111.4 66.8 12.5 55.7 10.2 44.6 8.20 33.4 6.46
-3.0 -3.7 104.1 62.5 12.2 52.0 9.90 41.6 8.00 31.2 6.29
-5.0 -5.6 99.4 59.6 12.0 49.7 9.74 39.7 7.87 29.8 6.19
-7.0 -7.6 94.3 56.6 11.7 47.1 9.56 37.7 7.73 28.3 6.08
-10 -10.5 86.7 52.0 11.4 43.4 9.31 34.7 7.53 26.0 5.92
-14.5 -15.0 74.6 44.8 11.0 37.3 8.93 29.9 7.21 22.4 5.68
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -65
11 Technical Specifications

MMY-AP4224HT8, AP4224T8 (42HP, 118kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 109.8 109.8 34.6 98.8 28.4 87.8 23.0 76.9 18.3
39 °C 111.6 111.6 34.1 100.4 28.0 89.3 22.6 78.1 18.0
37 °C 114.9 114.9 33.1 103.4 27.1 91.9 21.9 80.4 17.5
35 °C 118.0 118.0 32.0 106.2 26.3 94.4 21.2 82.6 17.0
33 °C 118.0 118.0 29.6 106.2 24.3 94.4 19.7 82.6 15.8
31 °C 118.0 118.0 27.4 106.2 22.6 94.4 18.3 82.6 14.7
30 °C 118.0 118.0 26.5 106.2 21.8 94.4 17.7 82.6 14.2
29 °C 118.0 118.0 25.5 106.2 21.0 94.4 17.1 82.6 13.8
27 °C 118.0 118.0 23.8 106.2 19.6 94.4 16.0 82.6 12.9
25 °C 118.0 118.0 22.2 106.2 18.3 94.4 15.0 82.6 12.1
23 °C 118.0 118.0 20.7 106.2 17.2 94.4 14.0 82.6 11.4
21 °C 118.0 118.0 20.3 106.2 16.8 94.4 13.8 82.6 11.2
20 °C 118.0 118.0 20.1 106.2 16.6 94.4 13.6 82.6 11.1
19 °C 118.0 118.0 19.9 106.2 16.5 94.4 13.5 82.6 11.0
17 °C 118.0 118.0 19.6 106.2 16.2 94.4 13.3 82.6 10.9
15 °C 118.0 118.0 19.3 106.2 16.0 94.4 13.2 82.6 10.7

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 109.8 65.9 14.5 54.9 11.4 43.9 9.09 32.9 7.56
39 °C 111.6 66.9 14.2 55.8 11.2 44.6 8.96 33.5 7.45
37 °C 114.9 68.9 13.8 57.5 10.9 46.0 8.68 34.5 7.22
35 °C 118.0 70.8 13.4 59.0 10.54 47.2 8.41 35.4 7.00
33 °C 118.0 70.8 12.5 59.0 9.91 47.2 7.98 35.4 6.70
31 °C 118.0 70.8 11.7 59.0 9.34 47.2 7.57 35.4 6.41
30 °C 118.0 70.8 11.4 59.0 9.08 47.2 7.38 35.4 6.27
29 °C 118.0 70.8 11.0 59.0 8.82 47.2 7.19 35.4 6.13
27 °C 118.0 70.8 10.4 59.0 8.33 47.2 6.83 35.4 5.86
25 °C 118.0 70.8 9.75 59.0 7.87 47.2 6.49 35.4 5.59
23 °C 118.0 70.8 9.17 59.0 7.44 47.2 6.16 35.4 5.33
21 °C 118.0 70.8 9.04 59.0 7.35 47.2 6.11 35.4 5.31
20 °C 118.0 70.8 8.98 59.0 7.31 47.2 6.09 35.4 5.30
19 °C 118.0 70.8 8.92 59.0 7.27 47.2 6.07 35.4 5.29
17 °C 118.0 70.8 8.82 59.0 7.21 47.2 6.03 35.4 5.28
15 °C 118.0 70.8 8.73 59.0 7.15 47.2 6.00 35.4 5.27
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 132.0 132.0 27.2 118.8 22.6 105.6 18.7 92.4 15.6
13.0 11.8 132.0 132.0 28.3 118.8 23.4 105.6 19.3 92.4 15.9
11.0 9.8 132.0 132.0 29.6 118.8 24.3 105.6 19.9 92.4 16.3
9.0 7.9 132.0 132.0 31.0 118.8 25.3 105.6 20.6 92.4 16.8
7.0 6.0 132.0 132.0 32.7 118.8 26.5 105.6 21.5 92.4 17.4
5.0 4.1 127.5 127.5 32.2 114.8 26.1 102.0 21.1 89.3 17.1
3.0 2.2 122.9 122.9 31.7 110.7 25.7 98.4 20.8 86.1 16.8
0.0 -0.7 115.8 115.8 30.9 104.2 25.1 92.6 20.3 81.1 16.4
-3.0 -3.7 108.2 108.2 30.2 97.4 24.5 86.6 19.8 75.7 16.0
-5.0 -5.6 103.3 103.3 29.7 92.9 24.0 82.6 19.5 72.3 15.8
-7.0 -7.6 98.0 98.0 29.1 88.2 23.6 78.4 19.1 68.6 15.5
-10 -10.5 90.1 90.1 28.4 81.1 23.0 72.1 18.6 63.1 15.1
-14.5 -15.0 77.6 77.6 27.2 69.8 22.1 62.1 17.9 54.3 14.5

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 132.0 79.2 12.9 66.0 10.7 52.8 8.84 39.6 7.12
13.0 11.8 132.0 79.2 13.2 66.0 10.9 52.8 8.92 39.6 7.16
11.0 9.8 132.0 79.2 13.4 66.0 11.0 52.8 9.01 39.6 7.21
9.0 7.9 132.0 79.2 13.7 66.0 11.2 52.8 9.11 39.6 7.27
7.0 6.0 132.0 79.2 14.1 66.0 11.4 52.8 9.24 39.6 7.33
5.0 4.1 127.5 76.5 13.9 63.8 11.3 51.0 9.09 38.3 7.22
3.0 2.2 122.9 73.8 13.7 61.5 11.1 49.2 8.95 36.9 7.11
0.0 -0.7 115.8 69.5 13.3 57.9 10.8 46.3 8.74 34.7 6.94
-3.0 -3.7 108.2 64.9 13.0 54.1 10.54 43.3 8.52 32.5 6.76
-5.0 -5.6 103.3 62.0 12.8 51.6 10.37 41.3 8.38 31.0 6.65
-7.0 -7.6 98.0 58.8 12.6 49.0 10.19 39.2 8.23 29.4 6.53
-10 -10.5 90.1 54.1 12.2 45.1 9.92 36.1 8.02 27.0 6.36
-14.5 -15.0 77.6 46.6 11.7 38.8 9.51 31.0 7.68 23.3 6.10
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -66
11 Technical Specifications

MMY-AP4424HT8, AP4424T8 (44HP, 123.5kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 114.9 114.9 36.9 103.4 30.2 91.9 24.4 80.4 19.5
39 °C 116.8 116.8 36.4 105.1 29.8 93.4 24.1 81.7 19.2
37 °C 120.3 120.3 35.3 108.2 28.9 96.2 23.3 84.2 18.6
35 °C 123.5 123.5 34.2 111.2 28.0 98.8 22.6 86.5 18.0
33 °C 123.5 123.5 31.6 111.2 25.9 98.8 21.0 86.5 16.7
31 °C 123.5 123.5 29.3 111.2 24.1 98.8 19.5 86.5 15.6
30 °C 123.5 123.5 28.2 111.2 23.2 98.8 18.8 86.5 15.1
29 °C 123.5 123.5 27.2 111.2 22.4 98.8 18.2 86.5 14.6
27 °C 123.5 123.5 25.4 111.2 20.9 98.8 17.0 86.5 13.7
25 °C 123.5 123.5 23.7 111.2 19.5 98.8 15.9 86.5 12.8
23 °C 123.5 123.5 22.1 111.2 18.3 98.8 14.9 86.5 12.1
21 °C 123.5 123.5 21.6 111.2 17.9 98.8 14.6 86.5 11.8
20 °C 123.5 123.5 21.4 111.2 17.7 98.8 14.5 86.5 11.7
19 °C 123.5 123.5 21.2 111.2 17.6 98.8 14.4 86.5 11.7
17 °C 123.5 123.5 20.9 111.2 17.3 98.8 14.2 86.5 11.5
15 °C 123.5 123.5 20.6 111.2 17.0 98.8 14.0 86.5 11.4

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 114.9 69.0 15.3 57.5 12.0 46.0 9.59 34.5 7.99
39 °C 116.8 70.1 15.1 58.4 11.9 46.7 9.45 35.0 7.87
37 °C 120.3 72.2 14.6 60.1 11.5 48.1 9.16 36.1 7.63
35 °C 123.5 74.1 14.2 61.8 11.1 49.4 8.87 37.1 7.39
33 °C 123.5 74.1 13.2 61.8 10.5 49.4 8.41 37.1 7.08
31 °C 123.5 74.1 12.4 61.8 9.87 49.4 7.99 37.1 6.77
30 °C 123.5 74.1 12.0 61.8 9.58 49.4 7.78 37.1 6.63
29 °C 123.5 74.1 11.7 61.8 9.31 49.4 7.59 37.1 6.48
27 °C 123.5 74.1 11.0 61.8 8.79 49.4 7.21 37.1 6.20
25 °C 123.5 74.1 10.3 61.8 8.31 49.4 6.85 37.1 5.92
23 °C 123.5 74.1 9.70 61.8 7.85 49.4 6.50 37.1 5.64
21 °C 123.5 74.1 9.55 61.8 7.76 49.4 6.44 37.1 5.62
20 °C 123.5 74.1 9.49 61.8 7.71 49.4 6.42 37.1 5.61
19 °C 123.5 74.1 9.43 61.8 7.68 49.4 6.40 37.1 5.60
17 °C 123.5 74.1 9.32 61.8 7.61 49.4 6.36 37.1 5.59
15 °C 123.5 74.1 9.23 61.8 7.55 49.4 6.33 37.1 5.58
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 138.0 138.0 29.5 124.2 24.4 110.4 20.2 96.6 16.8
13.0 11.8 138.0 138.0 30.7 124.2 25.3 110.4 20.8 96.6 17.2
11.0 9.8 138.0 138.0 32.1 124.2 26.3 110.4 21.5 96.6 17.6
9.0 7.9 138.0 138.0 33.6 124.2 27.4 110.4 22.3 96.6 18.2
7.0 6.0 138.0 138.0 35.4 124.2 28.7 110.4 23.2 96.6 18.8
5.0 4.1 133.3 133.3 34.9 120.0 28.3 106.6 22.9 93.3 18.5
3.0 2.2 128.5 128.5 34.3 115.7 27.8 102.8 22.5 90.0 18.2
0.0 -0.7 121.1 121.1 33.5 109.0 27.2 96.9 22.0 84.7 17.8
-3.0 -3.7 113.1 113.1 32.6 101.8 26.5 90.5 21.4 79.2 17.3
-5.0 -5.6 108.0 108.0 32.1 97.2 26.1 86.4 21.1 75.6 17.0
-7.0 -7.6 102.4 102.4 31.5 92.2 25.6 82.0 20.7 71.7 16.7
-10 -10.5 94.2 94.2 30.7 84.8 24.9 75.4 20.2 66.0 16.3
-14.5 -15.0 81.1 81.1 29.4 73.0 23.9 64.9 19.3 56.8 15.6

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 138.0 82.8 13.9 69.0 11.5 55.2 9.51 41.4 7.76
13.0 11.8 138.0 82.8 14.1 69.0 11.7 55.2 9.58 41.4 7.79
11.0 9.8 138.0 82.8 14.4 69.0 11.8 55.2 9.68 41.4 7.83
9.0 7.9 138.0 82.8 14.8 69.0 12.0 55.2 9.78 41.4 7.88
7.0 6.0 138.0 82.8 15.2 69.0 12.3 55.2 9.91 41.4 7.94
5.0 4.1 133.3 80.0 14.9 66.7 12.1 53.3 9.76 40.0 7.81
3.0 2.2 128.5 77.1 14.7 64.3 11.9 51.4 9.61 38.6 7.69
0.0 -0.7 121.1 72.6 14.3 60.5 11.6 48.4 9.38 36.3 7.51
-3.0 -3.7 113.1 67.9 14.0 56.6 11.3 45.2 9.14 33.9 7.32
-5.0 -5.6 108.0 64.8 13.8 54.0 11.1 43.2 8.99 32.4 7.20
-7.0 -7.6 102.4 61.5 13.5 51.2 10.9 41.0 8.83 30.7 7.07
-10 -10.5 94.2 56.5 13.2 47.1 10.6 37.7 8.60 28.3 6.89
-14.5 -15.0 81.1 48.7 12.6 40.6 10.2 32.4 8.24 24.3 6.60
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -67
11 Technical Specifications

MMY-AP4624HT8, AP4624T8 (46HP, 130kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 121.0 121.0 39.8 108.9 32.5 96.8 26.2 84.7 20.8
39 °C 122.9 122.9 39.2 110.6 32.1 98.3 25.8 86.0 20.5
37 °C 126.6 126.6 38.1 113.9 31.1 101.3 25.0 88.6 19.9
35 °C 130.0 130.0 36.9 117.0 30.1 104.0 24.2 91.0 19.3
33 °C 130.0 130.0 34.0 117.0 27.8 104.0 22.5 91.0 17.9
31 °C 130.0 130.0 31.5 117.0 25.8 104.0 20.9 91.0 16.7
30 °C 130.0 130.0 30.4 117.0 24.9 104.0 20.2 91.0 16.2
29 °C 130.0 130.0 29.3 117.0 24.0 104.0 19.5 91.0 15.6
27 °C 130.0 130.0 27.3 117.0 22.4 104.0 18.2 91.0 14.6
25 °C 130.0 130.0 25.5 117.0 20.9 104.0 17.0 91.0 13.7
23 °C 130.0 130.0 23.8 117.0 19.6 104.0 16.0 91.0 12.9
21 °C 130.0 130.0 23.2 117.0 19.2 104.0 15.6 91.0 12.7
20 °C 130.0 130.0 23.0 117.0 19.0 104.0 15.5 91.0 12.6
19 °C 130.0 130.0 22.8 117.0 18.8 104.0 15.4 91.0 12.5
17 °C 130.0 130.0 22.4 117.0 18.5 104.0 15.1 91.0 12.3
15 °C 130.0 130.0 22.1 117.0 18.3 104.0 15.0 91.0 12.2

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 121.0 72.6 16.4 60.5 12.9 48.4 10.3 36.3 8.55
39 °C 122.9 73.8 16.1 61.5 12.7 49.2 10.1 36.9 8.43
37 °C 126.6 76.0 15.7 63.3 12.3 50.6 9.80 38.0 8.17
35 °C 130.0 78.0 15.2 65.0 11.9 52.0 9.50 39.0 7.91
33 °C 130.0 78.0 14.2 65.0 11.2 52.0 9.01 39.0 7.58
31 °C 130.0 78.0 13.3 65.0 10.6 52.0 8.55 39.0 7.25
30 °C 130.0 78.0 12.9 65.0 10.3 52.0 8.33 39.0 7.09
29 °C 130.0 78.0 12.5 65.0 9.96 52.0 8.12 39.0 6.94
27 °C 130.0 78.0 11.7 65.0 9.41 52.0 7.72 39.0 6.63
25 °C 130.0 78.0 11.0 65.0 8.89 52.0 7.33 39.0 6.33
23 °C 130.0 78.0 10.4 65.0 8.40 52.0 6.96 39.0 6.04
21 °C 130.0 78.0 10.2 65.0 8.30 52.0 6.90 39.0 6.02
20 °C 130.0 78.0 10.1 65.0 8.25 52.0 6.88 39.0 6.01
19 °C 130.0 78.0 10.1 65.0 8.21 52.0 6.85 39.0 6.00
17 °C 130.0 78.0 9.97 65.0 8.14 52.0 6.81 39.0 5.98
15 °C 130.0 78.0 9.87 65.0 8.08 52.0 6.78 39.0 5.97
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 145.0 145.0 32.2 130.5 26.6 116.0 22.0 101.5 18.2
13.0 11.8 145.0 145.0 33.4 130.5 27.6 116.0 22.6 101.5 18.6
11.0 9.8 145.0 145.0 35.0 130.5 28.7 116.0 23.4 101.5 19.1
9.0 7.9 145.0 145.0 36.6 130.5 29.9 116.0 24.3 101.5 19.7
7.0 6.0 145.0 145.0 38.6 130.5 31.3 116.0 25.3 101.5 20.4
5.0 4.1 140.1 140.1 38.0 126.1 30.8 112.1 24.9 98.1 20.1
3.0 2.2 135.1 135.1 37.4 121.5 30.4 108.0 24.5 94.5 19.8
0.0 -0.7 127.2 127.2 36.5 114.5 29.6 101.8 23.9 89.0 19.3
-3.0 -3.7 118.9 118.9 35.6 107.0 28.9 95.1 23.3 83.2 18.8
-5.0 -5.6 113.4 113.4 35.0 102.1 28.4 90.8 23.0 79.4 18.5
-7.0 -7.6 107.6 107.6 34.4 96.9 27.9 86.1 22.6 75.3 18.2
-10 -10.5 99.0 99.0 33.5 89.1 27.2 79.2 22.0 69.3 17.7
-14.5 -15.0 85.2 85.2 32.1 76.7 26.1 68.2 21.1 59.7 17.0

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 145.0 87.0 15.0 72.5 12.4 58.0 10.3 43.5 8.51
13.0 11.8 145.0 87.0 15.3 72.5 12.6 58.0 10.4 43.5 8.53
11.0 9.8 145.0 87.0 15.6 72.5 12.8 58.0 10.5 43.5 8.56
9.0 7.9 145.0 87.0 16.0 72.5 13.0 58.0 10.6 43.5 8.59
7.0 6.0 145.0 87.0 16.4 72.5 13.2 58.0 10.7 43.5 8.64
5.0 4.1 140.1 84.0 16.2 70.0 13.0 56.0 10.5 42.0 8.51
3.0 2.2 135.1 81.0 15.9 67.5 12.8 54.0 10.4 40.5 8.38
0.0 -0.7 127.2 76.3 15.5 63.6 12.5 50.9 10.1 38.2 8.18
-3.0 -3.7 118.9 71.3 15.1 59.4 12.2 47.5 9.87 35.7 7.97
-5.0 -5.6 113.4 68.1 14.9 56.7 12.0 45.4 9.70 34.0 7.84
-7.0 -7.6 107.6 64.6 14.6 53.8 11.8 43.1 9.53 32.3 7.70
-10 -10.5 99.0 59.4 14.2 49.5 11.5 39.6 9.28 29.7 7.50
-14.5 -15.0 85.2 51.1 13.7 42.6 11.0 34.1 8.90 25.6 7.19
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -68
11 Technical Specifications

MMY-AP4824HT8, AP4824T8 (48HP, 135kW system)


Cooling Compressor + Oudoor Fan Power consumption (kW)
Outdoor Unit 100% 90% 80% 70%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 125.6 125.6 41.9 113.1 34.1 100.5 27.4 87.9 21.7
39 °C 127.6 127.6 41.2 114.9 33.6 102.1 27.0 89.4 21.4
37 °C 131.5 131.5 40.0 118.3 32.6 105.2 26.2 92.0 20.8
35 °C 135.0 135.0 38.8 121.5 31.6 108.0 25.4 94.5 20.1
33 °C 135.0 135.0 35.8 121.5 29.2 108.0 23.5 94.5 18.7
31 °C 135.0 135.0 33.1 121.5 27.1 108.0 21.9 94.5 17.5
30 °C 135.0 135.0 31.9 121.5 26.1 108.0 21.1 94.5 16.9
29 °C 135.0 135.0 30.8 121.5 25.2 108.0 20.4 94.5 16.3
27 °C 135.0 135.0 28.6 121.5 23.5 108.0 19.0 94.5 15.3
25 °C 135.0 135.0 26.7 121.5 21.9 108.0 17.8 94.5 14.3
23 °C 135.0 135.0 24.9 121.5 20.5 108.0 16.7 94.5 13.4
21 °C 135.0 135.0 24.4 121.5 20.1 108.0 16.3 94.5 13.2
20 °C 135.0 135.0 24.1 121.5 19.9 108.0 16.2 94.5 13.1
19 °C 135.0 135.0 23.9 121.5 19.7 108.0 16.1 94.5 13.0
17 °C 135.0 135.0 23.5 121.5 19.4 108.0 15.8 94.5 12.8
15 °C 135.0 135.0 23.1 121.5 19.1 108.0 15.6 94.5 12.7

Compressor + Oudoor Fan Power consumption (kW)


Outdoor Unit 60% 50% 40% 30%
Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Cooling Capacity
Dry-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
40 °C 125.6 75.4 17.1 62.8 13.4 50.3 10.7 37.7 8.91
39 °C 127.6 76.6 16.8 63.8 13.2 51.1 10.5 38.3 8.78
37 °C 131.5 78.9 16.3 65.7 12.8 52.6 10.2 39.4 8.51
35 °C 135.0 81.0 15.8 67.5 12.4 54.0 9.88 40.5 8.24
33 °C 135.0 81.0 14.8 67.5 11.7 54.0 9.37 40.5 7.89
31 °C 135.0 81.0 13.8 67.5 11.0 54.0 8.90 40.5 7.56
30 °C 135.0 81.0 13.4 67.5 10.7 54.0 8.67 40.5 7.39
29 °C 135.0 81.0 13.0 67.5 10.4 54.0 8.45 40.5 7.23
27 °C 135.0 81.0 12.2 67.5 9.79 54.0 8.03 40.5 6.91
25 °C 135.0 81.0 11.5 67.5 9.25 54.0 7.63 40.5 6.60
23 °C 135.0 81.0 10.8 67.5 8.74 54.0 7.24 40.5 6.30
21 °C 135.0 81.0 10.6 67.5 8.64 54.0 7.18 40.5 6.27
20 °C 135.0 81.0 10.6 67.5 8.59 54.0 7.16 40.5 6.26
19 °C 135.0 81.0 10.5 67.5 8.55 54.0 7.13 40.5 6.25
17 °C 135.0 81.0 10.4 67.5 8.47 54.0 7.09 40.5 6.24
15 °C 135.0 81.0 10.3 67.5 8.41 54.0 7.06 40.5 6.22
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 27.0°C dry-bulb / 19.0°C wet bulb

Heating Compressor + Oudoor Fan Power consumption (kW)


100% 90% 80% 70%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 150.0 150.0 34.0 135.0 28.2 120.0 23.2 105.0 19.1
13.0 11.8 150.0 150.0 35.4 135.0 29.2 120.0 23.9 105.0 19.6
11.0 9.8 150.0 150.0 37.0 135.0 30.3 120.0 24.8 105.0 20.2
9.0 7.9 150.0 150.0 38.8 135.0 31.6 120.0 25.7 105.0 20.8
7.0 6.0 150.0 150.0 40.8 135.0 33.1 120.0 26.8 105.0 21.5
5.0 4.1 144.9 144.9 40.2 130.4 32.6 115.9 26.4 101.4 21.2
3.0 2.2 139.7 139.7 39.6 125.7 32.1 111.8 25.9 97.8 20.9
0.0 -0.7 131.6 131.6 38.6 118.4 31.4 105.3 25.3 92.1 20.4
-3.0 -3.7 123.0 123.0 37.6 110.7 30.6 98.4 24.7 86.1 19.8
-5.0 -5.6 117.4 117.4 37.0 105.6 30.1 93.9 24.3 82.1 19.5
-7.0 -7.6 111.3 111.3 36.4 100.2 29.5 89.1 23.9 77.9 19.2
-10 -10.5 102.4 102.4 35.4 92.2 28.8 82.0 23.2 71.7 18.7
-14.5 -15.0 88.2 88.2 33.9 79.3 27.6 70.5 22.3 61.7 17.9

Compressor + Oudoor Fan Power consumption (kW)


60% 50% 40% 30%
Outdoor Unit Outdoor Unit 100%
Capacity Capacity Capacity Capacity
Heating Capacity
Dry-Bulb Wet-Bulb TC PI TC PI TC PI TC PI
(kW)
(°C) (°C) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
15.0 13.7 150.0 90.0 15.7 75.0 13.0 60.0 10.8 45.0 9.06
13.0 11.8 150.0 90.0 16.0 75.0 13.2 60.0 10.9 45.0 9.06
11.0 9.8 150.0 90.0 16.4 75.0 13.4 60.0 11.0 45.0 9.08
9.0 7.9 150.0 90.0 16.8 75.0 13.6 60.0 11.1 45.0 9.10
7.0 6.0 150.0 90.0 17.3 75.0 13.9 60.0 11.2 45.0 9.14
5.0 4.1 144.9 86.9 17.0 72.5 13.7 58.0 11.0 43.5 9.00
3.0 2.2 139.7 83.8 16.7 69.9 13.4 55.9 10.9 41.9 8.86
0.0 -0.7 131.6 79.0 16.3 65.8 13.1 52.6 10.6 39.5 8.65
-3.0 -3.7 123.0 73.8 15.9 61.5 12.8 49.2 10.3 36.9 8.43
-5.0 -5.6 117.4 70.4 15.7 58.7 12.6 46.9 10.2 35.2 8.29
-7.0 -7.6 111.3 66.8 15.4 55.7 12.4 44.5 10.0 33.4 8.14
-10 -10.5 102.4 61.5 15.0 51.2 12.0 41.0 9.73 30.7 7.93
-14.5 -15.0 88.2 52.9 14.4 44.1 11.5 35.3 9.33 26.4 7.60
TC : Total Capacity PI : Power Input
Indoor air temperature conditions : 20.0°C dry-bulb

11 -69
11 Technical Specifications

11-1-8. Sound Pressure level data (NC CURVE)


Outdoor unit
Microphone

Single unit
MMY-MAP0501HT8, MAP0501T8, MAP0501HT7 <SMMS> MMY-MAP0601HT8, MAP0601T8, MAP0601HT7 <SMMS>
Cooling Heating Cooling Heating
Sound pressure Level (dB(A)) Sound pressure Level (dB(A))
55.0 55.0 56.0 56.0
 

Cooling Cooling

 Heating  Heating
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 
0%
0%

 Audibiliy limits of  Audibiliy limits of


contuonous white noise 0% contuonous white noise 0%

 
               
Octave band center frequency(Hz) Octave band center frequency(Hz)

MMY-MAP0804HT8, MAP0804T8, MAP0804HT7 MMY-MAP1004HT8, MAP1004T8, MAP1004HT7


Cooling Heating Cooling Heating
Sound pressure Level (dB(A)) Sound pressure Level (dB(A))
55.0 56.0 57.0 58.0
 

Cooling Cooling

 Heating  Heating
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 
0%
0%

 Audibility limits of  Audibility limits of


continous white noise continous white noise
0% 0%

 
               
Octave band center frequency(Hz) Octave band center frequency(Hz)

11 -70
11 Technical Specifications

MMY-MAP1204HT8, MAP1204T8, MAP1204HT7 MMY-MAP1404HT8, MAP1404T8, MAP1404HT7


Cooling Heating Cooling Heating
Sound pressure Level (dB(A)) Sound pressure Level (dB(A))
59.0 61.0 60.0 62.0
 

Cooling Cooling

 Heating  Heating
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)


 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 Audibility limits of  Audibility limits of


continous white noise continous white noise
0% 0%

 
               
Octave band center frequency(Hz) Octave band center frequency(Hz)

MMY-MAP1604HT8, MAP1604T8, MAP1604HT7


Cooling Heating
Sound pressure Level (dB(A))
61.0 63.0


Cooling

 Heating
Octave band sound pressure level (dB)


0%


0%


0%


0%


0%

 Audibility limits of
continous white noise
0%


       
Octave band center frequency(Hz)

11 -71
11 Technical Specifications

Combination
• Standard model
MMY-AP1814HT8, AP1814T8, AP1814HT7 MMY-AP2014HT8, AP2014T8, AP2014HT7
Cooling Heating Cooling Heating
Sound pressure Level (dB(A)) Sound pressure Level (dB(A))
59.5 60.5 60.0 61.0
 

Cooling Cooling

 Heating  Heating

Octave band sound pressure level (dB)


Octave band sound pressure level (dB)

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 Audibility limits of  Audibility limits of


continous white noise continous white noise
0% 0%

 
               
Octave band center frequency(Hz) Octave band center frequency(Hz)

MMY-AP2214HT8, AP2214T8, AP2214HT7 MMY-AP2414HT8, AP2414T8, AP2414HT7


Cooling Heating Cooling Heating
Sound pressure Level (dB(A)) Sound pressure Level (dB(A))
61.5 63.0 62.0 64.0
 

Cooling Cooling

 Heating  Heating
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 Audibility limits of  Audibility limits of


continous white noise continous white noise
0% 0%

 
               
Octave band center frequency(Hz) Octave band center frequency(Hz)

MMY-AP2614HT8, AP2614T8, AP2614HT7 MMY-AP2814HT8, AP2814T8, AP2814HT7


Cooling Heating Cooling Heating
Sound pressure Level (dB(A)) Sound pressure Level (dB(A))
62.5 64.5 63.5 65.5
 

Cooling Cooling

 Heating  Heating
Octave band sound pressure level (dB)
Octave band sound pressure level (dB)

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 Audibility limits of  Audibility limits of


continous white noise continous white noise
0% 0%

 
               
Octave band center frequency(Hz) Octave band center frequency(Hz)

11 -72
11 Technical Specifications

MMY-AP3014HT8, AP3014T8, AP3014HT7 MMY-AP3214HT8, AP3214T8, AP3214HT7


Cooling Heating Cooling Heating
Sound pressure Level (dB(A)) Sound pressure Level (dB(A))
63.5 65.5 64.0 66.0
 

Cooling Cooling

 Heating  Heating
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)


 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 Audibility limits of  Audibility limits of


continous white noise continous white noise
0% 0%

 
               
Octave band center frequency(Hz) Octave band center frequency(Hz)

MMY-AP3414HT8, AP3414T8, AP3414HT7 MMY-AP3614HT8, AP3614T8, AP3614HT7


Cooling Heating Cooling Heating
Sound pressure Level (dB(A)) Sound pressure Level (dB(A))
63.5 65.0 64.0 66.0
 

Cooling Cooling

 Heating  Heating
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 Audibility limits of  Audibility limits of


continous white noise continous white noise
0% 0%

 
               
Octave band center frequency(Hz) Octave band center frequency(Hz)

MMY-AP3814HT8, AP3814T8, AP3814HT7 MMY-AP4014HT8, AP4014T8, AP4014HT7


Cooling Heating Cooling Heating
Sound pressure Level (dB(A)) Sound pressure Level (dB(A))
64.5 66.0 64.5 66.5
 

Cooling Cooling

 Heating  Heating
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 Audibility limits of  Audibility limits of


continous white noise continous white noise
0% 0%

 
               
Octave band center frequency(Hz) Octave band center frequency(Hz)

11 -73
11 Technical Specifications

MMY-AP4214HT8, AP4214T8, AP4214HT7 MMY-AP4414HT8, AP4414T8, AP4414HT7


Cooling Heating Cooling Heating
Sound pressure Level (dB(A)) Sound pressure Level (dB(A))
65.0 67.0 65.5 67.5
 

Cooling Cooling

 Heating  Heating
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)


 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 Audibility limits of  Audibility limits of


continous white noise continous white noise
0% 0%

 
               
Octave band center frequency(Hz) Octave band center frequency(Hz)

MMY-AP4614HT8, AP4614T8, AP4614HT7 MMY-AP4814HT8, AP4814T8, AP4814HT7


Cooling Heating Cooling Heating
Sound pressure Level (dB(A)) Sound pressure Level (dB(A))
65.5 67.5 66.0 68.0
 

Cooling Cooling

 Heating  Heating
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 Audibility limits of  Audibility limits of


continous white noise continous white noise
0% 0%

 
               
Octave band center frequency(Hz) Octave band center frequency(Hz)

• High efficiency model


MMY-AP1624HT8, AP1624T8, AP1624HT7 MMY-AP2424HT8, AP2424T8, AP2424HT7
Cooling Heating Cooling Heating
Sound pressure Level (dB(A)) Sound pressure Level (dB(A))
58.0 59.0 60.0 61.0
 

Cooling Cooling

 Heating  Heating
Octave band sound pressure level (dB)
Octave band sound pressure level (dB)

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 Audibility limits of  Audibility limits of


continous white noise continous white noise
0% 0%

 
               
Octave band center frequency(Hz) Octave band center frequency(Hz)

11 -74
11 Technical Specifications

MMY-AP2624HT8, AP2624T8, AP2624HT7 MMY-AP2824HT8, AP2824T8, AP2824HT7


Cooling Heating Cooling Heating
Sound pressure Level (dB(A)) Sound pressure Level (dB(A))
60.5 61.5 61.5 62.5
 

Cooling Cooling

 Heating  Heating

Octave band sound pressure level (dB)


Octave band sound pressure level (dB)

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 Audibility limits of  Audibility limits of


continous white noise continous white noise
0% 0%

 
               
Octave band center frequency(Hz) Octave band center frequency(Hz)

MMY-AP3024HT8, AP3024T8, AP3024HT7 MMY-AP3224HT8, AP3224T8, AP3224HT7


Cooling Heating Cooling Heating
Sound pressure Level (dB(A)) Sound pressure Level (dB(A))
62.0 63.0 61.0 62.0
 

Cooling Cooling

 Heating  Heating
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 Audibility limits of  Audibility limits of


continous white noise continous white noise
0% 0%

 
               
Octave band center frequency(Hz) Octave band center frequency(Hz)

MMY-AP3424HT8, AP3424T8, AP3424HT7 MMY-AP3624HT8, AP3624T8, AP3624HT7


Cooling Heating Cooling Heating
Sound pressure Level (dB(A)) Sound pressure Level (dB(A))
62.0 63.0 62.5 63.5
 

Cooling Cooling

 Heating  Heating
Octave band sound pressure level (dB)
Octave band sound pressure level (dB)

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 Audibility limits of  Audibility limits of


continous white noise continous white noise
0% 0%

 
               
Octave band center frequency(Hz) Octave band center frequency(Hz)

11 -75
11 Technical Specifications

MMY-AP3824HT8, AP3824T8, AP3824HT7 MMY-AP4024HT8, AP4024T8, AP4024HT7


Cooling Heating Cooling Heating
Sound pressure Level (dB(A)) Sound pressure Level (dB(A))
63.0 64.0 63.0 64.0
 

Cooling Cooling

 Heating  Heating
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)


 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 Audibility limits of  Audibility limits of


continous white noise continous white noise
0% 0%

 
               
Octave band center frequency(Hz) Octave band center frequency(Hz)

MMY-AP4224HT8, AP4224T8, AP4224HT7 MMY-AP4424HT8, AP4424T8, AP4424HT7


Cooling Heating Cooling Heating
Sound pressure Level (dB(A)) Sound pressure Level (dB(A))
64.0 65.0 64.5 66.0
 

Cooling Cooling

 Heating  Heating
Octave band sound pressure level (dB)
Octave band sound pressure level (dB)

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 Audibility limits of  Audibility limits of


continous white noise continous white noise
0% 0%

 
               
Octave band center frequency(Hz) Octave band center frequency(Hz)

MMY-AP4624HT8, AP4624T8, AP4624HT7 MMY-AP4824HT8, AP4824T8, AP4824HT7


Cooling Heating Cooling Heating
Sound pressure Level (dB(A)) Sound pressure Level (dB(A))
65.0 66.5 65.0 67.0
 

Cooling Cooling

 Heating  Heating
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 
0% 0%

 Audibility limits of  Audibility limits of


continous white noise continous white noise
0% 0%

 
               
Octave band center frequency(Hz) Octave band center frequency(Hz)

11 -76
11 Technical Specifications

11-2. Indoor Unit


11-2-1 4-way Air Discharge Cassette Type

4-way Air Discharge


Cassette Type

MMU-AP0092H / MMU-AP0122H
MMU-AP0152H / MMU-AP0182H
MMU-AP0242H / MMU-AP0272H
MMU-AP0302H / MMU-AP0362H
MMU-AP0482H / MMU-AP0562H

Contents
1. Specifications
2. Dimensions
3. Wiring diagram
4. Center of Gravity
5. Electrical characteristics
6. Sensible capacity table
7. Air throw distance chart
8. Sound characteristics (NC-Curve)
9. Fresh air intake (Design guide)
10. Branching duct (Design guide)
11. Accessories

11 -77
11 Technical Specifications

1. Specifications

Model name MMU- AP0092H AP0122H AP0152H AP0182H AP0242H AP0272H AP0302H AP0362H AP0482H AP0562H
Cooling/Heating capacity (Note 1) (kW) 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3 7.1/8.0 8.0/9.0 9.0/10.0 11.2/12.5 14.0/16.0 16.0/18.0

Power supply 1 phase 50Hz 230V (220-240V) (Sepatate power supply for indoor units is required.)

Electical Running current (A) 0.23 0.27 0.29 0.38 0.43 0.73 0.88
characteristics
Power consumption (kW) 0.021 0.023 0.026 0.036 0.043 0.088 0.112

Starting current (A) 0.30 0.33 0.36 0.42 0.59 0.87 1.23 1.26

Main unit Heat-insulating material attached Zinc hot dipping steel plate

Appearance Ceiling Model RBC-U31PG(W)-E / RBC-U31PGS(W)-E / RBC-U31PGS(WS)-E


panel
Panel color White (2.5GY9.0/0.5)

Hight (mm) 256 319

Main unit Width (mm) 840

Outer Depth (mm) 840


dimention
Hight (mm) 30
Ceiling
panel Width (mm) 950

Depth (mm) 950

Main unit (kg) 18 20 25


Total weight
Ceiling panel (kg) 4.0

Heat exchanger Fined tube

Soundproof / Heat-insulating material Non-flammable insulation

Fan Turbo fan

Standard air flow 930/ 1050/ 1320/ 1970/ 2130/ 2130/


Fan unit (m³/h) 800/730/680 1290/920/800
(High/Mid/Low) 830/790 920/800 1100/850 1430/1070 1430/1130 1520/1230

Motor output (W) 14 20 68 72

Air filter Standard filter (Long life filter)

Controller Remote controller

Gas pipe (mm) φ9.5 φ12.7 φ15.9


Connecting
Liquid pipe (mm) φ6.4 φ9.5
pipe
Drain port (Nominal dia.mm) 25 (Polyvinyl chloride tube)

Sound pressure level (Note 2)


(dB(A)) 30/29/27 31/29/27 32/29/27 35/31/28 38/33/30 43/38/32 46/38/33 46/40/33
(High/Med./Low)

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based
on the reference piping.
The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated values due to the
effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB

11 -78
11 Technical Specifications

2. Dimensions

MMU-AP0092H, AP0122H
860 to 910 Ceiling open dimension 1000 or more

15 or more
1000 or more
860 to 910 Ceiling open dimension
An obstacle
1000 or more

15 or more
The space that is necessary
for equipping and service

661 or less
Standing
300 or less

Take-in port of wiring Bottom face of ceiling

850 or less
Standing
30
44
112

129
172

189
77
74 105

Indoor unit Bottom face of ceiling


Refrigerant pipe connecting port
Ø6.4 (Liquid side) Drain pipe Drain upstanding size
Refrigerant pipe connecting port 397.5 105 337.5 connecting port
Ø9.5 (Gas side) (Material: PP)
157 263
Bottom face of ceiling 106.5 72 241.5 For branch duct knockout square hole Ø150
129
Electric parts box Hanging bolt M10 or Ø3/8(procured by locally)
77 10 5 74
950 Panel external dimension
256
780 Hanging bolt pitch
132
323
Ø162
287.5

74
690 ± 20 Hanging bolt pitch
950 Panel external dimension
840 Unit external dimension

129 For branch duct


416.5
408

351

knockout square
80

105 77
hole Ø150
135 105

105
240

16.5
105

384

Ceiling panel
45
207.5

(sold separately)

105
Bottom face
Ø162 269 of ceiling
30
Z

64
57

For branch duct knockout 840 Unit external dimension


32

square hole Ø150


28 61

(2 positions)
.5

362.5 105 372.5 Knockout for simple


OA for Ø100
74

For branch duct knockout


square hole Ø150
Bottom face of ceiling
105

15
5
18
7

Z view
Bottom face of ceiling Indoor unit
129

5
77

Bottom face of ceiling


12

Unit : mm

11 -79
11 Technical Specifications

MMU-AP0152H, AP0182H
860 to 910 Ceiling open dimension 1000 or more

15 or more
1000 or more
860 to 910 Ceiling open dimension
An obstacle
1000 or more

15 or more
The space that is necessary
for equipping and service

661 or less
Standing
300 or less

850 or less
Standing
Take-in port of wiring Bottom face of ceiling
30
44
112

129
172

Indoor unit Bottom face of ceiling

189
77
74 105

Drain upstanding size


Refrigerant pipe connecting port
Ø6.4 (Liquid side) Drain pipe
Refrigerant pipe connecting port 397.5 105 337.5 connecting port
Ø12.7 (Gas side) (Material: PP)
157 263
Bottom face of ceiling 106.5 72 241.5 For branch duct knockout square hole Ø150
129 Electric parts box
77 10 5 74 Hanging bolt M10 or Ø3/8 (procured locally)
950 Panel external dimension
256
780 Hanging bolt pitch
132
323
Ø162
287.5

74
690 ± 20 Hanging bolt pitch
950 Panel external dimension
840 Unit external dimension

129 For branch duct


416.5
408

351

knockout square
80

105 77
hole Ø150
135 105

105
240

16.5
105

384

Ceiling panel
45
207.5

(sold separately)

105
Bottom face
Ø162 269 of ceiling
30
Z
57

64

For branch duct knockout 840 Unit external dimension


32

square hole Ø150


28 61

(2 positions) 362.5 105 372.5


.5
74

For branch duct knockout


square hole Ø150
Knockout for simple OA for Ø100
105

15
5
18
7

Bottom face of ceiling

Bottom face of ceiling Z view


129

5
77

Indoor unit

Bottom face of ceiling


12

Unit : mm

11 -80
11 Technical Specifications

MMU-AP0242H, AP0272H, AP0302H


860 to 910 Ceiling open dimension 1000 or more

15 or more
1000 or more
860 to 910 Ceiling open dimension
An obstacle
1000 or more

15 or more
The space that is necessary
for equipping and service

661 or less
Standing
300 or less

850 or less
Standing
Take-in port of wiring Bottom face of ceiling
30
44
112

129
172

Indoor unit Bottom face of ceiling

189
77
74 105

Drain upstanding size


Refrigerant pipe connecting port
Ø9.5 (Liquid side) Drain pipe
Refrigerant pipe connecting port 397.5 105 337.5 connecting port
Ø15.9 (Gas side) (Material: PP)
157 263
Bottom face of ceiling 106.5 72 241.5 For branch duct knockout square hole Ø150
129 Electric parts box
4
77 10 5 74 Hanging bolt M10 or Ø3/8 (procured locally)
950 Panel external dimension
256
780 Hanging bolt pitch
132
323
Ø162
162
287.5

74
690 ± 20 Hanging bolt pitch
950 Panel external dimension
840 Unit external dimension

129 For branch duct


416.5
408

351

knockout square
80

105 77
hole Ø150
135 105

105
240

16.5
105

384

Ceiling panel
45
207.5

(sold separately)

105
Bottom face
Ø162 269 of ceiling
30
Z
57

64

For branch duct knockout 840 Unit external dimension


32

square hole Ø150


28 61

(2 positions) 362.5 105 372.5


.5
74

For branch duct knockout


square hole Ø150
Knockout for simple OA for Ø100
105

15
5
18
7

Bottom face of ceiling

Bottom face of ceiling Z view


129

5
77

Indoor unit

Bottom face of ceiling


12

Unit : mm

11 -81
11 Technical Specifications

MMU-AP0362H, AP0482H, AP0562H


1000 or more
860 to 910 Ceiling open dimension

15 or more
1000 or more
860 to 910 Ceiling open dimension
An obstacle
1000 or more

15 or more
The space that is necessary
for equipping and service

661 or less
Standing
300 or less

850 or less
Take-in port of wiring Bottom face of ceiling

Standing
30
44
112

129
172

189
77
105

Indoor unit Bottom face of ceiling


Refrigerant pipe connecting port
Drain pipe Drain upstanding size
137

Ø9.5 (Liquid side)


connecting port
Refrigerant pipe connecting port (Material: PP)
Ø15.9 (Gas side) 397.5 105 337.5
157 263
106.5 72 241.5 For branch duct knockout square hole Ø150

Bottom face of ceiling


Electric parts box Hanging bolt M10 or Ø3/8 (procured locally)
129
77 10 5 137 950 Panel external dimension 319
780 Hanging bolt pitch 132
323
Ø162

137
287.5

690 ± 20 Hanging bolt pitch


950 Panel external dimension

129 For branch duct


840 Unit external dimension

416.5
408

351

105 77 knockout square


80

hole Ø150
207.5 105 135 105

105
240

16.5
384

Ceiling panel
45

(sold separately)

105 Bottom face


Ø162 269 30 of ceiling
Z
57

64

840 Unit external dimension


32

For branch duct 362.5 105 372.5


28 1

knockout square hole Ø150


6
.5
137

(2 positions)

For branch duct knockout Knockout for simple OA for Ø100


square hole Ø150
15
105

5
18
7

Bottom face of ceiling

Bottom face of ceiling Z view


129

5
77

Indoor unit

Bottom face of ceiling

Unit : mm

11 -82
11 Technical Specifications

3. Wiring diagram

MMU-AP0092H, AP0122H, AP0152H, AP0182H, AP0242H,


AP0272H, AP0302H, AP0362H, AP0482H, AP0562H

Flow Selector unit (Option) LM1 LM3 LM2 LM4


1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5
Control P.C. board (BLU) 1 2 3 4 5 (WHI) 1 2 3 4 5 1 2 3 4 5 (RED) 1 2 3 4 5 (BLK)
(MCC-1431) PMV FM
CN01 CN02
(RED) (GRN)

1 2 3 1 2 3 4 5 6 4 3 1 2 5
1 2 3 1 2 3 4 5 6 4 3 1 2 5

1 2 3 4 5 1 2 3 4 5 6 1 2 3 1 3 5 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Flow
Selector unit 1 2 3 4 5 1 2 3 4 5 6 1 2 3 1 3 5 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Earth screw
CN81 CN82 CN334 CN333 CN510 1 1
(BLK) (BLU) (WHI) (WHI) (WHI) CN504 DM
(WHI) 2 2
Motor drive
Indoor unit circuit 1 1
Fuse, F01 Fuse, F02 CN34
Earth screw RED T6.3A, 250V~ T3.15A, 250V~ 2 FS
~ + (RED)
1 1 DC20V 3 3
CN67 Power supply DC15V
(BLK) circuit DC12V CN104 1 1
3 3 DC7V
~ – (YEL) 2 2
WHI TA
SW501 CN102 1 1
R(L) S(N) ON (RED) 2 2
Control P.C. board for Indoor unit TCJ
Power supply CN101 1 1
single phase (MCC-1570) 1 2 (BLK) 2 2
220–240V ~ 50Hz (High Wall setting) TC2
220V ~ 60Hz 1 1
CN100 2
BLK (BRW)
P01 CN71 (CHK) 3 3 TC1
1
1 CN66
CN519 2
2 (WHI) CN72 (DISP)
(WHI) 3
1 1 CN40 4
CN508
2 2 (BLU) (RED)
1
CN41 CN309 CN20 CN60 CN32 CN61 CN50 CN70 CN73 CN80
(BLU) (YEL) (BLU) (WHI) (WHI) (YEL) (WHI) (WHI) (RED) (GRN) 2

1 2 3 1 3 1 2 3 4 5 1 2 3 4 5 6 1 2 1 2 3 4 5 6 1 2 3 4 5 1 2 1 2 1 2 3
1 3 1 3 (GRL) (OPTION) (FAN DRIVE) T10 (FILTER) (EXCT) (PNL)
BLU BLU BLK BLK

TR 1 2
U1 U2 A B 1 2
Color Indication
BLK CN01 (WHI)
3 3
CN02 RED : RED GRY : GRAY
WHI (BLU) WHI : WHITE PNK : PINK
1 1
CN03 (RED) YEL : YELLOW ORN : ORANGE
WHI BLK 1 2 BLU : BLUE GRN : GREEN
1 2 BLK : BLACK BRW : BROWN
1 2
U1 U2 A B X Y
1 2
Outdoor CN001
unit (WHI) Network adaptor
Symbol Parts name
(Option) FM Fan Motor
Wired Adapter
Remote for Wireless TA Indoor temp. sensor
controller Remote controller
TC1, TC2, TCJ Temp. sensor
LM1, 2, 3, 4 Louver Motor
DM Drain pump Motor
1. indicates the terminal block. FS Float Switch
Letter at inside indicates the terminal number. PMV Pulse Motor Valve
2. A dotted line and broken line indicate the wiring site. Power supply Transformer
TR
3. indicates the control P.C. board. (Fot Nwtwork adapter)

11 -83
11 Technical Specifications

4. Center of Gravity

Total weight
Model name X(mm) Y(mm) Z(mm) Main unit Ceiling panel
(kg) (kg)
MMU-AP0092H
18
MMU-AP0122H
MMU-AP0152H
MMU-AP0182H 455 154
MMU-AP0242H 20
470 4.0
MMU-AP0272H
MMU-AP0302H
MMU-AP0362H
MMU-AP0482H 450 184 25
MMU-AP0562H

5. Electrical characteristics

Nominal Voltage Voltage Range Fan Motor Power Supply


Type Model
(V-Ph-Hz) Min Max kW FLA MCA MOCP
MMU-AP0092H 230-1-50 198 264 0.014 0.63 0.79 15
MMU-AP0122H 230-1-50 198 264 0.014 0.63 0.79 15
MMU-AP0152H 230-1-50 198 264 0.014 0.80 1.00 15
MMU-AP0182H 230-1-50 198 264 0.014 0.80 1.00 15
4-Way Air MMU-AP0242H 230-1-50 198 264 0.020 0.87 1.09 15
50Hz Discharge
Cassette Type MMU-AP0272H 230-1-50 198 264 0.020 0.87 1.09 15
MMU-AP0302H 230-1-50 198 264 0.020 0.87 1.09 15
MMU-AP0362H 230-1-50 198 264 0.068 1.15 1.44 15
MMU-AP0482H 230-1-50 198 264 0.072 1.15 1.44 15
MMU-AP0562H 230-1-50 198 264 0.072 1.15 1.44 15

MCA : Minimum Circuit Amps FLA : Full Load Amps


MOCP : Maximum Overcurrent Protection (Amps)

11 -84
11 Technical Specifications

6. Sensible capacity table

4-way Discharge Cassette Type (MMU-AP***2H)


indoor air temp.
outdorr air 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
unit size
temp. °CDB 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
12.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
14.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
16.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
18.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
20.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
21.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
23.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
009
25.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
27.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
29.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
31.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
33.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
35.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
37.0 2.2 1.8 2.5 1.9 2.6 2.0 2.7 2.0 2.8 2.0 3.0 2.0 3.1 2.0
39.0 2.2 1.8 2.4 1.9 2.6 2.0 2.6 2.0 2.7 2.0 2.9 2.0 3.0 1.9
10.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.5
12.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.5
14.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.5
16.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.5
18.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.5
20.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.5
21.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.5
23.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.5
012
25.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.5
27.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.5
29.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.5
31.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.5
33.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.5
35.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.5
37.0 2.9 2.2 3.2 2.4 3.4 2.5 3.5 2.5 3.6 2.5 3.8 2.5 4.0 2.4
39.0 2.8 2.2 3.1 2.3 3.3 2.5 3.4 2.4 3.5 2.4 3.7 2.4 3.9 2.4
10.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
12.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
14.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
16.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
18.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
20.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
21.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
23.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
015
25.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
27.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
29.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
31.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
33.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
35.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
37.0 3.6 2.7 4.0 2.9 4.2 3.1 4.4 3.1 4.5 3.1 4.7 3.1 5.0 3.0
39.0 3.5 2.7 3.8 2.8 4.1 3.0 4.2 3.0 4.4 3.0 4.6 3.0 4.8 2.9
10.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
12.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
14.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
16.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
18.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
20.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
21.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
23.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
018
25.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
27.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
29.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
31.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
33.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
35.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
37.0 4.5 3.4 4.9 3.7 5.3 3.9 5.4 3.9 5.6 3.9 5.9 3.8 6.2 3.7
39.0 4.3 3.3 4.8 3.6 5.1 3.8 5.3 3.8 5.4 3.8 5.7 3.7 6.0 3.6

TC: Total Capacity [kW]


SHC: Sensible Capacity [kW]

11 -85
11 Technical Specifications

4-way Discharge Cassette Type (MMU-AP***2H)


indoor air temp.
outdorr air 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
unit size
temp. °CDB 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.7
12.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.7
14.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.7
16.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.7
18.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.7
20.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.7
21.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.7
23.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.7
024
25.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.7
27.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.7
29.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.7
31.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.7
33.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.7
35.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.7
37.0 5.6 4.2 6.2 4.5 6.7 4.8 6.9 4.7 7.1 4.7 7.5 4.7 7.8 4.6
39.0 5.5 4.1 6.1 4.4 6.5 4.6 6.7 4.6 6.9 4.6 7.3 4.6 7.6 4.5
10.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.3
12.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.3
14.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.3
16.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.3
18.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.3
20.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.3
21.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.3
23.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.3
027
25.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.3
27.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.3
29.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.3
31.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.3
33.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.3
35.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.3
37.0 6.4 4.7 7.0 5.0 7.5 5.3 7.7 5.3 8.0 5.3 8.4 5.3 8.8 5.2
39.0 6.2 4.6 6.8 4.9 7.3 5.2 7.5 5.2 7.8 5.2 8.2 5.1 8.6 5.0
10.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
12.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
14.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
16.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
18.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
20.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
21.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
23.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
030
25.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
27.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
29.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
31.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
33.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
35.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
37.0 7.2 5.3 7.9 5.7 8.5 6.0 8.7 6.0 9.0 6.0 9.5 5.9 9.9 5.8
39.0 7.0 5.2 7.7 5.5 8.2 5.9 8.5 5.8 8.7 5.8 9.2 5.8 9.7 5.6
10.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.5
12.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.5
14.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.5
16.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.5
18.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.5
20.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.5
21.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.5
23.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.5
036
25.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.5
27.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.5
29.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.5
31.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.5
33.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.5
35.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.5
37.0 8.9 6.6 9.8 7.0 10.5 7.5 10.8 7.5 11.2 7.5 11.8 7.4 12.4 7.2
39.0 8.7 6.4 9.6 6.8 10.2 7.3 10.5 7.2 10.9 7.2 11.5 7.2 12.0 7.0

TC: Total Capacity [kW]


SHC: Sensible Capacity [kW]

11 -86
11 Technical Specifications

4-way Discharge Cassette Type (MMU-AP***2H)


indoor air temp.
outdorr air 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
unit size
temp. °CDB 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
12.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
14.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
16.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
18.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
20.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
21.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
23.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
048
25.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
27.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
29.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
31.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
33.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
35.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
37.0 11.1 8.4 12.3 9.0 13.1 9.5 13.6 9.5 14.0 9.5 14.8 9.4 15.4 9.2
39.0 10.8 8.2 12.0 8.7 12.8 9.2 13.2 9.2 13.6 9.2 14.4 9.1 15.0 8.9
10.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.6
12.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.6
14.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.6
16.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.6
18.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.6
20.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.6
21.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.6
23.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.6
056
25.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.6
27.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.6
29.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.6
31.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.6
33.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.6
35.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.6
37.0 12.7 9.4 14.1 10.1 15.0 10.7 15.5 10.6 16.0 10.6 16.9 10.5 17.7 10.3
39.0 12.4 9.2 13.7 9.8 14.6 10.4 15.1 10.4 15.5 10.4 16.4 10.3 17.2 10.0

TC: Total Capacity [kW]


SHC: Sensible Capacity [kW]

11 -87
11 Technical Specifications

7. Air throw distance chart

MMU-AP0092H / AP0122H MMU-AP0152H / AP0152H


Adv. wind speed : 4.9 Adv. wind speed : 4.3
2.8 2.8

0.7m/s 0.7m/s

0.5m/s 0.5m/s
2 2
Ceiling height (m)

Ceiling height (m)


0.3m/s
0.3m/s

1 1

0 1 2 3 4 5 0 1 2 3 4 5
Horizontal distance (m) Horizontal distance (m)

MMU-AP0242H/AP0272H/AP0302H MMU-AP0362H
Adv. wind speed : 5.4 Adv. wind speed : 5.4
3.0 3.9

0.7m/s
0.7m/s

0.5m/s 0.5m/s
Ceiling height (m)

0.3m/s
0.3m/s
Ceiling height (m)

1 2 3 4 5
Horizontal distance (m)

1 2 3 4 5
Horizontal distance

MMU-AP0482H / AP0561H MMU-AP0362H / AP0482H / AP0562H (High ceiling 3)


Adv. wind speed : 8.7 Adv. wind speed : 9.4
3.9 4.5
0.7m/s
0.7m/s
0.5m/s
0.5m/s
0.3m/s

0.3m/s
Ceiling height (m)
Ceiling height (m)

1 2 3 4 5
Horizontal distance (m)

1 2 3 4 5
Horizontal distance (m)

11 -88
11 Technical Specifications

8. Sound characteristics (NC-Curve)

MMU-AP0092H/AP0122H
Sound pressure HH-H-L
level(dB)(A) 30-29-27

90
HH
H
80
L

Octave band sound pressure level(dB


70 NC-70

60
NC-60

50
NC-50

1.5m 40
NC-40

30
Microphone NC-30

20
Audibility limits of NC-20
continous white level
10
63 125 250 500 1000 2000 4000 8000
Octave band center frequency(Hz)

MMU-AP0152H MMU-AP0182H
Sound pressure HH-H-L Sound pressure HH-H-L
level(dB)(A) 31-29-27 level(dB)(A) 32-29-27

90 90
HH HH

H H
80 80
L L
Octave band sound pressure level(dB

Octave band sound pressure level(dB

70 NC-70 70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 20
Audibility limits of NC-20 Audibility limits of NC-20
continous white level continous white level
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

MMU-AP0242H/AP0272H MMU-AP0302H
Sound pressure HH-H-L Sound pressure HH-H-L
level(dB)(A) 35-31-28 level(dB)(A) 38-33-30
90 90
HH HH

H H
80 80
L
L
Octave band sound pressure level(dB

70
Octave band sound pressure level(dB

NC-70 70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 20
Audibility limits of NC-20 Audibility limits of
NC-20
continous white level continous white level
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency(Hz)

11 -89
11 Technical Specifications

MMU-AP0362H MMU-AP0482H
Sound pressure HH-H-L Sound pressure HH-H-L
level(dB)(A) 43-38-32 level(dB)(A) 46-38-33

90 90
HH HH

H H
80 80
L L
Octabe nabd sound pressure level(dB

70

Octave band sound pressure level(dB


NC-7 70 NC-70

60 60
NC-6 NC-60

50 50
NC-5 NC-50

40 40
NC-40
NC-4

30 30
NC-30
NC-3
20 20
Audibility limits of Audibility limits of NC-20
continous white level NC-2 continous white level
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency(Hz) Ontave band center frequency(Hz)

MMU-AP0562H
Sound pressure HH-H-L
level(dB)(A) 46-40-33

90
HH

80 H

L
Octave band sound pressure level(dB

70 NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20
Audibility limits of NC-20
continous white level
10
63 125 250 500 1000 2000 4000 8000
Octave band center frequency(Hz)

11 -90
11 Technical Specifications

9.Fresh air intake (Design guide)


4-way Air Discharge Cassette Type (2series)

Usage
The fresh air and filter chamber is used as the filter chamber.
Fresh air intake by using the fresh air and filter chamber and fresh air inlet box.

Usage as the filter chamber


In case the optional filter is used, air volume may decrease. This can cause decrease temperature of cooling air
flow and dew drop.

Caution
1. Be sure to provide air return.
2. The fresh air shall be treated by heat reclaim ventilator or the like.
3. Recommended treated air temperature is 12C to 30C.
4. Be sure to decide the fresh air volume so that mixed suction air with fresh air keep operating temperature.
Provide an air filter in fresh air way to prevent sucking dust.
5. Be sure to insulate the fresh air duct.
In order to accelate starting up in heating mode, implement pre-heating operation by cutting off fresh air intake.

245 Booster fan


Static Pressure (Pa)

195

P1 P
145
(Atmospheric)
95

45
Fresh Air
Static Pressure = P (atmospheric) - P1
-5 Chamber
0 50 100 150 200 250 300 350 400
Fresh Air Volume (m³/h)

Characteristics between air volume of branching duct and static pressure


Up to 20% fresh air intake ratio is available by using the booster fan.
fresh air intake ratio = ( fresh air volume ) / ( total air volume ) X 100 %

Inter - lock circuit


1. Connect the driving relay of the duct fan ( DC 12 V ) between 1 and 6 on the indoor P.C.board.
Part indicated with a bold line is the connecting circuit.
After installation, implement a trial operation to check that the duct fan of the indoor unit start / stop
simultaneously.
(Implement the trial operation following to the installation manual of the indoor unit.)

Closed and Indoor


terminal +12V
Duct fan motor P.C.board
R 1 1
2 2
AC220 FAN 3 3 CN60
to 240V 4 4
5 5
(White)
Relay for Closed and 6 6
duct fan terminal GND

11 -91
11 Technical Specifications

10.Branching duct (Design guide)


4-way Air Discharge Cassette Type (2series)

Characteristics between air volume of branching duct and static pressure


In case of connecting dia.=150mm branching duct, static pressure is as follows.
60
VRF
50 009type,012type
Static Pressure (Pa)

40
8 015type
6 018type
30
4 024type,027type
5
20
030type
10 036type
1 2 3 048type
0
0 100 200 300 400 500 600 700 800 056type
Air volume (m³/h)

Cover method
Use air discharge direction kit
(TCB-BC1602UE)
to cover the air discharge port.

Install the cover

Dimension
45° 45°

114.6
105

2
Ø16
Ø145
Ø149

Ø176
114.6
105

4 - Ø6

Knockout square for 10


branching duct 100
in indoor unit
Design sample of branching duct flange

Installation sample

11 -92
11 Technical Specifications

11. Accessories

Optional parts for 4way cassette series2

6 7

1,2,3

Optional parts list


No Type Model name Qty/unit note
1 Ceiling Panel (wide-flow louver) RBC-U31PG(W)-E 1 White (2.5GY9.0/0.5)
2 Ceiling Panel (straight louver) RBC-U31PGS(W)-E 1 White (2.5GY9.0/0.5)
3 Ceiling Panel (straight louver) RBC-U31PGS(WS)-E 1 white/gray (2.5GY9.0/0.5 , 8B3/0.3)
4 Spacer for height adjustment TCB-SP1602UE 1 50mm
5 Fresh-air chamber TCB-GFC1602UE 1 use with TCB-GB1602U
6 Fresh-air inlet box TCB-GB1602UE 1 connection=Dia.100mm
Fresh air intake ratio : Up to 20%
7 Air-discharge direction kit TCB-BC1602UE 1 6-direction patterns
8 Auxiliary fresh air flange TCB-FF101URE2 1 connection=Dia.100mm
Fresh air intake ratio : Up to 5%

11 -93
SMMS-i Data book

11 -94
11 Technical Specifications

11-2-2. Compact 4-way Cassette(600x600) Type

Compact 4-way
Cassette (600 x 600) Type

Indoor Unit
MMU-AP0074MH-E
MMU-AP0094MH-E
MMU-AP0124MH-E
MMU-AP0154MH-E
MMU-AP0184MH-E

1. Specifications
2. Dimension
3. Wiring diagram
4. Center of Gravity
5. Sensible capacity table
6. Electrical characteristics
7. Air throw distance chart
8. Sound characteristics (NC-Curve)
9. Fresh air intake(Design guide)
10. Branching Duct(Design guide)
11. Accessories

11 -95
11 Technical Specifications

1. Specifications
Compact 4-way Cassette (600 x 600) Type

Model name MMU- AP0074MH-E AP0094MH-E AP0124MH-E AP0154MH-E AP0184MH-E

Cooling/Heating capacity (Note 1) (kW) 2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3

Power supply 1 phase 50Hz 230V (220-240V) (Separate power supply for indoor units is required.)

Running current (A) 0.28 0.30 0.31 0.34 0.42


Electrical
characteristics
Power consumption (kW) 0.034 0.036 0.038 0.041 0.052

Starting current (A) 0.49 0.52 0.54 0.59 0.73

Main unit Zinc hot dipping steel plate *Heat-insulating material attached to only upper plate

Appearance Model RBC-UM11PG(W)E


Ceiling
Panel
Panel color Moon white (Munsell/2.5GY 9.0/0.5)

Height (mm) 268

Main unit Width (mm) 575

Depth (mm) 575


Outer
dimension Height (mm) 27
Ceiling
panel Width (mm) 700

Depth (mm) 700

Main unit (kg) 17


Total weight
Ceiling panel (kg) 3

Heat exchanger Finned tube

Soundproof/Heat-insulating
material Non-flammble insulation

Fan Turbo fan

Standard air flow


Fan unit (High/Mid/Low) (m3/h) 552/462/378 570/468/378 594/504/402 660/552/468 762/642/522

Motor output (W) 60

Air filter Long life filter

Controller Remote controller

Gas side (mm) / 9.5


O / 12.7
O

Connecting
pipe Liquid side (mm) / 6.4
O

Drain port (Nominal dia. mm) 25 (Polyvinyl choride tube)

Sound pressure level(Note 2) (dB(A))


(High/Mid/Low) 36/32/28 37/33/28 37/33/29 40/35/30 44/39/34

PMV Kit Available

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on the reference piping.
The reference piping consist of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling :Indoor air temperature 27°C DB/1S0C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB

11 -96
11 Technical Specifications

2. Dimension
Compact 4-way Cassette (600 x 600) Type
MMU-AP0074MH-E, AP0094MH-E, AP0124MH-E, AP0154MH-E, AP0181MH
Bottom face of ceiling

105 93

145.5
For bracch duct
/ 150
knockout square hole O
207

70.5
Bottom face
175
/ 162
of ceiling O
235 105 235
Electric Knockout for 149
parts box 575 unit external dimension / 100
flesh air intake O
29 64

595 to 660 ceiling open dimension

142
575 unit external dimension

700 Panel external dimension


525 hanging bolt pitch

64
368.5
320.5

331.5

Model name

MMU-AP0071MH
4-way air Discharge Cassete Type
MMU-AP0091MH
MMU-AP0121MH
MMU-AP0151MH
Arialb1i0c0p34;TOSHIBA CARRIER CORPORATION
MMU-AP0181MH

177
525 hanging bolt pitch Hanging bolt
Refrigerant pipe (Gas) M10 or W3/8 local arrange
0151, 0181MH................. O
/ 12.7 595 to 660 ceiling open dimension
0071, 0091, 0121MH....... O / 9.5 700 Panel external dimension
Drain discharge port
214 105 256
/ 6.4
Refrigerant pipe (Liquid) O 97.5 42 148 / 162
O
105 70.5

268
220.5
190.5

145.5
193.5

134
63
93

55

Bottom face of ceiling


Wiring connection port 21 120
27

/ 150
For branch duct knockout square hole O 158 142 Ceiling panel
300
(NOTE)
827.5 or less

As ABS is used for the drain discharge port of the main unit,
Stand-up

the vinyl chloride paste cannot be used. Indoor unit


850 or less
Stand-up

Use the flexible hose (Band fix)


included in the package.

Bottom face
595 to 660 ceiling open dimension

200

Drain-up standing-up size of ceiling


Check port
( 450)
1000 or more

1000 or more 1000 or more


15 or more

15 or more

595 to 660 ceiling open dimension

Obustacle
Space required for installation and servicing

Unit : mm

11 -97
11 Technical Specifications

3. Wiring diagram
MMU-AP0074MH-E, AP0094MH-E, AP0124MH-E, AP0154MH-E, AP0184MH-E

11 -98
11 Technical Specifications

4. Center of Gravity
Total weight
Model name X (mm) Y (mm) Z (mm) Main unit Ceiling panel
(Kg) (Kg)
MMU-AP0074MH-E
MMU-AP0091MH-E
MMU-AP0121MH-E 316.5 336.5 174 17 3
MMU-AP0151MH-E
MMU-AP0181MH-E

11 -99
11 Technical Specifications

5. Sensible capacity table


Compact 4-way Cassette (600 x 600) Type (MMU-
***4MH-E)
TC:Total capacity[kW] SHC:Sensible capacity[kW]
indoor air temp.
unit outdoor 14.0CWB 16.0CWB 18.0CWB 19.0CWB 20.0CWB 22.0CWB 24.0CWB
size air temp. 20CDB 23CDB 26CDB 27CDB 28CDB 30CDB 32CDB
CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
12.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
14.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
16.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
18.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
20.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
21.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
007 23.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
25.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
27.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
29.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
31.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
33.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
35.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
37.0 1.7 1.5 1.9 1.6 2.1 1.7 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.6
39.0 1.7 1.4 1.9 1.5 2.0 1.6 2.1 1.6 2.1 1.6 2.3 1.6 2.4 1.5
10.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
12.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
14.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
16.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
18.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
20.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
21.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
009 23.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
25.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
27.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
29.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
31.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
33.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
35.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
37.0 2.2 1.7 2.5 1.8 2.6 1.9 2.7 1.9 2.8 1.9 3.0 1.9 3.1 1.9
39.0 2.2 1.7 2.4 1.8 2.6 1.9 2.6 1.9 2.7 1.9 2.9 1.9 3.0 1.8
10.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
12.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
14.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
16.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
18.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
20.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
21.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
012 23.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
25.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
27.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
29.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
31.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
33.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
35.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
37.0 2.9 2.1 3.2 2.3 3.4 2.4 3.5 2.4 3.6 2.4 3.8 2.4 4.0 2.3
39.0 2.8 2.1 3.1 2.2 3.3 2.4 3.4 2.4 3.5 2.4 3.7 2.3 3.9 2.3
10.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
12.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
14.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
16.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
18.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
20.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
21.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
015 23.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
25.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
27.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
29.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
31.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
33.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
35.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
37.0 3.6 2.7 4.0 2.8 4.2 3.0 4.4 3.0 4.5 3.0 4.7 3.0 5.0 2.9
39.0 3.5 2.6 3.8 2.8 4.1 2.9 4.2 2.9 4.4 2.9 4.6 2.9 4.8 2.8

11 -100
11 Technical Specifications

TC:Total capacity[kW] SHC:Sensible capacity[kW]


indoor air temp.
unit outdoor 14.0CWB 16.0CWB 18.0CWB 19.0CWB 20.0CWB 22.0CWB 24.0CWB
size air temp. 20CDB 23CDB 26CDB 27CDB 28CDB 30CDB 32CDB
CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
12.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
14.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
16.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
18.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
20.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
21.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
018 23.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
25.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
27.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
29.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
31.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
33.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
35.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
37.0 4.5 3.1 4.9 3.3 5.3 3.5 5.4 3.5 5.6 3.5 5.9 3.5 6.2 3.4
39.0 4.3 3.0 4.8 3.2 5.1 3.4 5.3 3.4 5.4 3.4 5.7 3.4 6.0 3.3

6. Electrical characteristics
Compact 4-way Cassette (600 x 600) Type

MMU-AP 0074 MH-E


MMU-AP 0094 MH-E
MMU-AP 0124 MH-E
MMU-AP 0154 MH-E
MMU-AP 0184 MH-E

MCA : Minimum Circuit Amps FLA : Full Load Amps


MOCP : Maximum Overcurrent Protection (Amps)

11 -101
11 Technical Specifications

7. Air throw distance chart


Compact 4-way Cassette (600 x 600) Type

MMU-AP0074MH-E MMU-AP0094MH-E

2.7m 2.7m
0.7m/s 0.7m/s
2 2
0.5m/s 0.5m/s

1 1
0.3m/s 0.3m/s

0 1 2 3 4 5m 0 1 2 3 4 5m

MMU-AP0124MH-E MMU-AP0154MH-E

2.7m 2.9m
0.7m/s 0.7m/s
2
2
0.5m/s 0.5m/s

1
0.3m/s 1 0.3m/s

0 1 2 3 4 5m
0 1 2 3 4 5m

MMU-AP0184MH-E MMU-AP0154MH-E,MMU-AP0184MH-E
(High ceiling mode)

3.2m 3.5m
3
0.7m/s
3
0.7m/s

2
0.5m/s
2
0.5m/s

1 0.3m/s
1 0.3m/s

0 1 2 3 4 5m
0 1 2 3 4 5m

11 -102
11 Technical Specifications

8. Sound Characteristics (NC-Curve)


Compact 4-way Cassette (600 x 600) Type

MMU-AP0074MH-E
Fan tap H M L
Sound pressure
36 32 28
level (dB(A))

70

Octave band sound pressure level (dB)


60

50 NC- 50
1.5m
40 NC- 40
Microphone H
30 M NC- 30
L

20
NC- 20
Approximate threshold of
hearing for continuous noise
10
63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)

MMU-AP0094MH-E MMU-AP0124MH-E

Fan tap H M L Fan tap H M L


Sound pressure Sound pressure
37 33 28 37 33 29
level (dB(A)) level (dB(A))

70 70
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

60 60

50 NC- 50 50 NC- 50

40 NC- 40 40 NC- 40
H H
M M
30 L NC- 30 30 NC- 30
L

20 20
NC- 20 NC- 20
Approximate threshold of Approximate threshold of
hearing for continuous noise hearing for continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

MMU-AP0154MH-E MMU-AP0184MH-E

Fan tap H M L Fan tap H M L


Sound pressure Sound pressure
40 35 30 44 39 34
level (dB(A)) level (dB(A))

70 70
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

60 60

50 NC- 50 50
NC- 50
H
40 H NC- 40 40 M NC- 40
M L
L
30 NC- 30 30 NC- 30

20 NC- 20 20
NC- 20
Approximate threshold of Approximate threshold of
hearing for continuous noise hearing for continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

11 -103
11 Technical Specifications

9. Fresh air intake (Design guide)

Compact 4-way Cassette (600 x 600) Type

Caution
The fresh air shall be conditioned by a heat reclaim ventilator or similar.
Ensure the fresh air volume is determined so that mixed suction air and fresh air can maintain the
operating temperature.
*1.Recommended conditioned air temperature is 12 oC to 30 oC.
However, Make a fresh air volume within 20% of standard.
Model name MMU- AP0074MH-E AP0094MH-E AP0124MH-E AP0154MH-E AP0184MH-E
Standard air flow (m3/h) 552 570 594 660 762

Install a filter within the fresh air duct.


(Fresh air does not pass through the filter of Indoor unit.)
Insulate the fresh air duct.
Electrically connect the fan of the Heat exchanger unit and the Indoor unit to a single isolator.

300

250
Static Pressure (Pa)

200

150

100

50

0
0 2 4 6 8 10 12 14 16 18 20 22
Fresh Air Volume (m3/h)

Indoor unit Duct fan


motor Fresh Air Volume

Flange Option : _

Inter - lock circuit


Connect the driving relay of the duct fan(DC 12V) between 1 and 6 on the indoor P.C. board.
(Rated current of the relay for duct fan should be up to 75mA.)
After installation, carry out a trial operation to check that the duct fan of the indoor unit start/stop
simultaneously.
(Carry out the trial operation following the installation manual of the indoor unit.)

11 -104
11 Technical Specifications

10. Branching Duct (design guide)


Compact 4-way Cassette (600 x 600) Type
Characteristics between air volume of branching duct and static pressure

70
VRF DI, SDI
MMU-AP0184MH-E* SM562MUT-E
60
MMU-AP0184MH-E SM562MUT-E
MMU-AP0154MH-E SM452MUT-E
50
Static pressure(Pa)

SM402MUT-E
MMU-AP0124MH-E -
40
MMU-AP0094MH-E -
MMU-AP0074MH-E -
30
* High ceiling mode
20

10

0
0 100 200 300
Air volume(m3/h)

Piping side

Branching
Duct

OA

Drain pump

Be sure to cover the air dischage port

11 -105
11 Technical Specifications

11. Accessories
Compact 4-way Cassette (600 x 600) Type

Optional accessories

TCB-FF101URE2

Ceiling panel
RBC-UM11PG(W)E

Parts Name Model name Applied Model Notes


Ceiling panel RBC-UM11PG(W)E Required accessory
MMU-AP***4MH-E For easy fresh air intake by using
Auxiliary fresh air Flange TCB-FF101URE2 the knockout hole of indoor
unit.(dia=100mm)

11 -106
11 Technical Specifications

11-2-3. 2-way Air Discharge Cassette Type

2-way Air Discharge


Cassette Type
MMU-AP0072WH / MMU-AP0092WH
MMU-AP0122WH / MMU-AP0152WH
MMU-AP0182WH / MMU-AP0242WH
MMU-AP0272WH / MMU-AP0302WH
MMU-AP0362WH / MMU-AP0482WH
MMU-AP0562WH

Contents
1. Specifications
2. Dimension
3. Wiring diagram
4. Center of Gravity
5. Electrical characteristics
6. Sensible capacity table
7. Air throw distance chart
8. Sound characteristics (NC-Curve)
9. Fresh air intake (Design guide)
10. Accessories

11 -107
11 Technical Specifications

1. Specifications
2-way Air Discharge Cassette Type

Model name MMU- AP0072WH AP0092WH AP0122WH AP0152WH AP0182WH AP0242WH AP0272WH AP0302WH AP0362WH AP0482WH AP0562WH

Cooling/Heating capacity (Note 1) (kW) 2.2 / 2.5 2.8 / 3.2 3.6 / 4.0 4.5 / 5.0 5.6 / 6.3 7.1 / 8.0 8.0 / 9.0 9.0 / 10.0 11.2 / 12.5 14.0 / 16.0 16.0 / 18.0
Power supply 1 phase 50Hz 230V (220-240V) (Sepatate power supply for indoor units is required.)

Running current (A) 0.23 0.24 0.32 0.39 0.46 0.48 0.57 0.75
Electical characteristics Power consumption (kW) 0.029 0.03 0.044 0.054 0.064 0.073 0.088 0.117
Power factor (%) 55 54 60 66 67 68
Starting current (A) 0.35 0.36 0.48 0.59 0.69 0.72 0.86 1.13
Appearance Main unit Heat-instulating material attached Zinc hot dipping steel plate

Ceiling panel Model RBC-UW283PG(W)-E RBC-UW803PG(W)-E RBC-UW1403PG(W)-E

Panel colour Moon white(Munsell 2.5GY9.0/0.5)

Hight (mm) 295 345


Main unit Width (mm) 815 1180 1600

Depth (mm) 570


Outer dimentions
Hight (mm) 20
Ceiling panel Width (mm) 1050 1415 1835

Depth (mm) 680

Main unit (kg) 19 26 36


Total weight
Ceiling panel (kg) 10 14

Heat exchanger Finned tube

Sound proof / Heat-insulating material Non-flammable insulation

Fan Turbo fan Centrifugal fan

Fan unit Standard air flow 3 600/534/ 900/750/ 1260/900/ 1740/1434/ 1800/1482/ 2040/1578/
(High/Mid/Low) (m /h) 558 / 498 / 450 1050 / 840 / 738
450 618 780 1182 1230 1320
Motor output (W) 20 30 40 50 70

Air filter Standard filter (Long life filter)

Controller Remote controller

Gas pipe (mm) Ø 9.5 Ø 12.7 Ø 15.9


Connecting pipe Liquid pipe (mm) Ø 6.4 Ø 9.5

Drain port(Nominal dia. mm) 25 (Polyvinyl chloride tube)

Sound pressure level (High/Med./Low) (Note 2) (dB(A)) 34 / 32 / 30 35 / 33 / 30 38 / 35 / 33 40/37/34 42/39/36 43/40/37 46/42/39

Note 1 :The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on the reference piping.
The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.
Note 2 :The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB

11 -108
11 Technical Specifications

2. Dimension
MMU-AP0072WH, 0092WH, 0122WH, AP0152WH

Model MMU A
0072WH, 0092WH, 0122WH 9.5
0152WH 12.7

MMU-AP0182WH, 0242WH, 0272WH, AP0302WH

Model MMU B C
0182WH 6.4 12.7
0242WH, 02742WH, 0302WH 9.5 15.9

11 -109
11 Technical Specifications

MMU-AP0362WH, 0482WH, 0562WH

11 -110
11 Technical Specifications

3. Wiring diagram
MMU-AP0072WH, AP0092WH, AP0122WH, AP0152WH, AP0182WH, AP0242WH, AP0272WH, AP0302WH,
AP0362WH, AP0482WH, AP0562WH

11 -111
11 Technical Specifications

4. Center of Gravity
Total weight(kg)
Model name X(mm) Y(mm) Z(mm)
Main unit Ceiling panel
MMU-AP0072WH
MMU-AP0092WH
280 435 162 19 10
MMU-AP0122WH
MMU-AP0152WH
MMU-AP0182WH
MMU-AP0242WH
600 205 26
MMU-AP0272WH
MMU-AP0302WH 285 14
MMU-AP0362WH
MMU-AP0482WH 835 175 36
MMU-AP0562WH

5. Electrical characteristics
2-way Air Discharge Cassette Type

Model Normal Voltage Voltage Range Fan Motor Power Supply


(V-Ph-Hz) Min Max kW FLA MCA MOCP
50Hz MMU-AP0072WH 230-1-50 198 264 0.020 0.32 0.40 15
MMU-AP0092WH 230-1-50 198 264 0.020 0.32 0.40 15
MMU-AP0122WH 230-1-50 198 264 0.020 0.32 0.40 15
MMU-AP0152WH 230-1-50 198 264 0.020 0.32 0.40 15
MMU-AP0182WH 230-1-50 198 264 0.030 0.70 0.88 15
MMU-AP0242WH 230-1-50 198 264 0.040 0.81 1.01 15
MMU-AP0272WH 230-1-50 198 264 0.040 0.81 1.01 15
MMU-AP0302WH 230-1-50 198 264 0.050 0.81 1.01 15
MMU-AP0362WH 230-1-50 198 264 0.070 0.87 1.09 15
MMU-AP0485WH 230-1-50 198 264 0.070 0.87 1.09 15
MMU-AP0562WH 230-1-50 198 264 0.070 0.87 1.09 15

MCA : Minimum Circuit Amps FLA : Full Load Amps


MOCP : Maximum Overcurrent Protection (Amps)

11 -112
11 Technical Specifications

6. Sensible capacity table


2-way cassette type 2series ( MMU-AP***2WH ) TC : Total capacity [kW] SHC : Sensible capacity [kW]
indoor air temp.
unit outdoor 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
size air temp. 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
°CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 1.8 1.4 2.0 1.5 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.6 2.5 1.6
12.0 1.8 1.4 2.0 1.5 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.6 2.5 1.6
14.0 1.8 1.4 2.0 1.5 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.6 2.5 1.6
16.0 1.8 1.4 2.0 1.5 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.6 2.5 1.6
18.0 1.8 1.4 2.0 1.5 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.6 2.5 1.6
20.0 1.8 1.4 2.0 1.5 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.6 2.5 1.6
21.0 1.8 1.4 2.0 1.5 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.6 2.5 1.6
007 23.0 1.8 1.4 2.0 1.5 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.6 2.5 1.6
25.0 1.8 1.4 2.0 1.5 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.6 2.5 1.6
27.0 1.8 1.4 2.0 1.5 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.6 2.5 1.6
29.0 1.8 1.4 2.0 1.5 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.6 2.5 1.6
31.0 1.8 1.4 2.0 1.5 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.6 2.5 1.6
33.0 1.8 1.4 2.0 1.5 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.6 2.5 1.6
35.0 1.8 1.4 2.0 1.5 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.6 2.5 1.6
37.0 1.7 1.4 1.9 1.5 2.1 1.6 2.1 1.6 2.2 1.6 2.3 1.5 2.4 1.5
39.0 1.7 1.3 1.9 1.4 2.0 1.5 2.1 1.5 2.1 1.5 2.3 1.5 2.4 1.5
10.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 2.0
12.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 2.0
14.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 2.0
16.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 2.0
18.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 2.0
20.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 2.0
21.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 2.0
009 23.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 2.0
25.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 2.0
27.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 2.0
29.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 2.0
31.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 2.0
33.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 2.0
35.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 2.0
37.0 2.2 1.7 2.5 1.8 2.6 2.0 2.7 2.0 2.8 2.0 3.0 1.9 3.1 1.9
39.0 2.2 1.7 2.4 1.8 2.6 1.9 2.6 1.9 2.7 1.9 2.9 1.9 3.0 1.8
10.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
12.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
14.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
16.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
18.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
20.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
21.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
012 23.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
25.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
27.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
29.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
31.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
33.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
35.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
37.0 2.9 2.2 3.2 2.3 3.4 2.4 3.5 2.4 3.6 2.4 3.8 2.4 4.0 2.4
39.0 2.8 2.1 3.1 2.2 3.3 2.4 3.4 2.4 3.5 2.4 3.7 2.3 3.9 2.3
10.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.0
12.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.0
14.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.0
16.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.0
18.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.0
20.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.0
21.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.0
015 23.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.0
25.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.0
27.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.0
29.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.0
31.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.0
33.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.0
35.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.0
37.0 3.6 2.6 4.0 2.8 4.2 3.0 4.4 3.0 4.5 3.0 4.7 2.9 5.0 2.9
39.0 3.5 2.6 3.8 2.7 4.1 2.9 4.2 2.9 4.4 2.9 4.6 2.9 4.8 2.8

11 -113
11 Technical Specifications

2-way cassette type 2series ( MMU-AP***2WH ) TC : Total capacity [kW] SHC : Sensible capacity [kW]
indoor air temp.
unit outdoor 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
size air temp. 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
°CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
12.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
14.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
16.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
18.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
20.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
21.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
018 23.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
25.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
27.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
29.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
31.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
33.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
35.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
37.0 4.5 3.4 4.9 3.6 5.3 3.8 5.4 3.8 5.6 3.8 5.9 3.8 6.2 3.7
39.0 4.3 3.3 4.8 3.5 5.1 3.7 5.3 3.7 5.4 3.7 5.7 3.7 6.0 3.6
10.0 5.8 4.3 6.4 4.6 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.7
12.0 5.8 4.3 6.4 4.6 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.7
14.0 5.8 4.3 6.4 4.6 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.7
16.0 5.8 4.3 6.4 4.6 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.7
18.0 5.8 4.3 6.4 4.6 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.7
20.0 5.8 4.3 6.4 4.6 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.7
21.0 5.8 4.3 6.4 4.6 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.7
024 23.0 5.8 4.3 6.4 4.6 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.7
25.0 5.8 4.3 6.4 4.6 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.7
27.0 5.8 4.3 6.4 4.6 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.7
29.0 5.8 4.3 6.4 4.6 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.7
31.0 5.8 4.3 6.4 4.6 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.7
33.0 5.8 4.3 6.4 4.6 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.7
35.0 5.8 4.3 6.4 4.6 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.7
37.0 5.6 4.1 6.2 4.4 6.7 4.7 6.9 4.7 7.1 4.7 7.5 4.6 7.8 4.5
39.0 5.5 4.0 6.1 4.3 6.5 4.6 6.7 4.5 6.9 4.5 7.3 4.5 7.6 4.4
10.0 6.6 4.7 7.3 5.0 7.8 5.3 8.0 5.3 8.2 5.3 8.7 5.2 9.1 5.1
12.0 6.6 4.7 7.3 5.0 7.8 5.3 8.0 5.3 8.2 5.3 8.7 5.2 9.1 5.1
14.0 6.6 4.7 7.3 5.0 7.8 5.3 8.0 5.3 8.2 5.3 8.7 5.2 9.1 5.1
16.0 6.6 4.7 7.3 5.0 7.8 5.3 8.0 5.3 8.2 5.3 8.7 5.2 9.1 5.1
18.0 6.6 4.7 7.3 5.0 7.8 5.3 8.0 5.3 8.2 5.3 8.7 5.2 9.1 5.1
20.0 6.6 4.7 7.3 5.0 7.8 5.3 8.0 5.3 8.2 5.3 8.7 5.2 9.1 5.1
21.0 6.6 4.7 7.3 5.0 7.8 5.3 8.0 5.3 8.2 5.3 8.7 5.2 9.1 5.1
027 23.0 6.6 4.7 7.3 5.0 7.8 5.3 8.0 5.3 8.2 5.3 8.7 5.2 9.1 5.1
25.0 6.6 4.7 7.3 5.0 7.8 5.3 8.0 5.3 8.2 5.3 8.7 5.2 9.1 5.1
27.0 6.6 4.7 7.3 5.0 7.8 5.3 8.0 5.3 8.2 5.3 8.7 5.2 9.1 5.1
29.0 6.6 4.7 7.3 5.0 7.8 5.3 8.0 5.3 8.2 5.3 8.7 5.2 9.1 5.1
31.0 6.6 4.7 7.3 5.0 7.8 5.3 8.0 5.3 8.2 5.3 8.7 5.2 9.1 5.1
33.0 6.6 4.7 7.3 5.0 7.8 5.3 8.0 5.3 8.2 5.3 8.7 5.2 9.1 5.1
35.0 6.6 4.7 7.3 5.0 7.8 5.3 8.0 5.3 8.2 5.3 8.7 5.2 9.1 5.1
37.0 6.4 4.5 7.0 4.8 7.5 5.1 7.7 5.1 8.0 5.1 8.4 5.1 8.8 4.9
39.0 6.2 4.4 6.8 4.7 7.3 5.0 7.5 5.0 7.8 5.0 8.2 4.9 8.6 4.8
10.0 7.4 5.0 8.2 5.4 8.7 5.7 9.0 5.7 9.3 5.7 9.8 5.6 10.3 5.5
12.0 7.4 5.0 8.2 5.4 8.7 5.7 9.0 5.7 9.3 5.7 9.8 5.6 10.3 5.5
14.0 7.4 5.0 8.2 5.4 8.7 5.7 9.0 5.7 9.3 5.7 9.8 5.6 10.3 5.5
16.0 7.4 5.0 8.2 5.4 8.7 5.7 9.0 5.7 9.3 5.7 9.8 5.6 10.3 5.5
18.0 7.4 5.0 8.2 5.4 8.7 5.7 9.0 5.7 9.3 5.7 9.8 5.6 10.3 5.5
20.0 7.4 5.0 8.2 5.4 8.7 5.7 9.0 5.7 9.3 5.7 9.8 5.6 10.3 5.5
21.0 7.4 5.0 8.2 5.4 8.7 5.7 9.0 5.7 9.3 5.7 9.8 5.6 10.3 5.5
030 23.0 7.4 5.0 8.2 5.4 8.7 5.7 9.0 5.7 9.3 5.7 9.8 5.6 10.3 5.5
25.0 7.4 5.0 8.2 5.4 8.7 5.7 9.0 5.7 9.3 5.7 9.8 5.6 10.3 5.5
27.0 7.4 5.0 8.2 5.4 8.7 5.7 9.0 5.7 9.3 5.7 9.8 5.6 10.3 5.5
29.0 7.4 5.0 8.2 5.4 8.7 5.7 9.0 5.7 9.3 5.7 9.8 5.6 10.3 5.5
31.0 7.4 5.0 8.2 5.4 8.7 5.7 9.0 5.7 9.3 5.7 9.8 5.6 10.3 5.5
33.0 7.4 5.0 8.2 5.4 8.7 5.7 9.0 5.7 9.3 5.7 9.8 5.6 10.3 5.5
35.0 7.4 5.0 8.2 5.4 8.7 5.7 9.0 5.7 9.3 5.7 9.8 5.6 10.3 5.5
37.0 7.2 4.9 7.9 5.2 8.5 5.5 8.7 5.5 9.0 5.5 9.5 5.4 9.9 5.3
39.0 7.0 4.7 7.7 5.0 8.2 5.4 8.5 5.3 8.7 5.3 9.2 5.3 9.7 5.2

11 -114
11 Technical Specifications

2-way cassette type 2series ( MMU-AP***2WH ) TC : Total capacity [kW] SHC : Sensible capacity [kW]
indoor air temp.
unit outdoor 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
size air temp. 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
°CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 9.2 6.9 10.2 7.3 10.9 7.8 11.2 7.7 11.5 7.7 12.2 7.7 12.8 7.5
12.0 9.2 6.9 10.2 7.3 10.9 7.8 11.2 7.7 11.5 7.7 12.2 7.7 12.8 7.5
14.0 9.2 6.9 10.2 7.3 10.9 7.8 11.2 7.7 11.5 7.7 12.2 7.7 12.8 7.5
16.0 9.2 6.9 10.2 7.3 10.9 7.8 11.2 7.7 11.5 7.7 12.2 7.7 12.8 7.5
18.0 9.2 6.9 10.2 7.3 10.9 7.8 11.2 7.7 11.5 7.7 12.2 7.7 12.8 7.5
20.0 9.2 6.9 10.2 7.3 10.9 7.8 11.2 7.7 11.5 7.7 12.2 7.7 12.8 7.5
21.0 9.2 6.9 10.2 7.3 10.9 7.8 11.2 7.7 11.5 7.7 12.2 7.7 12.8 7.5
036 23.0 9.2 6.9 10.2 7.3 10.9 7.8 11.2 7.7 11.5 7.7 12.2 7.7 12.8 7.5
25.0 9.2 6.9 10.2 7.3 10.9 7.8 11.2 7.7 11.5 7.7 12.2 7.7 12.8 7.5
27.0 9.2 6.9 10.2 7.3 10.9 7.8 11.2 7.7 11.5 7.7 12.2 7.7 12.8 7.5
29.0 9.2 6.9 10.2 7.3 10.9 7.8 11.2 7.7 11.5 7.7 12.2 7.7 12.8 7.5
31.0 9.2 6.9 10.2 7.3 10.9 7.8 11.2 7.7 11.5 7.7 12.2 7.7 12.8 7.5
33.0 9.2 6.9 10.2 7.3 10.9 7.8 11.2 7.7 11.5 7.7 12.2 7.7 12.8 7.5
35.0 9.2 6.9 10.2 7.3 10.9 7.8 11.2 7.7 11.5 7.7 12.2 7.7 12.8 7.5
37.0 8.9 6.6 9.8 7.1 10.5 7.5 10.8 7.5 11.2 7.5 11.8 7.4 12.4 7.2
39.0 8.7 6.4 9.6 6.9 10.2 7.3 10.5 7.3 10.9 7.3 11.5 7.2 12.0 7.0
10.0 11.5 7.9 12.7 8.5 13.6 9.0 14.0 9.0 14.4 9.0 15.3 8.9 16.0 8.7
12.0 11.5 7.9 12.7 8.5 13.6 9.0 14.0 9.0 14.4 9.0 15.3 8.9 16.0 8.7
14.0 11.5 7.9 12.7 8.5 13.6 9.0 14.0 9.0 14.4 9.0 15.3 8.9 16.0 8.7
16.0 11.5 7.9 12.7 8.5 13.6 9.0 14.0 9.0 14.4 9.0 15.3 8.9 16.0 8.7
18.0 11.5 7.9 12.7 8.5 13.6 9.0 14.0 9.0 14.4 9.0 15.3 8.9 16.0 8.7
20.0 11.5 7.9 12.7 8.5 13.6 9.0 14.0 9.0 14.4 9.0 15.3 8.9 16.0 8.7
21.0 11.5 7.9 12.7 8.5 13.6 9.0 14.0 9.0 14.4 9.0 15.3 8.9 16.0 8.7
048 23.0 11.5 7.9 12.7 8.5 13.6 9.0 14.0 9.0 14.4 9.0 15.3 8.9 16.0 8.7
25.0 11.5 7.9 12.7 8.5 13.6 9.0 14.0 9.0 14.4 9.0 15.3 8.9 16.0 8.7
27.0 11.5 7.9 12.7 8.5 13.6 9.0 14.0 9.0 14.4 9.0 15.3 8.9 16.0 8.7
29.0 11.5 7.9 12.7 8.5 13.6 9.0 14.0 9.0 14.4 9.0 15.3 8.9 16.0 8.7
31.0 11.5 7.9 12.7 8.5 13.6 9.0 14.0 9.0 14.4 9.0 15.3 8.9 16.0 8.7
33.0 11.5 7.9 12.7 8.5 13.6 9.0 14.0 9.0 14.4 9.0 15.3 8.9 16.0 8.7
35.0 11.5 7.9 12.7 8.5 13.6 9.0 14.0 9.0 14.4 9.0 15.3 8.9 16.0 8.7
37.0 11.1 7.7 12.3 8.2 13.1 8.7 13.6 8.7 14.0 8.7 14.8 8.6 15.4 8.4
39.0 10.8 7.5 12.0 8.0 12.8 8.5 13.2 8.4 13.6 8.4 14.4 8.4 15.0 8.2
10.0 13.1 8.8 14.5 9.4 15.5 9.9 16.0 9.9 16.5 9.9 17.4 9.8 18.2 9.6
12.0 13.1 8.8 14.5 9.4 15.5 9.9 16.0 9.9 16.5 9.9 17.4 9.8 18.2 9.6
14.0 13.1 8.8 14.5 9.4 15.5 9.9 16.0 9.9 16.5 9.9 17.4 9.8 18.2 9.6
16.0 13.1 8.8 14.5 9.4 15.5 9.9 16.0 9.9 16.5 9.9 17.4 9.8 18.2 9.6
18.0 13.1 8.8 14.5 9.4 15.5 9.9 16.0 9.9 16.5 9.9 17.4 9.8 18.2 9.6
20.0 13.1 8.8 14.5 9.4 15.5 9.9 16.0 9.9 16.5 9.9 17.4 9.8 18.2 9.6
21.0 13.1 8.8 14.5 9.4 15.5 9.9 16.0 9.9 16.5 9.9 17.4 9.8 18.2 9.6
056 23.0 13.1 8.8 14.5 9.4 15.5 9.9 16.0 9.9 16.5 9.9 17.4 9.8 18.2 9.6
25.0 13.1 8.8 14.5 9.4 15.5 9.9 16.0 9.9 16.5 9.9 17.4 9.8 18.2 9.6
27.0 13.1 8.8 14.5 9.4 15.5 9.9 16.0 9.9 16.5 9.9 17.4 9.8 18.2 9.6
29.0 13.1 8.8 14.5 9.4 15.5 9.9 16.0 9.9 16.5 9.9 17.4 9.8 18.2 9.6
31.0 13.1 8.8 14.5 9.4 15.5 9.9 16.0 9.9 16.5 9.9 17.4 9.8 18.2 9.6
33.0 13.1 8.8 14.5 9.4 15.5 9.9 16.0 9.9 16.5 9.9 17.4 9.8 18.2 9.6
35.0 13.1 8.8 14.5 9.4 15.5 9.9 16.0 9.9 16.5 9.9 17.4 9.8 18.2 9.6
37.0 12.7 8.5 14.1 9.1 15.0 9.6 15.5 9.6 16.0 9.6 16.9 9.5 17.7 9.3
39.0 12.4 8.3 13.7 8.8 14.6 9.4 15.1 9.3 15.5 9.3 16.4 9.2 17.2 9.0

11 -115
11 Technical Specifications

7. Air throw distance chart


Unit: [m/s]

MMU-AP0072WH, AP0092WH, AP0122WH, AP0152WH MMU-AP0182WH


Ceiling height (m)

Ceiling height (m)


Horizontal distance (m) Horizontal distance (m)

MMU-AP0242WH, AP0272WH MMU-AP0302WH


Ceiling height (m)

Ceiling height (m)

Horizontal distance (m) Horizontal distance (m)

MMU-AP0362WH, AP0482WH MMU-AP0562WH


Ceiling height (m)

Ceiling height (m)

Horizontal distance (m) Horizontal distance (m)

11 -116
11 Technical Specifications

8. Sound characteristics (NC-Curve)


MMU-AP0072WH, AP0092WH, 0122WH
Sound pressure level H-M-L
(dB(A)) 34 - 32 - 30
90

Octave band sound pressure level dB


80

70
NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20
Audibility limits of
contious white level NC-20
10
63 125 250 500 1000 2000 4000 8000

Octave band center frequency(Hz)

MMU-AP0152WH MMU-AP0182WH
Sound pressure level H-M-L Sound pressure level H-M-L
(dB(A)) 35 - 33 - 30 (dB(A)) 35 - 33 - 30
90 90
Octave band sound pressure level dB

Octave band sound pressure level dB

80 80

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 20
Audibility limits of NC-20 Audibility limits of
contious white level NC-20
contious white level
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave band center frequency(Hz) Octave band center frequency(Hz)

MMU-AP0242WH, AP0272WH MMU-AP0302WH


Sound pressure level H-M-L Sound pressure level H-M-L
(dB(A)) 38 - 35 - 33 (dB(A)) 40 - 37 - 34
90 90
Octave band sound pressure level dB

Octave band sound pressure level dB

80 80

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 20
Audibility limits of NC-20 Audibility limits of NC-20
contious white level contious white level
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave band center frequency(Hz) Octave band center frequency(Hz)

11 -117
11 Technical Specifications

MMU-AP0362WH MMU-AP0482WH
Sound pressure level H-M-L Sound pressure level H-M-L
(dB(A)) 42 - 39 - 36 (dB(A)) 43 - 40 - 37
90 90
Octave band sound pressure level dB

Octave band sound pressure level dB


80 80

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 20
Audibility limits of NC-20 Audibility limits of NC-20
contious white level contious white level
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave band center frequency(Hz) Octave band center frequency(Hz)

MMU-AP0562WH
Sound pressure level H-M-L
(dB(A)) 46 -42 - 39
90
Octave band sound pressure level dB

80

70
NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20
Audibility limits of NC-20
contious white level
10
63 125 250 500 1000 2000 4000 8000

Octave band center frequency(Hz)

11 -118
11 Technical Specifications

9. Fresh air intake (Design guide)


Usage
Fresh air intake by setting Auxiliary fresh air flange(TCB-FF151US-E) .

6. Be sure to connect wiring of inter-lock between Air to air heat exchanger unit and fan of indoor unit.

AP0072WH to AP0182WH to
AP0152WH AP0302WH
AP0362WH to
AP0562WH

Fresh Air Volume(m3/h)

11 -119
11 Technical Specifications

10. Accessories
Parts name Model name Applied model Notes Remarks
RBC-UW283PG(W)-E MMU-AP0072WH to 0152WH
Ceiling panel RBC-UW803PG(W)-E MMU-AP0182WH to 0302WH Required accessory
RBC-UW1403PG(W)-E MMU-AP0362WH to 0562WH
TBC-LF283UW-E MMU-AP0072WH to 0152WH Use with TBC-FC283UW-E
Dust collecting effect : 50%
Super long life filter TBC-LF803UW-E MMU-AP0182WH to 0302WH Use with TBC-FC803UW-E
(Weight method)
TBC-LF1403UW-E MMU-AP0362WH to 0562WH Use with TBC-FC1403UW-E
TBC-FC283UW-E MMU-AP0072WH to 0152WH
Filter champer TBC-FC803UW-E MMU-AP0182WH to 0302WH For super long life filter
TBC-FC1403UW-E MMU-AP0362WH to 0562WH
For fresh air intake by using the
Auxiliary fresh air flange TBC-FF151US-E MMU-AP0072WH to 0562WH
knockout hole of inddor unit.

11 -120
11 Technical Specifications

11-2-4. 1-way Air Discharge Cassette Type


\

1-way Air Discharge


Cassette Type
Indoor Unit
MMU-AP0074YH-E
MMU-AP0094YH-E
MMU-AP0124YH-E

MMU-AP0154SH-E
MMU-AP0184SH-E
MMU-AP0244SH-E

Contents
1. Specifications
2. Dimensions
3. Wiring diagram
4. Center of Gravity
5. Electrical characteristics
6. Sensible capacity table
7. Air throw distance chart
8. Sound characteristics (NC-Curve)
9. Fresh air intake (Design guide)
10. Accessories

11 -121
11 Technical Specifications

1. Specifications
1-way Air Discharge Cassette Type

Model name MMU- AP0074YH-E AP0094YH-E AP0124YH-E AP0154SH-E AP0184SH-E AP0244SH-E

Cooling/Heating capacity (Note 1) (kW) 2.2 / 2.5 2.8 / 3.2 3.6 / 4.0 4.5 / 5.0 5.6 / 6.3 7.1 / 8.0
Power supply 1 phase 50Hz 230V (220-240V) (Sepatate power supply for indoor units is required.)
Electical Running current (A) 0.24 0.34 0.37 0.62
characteristics Power consumption (kW) 0.053 0.042 0.046 0.075
Starting current (A) 0.6 0.51 0.54 0.80
Appearance Main unit Heat-instulating material attached Zinc hot dipping steel plate
Ceiling panel Model RBC-UY135PG RBC-US21PGE
Panel colour Moon white(Munsell 2.5GY9.0/0.5)
Hight (mm) 235 200
Main unit Width (mm) 850 1000
Depth (mm) 400 710
Outer dimentions
Hight (mm) 18 20
Ceiling panel Width (mm) 1050 1230
Depth (mm) 470 800
Main unit (kg) 22 21 22
Total weight
Ceiling panel (kg) 3.5 5.5
Heat exchanger Finned tube
Sound proof / Heat-insulating material Non-flammable insulation Polyethylene foam + Expanded polyethylene
Fan Centrifugal fan
Standard air flow 1140 / 960 /
Fan unit
(High/Mid/Low) (m3/h) 540 / 480 / 420 750 / 690 / 630 780 / 720 / 660
810
Motor output (W) 22 30
Air filter Standard filter (Long life filter)
Controller Remote controller
Gas pipe (mm) Ø 9.5 Ø 12.7 Ø 15.9
Connecting pipe Liquid pipe (mm) Ø 6.4 Ø 9.5
Drain port(Nominal dia. mm) 25 (Polyvinyl chloride tube)
Sound pressure level
(Note 2)(dB(A)) 42 / 39 / 34 37 / 35 / 32 38 / 36 / 34 45 / 41 / 37
(High/Med./Low)

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on the reference piping.
The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB

11 -122
11 Technical Specifications

2. Dimension
MMU-AP0074YH-E, AP0094YH-E, AP0124YH-E

Panel external dimension 1050


Space required for
20 Ceiling open dimension 1010 20
installation and servicing

20
Hanging bolt pitch 890

dimension 430

Panel external
dimension 470
Ceiling open
Hanging bolt
pitch 330
Power supply connecting port

400
Drain pipe connecting port
100 or more 100 or more

110 395 455 50

or more
20
150

245
Center of panel Hanging bolt 4-M10
225 100 400
procured locally
850

200 or more
Support metal
200

235
120

140
85

Stand-up 350 or less


18

Ceiling panel (Sold separately) 100 or less


Refrigerant pipe
Bottom face of ceiling
connecting port

150 or less
Discharge louver Air outlet
1050

Stand-up
(Gas side)
Refrigerant pipe
connecting port
(Liquid side)
470

Panel mounting hole 5 positions Bottom face of ceiling


Air inlet Drain standing-up size (Unit: mm)

MMU-AP0154SH-E, AP0184SH-E, AP0244SH-E

Fresh air intake (φ92 knockout hole) Wiring connection port


Space required for
Panel external dimension 1230 Drain pipe installation and servicing
112 20 Ceiling open dimension 1190 20 connecting port Ceiling panel (Sold separately)
72
205 or more

Hanging bolt pitch 1060 1230


20

φ112
Panel externaldimension 800

43
20 Ceiling open dimension 760
bolt pitch 475 100

1000 or more
122 233

Ceiling
220 Hanging

1000 or more
60

Obstacle
710

800
80
216
135

200 or more

94 Wireless sensor mounting section


Refrigerant pipe connecting port (Gas side)
154
Stand-up 850 or less

Refrigerant pipe connecting port (Liquid side) 140 or less


696 or less

1000
Stand-up

Hanging bolt M10 or W3/8 local arrange


706
76
200
93

73.4

Bottom face of ceiling


20

Bottom face of ceiling Knockout hole for front blow out (Unit: mm)
Drain standing-up size

11 -123
11 Technical Specifications

3. Wiring diagram
MMU-AP0074YH-E, AP0094YH-E, AP0124YH-E

11 -124
11 Technical Specifications

MMU-AP0154SH-E, AP0184SH-E, AP0244SH-E

11 -125
11 Technical Specifications

4. Center of Gravity
1-way YH Type

Total weight(kg)
Model name X(mm) Y(mm) Z(mm)
Main unit Ceiling panel
MMU-AP0074YH-E
MMU-AP0094YH-E 500 230 120 22 3.5
MMU-AP0124YH-E

X
Y

1-way SH Type

Total weight(kg)
Model name X(mm) Y(mm) Z(mm)
Main unit Ceiling panel
MMU-AP0154SH-E
370 475 80 21 5.5
MMU-AP0184SH-E
MMU-AP0244SH-E 22

11 -126
11 Technical Specifications

5. Electrical characteristics

Nominal Voltage Voltage Range Fan Motor Power Supply


Ty p e Mo d el
(V-Ph-Hz) Min Max kW FLA MCA MOCP
MMU-AP 0074 YH-E 230-1-50 198 264 0.022 0.28 0.35 15
MMU-AP 0094 YH-E 230-1-50 198 264 0.022 0.28 0.35 15
1-Way Air MMU-AP 0124 YH-E 230-1-50 198 264 0.022 0.28 0.35 15
Discharge
Cassette Type MMU-AP 0154 SH-E 230-1-50 198 264 0.030 0.40 0.49 15
MMU-AP 0184 SH-E 230-1-50 198 264 0.030 0.42 0.53 15
MMU-AP 0244 SH-E 230-1-50 198 264 0.030 0.71 0.88 15

MCA : Minimum Circuit Amps FLA : Full Load Amps


MOCP : Maximum Overcurrent Protection (Amps)

11 -127
11 Technical Specifications

6. Sensible capacity table

1-way Air Discharge Cassette Type ( MMU-AP***4YH-E )


TC : Total capacity [kW] SHC : Sensible capacity [kW]
indoor air temp.
o o o o o o o
unit outdoor 14.0 CWB 16.0 CWB 18.0 CWB 19.0 CWB 20.0 CWB 22.0 CWB 24.0 CWB
o o o o o o o
size air temp. 20 CDB 23 CDB 26 CDB 27 CDB 28 CDB 30 CDB 32 CDB
o
CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
12.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
14.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
16.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
18.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
20.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
21.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
007 23.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
25.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
27.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
29.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
31.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
33.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
35.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
37.0 1.7 1.5 1.9 1.6 2.1 1.7 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7
39.0 1.7 1.5 1.9 1.6 2.0 1.7 2.1 1.7 2.1 1.7 2.3 1.7 2.4 1.6
10.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.1
12.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.1
14.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.1
16.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.1
18.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.1
20.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.1
21.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.1
009 23.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.1
25.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.1
27.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.1
29.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.1
31.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.1
33.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.1
35.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.1
37.0 2.2 1.9 2.5 2.0 2.6 2.1 2.7 2.1 2.8 2.1 3.0 2.1 3.1 2.1
39.0 2.2 1.8 2.4 2.0 2.6 2.1 2.6 2.1 2.7 2.1 2.9 2.1 3.0 2.0
10.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.6
12.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.6
14.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.6
16.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.6
18.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.6
20.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.6
21.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.6
012 23.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.6
25.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.6
27.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.6
29.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.6
31.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.6
33.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.6
35.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.6
37.0 2.9 2.3 3.2 2.5 3.4 2.6 3.5 2.6 3.6 2.6 3.8 2.6 4.0 2.5
39.0 2.8 2.3 3.1 2.4 3.3 2.5 3.4 2.5 3.5 2.5 3.7 2.5 3.9 2.5

11 -128
11 Technical Specifications

1-way (SH series) Air Discharge Cassette Type (MMU-AP***4SH-E)


TC : Total capacity [kW] SHC : Sensible capacity [kW]
Indoor air temp.
Unit Outdoor 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
size air temp. 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
°CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
12.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
14.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
16.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
18.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
20.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
21.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
015 23.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
25.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
27.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
29.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
31.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
33.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
35.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
37.0 3.6 2.7 4.0 2.9 4.2 3.1 4.4 3.1 4.5 3.1 4.7 3.1 5.0 3.0
39.0 3.5 2.7 3.8 2.8 4.1 3.0 4.2 3.0 4.4 3.0 4.6 3.0 4.8 2.9
10.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
12.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
14.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
16.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
18.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
20.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
21.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
018 23.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
25.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
27.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
29.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
31.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
33.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
35.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
37.0 4.5 3.3 4.9 3.6 5.3 3.8 5.4 3.8 5.6 3.8 5.9 3.7 6.2 3.7
39.0 4.3 3.3 4.8 3.5 5.1 3.7 5.3 3.7 5.4 3.7 5.7 3.6 6.0 3.6
10.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
12.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
14.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
16.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
18.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
20.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
21.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
024 23.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
25.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
27.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
29.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
31.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
33.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
35.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
37.0 5.6 4.3 6.2 4.6 6.7 4.9 6.9 4.8 7.1 4.8 7.5 4.8 7.8 4.7
39.0 5.5 4.2 6.1 4.4 6.5 4.7 6.7 4.7 6.9 4.7 7.3 4.7 7.6 4.6

11 -129
11 Technical Specifications

7. Air throw distance chart

MMU-AP0074YH-E, AP0094YH-E, AP0124YH-E

H (High wind, L (Low wind,


blowing downward) blowing downward)
2.7m 5.0 2.7m 4.0

2 2
2.5
2.3

1 1
0.5
0.9
0.2
0.4 0.6 0.4 0.2 0.3
0 1 2 3m 0 1 2 3m

H (High wind, L (Low wind,


blowing horizontally) blowing horizontally)
2.7m 4.5 1.7 2.7m 3.0 1.5
1.5 0.3 1.1
2 0.3
2
0.4

1 1

0 1 2 3m 0 1 2 3m

MMU-AP0154SH-E, AP0184SH-E MMU-AP0244SH-E

Main unit Main unit


3.5m 3.5m

3m
3m

2m
2m

1.0 0.3
1m 0.3
0.3 1.0 1m
0.5 0.3
0.5 0.5
0.5

1m 2m 3m 4m
1m 2m 3m 4m

unit : [ m/s ]

11 -130
11 Technical Specifications

8. Sound Characteristics (NC Curve)

1-way (SH series) Air Discharge Cassette Type

MMU-AP0154SH-E MMU-AP0244SH-E
Fan tap H M L Fan tap H M L
Sound pressure Sound pressure
level (dB(A)) 37 35 32 level (dB(A)) 45 41 37

90 90
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)


80 80

70 NC-70 70 NC-70

60 NC-60 60 NC-60

50 NC-50 50 NC-50
H
40 NC-40 40 M NC-40
H M
30 NC-30 30 L NC-30
L
20 Approximate threshold of 20
NC-20 Approximate threshold of NC-20
hearing for continuous noise hearing for continuous noise
10 10
63 125 250 500 1000 2000 4000 8000
63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

MMU-AP0184SH-E
Fan tap H M L
Sound pressure
level (dB(A)) 38 36 34

90
Octave band sound pressure level (dB)

80

70 NC-70

60 NC-60

50 NC-50
Center
1.5m
40 NC-40
H M Microphone
30 NC-30
L
20
Approximate threshold of NC-20
hearing for continuous noise
10
63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)

11 -131
11 Technical Specifications

9. Fresh air intake (Design guide)

1-way (SH series) Air Discharge Cassette Type

Caution
The fresh air shall be conditioned by a heat reclaim ventilator or similar.
Ensure the fresh air volume is determined so that mixed suction air and fresh air can maintain the
operating temperature.
*1.Recommended conditioned air temperature is 12 °C to 30 °C.
However, Make a fresh air volume within 20% of standard.
Model name MMU- AP0154SH-E AP0184SH-E AP0244SH-E
Standard air flow (m 3/h) 750 780 1140

Install a filter within the fresh air duct.


(Fresh air does not pass through the filter of Indoor unit.)
Insulate the fresh air duct.
Electrically connect the fan of the Heat exchanger unit and the Indoor unit to a single isolator.

80

70
MMU-AP0154SH-E,MMU-AP184SH-E
60
Static Pressure (Pa)

50

40

30
MMU-AP0244SH-E
20

10

0
0 50 100 150 200 250
Fresh Air Volume (m3/h)

Indoor unit Duct fan


motor Fresh Air Volume

Flange Option :TCB-FF101URE

Inter - lock circuit


Connect the driving relay of the duct fan(DC 12V) between 1 and 6 on the indoor P.C. board.
(Rated current of the relay for duct fan should be up to 75mA.)
After installation, carry out a trial operation to check that the duct fan of the indoor unit start/stop
simultaneously.
(Carry out the trial operation following the installation manual of the indoor unit.)

11 -132
11 Technical Specifications

10. Accessories
Parts name Model name Applied model Note Remarks
RBC-UY136PG MMU-AP***4YH-E Required accessory
Ceiling panel
RBC-US21PGE Required accessory
Front air discharge unit TCB-BUS21HWE
MMU-AP***4SH-E
For easy fresh air intake by using the knockout hole of indoor unit. (dia.=100
Auxiliary fresh air flange TCB-FF101URE2
mm)

MMU-AP0074YH-E, AP0094YH-E, AP0124YH-E Front air discharge unit


TCB-BUS21HWE

Ceiling panel
RBC-UY136PG
TCB-FF101URE2

Ceiling panel
RBC-US21PGE
MMU-AP0154SH-E, AP0184SH-E, AP0244SH-E

11 -133
11 Technical Specifications

11 -134
11 Technical Specifications

11-2-5. Concealed Duct Type

Concealed Duct Type

MMD-AP0074BH-E / MMD-AP0094BH-E
MMD-AP0124BH-E / MMD-AP0154BH-E
MMD-AP0184BH-E / MMD-AP0244BH-E
MMD-AP0274BH-E / MMD-AP0304BH-E
MMD-AP0364BH-E / MMD-AP0484BH-E
MMD-AP0564BH-E

Contents
1. Specifications
2. Dimension
3. Wiring diagram
4. Center of Gravity
5. Electrical characteristics
6. Sensible capacity table
7. Fan characteristics
8. Sound characteristics (NC-Curve)
9. Accessories

11 -135
11 Technical Specifications

1. Specifications

Concealed Duct Type


Model name MMD- AP0074 AP0094 AP0124 AP0154 AP0184 AP0244 AP0274 AP0304 AP0364 AP0484 AP0564
BH-E BH-E BH-E BH-E BH-E BH-E BH-E BH-E BH-E BH-E BH-E

Cooling/Heating capacity (Note 1) (kW) 2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3 7.1/8.0 8.0/9.0 9.0/10.0 11.2/12.5 14.0/16.0 16.0/18.0

Power supply 1 phase 50Hz 230V (220 - 240V) (Separate power supply for indoor units is required.)

Running current (A) 0.29 0.34 0.43 0.52 0.61 0.83 0.98
Electrical
characteristics
Power consumption (kW) 0.033 0.039 0.050 0.060 0.071 0.107 0.128

Starting current (A) 0.5 0.59 0.75 0.90 1.05 1.44 1.70

Appearance Main unit Zinc hot dipping steel plate

Height (mm) 320

Main unit Width (mm) 550 700 1,000 1,350

Depth (mm) 800


Outer
dimension
Height (mm) 9
Suction
ceiling Width (mm) 630 780 1,080 1,430
panel
Depth (mm) 500

Main unit (kg) 28 32 43 55


Total weight
Ceiling panel (kg) 3.5 4 6 7

Heat exchanger Finned tube

Soundproof/Heat-insulating material Non-flammable insulation

Fan Centrifugal fan

Standard air flow High 480 570 650 780 1,140 1,260 1,620 1,980
(Mid./Low) (m3/h) (420/340) (490/400) (540/480) (660/540) (990/870) (1080/870) (1410/1200) (1710/1490)

Fan unit Motor output (W) 120

External static pressure


(Pa) 50
(factory setting)

External static pressure (Pa) 110

Air filter Standard filter (Long life filter)

Controller Remote controller

Gas side (mm) / 9.5


O / 12.7
O / 15.9
O

Connecting
pipe Liquid side (mm) / 6.4
O / 9.5
O

Drain port (Nominal dia. mm) 25 (Polyvinyl chloride tube)

Sound pressure level(Note 2)


(dB(A)) 30/ 28/ 26 31/ 29/ 27 32/ 30/ 28 33/ 31/ 29 34/ 32/ 29 36/ 34/ 32 38/36/32
(High/Mid./Low)

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on the
reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.
Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27 C DB/19 C WB, Outdoor air temperature 35 C DB
O O O

Heating : Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB/6 C WB


O O O

11 -136
11 Technical Specifications

2. Dimension

MMD-AP0074BH-E, AP0094BH-E, AP0124BH-E, AP0154BH-E, AP0184BH-E, AP0244BH-E, AP0274BH-E,


AP0304BH-E, AP0364BH-E, AP0484BH-E, AP0564BH-E
Hanging bolt 4-M10 procured locally
Drain pipe connecting port
Hanging bolt pitch A ±7.5 25 800 40
B
Hanging bolt pitch 700
(When attaching directly)
41 59
130 C 142
φ125 knockout hole for taking-in air 50 638
498
393
101

44 Refrigerant pipe
connecting port

41
215
(Gas side)
49

131
196

243
50
50
Air outlet Air inlet
70 to 270

10-φ4 tapping screw φ160


Refrigerant pipe
connecting port φ26 power supply, remote Panel C, L
Ceiling open dimension D (Liquid side) controller wire exit port
or less

240
271
550 or less

Ceiling opening 470

Air suction E
100 or less

Drain standing-up size

Space required for installation Air outlet Ceiling opening part


and servicing
Be sure to place a check port A at the (150) Check
position indicated in the figure for
port A
Model MMD- A B C D E maintenance of the equipment. 450
AP0074BH-E, AP0094BH-E, AP0124BH-E 616 550 350 600 470 Check

300
port B
AP0154BH-E, AP0184BH-E 766 700 500 750 620 450
AP0244BH-E, AP0274BH-E, AP0304BH-E 1066 1000 800 1050 920 Air filter
AP0364BH-E, AP0484BH-E, AP0564BH-E 1416 1350 1150 1400 1270 700 for maintenance of air filter 700 for maintenance of air filter

(Unit: mm)

11 -137
11 Technical Specifications

3. Wiring diagram

MMD-AP0074BH-E, AP0094BH-E, AP0124BH-E, AP0154BH-E, AP0184BH-E, AP0244BH-E,


AP0274BH-E, AP0304BH-E, AP0364BH-E, AP0484BH-E, AP0564BH-E

11 -138
11 Technical Specifications

4.Center of Gravity
Model name X(mm) Y(mm) Z(mm) Total weight(kg)
MMD-AP0074BH-E
MMD-AP0094BH-E 420 270 155 28
MMD-AP0124BH-E
MMD-AP0154BH-E
430 370 155 32
MMD-AP0184BH-E
MMD-AP0244BH-E
MMD-AP0274BH-E 435 460 155 43
MMD-AP0304BH-E
MMD-AP0364BH-E
MMD-AP0484BH-E 430 635 155 55
MMD-AP0564BH-E

Bottom side

Air outlet

11 -139
11 Technical Specifications

5. Electrical characteristics

Nominal Voltage Voltage Range Fan Motor Power Supply


Ty p e Mo d el
(V-Ph-Hz) Min Max kW FLA MCA MOCP
MMD-AP0074BH-E 230-1-50 198 264 0.120 0.33 0.41 15
MMD-AP0094BH-E 230-1-50 198 264 0.120 0.33 0.41 15
MMD-AP0124BH-E 230-1-50 198 264 0.120 0.39 0.49 15
MMD-AP0154BH-E 230-1-50 198 264 0.120 0.39 0.49 15
MMD-AP0184BH-E 230-1-50 198 264 0.120 0.50 0.62 15
Concealed Duct Type MMD-AP0244BH-E 230-1-50 198 264 0.120 0.60 0.75 15
MMD-AP0274BH-E 230-1-50 198 264 0.120 0.60 0.75 15
MMD-AP0304BH-E 230-1-50 198 264 0.120 0.70 0.88 15
MMD-AP0364BH-E 230-1-50 198 264 0.120 0.96 1.20 15
MMD-AP0484BH-E 230-1-50 198 264 0.120 1.13 1.41 15
MMD-AP0564BH-E 230-1-50 198 264 0.120 1.13 1.41 15

MCA : Minimum Circuit Amps FLA : Full Load Amps


MOCP : Maximum Overcurrent Protection (Amps)

11 -140
11 Technical Specifications

6. Sensible capacity

Concealed Duct Type ( MMD-AP***4BH-E ) TC : Total capacity [kW] SHC : Sensible capacity [kW]
indoor air temp.
o o o o o o o
unit outdoor 14.0 CWB 16.0 CWB 18.0 CWB 19.0 CWB 20.0 CWB 22.0 CWB 24.0 CWB
size air temp. o
20 CDB
o
23 CDB
o
26 CDB
o
27 CDB
o
28 CDB
o
30 CDB
o
32 CDB
o
CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
12.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
14.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
16.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
18.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
20.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
21.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
007 23.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
25.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
27.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
29.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
31.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
33.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
35.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
37.0 1.7 1.5 1.9 1.6 2.1 1.7 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.6
39.0 1.7 1.4 1.9 1.5 2.0 1.6 2.1 1.6 2.1 1.6 2.3 1.6 2.4 1.5
10.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
12.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
14.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
16.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
18.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
20.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
21.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
009 23.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
25.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
27.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
29.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
31.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
33.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
35.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
37.0 2.2 1.8 2.5 1.9 2.6 2.0 2.7 2.0 2.8 2.0 3.0 2.0 3.1 2.0
39.0 2.2 1.8 2.4 1.9 2.6 2.0 2.6 2.0 2.7 2.0 2.9 2.0 3.0 1.9
10.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
12.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
14.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
16.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
18.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
20.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
21.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
012 23.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
25.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
27.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
29.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
31.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
33.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
35.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
37.0 2.9 2.1 3.2 2.3 3.4 2.4 3.5 2.4 3.6 2.4 3.8 2.4 4.0 2.3
39.0 2.8 2.1 3.1 2.2 3.3 2.4 3.4 2.4 3.5 2.4 3.7 2.3 3.9 2.3
10.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.9
12.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.9
14.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.9
16.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.9
18.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.9
20.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.9
21.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.9
015 23.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.9
25.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.9
27.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.9
29.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.9
31.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.9
33.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.9
35.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.9
37.0 3.6 2.6 4.0 2.7 4.2 2.9 4.4 2.9 4.5 2.9 4.7 2.9 5.0 2.8
39.0 3.5 2.5 3.8 2.7 4.1 2.8 4.2 2.8 4.4 2.8 4.6 2.8 4.8 2.7

11 -141
11 Technical Specifications

Concealed Duct Type ( MMD-AP***4BH-E ) TC : Total capacity [kW] SHC : Sensible capacity [kW]
indoor air temp.
o o o o o o o
unit outdoor 14.0 CWB 16.0 CWB 18.0 CWB 19.0 CWB 20.0 CWB 22.0 CWB 24.0 CWB
size air temp. o
20 CDB
o
23 CDB
o
26 CDB
o
27 CDB
o
28 CDB
o
30 CDB
o
32 CDB
o
CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.6
12.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.6
14.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.6
16.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.6
18.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.6
20.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.6
21.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.6
018 23.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.6
25.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.6
27.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.6
29.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.6
31.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.6
33.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.6
35.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.6
37.0 4.5 3.2 4.9 3.4 5.3 3.6 5.4 3.6 5.6 3.6 5.9 3.5 6.2 3.5
39.0 4.3 3.1 4.8 3.3 5.1 3.5 5.3 3.5 5.4 3.5 5.7 3.4 6.0 3.4
10.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
12.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
14.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
16.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
18.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
20.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
21.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
024 23.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
25.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
27.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
29.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
31.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
33.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
35.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
37.0 5.6 4.3 6.2 4.6 6.7 4.9 6.9 4.8 7.1 4.8 7.5 4.8 7.8 4.7
39.0 5.5 4.2 6.1 4.4 6.5 4.7 6.7 4.7 6.9 4.7 7.3 4.7 7.6 4.6
10.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
12.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
14.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
16.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
18.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
20.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
21.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
027 23.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
25.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
27.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
29.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
31.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
33.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
35.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
37.0 6.4 4.8 7.0 5.1 7.5 5.4 7.7 5.4 8.0 5.4 8.4 5.4 8.8 5.2
39.0 6.2 4.7 6.8 5.0 7.3 5.3 7.5 5.3 7.8 5.3 8.2 5.2 8.6 5.1
10.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
12.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
14.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
16.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
18.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
20.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
21.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
030 23.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
25.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
27.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
29.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
31.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
33.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
35.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0
37.0 7.2 5.3 7.9 5.7 8.5 6.0 8.7 6.0 9.0 6.0 9.5 5.9 9.9 5.8
39.0 7.0 5.2 7.7 5.5 8.2 5.9 8.5 5.8 8.7 5.8 9.2 5.8 9.7 5.6

11 -142
11 Technical Specifications

Concealed Duct Type ( MMD-AP***4BH-E ) TC : Total capacity [kW] SHC : Sensible capacity [kW]
indoor air temp.
o o o o o o o
unit outdoor 14.0 CWB 16.0 CWB 18.0 CWB 19.0 CWB 20.0 CWB 22.0 CWB 24.0 CWB
size air temp. o
20 CDB
o
23 CDB
o
26 CDB
o
27 CDB
o
28 CDB
o
30 CDB
o
32 CDB
o
CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.1
12.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.1
14.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.1
16.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.1
18.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.1
20.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.1
21.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.1
036 23.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.1
25.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.1
27.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.1
29.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.1
31.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.1
33.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.1
35.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.1
37.0 8.9 6.3 9.8 6.7 10.5 7.1 10.8 7.1 11.2 7.1 11.8 7.0 12.4 6.8
39.0 8.7 6.1 9.6 6.5 10.2 6.9 10.5 6.9 10.9 6.9 11.5 6.8 12.0 6.6
10.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.9
12.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.9
14.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.9
16.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.9
18.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.9
20.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.9
21.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.9
048 23.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.9
25.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.9
27.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.9
29.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.9
31.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.9
33.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.9
35.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.9
37.0 11.1 7.9 12.3 8.4 13.1 8.9 13.6 8.9 14.0 8.9 14.8 8.8 15.4 8.6
39.0 10.8 7.7 12.0 8.2 12.8 8.7 13.2 8.7 13.6 8.7 14.4 8.6 15.0 8.4
10.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.5
12.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.5
14.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.5
16.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.5
18.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.5
20.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.5
21.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.5
056 23.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.5
25.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.5
27.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.5
29.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.5
31.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.5
33.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.5
35.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.5
37.0 12.7 9.3 14.1 9.9 15.0 10.5 15.5 10.5 16.0 10.5 16.9 10.4 17.7 10.1
39.0 12.4 9.0 13.7 9.6 14.6 10.2 15.1 10.2 15.5 10.2 16.4 10.1 17.2 9.8

11 -143
11 Technical Specifications

7. Fan characteristics
Factory default : Standard H tap

MMD-AP0074BH-E, AP0094BH-E MMD-AP0124BH-E


Standard air volume:480m3/h Standard air volume:570m3/h
140 140

Hi Hi
gh gh
-st -st
120 ati 120 ati
cp cp
res
su it re
s
re
2 lim su
re
External static pressure (Pa)

External static pressure (Pa)


on
it

H 2
lim

tap i H
at Hi tap
lic
n

gh
tio

100 Hig 100 pp sta


ica

hs A tic

Air volume limit (Max)


tat Air volume limit (Max) pr
Air volume limit (Min)

Air volume limit (Min)


pl

ic es
pre
Ap

su
ss re
u re 1
1 H
H tap
tap
80 80
St
Sta an
nd da
a rd rd
H H
tap ta
p
60 60 Lo
Lo w
w sta
sta tic
tic pr
pre es
ss su
ure re
H H
40 tap 40
tap
Sta Sta
nd nd
ard ard
Lt Lt
ap ap

20 20

long life filter long life filter


0 0
200 400 480 600 300 500 570 700

Air volume(m3/h) Air volume(m3/h)

MMD-AP0154BH-E MMD-AP0184BH-E

140
Standard air volume:650m3/h 140
Standard air volume:780m3/h

Hig
h-s
Hig tati
120
h-st 120 cp
res
atic it s ure
it pres im
lim sure nl 2 H
External static pressure (Pa)

External static pressure (Pa)

2 H o t
ati
ap
t ion tap
lic
ca Ap
p
pli Hig
Ap
100 100 hs
Air volume limit (Max)

Air volume limit (Max)

tati
Hig cp
Air volume limit (Min)
Air volume limit (Min)

h st res
atic s ure
pres 1 H
s u re
1 H tap
ta p
80 80

Sta
nda
Sta rd
nda Ht
rd ap
60 Ht 60
ap

Low
sta Low
tic sta
pre tic
ssu pre
re ssu
40 Ht 40 re
ap Ht
ap
Sta
nda Sta
rd nd
Lt ard
ap Lt
20 20 ap

long life filter long life filter


0 0
400 600 650 800 500 700 780 900

Air volume(m3/ h) Air volume(m3/h)

11 -144
11 Technical Specifications

Factory default : Standard H tap

MMD-AP0244BH-E, AP0274BH-E MMD-AP0304BH-E


3
Standard air volume:1140m /h Standard air volume:1260m3/h
140 140

High
High -stati
-stati c pre
120 c pre 120
ss ure 2
mit
ss ure 2 H tap
t
nl imi H tap
tion
li
External static pressure (Pa)

External static pressure (Pa)


a
lic atio plic
pp Ap
A
100 High 100 High
static static

Air volume limit (Max)

Air volume limit (Max)


press pres

Air volume limit (Min)


Air volume limit (Min)

ure 1 sure
H tap 1 H
tap

80 80

Stan
Stand dard
ard H H tap
tap
60 60

Low s Low s
tatic tatic press
press ure H
ure H tap
tap
40 40
Stand
ard L
tap Stan
dard
L tap

20 20

long life filter long life filter


0 0
8 00 1000 1140 1200 900 1100 1260 1300

3
Air volume(m /h) Air volume(m3/h)

MMD-AP0364BH-E MMD-AP0484BH-E, AP0564BH-E


3
Standard air volume:1620m /h Standard air volume:1980m3/h
140 140

High
-stati
c pre Hig
120 i t ssu re 2 120 h-s
lim H tap it tati
cp
on nl
im res
ati o
s ure
plic ati
2 H
External static pressure (Pa)
External static pressure (Pa)

Ap li c tap
A pp
100 High 100
stati Hig
c pre h st
s atic
Air volume limit (Max)

sure
1 H pre
Air volume limit (Max)

ss
Air volume limit (Min)

tap ure
Air volume limit (Min)

1 H
tap
80 80

Sta
Stan nda
dard rd
H tap H ta
60 60
p

Low
Low stat
stati ic p
c pre ress
ssu u re H
re H tap
40 tap 40

Stan
Stan dard
dard L ta
L tap p

20 20

long life filter long life filter


0 0
1200 1620 2000 1400 1800 1980 2200

Air volume(m3/h) Air volume(m3/h)

11 -145
11 Technical Specifications

8. Sound level data (NC CURVE)

MMD-AP0074BH-E, AP0094BH-E
Fan Tap H M L
Sound pressure level
(dB(A)) 30 28 26

90

80

Octave band sound pressure level(dB)


70 NC-70

60 NC-60

50 NC-50

40 NC-40

Microphone 30
H
NC-30
M
L
20 Audibility limits of NC-20
white level

10
63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)

MMD-AP0124BH-E MMD-AP0154BH-E
Fan Tap H M L Fan Tap H M L
Sound pressure level Sound pressure level
(dB(A)) 31 29 27 (dB(A)) 31 29 27

90 90

80 80
Octave band sound pressure level(dB)
Octave band sound pressure level(dB)

70 NC-70 70 NC-70

60 NC-60 60 NC-60

50 NC-50 50 NC-50

40 NC-40 40 NC-40

30 NC-30 30 NC-30
H
H
20 Audibility limits of NC-20 20 Audibility limits of
M NC-20
white level
M white level
L L
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

MMD-AP0184BH-E
Fan Tap H M L
Overall level
dB(A) 32 30 28

90

80
Octave band sound pressure level(dB)

70 NC-70

60 NC-60

50 NC-50

40 NC-40

30 H NC-30
M

20 Audibility limits of
L NC-20
white level

10
63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

11 -146
11 Technical Specifications

MMD-AP0244BH-E, AP0274BH-E MMD-AP0304BH-E


Fan Tap H M L Fan Tap H M L
Sound pressure level Sound pressure level
(dB(A)) 33 31 29 (dB(A)) 34 32 29

90 90

80 80

Octave band sound pressure level(dB)


Octave band sound pressure level(dB)

70 NC-70 70 NC-70

60 NC-60 60 NC-60

50 NC-50 50 NC-50

40 NC-40 40 NC-40

30 NC-30 30 NC-30

20 Audibility limits of NC-20 20 Audibility limits of NC-20


white level white level

10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

MMD-AP0364BH-E MMD-AP0484BH-E, AP0564BH-E


Fan Tap H M L Fan Tap H M L
Sound pressure level Sound pressure level
(dB(A)) 36 34 32 (dB(A)) 38 36 32

90 90

80 80
Octave band sound pressure level(dB)

Octave band sound pressure level(dB)

70 NC-70 70 NC-70

60 NC-60 60 NC-60

50 NC-50 50 NC-50

40 NC-40 40 NC-40

30 NC-30 30 NC-30

20 Audibility limits of NC-20 20 Audibility limits of NC-20


white level white level

10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz) Octave band center frequency (Hz)

11 -147
11 Technical Specifications

9. Accessories
Parts name Model name Applied model Note Remarks
TCB-UFM11BFCE MMD-AP0074/0094/0124BH-E Use with TCB-FC281BE
High-efficiency filter 65 TCB-UFM21BFCE MMD-AP0154/0184BH-E Dust collecting effect: 65% Use with TCB-FC501BE
(for rear suction) TCB-UFM11BFCE (2 pcs.) MMD-AP0244/0274/0304BH-E (NBS Colorimentric method) Use with TCB-FC801BE
TCB-UFM21BFCE (2 pcs.) MMD-AP0364/0484/0564BH-E Use with TCB-FC1401BE
TCB-UFH51BFCE MMD-AP0074/0094/0124BH-E Use with TCB-FC281BE
High-efficiency filter 90 TCB-UFH61BFCE MMD-AP0154/0184BH-E Dust collecting effect: 90% Use with TCB-FC501BE
(for rear suction) TCB-UFH51BFCE (2 pcs.) MMD-AP0244/0274/0304BH-E (NBS Colorimentric method) Use with TCB-FC801BE
TCB-UFH61BFCE (2 pcs.) MMD-AP0364/0484/0564BH-E Use with TCB-FC1401BE
TCB-FC281BE MMD-AP0074/0094/0124BH-E
Filter chamber TCB-FC501BE MMD-AP0154/0184BH-E
For high-efficiency filter
(for rear suction) TCB-FC801BE MMD-AP0244/0274/0304BH-E
TCB-FC1401BE MMD-AP0364/0484/0564BH-E
TCB-UFM11BE MMD-AP0074/0094/0124BH-E
High-efficiency filter 65 TCB-UFM21BE MMD-AP0154/0184BH-E Dust collecting effect: 65%
(for underside suction) TCB-UFM31BE MMD-AP0244/0274/0304BH-E (NBS Colorimentric method)
TCB-UFM41BE MMD-AP0364/0484/0564BH-E
TCB-UFH51BE MMD-AP0074/0094/0124BH-E
High-efficiency filter 90 TCB-UFH61BE MMD-AP0154/0184BH-E Dust collecting effect: 90%
(for underside suction) TCB-UFH71BE MMD-AP0244/0274/0304BH-E (NBS Colorimentric method)
TCB-UFH81BE MMD-AP0364/0484/0564BH-E
RBC-UD281PE(W) MMD-AP0074/0094/0124BH-E
Ceiling panel RBC-UD501PE(W) MMD-AP0154/0184BH-E
(half panel for underside
suction) RBC-UD801PE(W) MMD-AP0244/0274/0304BH-E
RBC-UD1401PE(W) MMD-AP0364/0484/0564BH-E
TCB-CA281BE MMD-AP0074/0094/0124BH-E
Suction canvas TCB-CA501BE MMD-AP0154/0184BH-E
Adjustment height of the suction canvas is between 40 mm and 100 mm
(for underside suction) TCB-CA801BE MMD-AP0244/0274/0304BH-E
TCB-CA1401BE MMD-AP0364/0484/0564BH-E
TCB-FK281BE MMD-AP0074/0094/0124BH-E
TCB-FK501BE MMD-AP0154/0184BH-E
Filter kit for underside Kit of underside prefilter & shielding plate of rear suction
TCB-FK801BE MMD-AP0244/0274/0304BH-E
TCB-FK1401BE MMD-AP0364/0484/0564BH-E

TCB-UFM11BFCE TCB-UFH51BFCE
TCB-UFM21BFCE TCB-UFH61BFCE

TCB-UFM11BE
TCB-UFM21BE
TCB-UFM31BE
TCB-UFM41BE

TCB-UFH51BE
TCB-UFH61BE
TCB-UFH71BE
TCB-UFH81BE
Filter chamber
TCB-FC281BE, TCB-FC501BE
TCB-FC801BE, TCB-FC1401BE

Suction canvas
TCB-CA281BE, TCB-CA501BE Back Filter kit for
TCB-CA801BE, TCB-CA1401BE cover underside
TCB-FK281BE
TCB-FK501BE
Ceiling panel TCB-FK801BE
RBC-UD281PE(W)/RBC-UD501PE(W) Filter guide TCB-FK1401BE
RBC-UD801PE(W)/RBC-UD1401PE(W)

11 -148
11 Technical Specifications

11-2-6. Concealed Duct High Static Pressure Type

Concealed Duct
High Static Pressure Type

MMD-AP0184H-E / MMD-AP0244H-E
MMD-AP0274H-E / MMD-AP0364H-E
MMD-AP0484H-E / MMD-AP0724H-E
MMD-AP0964H-E

Contents
1. Specifications
2. Dimension
3. Wiring diagram
4. Center of Gravity
5. Electrical characteristics
6. Sensible capacity table
7. Fan characteristics
8. Sound characteristics (NC-Curve)
9. Accessories

11 -149
11 Technical Specifications

1. Specifications

Concealed Duct High Static Pressure Type


M od el name MMD - AP0184H-E AP0244H-E AP0274H-E AP0364H-E AP0484H-E AP0724H-E AP0964H-E

Cooling/Heating capacity (Note 1) (kW) 5.6/6.3 7.1/8.0 8.0/9.0 11.2/12.5 14.0/16.0 22.4/25.0 28.0/31.5

Power supply 1 phase 50Hz 230V (220 - 240V) (Separate power supply for indoor units is required.)

Running current (A) 0.81 1.35 1.63 1.84 5.25 5.52

Electrical
Power consumption (kW) 0.184 0.299 0.368 0.414 1.200 1.260
characteristics
Power factor (%) 99 96 98 98 99 99

Starting current (A) 1.3 3.5 4.1 4.8 13.6 14.8

Appearance Zinc hot dipping steel plate

Outer (mm) 380 x 850 x 660 380 x 1,200 x 660 470 x 1,380 x 1,250
Height x Width x Depth
dimension

Total weight (kg) 50 52 56 67 150

Heat exchanger Finned tube

Soundproof/Heat-insulating material Non-flammable insulation

Fan Centrifugal fan

Standard air flow (m3/h) 900 1,320 1,600 2,100 3,600 4,200

Motor output (W) 160 260 370 x 3

Fan External static pressure


(Pa) 137
unit (Factory setting)

External static pressure (Pa) 68.6-137-196

Air flow limit (m3/h)


Lower limit/Upper limit 720/1,080 1,060/1,580 1,280/1,920 1,680/2,520 2,880/4,320 3,360/5,040

Air filter Option or field supply

Controller Remote controller

Gas side (mm) / 12.7


O / 15.9
O / 22.2
O

Connecting Liquid side (mm) / 6.4


O / 9.5
O / 12.7
O
pipe
Drain port (Nominal dia. mm) 25 (One side of male screw)

Sound pressure level(Note 2) (dB(A))


(High/Mid./Low) 37 40 49 50

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on the
reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.
Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27 C DB/19 C WB, Outdoor air temperature 35 C DB
O O O

Heating : Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB/6 C WB


O O O

11 -150
11 Technical Specifications

2. Dimension
MMD-AP0184H-E, AP0244H-E, AP0274H-E, AP0364H-E
150 275 275 (150)

17
70
Hole for hanging bolt
850

316
(4-φ12×72) Z view
Z
13

(182) 426 242

30 35
Left side
AP0181H Air outlet Air inlet

(47)
(141) 226

70

710
to
AP0271H Screw hole for
Electric parts box duct mounting (6-M6)
Screw hole Air outlet
Power supply/
for duct mounting (4-M6)

70
communication piping
850 port (φ26) (bottom side
13

348 348 77 of electric parts box) Hanging bolt pitch


Space required

or more
700 Service
(141) 226

500
Left side
AP0361H
740 for installation space
Refrigerant pipe Refrigerant pipe and servicing
Air outlet Screw hole for duct connecting port connecting port
mounting (6-M6) (Gas side) (Liquid side)
660 Check port
600

or more
Service

1000
105 60

380
90 40
space
35

Drain pipe

35
connecting port 110 (Unit: mm)
30

MMD-AP0484H-E
70

Hole for hanging bolt 150 300 300 300 (150)

316 17
(4-φ12×72)
Z Z view
1200

85
1060

Air outlet Air inlet


13

(47)
(202) 316 164 316
Screw hole for
duct mounting (8-M6)
(141) 226

Left side
Air outlet Electric parts box
Power supply/
70

Screw hole for


Space required

or more
duct mounting (8-M6) communication piping Service

500
port (φ26) (bottom side for installation space
of electric parts box) Hanging bolt pitch and servicing
700
740
Check port
Refrigerant pipe Refrigerant pipe 600
or more Service
1000
connecting port connecting port
(Gas side) (Liquid side) space

660
(Unit: mm)
105 60
380
90 40
35

35

Drain pipe
110
30

connecting port

MMD-AP0724H-E, AP0964H-E
250 250 250 250 190
Hanging bolt pitch 1260

Z Z view
370
1380

190 250 250 250 250


29

Air outlet Air inlet


65

Screw hole for


406

duct mounting (10-M6)

Left side
35

Air outlet
Screw hole for
100

duct mounting (10-M6) Hanging bolt pitch 1288


1328
Electric parts box
Hole for hanging bolt (4- φ12×92) Space required
or more

Service
200

for installation space


Refrigerant pipe Refrigerant pipe and servicing
connecting port connecting port
(Gas side) (Liquid side)
Check port
1250 1000
or more

Service
1000

space
200 150

470

(Unit: mm)
31
45

624
698
Drain pipe
connecting port

11 -151
11 Technical Specifications

3. Wiring diagram

MMD-AP0184H-E, AP0244H-E, AP0274H-E, AP0364H-E, AP0484H-E

11 -152
11 Technical Specifications

AP0724H-E, AP0964H-E

11 -153
11 Technical Specifications

4. Center of gravity

Model name X (mm) Total weight(kg)


MMD-AP0184H-E 50
MMD-AP0244H-E 520
52
MMD-AP0274H-E

MMD-AP0364H-E 400 56

MMD-AP0484H-E 565 67
MML-AP0724H-E 150
660
MML-AP0964H-E 150

290

220

Y=540, Z=205(mm)

5. Electrical characteristics
Nominal Voltage Voltage Range Fan Motor Power Supply
Ty p e Mo d el
(V-Ph-Hz) Min Max kW FLA MCA MOCP
MMD-AP0184H-E 230-1-50 198 264 0.160 0.93 1.16 15
MMD-AP0244H-E 230-1-50 198 264 0.160 1.55 1.94 15
MMD-AP0274H-E 230-1-50 198 264 0.160 1.55 1.94 15
Concealed Duct
High Static MMD-AP0364H-E 230-1-50 198 264 0.260 1.87 2.34 15
Pressure Type
MMD-AP0484H-E 230-1-50 198 264 0.260 2.12 2.65 15
MMD-AP0724H-E 230-1-50 198 264 0.370 x 3 6.04 7.55 15
MMD-AP0964H-E 230-1-50 198 264 0.370 x 3 6.35 7.94 15

MCA : Minimum Circuit Amps FLA : Full Load Amps


MOCP : Maximum Overcurrent Protection (Amps)

11 -154
11 Technical Specifications

6. Sensible capacity table

Concealed Duct High Static Pressure Type ( MMD-AP***4H-E )


TC : Total capacity [kW] SHC : Sensible capacity [kW]
indoor air temp.
o o o o o o o
unit outdoor 14.0 CWB 16.0 CWB 18.0 CWB 19.0 CWB 20.0 CWB 22.0 CWB 24.0 CWB
size air temp. o
20 CDB
o
23 CDB
o
26 CDB
o
27 CDB
o
28 CDB
o
30 CDB
o
32 CDB
o
CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
12.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
14.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
16.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
18.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
20.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
21.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
018 23.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
25.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
27.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
29.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
31.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
33.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
35.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9
37.0 4.5 3.5 4.9 3.7 5.3 3.9 5.4 3.9 5.6 3.9 5.9 3.9 6.2 3.8
39.0 4.3 3.4 4.8 3.6 5.1 3.8 5.3 3.8 5.4 3.8 5.7 3.8 6.0 3.7
10.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
12.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
14.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
16.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
18.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
20.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
21.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
024 23.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
25.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
27.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
29.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
31.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
33.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
35.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8
37.0 5.6 4.3 6.2 4.6 6.7 4.9 6.9 4.8 7.1 4.8 7.5 4.8 7.8 4.7
39.0 5.5 4.2 6.1 4.4 6.5 4.7 6.7 4.7 6.9 4.7 7.3 4.7 7.6 4.6
10.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.2
12.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.2
14.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.2
16.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.2
18.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.2
20.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.2
21.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.2
027 23.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.2
25.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.2
27.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.2
29.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.2
31.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.2
33.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.2
35.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.2
37.0 6.4 4.6 7.0 4.9 7.5 5.2 7.7 5.2 8.0 5.2 8.4 5.2 8.8 5.1
39.0 6.2 4.5 6.8 4.8 7.3 5.1 7.5 5.1 7.8 5.1 8.2 5.0 8.6 4.9
10.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.5
12.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.5
14.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.5
16.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.5
18.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.5
20.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.5
21.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.5
036 23.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.5
25.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.5
27.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.5
29.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.5
31.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.5
33.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.5
35.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.5
37.0 8.9 6.7 9.8 7.1 10.5 7.6 10.8 7.6 11.2 7.5 11.8 7.5 12.4 7.3
39.0 8.7 6.5 9.6 6.9 10.2 7.4 10.5 7.3 10.9 7.3 11.5 7.3 12.0 7.1

11 -155
11 Technical Specifications

Concealed Duct High Static Pressure Type ( MMD-AP***4H-E )


TC : Total capacity [kW] SHC : Sensible capacity [kW]
indoor air temp.
o o o o o o o
unit outdoor 14.0 CWB 16.0 CWB 18.0 CWB 19.0 CWB 20.0 CWB 22.0 CWB 24.0 CWB
size air temp. o
20 CDB
o
23 CDB
o
26 CDB
o
27 CDB
o
28 CDB
o
30 CDB
o
32 CDB
o
CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.2
12.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.2
14.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.2
16.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.2
18.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.2
20.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.2
21.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.2
048 23.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.2
25.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.2
27.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.2
29.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.2
31.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.2
33.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.2
35.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.2
37.0 11.1 8.2 12.3 8.7 13.1 9.2 13.6 9.2 14.0 9.2 14.8 9.1 15.4 8.9
39.0 10.8 7.9 12.0 8.4 12.8 9.0 13.2 8.9 13.6 8.9 14.4 8.9 15.0 8.7
10.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.4
12.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.4
14.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.4
16.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.4
18.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.4
20.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.4
21.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.4
072 23.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.4
25.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.4
27.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.4
29.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.4
31.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.4
33.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.4
35.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.4
37.0 17.8 12.8 19.7 13.6 21.0 14.5 21.7 14.4 22.3 14.4 23.6 14.3 24.7 14.0
39.0 17.3 12.4 19.1 13.2 20.4 14.1 21.1 14.0 21.7 14.0 23.0 13.9 24.0 13.6
10.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.7
12.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.7
14.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.7
16.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.7
18.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.7
20.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.7
21.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.7
096 23.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.7
25.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.7
27.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.7
29.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.7
31.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.7
33.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.7
35.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.7
37.0 22.3 15.7 24.6 16.7 26.3 17.8 18.3 17.7 27.9 17.7 29.5 17.6 30.9 17.1
39.0 21.6 15.3 23.9 16.3 25.6 17.3 26.3 17.2 27.1 17.2 28.7 17.1 30.0 16.7

11 -156
11 Technical Specifications

7.Fan characteristic
MMD-AP0184H-E MMD-AP0244H-E, AP0274H-E

Standard air volume: 900 m 3/h Standard air volume: 1320 m 3/h
1.5 2.0

Fan motor current (A)


Fan motor current (A)

High static pressure tap High static pressure tap


Medium static pressure tap

Medium static pressure tap


1.0 1.5

Low static pressure tap Low static pressure tap


0.5 1.0

300
250
50Hz 50Hz
60Hz 60Hz
Hi 250
gh

Air volume lower limit

Air volume upper limit


sta Hi
tic gh

Outside static pressure (Pa)


200
Outside static pressure (Pa)

pre st
ss at
ure ic
M pr
Air volume lower limit

ed tap 200 es
iu M su
ed
Air volume upper limit

m re
st iu ta
150 at m p
ic st
pr at
es 150 ic
Lo su pr
re es
w su
st ta re

Lo
100 at p ta

w
ic
pr p

st
es 100

at
ic
su

pr
re

es
ta

su
p

re
50

ta
50

p
1320
0 0
700 800 900 1000 1100 1000 1100 1200 1300 1400 1500 1600
Air volume (m3/h) Air volume (m3/h)

MMD-AP0364H-E MMD-AP0484H-E
Standard air volume: 1600 m 3/h Standard air volume: 2100 m 3/h
3.0
2.5
Fan motor current (A)

Fan motor current (A)

High static pressure tap


High static pressure tap 2.5
2.0

Medium static pressure tap


2.0
Medium static pressure tap
1.5

Low static pressure tap 1.5

1.0 Lo
Low static pressure tap

0.5
250
Air volume upper limit

50Hz
Hig 60Hz 250
Outside static pressure (Pa)

hs 50Hz
Air volume lower limit

tati Hi
Air volume upper limit

cp gh 60Hz
res sta
Outside static pressure (Pa)

200 sur tic


e ta
p pre
Air volume lower limit

200 ss
Me M ure
diu ed tap
m iu
sta m
150 tic st
pre at
ssu 150 ic
re pr
t ap es
su
Lo re
w ta
100 Lo p
w st
sta 100 at
tic ic
p re pr
ss es
ure su
tap re
50 ta
50 p

2100
0 0
1400 1500 1600 1700 1800 1500 2000 2500
Air volume (m3/h) Air volume (m3/h)

11 -157
11 Technical Specifications

MMD-AP0724H-E
Standard air volume : 3600m 3/h
8
High static pressure tap (60Hz)
7.5

Current of fan motor (A)


7
Medium static pressure tap (60Hz)
Low static pressure tap (60Hz)
6.5

6
High static pressure tap (50Hz)
Medium static pressure tap (50Hz)
5.5

4.5
Low static pressure tap
4

300
External static pressure (Pa)

High static pressure tap (50Hz)


250

200

150
High static pressure tap (60Hz)
100
Medium static pressure tap (50Hz)
50
Low static pressure tap (50Hz) Medium static pressure tap (60Hz)
5 Low static pressure tap (60Hz)
2880 3000 3200 3400 3600 3800 4000 4200 4320

Air volume (m3/h)


Lower limit of air volume Upper limit of air volume

MMD-AP0964H-E
Standard air volume : 4200m 3/h
8.5

8
High static pressure tap (60Hz)
Medium static pressure tap (60Hz)
7.5
Current of fan motor (A)

Low static pressure tap (60Hz)


7
High static pressure tap (50Hz)
6.5
Medium static pressure tap (50Hz)
6

5.5

5
Low static pressure tap
4.5

350
External static pressure (Pa)

High static pressure tap (60Hz)


300
High static pressure tap (50Hz)
250

200

150

100

50 Medium static pressure tap (50Hz)


Low static pressure tap (50Hz)
Low static pressure tap (60Hz)
5
3360 3600 4000 4400 4800 5040 Medium static pressure tap (60Hz)

Lower limit of air volume Air volume (m3/h) Upper limit of air volume

REQUIREMENT
Add a air volume damper to the supplied air duct, and adjust the air volume from 80% to 120% of
the standard air volume.

11 -158
11 Technical Specifications

8. Sound level data (NC CURVE) Sound level values shown are based on a measurement in a non resound room.

Microphone

MMD-AP0184H-E MMD-AP0244H-E, AP0274H-E


(50Hz) (50Hz)
Outside still pressure 68.6 (Pa) 137 (Pa) 196 (Pa) Outside still pressure 68.6 (Pa) 137 (Pa) 196 (Pa)

Overall level A 33 37 40 Overall level A 36 40 44


Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

(dB) C 46 51 53 (dB) C 50 53 57

(st and ard sound p ressure 0.0002 μb ar) (st and ard sound p ressure 0.0002 μb ar)
60 NC-60 60 60 NC-60 60

196.0(external static pressure(Pa))


50 50 50 50
NC-50 NC-50

196.0(external static pressure(Pa))


40 40 40 137.2 40
NC-40 NC-40
137.2 68.6
68.6
30 30 30 30
NC-30 NC-30

20 20 20 20
Audibility limits NC-20 Audibility limits NC-20
of continous of continous
10 white level 10 10 white level 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz) Octave band center frequency (Hz)

MMD-AP0364H-E MMD-AP0484H-E
(50Hz) (50Hz)
Outside still pressure 68.6 (Pa) 137 (Pa) 196 (Pa) Outside still pressure 68.6 (Pa) 137 (Pa) 196 (Pa)

Overall level A 36 40 44 Overall level A 36 40 44


Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

(dB) C 49.5 54 59 (dB) C 47 51 54

(st and ard sound p ressure 0.0002 μb ar) (st and ard sound p ressure 0.0002 μb ar)
60 NC-60 60 60 NC-60 60

50 50 50 50
NC-50 NC-50
196.0(external static pressure(Pa)) 196.0(external static pressure(Pa))
40 137.2 40 40 40
NC-40 137.2 NC-40
68.6
68.6
30 30 30 30
NC-30 NC-30

20 20 20 20
Audibility limits NC-20 Audibility limits NC-20
of continous of continous
10 white level 10 10 white level 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz) Octave band center frequency (Hz)

11 -159
11 Technical Specifications

MMD-AP0724H-E
(50Hz)
Outside still pressure 68.6 (Pa) 137 (Pa) 196 (Pa)
48 49 50.5
Overall level A
(dB) C 54 55 57

90

80
Octave band sound pressure level (dB)

70 NC-70

60 NC-60

50 NC-50

40 NC-40

30 NC-30

Audibility limits
20 of continous NC-20
white level

10
63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)

MMD-AP0964H-E
(50Hz)
Outside still pressure 68.6 (Pa) 137 (Pa) 196 (Pa)
49 50 51.5
Overall level A
(dB) C 56 59 61

90

80
Octave band sound pressure level (dB)

70 NC-70

60 NC-60

50 NC-50

40 NC-40

30 NC-30

Audibility limits
20 of continous NC-20
white level

10
63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)

11 -160
11 Technical Specifications

9. Accessories

Parts name Model name Applied model Note Remarks


TCB-UFM1D-1E MMD-AP0184H-E Use with TCB-FCY21DE
TCB-UFM2D-1E (2 pcs.) MMD-AP0244/0274/0364H-E Dust collecting effect: 65% Use with TCB-FCY31DE
High-efficiency filter 65
TCB-UFM1D-1E (2 pcs.) MMD-AP0484H-E (NBS Colorimentric method) Use with TCB-FCY51DE
TCB-UFM3DE MMD-AP0724/0964H-E Use with TCB-FCY100DE
TCB-UFH5D-1E MMD-AP0184H-E Use with TCB-FCY21DE
TCB-UFH6D-1E (2 pcs.) MMD-AP0244/0274/0364H-E Dust collecting effect: 90% Use with TCB-FCY31DE
High-efficiency filter 90
TCB-UFH5D-1E (2 pcs.) MMD-AP0484H-E (NBS Colorimentric method) Use with TCB-FCY51DE
TCB-UFH7DE MMD-AP0724/0964H-E Use with TCB-FCY100DE
TCB-PF1D-1E MMD-AP0184H-E Use with TCB-FCY21DE
TCB-PF2D-1E (2 pcs.) MMD-AP0244/0274/0364H-E Dust collecting effect: 50% Use with TCB-FCY31DE
Long life prefilter
TCB-PF1D-1E (2 pcs.) MMD-AP0484H-E (Weight method) Use with TCB-FCY51DE
TCB-PF3DE MMD-AP0724/0964H-E Use with TCB-FCY100DE
TCB-FCY21DE MMD-AP0184H-E
TCB-FCY31DE MMD-AP0244/0274/0364H-E
Filter chamber For high-efficiency filter or long life prefilter
TCB-FCY51DE MMD-AP0484H-E
TCB-FCY100DE MMD-AP0724/0964H-E
TCB-DP31DE MMD-AP0184H-E to 0484H-E Stand-up 330 or less
Drain pump kit
TCB-DP32DE MMD-AP0724/0964H-E (from bottom face of ceiling)

Filter chamber
TCB-FCY21DE, TCB-FCY31DE
TCB-FCY51DE, TCB-FCY100DE

TCB-PF1D-1E
TCB-PF2D-1E
TCB-PF3DE

TCB-UFM1D-1E, TCB-UFM2D-1E, TCB-UFM3DE

TCB-UFH5D-1E, TCB-UFH6D-1E, TCB-UFM7DE


Drain pump kit
TCB-DP31DE
TCB-DP32DE

11 -161
11 Technical Specifications

11 -162
11 Technical Specifications

11-2-7. Slim Duct Type

Slim Duct Type

Indoor Unit
MMD-AP0074SPH-E
MMD-AP0094SPH-E
MMD-AP0124SPH-E
MMD-AP0154SPH-E
MMD-AP0184SPH-E

Contents
1. Specifications
2. Dimension
3. Wiring diagram
4. Center of Gravity
5. Electrical characteristics
6. Sensible capacity table
7. Fan characteristics
8. Sound characteristics (NC-Curve)
9. Fresh air intake (Design guide)
10. Accessories

11 -163
11 Technical Specifications

1. Specification
50Hz

M odel name M M D- AP0074SPH-E AP0094SPH-E AP0124SPH-E AP0154SPH-E AP0184SPH-E


Cooling/Heating capacity (Note 1) (kW) 2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3
Electrical Power supply 1 phase 50Hz 230V (220-240V)
characteristics Running current (A) 0.29 0.29 0.31 0.32 0.39
Power consumption (kW) 0.039 0.039 0.043 0.045 0.054
Starting current (A) 0.51 0.51 0.54 0.56 0.68
Appearance Zinc hot dipping steel plate
Dimension Height (mm) 210
Width (mm) 845
Depth (mm) 645
Tot al w eight (kg) 22 22 22 23 23
Heat exchanger Finned tube
Soundproof / Heat-insulating material Polyethylene foam + Polyurethane foam
Fan Centrifugal fan (Sirocco fan)
3
Standard air High (m /h) 540 600 690 780
flow (Mid./Low) (m3/h) 470/400 520/450 600/520 680/580
Motor output (W) 60
External static pressure (Pa) 6 (Factory setting) 5 (Factory setting) 4 (Factory setting)
-16-31-46 4steps -15-30-45 4steps -14-29-44 4steps
Air filter pressure loss (Pa) 4 5 6
Controller Remote controller
Air filter Standard filter supplied (Long life filter)
Connecting Gas pipe (mm) Φ9.5 Φ12.7
pipe Liquid pipe (mm) Φ6.4
Drain pipe (Nominal dia.mm) 25 (Polyvinyl chloride tube : External dia.32 Internal dia.25)
Sound pressure level (Note 2) Under air inlet (dB(A)) 36/33/30 38/35/32 39/36/33 40/38/36
High/Mid./Low Back air inlet (dB(A)) 28/26/24 29/27/25 32/30/28 33/3129

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based
on the reference piping.
The reference piping consists of 5 m cf main piping and 2.5 m of branch piping connected with 0 meter height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated valves due to the
effects of external sound.
Note : Reted conditions Cooling: Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating: Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB

11 -164
11 Technical Specifications

2. Dimensions
MMD-AP0074SPH-E, AP0094SPH-E, AP0124SPH-E,AP0154SPH-E, AP0184SPH-E
21 845

57
(inside)
168

210
20 21

21 803 (inside) 21 Refrigerant piping


Air filter 103

67
4-Ø4
19

511
645
31
168
2

422
502
359
372
80
Ø9

120

67

40
805
80 59 910 33
163

Fresh air inlet Drain-up port


(Knock-out hole)
Hanger plate

Air inlet connecting flange (Field supply)


Underside
8.2 or less

805
41.5
100

286.8
266.5

100

12.5 12.5
100 100 100 100 100 100 100 100
45.3

825

n=24 M5 (Ø4.2 mounting hole)


805
Rearside
44.3
188.6
170

100
44.3

12.5 12.5
100 100 100 100 100 100 100 100
825

n=22 M5 (Ø4.2 mounting hole)

11 -165
11 Technical Specifications

Installation space
(length:mm) 5 or more
210
Air outlet 235 or more

100 or more 250 or more

Und er air inlet Rear air inlet

5 or more 5 or more
210 210
235 or m Air intlet 235 or more

Ceiling Air inlet Ceiling


50 or more 300 or more
2500 or more

2500 or more

Floor surface Floor surface

Service space
(length:mm)

Air outlet

50 50 645
945 Air filter

Service door (Ceiling opening)

645

645
945

Service door (Ceiling opening)


Air filter

745

745

945

11 -166
11 Technical Specifications

3. Wiring diagram
MMD-AP0074SPH-E, AP0094SPH-E, AP0124SPH-E, AP0154SPH-E, AP0184SPH-E

11 -167
11 Technical Specifications

4. Center of Gravity
Model name X (mm) Y (mm) Z (mm) Total weight(kg)
MMD-AP0074SPH-E
MMD-AP0094SPH-E 315 470 110 22
MMD-AP0124SPH-E

MMD-AP0154SPH-E
320 460 110 23
MMD-AP0184SPH-E

G
X

Y
Z

5. Electrical characteristics

Model Nominal Voltage Voltage Range Fan Motor Power Supply


(V-Ph-Hz) Min Max kW FLA MCA MOCP
MMD-AP0074SPH-E 230-1-50 198 264 0.060 0.35 0.44 15
MMD-AP0094SPH-E 230-1-50 198 264 0.060 0.35 0.44 15
MMD-AP0124SPH-E 230-1-50 198 264 0.060 0.37 0.47 15
MMD-AP0154SPH-E 230-1-50 198 264 0.060 0.38 0.48 15
MMD-AP0184SPH-E 230-1-50 198 264 0.060 0.47 0.59 15

MCA : Minimum Circuit Amps FLA : Full Load Amps


MOCP : Maximum Overcurrent Protection (Amps)

11 -168
11 Technical Specifications

6. Sensible capacity table


Slim Duct Type ( MMD-AP***4SPH-E )
TC : Total capacity [kW] SHC : Sensible capacity [kW]
Indoor air temp.
Unit Outdoor 14.0CWB 16.0CWB 18.0CWB 19.0CWB 20.0CWB 22.0CWB 24.0CWB
size air temp. 20CDB 23CDB 26CDB 27CDB 28CDB 30CDB 32CDB
CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
12.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
14.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
16.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
18.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
20.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
21.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
007 23.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
25.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
27.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
29.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
31.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
33.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
35.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
37.0 1.7 1.5 1.9 1.6 2.1 1.7 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7
39.0 1.7 1.5 1.9 1.6 2.0 1.7 2.1 1.7 2.1 1.7 2.3 1.7 2.4 1.6
10.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
12.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
14.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
16.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
18.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
20.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
21.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
009 23.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
25.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
27.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
29.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
31.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
33.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
35.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0
37.0 2.2 1.8 2.5 1.9 2.6 2.0 2.7 2.0 2.8 2.0 3.0 2.0 3.1 2.0
39.0 2.2 1.8 2.4 1.9 2.6 2.0 2.6 2.0 2.7 2.0 2.9 2.0 3.0 1.9
10.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
12.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
14.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
16.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
18.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
20.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
21.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
012 23.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
25.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
27.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
29.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
31.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
33.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
35.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
37.0 2.9 2.1 3.2 2.3 3.4 2.4 3.5 2.4 3.6 2.4 3.8 2.4 4.0 2.3
39.0 2.8 2.1 3.1 2.2 3.3 2.4 3.4 2.4 3.5 2.4 3.7 2.3 3.9 2.3

11 -169
11 Technical Specifications

Slim Duct Type ( MMD-AP***4SPH-E )


TC : Total capacity [kW] SHC : Sensible capacity [kW]
Indoor air temp.
Unit Outdoor 14.0CWB 16.0CWB 18.0CWB 19.0CWB 20.0CWB 22.0CWB 24.0CWB
size air temp. 20CDB 23CDB 26CDB 27CDB 28CDB 30CDB 32CDB
CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
12.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
14.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
16.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
18.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
20.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
21.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
015 23.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
25.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
27.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
29.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
31.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
33.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
35.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
37.0 3.6 2.7 4.0 2.9 4.2 3.1 4.4 3.1 4.5 3.1 4.7 3.1 5.0 3.0
39.0 3.5 2.7 3.8 2.8 4.1 3.0 4.2 3.0 4.4 3.0 4.6 3.0 4.8 2.9
10.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
12.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
14.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
16.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
18.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
20.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
21.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
018 23.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
25.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
27.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
29.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
31.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
33.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
35.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
37.0 4.5 3.3 4.9 3.6 5.3 3.8 5.4 3.8 5.6 3.8 5.9 3.7 6.2 3.7
39.0 4.3 3.3 4.8 3.5 5.1 3.7 5.3 3.7 5.4 3.7 5.7 3.6 6.0 3.6

11 -170
11 Technical Specifications

7. Fan characteristics
MMD-AP0074SPH-E MMD-AP0124SPH-E
MMD-AP0094SPH-E

Standard air volume : 540m3/h Standard air volume : 600m3/h


60 60

High (50Pa)
High (50Pa)
Upper limit of external
50 static pressure(50Pa) 50 Upper limit of external
static pressure(50Pa)

Upper limit of
external static
pressure(35Pa) High (35Pa)
External static pressure (Pa)

External static pressure (Pa)


40 High (35Pa)
40

Low (50Pa)

Upper limit of Lower limit of external


Upper limit of Low (50Pa) Lower limit of external external static static pressure (50Pa)
30 static pressure (50Pa) 30
external static pressure(35Pa)
pressure(20Pa)
Low (35Pa) High (20Pa)
High (20Pa)

Upper limit of Upper limit of


20 Low (35Pa) 20
external static external static Lower limit of external
Lower limit of external
pressure(10Pa) pressure(20Pa) static pressure (35Pa)
static pressure (35Pa)

High (10Pa)
High (10Pa)
Low (20Pa)
10 Low (20Pa) 10

Upper limit of Lower limit of external


Lower limit of external external static static pressure (20Pa)
static pressure (20Pa) pressure(10Pa) Low (10Pa)
Low (10Pa)
0 0
300 400 500 600 700 300 400 500 600 700

Air Volume (m3/h) Air Volume (m3/h)

MMD-AP0154SPH-E MMD-AP0184SPH-E

Standard air volume : 690m3/h Standard air volume : 780m3/h


60 60

High (50Pa)
High (50Pa)
Upper limit of external
static pressure(50Pa) Upper limit of external
50 50
static pressure(50Pa)

Upper limit of High (35Pa)


external static High (35Pa)
External static pressure (Pa)

pressure(35Pa) 40
External static pressure (Pa)

40

Low (50Pa)
Lower limit of external Upper limit of Lower limit of
30 Low (50Pa) static pressure (50Pa) 30 external static
external static
pressure(35Pa) pressure (50Pa)

High (20Pa) Low (35Pa) High (20Pa)

20 Upper limit of
20 Low (35Pa) Lower limit of external external static
static pressure (35Pa) pressure(20Pa) Lower limit of
external static
Upper limit of High (10Pa) pressure (35Pa)
Upper limit of
external static
10 external static
pressure(20Pa) Low (20Pa)
10 Low (20Pa) pressure(10Pa)

Lower limit of external Lower limit of


Upper limit of static pressure (20Pa) external static
Low (10Pa)
external static High (10Pa) pressure (20Pa)
Low (10Pa)
pressure(10Pa) 0
0
400 500 600 700 800 900
400 500 600 700 800
Air Volume (m3/h)
Air Volume (m3/h)

11 -171
11 Technical Specifications

(Filter attached)
MMD-AP0074SPH-E MMD-AP0124SPH-E
MMD-AP0094SPH-E
Standard air volume : 540m3/h Standard air volume : 600m3/h
60 60

High (50Pa)
High (50Pa)
Upper limit of external
50 static pressure(50Pa) 50
Lower limit of external
Upper limit of external
static pressure (50Pa)
Lower limit of externa static pressure(50Pa)
static pressure (50Pa)
Low (50Pa)
40
External static pressure (Pa)

40

External static pressure (Pa)


Upper limit o
external static Lower limit of external
Upper limit of High (35Pa)
Low (50Pa) pressure(35Pa) static pressure (35Pa)
30 external static Lower limit of external 30
pressure(35Pa) static pressure (35Pa)
Low (35Pa)
Low (35Pa)

Upper limit o
20 20 external static High (20Pa)
Upper limit of High (20Pa) pressure(20Pa) Lower limit of external
external static Lower limit of extern static pressure (20Pa)
pressure(20Pa) static pressure (20Pa)
Low (20Pa)
Low (20Pa)
10 10 High (10Pa)
Upper limit of Upper limit o
High (10Pa)
external static external static
pressure(10Pa) pressure(10Pa)
Standard filter
Standard filter
Low (10Pa) pressure loss Low (10Pa)
0 pressure loss
0
300 400 500 600 700
300 400 500 600 700
Air Volume (m3/h) Air Volume (m3/h)

MMD-AP0154SPH-E MMD-AP0184SPH-E

Standard air volume : 690m3/h Standard air volume : 780m3/h


60 60

High (50Pa) Upper limit of external High (50Pa)


Upper limit of external static pressure(50Pa)
static pressure(50Pa)
50 50
Lower limit of
Upper limit of external Lower limit of external Upper limit of external external static
static pressure(35Pa) static pressure (50Pa) static pressure(35Pa) pressure (50Pa)
High (35Pa)
External static pressure (Pa)

40
External static pressure (Pa)

40

Low (50Pa)
Lower limit of external
Low (50Pa) static pressure (35Pa) High (35Pa) Lower limit of
30 30 external static
Upper limit of pressure (35Pa)
High (20Pa)
external static Low (35Pa)
pressure(20Pa)

20 Low (35Pa) 20 Upper limit of external


static pressure(20Pa) High (20Pa)
High (10Pa) Lower limit of externa Lower limit of
static pressure (20Pa) external static
Upper limit of Upper limit of
external static pressure (20Pa)
external static
pressure(10Pa) Low (20Pa) High (10Pa)
10 10 pressure(10Pa)
Low (20Pa)
Low (10Pa)
Standard filter Standard filter
pressure loss pressure loss
Low (10Pa)
0 0
400 500 600 700 800 400 500 600 700 800 900

Air Volume ( m3/h) Air Volume (m3/h)

11 -172
11 Technical Specifications

8. Sound Characteristics (NC Curve)


MMD-AP0074SPH-E 2m 1m

MMD-AP0094SPH-E
Duct Duct
Measuring location Air outlet Air inlet

Rear air intake Center


1.5m

Microphone

External static pressure 10Pa External static pressure 20Pa


Fan tap H M L Fan tap H M L
Sound pressure Sound pressure
level (dB(A)) 28 26 24 level (dB(A)) 29 27 25

70 70

60 60
Octave band sound pressure level (dB)
Octave band sound pressure level (dB)

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30
H
H
M
M 20
20
L NC-20
L NC-20
Approximate threshold of Approximate threshold of
hearing for continuous noise hearing for continuous noise

10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz) Octave band center frequency (Hz)

External static pressure 35Pa External static pressure 50Pa


Fan tap H M L Fan tap H M L
Sound pressure Sound pressure
level (dB(A)) 30 28 26 level (dB(A)) 32 29 27

70 70

60 60
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30 H
NC-30 NC-30
H M

M
20 20 L
L
NC-20 NC-20
Approximate threshold of Approximate threshold of
hearing for continuous noise hearing for continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

11 -173
11 Technical Specifications

2m 1m
MMD-AP0124SPH-E
Measuring location Duct Duct
Air outlet Air inlet

Rear air intake Center


1.5m

Microphone

External static pressure 10Pa External static pressure 20Pa


Fan tap H M L Fan tap H M L
Sound pressure Sound pressure
level (dB(A)) 29 27 25 level (dB(A)) 30 28 26

70 70

60 60
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 H 30 H
NC-30 NC-30
M
M
20 L L
20
NC-20 NC-20
Approximate threshold of Approximate threshold of
hearing for continuous noise hearing for continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

External static pressure 35Pa External static pressure 50Pa


Fan tap H M L Fan tap H M L
Sound pressure Sound pressure
level (dB(A)) 31 29 27 level (dB(A)) 32 30 28

70 70

60 60
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

50 50
NC-50 NC-50

40 NC-40 40 NC-40

H H
30 30
NC-30 M NC-30
M

L L
20 20
NC-20 NC-20
Approximate threshold of Approximate threshold of
hearing for continuous noise hearing for continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

11 -174
11 Technical Specifications

MMD-AP0154SPH-E 2m 1m

Measuring location
Duct Duct
Air outlet Air inlet
Rear air intake
Center
1.5m

Microphone

Ext ernal st at ic p ressure 10Pa Ext ernal st at ic p ressure 20Pa


Fan tap H M L Fan tap H M L
Sound pressure Sound pressure
level (dB(A)) 32 30 28 level (dB(A)) 33 31 29

70 70

60 60
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)


50 50
NC-50 NC-50

40
NC-40 40 NC-40

30
H NC-30 30
NC-30
H
M M
20 L L
20
NC-20 NC-20
Approximate threshold of
Approximate threshold of
hearing for continuous noise
hearing for continuous noise
10
10
63 125 250 500 1000 2000 4000 8000
63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)
Octave band center frequency (Hz)

External static pressure 35Pa External static pressure 50Pa


Fan tap H M L Fan tap H M L
Sound pressure Sound pressure
level (dB(A)) 34 32 30 level (dB(A)) 35 33 31

70 70

60 60
Octave band sound pressure level (dB)
Octave band sound pressur level (dB)

50 50
NC-50 NC-50

40 NC-40 40 NC-40

30 H H
NC-30 30
NC-30
M
M

L L
20
20
NC-20 NC-20
Approximate threshold of Approximate threshold of
hearing for continuous noise hearing for continuous noise
10
10
63 125 250 500 1000 2000 4000 8000
63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)
Octave band center frequency (Hz)

11 -175
11 Technical Specifications

MMD-AP0184SPH-E 2m 1m

Measuring location Duct Duct


Air outlet Air inlet

Rear air intake Center


1.5m

Microphone

External static pressure 10Pa External static pressure 20Pa


Fan tap H M L Fan tap H M L
Sound pressure Sound pressure
level (dB(A)) 33 31 29 level (dB(A)) 34 32 30

70 70

60 60

Octave band sound pressure level (dB)


Octave band sound pressure level (dB)

50 50
NC-50 NC-50

40 40
NC-40 NC-40

H
30 H 30
NC-30 M NC-30
M
L L
20 20
NC-20 NC-20
Approximate threshold of Approximate threshold of
hearing for continuous noise hearing for continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

External static pressure 35Pa External static pressure 50Pa


Fan tap H M L Fan tap H M L
Sound pressure Sound pressure
level (dB(A)) 35 33 31 level (dB(A)) 36 34 32

70 70

60 60
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

50 50
NC-50 NC-50

40 40
NC-40 NC-40

H H
30 30
NC-30 NC-30
M M
L L

20 20
NC-20 NC-20
Approximate threshold of Approximate threshold of
hearing for continuous noise hearing for continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center fequency (Hz) Octave band center frequency (Hz)

11 -176
11 Technical Specifications

2m
MMD-AP0074SPH-E
MMD-AP0094SPH-E
Duct
Air outlet
Measuring location
Center
1.5m
Under air intake Air inlet

Microphone

External static pressure 10Pa External static pressure 20Pa


Fan tap H M L Fan tap H M L
Sound pressure Sound pressure
level (dB(A)) 36 33 30 level (dB(A)) 37 34 31

70 70

60 60
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

50 50
NC-50 NC-50

40 40 NC-40
NC-40

H H
M
30 M 30
NC-30 NC-30
L
L
20 20
NC-20 NC-20
Approximate threshold of Approximate threshold of
hearing for continuous noise hearing for continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

External static pressure 35Pa External static pressure 50Pa


Fan tap H M L Fan tap H M L
Sound pressure Sound pressure
level (dB(A)) 39 36 33 level (dB(A)) 41 38 35

70 70

60 60
Octave band sound pressure level (dB)
Octave band soune pressure level (dB)

50 50
NC-50 NC-50

40
NC-40
40 H NC-40
H
M
M

L
30 30
L NC-30 NC-30

20 20
NC-20 NC-20
Approximate threshold of Approximate threshold of
hearing for continuous noise hearing for continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

11 -177
11 Technical Specifications

2m
MMD-AP0124SPH-E

Measuring location Duct


Air outlet

Center
Under air intake 1.5m Air inlet

Microphone

External static pressure 10Pa External static pressure 20Pa


Fan tap H M L Fan tap H M L
Sound pressure Sound pressure
38 35 32 level (dB(A)) 39 36 33
level (dB(A))
70
70

60
60
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)


50
NC-50 50
NC-50

40
NC-40 40
H NC-40
H
M
M
30
NC-30 30
L NC-30
L

20
20
NC-20
NC-20
Approximate threshold of
hearing for continuous noise Approximate threshold of
hearing for continuous noise
10
10
63 125 250 500 1000 2000 4000 8000
63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)
Octave band center frequency (Hz)

External static pressure 35Pa External static pressure 50Pa


Fan tap H M L Fan tap H M L
Sound pressure Sound pressure
41 38 35 level (dB(A)) 43 40 37
level (dB(A))
70 70

60 60
Octave band sound pressure frequency (dB)
Octave band sound pressure level (dB)

50 50
NC-50 NC-50

40 H H
NC-40 40 NC-40
M
M
L
30 L
NC-30 30
NC-30

20
20
NC-20 NC-20
Approximate threshold of
hearing for continuous noise Approximate threshold of
hearing for continuous noise
10
10
63 125 250 500 1000 2000 4000 8000
63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)
Octave band center frequency (Hz)

11 -178
11 Technical Specifications

MMD-AP0154SPH-E 2m

Measuring location Duct


Air outlet

Under air intake Center


1.5m Air inlet

Microphone

External static pressure 10Pa External static pressure 20Pa


Fan tap H M L Fan tap H M L
Sound pressure Sound pressure
level (dB(A)) 39 36 33 level (dB(A)) 40 37 34

70 70

60 60

Octave band sound frequency level (dB)


Octave band sound pressure level (dB)

50 50
NC-50 NC-50

40 40 NC-40
NC-40
H
H
M

30
M 30
NC-30 L NC-30
L

20 20
NC-20 NC-20
Approximate threshold of Approximate threshold of
hearing for continuous noise hearing for continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

External static pressure 35Pa External static pressure 50Pa


Fan tap H M L Fan tap H M L
Sound pressure Sound pressure
level (dB(A)) 41 38 35 level (dB(A)) 43 40 37

70 70

60 60
Octave band sound frequency level (dB)
Octave band sound pressure level (dB)

50 50
NC-50 NC-50

H H
40 40
NC-40 NC-40
M
M

L L
30 30
NC-30 NC-30

20 20
NC-20 NC-20
Approximate threshold of Approximate threshold of
hearing for continuous noise hearing for continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

11 -179
11 Technical Specifications

MMD-AP0184SPH-E 2m

Measuring location Duct


Air outlet

Under air intake Center


1.5m Air inlet

Microphone

External static pressure 10Pa External static pressure 20Pa


Fan tap H M L Fan tap H M L
Sound pressure Sound pressure
level (dB(A)) 40 38 36 level (dB(A)) 42 40 37

70 70

60 60

Octave band sound pressure level (dB)


Octave band sound pressure level (dB)

50 50
NC-50 NC-50

H
40 40 NC-40
H NC-40
M
M
L
30 30
L NC-30 NC-30

20 20
NC-20 NC-20

Approximate threshold of Approximate threshold of


hearing for continuous noise hearing for continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz) Octave band center frequency (Hz)

External static pressure 35Pa External static pressure 50Pa


Fan tap H M L Fan tap H M L
Sound pressure Sound pressure
level (dB(A)) 43 41 38 level (dB(A)) 44 42 39

70 70

60 60
Octave band sound pressure level (dB)
Octave band sound pressure level (dB)

50 50
NC-50 NC-50

H
H
40 40
NC-40 NC-40
M M
L L
30 30
NC-30 NC-30

20 20
NC-20 NC-20
Approximate threshold of Approximate threshold of
hearing for continuous noise hearing for continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz) Octave band center frequency (Hz)

11 -180
11 Technical Specifications

9. Fresh air intake (Design guide)


Slim Duct Type MMD-AP0074SPH-E, AP0094SPH-E, AP0124SPH-E

Caution
The fresh air shall be conditioned by heat reclaim ventilator or similar.
Ensure the fresh air volume is determined so that mixed suction air and fresh air maintain the
operating temperature .
*1.Recommended conditioned air temperature is 12 °C to 30 °C.
However, make a fresh air volume within 20% of standard.
Model name MMD- AP0074SPH-E AP0094SPH-E AP0124SPH-E
Standard air flow (m 3/h) 540 540 600

Install a air filter within the fresh air duct.


( Fresh air does not pass through the filter of Indoor unit.)
Insulate the fresh air duct.
Electrically connect the fan of the Heat exchanger unit and the Indoor unit to a single isolator.

30
Static Pressure (Pa)

20

10

-10
0 20 40 60 80 100 120 140

Fresh Air Volume (m3/h)

Indoor unit Duct fan


motor Fresh Air Volume

Flange Option :TCB-FF101URE

Inter - lock circuit


Connect the driving relay of the duct fan (DC 12V) between 1 and 6 on the indoor P.C. board.
(Rated current of the relay for duct fan should be up to 75mA.)
After installation, carry out a trial operation to check that the duct fan of the indoor unit start/stop
simultaneously.
(Carry out the trial operation following the installation manual of the indoor unit.)

11 -181
11 Technical Specifications

Slim Duct Type MMD-AP0154SPH-E, AP0184SPH-E

Caution
The fresh air shall be conditioned by heat reclaim ventilator or similar.
Ensure the fresh air volume is determined so that mixed suction air and fresh air maintain the
operating temperature .
*1.Recommended conditioned air temperature is 12 °C to 30 °C.
However, Make a fresh air volume within 20% of standard.

Model name MMD- AP0154SPH-E AP0184SPH-E


Standard air flow (m 3/h) 690 780

Install a air filter within the fresh air duct.


( Fresh air does not pass through the filter of Indoor unit.)
Insulate the fresh air duct.
Electrically connect the fan of the Heat exchanger unit and the Indoor unit to a single isolator.

60
50
Static Pressure (Pa)

AP0154
40
30
20 AP0184
10
0
-10
0 20 40 60 80 100 120 140 160 180
Fresh Air Volume (m3/h)

Indoor unit Duct fan


motor Fresh Air Volume

Flange Option :TCB-FF101URE

Inter - lock circuit


Connect the driving relay of the duct fan (DC 12V) between 1 and 6 on the indoor P.C. board.
(Rated current of the relay for duct fan should be up to 75mA.)
After installation, carry out a trial operation to check that the duct fan of the indoor unit start/stop
simultaneously.
(Carry out the trial operation following the installation manual of the indoor unit.)

11 -182
11 Technical Specifications

10. Accessories

Parts name Model name Applied model Note Remarks


Auxiliary fresh air flange TCB-FF101URE2 MMD-AP***4SPH-E For fresh air intake by using the knockout hole of indoor unit. (dia.=100 mm)

TCB-FF101URE2

11 -183
11 Technical Specifications

11 -184
11 Technical Specifications

11-2-8. Ceiling Type

Ceiling Type

MMC-AP0154H-E / MMC-AP0184H-E
MMC-AP0244H-E / MMC-AP0274H-E
MMC-AP0364H-E / MMC-AP0484H-E

Contents
1. Specifications
2. Dimension
3. Wiring diagram
4. Center of Gravity
5. Electrical characteristics
6. Sensible capacity table
7. Air throw distance chart
8. Sound characteristics (NC-Curve)
9. Accessories

11 -185
11 Technical Specifications

1. Specifications

Ceiling Type
Model name MMC- AP0154H-E AP0184H-E AP0244H-E AP0274H-E AP0364H-E AP0484H-E

Cooling/Heating capacity (Note 1) (kW) 4.5/5.0 5.6/6.3 7.1/8.0 8.0/9.0 11.2/12.5 14.0/16.0

Power supply 1 phase 50Hz 230V (220 - 240V) (Separate power supply for indoor units is required.)

Running current (A) 0.29 0.32 0.42 0.78 0.84


Electrical
characteris-
tics Power consumption (kW) 0.033 0.038 0.050 0.091 0.110

Starting current (A) 0.43 0.48 0.62 1.17 1.25

Appearance White (Munsell 10Y 9.3/0.4)

Outer
dimension Height x Width x Depth (mm) 210 x 910 x 680 210 x 1,180 x 680 210 x 1,595 x 680

Total weight (kg) 22 26 34

Heat exchanger Finned tube

Soundproof/Heating-insulating material Non-flammable insulation

Fan Centrifugal fan

Standard air flow


Fan unit (High/Mid./Low) (m3/h) 720/600/540 780/660/540 1,110/900/840 1,650/1,380/1,2001,800/1,560/1,320

Motor output (W) 30 40 80

Controller Remote controller

Room thermostat Attached

Air filter Standard filter (Long life filter)

Gas side (mm) / 12.7


O / 15.9
O

Connecting
Liquid side (mm) / 6.4
O / 9.5
O
pipe

Drain port (Nominal dia. mm) 20 (Polyvinyl chloride tube)

Sound pressure level(Note 2)


(High/Mid./Low) (dB(A)) 35/32/30 36/33/30 38/36/33 41/38/35 43/40/37

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on the
reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.
Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27 C DB/19 C WB, Outdoor air temperature 35 C DB
O O O

Heating : Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB/6 C WB


O O O

11 -186
11 Technical Specifications

2. Dimension

MMC-AP0154H-E, AP0184H-E, AP0244H-E, AP0274H-E, AP0364H-E, AP0484H-E

Upper piping exhaust port * Z Piping exhaust port *


Power supply cable intake port *
128 216 210 Drain pipe connecting port
Remote controller
piping intake port * 167
84 110 76

50
105

114
170

130
53

70

141
680
(Hanging
position)
320

* : Knockout hole
Left drain size

200 (Liquid pipe)


216 (Gas pipe)
Drain pipe connecting port

A (Hanging position) 75 97
Refrigerant pipe connecting port (Gas side)
146 Remote controller cable intake port *
Refrigerant pipe connecting port (Liquid side) 347
262
Power supply intake port * Remote controller cable intake port *
135

32
84
90

32
92
145

171
B

Piping hole on the wall


(φ100 hole) Drain left piping exhaust port *
Air intake port φ92 *

Wireless sensor mounting section Z view

Space required for installation and servicing


Hanging bolt

Ceiling surface
Within 50

Model MMC- A B
500 or

Unit
more
AP0154H-E, AP0184H-E 855 910
250 or more 250 or more
AP0244H-E, AP0274H-E 1125 1180
(Front side to be positioned horizontally)
AP0364H-E, AP0484H-E 1540 1595

(Unit: mm)

11 -187
11 Technical Specifications

3. Wiring diagram
MMC-AP0154H-E, AP0184H-E, AP0244H-E, AP0274H-E, AP0364H-E, AP0484H-E

11 -188
11 Technical Specifications

4. Center of gravity

Model name X (mm) Y (mm) Z (mm) Total weight(kg)


MMC-AP0154H-E
320 460 90 22
MMC-AP0184H-E
MMC-AP0244H-E
320 570 90 26
MMC-AP0274H-E

MMC-AP0364H-E
320 770 90 34
MMC-AP0484H-E

X X

5. Electrical characteristics

Nominal Voltage Voltage Range Fan Motor Power Supply


Ty p e Mo d el
(V-Ph-Hz) Min Max kW FLA MCA MOCP
MMC-AP0154H-E 230-1-50 198 264 0.030 0.33 0.41 15
MMC-AP0184H-E 230-1-50 198 264 0.030 0.37 0.46 15
MMC-AP0244H-E 230-1-50 198 264 0.040 0.48 0.60 15
Ceiling Type
MMC-AP0274H-E 230-1-50 198 264 0.040 0.48 0.60 15
MMC-AP0364H-E 230-1-50 198 264 0.080 0.90 1.13 15
MMC-AP0484H-E 230-1-50 198 264 0.080 0.96 1.20 15

MCA : Minimum Circuit Amps FLA : Full Load Amps


MOCP : Maximum Overcurrent Protection (Amps)

11 -189
11 Technical Specifications

6. Sensible capacity table


Ceiling Type (MMC-AP***4H-E) TC : Total capacity [kW] SHC : Sensible capacity [kW]
indoor air temp.
o o o o o o o
unit outdoor 14.0 CWB 16.0 CWB 18.0 CWB 19.0 CWB 20.0 CWB 22.0 CWB 24.0 CWB
size air temp. o
20 CDB
o
23 CDB
o
26 CDB
o
27 CDB
o
28 CDB
o
30 CDB
o
32 CDB
o
CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
12.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
14.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
16.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
18.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
20.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
21.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
015 23.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
25.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
27.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
29.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
31.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
33.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
35.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1
37.0 3.6 2.7 4.0 2.9 4.2 3.1 4.4 3.1 4.5 3.1 4.7 3.1 5.0 3.0
39.0 3.5 2.7 3.8 2.8 4.1 3.0 4.2 3.0 4.4 3.0 4.6 3.0 4.8 2.9
10.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
12.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
14.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
16.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
18.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
20.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
21.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
018 23.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
25.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
27.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
29.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
31.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
33.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
35.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8
37.0 4.5 3.3 4.9 3.6 5.3 3.8 5.4 3.8 5.6 3.8 5.9 3.7 6.2 3.7
39.0 4.3 3.3 4.8 3.5 5.1 3.7 5.3 3.7 5.4 3.7 5.7 3.6 6.0 3.6
10.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.9
12.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.9
14.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.9
16.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.9
18.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.9
20.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.9
21.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.9
024 23.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.9
25.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.9
27.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.9
29.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.9
31.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.9
33.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.9
35.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.9
37.0 5.6 4.4 6.2 4.7 6.7 5.0 6.9 4.9 7.1 4.9 7.5 4.9 7.8 4.8
39.0 5.5 4.3 6.1 4.5 6.5 4.8 6.7 4.8 6.9 4.8 7.3 4.8 7.6 4.6
10.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
12.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
14.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
16.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
18.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
20.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
21.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
027 23.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
25.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
27.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
29.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
31.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
33.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
35.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4
37.0 6.4 4.8 7.0 5.1 7.5 5.4 7.7 5.4 8.0 5.4 8.4 5.4 8.8 5.2
39.0 6.2 4.7 6.8 5.0 7.3 5.3 7.5 5.3 7.8 5.3 8.2 5.2 8.6 5.1

11 -190
11 Technical Specifications

Ceiling Type (MMC-AP***4H-E) TC : Total capacity [kW] SHC : Sensible capacity [kW]
indoor air temp.
o o o o o o o
unit outdoor 14.0 CWB 16.0 CWB 18.0 CWB 19.0 CWB 20.0 CWB 22.0 CWB 24.0 CWB
size air temp. o
20 CDB
o
23 CDB
o
26 CDB
o
27 CDB
o
28 CDB
o
30 CDB
o
32 CDB
o
CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.4
12.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.4
14.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.4
16.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.4
18.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.4
20.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.4
21.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.4
036 23.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.4
25.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.4
27.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.4
29.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.4
31.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.4
33.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.4
35.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.4
37.0 8.9 6.5 9.8 6.9 10.5 7.4 10.8 7.4 11.2 7.4 11.8 7.3 12.4 7.1
39.0 8.7 6.3 9.6 6.8 10.2 7.2 10.5 7.2 10.9 7.2 11.5 7.1 12.0 6.9
10.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
12.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
14.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
16.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
18.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
20.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
21.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
048 23.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
25.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
27.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
29.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
31.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
33.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
35.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5
37.0 11.1 8.4 12.3 9.0 13.1 9.5 13.6 9.5 14.0 9.5 14.8 9.4 15.4 9.2
39.0 10.8 8.2 12.0 8.7 12.8 9.2 13.2 9.2 13.6 9.2 14.4 9.1 15.0 8.9

11 -191
11 Technical Specifications

7. Air throw distance chart

MMC-AP0184H-E, AP0484H-E MMC-AP0364H-E

1m 1m

2m 2m
1.0 0.3
1.0
0.3
3m 3m 0.5
0.3 0.5 0.5 0.3

1m 2m 3m 4m 1m 2m 3m 4m

MMC-AP0154H-E, AP0244H-E,AP0274H-E

1m

2m
1.0 0.3

3m
0.3 0.5
unit : [m/s]
1m 2m 3m 4m

11 -192
11 Technical Specifications

8. Sound level data (NC CURVE) Sound level values shown are based on a measurement in a non resound room.

MMC-AP0154H-E
Fan Tap H M L
Sound pressure
35 32 30
level(dB(A))

90
H

Octave band sound pressure level (dB)


M
80 L

70
NC-70

60
NC-60
50
NC-50

40
NC-40

Microphone 30
NC-30
20
Audibility limits of NC-20
continous white sound
10
63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

MMC-AP0184H-E MMC-AP0244H-E,AP0274H-E
Fan Tap H M L Fan Tap H M L
Sound pressure Sound pressure
36 33 30 38 36 33
level(dB(A)) level(dB(A))

90 90
H H
Octave band sound pressure level (dB)

M M
Octave band sound pressure level (dB)

80 L
80 L

70 70
NC-70 NC-70

60 60
NC-60 NC-60
50 50
NC-50 NC-50

40 40
NC-40 NC-40
30 30
NC-30 NC-30
20 20
Audibility limits of NC-20 Audibility limits of NC-20
continous white sound continous white sound
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz) Octave band center frequency (Hz)

MMC-AP0364H-E MMC-AP0484H-E
Fan Tap H M L Fan Tap H M L
Sound pressure Sound pressure
41 38 35 43 40 37
level(dB(A)) level(dB(A))

90 90
H H
M M
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

80 L
80 L

70 70
NC-70 NC-70

60 60
NC-60 NC-60
50 50
NC-50 NC-50

40 40
NC-40 NC-40
30 30
NC-30 NC-30
20 20
Audibility limits of NC-20 Audibility limits of NC-20
continous white sound continous white sound
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz) Octave band center frequency (Hz)

11 -193
11 Technical Specifications

9. Accessories

Parts name Model name Applied model Note Remarks


MMC-AP0154/0184H-E Stand-up 600 or less Use with TCB-KP12CE2
Drain pump kit TCB-DP22CE2
MMC-AP0244 to 0484H-E (from bottom face of ceiling) Use with TCB-KP22CE2
TCB-KP12CE2 MMC-AP0154/0184H-E
Elbow piping kit Needed when drain pump kit is used
TCB-KP22CE2 MMC-AP0244 to 0484H-E

Elbow piping kit


TCB-KP12CE2
TCB-KP22CE2

Drain pump kit


TCB-DP22CE2

11 -194
11 Technical Specifications
11 Technical Specifications

11-2-9.High-wall Type(3 series)

High-wall Type (3 series)

Model name:

MMK-AP0073H
MMK-AP0093H
MMK-AP0123H
MMK-AP0153H
MMK-AP0183H
MMK-AP0243H

Contents
1 Specifications
2 Dimensions
3 Wiring diagram
4 Center of Gravity
5 Electrical characteristics
6 Sensible capacity table
7 Fan characteristics
8 Sound characteristics (NC Curve)
9 Accessories

11 -195
11 Technical Specifications

1 Specifications
Model name MMK- AP0073H AP0093H AP0123H AP0153H AP0183H AP0243H

Cooling / Heating capacity (Note 1) (kW) 2.2 / 2.5 2.8 / 3.2 3.6 / 4.0 4.5 / 5.0 5.6 / 6.3 7.1 / 8.0

Power Supply 1 phase 50Hz 230V (220-240V)(Separate power supply for indoor units is required.)

Running current (A) 0.17 0.19 0.19 0.32 0.32 0.37


Electrical
Characteristics
Power consumption (kW) 0.018 0.021 0.021 0.043 0.043 0.050

Starting current (A) 0.22 0.24 0.24 0.41 0.41 0.47

Suction grille and side panel Moon white(Munsell 2.5GY9.0/0.5)

Appearance Discharge-grille Moon white(Munsell 2.5GY9.0/0.5)

Bottom surface Moon white(Munsell 2.5GY9.0/0.5)

Outer
Height x Width x Depth ( mm) 320 x 1050 x 228
dimension

Total weight (kg) 15

Heat exchanger Finned tube

Soundproof/Heat-insulating material No n -f la mm a b l e i n s u l a t i o n

Fan Cross-flow fan

Standard air flow


Fan unit (m3/h) 570 / 450 /390 600 / 480 / 390 600 / 480 / 390 840 / 660 /540 840 / 660 /540 1020 / 750 / 570
(High/Mid/Low)

Motor outlet (W) 30

Air filter Standard filter attached

Controller Wireless remote controller (packed with indoor unit)

Gas side (mm) Ø9.5 Ø12.7 Ø15.9

Connecting
Liquid side (mm) Ø6.4 Ø9.5
pipe

Drain port (Nominal dia.) 16 (polypropylene tube)

Sound pressure level (Note 2)


(dB(A)) 35-31-28 37-32-28 37-32-28 41-36-33 41-36-33 46-39-34
(High / Mid / Low)
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on the reference piping.
The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616.
Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB

11 -196
11 Technical Specifications

2 Dimensions
Model : MMK-AP0073H, AP0093H, AP0123H, AP0153H , AP0183H, AP0243H
1050

Front panel Air filter Air inlet 228


320
73.5

73.5
7

7
50 Heat exchanger 50

Knock out system Knock out system

50

204
72 78
Installation plate hanger
56 24
132 568 200 150
Wireless remote controller

163

82 26

Remote controller holder


Installation plate hanger
Gas Liquid
Connecting pipe (0.39m) Drain hose Connecting pipe (0.44m)
(07, 09, 12 series; 9.5mm (0.5m) (07, 09, 12 series; 6.4mm
15, 18 series; 12.7mm 15, 18 series; 6.4mm
24 series; 15.9mm) 24 series; 9.5mm)

132 786 132


235 235
215 215
Space required for installation and
Hanger servicing
85 23
320
40

40

Hanger Hanger
47 215.5 262.5 262.5 153.5 109 Distance Comments
A 110 or more
Center line Installation plate outline B 850 or more For exchange of cross flow fan
Installation plate C 170 or more

11 -197
11 Technical Specifications

3 Wiring diagram
Models: MMK-AP0073H, AP0093H, AP0123H, AP0153H, AP0183H, AP0243H

11 -198
11 Technical Specifications

4 Center of gravity
Model : MMK-AP0073H, AP0093H, AP0123H, AP0153H, AP0183H, AP0243H

Distance to center of gravity (mm)


X 445
Y 105
Z 170

5 Electrical characteristics
Nominal Voltage Voltage Range Fan Motor Power Supply
Type Model
(V-Ph-Hz) Min Max kW FLA MCA MOCP
MMK-AP0073H 230-1-50 198 264 0.030 0.20 0.22 15
MMK-AP0093H 230-1-50 198 264 0.030 0.22 0.24 15
MMK-AP0123H 230-1-50 198 264 0.030 0.22 0.24 15
50Hz High Wall Type
MMK-AP0153H 230-1-50 198 264 0.030 0.37 0.40 15
MMK-AP0183H 230-1-50 198 264 0.030 0.37 0.40 15
MMK-AP0243H 230-1-50 198 264 0.030 0.43 0.47 15

MCA : Minimum Circuit Amps FLA : Full load Amps


MOCP : Maximum Overcurrent Protection(Amps)

11 -199
11 Technical Specifications

6 Sensible capacity table


High-wall Type ( MMK-AP***3H )
indoor air temp.
outdoor
unit 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
air temp.
size 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
12.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
14.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
16.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
18.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
20.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
21.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
007 23.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
25.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
27.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
29.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
31.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
33.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
35.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
37.0 1.7 1.5 1.9 1.6 2.1 1.7 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.6
39.0 1.7 1.4 1.9 1.5 2.0 1.6 2.1 1.6 2.1 1.6 2.3 1.6 2.4 1.5
10.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
12.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
14.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
16.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
18.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
20.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
21.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
009 23.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
25.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
27.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
29.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
31.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
33.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
35.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
37.0 2.2 1.7 2.5 1.8 2.6 1.9 2.7 1.9 2.8 1.9 3.0 1.9 3.1 1.9
39.0 2.2 1.7 2.4 1.8 2.6 1.9 2.6 1.9 2.7 1.9 2.9 1.9 3.0 1.8
10.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
12.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
14.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
16.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
18.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
20.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
21.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
012 23.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
25.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
27.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
29.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
31.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
33.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
35.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
37.0 2.9 2.1 3.2 2.3 3.4 2.4 3.5 2.4 3.6 2.4 3.8 2.4 4.0 2.3
39.0 2.8 2.1 3.1 2.2 3.3 2.4 3.4 2.4 3.5 2.4 3.7 2.3 3.9 2.3

11 -200
11 Technical Specifications

High-wall Type ( MMK-AP***3H )


indoor air temp.
outdoor
unit 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
air temp.
size 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
12.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
14.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
16.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
18.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
20.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
21.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
015 23.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
25.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
27.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
29.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
31.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
33.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
35.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
37.0 3.6 2.5 4.0 2.7 4.2 2.8 4.4 2.8 4.5 2.8 4.7 2.8 5.0 2.7
39.0 3.5 2.4 3.8 2.6 4.1 2.7 4.2 2.7 4.4 2.7 4.6 2.7 4.8 2.6
10.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
12.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
14.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
16.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
18.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
20.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
21.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
018 23.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
25.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
27.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
29.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
31.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
33.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
35.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5
37.0 4.5 3.1 4.9 3.3 5.3 3.5 5.4 3.5 5.6 3.5 5.9 3.5 6.2 3.4
39.0 4.3 3.0 4.8 3.2 5.1 3.4 5.3 3.4 5.4 3.4 5.7 3.4 6.0 3.3
10.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.5
12.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.5
14.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.5
16.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.5
18.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.5
20.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.5
21.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.5
024 23.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.5
25.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.5
27.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.5
29.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.5
31.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.5
33.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.5
35.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.5
37.0 5.6 4.0 6.2 4.3 6.7 4.6 6.9 4.5 7.1 4.5 7.5 4.5 7.8 4.4
39.0 5.5 3.9 6.1 4.2 6.5 4.4 6.7 4.4 6.9 4.4 7.3 4.4 7.6 4.3

11 -201
11 Technical Specifications

7 Fan characteristics
Discharge Air Speed and Air Throw
High Wall Type (3 series)

Model : MMK-AP0073H Model : MMK-AP0093H, AP0123H


Horizontal discharge initial speed High wind : 3.8m/s Horizontal discharge initial speed High wind : 4.0m/s
Med wind : 2.9m/s Med wind : 3.2m/s
Low wind : 2.5m/s Low wind : 2.5m/s

5 5
Air speed (m/s)

Air speed (m/s)


4 High 4 High
3 3
Med Med
2 2
Low Low
1 1
0 0
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
Horizontal throw (m) Horizontal throw (m)

Model : MMK-AP0153H, AP0183H Model : MMK-AP0243H


Horizontal discharge initial speed High wind : 5.1m/s Horizontal discharge initial speed High wind : 6.2m/s
Med wind : 4.2m/s Med wind : 4.7m/s
Low wind : 3.2m/s Low wind : 3.7m/s

6 6
5 5
Air speed (m/s)

Air speed (m/s)

High High
4 4
3 Med 3 Med
2 Low 2 Low
1 1
0 0
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
Horizontal throw (m) Horizontal throw (m)

11 -202
11 Technical Specifications

8 Sound characteristics (NC Curve)


High Wall Type (3 series)

1m

1m

Microphone

MMK-AP0073H MMK-AP0093H/AP0123H
Sound pressure HH - H - L Sound pressure HH - H - L
level (dB(A)) 35 - 31 - 28 level (dB(A)) 37 - 32 - 28
90 90
HH HH
H H
80 80
L L

70 NC-70 70 NC-70
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 20
Approximate threshold of Approximate threshold of
hearing for continuous noise NC-20 hearing for continuous noise NC-20

10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

MMK-AP0153H/AP0183H MMK-AP0243H
Sound pressure HH - H - L Sound pressure HH - H - L
level (dB(A)) 41 - 36 - 33 level (dB(A)) 46 - 39 - 34
90 90
HH HH
H H
80 80
L L

70 NC-70 70 NC-70
Octave band sound pressure level (dB)
Octave band sound pressure level (dB)

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 20
Approximate threshold of Approximate threshold of
hearing for continuous noise NC-20 hearing for continuous noise NC-20

10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

11 -203
11 Technical Specifications

9 Accessories
Remote controller

Packed with the indoor unit


Model
Name A ppea r a nc e A p p l i c a ti o n F u n c ti o n
name
• Start / Stop
• Changing mode
• Temperature setting
Wireless remote controller

• Air flow changing (5 steps)


• Louver setting
• Clock
WH-L11SE

• Timer function
- ON/OFF timer (10 min. step)
- Everyday timer
- Sleep timer
- COMFORT SLEEP timer
• High power mode
• QUIET mode
• One-touch pre-set memory

11 -204
11 Technical Specifications

11-2-10. Floor Standing Concealed Type

Floor Standing
Concealed Type

MML-AP0074BH-E / MML-AP0094BH-E
MML-AP0124BH-E / MML-AP0154BH-E
MML-AP0184BH-E / MML-AP0244BH-E

Contents
1. Specifications
2. Dimension
3. Wiring diagram
4. Center of Gravity
5. Electrical characteristics
6. Sensible capacity table
7. Sound characteristics (NC-Curve)

11 -205
11 Technical Specifications

1. Specifications
Floor Standing Concealed Type
M od el name M M L- AP0074BH-E AP0094BH-E AP0124BH-E AP0154BH-E AP0184BH-E AP0244BH-E

Cooling/Heating capacity (Note 1) (kW) 2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3 7.1/8.0

Power supply 1 phase 50Hz 230V (220 - 240V) (Separate power supply for indoor units is required.)

Running current (A) 0.25 0.45 0.46

Electrical Power consumption (kW) 0.056 0.090 0.095


characteristics

Power factor (%) 97 87 90

Starting current (A) 0.60 0.80 1.00

Appearance Zinc hot dipping steel plate

Outer Height x Width x (mm) 600 x 745 x 220 600 x 1,045 x 220
dimension Depth

Total weight (kg) 21 29

Heat exchanger Finned tube

Soundproof/Heat-insulating material Non-flammable insulation

Fan Centrifugal fan

Standard air flow (m3/h) 460/ 400/ 300 740/ 600/ 490 950/ 790/ 640
(High/Mid./Low)
Fan unit

Motor output (W) 19 70

Static pressure range (kPa) 0

Air filter Standard filter (Simple filter)

Controller Remote controller

Gas side (mm) / 9.5


O / 12.7
O / 15.9
O

Connecting Liquid side (mm) / 6.4


O / 9.5
O
pipe

Drain port (Nominal dia. mm) 20 (One side of male screw)

Sound pressure level(Note 2)(High/Mid./Low)(dB(A)) 36/34/32 42/37/33

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on the
reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.
Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27 C DB/19 C WB, Outdoor air temperature 35 C DB
O O O

Heating : Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB/6 C WB


O O O

11 -206
11 Technical Specifications

2. Dimension
MML-AP0074BH-E, AP094BH-E, AP0124BH-E, AP0154BH-E, AP0184BH-E, AP0244BH-E

Hole for floor mounting (Air discharge port size in flange)


B
5

50
Ceiling board section
145

145
25
85 C 100
(Air discharge port size in flange)
A 10 2−φ4.7 hole (left/right side each) 123
65
20
10

D ×100

10
Expansion valve box
170
135
E −φ4.7 hole Refrigerant
(front side and rear side) pipe connecting port
(Liquid side)
402
600

Refrigerant Drain pipe

315
4−φ15 hole pipe connecting port connecting port

436
397
Electric parts box (earth terminal (for mounting rear side) (Gas side)
2−12×18 long hole

274
is provided in inner side)

224
(Hole for floor
mounting)

104
140
129
80

Air filter
B 110
85 55 155
220

Model MML- A B C D E
Space required for installation
AP0074BH-E to AP0124BH-E 610 580 550 4 5
and servicing
AP0154BH-E to AP0244BH-E 910 880 850 7 8

150 or more 150 or more


(Unit: mm)

11 -207
11 Technical Specifications

3. Wiring diagram
MML-AP0074BH-E, AP0094BH-E, AP0124BH-E, AP0154BH-E, AP0184BH-E, AP0244BH-E

11 -208
11 Technical Specifications

4. Center of gravity

Model name X (mm) Total weight(kg)


MML-AP0074BH-E
MML-AP0094BH-E 340 21
MML-AP0124BH-E

MML-AP0154BH-E

MML-AP0184BH-E 470 29
MML-AP0244BH-E

325 back side

x 100

5. Electrical characteristics

Nominal Voltage Voltage Range Fan Motor Power Supply


Ty p e Mo d el
(V-Ph-Hz) Min Max kW FLA MCA MOCP

MML-AP 0074 BH-E 230-1-50 198 264 0.019 0.29 0.36 15

MML-AP 0094 BH-E 230-1-50 198 264 0.019 0.29 0.36 15

Floor Standing MML-AP 0124 BH-E 230-1-50 198 264 0.019 0.29 0.36 15
Concealed Type MML-AP 0154 BH-E 230-1-50 198 264 0.070 0.52 0.65 15
MML-AP 0184 BH-E 230-1-50 198 264 0.070 0.52 0.65 15
MML-AP 0244 BH-E 230-1-50 198 264 0.070 0.53 0.66 15

MCA : Minimum Circuit Amps FLA : Full Load Amps


MOCP : Maximum Overcurrent Protection (Amps)

11 -209
11 Technical Specifications

6. Sensible capacity table


Floor Standing Concealed Type ( MML-AP***4BH-E ) TC : Total capacity [kW] SHC : Sensible capacity [kW]
indoor air temp.
o o o o o o o
unit outdoor 14.0 C WB 16.0 C WB 18.0 C WB 19.0 C WB 20.0 C WB 22.0 C WB 24.0 C WB
size air temp. o
20 C DB
o
23 C DB
o
26 C DB
o
27 C DB
o
28 C DB
o
30 C DB
o
32 C DB
o
C DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
12.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
14.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
16.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
18.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
20.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
21.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
007 23.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
25.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
27.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
29.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
31.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
33.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
35.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
37.0 1.7 1.2 1.9 1.3 2.1 1.4 2.1 1.4 2.2 1.4 2.3 1.3 2.4 1.3
39.0 1.7 1.2 1.9 1.2 2.0 1.3 2.1 1.3 2.1 1.3 2.3 1.3 2.4 1.3
10.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
12.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
14.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
16.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
18.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
20.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
21.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
009 23.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
25.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
27.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
29.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
31.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
33.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
35.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
37.0 2.2 1.4 2.5 1.5 2.6 1.6 2.7 1.5 2.8 1.5 3.0 1.5 3.1 1.5
39.0 2.2 1.3 2.4 1.4 2.6 1.5 2.6 1.5 2.7 1.5 2.9 1.5 3.0 1.5
10.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
12.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
14.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
16.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
18.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
20.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
21.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
012 23.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
25.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
27.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
29.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
31.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
33.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
35.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
37.0 2.9 1.9 3.2 2.0 3.4 2.1 3.5 2.1 3.6 2.1 3.8 2.1 4.0 2.1
39.0 2.8 1.8 3.1 2.0 3.3 2.1 3.4 2.1 3.5 2.1 3.7 2.1 3.9 2.0
10.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.7
12.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.7
14.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.7
16.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.7
18.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.7
20.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.7
21.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.7
015 23.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.7
25.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.7
27.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.7
29.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.7
31.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.7
33.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.7
35.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.7
37.0 3.6 2.4 4.0 2.6 4.2 2.7 4.4 2.7 4.5 2.7 4.7 2.7 5.0 2.6
39.0 3.5 2.3 3.8 2.5 4.1 2.7 4.2 2.6 4.4 2.6 4.6 2.6 4.8 2.6

11 -210
11 Technical Specifications

Floor Standing Concealed Type ( MML-AP***4BH-E ) TC : Total capacity [kW] SHC : Sensible capacity [kW]
indoor air temp.
o o o o o o o
unit outdoor 14.0 CWB 16.0 CWB 18.0 CWB 19.0 CWB 20.0 CWB 22.0 CWB 24.0 CWB
o o o o o o o
size air temp. 20 CDB 23 CDB 26 CDB 27 CDB 28 CDB 30 CDB 32 CDB
o
C DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
12.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
14.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
16.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
18.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
20.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
21.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
018 23.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
25.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
27.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
29.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
31.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
33.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
35.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
37.0 4.5 3.0 4.9 3.2 5.3 3.4 5.4 3.4 5.6 3.4 5.9 3.4 6.2 3.3
39.0 4.3 2.9 4.8 3.1 5.1 3.3 5.3 3.3 5.4 3.3 5.7 3.3 6.0 3.2
10.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
12.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
14.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
16.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
18.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
20.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
21.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
024 23.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
25.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
27.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
29.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
31.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
33.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
35.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
37.0 5.6 3.9 6.2 4.1 6.7 4.4 6.9 4.4 7.1 4.4 7.5 4.3 7.8 4.2
39.0 5.5 3.8 6.1 4.0 6.5 4.2 6.7 4.2 6.9 4.2 7.3 4.2 7.6 4.1

11 -211
11 Technical Specifications

7. Sound level data (NC CURVE) Sound level values shown are based on a measurement in a non resound room.

Microphone

MML-AP0074BH-E, AP0094BH-E, AP124BH-E MML-AP0154BH-E, AP0184BH-E


50Hz 50Hz
Fan Tap H M L Fan Tap H M L

Overall level A 36 34 32 Overall level A 36 34 32


(dB) C 42 40 38 (dB) C 41 40 39
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

(standard sound pressure 0.0002 μbar) (standard sound pressure 0.0002 μbar)
60 NC-60 60 60 NC-60 60

50 50 50 50
NC-50 NC-50

40 40 40 40
NC-40 NC-40
H
H
M
30 L 30 30 M 30
NC-30 NC-30
L

20 20 20 20
NC-20 NC-20
Audibility limits Audibility limits
of continous white level of continous white level
10 10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz) Octave band center frequency (Hz)

MML-AP0244BH-E
50Hz
Fan Tap H M L

Overall level A 42 37 33
(dB) C 46 41 38
Octave band sound pressure level (dB)

(standard sound pressure 0.0002 μbar)


60 NC-60 60

50 50
NC-50

H
40 40
NC-40
M
L
30 30
NC-30

20 20
NC-20
Audibility limits
of continous white level
10 10
63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

11 -212
11 Technical Specifications

11-2-11. Floor Standing Cabinet Type

Floor Standing
Cabinet Type

MML-AP0074H-E / MML-AP0094H-E
MML-AP0124H-E / MML-AP0154H-E
MML-AP0184H-E / MML-AP0244H-E

Contents
1. Specifications
2. Dimension
3. Wiring diagram
4. Center of Gravity
5. Electrical characteristics
6. Sensible capacity table
7. Air throw distance chart
8. Sound characteristics (NC-Curve)

11 -213
11 Technical Specifications

1. Specifications

Floor Standing Cabinet Type


M od el name M M L- AP0074H-E AP0094H-E AP0124H-E AP0154H-E AP0184H-E AP0244H-E

Cooling/Heating capacity (Note 1) (kW) 2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3 7.1/8.0

Power supply 1 phase 50Hz 230V (220 - 240V) (Separate power supply for indoor units is required.)

Running current (A) 0.26 0.43 0.47

Electrical
characteristics Power consumption (kW) 0.056 0.092 0.102

Power factor (%) 94 93 94

Starting current (A) 0.60 0.80 1.10

Appearance Silky shade (1Y8.5/0.5)

Outer
Height x Width x Depth (mm) 630 x 950 x 230
dimension

Total weight (kg) 37 40

Heat exchanger Finned tube

Soundproof/Heat-insulating material Non-flammable insulation

Fan Centrifugal fan

Standard air flow


Fan unit (High/Mid./Low) (m3/h) 480/420/360 900/780/650 1,080/930/780

Motor outlet (W) 45 70

Air filter Standard filter (Simple filter)

Controller Remote controller

Gas side (mm) / 9.5


O / 12.7
O / 15.9
O

Connecting
Liquid side (mm) / 6.4
O / 9.5
O
pipe

Drain port (Nominal dia. mm) 20 (Polyvinyl chloride tube)

Sound pressure level(Note 2)


(High/Mid./Low) (dB(A)) 39/ 37/ 35 45/ 41/ 38 49/ 44/ 39

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on the
reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.
Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27 C DB/19 C WB, Outdoor air temperature 35 C DB
O O O

Heating : Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB/6 C WB


O O O

11 -214
11 Technical Specifications

2. Dimensions
MML-AP0074H-E, AP0094H-E, AP0124H-E, AP0154H-E, AP0184H-E, AP0244H-E

Lower refrigerant piping port


Hole for floor (knockout hole 50x100)
mounting (2-φ10)
400 120
130
150

Hole for wall mounting


Air outlet 230
(knockout hole)

133
Power supply cord hole
(φ26 knockout hole)
630

430
Long hole for
wall mounting
35
50
70

97

Air inlet

57
950 30 120
Earth screw (M6) Refrigerant pipe port
130
Refrigerant pipe port (both sides) (knockout hole 50x100) (Knockout hole φ130)
(100 left side)

95 Refrigerant pipe
Space required for installation
(Gas)

connecting port
28 and servicing
35

(Liquid side)
Wall
(Liquid)
162

300 or
more

Refrigerant pipe
106

500 or
1000 or more

connecting port (Front side)


(Gas side) more
130 (Drain) Wall
5 138
Drain pipe connecting port 177 (Front side)
(Liquid) (Gas)

Piping positional drawing


(Unit: mm)

11 -215
11 Technical Specifications

3. Wiring diagram
MML-AP0074H-E, AP0094H-E, AP0124H-E, AP0154H-E, AP0184H-E, AP0244H-E

11 -216
11 Technical Specifications

4. Center of gravity

Model name Total weight(kg)


MML-AP0074H-E
MML-AP0094H-E
37
MML-AP0124H-E

MML-AP0154H-E

MML-AP0184H-E
40
MML-AP0244H-E

5. Electrical characteristics

Nominal Voltage Voltage Range Fan Motor Power Supply


Ty p e Mo d el
(V-Ph-Hz) Min Max kW FLA MCA MOCP
MML-AP0074H-E 230-1-50 198 264 0.045 0.30 0.37 15
MML-AP0094H-E 230-1-50 198 264 0.045 0.30 0.37 15

Floor Standing MML-AP0124H-E 230-1-50 198 264 0.045 0.49 0.62 15


Cabinet Type MML-AP0154H-E 230-1-50 198 264 0.045 0.49 0.62 15
MML-AP0184H-E 230-1-50 198 264 0.070 0.54 0.68 15
MML-AP0244H-E 230-1-50 198 264 0.070 0.54 0.68 15

MCA : Minimum Circuit Amps FLA : Full Load Amps


MOCP : Maximum Overcurrent Protection (Amps)

11 -217
11 Technical Specifications

6. Sensible capacity table


Floor Standing Cabinet Type ( MML-AP***4H-E ) TC : Total capacity [kW] SHC : Sensible capacity [kW]
indoor air temp.
o o o o o o o
unit outdoor 14.0 C WB 16.0 C WB 18.0 C WB 19.0 C WB 20.0 C WB 22.0 C WB 24.0 C WB
size air temp. o
20 C DB
o
23 C DB
o
26 C DB
o
27 C DB
o
28 C DB
o
30 C DB
o
32 C DB
o
C DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
12.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
14.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
16.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
18.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
20.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
21.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
007 23.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
25.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
27.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
29.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
31.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
33.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
35.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4
37.0 1.7 1.2 1.9 1.3 2.1 1.4 2.1 1.4 2.2 1.4 2.3 1.3 2.4 1.3
39.0 1.7 1.2 1.9 1.2 2.0 1.3 2.1 1.3 2.1 1.3 2.3 1.3 2.4 1.3
10.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
12.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
14.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
16.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
18.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
20.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
21.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
009 23.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
25.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
27.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
29.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
31.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
33.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
35.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5
37.0 2.2 1.4 2.5 1.5 2.6 1.6 2.7 1.5 2.8 1.5 3.0 1.5 3.1 1.5
39.0 2.2 1.3 2.4 1.4 2.6 1.5 2.6 1.5 2.7 1.5 2.9 1.5 3.0 1.5
10.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
12.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
14.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
16.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
18.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
20.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
21.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
012 23.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
25.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
27.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
29.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
31.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
33.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
35.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1
37.0 2.9 1.9 3.2 2.0 3.4 2.1 3.5 2.1 3.6 2.1 3.8 2.1 4.0 2.1
39.0 2.8 1.8 3.1 2.0 3.3 2.1 3.4 2.1 3.5 2.1 3.7 2.1 3.9 2.0
10.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.6
12.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.6
14.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.6
16.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.6
18.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.6
20.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.6
21.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.6
015 23.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.6
25.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.6
27.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.6
29.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.6
31.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.6
33.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.6
35.0 3.6 2.4 4.0 2.6 4.2 2.7 4.5 2.8 4.5 2.7 4.7 2.7 5.0 2.6
37.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.6
39.0 3.4 2.3 3.7 2.4 4.0 2.6 4.2 2.6 4.2 2.6 4.5 2.5 4.7 2.5

11 -218
11 Technical Specifications

Floor Standing Cabinet Type ( MML-AP***4H-E ) TC : Total capacity [kW] SHC : Sensible capacity [kW]
indoor air temp.
o o o o o o o
unit outdoor 14.0 C WB 16.0 C WB 18.0 C WB 19.0 C WB 20.0 C WB 22.0 C WB 24.0 C WB
size air temp. o
20 C DB
o
23 C DB
o
26 C DB
o
27 C DB
o
28 C DB
o
30 C DB
o
32 C DB
o
C DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
12.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
14.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
16.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
18.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
20.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
21.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
018 23.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
25.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
27.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
29.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
31.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
33.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
35.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4
37.0 4.5 3.0 4.9 3.2 5.3 3.4 5.4 3.4 5.6 3.4 5.9 3.4 6.2 3.3
39.0 4.3 2.9 4.8 3.1 5.1 3.3 5.3 3.3 5.4 3.3 5.7 3.3 6.0 3.2
10.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
12.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
14.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
16.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
18.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
20.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
21.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
024 23.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
25.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
27.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
29.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
31.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
33.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
35.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4
37.0 5.6 3.9 6.2 4.1 6.7 4.4 6.9 4.4 7.1 4.4 7.5 4.3 7.8 4.2
39.0 5.5 3.8 6.1 4.0 6.5 4.2 6.7 4.2 6.9 4.2 7.3 4.2 7.6 4.1

11 -219
11 Technical Specifications

7. Air throw distance chart

MML-AP0074H-E, AP0094H-E MML-AP0124H-E, AP0154H-E

3
Air speed (m/s)

Air speed (m/s)


High wind
2 High wind
2
Med. wind Med. wind
1 Low wind
1 Low wind

0 1 2 3 4 5 6 7
0 1 2 3 4 5 6 7

Distance from discharge grille (m) Distance from discharge grille (m)

MML-AP0184H-E, AP0244H-E
Air speed (m/s)

High wind
3
Med. wind
2
Low wind

0 1 2 3 4 5 6 7 8

Distance from discharge grille (m)

11 -220
11 Technical Specifications

8. Sound characteristics (NC-Curve)


[Measuring location]
Microphone

Air outlet 1m

1m

MML-AP0074H-E, AP0094H-E MML-AP0124H-E, AP0154H-E

Fan tap H M L Fan tap H M L


Sound pressure Sound pressure
39 37 35 45 41 38
level (dB(A)) level (dB(A))

90 90

80 80
Oct ave band sound pressure level (dB)
Oct ave band sound pressure level (dB)

NC- 7 0 70 NC- 7 0
70

60 NC- 6 0 60 NC- 6 0

50 NC- 5 0 50 NC- 5 0

40 NC- 4 0 40 NC- 4 0
H
H M
M NC- 3 0
30 NC- 3 0 30
L L
20 NC- 2 0 20 NC- 2 0
Approximate threshold of Approximate threshold of
hearing for continuous noise hearing for continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

MML-AP0184H-E, AP0244H-E

Fan tap H M L
Sound pressure
49 44 39
level (dB(A))

90

80
Oct ave band sound pressure level (dB)

70 NC- 7 0

60 NC- 6 0

50 NC- 5 0

H
40 NC- 4 0
M

30 L NC- 3 0

20 NC- 2 0
Approximate threshold of
hearing for continuous noise
10
63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)

11 -221
11 Technical Specifications

11 -222
11 Technical Specifications

11-2-12. Floor Standing Type

Floor Standing Type

MMF-AP0154H-E / MMF-AP0184H-E
MMF-AP0244H-E / MMF-AP0274H-E
MMF-AP0364H-E / MMF-AP0484H-E
MMF-AP0564H-E

Contents
1. Specifications
2. Dimension
3. Wiring diagram
4. Center of Gravity
5. Electrical characteristics
6. Sensible capacity table
7. AIR throw distance chart
8. Sound characteristics (NC-Curve)

11 -223
11 Technical Specifications

1. Specifications

Floor Standing Type


Model name MMF- AP0154H-E AP0184H-E AP0244H-E AP0274H-E AP0364H-E AP0484H-E AP0564H-E

Cooling/Heating capacity (Note 1) (kW) 4.5/5.0 5.6/6.3 7.1/8.0 8.0/9.0 11.2/12.5 14.0/16.0 16.0/18.0

Power supply 1 phase 50Hz 230V (220 - 240V) ( Separate power supply for indoor units is required.)

Running current (A) 0.67 0.88 1.29 1.60

Electrical (kW)
Power consumption 0.150 0.190 0.280 0.350
characteristics

Power factor (%) 97 94 95

Starting current (A) 0.90 1.10 1.70 2.10

Appearance Silky shade (1Y 8.5/0.5)

Outer Height x Width x


Depth (mm) 1750 x 600 x 210 1750 x 600 x 390
dimension

Total weight (kg) 48 49 65

Heat exchanger Finned tube

Soundproof/Heat-insulating material Non-flammable insulation

Fan Centrifugal fan

Standard air flow


Fan unit (m3/h) 900/780/660 1,200/1,020/840 1,920/1,680/1,380 2,160/1,860/1,560
(High/Mid./Low)

Motor output (W) 37 63 110 160

Air filter Standard filter (Simple filter)

Controller Remote controller

Gas side (mm) / 12.7


O / 15.9
O

Connecting
pipe Liquid side (mm) / 6.4
O / 9.5
O

Drain port (Nominal dia. mm) 20 (One side of male screw)

Sound pressure level(Note 2)(High/Mid./Low) (dB(A)) 46/43/38 49/45/40 51/48/44 54/50/46

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on the
reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.
Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27 C DB/19 C WB, Outdoor air temperature 35 C DB
O O O

Heating : Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB/6 C WB


O O O

11 -224
11 Technical Specifications

2. Dimension
MMF-AP0154H-E, AP0184H-E, AP0244H-E, AP0274H-E, AP0364H-E, AP0484H-E, AP0564H-E

600 Bracket for wall mounting


pitch pitch
30×3 80 30×3 Air outlet
E
40

20
25

Wall
210
815

1750

Pipe holes on side


(both sides)
50 (knockout hole)

Rear side pipe hole


(φ130 knockout hole) Drain pipe port
(both sides)
631

(knockout hole)
165
120

D
59

C
Air inlet F
10

Bracket for 180 120


floor mounting B
Floor fixing bracket Drain pipe Earth screw (M4)
(both sides) A
screw positions 640 connecting port

Space required for installation and servicing MMF-AP0151H MMF-AP0361H


200 or

Liquid
more

Liquid
Wall side side
1000 or more

500 or
358

380

(Front side)
more Wall Gas
155 side
164 165 215
(Front side) Refrigerant pipe connecting
204 port (Liquid side) 215
Gas side
Model MMD- A B C D E F Refrigerant pipe connecting port (Gas side)
AP0154H-E to AP0274H-E 200 107 132 157 210 50
Refrigerant piping position
AP0364H-E to AP0564H-E 380 125 120 160 390 40 (Unit: mm)

11 -225
11 Technical Specifications

3. Wiring diagram
MMF-AP0154H-E, AP0184H-E, AP0244H-E, AP0274H-E, AP0364H-E, AP0484H-E, AP0564H-E

11 -226
11 Technical Specifications

4. Center of Gravity

Model name X(mm) Y(mm) Z(mm) Total weight(kg)


MMF-AP0154H-E
48
MMF-AP0184H-E
90 290
MMF-AP0244H-E
49
MMF-AP0274H-E 880

MMF-AP0364H-E
MMF-AP0484H-E 120 295 65
MMF-AP0564H-E

Y X
G
Z

11 -227
11 Technical Specifications

5. Electrical characteristics

Nominal Voltage Voltage Range Fan Motor Power Supply


Ty p e Mo d el
(V-Ph-Hz) Min Max kW FLA MCA MOCP
MMF-AP0154H-E 230-1-50 198 264 0.037 0.77 0.96 15
MMF-AP0184H-E 230-1-50 198 264 0.037 0.77 0.96 15
MMF-AP0244H-E 230-1-50 198 264 0.063 1.01 1.27 15
Floor Standing Type MMF-AP0274H-E 230-1-50 198 264 0.063 1.01 1.27 15
MMF-AP0364H-E 230-1-50 198 264 0.110 1.48 1.85 15
MMF-AP0484H-E 230-1-50 198 264 0.160 1.84 2.30 15
MMF-AP0564H-E 230-1-50 198 264 0.160 1.84 2.30 15

MCA : Minimum Circuit Amps FLA : Full Load Amps


MOCP : Maximum Overcurrent Protection (Amps)

11 -228
11 Technical Specifications

6. Sensible capacity table

Floor Standing Type ( MMF-AP***4H-E ) TC : Total capacity [kW] SHC : Sensible capacity [kW]
indoor air temp.
o o o o o o o
unit outdoor 14.0 C WB 16.0 C WB 18.0 C WB 19.0 C WB 20.0 C WB 22.0 C WB 24.0 C WB
size air temp. o
20 C DB
o
23 C DB
o
26 C DB
o
27 C DB
o
28 C DB
o
30 C DB
o
32 C DB
o
C DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.3
12.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.3
14.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.3
16.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.3
18.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.3
20.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.3
21.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.3
015 23.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.3
25.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.3
27.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.3
29.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.3
31.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.3
33.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.3
35.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.3
37.0 3.6 2.9 4.0 3.1 4.2 3.3 4.4 3.3 4.5 3.3 4.7 3.3 5.0 3.2
39.0 3.5 2.8 3.8 3.0 4.1 3.2 4.2 3.2 4.4 3.2 4.6 3.2 4.8 3.1
10.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.0
12.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.0
14.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.0
16.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.0
18.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.0
20.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.0
21.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.0
018 23.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.0
25.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.0
27.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.0
29.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.0
31.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.0
33.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.0
35.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.0
37.0 4.5 3.5 4.9 3.7 5.3 4.0 5.4 4.0 5.6 4.0 5.9 3.9 6.2 3.8
39.0 4.3 3.4 4.8 3.6 5.1 3.9 5.3 3.9 5.4 3.9 5.7 3.8 6.0 3.7
10.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.1
12.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.1
14.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.1
16.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.1
18.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.1
20.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.1
21.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.1
024 23.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.1
25.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.1
27.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.1
29.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.1
31.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.1
33.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.1
35.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.1
37.0 5.6 4.5 6.2 4.8 6.7 5.1 6.9 5.1 7.1 5.1 7.5 5.1 7.8 5.0
39.0 5.5 4.4 6.1 4.7 6.5 5.0 6.7 5.0 6.9 5.0 7.3 4.9 7.6 4.8
10.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.7
12.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.7
14.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.7
16.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.7
18.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.7
20.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.7
21.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.7
027 23.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.7
25.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.7
27.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.7
29.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.7
31.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.7
33.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.7
35.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.7
37.0 6.4 5.1 7.0 5.4 7.5 5.7 7.7 5.7 8.0 5.7 8.4 5.7 8.8 5.5
39.0 6.2 4.9 6.8 5.2 7.3 5.6 7.5 5.6 7.8 5.6 8.2 5.5 8.6 5.4

11 -229
11 Technical Specifications

Floor Standing Type ( MMF-AP***4H-E ) TC : Total capacity [kW] SHC : Sensible capacity [kW]
indoor air temp.
o o o o o o o
unit outdoor 14.0 C WB 16.0 C WB 18.0 C WB 19.0 C WB 20.0 C WB 22.0 C WB 24.0 C WB
size air temp. o
20 CDB
o
23 C DB
o
26 C DB
o
27 C DB
o
28 C DB
o
30 C DB
o
32 C DB
o
C DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.7
12.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.7
14.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.7
16.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.7
18.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.7
20.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.7
21.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.7
036 23.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.7
25.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.7
27.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.7
29.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.7
31.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.7
33.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.7
35.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.7
37.0 8.9 6.9 9.8 7.3 10.5 7.8 10.8 7.7 11.2 7.7 11.8 7.7 12.4 7.5
39.0 8.7 6.7 9.6 7.1 10.2 7.6 10.5 7.5 10.9 7.5 11.5 7.5 12.0 7.3
10.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.6
12.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.6
14.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.6
16.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.6
18.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.6
20.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.6
21.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.6
048 23.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.6
25.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.6
27.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.6
29.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.6
31.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.6
33.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.6
35.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.6
37.0 11.1 8.5 12.3 9.0 13.1 9.6 13.6 9.6 14.0 9.6 14.8 9.5 15.4 9.3
39.0 10.8 8.3 12.0 8.8 12.8 9.3 13.2 9.3 13.6 9.3 14.4 9.2 15.0 9.0
10.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.0
12.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.0
14.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.0
16.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.0
18.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.0
20.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.0
21.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.0
056 23.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.0
25.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.0
27.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.0
29.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.0
31.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.0
33.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.0
35.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.0
37.0 12.7 9.8 14.1 10.4 15.0 11.1 15.5 11.0 16.0 11.0 16.9 10.9 17.7 10.7
39.0 12.4 9.5 13.7 10.1 14.6 10.8 15.1 10.7 15.5 10.7 16.4 10.6 17.2 10.4

11 -230
11 Technical Specifications

7. Air throw distance chart

(m) M M F- AP0154H-E, AP0184H-E (m) M M F- AP0244H-E, AP0274H-E


2.7 2.7
0.5m/s
2.0 0.5m/s 2.0
1.5m/s 1.0m/s 0.7m/s 1.5m/s 1.0m/s

1.0 1.0

1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
(m) (m)

(m) M M F- AP0364H-E (m) M M F- AP00484H-E, AP0564H-E


2.7 2.7
2.0 0.5m/s 2.0
1.0m/s 1.0m/s
2.0m/s 1.5m/s 1.5m/s 1.5m/s 1.5m/s

1.0 1.0

1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
(m) (m)

11 -231
11 Technical Specifications

8. Sound characteristics (NC Curve)


Measuring location

Microphon

Front

1m

1m

MMF-AP0154H-E, AP0184H-E MMF-AP0244H-E, AP0274H-E

Fan tap H M L Fan tap H M L


Sound pressure Sound pressure
46 43 38 49 45 40
level (dB(A)) level (dB(A))

90 90

80 80
Octave band sound pressure level (dB)
Octave band sound pressure level (dB)

70 70

60 60

50 50
H
H M
40 M 40
L
L
30 30

20 20 Approximate threshold of
Approximate threshold of
hearing for continuous noise hearing for continuous noise

10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

MML-AP0364H-E MML-AP0484H-E, AP0564H-E

Fan tap H M L Fan tap H M L


Sound pressure Sound pressure
51 48 44 54 50 46
level (dB(A)) level (dB(A))

90 90

80 80
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

70 70

60 60

H
50 H 50
M
M
40 40 L
L

30 30

20 Approximate threshold of 20 Approximate threshold of


hearing for continuous noise hearing for continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

11 -232
11 Technical Specifications
11 Technical Specifications

11-2-13. Fresh Air Intake Indoor Unit Type

Fresh Air Intake


Indoor Unit Type

Indoor Unit
MMD-AP0481HFE
MMD-AP0721HFE
MMD-AP0961HFE

Contents
1. System summary
2. Specifications
3. Dimensions
4. Wiring diagram
5. Center of Gravity
6. Electrical characteristics
7. Fan characteristics
8. Sound characteristics (NC Curve)

11 -233
11 Technical Specifications

1. System summary
Fresh Air Intake Indoor Unit Type

1. Outline of fresh air intake unit

• Type: Concealed Duct High Static Pressure type


Three models (5HP, 8HP, 10HP) are prepared.

• Connectable outdoor unit


Outdoor unit of SMMS and SMMS-i sereies.

• Corresponding system
Corresponds to a system in which there are the fresh air intake units and the indoor air
conditioners.
(For the fresh air intake units, up to 2 units for one system and also within 30% to capacity of the
connectable indoor air conditioners are allowed.)

• Definition
The fresh air intake unit means an air controller for taken-in fresh air.
Intake of the fresh air often influences on the system so that the normal control of the air conditioner
becomes difficult or gives a large load upon air controller and cooling performance.
Therefore it is frequently adopted to handle the fresh air to a certain condition before the fresh air
will enter in the main air conditioner.
This handling device is called a fresh air intake unit.

NOTE:
The Fresh Air Intake unit is an air conditioner provided to handle the fresh air load and is not to control
the room temperature. For correspondence to the load of the indoor air controller, set an air
conditioner separately.

11 -234
11 Technical Specifications

2. System able to be combined


The fresh air intake unit is connectable to S-MMS (Super Modular Multi system).
However this is not connectable to S-HRM (Super Heat Recovery Multi system).

Up to two fresh air intake


units occupy 30% or less

0.5m or less

80 to 100% to capacity of the outdoor

Keep the height difference between the fresh air intake units to 0.5m or less.

· The fresh air intake unit is usually used together with the indoor units on one line of the multi system.
The fresh air intake unit only cannot be connected.

· The total capacity of the indoor units and the fresh air intake units is restricted to 80% to 100%
against the capacity of the outdoor units. (This restriction should be strictly kept for correct control
of the refrigerant.)
· Up to two fresh air intake units can be connected on one line of the multi system.
The allowable total capacity of the two fresh air intake units shall be 30% or less against the total
capacity of the indoor units (including the fresh air intake units).

Connection which stretches


over two floors is unavailable

Height difference:
0.5m or more

11 -235
11 Technical Specifications

3. Use Conditions
· In COOL mode, if temperature of the fresh air is under the setup temp. +3°C, FAN status is
automatically made. When temperature of the fresh air is under 19°C, FAN status is also made
regardless of the setup temperature.
· In HEAT mode, if temperature of the fresh air is over the setup temp. -3°C, FAN status is
automatically made. When temperature of the fresh air is over 15°C, FAN status is also made
regardless of the setup temperature.

Ts

Ts + 3°C

Ts

Ts - 3°C

• Operable mode and discharge temp setup range


Operation mode At shipment from factory Setup range
COOL 18°C 16 to 27°C
HEAT 25°C 16 to 27°C

• Special mentions
1. The fan operation of the Fresh Air Intake unit stops during defrosting.
However the fan operation is enabled to continue by selection.
2. When a central controller is used, divide zone setup of indoor air conditioner and fresh air intake
unit.
3. The standard is to control the discharge temperature. However the priority is given to the capacity
control for the indoor air conditioner in a system in which the normal indoor air conditioner
concurrently operated.
4. The fresh air intake unit cannot be connected with remote controller group of the indoor air
conditioner.
5. In heating operation, if the temperature is below –5°C, the operation stops automatically. (FAN stop)
(To protect the refrigerant cycle)
6. In cooling operation, if the temperature is below 5°C, the operation stops automatically. (FAN stop)

11 -236
11 Technical Specifications

2. Specifications
Fresh Air Intake Indoor Unit Type

Model name MMD-AP0481HFE MMD-AP0721HFE MMD-AP0961HFE


Cooling/Heating capacity (Note 1) (kW) 14.0/8.9 22.4/13.9 28.0/17.4
Electical Power supply 1 phase 50Hz 230V (220-240V)
characteristics Running current (A) 1.43 2.52 2.73
Power consumption (kW) 0.28 0.45 0.52
Starting current (A) 3.50 7.00 7.00
Outer Main unit Height (mm) 492
dimension Width (mm) 892 1,392
Depth (mm) 1,262
Total weight Main unit (kg) 93 144
Heat exchanger Finned tube
Soundproof / Heat-insulating material Non-flammable insulation
Fan unit Fan Centrifugal fan
Standard air flow (m3/h) 1,080 1,680 2,100
Motor (W) 160 160 x 2
External static pressure
210 165 190
(factory setting)
External static pressure 170-210-230 140-165-180 160-190-205
Air flow limit (m3/h)
756 1,176 1,470
Lower limit/Upper limit
Air filter Option or field supply
Controller Wired remote controller
Connecting pipe Gas pipe (mm) 15.9 22.2
Liquid pipe (mm) 9.5 12.7
Drain pipe R1
Sound pressure level (Note 2) (dB(A))
45/43/41 46/45/44
(High/Med./Low)
Sound power level (High/Med./Low) (dB(A)) 65/63/61 66/65/64
Operation range Cooling (Note 3) (°C) 5 - 43
Heating (Note 4) (°C) -5 - 43

* The setting temperature is 16 - 27°C(standard FCU…18 - 29°C).


* An option humidifier is not available with Fresh Air Intake Indoor unit.
* Height difference between Fresh Air Intake Indoor units must be within 0.5m.
Height difference between Fresh Air Intake Indoor unit and standard FCU must be within 30m.
Note 1: Rated conditions Cooling : Outdoor air temperature 33°C DB/28°C WB setting temperature 18°C
Heating : Outdoor air temperature 0°C DB/-2.9°C WB setting temperature 18°C
Piping : Length 7.5m / Height 0m
Note 2: The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the
values meausured in the actual operating environment become large than the indicated values due to
the effects of external sound.
Note 3: * When supply air temperature is “setting temperature + 3°C” or less, Fresh Air Intake unit operates as
FAN mode.
* When supply air temperature is 19°C or less, Fresh Air Intake Indoor unit operates as FAN mode.
Note 4: * When supply air temperature is “setting temperature - 3°C” or over, Fresh Air Intake unit operates as
FAN d
11 -237
11 Technical Specifications

3. Dimensions
Fresh Air Intake Indoor Unit Type (MMD-AP***HFE)
MMD-AP0481HFE, AP0721HFE, AP0961HFE
Long hole for M10 hanging bolt 1328
Type Hole dia.-Wideth x Length 1288 (Hanging bolt pitch)
0481 4- 12 x 40 1262 X
0721, 0961 4- 12 x 92

Space necessary for service


Over
200

Service space

B (Hanging bolt pitch)


Fresh air
intake
unit A
Over 1000

200

Service
space
Check port (600 )
(65)

100
(185)

Filter direction
30

600

600
Drain piping work X
example at local site
Refrigerative piping work Check port
example at local site

Drain port Refrigerant pipe


(When drain-up kit is mounted) connecting port Electric parts box (With cover)
For vinyl chloride pipes (Gas side M)
(Nominal dia 25 : Inner dia 32)
Filter chamber
Drain piping work Refrigerant pipe High-performance
Refrigerant piping work
example at local site connecting port filter
example at local site
C D E F (Liquid pipe N)
Pre-filter
41

150
492

Z
370

360

216
47
61
81

Blow-off port 23 704


(205) 850 292
Discharge temp sensor
60 (250) 1262
Discharge port connecting flange (K)
(Accessory for main unit of product) Drain port (R1) (Main uint of product)

G H I J G H I J
38

35
406
406

51
38

Pre-filter Suction port


A
Suction port connecting flange (L)
Z View
(Accessory for main unit of product)
X - X detail diagram

AP0961HFE 1392 1260 250 250 250 250 250 250 250 250 10-M6 10-M6 22.2 brazing 12.7 flare
AP0721HFE 1392 1260 250 250 250 250 250 250 250 250 10-M6 10-M6 22.2 brazing 12.7 flare
AP0481HFE 892 810 215 107.5 107.5 215 250 250 8-M6 6-M6 15.9 flare 9.5 flare
Model MMD- A B C D E F G H I J K L M N

11 -238
11 Technical Specifications

Work example Filter chamber


Pre-filter Canvas duct
High-performance filter

Over
Canvas duct

50
Fresh air
intake unit

Over
100
Air intake duct Outside air

Check port
Ceiling

<Installation Notice>
1 The check port should be 600 x 600mm.
2 A slope the piping outside of the unit downward at 1/100.
Be sure to do heat insulating to the connecting peat with the indoor unit. In complete heat insulating may cause
dewing.
3 Check the water drainage is surely performed at the trial operation.
4 Do not install the air conditioner in a salty place such as seaside area and a place where sulfurous gasgenerated
such as in a spa.
5 Please clean the drain plate before the season of cooling air conditioning.
Water overflows from the drain plate when the drain plate and the drain poart are dirty, and the ceiling might be wet.
6 The air filter is not built into the Fresh Air intake indoor unit.
Please remove the dust that enters from air by installing optional Filter chamber, Pre-filter, and High Efficiency Filter.
If no air filter is installed, dust will collect in the heat exchanger, which may cause the air conditioner to fail or to leak.
(local prpcure)
7 Place where the unit cane installed horizontally.
8 Set the canvas duct at air inlet port and air supply port. It is to avoid conveyance of vibration, abnormal resonance
sound and also to make easy the disassembly of the main unit in service time.
9 Be sure to connect the wire and connection cable while matching the terminal.
Please refer to the wiring diagram for details.
10 Please note that the size is different because of MMD-AP0481HFE and MMD-AP0721HFE/MMD-AP0961HFE in the
electric part box.
11 The heat insulator is pasted to externals of the main body of the product. (Bottom board thickness : 16mm, other
thickness : 6mm)
12 Be sure to set the duct at air filter with descending inclination because the suction duct of the this unit is exposed to
outdoors and therefore rainwater, leaves and birds are easy to enter in if it is set horizontally.
Attching wire netting and others to end of the suction duct is also recommended.
13 Set the air inlet duct at descending inclination so that water can be drained even if rainwater enters in.
14 The balloon entrance connection flange and the inhalation mouth connection flange are installed in the main body
of the product.
Please use it detaching it when you connect the duct.
Please obtain Filter chamber directly in the main body of the product when you install Filter chamber and obtain
installation Air intake port connecting flange for C side of A.
15 Connect the ducts directly so that the ducts do not weight on the main unit.
Moreover, please do not damage, and do not knock down air supply temperature sensor when you connect the air
supply duct.
16 Be sure to apply heat insulation for the duct to prevent dewing.
Especially, when it is inhaled to heat it, the be dewy on the surface of the outside of the duct because cold air enters.
Please put the heat insulator.
17 When installing the drain pump and filter chamber sold separately, refer to attachment installation manual.

11 -239
11 Technical Specifications

Discharge port connecting flange

MMD-AP0481HFE MMD-AP0721HFE, AP0961HFE


775 1130
65 215 215 215 65 65 250 250 250 250 65
12

12
25

25
25 725 25 25 1080 25
394

394
370

370
344

344
25
25

8- 8 10- 8
12

12

Suction port connecting flange

MMD-AP0481HFE MMD-AP0721HFE, AP0961HFE


630 1130
65 250 250 65 65 250 250 250 250 65
12

12
25

25 580 25 25 1080 25 25
430

430
406

406
380

380
25

25

10- 8
12

12

6- 8

NOTE 1)
The left figure shows MMD-AP0721HFE / AP0961HFE.
For MMD-AP0481HFE, one fan motor and one fan are provided.

11 -240
11 Technical Specifications

4. Wiring diagrams
Model: MMD-AP0481HFE
WHI 8 7 RED (Option)
43F1 TA TCJ TC2 TC1 TF
DP
Surge absorber
LM
Fan DP CN033
CN083 7 CN068 1 3 (GRN) 1 3 1 2 1 2 1 2 1 3 1 2
(WHI) 9 7 5 3 1 (BLU) 1 3 1 3 1 2 3 1 2 1 2 1 2 1 2 3 1 2

CN030 CN104 CN102 CN101 CN100 CN103


(RED) (YEL) (RED) (BLK) (BRW) (GRN)
RY007 H M L UL FS 1
BLK CN080
P301 2 PNL
(GRN)
3

RY004 CN073 1
EXCT
1 Control P.C. Board (RED) 2
RY006
3
CN304 (GRY) RY002 RY001 for Indoor Unit CN070 1
Filter
(WHI) 2
MCC-1403
1 1 1
RY005
CN309 (YEL) 2
3 3 CN081 3
(BLK)
Fuse 4
RED ACIN T5.0A, 250V ~ 5
1 1
Power
supply circuit
WHI CN067 (BLK) 6 6 5 5
3 3 5 5 2 2
CN082 4 4 1 1
PMV
(BLU) 3 3 3 3
1 1 CN044 CN040 CN041 CN050 CN074 CN075 CN061 CN032 CN060 2 2 4 4
CN066 (WHI)
2 2 (BRW) (BLU) (BLU) (WHI) (WHI) (WHI) (YEL) (WHI) (WHI) 1 1 6 6

1 2 1 2 1 2 3 1 2 3 4 5 1 2 3 1 2 3 4 5 6 1 2 3 4 5 6 1 2 1 2 3 4 5 6
EMG 1 2 1 3 1 2 3 1 2 3 4 5 6 T10 Fan drive Option
1 2 3 4 5 6 CN02
BLU BLU BLK BLK 1 2 3 4 5 6 (YEL)

Line filter Sub P.C. board


MCC-1520
Fan motor inside wiring diagram
U1 U2 A B 1 2 3 4 5 6
1 2 3 4 5 6
CN01
(WHI) BLU

BLK ORN
TR1
RED WHI U1 U2 WHI
GRY
A B RED 49F
RED Outdoor unit Remote Remote controller
1 controller
WHI board Motor over heating protection switch
3
Connector WHI

RED F1 T10A, 250V ~ RED

RED
5 6

R(L) S(N) 43F1 43F1

3 4 RC
Indoor unit
earth screw YEL

Power supply
GRY
RED
WHI

220 – 240V ~ 50Hz Closed-end


220V ~ 60Hz connector
1 2 3 4
1 2 3 4
4P (WHI) A F1 F2 F3 F4
Fan 1 BLU ORN BLK
GRY
RED
WHI

Symbol Parts name

FM Fan Motor
GRY
RED
WHI

RC Running Capacitor
1 2 3 4
TR1 Transformer 1 2 3 4
4P (WHI) 1 2 3
BLU ORN BLK
GRY
RED
WHI

TA Intake air temp. sensor

TF Blow temp. sensor

TC1, TC2, TCJ Temp. sensor


FM Color Identification
G &Y
RED : RED
RY005 ~ 007 Fan motor control relay
WHI : WHITE
RY002 Drain control relay YEL : YELLOW
BLU : BLUE
PMV Pulse Motor Valve BLK : BLACK
F1 Fuse for fan motor GRY : GRAY
PNK : PINK
43F1 Fan motor control relay ORN : ORANGE
BRW : BROWN
DP Drin Pump motor
G &Y : GREEN & YELLOW
FS Float Swotch

1. indicates the terminal block.


Terminal block No. Fan motor wiring Note
Latter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site. F1 (Low static pressure tap) Blue (50/60Hz)
3. indicates the control P.C. board.
F2 (Intermediate static pressure tap) Orange (50/60Hz) At shipment from factory
4. When installing the drain pump connect the froat switch connector to CN030 connector.
5. A position is connected to terminal block when change to static pressure. F3 (High static pressure tap) Bkack (50/60Hz)
Exchange the lead wire of arrow ( ) pisition after the terminal number as figure and
F4 — —
lead wire’s color of fan motor.

11 -241
11 Technical Specifications

Models: MMD-AP0721HFE and MMD-AP0961HFE


WHI 8 7 RED
43F1

Surge absorber
(Option)
WHI 8 7 RED TA TCJ TC2 TC1 TF
43F2
DP
6
Surge absorber LM
Fan RED DP CN033
7 CN083 7 CN068 1 3 (GRN) 1 3 1 2 1 2 1 2 1 3 1 2
(WHI) 9 7 5 3 1 (BLU) 1 3 1 3 1 2 3 1 2 1 2 1 2 1 2 3 1 2

CN030 CN104 CN102 CN101 CN100 CN103


(RED) (YEL) (RED) (BLK) (BRW) (GRN)
RY007 H M L UL FS 1
BLK CN080
P301 2 PNL
(GRN)
3

RY004 CN073 1
EXCT
1 (RED) 2
CN304 (GRY) RY006 RY002 RY001 Control P.C. Board
3 CN070 1
for Indoor Unit (WHI) 2
Filter

1 1 MCC-1403 1
RY005
CN309 (YEL) 2
3 3 CN081 3
(BLK)
Fuse 4
RED ACIN T5.0A, 250V ~ 5
1 1
Power
supply circuit
WHI CN067 (BLK) 6 6 5 5
3 3 5 5 2 2
CN082 4 4 1 1
PMV
(BLU) 3 3 3 3
1 1 CN044 CN040 CN041 CN050 CN074 CN075 CN061 CN032 CN060 2 2 4 4
CN066 (WHI)
2 2 (BRW) (BLU) (BLU) (WHI) (WHI) (WHI) (YEL) (WHI) (WHI) 1 1 6 6

1 2 1 2 1 2 3 1 2 3 4 5 1 3 1 2 3 4 5 6 1 2 3 4 5 6 1 2 1 2 3 4 5 6
EMG 1 2 1 3 1 3 1 2 3 4 5 6 T10 Fan drive Option
1 2 3 4 5 6 CN02
BLU BLU BLK BLK 1 2 3 4 5 6 (YEL)

Line filter Sub P.C. board


MCC-1520
Fan motor inside wiring diagram
U1 U2 A B 1 2 3 4 5 6 CN01
1 2 3 4 5 6 (WHI) BLU

BLK ORN
TR1
RED WHI U1 U2 WHI
GRY
A B RED 49F
Outdoor unit Remote Remote controller
controller
RED board Motor over heating protection switch
1
WHI
3
RED F1 T10A, 250V ~ RED
Connector

RED WHI RED F2 T10A, 250V ~


8
5 RED 6 6

43F1 43F2 43F1


R(L) S(N) 3 4
ORN
4
Indoor unit 5 ORN
earth screw YEL
RC2 RC1
Power supply
220 – 240V ~ 50Hz Closed-end
220V ~ 60Hz connector
GRY

GRY
RED

RED
WHI

WHI

1 2 3 4 1 2 3 4
1 2 3 4
4P (WHI) A F1 F2 F3 F4 1 2 3 4
4P (WHI) A F1 F2 F3 F4
Symbol Parts name Fan 2 BLU ORN BLK Fan 1 BLU ORN BLK
GRY

GRY
RED

RED
WHI

WHI

FM1, FM2 Fan Motor


GRY

GRY
RED

RED
WHI

WHI

RC1, RC2 Running Capacitor

TR1 Transformer 1 2 3 4 1 2 3 4
1 2 3 4
4P (WHI) 1 2 3 1 2 3 4
4P (WHI) 1 2 3
TA Intake air temp. sensor
BLU ORN BLK BLU ORN BLK
GRY

GRY
RED

RED
WHI

WHI

TF Blow temp. sensor

TC1, TC2, TCJ Temp. sensor


FM2 FM1
RY005 ~ 007 Fan motor control relay G &Y G &Y

RY002 Drain control relay

PMV Pulse Motor Valve


Color Identification
F1, F2 Fuse for fan motor
RED : RED GRY : GRAY
43F1, 43F2 Fan motor control relay WHI : WHITE PNK : PINK
YEL : YELLOW ORN : ORANGE
DP Drin Pump motor BLU : BLUE BRW : BROWN
FS Float Swotch BLK : BLACK G &Y : GREEN & YELLOW

1. indicates the terminal block.


Terminal block No. Fan motor wiring Note
Latter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site. F1 (Low static pressure tap) Blue (50/60Hz)
3. indicates the control P.C. board.
F2 (Intermediate static pressure tap) Orange (50/60Hz) At shipment from factory
4. When installing the drain pump connect the froat switch connector to CN030 connector.
5. A position is connected to terminal block when change to static pressure. F3 (High static pressure tap) Bkack (50/60Hz)
Exchange the lead wire of arrow ( ) pisition after the terminal number as figure and
F4 — —
lead wire’s color of fan motor.

11 -242
11 Technical Specifications

5. Center of gravity
Fresh Air Intake Indoor Unit Type

Model name MMD- X (mm) Y (mm) Z (mm) Weight (kg)


AP0481HFE 670 480 220 93
AP0721HFE
670 770 220 144
AP0961HFE

X
Electric parts box

6. Electrical characteristics
Fresh Air Intake Indoor Unit Type

Model name NominalVoltage Voltage Range Fan Motor Power supply


(V-Ph-Hz) Min. Max. kW FLA MCA MOCP
MMD-AP0481HFE 198 264 0.16 1.60 2.00 15
MMD-AP0721HFE 230-1-50 198 264 0.16 x 2 2.78 3.47 15
MMD-AP0961HFE 198 264 0.16 x 2 3.05 3.81 15
MCA : Minimum Circuit Amps FLA : Full load Amps
MOCP : Maximum Overcurrent Protection(Amps)

11 -243
11 Technical Specifications

7. Fan characteristics
Fresh Air Intake Indoor Unit Type
<220V> 50Hz

MMD-AP0481HFE (5HP) MMD-AP0721HFE (8HP)


3
Standard air volume: 1080m /h Standard air volume: 1680m3/h
Fan motor current (A)

Fan motor current (A)


3.0
2.0 High static pressure tap
High static pressure tap
2.5
1.5

2.0
1.0 Mid static
Mid static pressure tap pressure tap
Low static
Low static pressure tap pressure tap
1.5
0.5

350
350

300
External static pressure (Pa)

External static pressure (Pa)


300
High static pressure tap
High static pressure tap
250 250

Mid static pressure tap

200 200

Mid static pressure tap


150 150
Low static pressure tap
Low static pressure tap
100 100

50 50

0 0
800 900 1000 1100 1200 1200 1400 1600 1800
Air volume (m3/h) Air volume (m3/h)

MMD-AP0961HFE (10HP)
Standard air volume: 2100m3/h
Fan motor current (A)

3.5
High static pressure tap
Mid static pressure tap
3.0

2.5
Low static
pressure tap
2.0

350

300
External static pressure (Pa)

High static pressure tap


250

200

150
Mid static pressure tap

100
Low static pressure tap

50

0
1500 1700 1900 2100 2300
Air volume (m3/h)

11 -244
11 Technical Specifications

<230V> 50Hz

MMD-AP0481HFE (5HP) MMD-AP0721HFE (8HP)


3
Standard air volume: 1080m /h Standard air volume: 1680m3/h
Fan motor current (A)

Fan motor current (A)


3.0
2.0 High static pressure tap
High static pressure tap
2.5
1.5

2.0
1.0 Mid static
Mid static pressure tap Low static pressure tap
Low static pressure tap pressure tap
1.5
0.5

350
350

High static pressure tap 300


External static pressure (Pa)

External static pressure (Pa)


300
High static pressure tap

250
250
Mid static pressure tap

200 200

Mid static pressure tap 150


150
Low static pressure tap
Low static pressure tap
100 100

50 50

0 0
800 900 1000 1100 1200 1200 1400 1600 1800
Air volume (m3/h) Air volume (m3/h)

MMD-AP0961HFE (10HP)
Standard air volume: 2100m3/h
Fan motor current (A)

3.5
High static pressure tap
Mid static pressure tap
3.0

2.5
Low static
pressure tap
2.0

350

300
External static pressure (Pa)

High static pressure tap


250

200

Mid static pressure tap


150

Low static pressure tap


100

50

0
1500 1700 1900 2100 2300
Air volume (m3/h)

11 -245
11 Technical Specifications

<240V> 50Hz

MMD-AP0481HFE (5HP) MMD-AP0721HFE (8HP)


Standard air volume: 1080m3/h Standard air volume: 1680m3/h
Fan motor current (A)

Fan motor current (A)


3.0
2.0 High static pressure tap
High static pressure tap
2.5
1.5
Mid static pressure tap

2.0
1.0
Mid static pressure tap
Low static pressure tap Low static pressure tap
1.5
0.5

350 350

High static pressure tap 300


External static pressure (Pa)

External static pressure (Pa)


300
Mid static pressure tap
High static pressure tap
250 250
Mid static pressure tap

200 200

Low static pressure tap


150 150
Low static pressure tap

100 100

50 50

0 0
800 900 1000 1100 1200 1200 1400 1600 1800
Air volume (m3/h) Air volume (m3/h)

MMD-AP0961HFE (10HP)
Standard air volume: 2100m3/h
Fan motor current (A)

3.5
High static pressure tap
Mid static pressure tap
3.0

2.5

Low static pressure tap


2.0

350

300
External static pressure (Pa)

High static pressure tap

250

200
Mid static
pressure tap
150
Low static
pressure tap
100

50

0
1500 1700 1900 2100 2300
Air volume (m3/h)

11 -246
11 Technical Specifications

8. Sound characteristics (NC Curve)


Fresh Air Intake Indoor Unit Type

Measureing MMD-AP0481HFE
Fan tap H M L
Sound pressure
level (dB(A)) 45 43 41

Octave band sound pressure (dB)


Center
1.5m

Microphon

Audibility limits of
continuous white

MMD-AP0721HFE 63 125 250 500 1000 2000 4000 8000


MMD-AP0961HFE
Fan tap H M L Octave band center frequency (Hz)
Sound pressure
level (dB(A)) 46 45 44
Octave band sound pressure (dB)

Audibility limits of
continuous white

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

11 -247
11 Technical Specifications

11 -248
11 Technical Specifications
11 Technical Specifications

11-2-14. Console Type

Console Type

MML-AP0074NH-E
MML-AP0094NH-E
MML-AP0124NH-E
MML-AP0154NH-E
MML-AP0184NH-E

Contents
1. Specifications
2. Dimensions
3. Center of Gravity
4. Electrical characteristics
5. Sensible capacity table
6. Wiring diagram
7. Air throw distance chart
8. Sound characteristics (NC-Curve)
9. Accessories

11 -249
11 Technical Specifications

1. Specifications

Model name MML- AP0074NH-E AP0094NH-E AP0124NH-E AP0154NH-E AP0184NH-E

Cooling / Heating capacity (Note 1) (kW) 2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3

Power Supply 1 Phase 50Hz 230V (220-240V) (Separate power supply for indoor units is required.)

Electrical Running current (A) 0.20 0.20 0.23 0.29 0.42


Characteristics
Power consumption (kW) 0.021 0.021 0.025 0.034 0.052

Starting current (A) 0.26 0.26 0.30 0.38 0.55

Suction grille and side panel Moon white

Appearance Discharge-grille Moon white

Bottom surface Moon white

Height (mm) 600

Dimension Width (mm) 700

Depth (mm) 220

Total weight (kg) 17

Heat exchanger Finned tube

Soundproof / Heat-insulating material Foamed polystyrene , Polyethylene

Fan Turbo fan


Standard air flow
Fan unit (m3/h) 510/366/282 510/366/282 552/408/324 624/468/384 726/528/426
(High/Mid/Low)
Motor output (W) 41

Air filter Standard filter attached

Controller Wireless remote controller (packed with indoor unit)

Gas side (mm) Φ9.5 Φ12.7

Connecting pipe Liquid side (mm) Φ6.4

Drain port (Normal dia.) 16 (Polypropylene tube)


Sound pressure level (Note 2
(dB(A)) 38/32/26 38/32/26 40/34/29 43/37/31 47/40/34
(High/Mid/Low)
PMV Kit* Available*
Note 1䋺The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on the reference piping.
The reference piping consists of 5m of main piping and 2.5m of branch piping connected with 0 meter height.
Note 2䋺The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operaiting environment become larger than the indicated values due to the effects of external sound.
Note䋺Rated conditions䇭䇭䇭Cooling : Indoor air temperature 27㷄 DB/19㷄WB, Outdoor air temperature 35 㷄 DB
䇭䇭 Heating : Indoor air temperature 20 㷄 DB, Outdoor air temperature 7 㷄 DB/6㷄 WB
* : Mini-SMMS only

11 -250
11 Technical Specifications

2.Dimension
MML-AP0074NH-E, AP0094NH-E, AP0124NH-E, AP0154NH-E, AP0184NH-E

unit:mm

Dia. 80mm Connecting pipe


MML- AP0074 to AP0154 to
AP0124 type AP0184 type
Liquid side dia. 6.35 dia. 6.35
Gas side dia. 9.52 dia. 12.7
Back body Vertical louver (Upper air outlet)
Air inlet grille
Heat exchanger
Front panel Air filter

Air inlet
Air inlet Air inlet

Connecting pipe
Gas side

Connecting pipe
Liquid side

Dia. 80mm Dia. 80mm


Bottom air outlet
Knock out system
Knock out system
Mounting screw Mounting screw

Space required for


Dia. 80mm installation and servicing

Mounting plate
C B

Distance
A 300 or more
B 300 or more
Mounting screw C 300 or more

Dia. 80mm Dia. 80mm

Drain hose

Front View Back side View

11 -251
11 Technical Specifications

MML-AP0074NH-E, AP0094NH-E, AP0124NH-E, AP0154NH-E, AP0184NH-E

11 -252
11 Technical Specifications

4. Electrical characteristics

Nominal Voltage Voltage Range Fan Motor Power Supply


Type Model
(V-Ph-Hz) Min Max kW FLA MCA MOCP
MML-AP0074NH-E 230-1-50 198 264 0.041 0.21 0.26 15
MML-AP0094NH-E 230-1-50 198 264 0.041 0.21 0.26 15
50Hz Console Type MML-AP0124NH-E 230-1-50 198 264 0.041 0.25 0.31 15
MML-AP0154NH-E 230-1-50 198 264 0.041 0.32 0.40 15
MML-AP0184NH-E 230-1-50 198 264 0.041 0.46 0.58 15

MCA : Minimum Circuit Amps FLA : Full Load Amps


MOCP : Maximum Overcurrent Protection (Amps)

11 -253
11 Technical Specifications

5. Sensible capacity table


Console Type ( MML-AP***4NH-E )
TC 䋺 Total capacity [kW] SHC 䋺 Sensible capacity [kW]
Indoor air temp.
Outdoor
Unit 14.0CWB 16.0CWB 18.0CWB 19.0CWB 20.0CWB 22.0CWB 24.0CWB
air temp.
size 20CDB 23CDB 26CDB 27CDB 28CDB 30CDB 32CDB
CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
12.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
14.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
16.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
18.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
20.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
21.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
23.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
007
25.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
27.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
29.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
31.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
33.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
35.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6
37.0 1.7 1.5 1.9 1.6 2.1 1.7 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.6
39.0 1.7 1.4 1.9 1.5 2.0 1.6 2.1 1.6 2.1 1.6 2.3 1.6 2.4 1.5
10.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
12.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
14.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
16.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
18.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
20.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
21.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
23.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
009
25.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
27.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
29.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
31.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
33.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
35.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9
37.0 2.2 1.7 2.5 1.8 2.6 1.9 2.7 1.9 2.8 1.9 3.0 1.9 3.1 1.9
39.0 2.2 1.7 2.4 1.8 2.6 1.9 2.6 1.9 2.7 1.9 2.9 1.9 3.0 1.8
10.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
12.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
14.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
16.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
18.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
20.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
21.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
23.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
012
25.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
27.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
29.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
31.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
33.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
35.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
37.0 2.9 2.1 3.2 2.3 3.4 2.4 3.5 2.4 3.6 2.4 3.8 2.4 4.0 2.3
39.0 2.8 2.1 3.1 2.2 3.3 2.4 3.4 2.4 3.5 2.4 3.7 2.3 3.9 2.3

11 -254
11 Technical Specifications

㪌㪅㩷Sensible capacity table


Console Type ( MML-AP***4NH-E )
TC 䋺 Total capacity [kW] SHC 䋺 Sensible capacity [kW]
Indoor air temp.
Outdoor
Unit 14.0CWB 16.0CWB 18.0CWB 19.0CWB 20.0CWB 22.0CWB 24.0CWB
air temp.
size 20CDB 23CDB 26CDB 27CDB 28CDB 30CDB 32CDB
CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
12.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
14.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
16.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
18.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
20.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
21.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
23.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
015
25.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
27.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
29.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
31.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
33.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
35.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.1 5.1 3.0
37.0 3.6 2.7 4.0 2.8 4.2 3.0 4.4 3.0 4.5 3.0 4.7 3.0 5.0 2.9
39.0 3.5 2.6 3.8 2.8 4.1 2.9 4.2 2.9 4.4 2.9 4.6 2.9 4.8 2.8
10.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.7
12.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.7
14.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.7
16.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.7
18.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.7
20.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.7
21.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.7
23.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.7
018
25.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.7
27.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.7
29.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.7
31.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.7
33.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.7
35.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.7
37.0 4.5 3.3 4.9 3.5 5.3 3.7 5.4 3.7 5.6 3.7 5.9 3.6 6.2 3.6
39.0 4.3 3.2 4.8 3.4 5.1 3.6 5.3 3.6 5.4 3.6 5.7 3.5 6.0 3.5

11 -255
M MS M
6 5 U2 U1

1 2 3 4 5 6 1 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 1 2
1
U1
2
U2
1 A
U 2
1 3 B
DC20V
3
DC15V
DC12V 1
6.Wiring diagram

DC 7V 2
5 t°
3

CN71 (CHK)
1
11 Technical Specifications

CN72 (DISP) 2

1 2 3 1 2 3 4 5 1 2 3 4 5 6 7 8 9 10

1
Control P.C board for indoor unit 2

1 2 3 4 5
7
1

11 -256
2
L N 1 2 3 4 5 6 7 8 1 2 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 1 2
5
1 2 3 4 5 6

5 A B

1.Broken lines indicate the wiring on site. Long dashed


MML-AP0074NH-E, AP0094NH-E, AP0124NH-E, AP0154NH-E, AP0184NH-E

short dashed line indicate the accessories.


2. indicates the terminal block.
indicates the connection terminal.
indicates the connector on the control P.C. board.
3. indicates the protection ground.
4. indicates the control P.C. board.
11 Technical Specifications

7. Air throw distance chart


Console Type

MML-AP0074NH-E, AP0094NH-E

Cooling - Upper & Lower Cooling - Upper


2.5 2.5

0.5m/s
2.0 2.0
0.5m/s 1.0m/s
1.0m/s
1.5 1.5
Height [m]

Height [m]
1.5m/s

1.0 1.0

0.5 0.5

0.5m/s
0.0 0.0
0.0 0.5 1.0 1.5 2.0 2.5 0.0 0.5 1.0 1.5 2.0 2.5
Horizontal distance [m] Horizontal distance [m]

Heating - Upper & Lower Heating - Lower


2.5 2.5

0.5m/s
2.0 2.0

1.0m/s

1.5 1.5
Height [m]

Height [m]

1.0 1.0

0.5 0.5

0.5m/s
0.5m/s
1.0m/s
0.0 0.0
0.0 0.5 1.0 1.5 2.0 2.5 0.0 0.5 1.0 1.5 2.0 2.5
Horizontal distance [m] Horizontal distance [m]

11 -257
11 Technical Specifications

MML-AP0124NH-E

Cooling - Upper & Lower Cooling - Upper


2.5 㪉㪅㪌
0.5m/s

0.5m/s
2.0 㪉㪅㪇
1.0m/s
1.0m/s

1.5m/s
㪈㪅㪌

㪟㪼㫀㪾㪿㫋㩷㪲㫄㪴
1.5
Height [m]

1.0 㪈㪅㪇

0.5 㪇㪅㪌

0.5m/s
0.0 㪇㪅㪇
0.0 0.5 1.0 1.5 2.0 2.5 0.0 0.5 1.0 1.5 2.0 2.5
Horizontal distance [m] 㪟㫆㫉㫀㫑㫆㫅㫋㪸㫃㩷㪻㫀㫊㫋㪸㫅㪺㪼㩷㪲㫄㪴

Heating - Upper & Lower Heating - Lower


2.5 2.5

0.5m/s
2.0 2.0
1.0m/s

1.5 1.5
Height [m]

Height [m]

1.0 1.0

0.5 0.5
0.5m/s
0.5m/s
1.0m/s
0.0 0.0
0.0 0.5 1.0 1.5 2.0 2.5 0.0 0.5 1.0 1.5 2.0 2.5
Horizontal distance [m] Horizontal distance [m]

11 -258
11 Technical Specifications

MML-AP0154NH-E

Cooling - Upper & Lower Cooling - Upper


2.5 2.5
0.5m/s
0.5m/s 1.0m/s
2.0 2.0
1.0m/s
1.5m/s

1.5 1.5
Height [m]

Height [m]
1.0 1.0

0.5 0.5

0.5m/s
0.0 0.0
0.0 0.5 1.0 1.5 2.0 2.5 0.0 0.5 1.0 1.5 2.0 2.5
Horizontal distance [m] Horizontal distance [m]

Heating - Upper & Lower Heating - Lower


2.5 2.5
0.5m/s

2.0 1.0m/s 2.0

1.5 1.5
Height [m]

Height [m]

1.0 1.0

0.5 0.5

0.5m/s 0.5m/s
1.0m/s
0.0 0.0
0.0 0.5 1.0 1.5 2.0 2.5 0.0 0.5 1.0 1.5 2.0 2.5
Horizontal distance [m] Horizontal distance [m]

11 -259
11 Technical Specifications

MML-AP0184NH-E

Cooling - Upper & Lower Cooling - Upper


2.5 㪉㪅㪌
0.5m/s 0.5m/s
1.0m/s
1.0m/s 㪉㪅㪇
2.0
1.5m/s

㪈㪅㪌

Height [m]
1.5
Height [m]

1.5m/s

1.0 㪈㪅㪇

0.5 㪇㪅㪌

0.5m/s
0.0 㪇㪅㪇
0.0 0.5 1.0 1.5 2.0 2.5 0.0 0.5 1.0 1.5 2.0 2.5
Horizontal distance [m] Horizontal distance [m]

Heating - Upper & Lower Heating - Lower


2.5 2.5
0.5m/s

1.0m/s
2.0 2.0

1.5m/s
1.5 1.5
Height [m]

Height [m]

1.0 1.0

0.5 0.5
0.5m/s
㪇㪅㪌㫄㪆㫊
㪈㪅㪇㫄㪆㫊 1.0m/s
0.0 0.0
0.0 0.5 1.0 1.5 2.0 2.5 0.0 0.5 1.0 1.5 2.0 2.5
Horizontal distance [m] Horizontal distance [m]

11 -260
11 Technical Specifications

8. Sound Characteristics (NC-Curve)


Console Type

Microphone

Unit
1m 1m

Floor

MML-AP0074NH-E/AP0094NH-E MML-AP0124NH-E
Fan tap H M L Fan tap H M L
Sound pressure Sound pressure
38 32 26 40 34 29
level (dB(A)) level (dB(A))

90 90
䇭 䂥䇭 H 䇭 䂥䇭 H
䇭 䂓䇭 M 䇭 䂓䇭 M
80 䇭 䃂䇭 L 80 䇭 䃂䇭 L
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

70 NC-70
70 NC-70

60 60
NC-60 NC-60

50 NC-50
50 NC-50

40 40
NC-40 NC-40

30 NC-30
30 NC-30

20 Approximate threshold of 20 Approximate threshold of


NC-20 NC-20
hearing for continuous noise hearing for continuous noise

10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

MML-AP0154NH-E MML-AP0184NH-E
Fan tap H M L Fan tap H M L
Sound pressure Sound pressure
43 37 31 47 40 34
level (dB(A)) level (dB(A))

90 90
䇭 䂥䇭 H 䇭 䂥䇭 H
䇭 䂓䇭 M 䇭 䂓䇭 M
80 䇭 䃂䇭 L 80 䇭 䃂䇭 L
Octave band sound pressure level (dB)

Octave band sound pressure level (dB)

70 NC-70 70 NC-70

60 60
NC-60 NC-60

50 NC-50
50 NC-50

40 40
NC-40 NC-40

30 NC-30
30 NC-30

20 Approximate threshold of 20 Approximate threshold of


NC-20 NC-20
hearing for continuous noise hearing for continuous noise

10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

11 -261
11 Technical Specifications

9. Accessories
Remote controller

Packed with the indoor unit


Model
Name Appearance Application Function
name
• Start / Stop
• Changing mode
• Temperature setting
Wireless remote controller

• Air flow changing (5 steps)


• Louver setting
• Clock
WH-L11SE

• Timer function
- ON/OFF timer (10 min. step)
- Everyday timer
- Sleep timer
- COMFORT SLEEP timer
• High power mode
• QUIET mode
• One-touch pre-set memory
• One-touch Auto (*1)

(*1) Super MMS-i cannot accept “AUTO” mode, Super HRM can accept “AUTO” mode.

11 -262
11 Technical Specifications
11 Technical Specifications

11-2-15. Air to Air Heat Exchanger with DX-coil Type

Air to Air Heat exchanger


with DX-coil Type

MMD-VN502HEXE
MMD-VN802HEXE
MMD-VN1002HEXE

Contents
1. Specifications
2. Dimension
3. Wiring Diagram
4. Exchange Efficiency Correction
5. Sensible Capacity Table
6. Fan Characteristics
7. Sound Characteristics (NC Curve)
8. Electrical characteristics

11 -263
11 Technical Specifications

1. Specifications
(50Hz)
Model name MMD-VN502HEXE MMD-VN802HEXE MMD-VN1002HEXE
Fresh air conditioning Cooling (* 1 ) kW 4.10 (1.30) 6. 56 (2. 06) 8.25 (2.32)
load Heating (* 1 ) kW 5.53 (2.33) 8. 61 (3. 61) 10.92 (4.32)
1phase 50Hz 230V (220V-240V)
Power supply
(Separate power supply for indoor units is required.)
Extra High % 70.5 70. 0 65. 5
Temperature exchange efficiency High % 70.5 70. 0 65. 5
Lo w % 71.5 72. 5 67. 5
Extra High % 56.5 56. 0 52. 0
Cooling High % 56.5 56. 0 52. 0
Enthalpy exchange Lo w % 57.5 59. 0 54. 0
efficiency Extra High % 68.5 70. 0 66. 0
Heating High % 68.5 70. 0 66. 0
Lo w % 69.0 73. 0 68. 5
Extra High kW 0. 300 0.505 0.550
Power input (Heat exchange mode) High kW 0. 280 0.465 0.545
Lo w kW 0. 235 0.335 0.485
Extra High A 1.30 2. 25 2. 46
Running current High A 1.21 2. 07 2. 43
Lo w A 1.01 1. 46 2. 16
Extra High m3/h 500 800 950
Standard air flow High m3/h 500 800 950
Low m3/h 440 640 820
Extra High Pa 120 120 135
Fan unit External static
High Pa 105 100 120
pressure
Lo w Pa 115 100 105
Lower limit m3/h 330 480 640
Air flow limit
Upper limit m3/h 600 960 1140
Extra High dB 37.5 41. 0 43. 0
Sound pressure High dB 36.5 40. 0 42. 0
Lo w dB 34.5 38. 0 40. 0
Appearance Zinc hot dipping steel plate
Height mm 430 430 430
Outer dimension Width mm 1140 1189 1189
Depth mm 1690 1739 1739
Total weight kg 84 100 101
Heat exchanger Finned tube
Heat-insulating material Flexible urethane foam
Standard filter (Gravitational method 82%)
Air filter
& High efficiency filter (Colorimetric method 65%)
Controller Remote controller (Separately sold parts)
G a s si d e mm Ø 9. 5 Ø 12. 7 Ø 12. 7
Connecting piping
Liquid side mm Ø 6. 4 Ø6.4 Ø6.4
Drain port (Nominal dia. mm) 25 (Polyvinyl chloride tube)

(*1) Cooling and heating capacities are based on the following conditions:
Cooling capacities are based on: indoor temperature: 27 °CDB/19°CWB, Outdoor temperature: 35°CDB
Heating capacities are based on: indoor temperature: 20°CDB, Outdoor temperature: 7 °CDB/6°CWB
Fan is based on Extra High and High
( ): The figures in ( ) indicate the heat reclaimed from the heat recovery ventilator.
When calculating the capacity code as indoor units, please use as below.
MMD-VN502HEXE: 1HP, MMD-VN802HEXE: 1.7HP,
MMD-VN1002HEXE: 2.0HP

11 -264
11 Technical Specifications

1. Dimension

MMD-VN502HEXE

Attention
1. Duct size (Nominal diameter): ø200
2. The above dimensions do not include
the thickness of the insulation material
on the unit body.

11 -265
11 Technical Specifications

MMD-VN802HEXE

Attention
1. Duct size (Nominal diameter): ø250
2. The above dimensions do not include
the thickness of the insulation material
on the unit body.

11 -266
11 Technical Specifications

MMD-VN1002HEXE

Attention
1. Duct size (Nominal diameter): ø250
2. The above dimensions do not include
the thickness of the insulation material
on the unit body.

11 -267
11 Technical Specifications

3. Wiring Diagram

MMD-VN502HEXE, MMD-VN802HEXE, MMD-VN1002HEXE

Code Parts name Code Parts name


CN*** Connector TB1 Terminal block (Power source)
F01 Fuse (Printed circuit board) TB2 Terminal block (Communication)
F02 Fuse (Motor) TB3 Terminal block (External output)
FM1 Air supplying motor TS1 Float switch
FM2 Air exhausting motor PMV Pulse modulating value
DAM Damper motor SW701 Dip switch
TRA TRA sensor 43F11, 43F12 Relay for air supplying motor
TOA TOA sensor 43F21, 43F22 Relay for air exhausting motor
TSA TSA sensor RY701, RY702 Relay for air supplying motor
TFA TFA sensor RY704, RY705 Relay for air exhausting motor
TCJ, TC1, TC2 Indoor coil sensor

1. The dotted line represents a wire procured locally, and the dashed line represents an option sold separately.
2. represents a terminal block, represents a connection terminal, represents a connector on the printed circuit board and represents a short circuit connector.
3. represents a protective earth.
4. represents a printed circuit board.
5. Using a no voltage a-contact input of the external input (option), the following operations are available.
Between 1 and 2: Selecting the remote controller operation (Invalid/Valid)
Between 1 and 3: Adjusting the fan speed (Low/High)
Between 1 and 5: Operation (ON/OFF)
Use a microcurrent contact (DC12V, 1mA). In addition, ON/OFF operation is possible when using a voltage of DC12V or 24V.
6. Orange wire (High) is connected as factory default. To switch to “Extra High”, connect black wire’s connector instead of orange.

11 -268
11 Technical Specifications

4. Exchange Efficiency Correction

Exchange efficiency correction when supply air volume and exhaust air volume are different

Exchange efficiency correction curve


Exhaust to supply ratio Exhaust air volume / Supply air volume
Exchange efficiency based on supply air volume [%]

0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.31.41.5


90

80

70

60

50

40
40 50 60 70 80 90 100

Corrected exchange effciency [%]

correction curve corresponding


efficiency based on
supply air volume to use condition

Enthal
p
efficien y exchange
Tem cy (hea
excha perature ting)
nge e
fficien
cy

Enthal
p
efficien y exchange
cy (co
oling)
Exchange efficiency

Air flow supply air volume


corrected efficiency

11 -269
11 Technical Specifications

5. Sensible Capacity Table


Cooling capacity tables
TC: Total Capacity [kW] SHC: Sensible Heat Capacity [kW]
MMD-VN ***HEXE
DX-coil DX-coil inlet temp. [°CWB]
Outdoor temp.
Class capacity 16.0 18.0 19.0 20.0 22.0 24.0
[°CDB]
[kW] TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 2.5 1.7 2.7 1.8 2.8 1.8 2.9 1.8 3.0 1.8 3.2 1.8
12.0 2.5 1.7 2.7 1.8 2.8 1.8 2.9 1.8 3.0 1.8 3.2 1.8
14.0 2.5 1.7 2.7 1.8 2.8 1.8 2.9 1.8 3.0 1.8 3.2 1.8
16.0 2.5 1.7 2.7 1.8 2.8 1.8 2.9 1.8 3.0 1.8 3.2 1.8
18.0 2.5 1.7 2.7 1.8 2.8 1.8 2.9 1.8 3.0 1.8 3.2 1.8
20.0 2.5 1.7 2.7 1.8 2.8 1.8 2.9 1.8 3.0 1.8 3.2 1.8
21.0 2.5 1.7 2.7 1.8 2.8 1.8 2.9 1.8 3.0 1.8 3.2 1.8
23.0 2.5 1.7 2.7 1.8 2.8 1.8 2.9 1.8 3.0 1.8 3.2 1.8
502 2.8
25.0 2.5 1.7 2.7 1.8 2.8 1.8 2.9 1.8 3.0 1.8 3.2 1.8
27.0 2.5 1.7 2.7 1.8 2.8 1.8 2.9 1.8 3.0 1.8 3.2 1.8
29.0 2.5 1.7 2.7 1.8 2.8 1.8 2.9 1.8 3.0 1.8 3.2 1.8
31.0 2.5 1.7 2.7 1.8 2.8 1.8 2.9 1.8 3.0 1.8 3.2 1.8
33.0 2.5 1.7 2.7 1.8 2.8 1.8 2.9 1.8 3.0 1.8 3.2 1.8
35.0 2.5 1.7 2.7 1.8 2.8 1.8 2.9 1.8 3.0 1.8 3.2 1.8
37.0 2.5 1.7 2.7 1.8 2.8 1.8 2.9 1.8 3.0 1.8 3.2 1.7
39.0 2.4 1.7 2.6 1.8 2.7 1.8 2.8 1.8 2.9 1.8 3.1 1.7
10.0 4.1 2.8 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
12.0 4.1 2.8 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
14.0 4.1 2.8 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
16.0 4.1 2.8 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
18.0 4.1 2.8 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
20.0 4.1 2.8 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
21.0 4.1 2.8 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
23.0 4.1 2.8 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
802 4.5
25.0 4.1 2.8 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
27.0 4.1 2.8 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
29.0 4.1 2.8 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
31.0 4.1 2.8 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
33.0 4.1 2.8 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
35.0 4.1 2.8 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
37.0 4.0 2.7 4.3 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8
39.0 3.9 2.7 4.2 2.8 4.4 2.8 4.5 2.9 4.7 2.8 5.0 2.7
10.0 5.3 3.7 5.7 4.0 5.9 4.0 6.1 4.0 6.4 3.9 6.8 3.8
12.0 5.3 3.7 5.7 4.0 5.9 4.0 6.1 4.0 6.4 3.9 6.8 3.8
14.0 5.3 3.7 5.7 4.0 5.9 4.0 6.1 4.0 6.4 3.9 6.8 3.8
16.0 5.3 3.7 5.7 4.0 5.9 4.0 6.1 4.0 6.4 3.9 6.8 3.8
18.0 5.3 3.7 5.7 4.0 5.9 4.0 6.1 4.0 6.4 3.9 6.8 3.8
20.0 5.3 3.7 5.7 4.0 5.9 4.0 6.1 4.0 6.4 3.9 6.8 3.8
21.0 5.3 3.7 5.7 4.0 5.9 4.0 6.1 4.0 6.4 3.9 6.8 3.8
23.0 5.3 3.7 5.7 4.0 5.9 4.0 6.1 4.0 6.4 3.9 6.8 3.8
1002 5.93
25.0 5.3 3.7 5.7 4.0 5.9 4.0 6.1 4.0 6.4 3.9 6.8 3.8
27.0 5.3 3.7 5.7 4.0 5.9 4.0 6.1 4.0 6.4 3.9 6.8 3.8
29.0 5.3 3.7 5.7 4.0 5.9 4.0 6.1 4.0 6.4 3.9 6.8 3.8
31.0 5.3 3.7 5.7 4.0 5.9 4.0 6.1 4.0 6.4 3.9 6.8 3.8
33.0 5.3 3.7 5.7 4.0 5.9 4.0 6.1 4.0 6.4 3.9 6.8 3.8
35.0 5.3 3.7 5.7 4.0 5.9 4.0 6.1 4.0 6.4 3.9 6.8 3.8
37.0 5.3 3.7 5.7 3.9 5.9 3.9 6.1 3.9 6.4 3.9 6.7 3.8
39.0 5.2 3.6 5.6 3.8 5.7 3.8 5.9 3.8 6.2 3.8 6.5 3.7

11 -270
11 Technical Specifications

Heating capacity tables


TC: Total Capacity [kW] SHC: Sensible Heat Capacity [kW]
MMD-VN ***HEXE
DX-coil DX-coil inlet temp. [°CDB]
Outdoor temp.
Class capacity 16.0 18.0 20.0 22.0 24.0
[°CWB]
[kW] SHC SHC SHC SHC SHC
–15.0 1.9 1.8 1.8 1.8 1.7
–13.0 2.0 2.0 2.0 1.9 1.9
–11.0 2.2 2.1 2.1 2.0 2.0
–10.0 2.2 2.2 2.2 2.1 2.1
–8.0 2.4 2.3 2.3 2.2 2.2
–6.0 2.5 2.4 2.4 2.3 2.3
–4.0 2.5 2.4 2.3 2.3 2.2
–2.0 2.5 2.5 2.4 2.4 2.3
502 3.2
0.0 2.6 2.7 2.6 2.5 2.5
2.0 2.8 2.8 2.7 2.6 2.6
4.0 3.2 3.1 3.0 3.0 2.9
6.0 3.3 3.3 3.2 3.1 3.0
8.0 3.3 3.3 3.2 3.1 3.0
10.0 3.3 3.3 3.2 3.1 3.0
12.0 3.3 3.3 3.2 3.1 3.0
14.0 3.3 3.3 3.2 3.1 3.0
–15.0 2.8 2.8 2.7 2.6 2.6
–13.0 3.0 3.0 2.9 2.9 2.8
–11.0 3.3 3.2 3.1 3.1 3.0
–10.0 3.4 3.3 3.2 3.2 3.1
–8.0 3.6 3.5 3.4 3.3 3.3
–6.0 3.7 3.6 3.6 3.5 3.4
–4.0 3.7 3.5 3.5 3.4 3.3
–2.0 3.8 3.7 3.6 3.5 3.4
802 4.8
0.0 3.9 4.0 3.9 3.8 3.7
2.0 4.2 4.1 4.1 4.0 3.9
4.0 4.7 4.7 4.6 4.5 4.3
6.0 5.0 4.9 4.8 4.7 4.6
8.0 5.0 4.9 4.8 4.7 4.6
10.0 5.0 4.9 4.8 4.7 4.6
12.0 5.0 4.9 4.8 4.7 4.6
14.0 5.0 4.9 4.8 4.7 4.6
–15.0 3.9 3.8 3.7 3.6 3.5
–13.0 4.2 4.1 4.0 3.9 3.8
–11.0 4.5 4.4 4.3 4.2 4.1
–10.0 4.6 4.5 4.4 4.3 4.2
–8.0 4.9 4.8 4.7 4.6 4.5
–6.0 5.1 5.0 4.9 4.8 4.6
–4.0 5.1 4.9 4.8 4.7 4.5
–2.0 5.2 5.1 5.0 4.9 4.7
1002 6.6
0.0 5.4 5.5 5.4 5.2 5.1
2.0 5.8 5.7 5.6 5.4 5.3
4.0 6.5 6.4 6.3 6.1 6.0
6.0 6.9 6.7 6.6 6.4 6.3
8.0 6.9 6.7 6.6 6.4 6.3
10.0 6.9 6.7 6.6 6.4 6.3
12.0 6.9 6.7 6.6 6.4 6.3
14.0 6.9 6.7 6.6 6.4 6.3

11 -271
11 Technical Specifications

6. Fan Characteristics
– – – – – – 230V, 50Hz

MMD-VN502HEXE MMD-VN802HEXE
3 3
Standard air voleme : 500m /h Standard air voleme : 800m /h
Lower limit air volume : 330m /h, Upper limit air volume : 600m3/h
3
Lower limit air volume : 480m3/h, Upper limit air volume : 960m3/h

400 80 400 80
En
th
effic alpy

Exchange efficiency [%]


Exchange efficiency [%]
Tempera ien exch
exchange ture cy
efficiency (he ange
T atin
exc em g)
350 70 350 han pera 70
ge tu
Enthalpy effic re
exchange ien
efficiency cy
(heating)

300 60 300 En 60
th
effic alpy
Enthalpy ex ien exch
cy
efficiency
change (co ange
olin
External static pressure [Pa]

External static pressure [Pa]


(cooling) g)
250 50 250 50

Extra High
Extra High
200 40 200 40

High
Low High Low
150 30 150 30

100 20 100 20

50 10 50 10

0 0 0 0
0 100 200 300 400 500 600 700 0 200 400 600 800 1,000
Air flow [m3/h] Air flow [m3/h]

MMD-VN1002HEXE
3
Standard air voleme : 950m /h
Lower limit air volume : 640m 3/h, Upper limit air volume : 1140m3/h

400 80
Exchange efficiency [%]

Ent
h
effic alpy
ien exch
cy
350 (he ange 70
atin
g)
exc Temp
han era
ge tu
effic re
300 ien
cy
60
External static pressure [Pa]

En
th
effic alpy
250 ien exch 50
cy
(co ange
olin
g)

Extra High
200 40

Low

150 30

High

100 20

50 10

0 0
0 200 400 600 800 1,000 1,200
Air flow [m3/h]

11 -272
11 Technical Specifications

( )

Sound pressure level (dB)


Model name Power supply (phase/Hz/V)
Extra High High Low

MMD-VN502HEXE Under from body 1.5m 37.5 36.5 34.5

MMD-VN802HEXE 1 phase / 50Hz / 220V-240V 41.0 40.0 38.0

1.5m
MMD-VN1002HEXE 43.0 42.0 40.0
Measuring point

MMD-VN502HEXE MMD-VN802HEXE
90 90
Extra High Extra High
High High
80 Low 80 Low

Octave band sound pressure level (dB)


Octave band sound pressure level (dB)

70 70
NC-70 NC-70

NC-65 NC-65
60 60
NC-60 NC-60

NC-55 NC-55
50 50
NC-50 NC-50

NC-45 NC-45
40 40
NC-40 NC-40

NC-35 NC-35
30 30
NC-30 NC-30

NC-25 NC-25
20 20
NC-20 NC-20

NC-15 NC-15
10 10

0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

MMD-VN1002HEXE
90
Extra High
High
80 Low
Octave band sound pressure level (dB)

70
NC-70

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

NC-25
20
NC-20

NC-15
10

11 -273
11 Technical Specifications

Sound pressure level (dB)


Model name Power supply (phase/Hz/V)
Extra High High Low

MMD-VN502HEXE 39.5 39.0 37.0


SA

MMD-VN802HEXE 1 phase / 50Hz / 220V-240V 45° 44.5 44.5 40.5


1.5m
Measuring point
MMD-VN1002HEXE 47.0 47.0 45.0

MMD-VN502HEXE MMD-VN802HEXE
90 90
Extra High Extra High
High High
Low 80 Low
80

Octave band sound pressure level (dB)


Octave band sound pressure level (dB)

70 70
NC-70 NC-70

NC-65 NC-65
60 60
NC-60 NC-60

NC-55 NC-55
50 50
NC-50 NC-50

NC-45 NC-45
40 40
NC-40 NC-40

NC-35 NC-35
30 30
NC-30 NC-30

NC-25 NC-25
20 20
NC-20 NC-20

NC-15 NC-15
10 10

0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz) Octabe band center frequency (Hz)

MMD-VN1002HEXE
90
Extra High
High
80 Low
Octave band sound pressure level (dB)

70
NC-70

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

NC-25
20
NC-20

NC-15
10

0
63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)

11 -274
11 Technical Specifications

7. Sound Characteristics (NC Curve)

Sound pressure level (dB)


Model name Power supply (phase/Hz/V)
Extra High High Low

MMD-VN502HEXE Under from body 1.5m 37.5 36.5 34.5

MMD-VN802HEXE 1 phase / 50Hz / 220V-240V 41.0 40.0 38.0

1.5m
MMD-VN1002HEXE 43.0 42.0 40.0
Measuring point

MMD-VN502HEXE MMD-VN802HEXE
90 90
Extra High Extra High
High High
80 Low 80 Low

Octave band sound pressure level (dB)


Octave band sound pressure level (dB)

70 70
NC-70 NC-70

NC-65 NC-65
60 60
NC-60 NC-60

NC-55 NC-55
50 50
NC-50 NC-50

NC-45 NC-45
40 40
NC-40 NC-40

NC-35 NC-35
30 30
NC-30 NC-30

NC-25 NC-25
20 20
NC-20 NC-20

NC-15 NC-15
10 10

0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

MMD-VN1002HEXE
90
Extra High
High
80 Low
Octave band sound pressure level (dB)

70
NC-70

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

NC-25
20
NC-20

NC-15
10

11 -275
11 Technical Specifications

Sound pressure level (dB)


Model name Power supply (phase/Hz/V)
Extra High High Low

MMD-VN502HEXE 39.5 39.0 37.0


SA

MMD-VN802HEXE 1 phase / 50Hz / 220V-240V 45° 44.5 44.5 40.5


1.5m
Measuring point
MMD-VN1002HEXE 47.0 47.0 45.0

MMD-VN502HEXE MMD-VN802HEXE
90 90
Extra High Extra High
High High
Low 80 Low
80

Octave band sound pressure level (dB)


Octave band sound pressure level (dB)

70 70
NC-70 NC-70

NC-65 NC-65
60 60
NC-60 NC-60

NC-55 NC-55
50 50
NC-50 NC-50

NC-45 NC-45
40 40
NC-40 NC-40

NC-35 NC-35
30 30
NC-30 NC-30

NC-25 NC-25
20 20
NC-20 NC-20

NC-15 NC-15
10 10

0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz) Octabe band center frequency (Hz)

MMD-VN1002HEXE
90
Extra High
High
80 Low
Octave band sound pressure level (dB)

70
NC-70

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

NC-25
20
NC-20

NC-15
10

0
63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)

11 -276
11 Technical Specifications

8. Electrical characteristics

Nominal Voltage Voltage Range Fan Motor Power Supply


Type Model
(V-Ph-Hz) Min Max kW FLA MCA MOCP
Air to Air Heat MMD-VN502HEXE 230-1-50 198 264 0.124 x 2 1.5 1.7 15
Exchanger with MMD-VN802HEXE 230-1-50 198 264 0.217 x 2 2.6 3.0 15
DX-coil MMD-VN1002HEXE 230-1-50 198 264 0.284 x 2 2.9 3.5 15

㪤㪚㪘 㪑㩷㪤㫀㫅㫀㫄㫌㫄㩷㪚㫀㫉㪺㫌㫀㫋㩷㪘㫄㫇㫊 㩷㪝㪣㪘 㪑㩷㪝㫌㫃㫃㩷㪣㫆㪸㪻㩷㪘㫄㫇㫊


㪤㪦㪚㪧 㪑㩷㪤㪸㫏㫀㫄㫌㫄㩷㪦㫍㪼㫉㪺㫌㫉㫉㪼㫅㫋㩷㪧㫉㫆㫋㪼㪺㫋㫀㫆㫅㩷㩿㪘㫄㫇㫊㪀

11 -277
Ovlašćeni Toshiba distributer:

KOVENT
Kumanovska 14, 11000 Beograd
Tel.:011 308 57 40
Faks 011 344 41 13
E-mail: office@kovent.rs
www.kovent.rs

Kumanovska 14, 11000 Beograd, Srbija


Tel.: 011 383 68 86, 308 57 40
Faks: 011 344 41 13
E-mail: gobrid@eunet.rs
www.airtrend.rs
www.toshiba-klima.rs • www.toshiba-estia.rs

SMMS i Engineering Data


< Full set version, without appendix >

Second Edition
Subject to misprinting. Second Edition, printed Feb. 2012

Vous aimerez peut-être aussi