33 kV Incoming Switchgear ( Indoor ) Specification

Sr
Material Specification
No
1 33 kV Incoming Switchgear ( Indoor )
1 33kV Incoming Switchgear ( Indoor type ), SCADA Compatible
( SF6 Gas Circuit Breaker ) ( Withdrawable Type )
(a) SF6 Switchgear
Maker To State
Country of Origin To State
Standard IEC 62271-100
Type To State
Normal Voltage 33 kV
Rated Voltage 36kV
Rated Normal Current 1600 A
Rated Short-Circuit Breaking Current 31.5kA , rms
Operating sequence O-0.3s-CO-3min- CO
Rated Power Frenquency withstand voltage 70 kV
Rated Lightning Impulse withstand voltage 170 kV
Closing & Tripping Control Voltage 110V DC
Spring Charge Motor Voltage 230V AC
(b) Enclosure To Include
Maker Same Manufacturer with Circuit Breaker
Country of Origin To State
Standard IEC 62271-100
Sheet Thickness ≥ 2 mm
Coating Colour To State
Coating Thickness 50 - 86 µ
(c) Discrepency Switch for GCB & DS To Include
Maker To State
Country of Origin To State
Type To State
Interlock facility for DS To Include
(d) Annunciators Lamp To Include
(Including Low Gas Pressure, Alarm Lockout for GCB)
Maker To State
Country of Origin To State
Type To State
No. of Window 16 Window
Position indicator for CB, DS, ES ON/OFF Position To Include
Bell for Trip, Buzzer for alarm To Include
Master Trip Relay with Reset button (86) To Include
(e) Ammeter Meter ( with Selector Switch) To Include
Maker To State
Country of Origin To State
Type To State
Class To State
(f) Volt Meter ( with Selector Switch) To Include 33 Incoming GCB
33 kV Incoming Switchgear ( Indoor ) Specification
Sr
Material Specification
No
Maker To State
Country of Origin To State
Type To State
Class To State
(g) Three Phase Digital Multi Function Meter To Include
Maker Elite,Socomec
Country of Origin To State
Type Panel Mounted Digital
To Read V, A, Hz, CosØ, MW, MVA, Mvar, etc. Must be
VT ratio and CT ratio must be programmed. Must be
Day light reading Liquid Crystal Display Must be
Com: Port: RS 485 and Etrernet comply to IEC 61850 Must be
Operating Voltage = 110 Vac Must be
Rated Input Voltage = 110 Vac Must be
Rated Input Current = 5 A Must be
Rated Input Frequency = 50 Hz Must be
Accuracy Class (0.5) Must be
(h) KWh Meter (3 Ph, 3Wire, 110V, 5A) (With GPRS/GSM Modem) To Include
Maker CEWE,Landis & Gyr,EMH,Elster,Itron,Siemens
Country of Origin USA , Europe
Type Panel Mounted Digital
Standard IEC- 62052, IEC-62053, IEC- 62056
Rated Input Voltage 110V AC (L-L)
Rated Input Current 1A and 5A
Rated Frequency 50 Hz ±5%
Accuracy Class 0.5S
Operating Voltage 110V AC (L-L) or Self Powered
Power Factor ZeroLag ↔ Unity ↔ Zero Lead
Display Day light reading Liquid Crystal Display
(or) LED Display
Direction of Energy Bidirectional (±Wh)
Communication Interface RS 485 and Ethernet
Burden
- Voltage Circuit (per Phase) < 1W , < 6VA
- Current Circuit (per Phase) < 1VA
VT ratio and CT ratio must be programmed. Must be
KWh Meters must be products for medium & High Voltage System Must be

(i) Combine Directional Three Phase Overcurrent To Include


& Earth Fault Relay
ABB (Relion), REF615LBFFAEAGCB
Alstom (Micom),P14DL16J7D0610A
Maker
Siemens (Siprotec),7SJ64555EB923LOR
Schneider (Micom) ,P127BA2Z512FE1 33 Incoming GCB
33 kV Incoming Switchgear ( Indoor ) Specification
Sr
Material Specification
No
Country of Origin To State
Nominal Frequency 50 Hz
Nominal Current (In) 1A and 5A
Earth Nominal Current 1A and 5A
Continuous withstand Current 4In and 40In(2s),100In(1s)
Voltage Input Range (Un) 57 to 130 V
Voltage Measuring range 0 to 260 V
Nominal Auxiliary Voltage 24 - 250V DC / 24 - 250V AC
Protection Functions
Phase Overcurrent
- Range 0.1 to 40 In
- Setting step 0.01 Im
- Stages I> , I>> , I>>>
- Directional Mode
- RCA 0 to 359
- Trip Relay Time DT for tI>,tI>>,tI>>>
IDMT: I>,I>> , TMS: 0.025 to 1.5
Earth Fault Overcurrent
- Range 0.1 to 40 Ine
- Setting step 0.01 Ien
- Stages Ie> , Ie>> , Ie>>>,Ie>>>>
- Directional Mode
- RCA 0 to 359
- Trip Relay Time DT for tIe>,tIe>>,tIe>>>
IDMT: I>,I>> , TMS: 0.025 to 1.5
Output Relay
- Make Current Max: 30A and carry ofr 3s
- Carry Capacity 5A Continuous
- Braking Capacity DC 250V DC , 50W resistive or 25W Inductive
(L/R = 40 ms)
- Operation time < 7 ms
Logic Inputs
- Type Optically insulated
- Burden 2.3mA per input
- Recognition time (DC) < 5ms

Communication Interface
PC Interface (front RS 232)
- Transmission rate 19200 baud (fixed)
- Parity None
- Frame 8 Bit
- Stop bit 1 Bit
Remote Accesssories (rear RS 485 port)
- Protocal available Modbus RTU, DNP3 & IEC 60870-5-103 33 Incoming GCB
33 kV Incoming Switchgear ( Indoor ) Specification
Sr
Material Specification
No
Optional RS 485 Port Protocol available Modbus
Negstive sequence (46) Must be
Thermal overload element (49) Must be
Three Phase undercurrent (37) Must be
Phase/Line under Voltage (27) Must be
Phase/Line over Voltage (59) Must be
Residual over voltage (59N) Must be
Auto reclose (79) Must be
Under / Over frequency (81U/O ) Must be
Directional power (32) Must be
Configuration Parameters
- VT Connection Must be
- Display Must be
Transformer Ratio
Phase CTs & Earth CTs
- Primary 0 to 9999 A
- Secondary 1A or 5A
Phase Voltage VTs & Residual Voltage VTs
- Primary nominal (phase to phase) 0.10 to 1000kV
- Secondary 57 or 130A
(j) Differential Relay To Include
Maker To State
Country of Origin Europe
-Type To State
-Rated current In 1A -5A
-Thermal crt withstand 4A 20A
-Dynamic Crt withstand 250A 1250A
-Input impedance <100mΏ <20mΏ
-Rated frequency 50HZ
-Rated voltage 250 V ac/dc
-Basic start ratio P/In 5....50%
-Starting ratio setting S 10...50%
-Harmonic blocking ratio 7....20%
-Operation accuracy ±4% of set value
Relay Commnication Com Port: Glass Fiber Optics
For SCADA Compatible,IEC 61850
Human Machine Interface
for Programming the Relay
Software to be provided.
(k) Control Voltage 110 Vdc
(l) Drawing (Circuit, Dimention) To State
(m) 33kV Voltage Transformer (33/rt3,.11/rt3,.11/3)kV, 3 N
Maker To State
Country of Origin To State 33 Incoming GCB
33 kV Incoming Switchgear ( Indoor ) Specification
Sr
Material Specification
No
Standard IEC 60994
Type Dry Type
Normal Voltage 33 kV
Rated Voltage 36 kV
Rated Power Frenquency withstand voltage 70 kV
Rated Lightning Impulse withstand voltage 170 kV
Rated Power Frenquency withstand voltage 3 kV
Secondary Winding
Voltage Ratio
-Primary 33/ √3 kV
-Secondary (1) 110/ √3 V
-Secondary (2) 110/ 3 V
Rated Output Burden 100 VA,100 VA
Accuracy Class CL 0.5, 3P
(n) 33kV Current Transformer (200-400/5/5/5A) 3 N
Maker To State
Country of Origin To State
Standard IEC 60994
Type Dry Type
Normal Voltage 33 kV
Rated Voltage 36 kV
Short time withstand Crt 31.5 kA,3 Sec
Rated Power Frenquency withstand voltage 70 kV
Rated Lightning Impulse withstand voltage 170 kV
Rated Power Frenquency withstand voltage 3 kV
Secondary Winding
CT Ratio 200-400/5/5/5A
Burden 30 VA
Accuracy Class 0.5 CL/ 5P 10/5P10
(o) 33kV Lightning Arrestor (MCOV-24kV) 3 N
Maker To State
Country of Origin To State
Standard IEC
Type To State
Normal Voltage 33 kV
Rated Voltage 36 kV
Maximum Continuous Operating Voltage 24 kV
Discharge Current 10 kA
1.2/50 µ Sec Impulse Withstand Voltage 70 kV
Frequency 50 HZ
(p) Copper Busbar To Include
Maker To State
Country of Origin To State
Rated Voltage 36kV 33 Incoming GCB
33 kV Incoming Switchgear ( Indoor ) Specification
Sr
Material Specification
No
Rated Current 2000 A
Short time withstand Crt 31.5kA,3 Sec
Long 2 Meter
Width 80 mm
Thickness 10 mm
Include Type Test Reports as per IEC 62271-201(Type test for Circuit Breaker with Enclosure)
1. Short Time Withstand Current & Peak Current withstand Test To Include
2. Lightning Impulse Voltage withstand Test To Include
3. Short Circuit Making & Breaking Test To Include
4. Power Frequency Withstand Voltage Test To Include
5. Temperature rise Test To Include
6. Mechanical Endurance Test To Include
7. Capacitive Current Switching Test To Include
8. Measurement of resistance of the main circuit To Include

33 Incoming GCB
Unit Qty

33 Incoming GCB
Unit Qty

33 Incoming GCB
Unit Qty

33 Incoming GCB
Unit Qty

Nos.

33 Incoming GCB
Unit Qty

Nos.

Nos.

33 Incoming GCB
Unit Qty

33 Incoming GCB