Académique Documents
Professionnel Documents
Culture Documents
for
Steel Structures
1. Introduction ............................................................................................................. 1
4. Conclusions ............................................................................................................. 4
5. References ............................................................................................................... 4
1.1 Code of Practice for Structural Use of Steel 2011 (the “Code”) published by Buildings
Department clause 6.3.2 on the elastic critical load factor, λcr, has been revised to clarify
the determination of λcr by the deflection method. However, there had not been any
elaboration on the use of the eigenvalue analysis method though the correct
determination of λcr is a critical step in the design and analysis of steel structures.
a) to summarize the available methods in the Code for the calculation of λcr;
b) to give examples to calculate λcr and to provide guidance on the correct
interpretation of λcr found by different methods; and
c) to study the effect of horizontal load on the calculation of λcr.
2.1 In the Code, λcr of a steel frame is defined as the ratio by which the factored loads
would have to be increased to cause elastic instability. λcr is an important parameter that
is required to classify a steel frame into “non-sway”, “sway” and “ultra-sensitive sway”.
Clause 6.3.3 of the Code classifies frames with λcr ≥10 as non-sway, and specifies that
the P- effect is insignificant for such frames. For sway frames with λcr <10, they are
classified as either sway with 5≤ λcr <10 or ultra-sensitive sway with λcr <5, and clause
6.6.1 of the Code specifies that both the P- and P-δ effects should be considered in
their design. In accordance with clause 6.3.3 to 6.3.5 of the Code, λcr can be calculated
either by the eigenvalue analysis for general structures or the deflection method for
geometrically regular and rectangular frame.
In the deflection method, a frame is classified into either sway (or ultra-sensitive sway)
or non-sway by considering the magnitude of the horizontal deflection of each storey
due to the application of notional horizontal loads at each storey which are taken
typically as 0.5% of the factored dead plus live loads on and above the floor considered.
For clad structure provided that the stiffening effect of masonry infill wall panels or
diaphragms of profiled steel sheeting is not explicitly taken into account, the frame is
considered as non-sway if the deflection of every storey is less than 1/2000 of the storey
height under the action of the notional horizontal loads. With such limit on deflection,
equation (6.1) of the Code therefore gives the following equation to calculate λcr of a
steel frame, except for frames with sloping members having moment-resisting
connections in which the calculation of λcr should refer to clause 8.11 of the Code:
F h
λcr N
FV δ N
where FV is the factored dead plus live loads on and above the floor considered;
FN is the notional horizontal force taken typically as 0.5% of FV for building
frames;
An example is included in Annex A to show how to determine the λcr for a typical
geometrically regular and rectangular frame by deflection method. Further example on
the calculation of λcr can also be found in NCCI: Calculation of alpha-cr (King 2005)
(available: http://www.access-steel.com/, accessed: 18 September 2012).
2.3.2 In the determination of λcr by eigenvalue analysis, it is therefore important to study the
form of each buckling mode to see if it is a sway mode or a non-sway mode. King (2005)
commented that when using eigenvalue analysis in finding the first sway-mode, “it is
important to study the form of each buckling mode to see if it is a frame mode or a local
column mode. In frames where sway stability is ensured by discrete bays of bracing
(often referred to as “braced frames”), it is common to find that the eigenvalues of the
column buckling modes are lower than the eigenvalue of the first sway mode of the
frame. Local column modes may also appear in unbraced frames at columns hinged at
both ends or at columns that are much more slender than the average slenderness of
columns in the same storey.” Similarly, Rathbone (2002) noted that “where the columns
are axial load predicated, many of the lower buckling modes will be [local] column
buckling modes. It is the [sway] buckling mode of the whole structure that is important”
to include second-order effects. Therefore, λcr should be taken as the factor
corresponding to the first sway buckling mode rather than the local buckling mode.
3.1 Clause 6.3.2.2 of the Code states that “… of a geometrically regular and rectangular
frame subjected to gravitational loads or gravitational loads plus horizontal load (e.g.
wind), the elastic critical load factor for a sway frame may be calculated as …”, and this
means that the deflection method is applicable to frames with or without horizontal load.
However, it should be noted that equation (6.1) of the Code is only a function of vertical
load and the storey height and is irrelevant of the horizontal load. Horne (1975)
remarked that “[i]t should be noted that the elastic critical load of a frame is affected to
an entirely negligible effect by horizontal loading, and only the vertical loads need be
considered.” In order to verify the accuracy of the deflection method and Horne’s
remark, the values of λcr of a simple portal frame (at Annex D) under various
combinations of horizontal and vertical loading by both deflection method and
eigenvalue analysis have been analysed.
3.2 From the example at Annex D, the following can be observed that:
a) The results from both deflection method and eigenvalue analysis are similar when
λcr is less than 10.
b) When λcr becomes larger, the differences between the deflection method and
eigenvalue analysis also become larger but this is not a concern as it has already
been a non-sway frame with λcr 10.
c) Under the same applied vertical load, λcr determined by deflection method remains
unchanged while that determined by eignevalue analysis remains of the same order
of magnitude under the action of different magnitude of horizontal loads.
d) For the case where the frame is subject to horizontal load only (from horizontal load
of small to large magnitude), the values of λcr so obtained are always substantially
larger than 10, i.e. non-sway frame.
Therefore, all of the above observations agree with Horne’s remark that “the elastic
critical load of a frame is affected to an entirely negligible effect by horizontal loading.”
4.1 In using eigenvalue analysis for the determination of λcr, PSE should use the eigenvalue
corresponding to the first sway buckling mode, not the local buckling mode, as λcr.
Alternatively, the deflection method can be used to calculate λcr for geometrically
regular and rectangular frame structure.
4.2 Horizontal loading has negligible effect on λcr of a frame, and hence only the vertical
loads need to be considered in the determination of λcr.
5. References
Buildings Department (2011), Code of Practice for the Structural Use of Steel 2011
(Hong Kong: Buildings Department) (available: http://www.bd.gov.hk/english/
documents/, accessed: 18 September 2012).
Horne, M R (1975), “An Approximate Method for Calculating the Elastic Critical
Loads of Multi-storey Plane Frames,” The Structural Engineer, 6(53), pp. 242-248
Example 1
Calculation of cr by Deflection Method
This example shows the procedures to determine the value of cr of a 3-storey portal frame at
5m c/c (Figure A1) by using the deflection method.
Design Loadings:
Dead Load = 7.5 kN/m2
Live Load = 5.0 kN/m2
Steel Members:
Steel Grade: S355
Beam Size: 356×171×51 kg/m UB
Column Size: 254×254×107 kg/m UC
Figure A1
The structrue was analsyed with QSE, and the displacement of each floor obtained is shown
in Figure A2:
Therefore, the value of cr should be taken as the smallest of cr,1, cr,2 and cr,3, i.e. 5.55.
Example 2
Calculation of cr by Eigenvalue Analysis
The same example at Annex A is now analysed by the eigenvalue analysis with NIDA and
SAP2000.
Design Loadings:
Dead Load = 7.5 kN/m2
Live Load = 5.0 kN/m2
Steel Members:
Steel Grade: S355
Beam Size: 356×171×51 kg/m UB
Column Size: 254×254×107 kg/m UC
The computer analysis by NIDA and SAP2000 is carried out in accordance with the following
steps:
(A) NIDA
Step 1:
The geometry of the structure to be analyzed is input in the computer model with the factored
design load case of 1.4 DL +1.6 LL.
Step 2:
In the analysis option, select the “Eigen-Buckling Analysis” as the analysis type.
Step 3:
After the completion of analysis, the load factor corresponding to the first buckling mode for
the load combination is found to be 5.36.
Step 4:
Check the mode shape of the model to confirm if the structure deforms in a sway buckling
mode.
Therefore, λcr should be taken as 5.36 (the load factor corresponding to the first sway buckling
mode) which is about the same value as that obtained from the deflection method at Annex A.
(B) SAP2000
Step 1:
The geometry of the structure to be analyzed is input in the computer model with the factored
design load case of 1.4 DL +1.6 LL.
Step 2:
In the definition of load cases, select the “Buckling” as the load case type.
Step 3:
After the completion of analysis, the load factor corresponding to the first buckling mode for
the load combination is found to be 5.29. Check the mode shape of the model to confirm if the
structure deforms in a sway buckling mode.
Therefore, λcr should be taken as 5.29 (the load factor corresponding to the first sway buckling
mode) which is about the same value as that obtained from the deflection method in Annex A
and NIDA.
Example 3
Considerations in the Determination of cr by Eigenvalue Analysis
The value of λcr of a single storey portal frame with a diagonal bracing (Figure C1) is
determined by both the deflection method and eigenvalue analysis.
Design Loading:
1000kN at ¼ th span of the first bay (factored load)
Steel Members:
Steel Grade: S355
Beam Size: 152 × 152 × 23 kg/m UC
Column Size: 152 × 152 × 23 kg/m UC
Bracing Size: 88.9 × 6.3mm CHS
1000 kN
3m
3m 3m
Figure C1
By Deflection Method
5 kN
Notional horizontal defelction due to the notional horizontal force (0.5%×1000 = 5kN) is
0.149mm (using computer software NIDA)
By Eigenvalue Analysis
The ratio by
which the load has
Mode Mode Shape Sway Mode to be increased to
cause elastic
instability
Non-sway
st buckling mode/
1 7.1
Local column
buckling mode
Non-sway
nd buckling mode/
2 25.1
Local column
buckling mode
Non-sway
buckling mode/
3rd 27.4
Local column
buckling mode
Sway buckling
4th 99.0
mode
Therefore, λcr should be taken as 99.0 (the load factor corresponding to the first sway buckling
mode) which is of about the same value as that obtained from the deflection method.
Example 4
Effects of Horizontal Load on cr
The value of λcr of a single storey portal frame (Figure D1) is determined by both the
deflection method and eigenvalue analysis under different combinations of horizontal and
vertical loads.
Steel Members:
Steel Grade: S355
Beam Size: 254 × 146 × 373 kg/m UB
Column Size: 203 × 203 × 46 kg/m UC
Vertical Load, Fv
Horizontal B C
Load, Fh
3m
A D
4.5m 1.5m
Figure D1
a) The results of both deflection method and eigenvalue analysis are similar when λcr is
less than 10.
b) When λcr becomes larger, the differences obtained from the deflection method and
eigenvalue analysis also become larger but this is not a concern as it has already been
a non-sway frame for λcr 10.
c) Under the same applied vertical load, λcr as determined by deflection method remains
unchanged while that as determined by eignevalue analysis remains of the same order of
magnitude under the action of different magnitude of horizontal loads.
Values of λcr of the same structure under the action of horizontal load only (Figure D2) has
also been determined as follows:
Horizontal B C
Load, Fh
3m
A D
6m
Figure D2
In the above cases where the frame is subject to horizontal load only (from horizontal load of
small to large magnitude), λcr so obtained are always substantially larger than 10, i.e. non-
sway frame and therefore the horizontal load will not affect sway stability for frame
classification.