QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12


SUBSTATIONS - PACKAGE S-10, S-13 & S-14
CONTRACT NO. GTC/643G/2014
CONSULTANT :
The Gate (16th FLOOR,
Doha, Qatar,
PO Box 13885.
TEL: +974 4020 6450, FAX: +974 4020 6451
www.wspgroup.com / www.pbworld.com

SUBSTATION NAME : PROJECT DRAWING NUMBER :


COMMON PH12-3G-10-40-T001

C
B1 _ 7/12/2016 Re-issued for Construction ar per DTA-16-4205 MV DMK RLG

B B 20/10/2016 Issued for Construction ar per DTA-16-1448 MV DMK RLG

A B 5/5/2016 Issued for Approval as per DTA-16-0262 MV DMK RLG

0 B 10/2/2016 Issued for comments MV DMK RLG

REV. STAT. DATE MODIFICATION PREPARED CHECKED APPROVED

SUBCONTRACTOR NAME : CONTRACTOR NAME :

MANUFACTURERS DRAWING NO: DRAWING/DOCUMENT TITLE:


(4)G719EA-HG9030-U2002 Technical data sheet for Substation Control
DATE NAME SIGNATURE System
PREPARED 10/2/2016 MV
CHECKED 10/2/2016 DMK SIZE SCALE : NTS REV.
APPROVED 10/2/2016 RLG A4 Sheet No. 01 of 28 C
B1
VOLUME 4 SECTION 3.4.10 PAGE 2 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

LIST OF CONTENTS PAGE

COVER SHEET 1

LIST OF CONTENTS 2

INTRODUCTION PAGE 4

1 SUBSTATION CONTROL SYSTEM 5

2 GENERAL 5

2.1 COMMON FOR SERVER / GATEWAYS / HMI / EWS 5

2.2 STATION SERVER 6

2.3 GATEWAY COMPUTER 6

2.4 OPERATOR WORKSTATIONS / HMI 7

2.5 OPERATOR DESK 7

2.6 COLOUR VISUAL DISPLAY UNIT (VDUS) 8

2.7 SUBSTATION LOCAL AREA NETWORK (LAN) 8

2.8 MANAGED ETHERNET SWITCH 9

2.9 FIREWALL 10

2.10 COLOUR PRINTERS (ONLY FOR 400KV SUBSTATIONS) 11

3 BAY CONTROL UNIT HARDWARE 12

3.1 GENERAL 12

3.2 BCU ENCLOSURE 13

3.3 IEC STANDARDS (OR EQUIVALENT) 14

3.4 BCU FUNCTIONS 14

3.5 BCU CONFIGURATION 15

3.6 PROCESSING UNIT 15

3.7 COMMUNICATIONS 15

3.8 POWER SUPPLY MODULE 16

3.9 DIGITAL INPUT MODULE 17

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 3 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

3.10 COMMAND OUTPUT MODULE 18

3.11 DIGITAL OUTPUT MODULE 18

3.12 ANALOGUE INPUT MODULE 19

3.13 DIRECT AC CONNECTION VOLTAGE 19

3.14 DIRECT AC CONNECTION CURRENT 20

4 BCU SOFTWARE 20

4.1 GENERAL REQUIREMENT 20

4.2 CAPABILITY 20

4.3 SYSTEM SOFTWARE 21

4.4 STANDARD FUNCTIONS PROGRAMS 21

4.5 ANALOGUE MEASUREMENTS, SCANNING AND TRANSMISSION PROGRAMS 21

4.6 FUNCTIONS AND CAPABILITIES 21

4.7 ALARM AND EVENT HANDLING 22

4.8 SUPERVISORY CONTROL PROGRAMS: FUNCTIONS AND CAPABILITIES 22

4.9 DATA PROCESSING PROGRAMS: FUNCTIONS AND CAPABILITIES 22

5 GATEWAY SOFTWARE 23

5.1 GENERAL REQUIREMENTS 23

5.2 CAPABILITY OF: 23

5.3 SYSTEM SOFTWARE 23

6 HMI SERVER /WORKSTATION SOFTWARE 24

7 GPS RECEIVER 25

8 LAPTOP 25

9 FIBER OPTIC PATCH CABLES 26

10 SYSTEM SECURITY REQUIREMENTS 26

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 4 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

SECTION 3.4.10
VOLUME 4 SECTION 3.4.10 PAGE 5 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

SUBSTATION CONTROL SYSTEM UNIT DATA


Required Offered
1. Substation Control System

2. General

System supplier Yes SIEMENS

- SCS System Name Yes SICAM PAS

- System version Yes


V 8.x
- Place of integration Yes
SIEMENS,INDIA
- SCS panel make/place
2.1. Common for Server / Gateways / HMI / EWS

2.1.1. Manufacturer Yes Siemens

2.1.2. Model Yes IPC847D

2.1.3. Type Industrial Yes

2.1.4. Country of Origin Germany

2.1.5. Suitable for 24 x 7 operation Yes Yes

2.1.6. Processor

- Type (Minimum) Intel core i7


(Xeon) Xeon E3-1275 v3
Processor or
Higher
- Clock speed (minimum) GHz 3.5 to 3.9 GHz
2.1.7. Memory size

- Supplied (minimum) GB 16GB 16GB

- Supportable/expandable GB 32GB

2.1.8. Storage size Configuration RAID Yes


Configuration
Hot-Swappable
type
- Storage Suitable for 24 x 7 operation Yes Yes

- Storage Type SCSI/SAS/ SSD SAS


(ST1000NM0023)
- Supplied (minimum 1 TB) TB As required to 1 TB
store 1 year Data
2.1.9. Optical Storage DVD RW Yes Yes

2.1.10. Operating system MS Windows Windows 7


Professional
(64bit)
Updation of Microsoft recommended fixes and history to be Up to FAC Microsoft
provided Recommended
HQ tested hot
fixes shall be
provided up to
FAC.

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 6 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

2.1.11. Antivirus Software

Validity Years Up to FAC Yes

Antivirus Updation through Centralized Client /Server in S/S Yes Yes

2.1.12. Operating temperature range °C 0 to 35 °C

2.1.13. Maximum relative humidity % 5% to 80% at 25


°C (no
condensation)
2.1.14. Nominal voltage VAC 240AC 240 VAC

2.1.15. Redundant Power Supply Modules (Hot Swappable) Yes Yes

2.1.16. Operating frequency Hz 50 50Hz

2.1.17. Power requirement W 300 W at 77 %


efficiency
2.1.18. Mean time between failure h 170,000 hours @
25 °C

110,000 hours @
35 °C

2.1.19. Mean time to repair h 53 h, From the


time, when IPC
reaches the repair
center.
2.1.20. Mounting 19” Rack Yes

2.1.21. Type test

- Witnessed by independent LAB yes Yes

- Date issued Not older than 5 Yes


years
2.1.21 Communication Protocols in Substation IEC 61850 over Yes
dual fibre optic

2.2. Station Server

2.2.1. Software supplied (Attach a list of software other than Required SICAM PAS
operating systems to be installed)
2.2.2. Remote Access of Server through KVM Switches Yes Yes

2.2.3. Configuration of Remote Access from HMI/EWS Yes Yes

2.3. Gateway Computer

2.3.1. Communication Protocols To Control Centre(s)

- NCC Main & Standby IEC 60870-5-104 (101 if Yes Yes


applicable)
- DCC Main and Standby IEC 60870-5-104 Yes Yes

2.3.2. Dual LAN ports for Control Centre Communication Yes Yes

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 7 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

2.3.3. List other operating Protocols available/supported Yes IEC 61850

2.3.4. Software supplied (Attach a list of software other than Required SICAM PAS
operating systems to be installed)
2.3.5. Remote Access of Server through KVM Switches Yes Yes

2.3.6. Configuration of Remote Access from HMI/EWS Yes Yes

2.4. Operator Workstations / HMI

2.4.1. Mouse Yes Yes

2.4.2. Keyboard Yes Yes

2.4.3. Literature reference for principle of operation Yes Yes. Shall be


covered in FDS.
2.4.4. Software supplied (Attach a list of software other than Yes SICAM SCC
operating systems to be installed)
2.4.5. MS Office Software with PDF Writer Yes Yes

2.4.6. Operator interface screens Dual Yes

2.4.7. LAN Interface for Remote Access from Control Center Yes Yes

2.4.8. LAN Interface for PMR files uploading to Control Center Yes Yes

2.5. Operator Desk

2.5.1. Manufacturer Yes Knurr

2.5.2. Type of construction Yes Aluminium / Steel


extrusions
2.5.3. Country of Origin

2.5.4. Placing of the Industrial Computer with Suitable Ventilation Yes Yes

2.5.5. Method of mounting VDUs Yes Vertical at top the


desk
2.5.6. Industrial Grade Power Sockets Yes Yes

2.5.7. Provision for Routing Communication Cables & Power Cables Yes Yes

2.5.8. Colour of Furniture Yes As per approved


Control desk view.
2.5.9. Dimension (Length, Width, Height) Yes As per approved
Control desk view.
2.5.10. Number 1 Nos. per station

2.5.11. Operator Chairs

Manufacturer Knurr

- Type of construction Seat & Back made


of PU foam
- Type of upholstery PU Leather

- Number No 2 2

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 8 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

2.6. Colour Visual Display Units (VDUs)

2.6.1. Number per HMI Workstation 2 2

2.6.2. Manufacturer Yes Fujitsu

2.6.3. Model Yes B24W-7/


Equivalent
2.6.4. Screen size across diagonal inch 24 “(LED) 24 “(LED)

2.6.5. Operating temperature range °C 5 - 35 °C

2.6.6. Operating relative humidity range % 10%-85% at 25 °C

2.6.7. Nominal voltage VAC 240 100 V - 240 V

2.6.8. Operating frequency Hz 50Hz 50 Hz - 60 Hz

2.6.9. Power requirement W 24W, for


maximum
brightness
2.6.10. Approximate lifetime of monitor under continuous use h 50K hours

2.6.11. Mean time between failure h 70,000h

2.6.12. Mean time to repair h Next Business


Day
2.6.13. Input Connectors Type 1 x DisplayPort
1.2,
1 x DVI-D
(HDCP),
1 x D-SUB

2.6.14. Monitor suitable for 24 x 7 Operation Yes Yes

2.6.15. Response Time ms Yes 5 ms (in Video


mode)

2.7. Substation Local Area Network (LAN)

2.7.1. Architecture and Technology (RSTP/PRP/HSR/Others) Yes RSTP

2.7.2. Literature reference for principle of operation Yes Yes

2.7.3. Transmission medium (e.g. optical fiber) and physical Optical Optical
specification
2.7.4. Protocols

- TCP/IP Yes for remote Yes


access
- Redundancy Yes Yes, RSTP,
eRSTP
- IEC 61850 – Fiber Optic Yes Yes

- List all other protocols Yes IEC104 Slave

2.7.5. Data transmission rate(s) Gb/s 1 (at substation 1Gb/s (at


level) substation level)
2.7.6. Physical arrangement - Identify all main elements in the Yes Shall be part of
network e.g. switches, routers, gateways switches, etc. and configuration

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 9 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

the number of each drawing

2.7.7. For each element of the LAN indicate the

- No and type of ports RSG2488 - Max.


28 Ports, can be
configured as per
substation
requirement.

Type of Ports -
LC/ST/RJ45
- % of spare for each type of port % 20 % 20 %

2.7.8. Management software package, functions and facilities, etc. Yes Yes

2.7.9. % Loading under various system activity scenarios including

- normal loading for performance testing %


<=40
- high loading for performance testing %
<=80
- system power up %
<=50
- main server fail-over and database % <=50
resynchronization
2.7.10. Overall availability % For Ruggedcom
Switches, 85%
(MTBF/(MTBF+MT
TR)
Based on the
availability of the
spare.
2.7.11. Network Recovery time at Station level and bay Level ms Yes Max. 200ms for
RSTP
2.7.12. Capacity in the network for connecting IEDs of future bays to % As per future 20% Spare
the proposed network architecture bays. capacity of offered
system shall be
provided. The
confirmation for
each substation
for future bays
shall be given in
each system
configuration.

2.8. Managed Ethernet Switch

2.8.1. Manufacturer Yes RUGGEDCOM

2.8.2. Type Yes (IEC 61850 RSG2488


compatible,
industrial grade
switch)
2.8.3. Country of Origin Canada

2.8.4. Nominal voltage VDC / Dual Power red. 88-300 VDC /


VAC Supply red. 85-264VAC

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 10 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

2.8.5. 61850 Interoperability Test Yes

2.8.6. Power requirements W max. 66 W


o
2.8.7. Range of ambient temp. and max relative humidity for C, Yes -40ºC / 85ºC
continuous reliable operation %RH
2.8.8. Mean time between failures h 6.1 Yrs @ 55 ºC
9.2 Yrs @ 25 ºC
2.8.9. Mean time to repair h Approx. 24 h
Based on the
availability of the
spare.
2.8.10. For each LAN Switch indicate the

- No and type of ports RSG2488 - Max.


28 Ports, can be
configured as per
substation
requirement.

Type of Ports -
LC/ST/RJ45

Ports & Spare for


each switch
mentioned in
architecture along
with spares.
- % of spare for each type of port % 20 % 20%

2.8.11. Tagging support Yes Yes

2.8.12. VLAN support Yes Yes

2.8.13. SNTP Time Synchronization Yes Yes

2.8.14. Redundancy Protocol Supported Yes Yes

2.8.15. Product function Web Based Management Yes Yes

2.8.16. SNMP support Yes Yes

2.8.17. Suitable Cover for unused Communication Ports Yes Yes

2.8.18. EMC Compliance Yes Yes

2.8.19. LAN configuration to support availability and failure scenario Yes Yes
to be specified.
2.8.20. Type test

- Witnessed by independent LAB yes Yes

- Date issued Not older than 5 Yes


years

2.9. Firewall

2.9.1. Manufacturer Siemens (Model :


RX1500)

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 11 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

2.9.2. Type Firewall


(Hardware
Appliance)
06/12 RJ45 Ports
2.9.3. Country of Origin Canada

2.9.4. Dual Firewalls for IEC 60870-5-104 Yes Yes

2.9.5. Firewall for PMR/Remote Access Yes Yes

2.9.6. Firewall for Condition Monitoring system wherever Yes


applicable
2.9.7. Routing (static, Dynamic, policy Based) Yes Yes

2.9.8. V LAN Supporting Yes Yes

2.9.9. Alarms & Notification through SNMP Yes Yes

2.9.10. Web Based User Interfaces Yes Yes

2.9.11. Real time violation alarms & Rules (IPS/IDS) Yes Yes

2.9.12. MAC Filtering Yes Yes

2.9.13. Source/Destination Port Filtering Yes Yes

2.9.14. Stateful Packet Inspection Yes Yes

2.9.15. SCADA Specific protocol filtering Yes Yes

2.9.16. Nominal voltage VAC/VD Yes HI (88 – 300VDC/


C 85 – 264 VAC)

2.9.17. Power requirements W 50 Watts (max)


o
2.9.18. Range of ambient temp. and max relative humidity for C, -40°C to +85°C
continuous reliable operation %RH
2.9.19. Mean time between failures h Around 29 Years

2.9.20. Mean time to repair h RX1500 has a


field replaceable
media modules
and hot
swappable power
supplies. So
depending upon
spare availability
repair can be
done within
Approx. 2-hours
2.9.21. No and Type of Ports (as per scope requirement) 6/12 Copper
Interfaces
10/100MBit
2.9.22. % of spare for each type of port 20%
Yes
2.9.23. Suitable Cover for unused Ports Yes Yes

2.10. Colour Printers Only for 400Kv


Substations

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 12 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

2.10.1. Manufacturer Yes HP

2.10.2. Model Yes CP5225N/


Equivalent
2.10.3. Print speed (minimum) PPM Up to 20 ppm,
letter/A4 and
black-and-
white/color
2.10.4. Technology Colour Laser Color LaserJet
Printer
2.10.5. Resolution dpi Up to 600 x 600
dpi
2.10.6. Paper size Upto A3 Yes

2.10.7. Sheet feed paper tray capacity Sheets 100-sheet


multipurpose
tray1,
250-sheet tray 2
2.10.8. Internal memory Upto Mb 192 MB

2.10.9. Operating temperature range °C Operating: 10 to


30º C
2.10.10. Maximum relative humidity %
20 to 60% RH

2.10.11. Nominal voltage V ac 240V AC 220 to 240 VAC


(+/- 10%)
2.10.12. Operating frequency Hz 50Hz 50 Hz (+/- 2 Hz)

2.10.13. Power requirement W Active: 440 watts;


Standby: 30 watts;
PowerSave: 4.4
watts;
Off: 0.5 watts
2.10.14. Max noise level at 1 m dB(A) Acoustic pressure
emissions –
49dB(A)
2.10.15. Mean time between failure h ----

2.10.16. Mean time to repair h ----

2.10.17. Functions

Event &alarm printing


Yes Yes
Display printing
Yes
Yes

3. Bay Control Unit Hardware

3.1. General

3.1.1. Manufacturer Yes SIEMENS

3.1.2. Country of Origin Germany

3.1.3. Model designation Yes 6MD85

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 13 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

3.1.4. Literature reference for principle of operation Yes SIPROTEC 5

3.1.5. Normal Power supply VDC 110 60-250VDC


110-230VAC
3.1.6. Power requirements W 16-35W Varies
according to
Modules
3.1.7. Interface to substation LAN IEC-61850 over IEC-61850
fiber Fiber-optic loop
3.1.8. Maximum Number of expansion modules of different types 9

3.1.9. Mean-time to repair H 24 h

3.1.10. Mean-time between failure H 87,600 h

3.1.11. Local LCD Display (mimic) Yes Yes

3.1.12. Password facility for access to setting/configuration Yes Yes


available
3.1.13. Operating temperature range °C 0 – 50 -25 to 70°C

3.1.14. Operating relative humidity range % 75 % (Annual


Average) Relative
Humidity, on 56
days a year up to
95% Relative
Humidity,
condensation not
permitted
3.1.15. I/O Capacity (equipped) As required to Yes
meet signal
requirement +
20% spare for
each type of IO
3.1.16. Type test

- Witnessed by independent LAB Yes Yes

- Date issued Not older than 5 Yes


years
3.1.17. IEC 61850 conformance test

- Witnessed by independent LAB Yes Yes

- Date issued Not older than 3 Yes


years
3.2. BCU Enclosure

3.2.1. Manufacturer Yes SIEMENS

3.2.2. Module designation Yes SIPROTEC 5

3.2.3. Literature reference for enclosure Yes SIPROTEC 5

3.2.4. Weight Yes Approx. 10-27 kg


(6MD85) Varies
according to
Modules
3.2.5. Dimensions Yes As per the
configuration
3.2.6. Degree of protection Yes Front IP51
Rear IP50

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 14 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

3.2.7. Flush Mounted housing Yes Yes

3.2.8. Surface mounted housing Yes Optional

3.3. IEC Standards ( or Equivalent )

3.3.1. Type tests (Provide Class/Level or Severity rating)

- Dielectric withstand test IEC 60255-4/-5 Yes Yes

- High Voltage impulse test IEC 60255-4/-5 Yes Yes

- Fast transient disturbance test IEC 61000-4-4 Yes Yes

- Oscillatory transient IEC 61000-4-12 Yes Yes

- Radiated immunity test IEC 61000-4-6 Yes Yes

- Electrostatic discharge test IEC 61000-4-2 Yes Yes

- Emitted interference test IEC 61000-4-3 Yes Yes

3.3.2. Mechanical test Compliance Yes Yes

- Vibration test IEC 60255-21-1 Yes Yes

- Shock test IEC 60255-21-2 Yes Yes

- Seismic test IEC 60255-21-3 Yes Yes

- Temperature rise test IEC 60068-2-2 Yes Yes

3.3.3. Date of Type test certificate by independent LAB Not older than 5 Yes
years
3.4. BCU Functions

The monitoring functions include:

3.4.1. Switching status monitoring (breakers) Yes Yes

3.4.2. Indication & alarm status monitoring Yes Yes

3.4.3. Analogue measurements (currents, voltages, etc.) Yes Yes

3.4.4. Resolution of time tagging ms 1 1 ms

The control functions include:

3.4.5. - Close / open of circuit breakers Yes Yes

3.4.6. - Close / Open of isolators / disconnectors Yes Yes

3.4.7. - Transformer Automatic tap change control Yes Yes

3.4.8. - Breaker Voltage Synchronization Check Control Yes Yes

3.4.9. - Bay interlocking facilities Yes Yes

The reporting functions include:

3.4.10. - Sequence of Events recording Yes Yes

3.4.11. - Post – Mortem Review / Fault waveform capture If applicable Yes

3.4.12. - Tenders to state memory capacity and functionality Maximum 128

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 15 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

of Sequence of events (and fault waveform capture, faults records


if applicable)
3.4.13. Remote end status/ indication Yes Yes

- Mimic of remote end Yes Yes

- Status / indications for remote end Yes Yes

3.5. BCU Configuration

3.5.1. Number of processors Yes 1

3.5.2. Main processor CP300

3.5.3. Secondary processors Not Applicable

3.5.4. Communication processor (module) Yes Yes

3.5.5. LCD Display and selector Buttons on front of BCU Yes Yes

Functionality to include

- Full control of circuit bay Yes Yes

- Status of bay plant Yes Yes

- Circuit active line diagram Yes

- Power system Measurements Yes Yes

- Display alarms and events Yes

3.6. Processing Units

3.6.1. Main CPU Yes Yes

3.6.2. Manufacturer Yes FREESCALE

3.6.3. Module designation CP300

3.6.4. Literature reference for principle of operation Not Applicable

3.6.5. Mean - time between failure h 87,600 h

3.6.6. Power requirements W <3W

3.6.7. Type of processor FREESCALE


MPC8343
3.6.8. Word length bit 32Bit

3.6.9. Clock speed MHz 400 MHz

3.6.10. Type of memory used: DRAM / SRAM /


Flash
3.6.11. Type, size and extension capabilities KByte D-RAM 256MByte
S-RAM 512MByte
Flash 128Mbyte
3.6.12. Simultaneous communication towards multiple IEC 61850 Yes Yes (6 max.
clients (indicate max. number supported) number
supported)
3.7. Communications

3.7.1. Manufacturer Yes SIEMENS

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM_1.DOCX TECHNICAL AFFAIRS


Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 16 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

3.7.2. Module designation Ethernet module


ETH-BB-2FO
3.7.3. Literature reference for principle of operation SIPROTEC 5

3.7.4. Number of communications channels 2 (Transmission /


Reception)
3.7.5. Type of processor If applicable NA

3.7.6. Word length If applicable NA

3.7.7. Clock speed bit If applicable NA

3.7.8. Type and size of memory MHz If applicable NA

3.7.9. Line interface to communication channel NA

3.7.10. Speed of transmission B/s 100Mbps 100Mbps

3.7.11. Number and type of communication ports No 2 Channels (FO 2x LC-FO ports for
port) 61850
3.7.12. Meantime between failure h NA

3.7.13. Power requirement W 2.5W

3.7.14. Communication Interfaces

- IEC60870-5-101 direct to Control Centre(s) --

- IEC60870-5-103 interface to protection IED --

- IEC61850 interface to substation LAN Yes Yes

- IEC60870-5-101 for remote downloading of BCU --


data
- List all Protocols available at BCU --

3.7.15. Local interface for Laptop Computer Yes

3.7.16. IED Interface

- List of manufactures the BCU has interfaced Yes ABB, ALSTOM,


TAPCON, A-
EBERLE
- Standard communication protocols available Yes Yes

- Optional communication protocols available Yes Yes

3.8. Power Supply Module

3.8.1. Module designation PS201, PS203

3.8.2. Literature reference for principle of operation SIPROTEC 5

3.8.3. Maximum number of modules per processor 2

3.8.4. Nominal Input voltage VDC 110V DC 60-250 VDC


110-230 VAC
3.8.5. Operating voltage range (Min/Max) -20% to +20%

3.8.6. Power requirement W PS201 / PS203:


13W – additional
expansion

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 17 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

module: 3W

3.8.7. Isolation 3.5 kV DC

3.8.8. Meantime between failure h 87,600 h

3.8.9. Power requirement W 16-35W Varies


according to
Modules
3.9. Digital Input Module

3.9.1. Module designation PS201 / IO202/


IO207 / IO230
3.9.2. Literature reference for principle of operation SIPROTEC 5

3.9.3. Maximum number of modules supported 9

3.9.4. Input voltage VDC 24 – 250 Vdc

Is contact input type configurable as NA

3.9.5. Status and alarms Yes

3.9.6. Sequence of events Yes

3.9.7. SP, DP, BCD or parallel inputs Yes

3.9.8. Pulse accumulator Yes

3.9.9. Or any combination of these Yes

3.9.10. Standard number of inputs per module: PS201 (3 common


potentcial)
IO202 (8 isolated);
IO207 (16
isolated);
IO230 (48
common
potential);
3.9.11. double position Yes

3.9.12. single position Yes

3.9.13. Minimum Binary Input threshold Vdc DC 24 V-250 V

3.9.14. Type of input circuit isolation optical coupler

3.9.15. Input galvanic separation NA

3.9.16. Impulse voltage withstand kV 5 kV

3.9.17. Scan time ms Each 250


Microseconds

3.9.18. Minimal pulse duration ms 6MD8: 4.3 ms

3.9.19. Input impedance ohm Variable


Impedance
3.9.20. Filter time constant ms NA

3.9.21. Meantime between failure h NA

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 18 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

3.9.22. Power requirement W NA

3.10. Command Output Module

3.10.1. Module designation IO202 / IO207

3.10.2. Literature reference for principle of operation SIPROTEC 5

3.10.3. Maximum number of modules supported 9

3.10.4. Contact ratings NA

3.10.5. Switched voltage V <250Vdc

3.10.6. Switched power VA max 1000 W/VA

3.10.7. Switched current A 5A

3.10.8. Range of duration of command output S 10 ms (standard


relays)
5ms
(fast relays)
3.10.9. Number of two position output channels per module NA

3.10.10. Are outputs activated by select-check-actuate procedure? Yes

3.10.11. Are welded contacts checked prior to command output? Yes

3.10.12. Are the outputs fused and fuse status monitored? Yes

3.10.13. Impulse voltage withstand kV 5 kV

3.10.14. Meantime between failure h 87,500 h

3.10.15. Power requirement W NA

3.11. Digital Output Module

3.11.1. Module designation PS101


IO202
IO207
3.11.2. Literature reference for principle of operation SIPROTEC 5

3.11.3. Number of outputs per module IO202 (8 isolated /


4 NO);
IO207 (16 isolated
/ 8 common
potential);
IO230 (48
common potential)
3.11.4. Maximum number of modules per processor 9

3.11.5. Maximum output current mA NA

3.11.6. Maximum switched output voltage V <250Vdc

3.11.7. Impulse voltage withstand kV 5 kV

3.11.8. Type of protection against back EMF kV NA

3.11.9. Command duration adjustable in the range s NA

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 19 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

3.11.10. Meantime between failure h NA

3.11.11. Power requirement W NA

3.12. Analogue Input Module

3.12.1. Module designation ANAI- CA- 4EL

3.12.2. Literature reference for principle of operation SIPROTEC 5

3.12.3. Maximum number of modules supported. 5

3.12.4. Scanning resolution bits NA

3.12.5. Accuracy % <1 % of Nominal


Value
3.12.6. How are overflow and conversion failures dealt with? NA

3.12.7. Conversion time NA

3.12.8. Input filter attenuation at 50 Hz dB NA

3.12.9. Input signal types (e.g. 4-20 mA) -24mA to +24mA

3.12.10. Method of isolation NA

3.12.11. Impulse voltage withstand kV 5 kV

3.12.12. Input impedance ohm 140 ohm


resistance
3.12.13. Type of ADC switching NA

3.12.14. Standard number of inputs per module 4

3.12.15. Mean time between failure h 87,500h

3.12.16. Power requirement W 5.8mW

3.13. Direct AC Connection Voltage

3.13.1. Module designation IO202

3.13.2. Literature reference for principle of operation SIPROTEC 5

3.13.3. Maximum number of modules supported 5

3.13.4. Number of inputs per module 4

3.13.5. Input voltage ranges V ac 0V - 200VAC

3.13.6. Input filter attenuation at 50 Hz dB NA

3.13.7. Burden on instrument transformer circuit VA <0.1VA at


57,735V/phase
3.13.8. Conversion time ms NA

3.13.9. Scanning resolution bits NA

3.13.10. Accuracy % <0.5% of


measured
value
3.13.11. What calculations are supported NA

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 20 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

3.13.12. How are overflow and conversion failures dealt with? NA

3.13.13. Method of isolation NA

3.13.14. Impulse voltage withstand kV kV


5 kV
3.14. Direct AC Connection Current

3.14.1. Module designation IO202

3.14.2. Literature reference for principle of operation SIPROTEC 5

3.14.3. Maximum number of modules processor 5

3.14.4. Number of inputs per module 4

3.14.5. Input current ranges A 1A or 5A

3.14.6. Input filter attenuation at 50 Hz dB NA

3.14.7. Burden on instrument transformer circuit VA <0.1VA at rated


current
3.14.8. Conversion time ms NA

3.14.9. Scanning resolution bits NA

3.14.10. Accuracy % <0.5% of


measured
value
3.14.11. What calculations are supported NA

3.14.12. How are overflow and conversion failures dealt with? NA

3.14.13. Method of isolation NA

3.14.14. Impulse voltage withstand kV kV 5 kV

4. BCU Software

4.1. General Requirements

4.1.1. Software Name and Version Yes Std. DIGSI


Software
4.1.2. Program structure Std. DIGSI
Software
4.1.3. System software CFC, Interlocking,
Logic gates
4.1.4. Standard functions programs SP. DP
informations,
Grouping in CFC
4.1.5. User functions programs NA

4.2. Capability

4.2.1. BCU program downloading from HMI/Control Centre Yes Through HWS on
LAN
4.2.2. Application configuration from HMI/Control Centre Yes Through HWS on
LAN
4.2.3. Remote selection of processing parameters On demand

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 21 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

4.2.4. Selection of communication protocols Yes Only one protocol


is offered
4.2.5. Selection of operation modes (cyclic, polled, etc.) Through remote
DIGSI
4.2.6. Appropriate protection of software against power failure Yes

4.2.7. Automatic BCU re-start without software down-loading Yes

4.3. System Software

4.3.1. Operating System (Monitor) Functions and capabilities PSOS

4.3.2. Calendar program Type, functions and capabilities NA

4.3.3. Time Synchronization Program Functions and capabilities Yes

4.3.4. Data Base Updating program Functions and capabilities Yes

4.3.5. Testing and Diagnostics Programs Functions and capabilities Yes Yes

4.4. Standard Functions Programs

4.4.1. Data Communication Programs: Functions and capabilities Yes

4.4.2. Capability of communication protocol selection Yes

4.4.3. Capability of operating modes selection Yes

4.5. Analogue Measurements, Scanning and


Transmission Programs
4.5.1. Capabilities of adjustments Self calibrated

4.5.2. Transducers constants 4-20 mA

4.5.3. Periodic transmission/transmission by exception Cyclic

4.5.4. Automatic checking of A/D-conversion accuracy Yes

4.5.5. Smoothing Yes

4.5.6. Threshold values Yes

4.5.7. Limits ±0.25%

4.5.8. Scan duration (range) NA

4.5.9. Cycle duration (range) s NA

4.5.10. Priority of transmission s Yes

4.5.11. Digital Input Data Scanning and transmission Program --

4.6. Functions and capabilities

4.6.1. Capability of adjustments; Yes

4.6.2. Scan duration (range) ms NA

4.6.3. Transient time of status information (range) Configurable

4.6.4. Cycle duration (range) ms NA

4.6.5. Debouncing filter s Yes, Configurable

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM_1.DOCX TECHNICAL AFFAIRS


Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 22 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

Chatter blocking

4.6.6. Suppression of intermediate status information Yes

4.6.7. Time tagging Yes, 1ms

4.6.8. Transmission mode Spontaneous,


cyclic
4.6.9. Priority of transmission Yes

4.7. Alarm and Event handling

4.7.1. Grouping of alarms and events Yes

4.7.2. Maximum number of groups 2

4.8. Supervisory Control Programs: Functions


and capabilities
4.8.1. Select before execute Yes

4.8.2. Target check Yes

4.8.3. Cancelling control after adjustable time delay Yes

4.8.4. Capability of adjustments:

4.8.5. Duration of output (range) s Settable

4.8.6. Allowed duration of execution (range) s Settable

4.8.7. Sequence of Events programs Yes standard SOE


as per applicable
protocol/ (in SCC)
4.8.8. Minimal sequence of events time resolution ms 1

4.8.9. Sequence of events memory capacity 200

4.8.10. Events time resolution (adjustable range) 1ms (fixed)

4.8.11. Priority of transmission Yes

4.8.12. Post - Mortem Review / Program COMTRADE View/


SIGRA
4.8.13. Selection of analogues for post-mortem review Yes

4.8.14. Short interval time resolution (adjustable range) s NA

4.8.15. Long interval time resolution (adjustable range) s NA

4.9. Data processing programs: Functions and


capabilities
4.9.1. Required minimum data processing: Yes

4.9.2. Logic functions Yes

4.9.3. Arithmetical functions (MW , Mvar etc ) Yes

4.9.4. Limiting functions s Yes

4.9.5. Comparative functions Yes

4.9.6. Time functions Yes

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM_1.DOCX TECHNICAL AFFAIRS


Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 23 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

5. Gateway Software

5.1. General Requirements

5.1.1. Software Name and Version Yes SICAM PAS

5.1.2. No. of IEDs Software can handle No Yes Max: 450


(dependent on
number of IPCs in
parallel)
5.1.3. No. of Tags Software can handle No Yes 15.000-25.000
(from IEDs)
30.000-50.000(to
HMI and CC)
(dependent on
number of IPCs in
parallel)
5.1.4. Software has provision for future IEDs. % 20% spare is
available for future
use
5.1.5. No. of Spare tags for future use % 20% spare is
available for future
use
5.1.6. Alarm and Event Grouping Yes

5.1.7. Alarm and Event Separation for NCC and DCC Yes

5.1.8. Alarm and Event storage and remote / local access Yes

5.1.9. All IEDs (including Third Party) can be interfaced on Yes Yes
IEC61850 Protocol
5.1.10. IEC 61850/IEC 60870-5-101/IEC60870-5-104 Logging Yes
Facility
5.2. Capability of:

5.2.1. Gateway program downloading from Control Centre Yes

5.2.2. Application configuration from Control Centre Yes

5.2.3. Remote selection of processing parameters Yes

5.2.4. Selection of communication protocols As per


Specification
Requirement
5.2.5. Selection of operation modes (cyclic, polled, etc.) Yes

5.2.6. Appropriate protection of software against power failure Yes

5.2.7. Automatic re-start without software down-loading Yes

5.2.8. Online Modification of Gateway Software Yes

5.3. System Software

5.3.1. Operating System (Monitor) Functions and capabilities Yes, Part of FDS

5.3.2. Calendar program Type, functions and capabilities NA

5.3.3. Time Synchronization Program Functions and capabilities Yes, Part of FDS

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 24 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

5.3.4. Data Base Updating program Functions and capabilities Yes, Part of FDS

5.3.5. Testing and Diagnostics Programs Functions and capabilities Yes, Part of FDS

6. HMI Server /Workstation Software

6.1. Software Name and Version Yes SICAM SCC

6.2. No. of IEDs Software can handle No Yes Max. 450 Via
PAS Server
6.3. No. of Tags Software can handle No Yes Max. 65536 Via
PAS Server
6.4. Software has provision for future IEDs. % 20% spare is
available for future
use
6.5. No. of Spare tags for future use % 20% spare is
available for future
use
6.6. Status updating Time Yes Yes

6.7. Analog value Updating Time Yes Yes

6.8. Command operation Time Yes Yes

6.9. Event List Yes Yes

6.10. Dynamic Single Line Diagram Yes Yes

6.11. Dynamic Communication Overview Yes Yes

6.12. Alarm list, Event, reports and Trends with filter option. Yes Yes

6.13. Export of Analogues in CSV/Excel format Yes Yes

6.14. Export of Events in CSV or Standard Format Yes Yes

6.15. Export of Events, Graphical trends and Reports in PDF Yes Yes
format
6.16. Online modification and DB generation Yes Yes
Modification of
screens/Texts is
possible
6.17. Monitoring healthiness of all components of SCS Yes By monitoring port
including the LAN cables status and SNMP
Signals
6.18. Monitoring Healthiness of ports in Ethernet Switches, Yes Yes
GPS ,Router, etc
6.19. Remote end bay details in SCS Yes Yes

6.20. Offered SCS is expandable in future Yes Yes

6.21. Lockout trip relay reset from HMI Yes Yes

6.22. All HMI displays mentioned in specifications Yes Yes

6.23. Third Party IED interfaces on IEC 61850 Protocol. Yes Yes

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 25 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

7. GPS Receiver

7.1.1. Make & Model No MEINBERG


LANTIME M300
7.1.2. Country of Origin Germany

7.1.3. Lighting Protection Yes MBG S-PRO

7.1.4. Display Yes Yes

7.1.5. Network Interfaces to Ethernet LAN RJ45 or FO RJ45


o
7.1.6. Range of ambient temp. and max relative humidity for C, 0-50°C /85%
continuous reliable operation %RH
7.1.7. Types of port available RJ45

7.1.8. No. Of SNTP ports (Minimum) 3 6

7.1.9. SNMP based alarm Messaging Yes Yes

7.1.10. Remote user Interfaces for configuration Yes Yes

7.1.11. Time Syhcronization of online Monitoring Systems Yes Yes, Provided


systems can be
synchronized via
NTP
7.1.12. Time Synchronization of Telecom Equipment Yes Yes, Provided
systems can be
synchronized via
NTP
7.1.13. Nominal Input voltage VAC / Yes 100-240 VAC
VDC
7.1.14. % of spare for each type of port % 20% Yes

7.1.15. Power Requirements W 30 W

7.1.16. Mean Time Between failure 118294 Hours

8. Laptop

8.1.1. Manufacturer Yes Fujitsu

8.1.2. Model Yes CELSIUS H730/


Equivalent
8.1.3. Country of Origin Germany

8.1.4. Processor

- Type (Minimum) Intel core i7 Intel Core i7


Processor or
Higher
- Clock speed (minimum) GHz up to 3.7GHz

8.1.5. Memory size

- Supplied (minimum) GB 8GB 8GB

- Supportable/expandable GB 32GB

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 26 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

8.1.6. Storage Type Hard disk TB 1TB 1TB

8.1.7. Optical Storage DVD RW Yes Yes

8.1.8. Display Screen Size Inches 15.6 Yes

8.1.9. Operating system MS Windows Yes

Updation of Microsoft recommended fixes and history to be Up to FAC Yes


provided
8.1.10. Antivirus Software Make & Trend micro
Version Latest Version
Validity Years Up to FAC Yes

Antivirus Updation through Centralized Client /Server in S/S Yes Yes

8.1.11. Nominal Input voltage VAC Yes 240VAC

8.1.12. Power Requirements W 150W

9. Fiber Optic Patch Cables

9.1.1. Make Yes Preston

9.1.2. No. of Fiber cores Yes 2/4

9.1.3. Type of Fiber Cable Yes Ruggedize

9.1.4. Flame Retardant Low Smoke Zero Halogen Yes Yes

9.1.5. Maximum tensile strength Short term N 800 800

9.1.6. Maximum tensile strength long term N 200 200

9.1.7. Outer Sheath Colour Yes Orange

10. System Security Requirements

10.1.1. Cyber Security shall be implemented as mentioned in Yes Yes


specifications.
10.1.2. Cyber Security implementations shall be carried out strictly Yes Yes
under the guide lines of ICT Qatar, QCERT “National ICS
Security Standard” with a broad band to adopt IEC 62351 and
ISO/IEC 27002 and/or ISA99 standards
10.1.3. All User accounts shall be configured as Role based access Yes Yes
model (RBAC).
10.1.4. All the Removable media usage in SCS system shall be Yes Yes
restricted
10.1.5. All the latest security patterns/hot fixes shall be implemented Yes
up to FAC
10.1.6. Application White listing software shall be adopted in all Yes Yes
Computers
10.1.7. Yes Yes
All default and unused accounts in operating systems and in
all real time applications shall be disabled.
10.1.8. Yes Yes
All unnecessary software shall be removed from the SCS
System.
10.1.9. Yes Yes
Use of latest stable release of operating system on all

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
VOLUME 4 SECTION 3.4.10 PAGE 27 OF 27

GTC/643G/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

machines and network devices.

10.1.10. Yes Yes


Operating System, SCS software, Antivirus and
Firewall/switch firmware updates shall be provided during the
period of warranty.

_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS
Electrical Projects Dept.
Software List

Station Server
Windows 7 Operating System Professional
SICAM PAS "full Server" Software – Runtime
License OPC Client
License CFC Automation
License - IEC 61850 (Client)
Teaming Utility Software
Trend Micro Office Scan Client

Gateway
Windows 7 Operating System Professional
SICAM PAS "full Server" Software – Runtime
License OPC Client
License CFC Automation
License - IEC 61850 (Client)
License - IEC 104 (Slave)
Teaming Utility Software
Trend Micro Office Scan Client

HWS PC
Windows 7 Operating System Professional
SICAM SCC
SIMATIC Win CC System Software
Teaming Utility Software
PDF Writer
Trend Micro Office Scan Client

EPC/HMI
Windows 7 Operating System Professional
Trend Micro Office Scan Server
SICAM SCC
SIMATIC Win CC System Software
Teaming Utility Software
PDF Writer
Microsoft Office
SICAM PAS Configuration Tool
Incident Explorer for Evaluation of Fault records
Watch Directory - Professional
Firewall Software
Digsi
ABB PCM600, if applicable
ALSTOM MICOM S1 Agile
SCHNEIDER MiCOM S1 Studio
AVR Software
Net view
WinZip