Académique Documents
Professionnel Documents
Culture Documents
This document has been prepared for the purpose of training. It is based on the
respective operation and maintenance manuals. Operation and maintenance must be
performed in accordance with the operating and maintenance manuals!
Siemens AG
Sector Industry, I&S IS ICS2 KHC
P.O.Box 3240
D-91050 Erlangen
E-Mail: ics2khc.industry@siemens.com
Section 3 — Common maintenance procedures
21
3500 Monitoring System Installation and Operation Guide
4. Select the monitor channel to be adjusted in the Monitor Channel list box.
5. For all measurement parameters except phase, adjust the setpoint level by
dragging the bar in the bar graph or by entering a value in the text box above
or below the parameter.
Notice that setpoints can be adjusted only for those parameters that are
enabled and that some parameters have both upper and lower setpoint
values. Parameters are enabled or disabled by using the Channel Option
screen. Refer to the 3500 Monitoring System Rack Configuration and
Utilities Guide for more information.
6. For phase setpoints, enter the values for the beginning and ending setpoint in
the text boxes below the phase diagrams.
7. Apply the adjusted setpoints to the rack by clicking OK and then downloading
the revised configuration to the rack.
22
Section 3 — Common maintenance procedures
2. Remove the module to be replaced.
Refer to Removing and inserting a main module on page 24.
3. Insert the new module
Refer to Removing and inserting a main module on page 24.
4. Download the configuration to the new module.
The 3500 Monitoring System Configuration and Utilities Guide, part number
129777-01, shows how to download configuration files.
5. Verify operation.
- Check that the LEDs for the replaced module are indicating correct
operation (see Reading the LEDs on page 16).
- The values of the measurement parameters of a channel are verified by
using the Verification utility in the 3500 Rack Configuration program and
the verification procedure in the reference manual for that module.
23
3500 Monitoring System Installation and Operation Guide
- Check that the LEDs for the replaced module are indicating correct
operation (see Reading the LEDs on page 16.
- The values of the measurement parameters of a channel are verified by
using the Verification untility in the 3500 Rack Configuration program and
the verification procedure in the reference manual for that module.
3. Once freed from the backplane, the main module can be removed completely
from the rack
24
Section 3 — Common maintenance procedures
2. Slide the main module into place, ensuring that they are properly in the
guides provided on the floor and roof of the rack chassis.
3. Tighten the screws securely.
Application Advisory: It is important to tightly secure the thumb screws to
ensure each module is Chassis grounded. Loose thumb screws may allow noise
to show on the channel readings.
25
3500 Monitoring System Installation and Operation Guide
26
Maintenance 3500/42 Operation and Maintenance
Adjusting the scale factor affects the readings of all configured parameters
associated with the channel. If you change the scale factor, be sure to use the
new value when calculating inputs for verification of channel values.
The Zero Position Adjustment is used for Thrust, Eccentricity, and Differential
Expansion measurements as well as for Gap measurements when Gap is
configured to read in displacement units (not volts). Adjust the zero position after
the probe is gapped and its target is in the proper position.
enter a new value in the scale factor box on the transducer screen or the zero
position box on the Channel Options screen.
use Adjust to get immediate feedback from the channel on the Adjust screen.
The advantage of using the Adjust screen is that you can use the bar graphs to
see the effect of your adjustments on the output signals of the channel. The
following procedures show how to use the methods.
3. Initiate communication with the rack by clicking on the Connect option in the
File menu and then selecting the connection method that you used in step 1.
4. Upload the configuration from the rack by clicking on the Upload option in the
File menu.
184
3500/42 Operation and Maintenance Maintenance
6. Select the monitor you want to adjust. The Monitor screen will appear.
7. Select the Options button under the appropriate Channel. The configured
Channel Options screen will appear.
9. Enter a value for scale factor in the Scale Factor box. If you go to the Adjust
screen by selecting Adjust, be sure to adjust the input to the channel away
from the Zero Position so you can adjust the scale factor and see the results.
185
Maintenance 3500/42 Operation and Maintenance
186
3500/42 Operation and Maintenance Maintenance
187
Maintenance 3500/42 Operation and Maintenance
188
3500/42 Operation and Maintenance Maintenance
189
Maintenance 3500/42 Operation and Maintenance
When increasing or decreasing the zero position voltage, you are actually
mapping the monitor full scale range to a portion of the transducer linear range.
The zero position voltage adjustment range is dependent upon the full-scale
range of the proportional value being adjusted, the transducer scale factor, and
the transducer Ok limits. The following example shows how these parameters
are related to the zero position voltage range.
30
20 40 -17.
10 30
Max Zero Adj -10.99 0
Zero 20
Position Center of Range -10.16 -10
Range 10
-9.33 -20 0
Min Zero Adj
-30 -10
-40 -2.99V
-20
-30
-40 -1.3
Scale at max
Lower Ok Limit -1.28 zero adj
Scale at min
zero adj
3. Initiate communication with the rack by clicking on the Connect option in the
File menu and then selecting the connection method that you used in step 1.
4. Upload the configuration from the rack by clicking on the Upload option in the
190
3500/42 Operation and Maintenance Maintenance
File menu.
6. Select the monitor you want to adjust. The Monitor screen will appear.
7. Select the Options button under the appropriate Channel. The Channel
Options screen will appear.
8. Enter the voltage in the Zero Position or the Gap Position box. Changes are
limited to the values listed adjacent to the box. If you go to the Adjust screen
by selecting Adjust, you can adjust the Zero Position and see the results.
10. Download the new configuration to the appropriate monitor by selecting the
Download option in the File menu and then selecting the appropriate
monitor. The new setting for Zero Position will take effect when the
"Download successful" prompt appears.
191
Gap (mm)
0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
10 0.25
8 0.20
6 0.15
10
ISF Error (%)
-5
- 10
- 20
- 18
- 16
- 14
Output (Volts)
- 12
- 10
-8
-6
-4
-2
0
20 40 60 80 100 120 140 160 180 200
Gap (mils)
6. Troubleshooting
This section describes how to troubleshoot a problem with the
Proximitor®/Seismic Monitor or the I/O module by using the information provided
by the self-test, the LED’s, the System Event List, and the Alarm Event List.
6.1 Self-test
To perform the Proximitor/Seismic Monitor self-test:
2. Select Utilities from the main screen of the Rack Configuration Software.
Application Alert
Machinery protection will
be lost while the self-test
is being performed.
5. Select the slot that contains the Proximitor/Seismic Monitor and press the OK
button. The Proximitor/Seismic Monitor will perform a full self-test and the
System Events screen will be displayed. The list will not contain the results
of the self-test.
7. Press the Latest Events button. The System Events screen will be updated
to include the results of the Proximitor/Seismic Monitor self-test.
192
3500/42 Operation and Maintenance Troubleshooting
193
Troubleshooting 3500/42 Operation and Maintenance
Sequence Number: The number of the event in the System Event List (for
example 123).
Event Information: The name of the event (for example Device Not
Communicating).
0 Severe/Fatal Event
1 Potential Problem Event
2 Typical logged Event
3 Reserved
Event Specific: It provides additional information for the events that use this
field.
194
3500/42 Operation and Maintenance Troubleshooting
The following System Event List Messages may be placed in the list by the
Proximitor/Seismic Monitor and are listed in numerical order. If an event marked with a star
(*) occurs the Proximitor/Seismic Monitor will stop alarming. If you are unable to solve any
problems contact your nearest Bently Nevada Corporation office.
Device Is Communicating
Event Number: 33
Event Classification: Potential Problem
Action: Check to see if one of the following components is faulty:
- the Monitor Module
- the rack backplane
* Neuron Failure
Event Number: 34
Event Classification: Severe / Fatal Event
Action: Replace the Monitor Module immediately.
Monitor Module will stop alarming.
195
Troubleshooting 3500/42 Operation and Maintenance
Fail Main Board +5V-A (Fail Main Board +5V - upper Power Supply)
Event Number: 100
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
Pass Main Board +5V-A (Pass Main Board +5V - upper Power Supply)
Event Number: 101
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
Fail Main Board +5V-B (Fail Main Board +5V - lower Power Supply)
Event Number: 102
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Monitor Module
- the Power Supply installed in the lower slot
196
3500/42 Operation and Maintenance Troubleshooting
Pass Main Board +5V-B (Pass Main Board +5V - lower Power Supply)
Event Number: 103
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Monitor Module
- the Power Supply installed in the lower slot
* Fail Main Board +5V-AB (Fail Main Board +5V - upper and lower
Power Supplies)
Event Number: 104
Event Classification: Severe/Fatal Event
Action: Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
- the Power Supply installed in the lower slot
Monitor Module will stop alarming.
Pass Main Board +5V-AB (Pass Main Board +5V - upper and lower
Power Supplies)
Event Number: 105
Event Classification: Severe/Fatal Event
Action: Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
- the Power Supply installed in the lower slot
Fail Main Board +15V-A (Fail Main Board +15V - upper Power Supply)
Event Number: 106
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
Pass Main Board +15V-A (Pass Main Board +15V - upper Power Supply)
Event Number: 107
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
197
Troubleshooting 3500/42 Operation and Maintenance
Fail Main Board +15V-B (Fail Main Board +15V - lower Power Supply)
Event Number: 108
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Monitor Module
- the Power Supply installed in the lower slot
Pass Main Board +15V-B (Pass Main Board +15V - lower Power Supply)
Event Number: 109
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Monitor Module
- the Power Supply installed in the lower slot
* Fail Main Board +15V-AB (Fail Main Board +15V - upper and lower Power
Supplies)
Event Number: 110
Event Classification: Severe/Fatal Event
Action: Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
- the Power Supply installed in the lower slot
Monitor Module will stop alarming.
Pass Main Board +15V-AB (Pass Main Board +15V - upper and lower
Power Supplies)
Event Number: 111
Event Classification: Severe/Fatal Event
Action: Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
- the Power Supply installed in the lower slot
Fail Main Board -24V-A (Fail Main Board -24V - upper Power Supply)
Event Number: 112
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
198
3500/42 Operation and Maintenance Troubleshooting
Pass Main Board -24V-A (Pass Main Board -24V - upper Power Supply)
Event Number: 113
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
Fail Main Board -24V-B (Fail Main Board -24V - lower Power Supply)
Event Number: 114
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Monitor Module
- the Power Supply installed in the lower slot
Pass Main Board -24V-B (Pass Main Board -24V - lower Power Supply)
Event Number: 115
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Monitor Module
- the Power Supply installed in the lower slot
* Fail Main Board -24V-AB (Fail Main Board -24V - upper and lower
Power Supplies)
Event Number: 116
Event Classification: Severe/Fatal Event
Action: Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
- the Power Supply installed in the lower slot
Monitor Module will stop alarming.
Pass Main Board -24V-AB (Pass Main Board -24V - upper and lower
Power Supplies)
Event Number: 117
Event Classification: Severe/Fatal Event
Action: Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
- the Power Supply installed in the lower slot
199
Troubleshooting 3500/42 Operation and Maintenance
* Configuration Failure
Event Number: 301
Event Classification: Severe/Fatal Event
Action: Download a new configuration to the Monitor Module. If the problem
still exists replace the Monitor Module immediately.
Monitor Module will stop alarming.
Configuration Failure
Event Number: 301
Event Classification: Potential Problem
Action: Download a new configuration to the Monitor Module. If the problem
still exists replace the Monitor Module as soon as possible.
Module Reboot
Event Number: 320
Event Classification: Typical Logged Event
Action: No action required.
200
3500/42 Operation and Maintenance Troubleshooting
201
Troubleshooting 3500/42 Operation and Maintenance
202
3500/42 Operation and Maintenance Troubleshooting
203
Troubleshooting 3500/42 Operation and Maintenance
* Kph Lost
Event Number: 493
Event Classification: Potential Problem
Event Specific: Ch pair x
Action: Check to see if one of the following is faulty:
- both Keyphasor transducers on the machine
- the Monitor Module
- the Keyphasor Module
For vector and Keyphasor based, alarms the Monitor Module will stop
alarming.
204
Proximitor and Probes Chapter 3 — Maintenance and Troubleshooting
13
3300 XL Proximity Transducer System Manual
The scale factor verification uses the test setup as shown in the following figure:
Vdc
-24 Vdc
Vin Com
10 kΩ
OUT
+ -
COM
VT
Proximitor® Sensor
14
Chapter 3 — Maintenance and Troubleshooting
500 µm 200 µm
or or
20 mil 8 mil
250 µm
or
10 mil
15
3300 XL Proximity Transducer System Manual
If the incremental scale factor (ISF) or the average scale factor (ASF) of the
system is out of tolerance, contact Bently Nevada Corporation for further
information on possible calibration problems.
The preceding pages indicate scale factor verification using a TK-3. This is
suitable for rough verification. For API 670 system verification a more precise
micrometer and target must be used. There are two different 3300 XL
Micrometer Kits that can be used to verify the calibration of our transducer
systems or to check the scale factor of specific shafts. Both micrometer kits will
work with Bently Nevada eddy current transducers ranging in size from the 3300
RAM transducer system up to the 7200 14 mm transducer system. Both
micrometers also have options for either a metric or English micrometer.
The 3300 XL Precision Micrometer (p/n 330185) is a highly accurate
verification device. It should be used when performing acceptance testing on our
transducer systems. All of our transducer systems have a specified linear range
and average scale factor (ASF). The transducer systems also have a maximum
deviation from straight line (DSL) and ISF tolerances for ambient and extended
temperatures. The 3300 XL Precision Micrometer comes with a high precision
4140 steel target and is used to make precise measurements and verify whether
the transducer system is working properly and within published specifications.
The 3300 XL Shaft Micrometer (p/n 330186) is used to check the scale factor
of the transducer system directly on your shaft. You can compare the scale
factor of your transducer system with that of a Bently Nevada supplied 4140
steel target to check whether errors in the measurement are due to runout, target
material or a problem in the transducer system.
Troubleshooting
This section shows how to interpret a fault indication and isolate faults in an
installed transducer system. Before beginning this procedure, be sure the system
has been installed correctly and all connectors have been secured properly in the
correct locations.
When a malfunction occurs, locate the appropriate fault, check the probable
causes for the fault indication and follow the procedure to isolate and correct the
fault. Use a digital voltmeter to measure voltage. If you find faulty transducers,
contact your local Bently Nevada Corporation office for assistance.
16
Chapter 3 — Maintenance and Troubleshooting
VPS VXDCR
VSIG
Note: VSIG, VPS, and VXDCR are all negative voltage values.
Definitions
A>B "A" value is more positive than "B" -21 > -23
A<B "A" value is more negative than "B" -12 < -5
A=B "A" same value (or very close) to "B" -24.1 = -24.0
17
3300 XL Proximity Transducer System Manual
Fault Type 1: VXDCR > -17.5 Vdc or VXDCR < -26 Vdc
Possible causes:
• Faulty power source
• Faulty field wiring
• Faulty Proximitor Sensor
VPS
No
18
Chapter 3 — Maintenance and Troubleshooting
VXDCR
No
19
3300 XL Proximity Transducer System Manual
U.S.A. IN MADE
VSIG
No
Measure VSIG: Short in wiring or
at Proximitor
VSIG = 0 Vdc? Sensor terminal
connection
Yes
Faulty Proximitor
Sensor
20
Chapter 3 — Maintenance and Troubleshooting
No
Is the probe gapped correctly? Re-gap the probe
Are counterbore dimensions correct? or check
(see probe installation on page 2) counterbore.
Retest system.
Yes
Step 2 Step 1
Original probe/extension
cable
21
3300 XL Proximity Transducer System Manual
Yes
Clean connector
(using isopropyl
Inspect for clean connection. Yes alcohol or electronic
terminal cleaner),
Dirty, rusty, poor connection? reassemble and retest
the system.
No
RTOTAL
22
Chapter 3 — Maintenance and Troubleshooting
No
RPROBE
Yes
23
3300 XL Proximity Transducer System Manual
RJACKET
RCORE
Yes
24
Chapter 3 — Maintenance and Troubleshooting
VSIG
No
Measure VSIG: Faulty
Proximitor
-1.2 Vdc < VSIG < -0.3 Vdc? Sensor
Yes
Reconnect system
Regap the probe
Retest system
25
3300 XL Proximity Transducer System Manual
U.S.A. IN MADE
VSIG
Yes
Measure VSIG: Faulty
Proximitor
VSIG = VXDCR? Sensor
No
Bently Nevada is very concerned when a part fails. Please return the part with a
brief note to our corporate headquarters in Minden, Nevada for analysis if you
encounter a part that has failed.
Bently Nevada Corporation
Attn: Product Repair Department
1617 Water Street
Minden, Nevada 89423 USA
26