QRE Sen
TYPE SYJ
INSTRUCTION FOR
SUDDEN OIL PRESSURE RELAY
Shenyang STI Electrical Technology Co., Ltd.
Page 1 of 6QRE S85
1. General
Sudden oil pressure relay type SYJ-50 is a protective device for
transformer. It is activated by sudden pressure increase caused by fault in
transformer. The fast the speed of oil pressure increase, the fast it action,
quick warming and shut off power supply. Mounting sudden oil pressure relay on
transformer can prevent tank from damage when severe fault(such as
short-circuit) occurred.
2. The meaning of product type
Ss i
|
Oil pipe diameter (nominal), mm
relay
oil pressure
[
sudden
3. Specification
3.1 Scope
It applies for oil-immersed transformer or reactor.
3.2 Technical requirements.
3.2.1 Ambient temperature:-20~50°C;
3.2.2 Relative humidity: <95%, at 420°C
3. 2. 3 Power-frequency voltage 2000v 1 min can be withstand between connecting
terminals of microswitch or between active part and earth. No insulation body
overheat, breakdown, discharge occurs.
3.2.4 The contact power of microswitch:
DC220V0. 3A time factor t<5X10°S
AC220V3A power factor cos®<0.6
3.2.5 The contact of relay do not active, when vibrate frequency is
4-20Hz (sine wave), accelerate is 2~4g.
4. Construction
The construction of sudden oil pressure relay is shown as follow.
Page 2 of 6QRE S80
Fig 1 The construction of sudden oil pressure relay
5. Operation principle
During transformer normally runs, the mounting place of sudden oil pressure
relay is lower than oil lever of transformer, oil chamber of relay connect with
oil tank of transformer, separate bellow in oil pressure for balance, so sudden
oil pressure relay do not activate, If fault occurs in oil chamber increase
suddenly and exceed the safety limit, at this moment the pressure variation
occurred in the relay will compress the separate bellows and increase the
pressure chamber I. This increased pressure will deformed the operation bellows
which causes the microswitch to activate, and to send out a warning signal and
disconnecting transformer from power supply.
When a equalizer is equipped in relay, the pressure in chamber I and chamber
Il is kept balance, in transformer when internal pressure slowly increase caused
by fault, but the pressure is lower than safety limit, the pressure in chamber
I increase slowly with separate bellows displacement. Operation bellows will
not be deformed, so microswitch do not activate.
Page 3 of 6