b) Windings, C 50 C
LV side
0
25 Efficiencies at 75 C at unity power factor
a) At full load, percent 99.48 % Approx.
b) At ¾ full load, percent 99.54 % Approx.
c) At ½ full load, percent 99.56 % Approx.
d) Max efficiency 99.56% Approx.
e) Load at which max efficiency occurs 54.77 % Approx.
26 Equipment for ONAN or ONAF/ONAN cooling:
a) State:
i) Radiators on main tank Yes
ii) Separate cooler bank No
b) ONAN rating 10 MVA
c) ONAF rating Not Applicable (NA)
d) ODAF /OFWF rating Not Applicable (NA)
27 Number of coolers or cooler banks per transformer 1
28 Rating of each cooler or cooler bank 100%
29 In case of Off circuit voltage variation, state (a) or (b):
a) off circuit tap switch Not Applicable (NA)
b) off circuit tap links Not Applicable (NA)
30 Short circuit current for 2 sec on HV side
31 Terminal arrangement:
a) High voltage 72.5 kV, 800A
b) Medium voltage Not Applicable (NA)
c) Low Voltage 36 kV, 1000A
d) Tertiary Voltage Not Applicable (NA)
e) HV Neutral 36 kV, 1000A
f) LV Neutral 36 kV, 1000A
32 Approximate masses: (kg)
a) Core and windings (Active part) 13500 Approx.
b) Tank 4000 Approx.
c) Fittings, and accessories 5000 Approx.
d) Oil 4500 Approx.