Operation and Instruction Manual

emfis
R 145.0 kWh
Y 150.0 kVAh
B 38.0 kVArh

CAL

Scroll Scroll Prog


Up Down

HPL ELECTRIC & POWER PVT. LTD.


CDNEMFISRS48500-R3

1/21, Atma Ram Mansion, Asaf Ali Road, New Delhi-110 002
Phone : 23234411, 23234811, 23236811; Fax : 23232639
E-Mail : hpl@hplindia.com; Website : www.hplindia.com
This document is not contractual, HPL ELECTRIC & POWER PVT. LTD. reserves
the right to modify features without prior notice in view of continued improvements. HPL ELECTRIC & POWER PVT. LTD.
Emfis

In the CRC 16, the first OCTET Transmitted is LSB:


EXAMPLE : Development of CRC CRC 16 FLAG

Initialis ation CRC regis ter 1111 1111 1111 1111


of 1s t c harac ter 0000 0010
1111 1111 1111 1101
M ovem ent 1 0111 1111 1111 1110 1
Flag to 1, P oly nom e 1010 0000 0000 0001
1101 1111 1111 1111
M ovem ent 2 0110 1111 1111 1111 1
Flag to 1, P oly nom e 1010 0001
1100 1111 1111 1110
M ovem ent 3 0110 0111 1111 1111 0
Flag to 0 M ovem ent 4 0011 0011 1111 1111 1
101 1
1001 0011 1111 1110
M ovem ent 5 0100 1001 1111 1111 0
M ovem ent 6 0010 0100 1111 1111 1
101 1
1000 0100 1111 1110
M ovem ent 7 0100 0010 0111 1111 0
M ovem ent 8 0010 0001 0011 1111 1
101 1
1000 0001 0011 1110
2nd c harac ter 0000 0111
1000 0001 0011 1001
M ovem ent 1 0100 0000 1001 1100 1
101 1
1110 0000 1001 1101
M ovem ent 2 0111 0000 0100 1110 1
101 1
1101 0000 0100 1111
M ovem ent 3 0110 1000 0010 0111 1
101 1
1100 1000 0010 0110
M ovem ent 4 0110 0100 0001 0011 0
M ovem ent 5 0011 0010 0000 1001 1
101 1
1001 0010 0000 1000
M ovem ent 6 0100 1001 0000 0100 0
M ovem ent 7 0010 0100 1000 0010 0
M ovem ent 8 0001 0010 0100 0001 0

Operation and Instruction Manual 17


Emfis Emfis

Guide to CRC 16 Calculation :

Contents

1. General Information ........................................ 2

2. Programming .................................................. 4

3. Communication …...………………………….… 6
n=0

MOVEMENT TO THE
RIGHT CRC 16

No CARRY OVER Yes

n=n+1

No n>1 Yes

NEXT BYTE

No MESSAGE TERMINATED Yes

END

Operation and Instruction Manual 16 Operation and Instruction Manual 1


Emfis Emfis

1. General Information Range and Default Value of Programming Parameter

PARAMETER RANGE DEFAULT VALUE


1.1 Function: CT Ratio
This model of Emfis with RS485 provides communication facility on RS485 Primary 5-6000 in step of 5 for -/5 500

MODBUS. Emfis with RS485 works on a master slave configuration, where the 1-1200 in step of 5 for -/1
Secondary -/1A or -/5A -/5A
Emfis is the slave and the master can be computer / PLC etc.
Slave Address 1-255 5
The following are also supplied with this model: Baud Rate 4800 / 9600 / 19200 bps 9600 bps
2 numbers 120Ω End-Of-Line resistance. Table 1.0
Example : For CT Secondary Writting.
1.2 General Points: Slave Function Higher Low Number Number No. of Data CRC CRC
Address code order order of word of word byte High low
address address high low
For standard configuration, RS 485 serial link 2 wire is used to connect 255
0x0005 0x0010 0x388 0x0001 0x0002 0x0005 0x791B
Emfis with one RS232 port on the master (computer/PLC etc.) over a distance
of 1200 meters using MODBUS protocol. 3.3 Reset Parameters (Reset to Zero):
kW & kVA MD with Date Time
1.3 Typical Network Architecture:
Run Hour
Power On Hours

Address Table
RS 485 RS 232 HEX DECIMAL No. OF
PARAMETER ADDRESS ADDRESS WORDS UNIT

emfis emfis
kW MD 0x375 885 1 MW/100
emfis
R 145.0 kWh R 145.0 kWh R 145.0 kWh
Y 150.0 kVAh Y 150.0 kVAh Y 150.0 kVAh
38.0 kVArh B 38.0 kVArh
38.0 kVArh
RUN HOUR 0x38A 906 2 Hour/100
B
B

CAL
CAL
CAL
Scroll Scroll Prog
Scroll Scroll Prog Down
Prog Up
Scroll Scroll Up Down
Up Down

POWER ON HOURS(Auxiliary) 0x38C 908 2 Hour/100

Cables and RS485/232 converter, computer are not supplied with this
Example: For Resetting the kW MD
Emfis meter.
Slave Function Higher Low Number Number No. of Data CRC CRC
Address code order order of word of word byte High low
Recommendation: Please use a shielded twisted pair cable for connection address address high low
A repeater should be used if one intends to exceed the cable distance of over 0x0005 0x0010 0x036B 0x0001 0x0002 0x007B* 0xEF68
1200 meters.
*007B i.e. 1234 is the Default Programming Password

Operation and Instruction Manual 2 Operation and Instruction Manual 15


Emfis Emfis

An example has been given using WINBUS32 S/w. 1.4 Connection Diagram:
Example 1: To read Second, Minute & Hour.
Slave Function Higher Low Number Number No. of CRC CRC
Address code order order of word of word byte High low RS 485 Bus
address address high low
+RX -RX
0x0005 0x0003 0x0383 0x0003 0x0006 0xF5E3
P A

N U
X RS 485

RS 485/232
3.2 Writing Parameters: L1
AUX. SUPPLY =
I1
S1
Converter
230±30%, ac S2
L2
Writing Frame L3
S1
I2
N S2 Master
Slave Function Address No. Of No. of Data CRC 16
Address Code Word Bytes S1
I3
S2

Function Code 16: For Writing, Maximum Word Length is 10 words. 120Ω
End-Of-Line
Resistance
Address Table +Rx -Rx
RS485
PARAMETER HEX DECIMAL No. OF Unit
ADDRESS ADDRESS WORDS
Note: This serial communication requires 120Ω end-of-line resistance to be connected on first and last
device in an RS485 MODBUS network.
SECOND 0x381 897 1 Sec
The End Of-Line resistance supplied with Emfis is to be connected between Rx- and Rx+ as shown
MINUTE 0x382 898 1 Min above.

HOUR 0x383 899 1 Hrs


1.5 RS485 configuration :
DATE 0x384 900 1 DD
Baud Rate : 4800 / 9600 / 19200 bps
MONTH 0x385 901 1 MM Stop Bit : 1
YEAR 0x386 902 1 YY Byte size : 8 Bit

CT RATIO 0x387 903 1


Parity : None

CT SECONDARY 0x388 904 1


1 : Secondary 1
5 : Secondary 5

Operation and Instruction Manual 14 Operation and Instruction Manual 3


Emfis Emfis

2. Programming PARAMETER STARTING No. OF No. OF UNIT


ADDRESS BYTES WORDS
To access / view the programming mode:
DATE 0x45B 1115 1 DD
Keys Instruction Display Comment
MONTH 0x45C 1116 1 MM
Prog Press Once You are now in programming
PS mode. Password has to be
YEAR 0x45D 1117 1 YY
0--- Entered. 5th Last Month kVA MD 0x45E 1118 1 kVA/10
2.1 Enter the access code '1234’ (default password) to access the programming MINUTE 0x45F 1119 1 Min
mode:
HOUR 0x460 1120 1 Hrs
Keys Instruction Display Comment
DATE 0x461 1121 1 DD
Scroll up Press Once PS Digit increment by 1.
1-- - MONTH 0x462 1122 1 MM

Scroll down Press Once PS Moves one digit right. YEAR 0x463 1123 1 YY
10--
6th Last Month kWh 0x464 1124 2 kWh/10
Scroll up Press Twice PS Digit increment by 2.
12-- 6th Last Month kVAh 0x466 1126 2 kVAh/10

6th Last Month kVArh Lag 0x468 1128 2 Lag/10


Scroll down Press Once PS Moves one digit right.
120- 6th Last Month kVArh Lead 0x46A 1130 2 Lead/10

Scroll up Press Thrice PS Digit increment by 3. 6th Last Month kW MD 0x46C 1132 1 kW/10
123-
MINUTE 0x46D 1133 1 Min
Scroll down Press Once PS Moves one digit right.
1230 HOUR 0x46E 1134 1 Hrs

Scroll up Press Four Time PS Digit increment by 4. DATE 0x46F 1135 1 DD


1234
MONTH 0x470 1136 1 MM
Prog Press Once PS To Configure Password.
1234 YEAR 0x471 1137 1 YY

If your password is correct ‘1234’ (default password) you can see all setting parameters 6th Last Month kVA MD 0x472 1138 1 kVA/10
using Scroll up/Scroll down button. MINUTE 0x473 1139 1 Min

2.2 Set Slave Address: HOUR 0x474 1140 1 Hrs

Keys Instruction Display Comment DATE 0x475 1141 1 DD

Sl Default slave address. MONTH 0x476 1142 1 MM


005
YEAR 0x477 1143 1 YY

Operation and Instruction Manual 4 Operation and Instruction Manual 13


Emfis Emfis

PARAMETER HEX DECIMAL No. OF UNIT


Prog Press Once
Sl Setting a new value.
ADDRESS ADDRESS WORDS
0--
YEAR 0x43B 1083 1 YY
Scroll up Press Once
Sl Digit increment by 1.
4th Last Month kWh 0x43C 1084 2 kVAh/10
1 --
Scroll down Press Once
Sl Moves 1 digit to right.
4th Last Month kVAh 0x43E 1086 2 kVAh/10
10 -
4th Last Month kVArh Lag 0x440 1088 2 Lag/10
Scroll up Press twice
Sl Digit increment by 2.
4th Last Month kVArh Lead 0x442 1090 2 Lead/10
12-
Scroll down Press Once
Sl Moves 1 digit to right.
4th Last Month kW MD 0x444 1092 1 kW/10
120
MINUTE 0x445 1093 1 Min
Scroll up Press thrice
Sl Digit increment by 3.
HOUR 0x446 1094 1 Hrs
123
Slave Address setting
Prog Press Once completed successfully.
DATE 0x447 1095 1 DD

MONTH 0x448 1096 1 MM

YEAR 0x449 1097 1 YY 2.3 Set Baud Rate (4800/9600/19200)


4th Last Month kVA MD 0x44A 1098 1 kVA/10 Keys Instruction Display Comment
MINUTE 0x44B 1099 1 Min
Prog Press Once Default Baud Rate.
HOUR 0x44C 1100 1 Hrs

DATE 0x44D 1101 1 DD Scroll up Press Once Next.

MONTH 0x44E 1102 1 MM


Scroll up Press Once Next.
YEAR 0x44F 1103 1 YY

5th Last Month kWh 0x450 1104 2 kWh/10 Scroll up Press Once Next.

5th Last Month kVAh 0x452 1106 2 kVAh/10


Successfully set
Prog Press Once New Baud Rate (19200).
5th Last Month kVArh Lag 0x454 1108 2 Lag/10

5th Last Month kVArh Lead 0x456 1110 2 Lead/10

5th Last Month kW MD 0x458 1112 1 kW/10

MINUTE 0x459 1113 1 Min

HOUR 0x45A 1114 1 Hrs

Operation and Instruction Manual 12 Operation and Instruction Manual 5


Emfis Emfis

PARAMETER HEX DECIMAL No. OF UNIT


3. Communication ADDRESS ADDRESS WORDS

The MODBUS used by the Emfis involves a dialogue using a Master-Slave structure. DATE 0x41F 1055 1 DD
The mode of communication is the RTU (Remote Terminal Unit) using hexadecimal
MONTH 0x420 1056 1 MM
characters of at least 8 bit.
YEAR 0x421 1057 1 YY
3.1 Reading Parameters
2nd Last Month kVA MD 0x422 1058 1 kVA/10
The Standard Reading Communication frame consists of
MINUTE 0x423 1059 1 Min
Device Function Address Data CRC16
address Code HOUR 0x424 1060 1 Hrs

Function Code 3: For Reading Maximum Word length is 40 words. DATE 0x425 1061 1 DD

Address Table MONTH 0x426 1062 1 MM

INSTANTANEOUS HEX DECIMAL No. OF UNIT YEAR 0x427 1063 1 YY


PARAMETER ADDRESS ADDRESS WORDS
3rd Last Month kWh 0x428 1064 2 kWh/10
SERIAL NUMBER_H. 0X340 832 1
3rd Last Month kVAh 0x42A 1066 2 kVAh/10
SERIAL NUMBER_L. 0X341 833 1
3rd Last Month kVArh Lag 0x42C 1068 2 Lag/10
R-PHASE TO NEUTRAL VOLTAGE 0X342 834 1 Volt/10
3rd Last Month kVArh Lead 0x42E 1070 2 Lead/10
Y-PHASE TO NEUTRAL VOLTAGE 0X343 835 1 Volt/10
3rd Last Month kW MD 0x430 1072 1 kW/10
B-PHASE TO NEUTRAL VOLTAGE 0x344 836 1 Volt/10
MINUTE 0x431 1073 1 Min
PHASE TO PHASE VOLTAGE (R-Y) 0x345 837 1 Volt/10
HOUR 0x432 1074 1 Hrs
PHASE TO PHASE VOLTAGE (Y-B) 0x346 838 1 Volt/10
DATE 0x433 1075 1 DD
PHASE TO PHASE VOLTAGE (B-R) 0x347 839 1 Volt/10
MONTH 0x434 1076 1 MM
R-PHASE CURRENT 0x348 840 1 Amp/10
YEAR 0x435 1077 1 YY
Y-PHASE CURRENT 0x349 841 1 Amp/10
3rd Last Month kVA MD 0x436 1078 1 kVA/10
B-PHASE CURRENT 0x34A 842 1 Amp/10
MINUTE 0x437 1079 1 Min
R-PHASE AVERAGE CURRENT 0x34B 843 1 Amp/10
HOUR 0x438 1080 1 Hrs
Y-PHASE AVERAGE CURRENT 0x34C 844 1 Amp/10
DATE 0x439 1081 1 DD
B-PHASE AVERAGE CURRENT 0x34D 845 1 Amp/10
MONTH 0x43A 1082 1 MM

Operation and Instruction Manual 6 Operation and Instruction Manual 11


Emfis Emfis

Last 6 Months History Data PARAMETER HEX DECIMAL No. OF UNIT


ADDRESS ADDRESS WORDS
PARAMETER HEX DECIMAL No. OF UNIT
ADDRESS ADDRESS WORDS R-PHASE MAXIMUM CURRENT 0x34E 846 1 Amp/10

Last Month kWh 0x400 1024 2 kWh/10 Y-PHASE MAXIMUM CURRENT 0x34F 847 1 Amp/10

Last Month kVAh 0x402 1026 2 kVAh/10 B-PHASE MAXIMUM CURRENT 0x350 848 1 Amp/10

Last Month kVArh Lag 0x404 1028 2 Lag/10 TOTAL CURRENT 0x351 849 1 Amp

Last Month kVArh Lead 0x406 1030 2 Lead/10 ACTIVE POWER (R-PHASE ) 0x352 850 1 kW/10

Last Month kW MD 0x408 1032 1 kW/10 ACTIVE POWER (Y-PHASE) 0x353 851 1 kW/10

MINUTE 0x409 1033 1 Min ACTIVE POWER (B-PHASE) 0x354 852 1 kW/10

HOUR 0x40A 1034 1 Hrs APPARENT POWER (R-PHASE ) 0x355 853 1 kVA/10

DATE 0x40B 1035 1 DD APPARENT POWER (Y-PHASE) 0x356 854 1 KVA/10

MONTH 0x40C 1036 1 MM APPARENT POWER (B-PHASE) 0x357 855 1 kVA/10

YEAR 0x40D 1037 1 YY REACTIVE POWER (R-PHASE ) 0x358 856 1 kVAR/10

Last Month kVA MD 0x40E 1038 1 kVA/10 REACTIVE POWER (Y-PHASE) 0x359 857 1 KVAR/10

MINUTE 0x40F 1039 1 Min REACTIVE POWER (B-PHASE) 0x35A 858 1 KVAR/10

HOUR 0x410 1040 1 Hrs POWER FACTOR (R-PHASE) 0x35B 859 1 .01

DATE 0x411 1041 1 DD POWER FACTOR (Y-PHASE) 0x35C 860 1 .01

MONTH 0x412 1042 1 MM POWER FACTOR (B-PHASE) 0x35D 861 1 .01

YEAR 0x413 1043 1 YY SYSTEM POWER FACTOR 0x35E 862 1 .01

2nd Last Month kWh 0x414 1044 2 kWh/10 Σ ACTIVE POWER 0x35F 863 1 kW/10

2nd Last Month kVAh 0x416 1046 2 kVAh/10 Σ APPARENT POWER 0x360 864 1 kVA/10

2nd Last Month kVArh Lag 0x418 1048 2 Lag/10 Σ REACTIVE POWER 0x361 865 1 kVAR/10

2nd Last Month kVArh Lead 0x41A 1050 2 Lead/10 AVERAGE VALUE Σ ACTIVE POWER 0x362 866 1 kW/10

2nd Last Month kW MD 0x41C 1052 1 kW/10 AVERAGE VALUE Σ APPARENT POWER 0x363 867 1 kVA/10

MINUTE 0x41D 1053 1 Min AVERAGE VALUE Σ REACTIVE POWER 0x364 868 1 kVAR/10

HOUR 0x41E 1054 1 Hrs MAXIMUM VALUE Σ ACTIVE POWER 0x365 869 1 kW/10

Operation and Instruction Manual 10 Operation and Instruction Manual 7


Emfis Emfis

PARAMETER HEX DECIMAL No. OF UNIT PARAMETER HEX DECIMAL No. OF UNIT
ADDRESS ADDRESS WORDS ADDRESS ADDRESS WORDS
MAXIMUM VALUE Σ APPARENT POWER 0x366 870 1 kVA/10 kVA MD HOUR 0x37D 893 1 HOUR

MAXIMUM VALUE Σ REACTIVE POWER 0x367 871 1 kVAR/10 kVA MD DATE 0x37E 894 1 DATE

FREQUENCY 0x368 872 1 Hz/100 kVA MD MONTH 0x37F 895 1 MONTH

ACTIVE ENERGY <1000.0 0x369 873 1 kWh/10 kVA MD YEAR 0x380 896 1 YEAR

ACTIVE ENERGY >1000.0 0x36A 874 1


RTC
APPARENT ENERGY <1000.0 0x36B 875 1 kVAh/10
SECOND 0x381 897 1 SECOND
APPARENT ENERGY >1000.0 0x36C 876 1
MINUTE 0x382 898 1 MINUTE
REACTIVE ENERGY LAG <1000.0 0x36D 877 1 kVArh/10 HOUR 0x383 899 1 HOUR

REACTIVE ENERGY LAG >1000.0 0x36E 878 1 DATE 0x384 900 1 DATE

REACTIVE ENERGY LEAD <1000.0 0x36F 879 1 kVArh/10 MONTH 0x385 901 1 MONTH

REACTIVE ENERGY LEAD >1000.0 0x370 880 1 YEAR 0x386 902 1 YEAR

RUN ON HOUR <100.00 0x371 881 1 HOUR/100 CT RATIO 0x387 903 1

RUN ON HOUR >100.00 0x372 882 1 CT SECONDARY 0x388 904 1

POWER ON HOUR <100.00 0x373 883 1 HOUR/100

POWER ON HOUR >100.00 0x374 884 1

MD Read or Reset Energy & Hours in Long


PARAMETER HEX DECIMAL No. OF UNIT
kW MD 0x375 885 1 kW/10
ADDRESS ADDRESS WORDS
kW MD MINUTE 0x376 886 1 MINUTE RUN HOUR 0x389 905 2 Hour/100
kW MD HOUR 0x377 887 1 HOUR POWER ON HOUR (Auxiliary) 0x38B 907 2 Hour/100

kW MD DATE 0x378 888 1 DATE ACTIVE ENERGY 0x38D 909 2 kWh/10

kW MD MONTH 0x379 889 1 MONTH APPARENT ENERGY 0x38F 911 2 kWh/10

kW MD YEAR 0x37A 890 1 YEAR REACTIVE ENERGY LAG 0x391 913 2 kVArh/10

KVA MD 0x37B 891 1 kVA/10 REACTIVE ENERGY LEAD 0x393 915 2 kVArh/10

KVA MD MINUTE 0x37C 892 1 MINUTE

Operation and Instruction Manual 8 Operation and Instruction Manual 9