M Family Voltage/Frequency Relay

Three-phase and ground


voltage protection relay.

9
Features and Benefits Applications
■ Advanced 16-bit microprocessor ■ Voltage and/or frequency protection at any
■ Configurable logic, curves, digital I/Os, voltage in automatic transfer systems,
and LEDs generators, motors, lines and busbars
■ Flash memory for field upgrades ■ enerVista.com compatible (see page 275)
■ Two settings groups Protection and Control
■ Three models available for voltage, ■ Three-phase over and undervoltage,
frequency and combined protection ground overvoltage
■ Drawout case for easy maintenance ■ Voltage unbalance, over and
■ AC/DC power supply underfrequency
■ Access via front panel keypad or Monitoring and Metering
communication links
■ Frequency and per-phase voltage
■ Diagnostic features – event recording
and analog/digital oscillography User Interfaces
■ Compatible with M Family systems in ■ M+PC software for setting and
half or full 19" racks monitoring
■ Front RS232 and rear RS485 ports using
ModBus® RTU protocol up to 19,200 bps

GE Multilin 1
MIV M Family Voltage/Frequency Relay

Protection are located on the line side, a Configurable Logic


setting is provided to enable/ Up to four configurable logic
The MIV, a member of the M disable undervoltage protection
Family, is a digital device that schemes can be implemented via
units. four pre-configured logic gates and
provides voltage and frequency
protection for a wide range of timer cells. A graphical user inter-
Ground Overvoltage face provides easy configuration.
applications at any voltage level:
Two separately adjustable ground The configurable logic output can
NOTE: The MIV1000 includes volt- be used to configure digital
overvoltage units can be inde-
age functions, the MIV2000 outputs and LEDs.
pendently enabled. The pickup
includes frequency functions (four
setpoint can be set from 2 to
units), and the MIV3000 includes
250 V depending on the model
both voltage and frequency (two)
and a time delay from 0 to 600
MIV Guideform
units.
seconds. Specifications
Phase Overvoltage For an electronic version of the MIV
Voltage Unbalance guideform specifications, please
Two separately adjustable phase visit: www.GEindustrial.com/
This function operates on nega-
overvoltage units can be inde- Multilin/specs, fax your request
tive sequence voltage, and is
pendently enabled. The pickup set- to 905-201-2098 or email to
included in the MIV 3000 relay.
point can be set from 2 to 250 V literature.multilin@indsys.ge.com.
Pickup and time delay settings are
depending on the model, and a
the same as those of voltage
time delay from 0 to 600 seconds.
functions.
The protection units operate on
phase-to-phase or phase-to-
ground voltage magnitudes. Frequency Functions
Depending on the model, either
Phase Undervoltage two or four independent definite
time frequency units are provided.
This function has the same settings
Each unit can be independently
and features as the phase over-
set as over and underfrequency,
voltage protection. To avoid
and is supervised by an independ-
permanent undervoltage tripping
ently adjustable undervoltage
when a breaker is open and the VTs
element.

9
Functional Block Diagram

BUS

52 3

2x27 2x59 2x59N 2x81O/ 47


81U

LOAD
MIV 3000
743751A1.ai

2 www.GEindustrial.com/Multilin
MIV M Family Voltage/Frequency Relay

Typical Wiring
OPEN DELTA VT CONNECTION DIRECTION OF TRIP SINGLE PHASE VT CONNECTION
A A NOTE: 14 AWG wiring A
recommended
B B B
AC
C C C
or
DC

B1 B2 B3 B4 A3 A4 B1 B2 B3 B4 A3 A4 A1 A2 B1 B2 B3 B4 A3 A4
VI N VII N VIII N VI N VII N VIII N +/L -/N VI N VII N VIII N
POWER
VOLTAGE INPUTS VOLTAGE INPUTS Internally fused VOLTAGE INPUTS
1A/250V fast blow

GE Multilin SDA B12(*) A

RS485
52a 52a

MIV SDB A12(*)


TRIP COIL -
TRIP
<< >> A5
B
TRIP

COIL
CONTROL M-Family
Voltage/Frequency GND B11(*) GROUND
POWER + A6
Relay PROGRAMMABLE
CAUTION: Fork or ring terminals must be used on the CONTROLLER

COM OUT4 OUT3 OUT1/2 OUT1


termainal block. B7
READY

INPUT
NOTE: Suitable disconnect devices (switch or circuit B5
breaker) recommended located near the relay. INPUT
OVERVOLTAGE CATEGORY: II B6 DIGITAL OUTPUTS(**)
(*) Terminals B12, A12 and B11 must be connected to WYE-BROKEN-DELTA
SELV (safety extra-lowvoltage) parts (on the PLC). B8 VT CONNECTION
They are not to be tested for hipot test under any A
INTPUTS(**)

circumstance. A8 CC1 JX B
DIGITAL

(**)The default configuration of inputs and outputs C


is as follows:
INPUTS A9 CC2 B9
CC1: Block unit 78
CC2: Block voltage A10 COM
functions
OUTPUTS B10 B1 B2 B3 B4 A3 A4
OUT1: 78 Trip RS232
OUT2: 59/27 Trip VI N VII N VIII N
OUT3:59N Trip SAFETY
OUT4: 81 Trip GROUND
GND GROUND A7
BUS VOLTAGE INPUTS
9
743750a4.ai

Ordering
MIV * 0 * 0E000 * 00 *
MIV Voltage/frequency relay
1 Voltage functions
2 Frequency functions
3 Voltage + frequency functions
0 10 – 250 V setting range
1 2 – 60 V setting range
F 24 – 48 VDC auxiliary voltage
H 110 – 250 VDC 110 – 230 VAC auxiliary voltage
C Individual relay
S Mounted in an M+ system†

†If relays are to be mounted in an M+ system either an M050 half 19" rack or M100 full 19" rack case must be ordered. The M050 and M100 racks are provided at no additional cost.

Accessories
B1315P2 Depth reducing collar

enerVista enabled See page 275.


www.enerVista.com

www.GEindustrial.com/Multilin 3