Features and Benefits Applications
■ Advanced 16-bit microprocessor ■ Voltage and/or frequency protection at any
■ Configurable logic, curves, digital I/Os, voltage in automatic transfer systems,
and LEDs generators, motors, lines and busbars
■ Flash memory for field upgrades ■ enerVista.com compatible (see page 275)
■ Two settings groups Protection and Control
■ Three models available for voltage, ■ Three-phase over and undervoltage,
frequency and combined protection ground overvoltage
■ Drawout case for easy maintenance ■ Voltage unbalance, over and
■ AC/DC power supply underfrequency
■ Access via front panel keypad or Monitoring and Metering
communication links
■ Frequency and per-phase voltage
■ Diagnostic features – event recording
and analog/digital oscillography User Interfaces
■ Compatible with M Family systems in ■ M+PC software for setting and
half or full 19" racks monitoring
■ Front RS232 and rear RS485 ports using
ModBus® RTU protocol up to 19,200 bps
GE Multilin 1
MIV M Family Voltage/Frequency Relay
9
Functional Block Diagram
BUS
52 3
LOAD
MIV 3000
743751A1.ai
2 www.GEindustrial.com/Multilin
MIV M Family Voltage/Frequency Relay
Typical Wiring
OPEN DELTA VT CONNECTION DIRECTION OF TRIP SINGLE PHASE VT CONNECTION
A A NOTE: 14 AWG wiring A
recommended
B B B
AC
C C C
or
DC
B1 B2 B3 B4 A3 A4 B1 B2 B3 B4 A3 A4 A1 A2 B1 B2 B3 B4 A3 A4
VI N VII N VIII N VI N VII N VIII N +/L -/N VI N VII N VIII N
POWER
VOLTAGE INPUTS VOLTAGE INPUTS Internally fused VOLTAGE INPUTS
1A/250V fast blow
RS485
52a 52a
COIL
CONTROL M-Family
Voltage/Frequency GND B11(*) GROUND
POWER + A6
Relay PROGRAMMABLE
CAUTION: Fork or ring terminals must be used on the CONTROLLER
INPUT
NOTE: Suitable disconnect devices (switch or circuit B5
breaker) recommended located near the relay. INPUT
OVERVOLTAGE CATEGORY: II B6 DIGITAL OUTPUTS(**)
(*) Terminals B12, A12 and B11 must be connected to WYE-BROKEN-DELTA
SELV (safety extra-lowvoltage) parts (on the PLC). B8 VT CONNECTION
They are not to be tested for hipot test under any A
INTPUTS(**)
circumstance. A8 CC1 JX B
DIGITAL
Ordering
MIV * 0 * 0E000 * 00 *
MIV Voltage/frequency relay
1 Voltage functions
2 Frequency functions
3 Voltage + frequency functions
0 10 – 250 V setting range
1 2 – 60 V setting range
F 24 – 48 VDC auxiliary voltage
H 110 – 250 VDC 110 – 230 VAC auxiliary voltage
C Individual relay
S Mounted in an M+ system†
†If relays are to be mounted in an M+ system either an M050 half 19" rack or M100 full 19" rack case must be ordered. The M050 and M100 racks are provided at no additional cost.
Accessories
B1315P2 Depth reducing collar
www.GEindustrial.com/Multilin 3