ENERGYPAC
POWER TRANSFORMER TESTING LABORATORY FORM NO. : EELF /11
REF : EELF/TR-30/35 Dated : 30-09-11
REV : SL. NO: 30/35-4-0023/1700 0001
Terminal Notation : A B C N a b c
Rated Capacity in MVA
ONAN : 30 30
ONAF : 35 35
Standard : BS-171/IEC-76
LV Voltage : 11000 Volts in all Tap Positions.
ENERGYPAC
POWER TRANSFORMER TESTING LABORATORY FORM NO. : EELF /11
REF : EELF/TR-30/35 Dated : 30-09-11
REV : SL. NO: 30/35-4-0023/1700 0001
Currents in Ampere
Tap Position Voltage
30 MVA 35 MVA
1 145200 139.17 119.29
2 143550 140.77 120.66
3 141900 142.40 122.06
4 140250 144.08 123.50
5 138600 145.80 124.97
6 136950 147.55 126.47
7 135300 149.35 128.02
8 133650 151.20 129.60
9 132000 153.09 131.22
10 130350 155.02 132.88
11 128700 157.01 134.58
12 127050 159.05 136.33
13a 125400 161.14 138.12
13b 125400 161.14 138.12
13c 125400 161.14 138.12
14 123750 163.29 139.96
15 122100 165.50 141.86
16 120450 167.76 143.80
17 118800 170.09 145.80
18 117150 172.49 147.85
19 115500 174.95 149.96
20 113850 177.49 152.13
21 112200 180.10 154.37
22 110550 182.79 156.68
23 108900 185.56 159.05
24 107250 188.41 161.50
25 105600 191.36 164.02
ENERGYPAC
POWER TRANSFORMER TESTING LABORATORY FORM NO. : EELF /11
REF : EELF/TR-30/35 Dated : 30-09-11
REV : SL. NO: 30/35-4-0023/1700 0001
ENERGYPAC
POWER TRANSFORMER TESTING LABORATORY FORM NO. : EELF /11
REF : EELF/TR-30/35 Dated : 30-09-11
REV : SL. NO: 30/35-4-0023/1700 0001
REMARKS: The Voltage Ratio between HT & LT Side of the Transformer for every Tap position is OK.
Polarity of the Transformer is OK.
The vector Group of the Transformer is YNd1.
** Turn Ratio is measured by Eltel Turn Ratio Meter (Model TRM 100.)
Manufactured by Eltel Industries, Bangalore, India , Calibrated by Cali-Labs, Bhopal, India,
Test Performed by Checked by
ENERGYPAC
POWER TRANSFORMER TESTING LABORATORY FORM NO. : EELF /11
REF : EELF/TR-30/35 Dated : 30-09-11
REV : SL. NO: 30/35-4-0023/1700 0001
Tap Position : 9
Temperature : 30 C
LT Side
a -b : 12.08 m ohms
b- c : 11.92 m ohms
c -a : 12.27 m ohms
Average : 12.09 m ohms
HT Side
ENERGYPAC
POWER TRANSFORMER TESTING LABORATORY FORM NO. : EELF /11
REF : EELF/TR-30/35 Dated : 30-09-11
REV : SL. NO: 30/35-4-0023/1700 0001
Measurement of
No-Load Loss and No-Load Current
Test Frequency : 50 Hz
Tap Position : 9 [Principal Tap]
** Digital Power Analyzer WT-230 Calibrated by Cali-Labs, Bhopal, India, Calibration due on 28-08-
2012.
ENERGYPAC
POWER TRANSFORMER TESTING LABORATORY FORM NO. : EELF /11
REF : EELF/TR-30/35 Dated : 30-09-11
REV : SL. NO: 30/35-4-0023/1700 0001
Supply from LV Side with HV Side shorted at Principal Tap at Rated Current
Temperature : 30 C
Rated Applied
Applied Watt meter Watt meter Watt meter
Current Voltage Remarks
Current (A) Reading (W1) Reading (W2) Reading (W3)
(A) (V)
IA = 1135 VA-N = 623
CT Ratio= 300
IB = 1146 VB-N = 642
1574.6 35 31 38 PT Ratio=10
IC = 1137 VC-N = 615
IAVG =1139 VAVG = 627
At 30C
% Impedance = 13.648
** Digital Power Analyzer WT-230 Calibrated by Cali-Labs, Bhopal, India, Calibration due on 28-08-
2012 .
ENERGYPAC
POWER TRANSFORMER TESTING LABORATORY FORM NO. : EELF /11
REF : EELF/TR-30/35 Dated : 30-09-11
REV : SL. NO: 30/35-4-0023/1700 0001
ENERGYPAC
POWER TRANSFORMER TESTING LABORATORY FORM NO. : EELF /11
REF : EELF/TR-30/35 Dated : 30-09-11
REV : SL. NO: 30/35-4-0023/1700 0001
ENERGYPAC
POWER TRANSFORMER TESTING LABORATORY FORM NO. : EELF /11
REF : EELF/TR-30/35 Dated : 30-09-11
REV : SL. NO: 30/35-4-0023/1700 0001
VB-C = 401 V
VC-A= 398 V
As the terminal voltage across A-b > Voltage across All Other Terminals & B-b = A-a = B-a ,
The Vector Group Test is confirmed as YNd1.
** Voltage measured by HIOKI 3261 Digital Meter, manufactured by HIOKI, Japan , Calibrated by
Cali-Labs, Bhopal, India, Calibration due on 28-08-2012 .
ENERGYPAC
POWER TRANSFORMER TESTING LABORATORY FORM NO. : EELF /11
REF : EELF/TR-30/35 Dated : 30-09-11
REV : SL. NO: 30/35-4-0023/1700 0001
LV / HV + Earth : 22 kV at 50Hz
for 60 seconds
** High voltage test is Performed by 500 kV High Voltage Transformer , manufactured by JIANGDU
SHENGHUA HIGH VOLTAGE ELECTRICAL EQUIPMENT CO., China , by Cali-Labs, Bhopal,
India, Calibration due on 28-08-2012.
ENERGYPAC
POWER TRANSFORMER TESTING LABORATORY FORM NO. : EELF /11
REF : EELF/TR-30/35 Dated : 30-09-11
REV : SL. NO: 30/35-4-0023/1700 0001
HV Tap Position :1
Applying 16.835 KV across a-b Terminal , Keeping B-C shorted & earthed @ 150 HZ
For 40 Sec
Ia = 3.56 Amp
Applying 16.835 KV across b-c Terminal , Keeping C - A shorted @ 150 HZ For 40 Sec
Ib = 3.4 Amp
Voltage measured in Terminal B = 275 KV
Ic = 3.51 Amp
** All data of Induced Over Voltage Withstand test is measured by Digital Power Analyzer WT-230
manufactured by YOKOGAWA , Japan
ENERGYPAC
POWER TRANSFORMER TESTING LABORATORY FORM NO. : EELF /11
REF : EELF/TR-30/35 Dated : 30-09-11
REV : SL. NO: 30/35-4-0023/1700 0001
TEST OF OLTC
OK
1. OPEERATION BY HANDLE …………………………………………… _____________
OK
2. RAISE OPERATION ……………………………………………………………….. _____________
OK
3. LOWER OPERATION ……………………………………………………………….. _____________
OK
4. STEP-BY-STEP OPERATION AT LOAD CONDITION …………………….. _____________
OK
5. TAP POSITION INDICATOR ……………………………………………….. _____________
OK
6. EARTHING POINT …………………………………………………………… _____________
OK
7. VISIUAL CHECK …………………………………………………………… _____________
ENERGYPAC
POWER TRANSFORMER TESTING LABORATORY FORM NO. : EELF /11
REF : EELF/TR-30/35 Dated : 30-09-11
REV : SL. NO: 30/35-4-0023/1700 0001
Temperature : 30c
ENERGYPAC
POWER TRANSFORMER TESTING LABORATORY FORM NO. : EELF /11
REF : EELF/TR-30/35 Dated : 30-09-11
REV : SL. NO: 30/35-4-0023/1700 0001
Serial Measured
Particulars Units Remarks
No Value
01 Visual Inspection OK
02 Measurement of Insulation Mega-ohms
OK
Resistance
03 Measurement of Turn-ratio OK
04 Measurement of Winding OK
Resistance
05 No-load Loss KW 27.7 OK
06 Load Loss at Principal KW OK
Tap Position 9 ( 35 MVA 274.51
Base )
07 Impedance at Principal Tap % 15.922 OK
position 9 ( 35 MVA Base )
08 Vector Group Test YNd1 OK
09 Power Frequency Withstand Withstood
Test
10 Combined Induced Over Withstood
Voltage & Power
frequency Withstand
Test
11 Test of On Load Tap OK
Changer
12 Di-Electric strength kV Satisfactory
measurement of Transformer 60
Oil