Vous êtes sur la page 1sur 9

continuous-current rating increases the used.

used. I had hoped to read that they had low-voltage air circuit breakers appears to
specific loading of the main current-carrying provided a better means of adjustment for be an improvement in design of this manu-
elements does not decrease as one would the long-time delay, and at least some facturer's circuit breakers. However, the
expect, thinking in terms of the skin effect adjustment for the short-time delay. My stored-energy closing mechanism seems to
at higher current capacities. I am curious company has found that both these adjust- be more complex than a solenoid mecha-
regarding this. ment features are most desirable from the nism. I believe that a hazard exists to main-
Regarding the second item I mentioned, user's standpoint, especially in selective tenance personnel, inasmuch as the closing
the use of a stored-energy closing mechanism tripping applications. The introduction of mechanism is energized when in the open
certainly answers the problem of closing a a completely new line of circuit breakers position. Although provision is made for
breaker when the control source is taken should certainly not carry with it certain blocking the loaded springs, I believe that a
from the primary circuit. The question definite limitations of the superseded line. means of automatically unloading the spring
then naturally arises: is this advantage I find no reference in this paper to 5,000- mechanism when the breaker is withdrawn
worth the increased complexity and loss of and 6,000-ampere frame breakers, and I from its cubicle or blocking so that the
accessibility wheich is thereby encoun- should like to ask what the General Electric breaker cannot be withdrawn beyond the
tered? In place of two time-proven devices, Company intends to do in these sizes. test position unless the springs have been
namely, the solenoid and control relay, we Even though these sizes may not remain released would provide sufficient safety.
now find a motor and its control scheme, standard in the future, there will always be The overcurrent trip devices are satis-
plus a 1,000-to-1 reduction unit, springs, considerable application for them. There- factory for general applications; however,
mechanisms, cams, etc., all undoubtedly fore, is it the intention of this company to for essential auxiliary motor feeds in power
critical in their adjustments and in their extend their developments higher, or will plants it would be desirable to have high-
relations to each other. they continue to offer their present equip- current instantaneous trip on three poles for
Very little is said in this paper regarding ment which would now appear rather obso- fault protection, long inverse time delay on
the overcurrent trip devices, other than that lete by comparison with their new line? at least two poles for overload protection,
the direct-acting principle has been ex- and a long-time delay with a making con-
tended to the full line up to and including tact for a remote alarm on one pole. This is
the 4,000-ampere frame. By this, I assume L. H. Romzick (The Detroit Edison Com- a common practice for utility companies.
that their present standard device has been pany, Detroit, Mich.): This new line of
(Author's closure appears on page 1354.)

Field Excitation in Relation to Macline Also, there have been within the past few
years several prominent cases of system
shutdowns attributable to complete ac-
and System Operation cidental loss of field excitation, or to lack
of means to increase the field strength
quickly after a system disturbance.
With this background of interest, a
S. B. FARNHAM R. W. SWARTHOUT fundamental understanding of machine
MEMBER AIEE ASSOCIATE MEMBER AIEE
capabilities will be helpful in answering
the questions which arise.
U NDER normal conditions, an opera- not only with the conventional resistance
tor can do only two things to a syn- box with handwheel or motor mechanism Kilowatts and Kilovars
chronous machine to influence its be- but equally with the automatic volt-
havior with respect to the system to age regulator, with which most important Just as there is a direct and well-under-
which it is connected, that is, he can ad- machines are today equipped, and which stood relationship between shaft torque
just the throttle valve or change the can be adjusted by the operator to hold a and kilowatts, so also is there an equally
driven load, thereby changing the shaft desired voltage level. distinct relationship between field current
torque; and he can turn the rheostat, and The current interest in field excitation and that other well-defined commodity,
hence change the field current. stems from the fact that many systems kilovars. Broadly speaking, all synchro-
Even in these operations, he does not are now operating at power factors higher nous machines are capable of both produc-
have unlimited freedom of choice, for than have previously been experienced. ing and consuming each of these two
usually the torque can be in one direction This is true for several reasons, among separate and distinct kinds of commodity.
only, depending on whether the machine them being the application of capacitors By convention, kilowatts are considered
happens to be a generator or a motor. If in substantial quantities, the increasing positive when they flow from the machine
it is a synchronous condenser, he may not use of underground cable, and the inter- out into the system. Hence, generator
be able to do anything at all about shaft connection of system to system, resulting kilowatts are plus kilowatts, while motor
torque, since the shaft may be sealed up in substantial new mileage of high-volt- kilowatts are minus kilowatts. Similarly,
inside the housing where it is inaccessible. age lines. when the machine is overexcited, it gen-
Happily, however, the operator does have Since all of these things help supply ex erates kilovars and delivers them to the
somewhat more freedom of action in citation to every machine on the system,
what he does to the field current. system. By analogy to the positive
the general voltage level tends to rise. direction of power flow, this is accepted
It is the purpose of this discussion to As a result, it becomes necessary to re-
indicate, qualitatively and quantitatively, duce the d-c field strengths of synchronous
the effects of the operator's manipulation machines so as to hold an acceptable sys- Paper 53-387, recommended by the AIEE System
Engineering Committee and approved by the
of the field rheostat, both on the individ- tem voltage level. The operator, there- AIEE Committee on Technical Operations for
presentation at the AIEE Fall General Meeting,
ual machine and on the system of which fore, logically wonders: what are the ef- Kansas City, Mo., November 2-6, 1953. Manu-
that machine is a part. As referred to fects of operation with weak field, and script submitted June 8, 1953; made available for
printing August 6, 1953.
here, field rheostat is used in its broadest what are the limits to which this field S. B. FARNHAM and R. W. SWARTHOUT are with the
sense. The discussion will be concerned weakening can reasonably be carried? General Electric Company, Schenectady, N. Y.

DECEMBER 1 953 Farnham, Swarthout-Field Excitation in Machine Operation 1215


POSITIVE POSITIVE A
KILO VARS KILOVARS
(PER UNIT) X MACHINE RATING
0.53 .A = 1.0 P. U. KVA
/(i 0.85 PRF.

AREA OF AREA OF
MOTOR OPERATION, GENERATOR OPERATION,
OVER- EXCITED OVER- EXCITED 2° I I B POSITIVE
o KILOWATTS
0.85 1.0 * (PER UNIT)

Fig. 2. Typical generator capabilities as de-


NEGATIVE _ _
l POSITIVE termined from name-plate rating
KILOWATTS KI LOWATTS NEGATIVE v
KILOVARS arc AB, having its center at 0, and radius
equal to rated armature amperes, we
Fig. i (left). Defini- have begun to outline an area of per-
tion areas of syn- missible operation. The operator of the
AREA OF AREA OF chronous machine
MOTOR OPERATION, GENERATOR OPERATION, assumed typical machine, of course, does
UNDER - EXCITED UNDER-EXCITED operation not hesitate to operate at reduced load
anywhere within the sector OAB. He
may also on occasion operate at overload
in the region to the right of the arc AB,
v ful power is neither deliver to, nor re- but in so doing he encroaches upon the
NEGATIVE moved from, its shaft. margins which the designer provided to
KILO VAR S As a practical matter, most machines cover the variables that mav occur in
are designed for one specific duty only, materials, workmanship, maintenance, or
as also being the positive direction of hence there are definite limitations to the the demands of emergency loading, and
kilovar flow. Negative kilovars, then, area within which any given machine over which he has no control. These mar-
are those which flow from the system into may be operated successfully. Since gins are essential both to the designer's
the machine to maintain its magnetiza- this discussion is primarily about genera- own peace of mind and to the preserva-
tion when its own field is underexcited. tors, and if it is agreed to omit reference tion of the good name of the company he
Fig. 1 shows these concepts translated to those abnormal circumstances under represents. It is outside the scope of this
into diagramatic form, in which kilowatts which they may motor temporarily, we discussion to explore overload operation.
and kilovars are plotted along co-ordinate immediately cut the area in half. Fig. 2, Rather, it is our intent to define the entire
axes, with the positive direction upward then, is merely the right-hand or positive area within which operation within rating
and toward the right, as is customary. kilowatt side of Fig. 1. is possible, so that full advantage of this
As previously indicated, a synchronous flexibility may be taken in securing opti-
machine, in the broadest sense, can be Generator Capabilities mum over-all system operation. Hence
operated in any quadrant of Fig. 1. If the immediate problem is to close off the
driven by a prime mover, it operates as a In Fig. 2, there is plotted at point A openings at the top and bottom of the
generator somewhere in the positive kilo- the name-plate rated conditions for an now partially bounded area of Fig. 2.
watt area (right). If the rotation of its assumed typical 0.83 power factor genera- This can be begun from information ob-
shaft is restrained by a driven load, we tor. Rated kilovolt-amperes of the ma- tainable from the simple phasor diagram
call it a motor, and it operates in the chine are taken as 1.0 per unit on its own of the assumed typical machine, as shown
negative kilowatt area (left). If its rated kva base. Hence, the rated condi- in Fig. 3.
field strength is more than enough to tions for machine operation, upon which
supply its own excitation requirements, its performance guarantees are based, are Field Current Limit
the excess appears as a component of 0.85 per unit kilowatts and 0.33 per unit
armature current representing kilovars kilovars (cos 0=0.85)), (sin 6=0.53). Starting with rated terminal voltage Et
exported to the system, and the machine Point A, however, is just one point in a and rated armature current Ia, each equal
operates in the positive kilovar area rather extensive area; and few, if any, ma- to 1.0 per unit, and at an angle 0 with re-
(above). If its field is underexcited, the chines are operated for any length of time spect to one another (cos 0=0.85 in the
deficiency must be made up by armature at exactly the conditions stated on the
current, representing kilovars drawn from name plate. The question is then: what
the system, and the machine operates in are the boundaries of the area on the
the negative kilovar area (below). kilowatt-kilovar diagram within which
A machine operating at unity power the machine may be operated?
factor is just self-sufficient in its excita- 0F E,=.ORUXd
tion. It neither produces nor consumes Armature Current Limit
system kilovars. Hence its operation is
depicted along the horizontal axis of In addition to point A, it is usual that 0 4 E,
E-- I 1.0 P. U.
Fig. 1. When used as a synchronous generators be suitable for delivering kilo-
condenser, on the other hand, the ma- watts equal to rated kilovolt-amperes at
chine operates very nearly along the unity power factor, corresponding to
vertical axis (except for losses) since use- point B in Fig. 2. Thus, by drawing the Fig. 3. Typical generator phasor diagram

1216 Farnham, Swarthout-Field Excitation in Machine Operation DIECEMBER 1 953


assumed typical case), we can lay off sent some kind of current; and since we CA = V/(O.80 +0.53)2+(0.85)2= 1.58
IaXd at right angles to Ia, where Xd is are dealing in per unit quantities, there is
CO = 0.80
the synchronous reactance of our ma- no constant of proportionality with which
chine. E. then is internal or generated to be concerned. E9 is generated voltage Hence
voltage corresponding to rated terminal and is proportional to air gap flux, which
conditions. It would also be equal to OD= 1.58 = 0.80 = 0.78
is in turn proportional to field current,
the terminal voltage if full load were re- neglecting saturation. Thus E, Xd rep- This machine, then, can generate maxi-
moved without making any change in resents per unit field current. Hence, mum kilovars equal to 78 per cent of
field current. just as OA represents rated armature name-plate rated kilovolt-amperes.
Keeping the phasor triangle in mind, current, so CA represents rated full-load
refer now to Fig. 4. Here Et, IaXd, and field current. Then with C as a center, End Region Heating Limit
E0 are each divided by Xd. Also, the tri- and CA as a radius, the arc AD may be
angle is inverted and reoriented so that it drawn representing the locus of rated field
falls on the kilowatt-kilovar co-ordinates, There remains now only the lower part
current, thereby closing off the top of the
with the side representing IaXdlXd = area within which the machine may be
of the area to be bounded. Since this is
a region of low field current, being well
Ia so placed as to form the radius OA of operated.
the previously determiined constant arma- below the limiting field current arc DA.
In any balanced design, point A, the it might be said offhand that the limit
ture current arc AB. point representing name-plate rating, is
The side of the triangle representing must therefore be armature current, and
also the point at which the designer ar- so the constant armature current arc AB
Et/Xd= 1.0 Xd falls along the kilovar ranged for the thermal limits of both field could be extended all the way around to E.
axis. Note however that, neglecting and armature to be reached together.
saturation, the quantity 1. (Xd is equal This would, however, be wrong for several
Thus the output of the typical machine is reasons. For one, system stability would
to the short-circuit ratio of the assumed limited by field heating from D to A, and
typical machine. Hence, point C is have been completely overlooked. For
by armature heating from A to B. another, localized heating in the machine
established on the negative kilovar axis, at As an example of the usefulness of Fig.
a point corresponding to the short-circuit would very likely become a problem, in
4, it gives a ready answer to the fre- the case of steam turbine generators.
ratio. This value might typically be quently encountered question: what
0.80, corresponding to Xd = 1.25 for the Now, as the boundary line is extended
maximum kilovars can this machine into the region below the horizontal axis,
assumed machine (1/1.25=0.80). generate at zero kilowatt load? In
This leaves only the third side, EglXd, we come to the one place where general-
other words, what is its capability as a ized reasoning fails, and where specific
of the phasor diagram triangle to be ac- synchronous condenser? To answer this,
counted for. Dimensionally, since it is a knowledge of the individual machine is
it is only necessary to measure the ver- required, namely, in establishing that
ratio of voltage to reactance, it must repre- tical intercept OD, which represents the part of the operating limit resulting from
maximum permissible per unit kilovars to localized heating in the machine iron.
Pn4,, riv;r
scale. Or, mathematically The reason for the problem is that all
KILOVARS OD= CD= CO= CA =CO synchronous machines have an armature
reaction end leakage flux at both ends
where, for the constants it is assumed of the stator. This flux is produced by

Et I
Xd Xd

0.8
SCR

NEGATIVE
KI LOVARS
Fig. 4. Composite capability limits of typical generator at rated termi- Fig. 5. Sectional view of end-region construction of a modern turbine
nal voltage generator

DECEMBER 1 953 RFarnham, Swarthout-Field Excitation in Machine Operation 1217


load current flowing in the stator conduc- paths are not at right angles to the plane Stability Limitations
tors. It revolves at synchronous speed of stator laminations; and also the use
with respect to the stator, and hence is of magnetic shields to control the flux It has been hinted that system stability
stationarv with respect to the rotor. It paths. might constitute a limitation. With
crosses from one side of the stator to The success of these methods is at- respect to steady-state stability, it can
another point on the stator 180 electrical tested by the fact that modern generators be shown that if the machine in question
degrees away. In so doing, it takes the may be operated successfully in the under- is connected through negligibly small
low-reluctance path, which as shown in excited region down to a line such as HJ impedance into an infinitely large system,
Fig. 5, representing this portion of a in Fig. 4, where point H is at 60-per-cent then the stability limit may be repre-
typical steam turbine generator, carries rated kva at zero power factor leading, sented by a horizontal straight line passing
it through the stator core flange and end and point J is at rated kva, 0.95 power through the point on the negative vertical
fingers, across the air gap into the rotor factor leading. axis representing short-circuitratio. This
retaining ring, circumferentially around These limits, however, may not apply line is CF in Fig. 4. If the machine is
the retaining ring, and so on back across to older machines; and it becomes neces- operated at any kilowatt and kilovar load-
the air gap, fingers, and flange, to the sary to investigate the capabilities of each ing above this line, it will be stable. On
stator core. While the main flux in the such machine in question. Sometimes the other hand, operation along the arc
body of the stator is parallel to the lam- the manufacturer mav have test data on EK, even if it did not exceed any heating
inations, it is to be noted that this end that particular machine or on one of very limitation, would be impossible, as the
leakage flux enters and leaves the ends of similar design, from which he will be machine would not remain in synchro-
the stator in a direction essentially per- willing to give a reasonably close esti- nism with the system. Actually few, if
pendicular to the laminations. Hence mate of the expected capabilities. In any, machines operate through negligibly
the effect of the laminations in reducing other instances the users may have the small impedance into a system so "stiff"
eddy currents caused by the end leakage choice either of accepting some rather that it approaches the infinite. In most
flux is minimized. To understand the conservative estimate based on general practical cases, the machine operates
significance of this change in flux direc- knowledge and experience, or of making an through impedance representing trans-
tion with respect to the laminations, it actual test onthe particular machine itself. formers, lines, and the paralleled value of
must be appreciated that the core losses If a test is to be undertaken, the manufac- the impedances of all the other machines
are typicaly something in the neighbor- turer will generally be willing to suggest on the system. This resultant impedance
hood of 100 times greater for perpendicu- the locations at which thermocouples are is typically about 0.20 to 0.40 per unit,
lar flux than for flux parallel to the lam- most likely to reveal the limiting tempera- based on the individual machine rating,
inations. Hence, considerable additional tures. although it is of course determined in any
heat is generated; and since it is applied Often, however, the operator already specific case by the system configuration
to only a relatively small volume of ma- has a fairly clear conception of the capa- and constants. At any rate, the effect of
terial, dangerously high temperatures may bilities of his older machines, based on this external impedance Xe is to bend up-
be produced within only a matter of his operating temperature records, visual ward the straight line CF to some position
minutes. inspections, and maintenance experience such as CG. With terminal voltage held
Now, how is field current related to this over the years. Evidences of having constant at 1.0 per unit, it can be shown
end leakage flux and its resultant heating? reached the limits of underexcited opera- that CG is the arc of a circle whose center
Simply in this way: Normal values of tion may occasionally be found in the lies on the vertical axis at a point SCR/2+
field current keep the retaining ring sat- blueing of iron parts of the end structure, 1/2Xe above point C. Hence, with the
urated, so that only a relatively small or the charring of insulation on the arma- aid of numbers already known or readily
amount of armature end leakage flux ture bars where they emerge from the determinable, the part of the boundary
traverses the path described. However, core stacking. established by steady-state stability can
when the field excitation is reduced, Having determined, by whatever means be established. This limit is slightly
corresponding to operation of the machine are appropriate to the particular ma- conservative, in keeping with its deter-
in the region of unity and leading power chine, the limits imposed bv end heating, mination by the commonly accepted prac-
factor, then the retaining ring is no longer these limits may be plotted, Fig. 4, to tices of approximating saturation and
saturated, and permits an increase in complete the boundary of the permissible neglecting saliency.
armature end leakage flux. As we have operating area. For illustration, in Fig. 4 Transient stability also is of course af-
seen, this increased leakage flux produces this is the line HJ which as has been indi- fected to some degree by the machine ex-
heating in those areas of restricted ma- cated, is typical of a modern machine. citation as dictated by the kilowatt and
terial cross section, and where the flux For some older machines, this line will kilovar load which it carries, as well as
direction is at right angles to the plane of be displaced upward toward the hori- by its operating voltage. However,
the laminations. zontal axis, and in a few cases it may be many other factors outside the scope of
This plhenomenon has been recog- found that point J will actuallv be above this discussion such as type and location
nized since the middle 1920's. Several the axis, since the end heating limitations of the fault, operating times of relays and
different approaches have been used, of some machines may be such that they clearing times of circuit breakers, sys-
either singly or in combination, to reduce can not be operated near full load even tem grounding, machine inertias, and
the armature end leakage flux and the at unity power factor. Fortunately, this automatic reclosing play a so much more
resultant heating. Among these are the restriction will apply to only a few of the dominant part in transient stability con-
use of nonmagnetic materials for the re- oldest steam turbine generators still re- siderations that the effect of field excita-
taining rings and parts of the stator end maining in service. It is not a limitation tion in thisregard is greatly overshadowed.
structure; changing the end structure sur- to the operation of water-wheel genera- It would appear to be a very extreme case
face configuration so that leakage flux is tors, because of their generally different where system transient stability were
reduced and so that the remaining flux construction. critically dependent on field excitation.
1218 Farnham, Swarthout-Field Excitation in illachine Operation DE-CEMBER 195-3
It is reasonable to conclude, therefore, previously determined, for rated ter- at the intersection of the circular arc
that in most practical cases transient minal voltage. Also shown is the steady- with a vertical line, such as XY, repre-
stability will not become a barrier to suc- state stability limit CG, for this machine senting the new kilowatt load, and of
cessful underexcited operation if it has and connected system. course the terminal voltage is substan-
not previously been an obstacle while It will be apparent from our earlier tially below normal.
operating in the overexcited region. derivation that the field current of this Several conditions immediately be-
To summarize, the limits of generator machine is represented by CP. (Remem- come apparent from inspection of Fig. 6:
capability in each of the several potential ber that CA is proportional to rated field 1. Load increase without corresponding
areas of operation, as illustrated in Fig. 4 current. Hence CP/CA is simply the adjustment of field current pushes the ma-
are proportion of name-plate rated field cur- chine operating power factor toward the
rent; and this is just the amount neces- leading (underexcited) region.
DA-field heating
sary to permit the machine to handle the 2. The more lagging (overexcited) the
A J-armature heating initial load power factor, the greater the
kilowatts and kilovars represented by
JH-armature end region heating total load the machine can carry before
point P.) running into one of the limits.
In addition, there may also be a steady- Now, suppose this machine is called 3. If adequate field strength could always
state stability limit CG but as has been upon to pick up load. This might well be be assured, steady-state stability would, for
seen, this would not constitute an operat- in consequence of the system normal daily all practical purposes, never be a problem,
ing limit unless the machine under con- load pattern, or perhaps because some because the limit is greater than the capa-
sideration were connected to the system other machine on the system has had to bility of the typical prime mover.
through a tie so weak that the curve CG drop load. At any rate, let us assume A somewhat broader picture of this
bent upward to intersect HJ. that the load increase on the machine variation of steady-state stability limit
occurs before the operator notices the with initial operating power factor is
Automatic Voltage Regulators resulting drop in terminal voltage, and shown in Fig. 7, based on typical con-
hence that he makes no change in the field stants. It will be apparent from this
As a basis for appreciating the role of rheostat setting. On the co-ordinate figure why some operators (who perhaps
the automatic voltage regulator in permit- diagram of Fig 6, this situation, namely experienced a shutdown resulting from
ting the widest possible flexibility of ma- increasing kilowatts with constant field instability while operating in the leading
chine operation within the boundaries excitation, is depicted as a movement of or near unity power factor region) have
established, it may be in order first to the operating point from P along the a phobia against approaching the unity
consider the case of a machine operating circular arc PK. This path runs almost power factor line. Actually, however, as
without a voltage regulator. Assume that directly into the end region heating limit Fig. 7 shows, there is no precipitous
this machine is carrying a kilowatt and HJ and the system steady-state stability breaking point at unity power factor.
kilovar load as represented by point P limit CG. Whether or not one or both of The criterion, therefore, should not be
in Fig. 6. On this figure will immediately these limits will be exceeded depends of what the power factor is, but rather what
be recognized the composite boundary of course on the amount of the kilowatt load the maximum available synchronizing
permissible machine operation DAJH as increase. The final operating point lies power is, relative to the maximum load
POSITIVE
KILOVARS z
N

Xz c Z
M
3
zr ow

I1.2- _ INITIAL LOAD:


1.0 RPU. KW
ARMATURE
-CURRENT
LIMIT
INITIAL LOAD=
Xe=0.4 0.5 P U. KW
-(WITHOUT REGULATOR) 0.8F
POSITIVE
-1 KILOWATTS
(PER UNIT) 0.6 i _ Xe = 0.4
Xd = 1.25
SCR =0.8
0.4 F
,G - Xe=0.4
(WITH REGULATOR) 0.2 _

l 01 I I
0.80 0.85 0.90 0.95 1.0 0.90 0.85
0.95 0.80
LEADING LAGGING
(UNDER-EXCITED) (OVER-EXCITED)
POWER FACTOR OF INITIAL LOAD
Fig. 6. Generator capability limits as Fig. 7. Ultimate maximum synchronizing power versus power fac-
K ILOVARS affected by automatic voltage regulator tor of initial load

DECEMBER 1953 Farnham, Swarthout-Field Excitation in Machine Operation 1219


POWER FANCTOR a Fig. 8. Ultimate maximum syn- chine immediately from the system, for
MACHINE TERM. chronizing power versus generator two reasons: 1. The machine may be
I I terminal voltage for assumed initial damaged through heating caused by large
z F. LAG toad of 0.8 per unit eddy currents flowing in the surface of the
EXC.) rotor. 2. The system may not be able to
w 1.0 1.0 P.F withstand successfully the large kilovar
a.
I
load suddently imposed on it. System
w F. LEAD voltage will drop, and other machines
30 0.9 t-EXC.)
a- may lose synchronism.
0 With respect to the first possibility,
Ri 0.8
z namely, rotor damage, it is true that ma-
z INITIAL LOAD - 0.8 PU KW chines have been operated for extended
0
cr Xd = 1.25 periods without apparent damage; and
0 0.7 _-X -0 4
Xe =0.4
z
, ' SCR = 0.8 some power companies feel that an opera-
(I) tor can correctly diagnose the symptoms
0.1_ in time either to restore the excitation
x (perhaps by switching over to a spare
exciter) or to trip the machine off the
0.90 0.95 1.00 1.05 1.10 system manually. On the other hand,
GENERATOR TERMINAL VOLTAGE - PE R UNIT generators have had to be repaired be-
cause of damage resulting from this sort
demand that may be made on the par- Actually the characteristic of this device of procedure. Regardless, however, of
ticular machine in question. On this is a straight line, such as JUN, and may whether the machine suffers obvious
basis, any machine under hand control be located anywhere within the area by damage or not, there is the very real
can have its loading so scheduled as to independent adjustments of its slope and possibility of reduction of field-winding
insure stable operation under whatever point of intersection with the vertical insulation life or other incipient damage
emergency load condition may be im- axis. Hence this characteristic can be which may be impossible to evaluate even
posed upon it. set so that the lower excitation limit will through careful examination, and the ma-
WVith an automatic voltage regulator, come into operation just short of either chine will certainly be out of service while
however, any practical concern over the end-heating limit or the steady-state the examination is being made. In con-
steady-state stability can be dismissed, stability limit, as determined for the trast, if an automatic protective relay is
for the regulator will hold the machine particular machine and associated system. employed to trip the main breaker before
excitation at a level corresponding to This obviously is not a fixed minimum the machine begins to slip poles, there
synchronizing power in excess of the maxi- field current limit, but rather it varies the need be no delay in returning the ma-
mum capability of the prime mover. minimum allowable excitation automat- chine to service immediately after the
ically with the load on the machine, as cause of lost excitation is corrected, and
Lower Excitation Limit measured through instrument transform- without the necessity for examining and
ers connected to the machine terminals. testing the rotor insulation.
Notwithstanding the practical assur- Thereby it permits the maximum of The amount of the increased kilovar
ance against loss of steady-state stability operating flexibility, right up to the limits load imposed on the system as a conse-
provided by the automatic voltage regula- imposed by the machine and system. quence of generator excitation failure
tor holding normal terminal voltage, there This lower excitation limit is a standard will vary, depending on the machine
may be instances where an operator, in feature of all amplidyne-type automatic constants and the rate at which it is slip-
his efforts to reduce system voltage dur- voltage regulators, but is not adaptable to ping poles, from something about equal
ing light load, may lower the setting of the rheostatic-type regulators. to its name-plate kilovolt-ampere rating
regulator voltage adjusting rheostat so to as much as four times this rating.
that the machine excitation and terminal Loss of Excitation Relay Especially if, previous to the disturbance,
voltage are reduced substantially below the machine was overexcited, that is,
normal. This action on the part of the The extreme case of underexcitation is delivering kilovars to the system, the net
operator may reintroduce a steady-state of course, complete loss of excitation, as change so far as the system is concerned
stability problem for, as shown in Fig. 8, may happen, for example, when a field may be very serious indeed. The newest
the limits, which may be ample at rated lead is broken or when someone inadvert- and largest generator on a well-planned
terminal voltage, become materially re- ently trips the field breaker. Loss of system usually represents the largest
duced at lower values of terminal voltage. synchronism with the system is, under this block of power that can be lost to the
Recognizing this possibility, some mod- condition, a foregone conclusion, although system without causing undue hardship.
ern voltage regulators include a lower the machine may continue to produce Often overlooked, however, is the fact
excitation limit which automatically kilowatts as an induction generator. The that the larger kilovar load resulting from
comes into play below a predetermined amount of kilowatts thus generated will loss of excitation on such a machine may
level of excitation to prevent loss of svn- depend both on the initial setting and be more of a shock to the system than
chronism. It may also be used advan- droop characteristics of the speed gover- the loss of its kilowatt output. If other
tageously to prevent operation where end nor, and on whether the excitation fail- machines on the system are equipped with
region heating might become a problem. ure left the field circuit completely open, automatic voltage regulators, and if the
The region within which this lower limit or closed (perhaps through a field dis- resulting demand on them is not exces-
is typically set to come into operation is charge resistor). In anv event, however, sive, they may be able to supply the neces-
shown by the shaded area of Fig. 6. it becomes desirable to remove the ma- sary additional kilovars and so help main-

1220 Farnham, Swarthout-Field Excitation in Machine Operation DECEMBER 1 953


tain system voltage. If, however, these and it is fail-safe in the event of open machine from the system in the event of
other machines are inadequate to the circuit in its supply leads. failure of its excitation, is desirable, both
demand, or if their excitation controls do as primary protection against damage to
not provide immediate response to the Conclusions the machine itself and as backup protec-
need, system voltage levels will fall, syn- tion against serious disturbance to the
chronizing power among them will be Modern system operation is increasingly interconnected system.
reduced, and instability may occur. If in the region of unity and leading power
this happens, a major system shutdown factor. Generators may safely be oper- References
is probable. ated in this region, up to limits which
While automatic voltage regulators usually are readily determinable. Such 1. UNDEREXCITED OPERATION OF TURBOGENERA-
should always be regarded as the first operation generally is not a determining TORS, C. G. Adams, J. B. McClure. AIEE Trants-
actions, vol. 67, pt. I, 1948, pp. 521-28.
line of defense, backup protection against factor in system transient stability, al- 2. UNDEREXCITED OPERATION OF LARGE TURBINE
this difficulty can be provided by a suita- though steady-state stability may be- GENERATORS ON PACIFIC GAS AND ELECTRIC
ble loss-of-excitation relay on each large come a problem if machine kilowatt load- COMPANY'S SYSTEM, V. F. Estcourt, C. H. Holley,
W. R. Johnson, P. H. Light. AIEE Transactions,
or otherwise important machine on the ings are increased from light-load opera- vol. 72, pt. III, Feb. 1953, pp. 16-22.
system. Like the lower excitation limit tion without corresponding increases in 3. POWER SYSTEM STABILITY, VOLUMES I AND II
on the regulator, this relay responds to excitation. Automatic voltage regula- (book), S. B. Crary. John Wiley and Sons, Inc.,
New York, N. Y., 1947.
current and voltage at the a-c terminals tors are very desirable, since they effec-
4. EFFECT OF A MODERN AMPLIDYNE VOLTAGE
of the machine, rather than to some arbi- tively eliminate this problem; and if of a REGULATOR ON UNDEREXCITED OPERATION OF
trary minimum value of field current or type incorporating a lower excitation LARGE TURBINE GENERATORS, W. G. Heffron,
R. A. Phillips. AIEE Transactions, vol. 71, pt. III,
voltage alone. Hence it is immune to limit, they provide a means for auto- Aug. 1952, pp. 692-97; discussion pp. 1134-35.
false operation when the field strength is matically avoiding the regions where end 5. SYSTEM STABI ITY LIMITATIONS AND GEN-
purposely reduced, as during times of heating and stability become limitations. ERATOR LOADING, H. C. Anderson, H. 0. Simmons,
Jr., C. A. Woodrow. AIEE Transactions, vol. 72,
light load. Its application is clean-cut, A protective relay, arranged to isolate the pt. III, June 1953, pp. 406-23.

Discussion would lead to a description of a steam-elec-


tric generating station as a "disposal" for
In the initial months of plant operation,
operators at the Meramec Plant of the Union
negative kilowatts and a means for supply- Electric System noticed certain oscillatory
W. R. Brownlee (Southern Services, Inc., ing negative coal to the mines. phenomena which instigated a thorough
Birmingham, Ala.): This comprehensive study of machine stability at high and un-
summary of various factors influencing the REFERENCE derexcited power factors. The results of
operating limitations on the excitation of 1. THE SIGN OF REACTIVE POWER, AIEE Commit-
calculations and a network analyzer study
generators is most timely because of two tee Report. Electrical Engineering, vol. 65, Nov. agree very well with conclusions presented
important trends. One is the continuing 1946, pp. 512-16. by the authors regarding transient stability,
upsurge of unswitched capacitor installa- steady-state stability, and the advantages
tions, and the other is the use of larger of an automatic voltage regulator for main-
conductors on and the more economical John F. Watson (Union Electric Company taining stability under conditions of rapid
loading of transmission lines. These fac- of Missouri, St. Louis, Mo.): The authors load change. However, the results of this
tors require greater control of kilovar sup- have done a commendable job, first in study show an important disadvantage of
plies and generator voltages. their presentation of a method of determin- the automatic voltage regulator which is not
One caution is in order in the use of the ing the capabilities of a synchronous mentioned by the authors.
curves and equations with respect to the generator for a complete range of power Machine steady-state stability depends on
effective external reactance. For example, factors, and second, in viewing these limits external impedance as well as loading and
consider a generating plant with three 60- from a standpoint of stability in order to load changes. If the impedance between
megawatt units, connected to each other reach some important conclusions regarding the generator and the "infinite" system is
and to the transmission system through a machine and system operation. increased suddenly as a result, for example,
high-voltage bus. If the short-circuit contri- In the development of the capability of losing a transmission line, the machine
bution of the transmission system, together curves, the assumption is made that ar- would be forced to deliver the same amount
with that of generators no. 2 and 3, is mature and field thermal limitations are of power to the constant voltage system
taken in determining the excitation limit of reached at the point of name-plate rating. through an increased external impedance.
generator no. 1, then the only criterion de- Despite the fact that this assumption is Under certain conditions this can result in a
rived might be the ability of this generator quite commonly made, there may be some reduction of excitation and a consequent re-
to remain at parallel with the other two. question as to whether this actually occurs. duction in stability margin.
For stability with the power system, the Perhaps some elaboration on this point This is not as remote a possibility as might
external reactance is a function of the short- would be helpful. first be assumed, for it is rather common for
circuit contribution from the transmission In regard to the method of rating a gener- a generator or a plant to be connected into
lines only, and is applied on a base of all ator in the underexcited region of operation, a large system by two or three lines with
three generators rather than just one. the authors suggest specific limitations for machine and external impedances, as in the
While the general tone of the paper is modern machines but go on to say that test Meramec case, to the typical values used by
-clear and simple, a serious defection appears data, operating experience, etc., furnish the the authors in their work. It is not sug-
in the section entitled "Kilowatts and only definite means of rating a certain gested that this particular detrimental ef-
Kilovars," namely the expression "negative machine. While this is true, it does impose fect of the regulator is of sufficient impor-
kilovars." Usage of this type encourages a limitation on the usefulness of the rating tance to be comparable to the many advan-
such dangerous equivocations as "leading method because very often it is the absence tages of automatic voltage regulation, but it
reactive," "leading or lagging current," of specific data and experience that make is believed to be of general interest and
and "impressed voltage reference or induced some method of rating imperative. It may possibly worthy of mention and perhaps
voltage reference." In view of the action be that no better way of establishing limits further investigation.
of the AIEE Standards Committee in is possible, but if a method existed whereby
1946,1 it is urged that such expressions be limits could be determined from the more
avoided. Actually, there should be no more readily available machine data and curves, H. C. Anderson (General Electric Company,
temptation to say "negative kilovars" than the usefulness of the whole scheme would be Schenectady, N. Y.): The authors are to be
to say "negative kilowatts." The latter greatly enhanced. congratulated on a paper that explains, in

DECEMBER 1 953 Farnham, Swarthout Field Excitation in Machine Operation1 1221


3 PHASE,6-CYCLE FAULT voltage in both cases is that corresponding raising system voltage, and generator volt-
et to initial operation of the generator at maxi- age is maintained nearly constant, the
mum turbine capability with unit terminal stability margins are increased. As a
voltage at 0.95 power factor overexcited. matter of fact, if equivalent system react-
INFINITE BUS
XeI OR Xe2 e2=SYSTEM VOLTAGE In both systems (0.20 initial reactance and ance is tmly high, on the order of 70 per
0.40 initial reactance) the equivalent system cent to 80 per cent, the generator can supply
voltage is 0.95. very little kilovar to the system, if stable
Curve A in Fig. 9 is the limit of opera- operation is to be maintained at maximum
tion, based on transient stability con- turbine capability.
siderations, of a generator when it is con-
nected to a system whose reactance is 20
0 per cent initially and 40 per cent after a S. B. Farnham and R. W. Swarthout: The
I
line or other facility is switched out on the authors are appreciative of the interest
occurrence of a 3-phase fault, 6 cycles in shown by all those who presented discus-
duration. Note that the limit of stable oper- sions, both written and oral.
U) ation for this case is well outside the limits Mr. Anderson has pointed out the reduc-
outlined in the paper. tion in system transient stability that re-
4- Curve B is the limit of stable operation sults, at lower than normal voltage, when
± for the same generator operating on a system the external system reactance is abruptly
whose initial reactance is 40 per cent and increased. He has thus extended the scope
whose reactance after switching out a line of the paper, which is predicated on the con-
0 or other facility is 60 per cent. Note dition of rated machine terminal voltage,
-J
that in both cases the transient power limit except for Fig. 8 wherein is shown the typical
decreases quite rapidly as the kilovar output variation in steady-state stability limit with
is decreased by lowering the field excita- changes in terminal voltage. To an oper-
0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 tion, when system voltage is held constant. ator faced with the practical necessity for
KW However, in the low-reactance system, the maintaining lower than normal voltage
Fig. 9. Transient stability limits for (A) decrease in power limit is of no conse- levels, transient stability may indeed be-
quence since maximum turbine capability come a limiting factor, particularly if the
0.20/0.40 system and (B) 0.40/0.60 system limits the amount of power which can be reactance between the machine and the sys-
transmitted. tem can be substantially increased, as, for
In the higher reactance system, curve B, example, by the faulting and subsequent
simple terms, the factors which affect the operation of the generator is somewhat re- isolation of the shorter of two lines which
lower limit on field current. stricted, as long as system voltage is not normally connect the machine to the system.
In their paper a statement concerning the allowed to increase. The generator may Mr. Watson describes another manifesta-
transient stability limit is made. "It is be operated at maximum turbine capa- tion of this 2-tie-line problem as it pertains
reasonable to conclude, therefore, that in bility in the overexcited region at power fac- to steady-state stability. Fig. 10 illustrates
most practical cases transient stability will tors up to about 98 per cent (corresponding his statement: "An automatic voltage
not become a barrier to successful under- to about 20 per cent kilovar output) without regulator would, by attempting to maintain
excited operation, if it has not previously fear of transient instability. If it becomes a constant generator terminal voltage, de-
been an obstacle while operating in the over- necessary to operate at still lower values of crease the stability limit of the machine."
excited region." This statement is correct kilovar output, the power must be reduced Here, generator terminal voltage is plotted
if the day-to-day generator voltage is not as the kilovars are reduced until at unity as a function of the increase in system re-
allowed to vary appreciably. In other power factor the machine may be operated actance when one of two parallel lines is
words, if the reactive oultput of a given plant at only about 90 per cent of its maximum opened. It is to be noted that, depending
is decreased by raising system voltage, as turbine capability. If underexcited opera- on the degree to which the machine is ini-
opposed to lowering generator terminal volt- tion is necessary, the power must be reduced tially operating overexcited (generating
age, the transient stability margin is not still further. The foregoing explanation kilovars), there is actually a rise in the volt-
reduced. applies when the equivalent system voltage age seen by a regulator at the machine
However, in the day-to-day operation of a is held constant. terminals. Hence, the regulator neces-
given plant, generator reactive output is If the system is called on to supply more of sarily acts in the direction to reduce the
usually varied considerably to meet system its own kilovar requirements, either by stability limit. However, each curve of
requirements. If system voltage is held changing transformer taps or by actually Fig. 10 is terminated at the value of react-
nearly constant, and generator voltage is
lowered to produce a reduction in reactive
output, there will be an appreciable decrease 1.2
in transient stability limit. It is the pur-
pose of this discussion to show how reactive
output, and hence field excitation (with 1.0
system voltage constant), affects the tran- z
CL
w
sient stability limit. a-
H
In a so-called "low-reactance" system, w
(9
such as the examples Mr. Farnham and Mr. Q8 Et-1=.0 1.0 1.0 1..0 INITIAL
Swarthout have used, where reactance ex- I PF= 1.0 0.95 0.90 0..85 OPERATING
CCONDITIONS
0
ternal to the generator does not exceed 40 wut-I ,, OVER EXCITED
per cent (with maximum turbine capa- K.W.=I.V
-4 1.0 1.0 1.1.0
bility as a kilovolt-ampere base), the gen- z 0.6 _
erator may be operated over its entire capa-
bility range without fear of its becoming w
unstable. There are other factors, as / Xd \ INFINITE
pointed out in the paper, which will limit
i-
Fig. 10. Gener- 0 0.4 V ) --Fs7 SYSTEM
its range of operation. However, if the ator terminal vol- H
same generator is operated on a higher re- tage as system Erw Et= 1.0 Xe= 0.2
actance system, say 50 per cent to 60 per reactance is in- z 0.2 _
cent, it is safe to assume that transient sta- w
bility will be a factor determining part of its creased tosteady- LI)

operating range. state stability


Fig. 9 shows operating limits of a gen- limit, maintaining
erator when it is connected to either of two constant field 0.l 2 0.3 0.4 0.5 0.6 0.7 0.8
different systems. The equivalent system excitation PER UNIT Xe WITH ONE LINE OUT
1222 Farnham, Swarthout -Field Excitation in Machine Operation DE-CEMBE-R 1 953
ance representing the stability limit for its however, particularly if it has been rebuilt chines, the limits are definitely set forth in
assumed initial operating conditions; and and rerated, it is possible that the field the paper. Hence, it appears that the
it is to be noted that in all cases the terminal and armature windings may not both attain alleged limitation to the usefulness of the
voltage has fallen below normal before this the same temperature rise at name-plate generalized capability data as outlined in
point is reached. Hence, it can be con- rating, and specific knowledge of the par- the paper would pertain to only a relatively
cluded that, while the regulator may act in ticular machine may therefore be desirable few of the less important machines remain-
the direction to impair stability in those if precise operating limits are to be drawn. ing in service today.
regions where stability is not a problem, The published percentage increases in rat- Mr. Brownlee's dissent with the expres-
nevertheless it does come into play in the ings of modern hydrogen-cooled machines sion "negative kilovars" is well worthy of
desirable direction before a critical stability permit the same relative increases in loading note. There is only one kind of kilovar.
situation is reached. of both field and armature, again on the While, for purpose of recording data or
In response to the questions raised by premise that the designer has the knowledge indicating direction on co-ordinate diagrams
Mr. Watson, it is the usual objective of a to make equally effective application of the (as in Figs. 1, 2, 4, and 6) the terms "posi-
balanced machine design to have all parts cooling medium to both the field and arma- tive" and "negative" or their counterpart
of that machine meet their thermal require- ture windings. plus and minus signs are very convenient,
ments at name-plate rating. In this way, The statement in the paper to the effect and are widely used, such use must be under-
the most economical design is achieved. that test data, operating experience, etc., stood to pertain to direction of flow only.
In the case of modern machines, it is a rea- provide the only means for determining the It must not be permitted to lead to a con-
sonable assumption that the designer has operating capabilities in the underexcited cept that there are two kinds of kilovars,
sufficient knowledge to accomplish this region applies only to machines built prior any more than there are two kinds of kilo-
objective. AWTith an extremely old machine, to the mid-1920's. For more modern ma- watts.

Experience and Reliability of Carrier- B. Nominal operating range of voice


transmitter-receiver in decibels?
7. Type of relaying system (directional or

Relaying Channels phase comparison, transfer trip)?


8. Is this relay carrier channel used for
other services?
9. What other carrier channels are on this
AIEE COMMITTEE REPORT circuit?
10. Years of service of the carrier-relaying
channel?
THE USE of power-line carrier as a facturers in producing more trouble-free 11. Total outage time of carrier relay
pilot channel for high-speed relaying equipment. The tabulated results of the channel for routine maintenance?
is an accepted practice for transmission- questionnaires will also be of benefit to 12. Total outage time of carrier relay
line protection. However, there has been the user of carrier relaying in indicating channel from terminal equipment defects?
a lack of concrete information on the per- what degree of reliability he can expect 13. Number of outages of carrier relay
formance and reliability of carrier-relay- from his equipment. channel caused by carrier equipment de-
ing channels. In addition, there is con- With these objectives in mind, the fects?
siderable variation among power com- following questionnaire on carrier relay- 14. Number of outages of carrier relay
panies as to the testing and maintenance ing was sent out. It is made up of two channel caused by relaying equipment de-
of the various components of a carrier parts. Part I covers circuit information fects?
installation. Recognizing these condi- and performance data, and each ques- 15. Number of correct operations?
tions, the AIEE Carrier Committee tion requires one answer per line section 16. Number of incorrect operations?
several years ago established a project protected by carrier relaying. Part II
subcommittee to obtain data on the ex- covers maintenance on the carrier com- PART II-MAINTENANCE
perience and reliability of carrier-relaying ponents, and the questions in this part 17. How often is the carrier transmission
channels. require only one answer from each power tested? A. Manual. B. Automatic.
A detailed questionnaire was drawn up company. 18. Is a reserve signed test (or sleet test)
to obtain information which would serve made, and if so, at what intervals?
two purposes: first, to help users of car- Summary of Questionnaire 19. What is the inspection schedule on
rier-relaying equipment in determining relays? Describe routine very briefly.
reasonable maintenance intervals and PART I CIRCUIT INFORMATION AND
A. Inspection. B. Calibration and opera-
procedure; and second, to guide manu- tion check.
PERFORMANCE DATA 20. What is the inspection schedule on the
1. Length of circuit in miles? carrier equipment? Describe briefly. A.
Paper 53-377, recommended by the AIEE Carrier 2. Nominal line voltage rating in kilovolts? Transmitter-receiver. B. Coupling capaci-
Current Committee and approved by the AIEE tor and potential device. C. Line trap.
Committee on Technical Operations for presenta- 3. Number of carrier-relaying terminals on
tion at the AIEE Fall General Meeting, Kansas
this line? 21. How often are the vacuum tubes
City, Mo., November 2-6, 1953. Manuscript checked?
submitted March 13, 1953; made available for 4. Carrier frequency or frequencies?
printing July 29, 1953. 22. What tests are made to determine that
The personnel of the Project Subcommittee are: 5. A. Transmitter output watts for re- a tube has reached the end of its useful life?
H. W. Lensner, Chairman; T. A. Cramer, G. M. laying? 23. What are the reasons for removing
Babcock, J. R. Curtin, W. J. Googe, V. J. Hayes,
L. E. Ludekens, M. Warren, J. Youngblood, 0. A. B. Transmitter output watts for voice tubes from service? State results in per-
Starcke, and B. W. Storer. or telemetering? centage.
The committee wishes to express their appreciation 24. WVhat is the average tube life? List by
of the co-operation given by the contributing 6. A. Nominal operating range of relay-
power companies for the data in this report. ing transmitter-receiver in decibels? types.

DECE-MBIER 1 953 Reliability of Carrier-Relaying Channels 1223

Vous aimerez peut-être aussi