Vous êtes sur la page 1sur 10

Installation and Maintenance Manual IM 901

McQuay Steam Coils Group: Applied Air

Part Number: IM 901

Date: February 2008

Types HI-F5, HI-F8, & E-F5

© 2008 McQuay International


Contents
Introduction .............................................................. 3 Installation ................................................................ 5
General Information................................................ 3 Mounting ................................................................ 5
Hazard Identification Information............................ 3 Installation .............................................................. 5
Receiving Instructions ............................................ 3 Operation and Maintenance.................................... 8
Coil Types............................................................... 3 Operation ............................................................... 8
Distributing.......................................................... 3 General .............................................................. 8
Single Tube ........................................................ 3 Maintenance .......................................................... 8
Nomenclature ......................................................... 4 General .............................................................. 8
Introduction
General Information 3 Coils are factory tested at 315 psig (minimum air pressure)
Introduction

while submersed in water.


These are general guidelines for the installation, operation and
4 For additional assistance, contact your local McQuay sales
maintenance of McQuay steam heating. They may have to be
representative.
tailored to meet the specific requirements of any one job. An
experienced installation company or fully trained personnel
should perform the installation and maintenance of any coil. Coil Types

Hazard Identification Information Distributing


McQuay models JA, RA and DA jet-tube steam distributing
DANGER coils (Figure 1) are excellent for any general purpose heating
Dangers indicate a hazardous situation which will result in application. With the superior freeze resistance provided by
death or serious injury if not avoided. the tube-with-in-a-tube construction, it is ideal for low
temperature preheating and special process applications. The
WARNING construction features inner tubes with directional orifices to
Warnings indicate potentially hazardous situations, which can aid in steam distribution and condensate removal. Model JA
result in property damage, severe personal injury, or death if offers same-end supply and return connections. Model RA
not avoided. offers opposite-end supply and return connections. Model DA
offers dual-supply opposite-end connections for long coils that
CAUTION see sub-freezing air temperatures. Models GA, TA and LA
utilize cupro-nickel, carbon steel and stainless steel tubing for
Cautions indicate potentially hazardous situations, which can
high-pressure construction.
result in personal injury or equipment damage if not avoided.
Single Tube
Receiving Instructions McQuay model SA steam coils (Figure 1) are designed for
general purpose heating. The construction features a single
1 Coils should be inspected for shipping damage upon
tube design with opposite-end supply and return connections.
receipt. The freight bill should also be checked against
A perforated baffle located directly behind the supply
items received for complete delivery.
connection insures proper steam distribution. Model HA
2 Damaged and/or missing items should be noted on the utilizes cupro-nickel, carbon steel and stainless steel tubing for
carrier's freight bill and signed by the driver. high-pressure construction.

Figure 1: Coil Types

5R 5T 5J 5G 5S 5H

McQuay IM 901 3
Introduction
Nomenclature

5 SA 12 01 C 24.00 x 110.00
Tube O.D. Finned Length (inches)
8=1"
5=5/8"
Finned Heigth (inches)
Coil Type
Fin Design
5SA: single tube, opposite end connection
5JA, 8JA: distributing tube, same end connection A - flat (AI, Cu)
5DA, 8DA: distributing tube, dual supply, B - corrugated (AI, Cu)
opposite end connection C - sine wave (AI, Cu)
8RA: distributing tube, opposite end connection F - flat (SS, CS)
5HA: high-pressure constructionsingle tube, G - corrugated (SS, CU)
opposite end connection H - sine wave (SS, CU)
5GA, 8GA: high-pressure construction distributing
tube, same end connection
5LA, 8LA: high-pressure construction dual supply,
opposite end connection
8TA: high-pressure construction distributing tube,
opposite end connection
5SB: single tube, 3" center to center Rows Deep
opposite end connection

Fins Per Inch

4 McQuay IM 901
Installation
Mounting Installation
Installation

Steam coils must be properly mounted for condensate removal.


WARNING
This will aid in preventing destructive water hammer, keeping
Steam, even at low pressure, can cause serious bodily injury
coils from freezing and preventing corrosive elements from
that may result in death. Be sure the system is off or the
collecting in the tubes. Case-pitched coils (Figure 2) should be
components are isolated before beginning work..
installed level. McQuay models SA, SB, HA, JA, GA, DA,
LA, RA and TA come standard pitched in the casing. CAUTION
Coils that are un-pitched (Figure 3) must be installed with the Sharp edges on sheet metal and fasteners can cause
tubes pitched towards the return connection. A minimum pitch personal injury. This equipment must be installed, operated,
of 1/8” per foot of coil length is required (pitch has been and serviced only by an experienced installation company and
exaggerated in Figure 3). Coils with opposite end connections fully trained personnel.
(RA, TA, SA, & HA) should be furnished with an expansion Protective equipment such as safety glasses, steel toe boots
joint or provisions made for expansion on opposite connection and gloves are recommended during the installation and
end. routine maintenance of the coil.
Figure 2: Case Pitched
CAUTION
Failure to properly install the coil can result in irreparable
damage to the coil as well as other components in the system.

If you are unsure about any portion of the installation, contact


your local steam specialist for assistance.
1 Carefully remove the coil from the shipping package to
avoid damage to the finned surface area. Damaged fins can
Figure 3: Case Unpitched be straightened using an appropriate fin comb.
2 McQuay recommends cleaning the coil with a
commercially available coil cleaner prior to installation.
Refer to “Operation and Maintenance” on page 8 for
cleaning recommendations.
Note: Vacuum breakers and air vents should be piped to a
drain or other suitable location where discharged
steam cannot lead to personal injury.
3 Mount coil properly to provide positive condensate
drainage. Refer to “Mounting” on this page.
4 Proper clearance should be maintained between the coil
and other structures such as the fan, filter racks, transition
areas, etc.
5 Utilize vacuum breakers on each coil. Steam traps require a
positive pressure differential to force the condensate
through the valve seat. If the coil's pressure drops below
atmospheric, the pressure differential across the valve will
be negative and the condensate will not drain. This
condition can lead to serious damage or failure of the coil
due to freezing, water hammer and corrosion. Refer to
Figure 4 and Figure 5 for recommended placement.

McQuay IM 901 5
Installation
Figure 4: Low Pressure Steam Coil Piping Diagram

SYMBOLS FOR PIPING ARRANGEMENTS

LOW PRESSURE (TO 25 PSI)

*5JA or 8JA coil installed with tubes vertical.


The coil supply piping must be dripped ahead of
the coil on an installation of this type.

*5SA coil installed for vertical airflow. Installer


must pitch coil toward the return connection on
vertical airflow installations. For horizontal air-
flow installation, the required pitch is built into
the casing.

* NOTE: Rating data is ARI certified only for the


standard ARI coil orientation; i.e., horizontal
tubes, vertical coil face and horizontal airflow.

5JA or 8JA coil installed in


series. Note that each coil
must have a separate control
valve and trap.

8RA and 5SA coils banked three high by


three deep. Individual trapping of each coil
as shown is preferred. Note that it is nec-
essary to provide a separate control valve
for each bank in the direction of airflow.

*5SA coils installed with tubes vertical. Diagram


shows single trap; however, it is always preferable
to trap each coil individually.

* NOTE: Rating data is ARI certified only for stan-


dard ARI coil orientation; i.e., horizontal tubes,
vertical coil face and horizontal airflow.

6 McQuay IM 901
Installation
Figure 5: High Pressure Steam Coil Piping Diagram

SYMBOLS FOR PIPING ARRANGEMENTS

HIGH PRESSURE (OVER 25 PSI)

8TA or 5HA coils. Condensate is lifted to over-


5GA or 8GA coils. Note the addition of a vacuum head return main.
breaker to permit the coil to drain during shutdown.

6 Trap each coil separately. Differences in pressure from coil there are more than likely one or more small leaks, which
to coil can result in the backing-up of condensate that will should be located and repaired. Pressure losses greater than
result in poor coil performance and possible damage. 5 psig would indicate a larger leak, which should be
7 Provide an air vent for each coil at its highest location. isolated and repaired. Be sure to check valves and fittings
Non-condensable gasses present in the steam will collect in as potential sites for leakage or bleed. If the coil itself is
a coil and reduce its capacity. Therefore, it is necessary to found to be leaking, contact your local McQuay
provide a means for the removal of these gasses. Also, representative.
these gasses can diffuse into the condensate forming bi- Note: Unauthorized repair to the coil may void the coil's
products, which can lead to severe corrosion. warranty (see McQuay’s warranty policy on back
8 Steam supply lines need to be drained of condensate. This cover).
can be accomplished by the use of drip legs. This ensures 11 All field brazing and welding should be performed using
that high quality steam enters the coil. high quality materials and an inert gas purge (such as
9 Condensate return piping should be the same size as the nitrogen) to reduce oxidation of the internal surface of the
coil's return connection from the coil outlet to the steam coil.
trap. 12 All field piping must be self-supporting. System piping
10 Once installed, the coil should be pressurized to 100 psig should be flexible enough to allow for thermal expansion
with dry nitrogen or other suitable gas. The coil should be and contraction of the coil. The use of flexible connections
left pressurized for a minimum of 10 minutes. If the coil and/or swing joints is recommended.
holds the pressure, the hook-up can be considered leak free. 13 The coil along with the control valve and trap should be
If the pressure drops by 5 psig or less, re-pressurize the coil isolated by manual valves to allow for servicing.
and wait another 10 minutes. If the pressure drops again,

McQuay IM 901 7
Operation and Maintenance
Operation b Acti-Brite (AB-1) is the recommended cleaning
Operation and Maintenance

solution. Contact your local McQuay Parts Distributor.


General
1 Proper air distribution is vital to coil performance. Airflow CAUTION
anywhere on the coil face should not vary by more than Carefully read and follow the manufacturer's recommendations
20%. before using any cleaning fluid.
2 Air velocities should be maintained within McQuay’s c Determine required dilution for the specific application.
recommended values of between 200 and 1500 fpm. It is recommended to start with a dilution ratio of 10:1
3 Operating pressures must be at or below the maximum and increase concentration until the desired results are
operating pressure for that coil at the steam temperature. achieved.
Operating pressure maximum is 150 psig @ 300 F for low d As with mixing all acids, place the desired amount of
pressure steam coils and 350 psig @ 450 F for high water into the tank and then add the chemicals.
pressure steam coils.
e Turn off fans and allow hot coils to cool before
applying.
Maintenance f Using plain water, wet both the coil as well as the area
surrounding the equipment. Wetting the coil with water
DANGER aids in product penetration and performance.
Follow the manufacturer’s guidelines for lockout/tagout and
g Apply properly diluted product to coil surface.
disconnect all power to the unit before performing maintenance.
whenever possible, apply solution from the outlet side
Contact with high voltage power will cause electrical shock,
resulting in severe personal injury or death. of the coil. Allow solution to remain on surface,
normally 5-10 minutes. Do not allow solution to dry on
WARNING the coil.

Moving parts, high pressure, and/or high temperature fluids can Note: Note; In extreme cases, application may have to be
cause serious personal injury. repeated to achieve desired results.
h If foaming does not occur, check for extreme grease
General buildup which will slow cleaning process. Foaming may
not occur if coil is coated or painted.
1 Filters should be inspected on a regular basis and changed
as needed. Clean filters help maintain maximum coil i Rinse coils, tools and surrounding area thoroughly after
performance and service life. the coil cleaning.
2 Periodic inspection of the coil for signs of corrosion and/or j Clean the coil from the leaving airside so that foreign
leaks is recommended. Repair and replacement of the coil material will be washed out of the coil rather than
and the connecting piping, valves, etc., should be pushed further in.
performed as needed by a qualified individual. 5 Internal coil maintenance consists of preventing scale and
3 Should the coil surface need cleaning, caution should be corrosion. This is accomplished through aggressive boiler
exercised in selecting the cleaning solution as well as the water treatment, removal of dissolved oxygen and the
cleaning equipment. Improper selection can result in removal of non-condensable gasses such as carbon dioxide.
damage to the coil and/or health hazards. Note: Boiler water treatment is beyond the scope of this
4 Suggested cleaning instructions: manual. Contact your local water treatment
a When handling strong chemicals, be sure to wear specialist for assistance in establishing a proper
chemical impervious gloves, apron and splash goggles. boiler-water treatment program.

8 McQuay IM 901
McQuay Training and Development

Now that you have made an investment in modern, efficient McQuay equipment, its care should be a high priority.
For training information on all McQuay HVAC products, please visit us at www.mcquay.com and click on training, or
call 540-248-9646 and ask for the Training Department.

Warranty
All McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product
Warranty. Consult your local McQuay Representative for warranty details. Refer to Form 933-43285Y. To find your
local McQuay Representative, go to www.mcquay.com.

This document contains the most current product information as of this printing. For the most up-to-date product
information, please go to www.mcquay.com.

© 2008 McQuay International • www.mcquay.com • 800-432-1342

Vous aimerez peut-être aussi