AUXILIARY RELAYS

FOR TRIPPING
APPLICATIONS
This document may be subject to changes. Contact
ARTECHE to confirm the characteristics and availability
of the products described here.

Moving together
INDEX

4. ›› Answers for any tripping application

4. ›› Technical standards

5. ›› General characteristics
.
6. ›› Range of products

7. ›› Trip relays

11. ›› Trip and lockout relays



13. ›› Trip circuit supervision relays

14. ›› Auxiliary supply circuit supervision relays

15. ›› High / low burden configuration



16. ›› Breaking capacity

22. ›› Pick-up voltage/release voltage-temperature charts

24. ›› Model selection

26. ›› Dimensions and panel mounting cut-off

Auxiliary relays | Tripping applications 3


ANSWER FOR ANY
TRIPPING APPLICATION
ARTECHE offers a wide range of relays
specially designed to be used in circuit
breaker tripping applications.

›› Interface between protection and control


equipments and HV and/or MV primary
equipment, protecting valuable and with
not easy replacement assets from the failure
of those main actuators.
›› Trip contacts multiplication, to operate
directly on the primary equipment and
transmit the corresponding alarms in a
minimum and cohesive time.
›› Trip and lock-out, with electric or hand reset
to avoid accidental actuation on circuit
breakers associated to power transformers,
generators or machines.
›› The surveillance of the trip circuit,
guarantees it is in perfect conditions to
allow the trip when it is needed.

TECHNICAL STANDARDS
GENERAL STANDARDS

In addition to the specific applicable standards, ARTECHE auxiliary


relays are designed to comply the following standards as reference:

›› IEC 61810: Electromechanical all-or-nothing relays.


›› IEC 60255: Electrical relays. Measuring relays and protection
equipment.
›› IEC 61812: Specified time relays for industrial use.
›› IEC 60947: Low-voltage switchgear and controlgear.
›› IEC 61000: Electromagnetic compatibility.

4 Auxiliary relays | Tripping applications


GENERAL
CHARACTERISTICS
Some of the general characteristics of the ARTECHE
trip relays are:

›› High isolation level between circuits, which


guarantees that a problem in the primary
equipment will not cause irreparable
damages in the secondary equipment
(typically, protection/control electronics).
›› Fastoperating times, down to 3 ms,
minimizing the impact on the total trip time.
›› High breaking capacity, which allows direct
operation on highly inductive circuits.
›› Sturdy design, which ensures high reliability.
›› Wide range of auxiliary voltage (Vdc and
Vac).
›› Self-cleaning of the contacts.
›› Security contacts according to EN 50205.
›› Versatile installation (plug-in relays with
different installation possibilities).
›› Designed to work in permanent service,
even at high temperature for the whole
voltage range.
›› Capable to work under environments with
relative humidity around 100%.
›› Tested to comply seismic standards,
allowing their use in installations which can
be subject to vibrations, as for example in
power stations or in regions with high risk
of seism.
›› High protection degree (IP40), with
transparent cover, enabling its use in tropical
and saline environments.
›› Compliant of the most demanding
standards: IEC, EN, IEEE, CE and UL mark.
›› No maintenance needed.

In addition, the different number of alternatives available while the


equipment is selected, both technically (increase of the breaking
capacity by serializing contacts, high speed operation, possibility of
adding different options to the relay) and in the assembly method
(front, rear or flush mounted sockets, with screws or fastons) must be
considered.

E322124

UL Recognized Component Marks for USA and


Canada: The combined UL signs for the USA and
Canada are recognized by the authorities of both
countries. All auxiliary relays identified with this mark
meet the requirements of both countries.

Auxiliary relays | Tripping applications 5


RANGE OF PRODUCTS
TRIP RELAYS
Instantaneous trip relays, whose contacts change instantaneously from
the rest position to the working position when the coil is energized.
The contacts return to the rest position when the coil is no longer
energized.

This range includes relays with 2, 4, 8 and 16 contacts, with operating


times from 3 ms to 8 ms, depending on the model.

All the relays include a diode in parallel with the coil (see auxiliary
relays with overvoltage protection characteristic) and comply with
the shock and vibration standards, related to the relays with seismic
characteristics.

TRIP AND LOCKOUT RELAYS


Trip relays with 2 stable positions for the output contacts. Depending
on which coil is energized, the contacts will change from one position
to the other. The design of the ARTECHE relays has no consumption
in permanence, and prevents both coils from being energized
simultaneously.

This range includes relays with 3, 4, 8 and 16 contacts, with operating


times below 10 ms, depending on the model, and possibility of manual
reset. The position change is made with 2 sets of coils with separated
entrances, in BF-3 and BJ-8, and with breaking-flame contacts for each
set of coils.

TRIP CIRCUIT SUPERVISION RELAYS


For single phase or three phase coil breakers. Through a small
supervision current the whole circuit is supervised, in both positions of
the circuit breaker (open or closed).

The correct state of the circuit is showed with a green LED on the front
plate of the relay. The output contacts change their position if the relay
detects a failure in the continuity of the circuit.

The single coil trip circuit supervision relay can be manufactured with
different LED indicator configurations, refers to selection chart for
more detailed information

AUXILIARY SUPPLY CIRCUIT SUPERVISION


RELAYS
Auxiliary relay with four changeover contacts, aimed to supervise the
failure of trip supply.

Connecting the relay across the trip circuit supply, the equipment
is normally energized. Faults will occur when the trip voltage is lost,
so the relay drops off in those cases, providing the related signs and
alarms. In order to avoid faulty alarms due to instantaneous supply
voltage dips, the drop off time of the relay is delayed over 100 ms so
those non-permanent failures of trip supply would not be considered.

Auxiliary supply circuit supervision relays can be manufactured


with different LED indicator configuration, refers to selection chart
for more detailed information

6 Auxiliary relays | Tripping applications


TRIP RELAYS

›› World-class range of
auxiliary relays for
energy sector, specially
designed for the most
demanding applications

Auxiliary relays | Tripping applications 7


TRIP RELAYS (I)
Model RD-2R RD-2XR RF-4R RF-4XR

Applications Intended for tripping applications where high demanding requirements in operating time
(with tripping time from 8ms to 3 ms) and breaking capacity are needed,
that is the case of tripping HV and MV circuit breakers.

High burden configuration not available See page 15 for technical details
Construction characteristics
Contacts no. 2 Changeover 4 Changeover

11
3 7
(+) 2 7 (+) 2
12
3 5 4 8
8 13
4 6 5
Connections 9
(-) 1 (-) 1 14
6 10
Options
With 0P options • LED included • Diode in parallel with the coil included
Weight (g) 125 250
Dimensions (mm) (A) 22,5 x (B) 50,4 x (C) 72 (D type) (A) 42,5 x (B) 50,4 x (C) 72 (F short type)
Coil characteristics

Standard voltages(1) 24, 48, 110, 125, 220, 24, 48, 110, 125, 220,
250 Vdc /110, 127, 48, 110, 125, 220, 250 250 Vdc / 110, 127, 48, 110, 125, 220, 250
230 Vac (50-60Hz) Vdc 230 Vac (50-60 Hz) Vdc

Voltage range +10% -20% UN


Pick-up voltage
See pick-up/release voltage-temperature curves
Release voltage
Average consumption In permanence (UN) 0,95 W 1W

Peak • ≤96 Vdc 0,8 A / 20 ms 2,5 A / 20 ms 0,8 A / 20 ms 2,5 A / 20 ms

Peak • >96 Vdc 0,3 A / 20 ms 0,8 A / 20 ms 0,3 A / 20 ms 0,8 A / 20 ms


Operating time
Pick-up time <8 ms (<10 ms Vac) <5,5 ms <8 ms (<10 ms Vac) <5,5 ms
Drop-out time Vdc: <40 ms Vdc: <40 ms Vdc: <40 ms Vdc: <40 ms
Vac: <50 ms Vac: <50 ms
Contacts
Contact material AgNi
Contacts resistance (2)
≤30 mΩ
Distance between contacts 1,2 mm
Permanent current 10 A
Instantaneous current 30 A during 1 s / 80 A during 200 ms / 200 A during 10 ms
Max. making capacity 40 A / 0,5 s / 110 Vdc
Breaking capacity See breaking capacity curves (Contact configuration type B)
Max. breaking capacity See value for 50.000 operations
Umax opened contact 250 Vdc / 400 Vac
Perfomance data
Mechanical endurance 107 operations
Operating temperature -25ºC +70ºC
Storage temperature -40ºC +85ºC
Max. operating humidity 93% / +40ºC
Operating altitude (3)
<2000 m

(1)
Other voltage upon request (3)
Ask for higher altitudes
(2)
Guarantee data for relays just manufactured

8 Auxiliary relays | Tripping applications


TRIP RELAYS (II)
Model RJ-8R RJ-8XR RJ-4XR4*

Intended for tripping applications where high quality requirements in operating time (with models
Applications even tripping in less than 3 ms) and breaking capacity are needed, that is the case of tripping HV and
MV circuit breakers.

High burden configuration See page 15 for technical See page 15 for technical
not available
details details
Características constructivas
4 Changeover +
Contacts no. 8 Changeover 4 Fast Singles-Inversors without break
power
10
10
1 1 11
11
20 20
2 2 21
21

Trip
30 30
3 3 31
31
(+) d (+) d
Connections 40 40
4 4 41
41
50
50
5 51 5

High breaking capacity


(-) a (-) a 51
60
60
6 61 6 61
70
70
7 71 7 71
80
80
8 81 8 81

Options With 0P options • LED included • Diode in parallel with the coil included
Weight (g) 500 335
Dimensions (mm) (A) 82,5 x (B) 50,4 x (C) 72 (J short type) (A) 82,5 x (B) 50,4 x (C) 72 (J short Type)

Coil characteristics
Standard voltages(1) 24, 48, 110, 125, 220, 250 48, 110, 125, 220, 110, 125, 220, 250 Vdc
Vdc/110, 127, 230 250 Vdc
Vac (50-60 Hz)
Voltage range +10% -20% UN +15% -20% UN
Pick-up voltage 85% UN
See pick-up/release voltage-temperature curves
Release voltage 65% UN
Average consumption In permanence (UN) 1,4 W 6,5 W

Peak • ≤96 Vdc 0,8 A / 20 ms 2,5 A / 20 ms 25 W / 5 ms

Peak • >96 Vdc 0,3 A / 20 ms 0,8 A / 20 ms

Operating time
Pick-up time <8 ms Vdc (<10 ms Vac) <6,5 ms Contacts 1-4: <3 ms
(Range 24 Vdc <10 ms) Contacts 5-8: <20 ms
Drop-out time Vdc: <40 ms Vdc: <40 ms Contacts 1-4: <25 ms
Vac: <50 ms Contacts 5-8: <50 ms
Contacts
Contact material AgNi

Contacts resistance(2) ≤30 mΩ

Distance between contacts 1,2 mm Contacts 5-8: 1,2 mm

Permanent current 10 A Contacts 1-4: 8 A


Contacts 5-8: 15 A

Instantaneous current 30 A during 1 s / 80 A during 200 ms / 200 A during 10 ms Contacts 5-8: 30 A during 1 s / 80 A
during 200 ms / 200 A during 10 ms

Max. making capacity 40 A / 0,5 s / 110 Vdc Contacts 5-8: 40 A / 0,5 s / 110 Vdc

Breaking capacity See breaking capacity curves (Contact configuration type B) Contacts 5-8: See breaking capacity
curves (Contact configuration type B)

Max. breaking capacity See value for 50,000 operations Contacts 5-8: See value for 50,000
operations

Umax opened contact 250 Vdc / 400 Vac

Perfomance data
Mechanical endurance 107 operations

Operating temperature -25ºC +70ºC -40ºC +55ºC

Storage temperature -40ºC +85ºC

Max. operating humidity 93% / +40ºC

Operating altitude(3) <2000 m

(1)
Other voltage upon request (3)
Ask for higher altitudes *Not recognized by UL
(2)
Guarantee data for relays just manufactured

Auxiliary relays | Tripping applications 9


TRIP RELAYS (III)
Model RI-16R RXR-4 RF-4UR

Intended for trip applications where


Applications high demanding requirements in
operating Tripping applications with very high Tripping applications with very high
time and breaking capacity are speed requirements. speed requirements.
needed.

High burden configuration See page 15 for technical details Not available Not available
Construction characteristics

Contacts no. 16 Changeover 4 Changeover 4 Changeover


Terminals A Terminals B
10 10
1 11 1 11
NC1 11
20 20
2 2 C1 3 7
21 21 NO1
30 30 2 +
12
Connections 3 31 3 31 (+) 2 NC2
(-) d 4 8
40 40 C2
4 4
NO2
41 41 13
50 50 NC3 5
5 5 9
51 51 C3
60
(+) a
60 NO3 1 - 14
6 6
61 61
(-) 1 NC4 6 10
70 70
7 7 C4
71 71 NO4
80 80
8 81 8 81
Options
With OP options • Operation indication With 0P options • LED included
LED • Alarm indication LED with • Diode in parallel with the coil
manual reset No options available included
Weight (g) 1250 126 250

Dimensions (mm) (A) 120 x (B) 110 x (C) 105 (A) 53 x (B) 90 x (C) 58 (A) 42,5 x (B) 50,4 x (C) 72 (type
F short)
Coil characteristics

Standard voltages(1) 48, 110, 125, 220 Vdc 110, 125, 250 Vdc 110, 125, 250 Vdc
Voltage range +10% -20% UN +10% -20% UN +10% -20% Un
Pick-up voltage See pick-up/release voltage- 61% 75%
Release voltage
temperature curves 26% 40%
Average consumption 12 W 2,8 W 2W

Operating time

Pick-up time < 10ms <3 ms < 3ms


Drop-out time <50 ms <4 ms < 4ms
Contactos

Contact material AgNi AgNi AgNi


Permanent current 10 A 8A 8A
Max. making capacity 40A / 0,5 s / 110 Vdc 15 A during 4s 15 A during 4s
Breaking capacity ee breaking capacity curves See breaking capacity curves See breaking capacity curves
(Contact configuration type A)
Umax opened contact 250 Vdc / 400 Vac 250 Vdc / 400 Vac 250 Vdc / 400 Vac
Performance data

Mechanical endurance 107 operations 107 operations 107 operations

Operating temperature -25ºC +70ºC -40ºC +55ºC -40ºC +55ºC


Storage temperature -40ºC +85ºC -40ºC +85ºC -40ºC +85ºC
Max. operating humidity 93% / +40ºC 93% / +40ºC 93% / +40ºC
Operating altitude(2) <2,000 m <2,000 m <2,000 m

(1)
Other voltage upon request
(2)
Ask for higher altitudes

10 Auxiliary relays | Tripping applications


TRIP AND LOCKOUT RELAYS (I)
Model BF-3R BF-4R BJ-8R BJ-10R BI-16R

Applications Intended for trip and lockout applications where high demanding requirements in operating
time and breaking capacity are needed.

High burden See page 15 for See page 15 for See page 15 for See page 15 for
not available
configuration technical details technical details technical details technical details
Construction characteristics

Contacts no. 3 Changeover 4 Changeover 8 Changeover 10 Changeover 16 Changeover


10 00 A Terminals B Terminals
0 10 10
1 11
01
10 1 11 1 11
20 1 11 20 20
2 21 20 2 2
+ 11 21 21
b 2
+
Trip

14 3 30 21 b
=

11 7 30 30

Trip
+

Trip
3 b +

=
B1 30
Trip

=
3 31 + 3 3
7
=

12 3 31 31

=
31
4 40
Connections -
10
12
2
8 a 4 a
40 40
a
40
4 41 4 41 4 41 -
4 41
8 13 - -
-
50 50
50 50
+ 13 5 9 d d
5 d

Reset
Reset
Reset

5 + 51 5 5

-
+ 51 +

-
-
2 51 51
Reset

5
-

9 14 60
-

+ 60 6 60 60
6 10 c 61
1 6 61 6 c 6
- c - 70 61 61
- 7 -
1 70 71 70 70
7 80 7 71 7 71
71
8 81
80 80 80
90 8 8
8 81 81
Options Options are not available 81 9 91

Weight (g) 300 600 600 1250

Dimensions (mm) (A) 45 x (B) 45 x (C) 96,5 (F large Type) (A) 90 x (B) 50 x (C) (A) 109 x (B) 50 x (A) 120 x (B) 110 x
100,5 (C) 111 (C) 105
(J large Type)
Coil characteristics

Standard voltages(1) 24, 48, 72, 110, 125, 220 Vdc / 63,5, 110, 127, 230 Vac (50-60 Hz)
Voltage range +10% -20% UN
Pick-up voltage See pick-up voltage / temperature curves for Latching relays
Average consumptions 17 W 17 W 30 W 30 W 90 W
only in the change-over
Operating time
Pick-up time <10 ms (Vdc) <20 ms (Vac)
Contacts
Contact material AgNi
Distance between 1,8 mm
contacts
Permanent current 10 A
Instantaneous current 80 A during 200 ms / 200 A during 10 ms
Max. making capacity 40 A / 0,5 s / 110 Vdc
Breaking capacity See breaking capacity curves (Contact configuration type A)
Max. breaking capacity See value for 50.000 operations
Umax opened contact 250 Vdc / 400 Vac
Performance data
Mechanical endurance 107 operations 106 operations
Operating temperature -40ºC +70ºC
Storage temperature -40ºC +85ºC
Max. operating humidity 93% / +40ºC
Operating altitude(2) <2000 m

(1)
Other voltage upon request
(2)
Ask for higher altitudes

Auxiliary relays | Tripping applications 11


TRIP AND LOCKOUT RELAYS (II)
Model BF-4RP BJ-8RP BJ-10RP BI-16RP

Applications Intended for tripping and locking applications where high quality requirements in operating time and breaking capacity are
needed, with manual reset.

High burden configuration See page 15 for technical details


Construction characteristics

Contacts no. 4 Changeover 8 Changeover 10 Changeover 16 Changeover


00
10 A Terminals B Terminals
0 01
1 11 10 10
10 1 11 1 11
20 1 11
2 20 20
11 21 20 2 2
2 21 21
+ 3 b 30 21 b
Connections 7 30 30

Trip
B1 3 +
Trip

b
Trip

+ 30

=
31
=
3 3
=

12 + 3 31 31

=
31
4 40
8 40 40 40
2 4 a
a 41 a 4 4 4
- 13 41 41 - 41
- -
5 50
-

50 50 50
Reset

9 d d

Reset
d 5 5 5 + 5

-
51 + 51 51 51

-
Reset

14 +
+
-

60
6 60 60 60
1 10 6 61 6 6
6 61
c
61 c 61
- 70 -
c 70 70
70 7
- 71
7 7
7 71 71 71
80
8 80 80
80 81
8 81 8 81
8 81
90
9
Options Options are not available 91

Weight (g) 300 600 600 1400


Dimensions (mm) (A) 45 x (B) 45 x (C) 96,5 (A) 90 x (B) 50 x (C) 100,5 (A) 109 x (B) 50 x (C) 111 (A) 120 x (B) 110 x (C) 105
(F large Type) (J large Type)
Coil characteristics

Standard voltages(1) 24, 48, 72, 110, 125, 220 Vdc 48, 110, 125, 220 Vcc(3)
63,5, 110, 127, 230 Vac (50-60 Hz)
Voltage range +10% -20% UN
Pick-up voltage (20ºC) See pick-up voltage / temperature curves for Latching relays

Average consumptions only 17 W 30 W 30 W 90W


in the change-over
Operating time
Pick-up time <10 ms (Vdc) <13 ms (Vac) <10 ms (Vdc) <20 ms (Vac) <10 ms (Vdc) <20 ms (Vac) <10 ms
Contacts
Contact material AgNi
Distance between contacts 1,8 mm
Permanent current 10 A
Instantaneous current 80 A during 200 ms / 200 A during 10 ms
Max. making capacity 40 A / 0,5 s / 110 Vdc
Breaking capacity See breaking capacity curves (Contact configuration type A)
Max. breaking capacity See value for 50,000 operations
Umax opened contact 250 Vdc / 400 Vac
Performance data
Mechanical endurance 107 operations 106 operations
Operating temperature -40ºC +70ºC
Storage temperature -40ºC +85ºC
Max. operating humidity 93% / +40ºC
Operating altitude(2) <2000 m

(1)
Other voltage upon request
(2)
Ask for higher altitudes
(3)
Vac voltage upon request

12 Auxiliary relays | Tripping applications


TRIP CIRCUIT SUPERVISION
RELAYS
Model VDF-10 VDJ-30

Applications Trip circuit supervision for single-phase circuit Trip circuit supervision for three-phase circuit
breakers breakers

Construction characteristics
Timing Contacts no. 2 Changeover 2 Changeover

FU
TRIP SUPPLY
+

FU
TRIP SUPPLY
Connections Trip contact
1 2 3
Trip contact Trip contact Trip contact

6 5
1 4 1 2 a 3 b 4 e 7

K23
K22

K13
K21

K12
K2

K11
K1 h

40
30

41

70
31

71
10

21

20
11
2 12 8
10 14 9 13

52b

52b

52b
52a

52a

52a
CB1 CB2 CB3
52a 52b
CIRCUIT BREAKER

CB
CIRCUIT BREAKER FU
TRIP SUPPLY
-

FU
TRIP SUPPLY
-

With OP options.
Options See model selection table. Options are not available.
Weight (g) 100 163
Dimensions (mm) (A) 42,5 x (B) 50,4 x (C) 96,6 (F large Type) (A) 82,5 x (B) 50,4 x (C) 96,6 (J large Type)
Coil characteristics

Standard voltages(1) 24/30, 60, 110/125, 220 Vdc, 110/127, 230 Vac 24/30, 60, 110/125, 220 Vdc
(50-60 Hz)
Voltage range +10% -25% UN
Pick-up voltage (23º C) 70% UN

Release voltage (23º C) 60% UN

Consumptions 1,35 W 1,6 W

Operating time
Drop-out time >500 ms
Contacts
Contact material AgNi
Permanent current 8A
Instantaneous current 15 A
Max. making capacity 15 A during 4 s
Max. breaking capacity 0,3 A / 110 Vdc
Umax opened contact 250 Vdc / 400 Vac
Performance data
Mechanical endurance 107 operations
Operating temperature -40ºC +55ºC
Storage temperature -40ºC +85ºC
Max. operating humidity 93% / +40ºC
Operating altitude(2) <2000 m

(1)
Other voltage upon request
(2)
Ask for higher altitudes

Auxiliary relays | Tripping applications 13


AUXILIARY SUPPLY
SUPERVISION RELAYS
Model RUT- 4 OP RUT- 4 OP 2

Applications Supervise only the auxiliary supply circuit of the protection equipments,
avoiding false alarms due to short-time drop of supply

Construction characteristics
Timing Contacts no. 4 Changeover

11
3 7
(-) 1 12
4 8
Connections 13
5 9
(+) 2 14
6 10
Options With OP options. See model selection table.
Weight (g) 265
Dimensions (mm) (A) 42,5 x (B) 50,4 x (C) 96,6 (F large Type)
Coil characteristics

Standard voltages (1) 24, 48, 72, 110, 125, 220 Vdc 48, 60, 110, 125 Vdc
63,5 , 110 , 127 , 230 Vac
Voltage range +10% -20% UN
Voltage limits See pick-up release voltage-temperature
curves for standard relays
Average consumptions in permanence 4,5 W

Operating time
Timing range
Pick-up time <20 ms < 35 ms
Drop-out time
To minimum voltage >100 ms
To maximum voltage <400 ms
Tolerance
Contacts
Contact type 4 Changeover
Contact material AgNi
Contacts resistance (2)
≤30 mΩ
Distance between contacts 1,8 mm
Permanent current 10 A
Instantaneous current 80 A during 200 ms / 200 A during 10 ms
Max. making capacity 40 A / 0,5 s / 110 Vdc
Breaking capacity See breaking capacity curves
(Contact Configuration Type A)
Max. breaking capacity See value for 50.000 operations
Umax opened contact 250 Vdc / 400 Vac
Performance data
Operating temperature -40ºC +55ºC
Storage temperature -40ºC +85ºC
Max. operating humidity 93% / +40ºC
Operating altitude(3) <2000 m

(1)
Other voltage upon request
(2)
Guarantee data for relays just manufactured
(3)
Ask for higher altitudes

14 Auxiliary relays | Tripping applications


HIGH / LOW BURDEN CONFIGURATION
High Burden configuration:
›› Fast and extra-fast types
Low Burden configuration:
›› Ultra-fast, extra-fast and fast types

The standard high speed tripping relays For relays with rated voltage up to and
are manufactured with a low burden including the 125 V, the relays will withstand,
configuration, considering that the initiating without operating, a discharge into their
contact is placed close to the tripping relay. operate circuits of a 10µF capacitor charged
to 120% of the nominal voltage.
However, and in order to avoid unwanted trip
relay operation due to pickup or transients, For relays with rated voltage of 220 V, the
particularly if the relay operating coil is relays will withstand, without operating a
connected to extensive wiring, ARTECHE discharge into their operate circuits of a 10µF
tripping relays could be manufactured with capacitor charged to 100% of the nominal
a high burden configuration, complying with voltage.
ESI 48-4 international standard, as EB2 class
relays. These EB2 class relays are suitable Specifications:
for use in high security circuit breaker
tripping circuits, increasing their immunity to ESI 48-4 EB1: 1983 Low Burden
capacitance discharge currents. ESI 48-4 EB2: 1983 High Burden

HIGH BURDEN RELAYS CONSUMPTIONS


See table below:

Standard Voltage Consumption

Model Peak (< 2ms) Steady-State

RF4R HB ≤4W
Instantaneous
RJ8R HB ≤ 300 W ≤6W

RI16R HB ≤4W

≤ 21 W
RF4R (RP) HB
(Only In commutation)
≤ 45 W
Latching BJ8R (RP) HB
(Only In commutation)
Electrical and ≤ 500 W
≤ 45 W
hand&electric reset BJ10R (RP) HB
(Only In commutation)

≤ 90 W
BI16R (RP) HB
(Only In commutation)

Auxiliary relays | Tripping applications 15


BREAKING CAPACITY

›› With devices operating


worldwide, also heavy
industries like oil &
gas sector trust in our
relays.

16 Auxiliary relays | Tripping applications


BREAKING CAPACITY MAX. BREAKING CAPACITY ULTRA-FAST
TYPE (Tripping contact):
The breaking capacity is a critical parameter on
the design and the applications of the relays.
Its mechanical life could be considerably
reduced, depending on the value of the
load (especially with heavy duty loads), the
number of operations and the environmental
conditions in which the relay is operating.

In any configuration, ARTECHE’s auxiliary


relays have a high breaking capacity values.
These limits are showed in the table below,
in terms of power and current values. In
all the cases, these relays guarantee a right
performance during 50,000 operations.

Likewise, the values showed in the following


ELECTRICAL ENDURANCE ULTRA-FAST TYPE
charts have been obtained in standard (Tripping contact):
conditions in the laboratory, and they could
be different in real conditions. In any case,
the possibility of connecting serial contacts ›› Voltage 250Vac
or a bigger distance between contacts makes ›› Configuration of
these values to be considerably increased. resistive load:
›› L/R=0 ms
ELECTRICAL ENDURANCE
OTHER MODELS

24 Vdc voltage *The two loads may open


simultaneously up to 8A
Different loads configurations.

Resistive load: Highly inductive load:


›› L/R= 0 ms. ›› L/R= 40 ms.
10000000
107 10000000
107

106
1000000 1000000
106
No. operations

No. operations

100000
105 100000
105

104
10000 10000
104
0
0,00 5,00
5 10,00
10 15,00
15 20,00
20 25,00
25 0,00
0 2,00
2 4,00
4 6,00
6 8,00
8 10,00
10 12,00
12

Current Current
Type A (Distance between contacts = 1,8 mm)
Type B (Distance between contacts = 1,2 mm)

0 ms 20 ms 40 ms

Vdc Contact configuration P(W) I(A) P(W) I(A) P(W) I(A)

Type A
500 20,83 370 15,42 250 10,42
24
Type B 450 18,75 300 12,50 210 8,75

Auxiliary relays | Tripping applications 17


110 Vdc voltage
Different loads configurations.
Resistive load: Highly inductive load:
›› L/R= 0 ms. ›› L/R= 40 ms.

10000000
107 10000000
107
No. operations

No. operations
1000000
106 1000000
106

100000
105 100000
105

10000
104 104
10000
0
0,00 1
1,00 2
2,00 3
3,00 4
4,00 5
5,00 6
6,00 7
7,00 8
8,00 9
9,00 10
10,00 0
0,00 1
1,00 2
2,00 3
3,00 4
4,00 5
5,00 6
6,00 7
7,00

Current Current

Type A (Distance between contacts = 1,8 mm) 2 contacts type A


Type B (Distance between contacts = 1,2 mm) 2 contacts type B

0 ms 20 ms 40 ms

Vdc Contacts configuration P(W) I(A) P(W) I(A) P(W) I(A)

Type A
170 1,55 140 1,27 90 0,82

Type B 125 1,14 100 0,91 65 0,59

110 2 contacts type A 1.360 12,36 1.106 10,05 730 6,63

2 contacts type B 874 7,95 742 6,74 482 4,38

125 Vdc voltage


Different loads configurations.
Resistive load: Highly inductive load:
›› L/R= 0 ms. ›› L/R= 40 ms.
10000000
107 107
No. operations

No. operations

1000000
106 106

100000
105 105

104
10000 104
0 1 2 3 4 5 6 7 8 9 10 0 0,5 1 1,5 2 2,5 3 3,5 4
0,00 1,00 2,00 3,00 4,00 5,00 6,00 7,00 8,00 9,00 10,00
Current Current

Type A (Distance between contacts = 1,8 mm) 2 contacts type A


Type B (Distance between contacts = 1,2 mm) 2 contacts type B

18 Auxiliary relays | Tripping applications


0 ms 20 ms 40 ms

Vdc Contacts configuration P(W) I(A) P(W) I(A) P(W) I(A)

Type A
158 1,26 120 0,96 75 0,60

Type B 125 1 96 0,77 65 0,52


125

2 contacts type A 987,5 7,90 733,809 5,87 472,972 3,78

2 contacts type B 528,547 4,23 395,983 3,17 263,827 2,11

220 Vdc voltage


Different loads configurations.

Resistive load: Highly inductive load:


›› L/R= 0 ms. ›› L/R= 40 ms.
10000000
107 10000000
107

1000000
106 106
1000000
No. operations

No. operations

100000
105 100000
105

10000
104 104
10000
0,00
0,00 0,20
0,20 0,40
0,40 0,60
0,60 0,80
0,80 1,00
1,00 1,20
1,20 1,40
1,40 1,60
1,60 0,00
0,00 0,10
0,10 0,20
0,20 0,30
0,30 0,40
0,40 0,50
0,50 0,60
0,60 0,70
0,70 0,80
0,80

Current Current

Type A (Distance between contacts = 1,8 mm) 2 contacts type A


Type B (Distance between contacts = 1,2 mm) 2 contacts type B

0 ms 20 ms 40 ms

Vdc Contacts configuration P(W) I(A) P(W) I(A) P(W) I(A)

Type A
150 0,68 115 0,52 66 0,30

Type B 125 0,57 104 0,47 60 0,27


220

2 contacts type A 319 1,45 234 1,06 134 0,61

2 contacts type B 242 1,10 177 0,81 100 0,45

Auxiliary relays | Tripping applications 19


HOW TO SELECT THE CURVE
OF MY RELAY
These charts show the breaking capacity values, either for resistive
and highly inductive loads, in three voltage values of reference (ask for
other voltage values). The charts show four different curves:

›› TypeA: Breaking capacity of the relays with distance between


contacts = 1.8 mm.
›› TypeB: Breaking capacity of the relays with distance between
contacts = 1.2 mm.
›› 2 contacts type A: Breaking capacity for relays with serial contacts,
and distance between contacts=1.8 mm.
›› 2 contacts type B: Breaking capacity for relays with serial contacts,
and distance between contacts=1.2 mm.

The distance between contacts is shown in the tables of technical data.

HOW THE BREAKING CAPACITY


CAN BE INCREASED
ARTECHE’s auxiliary relays are power relays, designed specially to
have a high breaking capacity. Thus, there are applications where the
loads are so high that it is necessary to even increase the breaking
capacity, keeping the reliability of the contacts of the auxiliary relays.

Recommendations to increase breaking capacity:

›› Connect contacts in series. The breaking capacity is increased


considerably, guaranteeing the right performance during a high
number of operations. See curves for two contacts.
›› Use ARTECHE range of contactors. See ARTECHE contactors
catalogue for more detailed information.

LOW DUTY LOADS CAPALBLE


RELAYS (LDL)
There are some applications where the relay contacts stablish circuits
where the driven current is intrinsically low and are very dependent
upon the voltage applied. In this kind of use, if the voltage applied
to those kind of circuits differs (even slightly) from the one already
specified, the circuit energisation fails. One of these cases is when we
use relays to activate digital inputs. In these situations is necessary
to minimise the contact resistance in the relay. To achieve that, while
the relay is manufactured, its contacts are submitted to an special
conditioning to make its contacts resistance extremely low.

20 Auxiliary relays | Tripping applications


PICK-UP VOLTAGE/RELEASE
VOLTAGE-TEMPERATURE
CHARTS

Auxiliary relays | Tripping applications 21


Variability of operative voltage range against temperature for the
instantaneous auxiliary relays.

TRIPPING RELAYS

Operative range against ambient temperature.

Maximum storage temperature

200

Upper limit of the pick-up voltage

150 Pick-up voltage limit


U/UN (%)

Drop-out voltage limit


100
Operative range of the coil voltage

50

0
-40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100

Temperature (ºC)

TRIP AND LOCKOUT RELAYS AND TRIP AND


LOCKOUT RELAYS WITH RESET PUSH BUTTON

Operative range against ambient temperature.

Maximum storage temperature


250

200

Upper limit of the pick-up voltage


150

Pick-up voltage limit


U/UN (%)

100
Operative range of the coil voltage

50

0
-40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130

Temperature (ºC)

22 Auxiliary relays | Tripping applications


MODEL SELECTION
TRIP Type Range Aux. Supply Options

Model Selection OP

Relay type
2 contacts relay RD-2R -* 0* 1 0 0 0
2 contacts relay RD-2XR -* 0* 1 0 0 0
4 contacts relay RF-4R 0* 1 0 0 0

Standard model
4 contacts relay RF-4XR 0* 1 0 0 0
8 contacts relay RJ-8R 0* 1 0 0 0
8 contacts relay RJ-8XR 0* 1 0 0 0
Ultra-fast (only Vdc) RJ-4XR4 -* 0* 1* 0* 0* 0*
Ultra-fast (only Vdc) RXR-4 -* -* -* -* -* -*
Ultra-fast (only Vdc) RF-4UR -* -* -* -* -* -*

Range
High Burden HB
Low burden (all by default) -

Low duty loads** LD

Aux. Supply Vdc or Vac


Indicate voltage level and if it is
VDC or VAC (ex: 24 VDC)

Options
0

No 0
Front LED
Yes 1

Mechanical contact position No 0


indicator Yes 1

No 0
Trip flag
Yes 1

No 0
Push to test button
To Push the contacts 1
*Mandatory option
** For more information refer to railway application brochure
*** Option only available for HB models with 48 and 125 Vdc rated voltage. Red LED for trip signaling.

Trip Type Range Aux. Supply Options

Model Selection OP

Relay type
16 contacts relay RI-16R -0*

Range
High Burden HB
Low burden (all by default) -

Aux. Supply - Vdc or Vac


Indicate voltage level and if it is VDC or VAC

Options
0

Operation indicator (green) LED 1000


Front LED
Alarm indicator (red) LED with manual reset** 2010
*Mandatory option
**Available for 125 and 48 VDC, other voltages upon request.

Auxiliary relays | Tripping applications 23


Trip and lockout Type Range Aux. Supply

Model Selection

Relay type
3 contacts relay BF-3R -
4 contacts relay BF-4R
4 contacts relay BF-4RP
8 contacts relay BJ-8R
8 contacts relay BJ-8RP
10 contacts relay BJ-10R
10 contacts relay BJ-10RP
16 contacts relay BI-16R
16 contacts relay BI-16RP

Range
High Burden HB
Low burden (all by default) -

Aux. Supply - Vdc or Vac


Indicate voltage level and if it is VDC or VAC (ex: 24 VDC)

Trip circuit supervision Type LED Indicator Aux. Supply


configuration

Model Selection

Relay type
One phase VDF-10
Three phase VDJ-30

One phase relay LED Indicators configurator


Correct operation of the VDF-10 OP is shown via an illuminated green LED
OP.
(in the bottom left)
Correct operation of the VDF-10 OP is shown via an illuminated red LED
OP.1
(in the bottom left)
Correct operation of the VDF-10 OP is shown via an illuminated green LED (in the
OP.2
bottom left) in case of loss of continuity a red LED is illuminated in the upper left

Aux. Supply- Vdc or Vac


Indicate voltage level and if it is VDC or VAC (ex: 24 VDC)

Auxiliary supply circuit supervision Type LED Indicator Aux. Supply


configuration

Model Selection

Relay type
One phase RUT-4

One phase relay Indicators.Options


Correct operation of the RUT-4 OP is shown via an illuminated green LED
OP.
(in the bottom left)
Correct operation of the RUT-4 OP is shown via an illuminated green LED (in the
OP.2
bottom left) in case of voltage lack a red LED is illuminated in the upper left

Aux. Supply- Vdc or Vac


Indicate voltage level and if it is VDC or VAC (ex: 24 VDC)

DIMENSIONS OF THE RELAYS


›› Dimensions: A x B x C Type RXR
A
B

C
10,5

Size and weight vary depending on the model. Please refer to datasheet for detailed info.

24 Auxiliary relays | Tripping applications


RETAINING CLIPS
RETAINING CLIPS OP SOCKET RELATED PLUGGED RELAY
Universal (D and F sized sockets RD; RF; RJ; Universal (Bag of 20 units)
E0 require 2 units ; J sized sockets TDF; TDJ; VDF;
require 4 units) VDJ; BJ10 Universal (Bag of 100 units)
E41 DN-DE IP, DN-DE 2C IP RD OP
E50 DN-TR OP, DN-TR 2C OP RD OP
E40 FN-DE IP, FN-DE 2C IP RF OP
E43 FN-DE IP, FN-DE 2C IP TDF OP; VDF OP; RUT
E42 FN-TR OP, FN-TR 2C OP RF OP
E44 FN-TR OP, FN-TR 2C OP TDF OP; VDF OP; RUT
E31 FN-DE IP, FN-DE 2C IP BF ›› E0 retaining clips
E21 FN-TR OP, FN-TR 2C OP BF
E45 JN-DE IP, JN-DE 2C IP RJ OP
E47 JN-DE IP, JN-DE 2C IP TDJ OP; VDJ OP
E46 JN-TR OP, JN-TR 2C OP RJ OP
E48 JN-TR OP, JN-TR 2C OP TDJ OP; VDJ OP
E49 J10N-TR OP, J10N-TR 2C OP BJ10
E51 JN10-DE IP, J10N-DE 2C IP BJ10
E29 JN-DE IP, JN-DE 2C IP BJ; UJ
E27 JN-TR OP, JN-TR 2C OP BJ; UJ
OTHER ACCESSORIES
Security pins for RD; RF; RJ; TDF; TDJ; VDF; VDJ relays (bag of 100 units)

›› E** retaining clips


SOCKETS, DIMENSIONS AND CUT-OUT
Sockets Accessories
Relay Type Screw Double faston Weight (g)
IP10 Front connection DN-DE IP10 DN-DE2C IP10 60
D IP20 Front connection DN-DE IP20 DN-DE2C IP20 60
IP10 Rear connection DN-TR OP DN-TR2C OP 50
IP10 Front connection FN-DE IP10 FN-DE2C IP10 110
IP20 Front connection FN-DE IP20 FN-DE2C IP20 110
F IP10 Rear connection FN-TR OP FN-TR2C OP 90
IP10 Flush mounting (short) F-EMP CORTA OP 300
IP10 Flush mounting F-EMP OP 300 Accessories

IP10 Front connection JN-DE IP10 JN-DE2C IP10 225 Retaining clips
IP20 Front connection JN-DE IP20 JN-DE2C IP20 225
Function signs on the extraction
J IP10 Rear connection JN-TR OP JN-TR2C OP 180 ring
IP10 Flush mounting (short) J-EMP CORTA OP 300
Security pins
IP10 Flush mounting J-EMP OP 300
IP20 Front connection J10N-DE IP20 J10N-DE2C IP20 280
J10 IP10 Rear connection J10N-TR OP J10N-TR2C OP 225
IP10 Flush mounting J10-EMP OP 325
IP10 Rear connection I-TR I-TR2C 500
I
IP10 Flush mounting I-EMP 500

Front connection for double


faston IP10 sockets
DN-DE2C IP10
FN-DE2C IP10
JN-DE2C IP10

lateral connection for the


rest of the sockets

›› Front connection socket ›› Rear connection socket ›› Flush mounting socket


Auxiliary relays | Tripping applications 25
Relays Type D Relays Type F Relays Type J Relays Type J10 Relays Type I

I-DE IP10

155

154
105
105

105
Socket
rear
connection
for DIN rail
or fix
Drilling J10N DE IP20  J10N DE2C IP20
(1)
31 31 31
102.7 31
99,8 29

64
112
Fix Drilling Fix Drilling Fix Drilling Fix Drilling Fix Drilling
2,1 45 12 117
1 of
onal)
AGUJEROS DE FIJACIÓN
5
(opti 20 60 FIX DRILLING

3,5 4o
= = 3,5 = =
2 of
80,00
2 of

145
26

3,5
1 of

DN-TR OP IP10 DN-TR2C OP IP10 FN-TR OP IP10 FN-TR2C OP IP10 JN-TR OP IP10 JN-TR2C OP IP10 J10N TR OP  J10N TR2C OP I-TR, I-TR2C IP10
41
120 6
6 6 104 43
100
6

110
41,8
51,2

Sockets for
rear 108
connection 100,5
+
- +
84
= = -

Cut-out
= 52,6 =
Cut-out
Cut-out

Cut-out 104
=

90
42

112 min.
=

5
fø 122 min.
8o

F-EMP TR OP J-EMP TR OP I-EMP IP20

15
15
Flush
mounting
sockets
for rear F-EMP TR OP J-EMP TR OP J10 EMP TR OP
connection
80

(1)
DIN rail according to EN50022 DIN46277/3

(2)
Minimum distance between sockets will depend on type of relay and sockets. Please request sockets user manual for more detailed information.
140
124

15

15

15
8

12.5

106
126 5
2.2
4X
Ø
116 Auxiliary
26 61
50
Cut-out
relays | Tripping applications
66

66
57

Cut-out
Cut-out
6
6
100
6

110
41,8
51,2
Sockets for
rear 108
connection 100,5
+
- +
84
= = -

Cut-out
= 52,6 =
Cut-out

Cut-out
Cut-out

104
=

90
42

112 min.
=
Relays Type D Relays Type F Relays Type J Relays Type J10 5 Relays 122
Type
fø min.I
8o

F-EMP TR OP J-EMP TR OP I-EMP IP20


I-DE IP10

155

154
105
105

105
Socket
rear
connection
for DIN rail 15
or fix 15
Drilling J10N DE IP20  J10N DE2C IP20
Flush
mounting
(1)
31 31 31
sockets 102.7 31
for rear 99,8 29
F-EMP TR OP J-EMP TR OP J10 EMP TR OP
connection
80

64
112

140
Fix Drilling Fix Drilling Fix Drilling Fix Drilling Fix Drilling
2,1 45 12 117
1 of
onal)
AGUJEROS DE FIJACIÓN
5
(opti 20 60 FIX DRILLING

3,5 4o
= = 3,5 = =
2 of
80,00
2 of

124

145
26

3,5

15
1 of 15

15

12.5
DN-TR OP IP10 DN-TR2C OP IP10 FN-TR OP IP10 FN-TR2C OP IP10 JN-TR OP IP10 JN-TR2C OP IP10 J10N TR OP  J10N TR2C OP I-TR, I-TR2C IP10
41
106 120 6
104 126 43 2.2 5
6 6
100 116 4X
Ø
61 6
Cut-out
50
66

110
41,8
51,2
66
57

Cut-out
Sockets for Cut-out
66

rear 108
connection 66 100,5
R2

Cut-Out +
- +
84
= = -

Cut-out
= 52,6 =
Cut-out
Cut-out

Cut-out

104
=

90
42

112 min.
106
Cut-out
=

5
fø 122 min.
8o

F-EMP TR OP J-EMP TR OP I-EMP IP20

15
15
Flush
mounting
sockets
for rear F-EMP TR OP J-EMP TR OP J10 EMP TR OP
connection
80
140
124

15

15

15
8

12.5

106
126 5
2.2
4X
Ø
61 116
Auxiliary relays | Tripping applications 50
Cut-out
27
66

66
57

Cut-out
Cut-out
66
Updates: ARTECHE_CT_Tripping-relays_EN