P R O D U C T C ATA LO G U E

DCGear
DC switchgear for traction power supply
applications

DC switchgear for traction power supply applications

• High active and passive safety


• Internal arc proof 50 kA 250 ms
DCGear

• High availability and low maintenance





Table of contents

004 Product introduction

005 Panel design

006 Panel arrangement


4 D C G e a r P R O D U C T C ATA LO G U E


Product introduction

Building upon decades of market and Main benefits


manufacturing experience, ABB designs and • Meets the most stringent safety
manufactures complete DC traction power requirements to ensure the protection of
supply solutions. operations and maintenance personnel
• Can easily be combined with other
ABB’s comprehensive product and solution medium-voltage AC switchgear and
portfolio covers a wide range of ratings and transformer-rectifier groups, representing
standards to fulfill customer requirements. the main equipment in DC traction
substations
DCGear • Can form part of factory assembled and
DCGear serves as control and protection tested DC E-Houses, reducing on site work
equipment in DC traction power distribution significantly
networks. The cubicles contain proven technology
components and are designed and type-tested Main features
in accordance with the latest standards. • Full conformity with IEC, EN and GB standards
• High active and passive safety through
freestanding rigid metal enclosed cubicles
with separate screened compartments
• Internal arc proof 50 kA 250 ms
• High availability and low maintenance
• Indoor installation

Main electrical data


Nominal voltage Un V 600 / 750 1500
Rated voltage UNe V 900 1800
Nominal insulation voltage UNm V 1800 3000
Rated lightening impulse withstand voltage to earth UNI kV 15 20
and between phase (1.2/50 μs)
Rated lightening impulse withstand voltage across an UNI kV 18 24
isolating distance if applicable (1.2 / 50 μs)
Rated power frequency voltage to earth and between Ua kV 6.9 9.2
phase (50 Hz, 1 min)
Rated power frequency voltage across an isolating Ua kV 8.3 11
distance if applicable (50 Hz, 1 min)
Rated service current 1) INe A ... 6000 … 6000
Main busbar current 1) Ie A … 6000 … 6000
Rated short-circuit current INSS / ÎNSS kA 125 / 178 90 / 128
Rated track time constant TNC ms 100 63
Rated earth fault current INcwe kA 50 50

1) higher values on request.


PANEL DESIGN 5


Panel design

Panel design Rear busbar compartment


The switchgear is made of a free standing The busbar compartment is at the rear of the
structure. Its external casing is made of bolted cubicle and contains the main busbar, cable
panels and doors on the front side. Panels and connections, voltage and current measuring.
diaphragms divide the inner part of the cubicle Furthermore, it can also hold bypass busbar and
in different compartments. additional equipment, such as surge arresters and
disconnector switches where applicable.
HSCB compartment
This compartment houses the DC high speed Low voltage compartment
circuit breaker mounted on a removable The low voltage compartment contains the
four-wheeled trolley, which can easily be withdrawn combined protection and control relay with
from the cubicle. The trolley is also equipped display, the low voltage components and all the
with the line test device. The withdrawable DC other equipment necessary to realize the control
high-speed circuit breaker trolley has the following and signaling circuit.
positions:
• Normal operating position: Main and auxiliary
circuits are connected
• Test position: Main circuits are disconnected
while auxiliary circuits are connected
• Disconnected position: Main and auxiliary
circuits are disconnected


Main compartments feeder panel

A: HSCB compartment
B: Rear busbar compartment
C: Low voltage compartment

A C
B
6 D C G e a r P R O D U C T C ATA LO G U E


Panel arrangement

Type of panels
DCGear is available in different variants covering various substation configurations.
Panel types HSCB DS
Incoming panel ● Standard requirement for substations with two or more rectifiers
Incoming panel ● Equipped with HSCB it can detect and switch-off of reverse
currents in case of rectifier faults
Incoming and return panel ● Preferred solution for substations with one rectifier only
Return panel ● Standard requirement for substations with two rectifiers
Line feeder panel ● ● Standard requirements
Optionally equipped with line disconnector
Line feeder panel with bypass DS ● ● Increased availability in combination with bypass panel
Bypass panel ● ● Increased availability in combination with bypass disconnector
Coupler panel ● ● Disconnection and connection of switchgear sections or contact
line / third rail sections

DCGear panel arrangement


The following illustration is an example of a possible configuration with DCGear panels.
Return panel Incoming panel Feeder panels Incoming panel

Running rail Overhead line or third rail

Main mechanical data and service conditions


Height mm 2105
Width mm 600
Depth mm 1600
Weight kg .. 600
Protection degree (IEC 60529)
Low voltage compartment - IP4X
Enclosure - IP2X
Panel with open doors - IP2X
Working ambient temperature °C -5 - + 40
Average relative humidity measured over 24 h % < 90
Maximum installation altitude above sea level m < 1400 m
Type of installation - indoor

ABB Xiamen Switchgear Co., Ltd.
No.885, FangShanXiEr Road, Xiang'an District,
Xiamen, Fujian, 361101
Tel: 0592 602 6033
Fax: 0592 603 0505

ABB Inc.
10300 Henri-Bourassa West St-Laurent,
Quebec, Canada H4S 1N6
Phone: +1 514 332 5350
Fax: +1 514 332 0609
Email: pes@ca.abb.com

ABB Sp. Zo.o.


Power Conversion 27, Placydowska Str.
95-070, Aleksandrow Lodzki, Poland
Phone: +48 42 24 00 100
Fax: +48 42 29 93 340
Email: enviline@pl.abb.com

ABB Sécheron SA
Rue des Sablières 4-6
CH-1211 Geneva, Switzerland
Phone: +41 58 586 22 11