Académique Documents
Professionnel Documents
Culture Documents
FOR
DIGITAL AUTOMATIC VOLTAGE REGULATOR
DIGITAL
RATING :- 2 X 660MW
CUSTOMER : - OPGCL
Prepared by :- R.RAJKUMAR
Date :- 27.01.2017
Page 1 of 4
OPERATION AND MAINTENANCE MANUAL
FOR
DIGITAL AUTOMATIC VOLTAGE REGULATOR
VOLUME-1
(OPERATING INSTRUCTIONS FOR DAVR)
SECTION – 1:
Document No:
Operating Instructions for DAVR EDN 48-1050-01
SECTION – 2:
VOLUME-2
(REFERENCE DOCUMENTS)
SECTION - 1 :-
(UNITROLS & ELECTRONIC SUB-ASSEMBLIES (ANALOG))
Page 2 of 4
OPERATION AND MAINTENANCE MANUAL
FOR
DIGITAL AUTOMATIC VOLTAGE REGULATOR
SECTION - 2 :-
(UNITROLS & ELECTRONIC SUB-ASSEMBLIES (DIGITAL))
SECTION – 3:
(ValmetDNA MODULES)
Module description Module Ref.
1. CONTROLLER ACNCS
2. ANALOG INPUT MODULE AII8V
3. ANALOG OUTPUT MODULE AOI4C
4. DIGITAL INPUT MODULE DII8P24
5. DIGITAL OUTPUT MODULE DOI4RO
6. BUS CONTROLLER IBC
7. RACK POWER SUPPLY MODULE IPSP
8. MOUNTING BOARD MBM120
9. MOUTING BOARD MBI8
10. BUS TERMINATOR IT
SECTION - 4 :-
(FIELD BREAKER)
Item Make /
Type
Exciter field breaker Lenoir,
CEX-150
Page 3 of 4
OPERATION AND MAINTENANCE MANUAL
FOR
DIGITAL AUTOMATIC VOLTAGE REGULATOR
SECTION - 5 :-
(THYRISTOR CONVERTER)
Item Make / Doc.No.
Type
Operating principle of thyristor CED 82-653-070
converter
Thyristor Device Data sheet BHt N45 BHt N45
Power module 6QG12 CED 82-653-067
Current flow monitoring 6QM1210 69203SJ2AA
SECTION - 6 :-
(CATALOGUES FOR RELAYS, MCBS & CONTACTORS)
Item Make / Type
VOLUME-3
(DOCUMENTS AND DRGS.)
Page 4 of 4
OPERATING INSTRUCTIONS
FOR
DIGITAL
AUTOMATIC VOLTAGE REGULATOR
EDN 48-1050-01 1
TABLE OF CONTENTS
1. General Information 3
1.1 Purpose of the Operating Instructions 3
1.2 Mechanical Structure 4
1.3 Design and Schematic Representation 5
1.4 Explanatory Notes on the Schematic Diagram 6
1.5 Brief description of Excitation Sysem 11
1.6 Power Supply System 15
2. Digital Voltage Regulator, DVR 16
2.1 Principle of Operation of the Regulator AVR 17
2.2 Basic Structure of the Regulation Processor 17
2.3 Operation of AUTOMATIC Channel 18
2.4 The MANUAL Channel 30
3. Pulse Section 31
3.1 Pulse Generation and Amplification 31
4. Converter 32
4.1 Final Pulse Stages 32
4.2 Converter Power Section 32
5. Field Current Circuit 32
5.1 Exciter Field Circuit-Breaker 32
5.2 De-excitation 33
6. Monitoring 34
6.1 Excitation Monitoring 34
7. Binary Controls 35
7.1Commands 35
7.2DisplayofAnalogSignals 36
7.3Alarms 36
7.4ChecklistforOperatingStaff 37
7.5LocalHMI 38
7.6Micro-Terminal 43
8. Preventive Maintenance and Operational Malfunctions 47
8.1 General Overview 47
8.2 Preventive Maintenance and Care 49
8.3 Operational Malfunctions and Functional Tests 49
9. Installation and Commissioning 57
EDN 48-1050-01 2
1. General Information
Operating Instructions (OI) for the excitation system describe the most essential
functions of the excitation system and provide instructions for its correct operation,
installation, and preventive maintenance. They are directed at trained operating
staff who have a basic familiarity with electronics.
The Operating Instructions also contain suggestions and recommendations for the
installation and operation of the unit. They provide recommendations for the basic
procedures and the rough scope of testing for initial commissioning. These
instructions are, however, not a commissioning manual and are based on
the assumption that the commissioning staff possesses special know-how
and experience.
EDN 48-1050-01 3
1.2 Mechanical Structure
The Field Suppression cubicle-FS contains components of the Exciter field circuit
including the Exciter field circuit-breaker, the De- excitation resistor and PMG
(Permanent Magnet Generator) supply isolator.
The converter units TY contain the thyristor bridges and their auxiliary
components, firing pulse transformers, thyristor fuses etc.
The racks R1 to R6 for binary controls have been placed in REG-1 (Refer scheme
sheet YD102 for layout of modules). On the back of REG-1 are placed the
Terminal blocks for interconnection to these racks R1 to R6. This panel also
contains the Power supplies for Binary controls.
Input / Output modules provided in Racks R1 to R4 are normally used for binary
signal exchange between Regulation circuits and Binary controls. The binary
control and signal connections between Regulation & FB / Thyristor cubicles or
Regulation to other plant Equipment are made mainly via the input and output
modules placed in R5 and R6. Auxiliary relays are provided for driving the breaker
/ contactor coils and for providing remote potential free contacts where required.
OWS PC is mounted in REG-1 provides the local operator’s control, display and
alarm signaling.
The swing frame containing the electronic tiers (refer to scheme sheet: YD101) is
mounted on the front of the regulation cubicle REG-2. Other components of the
open and closed-loop controls are mounted on the two side walls and the back
wall, UNC 4660 analog input module, transformers, relays, protective switches,
signal converters, etc.The view of swing frame (refer to scheme sheet: YD101)
shows the physical arrangement of the electronic equipment.
CHANNEL 1 is on the right in tier AA. The left half of the tier AA comprises of
modules for Adaptive PSS (Power System Stabiliser) of Channel -1. CHANNEL 2
is on the right in tier AB. The left half of the tier AB comprises of modules for
Adaptive PSS (Power System Stabiliser) of Channel -2. Tier AC in Regulation
cubicle-2 has a Micro-Terminal useful for communicating with Regulator CPU, for
analog values and parameters.Channel-3 is on the right in tier AE.
Firing pulses are processed in Tier AG and AP which include Pulse intermediate
stage, final pulse (amplifier) stages, and the power supply for the Final Pulse
Stages.
On the back of tiers AA, AB and AE there are bus circuit boards in the upper
portion for the standard connections for DVR modules (power supply units, data
bus, etc.). Other signal connections specific to the given application are installed
in the lower portion of these tiers, using WIRE-WRAP technology. 9- or 21-
conductor (plug-in) system cables are used to interconnect the tiers. 96 pin
Harting connectors are provided at DVR racks for signal exchange to and from
racks provided for Binary Controls. Tiers AG & AP have MAXI-TERMI-POINT
connections.
EDN 48-1050-01 4
1.3 Design and Schematic Representation
All apparatuses in swing frame of REG-2 have a type designation that has been
shown on the schematic diagram for the excitation equipment and marked on the
module itself. Always use this designation when ordering or making inquiries. The
following example (Micro-Terminal UNS 2660) will explain the coding system:
UN S2660a-PVar.1
DVR (Name: Equipment System)
Series of Numerals
Revision Status
IMPORTANT: “b,c,...” supersedes “a”,
but not vice-versa(=upward compatibility)
-
Sub-classification,
Type of Unit:
E: Electronic Unit in general
G: Casing without Circuit Boards
installed
P: Plug-in Module
Z: Casing with Boards installed
Variable Equipment
i.e., special equipment of the
module for a given standard
function (“Spec.” -> adaptation as
described in the test/commissioning
report
IMPORTANT: The variant number on
the module used must always be the
same as the variant number in the
schematic diagram
EDN 48-1050-01 5
1.4 Explanatory Notes on the Schematic Diagram
The schematic diagram shows all essential functions of the hardware and
software and all electrical connections of the components, including the
interconnections for the given excitation system. For purposes of clarity for
practical use, all unessential information has been deliberately omitted from the
schematic diagram. Such details, generally needed only in special cases, can be
obtained from the data sheets for the modules in question. Plant-specific hardware
and software settings can be obtained from the test / commissioning report.
The view of the swing frame /YD101 shows not only the names of the modules but
also, usually, a cross-reference to the page of the schematic diagram on which the
pertinent connections for the module are to be found. Locations where no entry is
made for the type of module but where a cross-reference to the schematic
diagram appears are locations left open for standard optional equipment.
As seen from the examples below, every signal has a signal designation and a
diagram cross-reference. The signal designation gives the signal a specific and
unambiguous name made up of the name of the functional group (e.g., GS020)
and the signal code (e.g., XU12). The cross-reference to the diagram indicates the
page in the schematic diagram on which the associated signal source, or sink, can
be found. The signals also form the tag names where they are referred in logic
EDN 48-1050-01 6
sheets. The signals are also described in plain text where that is helpful. This plain
text provides the user with information on the functional characteristics of the
signal in question (it is not an identification of the signal!). Different text can be
used to designate the same signal at the output and the input. There are often
different texts at the signal branching points as well, to explain their specific
functions at the signal sinks.
EDN 48-1050-01 7
(6) Designation for the signal (Also called as tag)
This consists of the functional group name (e.g., GS020) and the signal code
(e.g., XU12). For output signals, the functional group name is normally identical to
the designation in the page heading (2). There is a different signal code for each
signal within any given functional group. Naturally, the outputs for signal branching
(as in the present example) have identical signal codes. In certain cases for
convenience of understanding while trouble shooting short forms of texts are also
given as tag names.
EDN 48-1050-01 8
Generally, the entry for this hardware assignment is needed only for the
factory tests. Hardware connections from pin to pin within a tier are made with
WIRE-WRAP wires and identified with a “w”. Connections from Regulation
tiers AA, AB (without the “w”) are via 9- or 21-conductor system cables, some
of which are plugged on directly on the rack connector of modules. (Refer to
the Cable List, Schematic Diagram /YD003).
EDN 48-1050-01 9
Direct hardware signals on modules (Example):
Note: Connections to and from binary controls are grouped on to free rack
connector and connected to the terminals behind racks R1 to R3 (maximum up to
R6 using Harting connectors.
EDN 48-1050-01 10
1.5 Brief Description of the Excitation System
The Digital Automatic Voltage Regulator regulates the terminal voltage (and/or the
flow of reactive power during parallel operation with other machines or the grid) of
the synchronous machine (generator) by direct control of the Main Exciter field
current using (static) Thyristor Converter.
The Voltage Regulator is intended for the excitation control of generator equipped
with Alternator Exciter employing rotating non-controlled rectifiers. The excitation
equipment of the generator and its interconnections with the voltage regulator is
shown in the block schematic diagram sheet - YU101. The PMG (Permanent
Magnet Generator) as applicable for the project and indicated in block diagram
normally provides supply to the thyristor sets.
The Excitation system consists of two Regulation panels (REG-1 & REG-2),
Thyristor panel and Field suppression panel in one shipping section. The first
Regulation panel houses the components / modules pertaining to logic sequence
and the second one houses components / modules for Regulation function.
EDN 48-1050-01 11
Regulation part consists of two Auto channels and one Manual channel. Each
Auto channel is provided with independent sensing unit, power supply unit, gate
control unit and pulse intermediate stage. Manual channel is provided with
independent sensing unit, power supply unit, gate control unit and pulse
intermediate stage.
Excitation of the generator is started by closing the field circuit breaker Q2 and by
switching ON Excitation. Intermediate pulse stage of channel selected for
operation provides the gate pulses to both the thyristor bridges through the
respective pulse final stage modules and pulse transformer.
Each converter block is provided with its dedicated Pulse Final Stage and
conduction- monitoring unit for necessary control and logical operation. Each arm
in the thyristor bridge is fitted with a thyristor device and branch fuse.Each device
is protected with suitableRC snubber circuit for dV/dt protection of device. The
Thyristors are generously dimensioned with respect to voltage and current, thus
ensuring a very low failure rate.
When Channel -1 is ON, the pulses from Pulse intermediate Stage of Channel-2 &
Channel-3 are blocked and so on. Under faulty conditions of both Auto channels,
automatic bumpless transfer to Manual channel is initiated.
Channel 3 (the Manual channel) built as a simple field current Regulator with a PI
control algorithm. The Manual channels are very useful for the purpose of
commissioning & maintenance and also serve as backup channel in case of
failure of Channel 1 & 2.The excitation can be controlled in Manual channel either
from local or remote as desired by the commissioning /operating personnel.
EDN 48-1050-01 12
Field discharge normally is initiated on shutdown of the generator, or in fault
situations by the generator protection equipment. Field discharge commands drive
the thyristors set in operation to the maximum negative output voltage (inverter
operation) via the gate control sets in operation. In addition to this, a tripping
command is given to the main Exciter Field Breaker. The field breaker connects a
discharge resistor across the field of the main exciter for effective field
suppression.
Automatic follow up of channels ensures that the standby channel always
generates the same control variable as the operating channel under steady-state
operation. This ensures smooth switchover from operating channel to any one of
the healthy standby channels.
To ensure that the stand by Channel will, in case of a switch-over initiated by a
malfunction in the operating Channel, take over without disturbing the operating
point of the machine as it was prior to the problem, the response of the tracking for
the channels is set relatively slow. The sequence of Automatic changeover
between channels, incase of fault occurring in operating channel is as given
below.
Channel Changeover Sequence:
Channel-1(Auto) to Channel-2 (Auto) on Channel-1 failure
Channel-2 (Auto) to Channel-1(Auto) on Channel-2 failure
Channel-1 (Auto) to Channel-3 (Manual) on Channel-1failure when Channel-2
has already failed, if Channel -3 is healthy.
Channel-2 (Auto) to Channel-3 (Manual) on Channel-2 failure when Channel-
1 has already failed, if Channel -3 is healthy.
In addition to voltage regulation the Auto channel is also capable of performing the
following functions and is designed and set at works as per the project specific
requirement. The functions/features possible in Channel-1 / Channel-2 are
Reactive droop / Decreases / increases the excitation proportional to the
drop compensation Generator reactive current.
Soft start Enables gradual buildup of Generator terminal voltage to
preset value in both channels depending on the set time.
V / Hz Limiter Reduces excitation with a delay whenever set V/Hz ratio
has been exceed to prevent saturation effect in Generator
or Generator Transformer.
Maximum Field Reduces excitation with a delay whenever set maximum
Current Limiter excitation (exciter field / Gen rotor) current limit has been
exceeded.
Inductive Stator Reduces excitation with a delay whenever set maximum
Current Limiter Generator Stator current limit has been exceeded in the
lagging zone of the machine capability.
Capacitive Stator Increases excitation whenever set max. Generator stator
Current Limiter current limit has been exceeded in the leading Zone of the
machine capability.
Load Angle Limiter Whenever the load angle increases beyond the set value,
the limiter increases the excitation to reduce the load angle.
Power System Influences the voltage regulator to dampen low frequency
Stabilizer (PSS) active power oscillations.
EDN 48-1050-01 13
In addition to the closed control systems for Generator Voltage or Field Current
regulation, the Digital Automatic Voltage Regulator is provided with redundant
BINARY CONTROLS SYSTEMS, PLC-1and PLC-2, realised using Valmet DNA
architecture. Each PLC unit is provided with an ACN-CS (Processor) along with its
dedicated set of Analog/digital Input/ Output modules. Modules housed in Racks
R1, R3 and R5 of Regulation panel-1 (REG-1) are dedicated for PLC-1 and those
modules housed in Racks R2, R4 and R6 of Regulation panel-1 (REG-1) are
dedicated for PLC-2. Each PLC unit is capable of complete logic control
processing and initiating logical operation as per the system requirement.
Redundancy of the PLC units ensure that at any instant of time only one of the
PLC units will be in operation while the other unit will be in hot standby state. In
case of failure of operating PLC the entire logic control is automatically transferred
to the stand by PLC unit. Any one of the redundant PLC-1 / PLC-2 have the
capability to act as master for realising the complete logical / binary controls of the
Excitation System. In case of failure of both PLCs a trip command is initiated.
EDN 48-1050-01 14
Following push button & selector switch is provided on swing frame (AD rack)
In this Brushless excitation system, the PMG provides the power supply for the
converter.
A station battery supply is absolutely necessary for the control of the field circuit
breaker. It is the power source for the electronic devices. In addition to this, 220V
DC is also derived from PMG voltage. This DC supply is paralleled with Station
DC supply in UNC4664, Power supply interface unit. Two such interface units are
provided, one for Channel-1 & Channel -3 (G01) and the other for Channel-2
(G02). When two 220VDC feeders are available one of them is connected to G01
and other to G02.
The synchronous voltages Usyn1, Usyn2, and Usyn3 are each supplied to the
CHANNEL-1, CHANNEL-2, and CHANNEL-3 separately through transformers T3
and T4. The Gate Control Units need these voltages to enable them to issue the
pulses at a given firing angle relative to the input voltage of the converter.
For testing, the synchronous voltages can be switched over to an auxiliary power
supply while the generator is at a standstill (T3, T4) using switch –S20. The
electronic equipment and the Gate Control Unit circuits can then be tested while
at standstill. Normal operation of the unit using Test Supply is not
permitted.
EDN 48-1050-01 15
1.6.2 Power Supply Distribution System
refer to block diagram (/YU101 & YU102)
Regulation Channel-1 and Channel-3 are powered from the output of separate
power supply interface unit (UNC 4664) G01.Regulation Channel-2 is powered
from the output of separate power supply interface unit (UNC 4664) G02. The
output from power supply interface units G01 & G02 feed the rack mounted
DC /DC converter Power supply units(AA37/AB37/AE37) of regulating Channel
1 , Channel 2 , & Channel 3 respectively through miniatures circuit breakers.
The electronic modules for Channel 1, Channel 2 and Channel 3 are each
supplied exclusively from their own rack mounted, DC/DC converter (AA37,
AB37, AE37) with electrical isolation between input and the output. These
power supply units can function within a input voltage range of 75% to 140% of
rated input voltage. All output voltages (+5V; 15V and +24V) are directly or
indirectly monitored for under / over voltage. An event of disturbance in voltage
level is signaled by a fault signal while at the same time the output current is
reduced and the unit shuts down.
The outputs of, Power supply interface units G01 and G02 are also fed to the
Power supply modules of Binary controls. There are four Power Supply modules
for Binary controls. Two of them are for System Power Supply (PSS10 and
PSS11) and provide the supply, redundantly for Electronic modules of Binary
controls. The other two are Field Power Supply modules and provide the
interaction voltage for field signals (PSF10 and PSF11). The field signals can
either be from any one of the Excitation cubicles for sensing faults or from any
other plant equipment. For scheme of connections refer sheets GW030-YS002 to
GW030-YS005.
All power supply units have current limiters (short-circuit strength) and under
voltage monitoring of their outputs. If any of the power supply units malfunctions,
its output voltage is switched off. The malfunction is stored in the module, and an
alarm is given. (In certain cases, a switch-over to the standby channel is initiated.)
To regulate the voltage and the reactive power of a synchronous machine, the
field voltage must be adjusted quickly to the changes in the operating conditions
(with a response time that does not exceed a few ms). To accomplish this, analog
control systems include amplifiers, which make continuous comparison of the
actual values against the reference values and vary the control variable to the
converter with almost no delay. Most of the delay that occurs originates in the
converter, since the firing pulses for changing the rectifier phase angle are only
issued periodically (every 2.8 or 3.3 ms).
The DVR Digital Voltage Regulator calculates the control variable from the
measured and reference data in very short time intervals. This results outwardly in
a quasi-continuous behavior with a negligible delay time (as in an analog
regulator).
EDN 48-1050-01 16
The calculations are made in the binary number system. Analog measurement
signals, such as those for generator voltage and generator current, are converted
into binary signals in analog/digital converters. The set-points and limit values
have already been defined in digital (binary) form.
For that reason, we will explain below only the principle division of work among
the various modules and the flow of data processing. The purpose is, above all, to
make clear how the processor system has been integrated into the rest of the
power electronics system.
The actual values Generator Voltage, Generator current, Field Current and
Synchronizing Voltage measured are processed in a separate UNC 4660
peripheral unit for each channel. These peripheral units are used for
preprocessing signals from external measurement circuits, i.e., for galvanic
isolation and adaptation to the electronics level.
The binary input signals required (For example, FB is ON/OFF, GCB is ON/OFF,
Pulse block ON/OFF etc.) for the Regulation processor is provided by the Digital
Output modules in Binary Control system in Regulation cubicle REG-1. Similarly,
the binary output signals (For example, Various limiters in operation, Ref value
Max/Min, DC short circuit etc.) from the Regulation processor are passed on to
the Digital Input modules in Binary Control system in Regulation cubicle REG-1.
The most important input parameters to the AUTOMATIC mode are the generator
voltage Ug, the generator current Ig, the field current If, and the synchronous
voltage Usyn. From the UNC 4660 peripheral unit, Ug, Ig, and Usyn are sent to
the UN 0661 Interrupt Generator (plug-in module on the processor bus) for filtering
and further processing. The UN 0661 Interrupt Generator also uses the 3-phase
U signal to generate the 12 interrupts per period to trigger the cycles for
g
processing actual values in the processor while in Auto mode. Synchronized with
these interrupts (i.e., with the phase positions of generator voltage Ug) this
processor measures the generator current Ig, and then calculates the reactive
current (I . sin ) and the active current (I . cos ). With these two results, the
processor is then able to derive further operating parameters, such as the load
angle, the active power, etc. The processed analog signals are converted to
EDN 48-1050-01 17
Digital Signals (by UN0610) for processing by CPU module (UN0660) using
software (firmware).
The functions of Voltage Regulation, Limiters, Power System Stabiliser etc. have
been accomplished in firmware. The non-varying standard software function
modules can be configured to the design desired, for plant-specific purposes,
using software switches (K-Flags). Thus, for example, the stored status of a K-
Flag determines whether or not a limiter is active, and whether the de-excitation or
the excitation limiters take precedence. Because these K-flags determine the
software Scope of Supply for the installation, they cannot be changed permanently
via the Micro-Terminal. In this way, they differ from such setting data as the values
of the parameters for the PID filter of the voltage regulator or the set points for the
limiters. These values can be permanently changed using the Micro-Terminal.
Communication is possible, with each of the UN 0660 processor systems, via the
Micro-Terminal by plugging on the connecting cable. In this way, signals within the
processor, set parameters, analog signals can be viewed and the set parameters
can be altered temporarily (F... range) or permanently (C... range).
The control voltage output from the voltage regulator (in the AUTOMATIC
Channel) is processed in UN 0663 Gate Control Unit and formed into a chain of
pulses at the appropriate firing angle. The pulses of the active channel are
directed to the pulse bus via the associated UN 0096 Intermediate Pulse Stage.
The pulses for each converter block are amplified sufficiently in UN 0809 Final
Pulse Stage to fire the thyristors.
to regulate the effect of reactive and/or active current on the voltage (droops)
to limit Volt/Hz
Block Diagram /YU105 shows the software structure of the AUTOMATIC mode
(Channel-1 or Channel-2). The generator limiters not provided for the installation
in question (optional equipment) are identified in this overview as “Not Supplied.”
The parameter values, signal values, and software switches (flags) marked with
addresses (hexadecimal numbers) can be viewed and altered via the Micro-
Terminal (refer also to Sect.7.6).The values selected are displayed in %, sec, p.u.,
EDN 48-1050-01 18
Hz, etc. and can, where necessary, be changed directly in these formats. The
plant-specific settings of the variables and the flags can be obtained from the Test
and Commissioning Report.
This block diagram provides the information about the important functions and
possible settings of the AUTOMATIC mode of channel. For the sake of clarity, no
detailed presentation has been given of special functions such as tracking circuits,
initializations, etc. Binary signals are shown in broken lines, analog signals in solid
lines. The corresponding text designations in the schematic diagram can be used
for identification of the input signals (hardware inputs). The only analog output
signal from the automatic voltage regulator, control variable Ucontr, is sent via the
data bus (CRU bus) to the Gate Control Unit (refer to Data Sheet). Most of the
binary messages (outputs) from the AVR are of no interest functionally and they
have been omitted for the sake of clarity.
The basic structure of the digital voltage regulator and the limiters is simple. This
is necessary in order that the behavior of the regulators/limiters will remain
calculable and understandable in all operating situations and that there will be no
problem in adjusting and optimizing them. The central PID filter in the digital
voltage regulator defines the dynamic response of the closed-loop controls both in
the voltage regulator mode and after limiters have intervened. The “control
deviation” at the input to the PID filter is the control deviation for voltage, the
control deviation of a de-excitation limiter (the value determined by minimum value
selection), or the control deviation of an excitation limiter (the value determined by
maximum value selection). Flag F730 (“PRIOR”) is used to determine whether the
exciting (Min. value) or the de-exciting signal takes precedence on the min/max
value limiter (normally: F730 = 1111, i.e., the de-exciting signal takes
precedence).
With the exception of the Minimum Field Current Limiter, all other limiters have
variable factoring multipliers of the signal outputs so that they can be adjusted
individually together with the common PID filter, which has been optimized for
voltage regulation. The setting parameters for this PID filter are as follows:
Vo = KR Static amplification
Vp Proportional amplification
EDN 48-1050-01 19
The BODE diagram below shows the assignment of settings in accordance with
DIN/IEC standards based on a typical example:
The PID filter amplifications Vo, Vp, and V can be adjusted in p.u. values. But
the “ceiling factor” Vp1 must be adjusted correctly with parameter F310 if the total
amplification (circuit amplification) of the control circuit is actually to conform to
this p.u. setting. This factor must agree with the “external” amplification, i.e., with
the ceiling value of the transformer-/ converter circuit:
Ufmax
Vp1 = -------
Ufo
The standard operating mode for the PID filter is voltage regulation, for which the
discrepancy between the voltage set-point (F270) and the current value for
generator voltage Ug (F90A) (the control deviation) is supplied at the input. To
compensate for the voltage drop in the Generator transformer, or whenever
several generators are operating to the same distributing bus, the generator
voltage must be varied in proportion to the measured generator current (droop
influence). To accomplish this, the voltage set-point is varied as a function of the
measured reactive current IX and/or active current IR. Flag F712 enables the IX
EDN 48-1050-01 20
droop, Flag F710 the IR droop. The desired compensation is set in F282 and F286
respectively. Flags F284 and F288 are used to select whether this droop
influence is to increase the voltage or to reduce it (compensation). Combined
influence of the active and reactive currents is attained by enabling both droops,
IX and IR.
Flag F716 activates a so-called “Soft-Start” at the starting of excitation. This “Soft-
Start” ensures that the voltage set-point integrates from 0% to 100% within the
time set on F290 when the excitation is switched on (“EXCITATION ON”). A
“smooth” excitation of the generator can be achieved in this way whenever there is
no demand for a quick excitation.
The Firmware of the channels supplies the criterion for switching on the
conduction monitoring. Whether this criterion is activated based on the actual
value for generator voltage Ug or for field current If, or both, depends on the
settings of the two threshold values F2A0 / F2A2 (0% setting means that the
output is always “logical 1”). Whenever Flag F72A is not activated, the binary
output is fixed at “logical 1”. This criterion is used for permission of Conduction
monitoring function.
EDN 48-1050-01 21
2.3.5 Ug/f Limiter
At under frequency, the Ug/f Limiter reduces the generator voltage so as to
prevent saturation effects in the supply and measuring transformers. To adjust this
limiter, the max. permissible generator voltage at rated frequency is defined and
set using parameter F280. When any under-frequency occurs, the generator
voltage is thus reduced in proportion to that setting. An appropriate adjustment on
parameter F28E is used to achieve a delayed intervention of the Ug/f Limiter.
The Field Current Maximum Limiter is provided to protect the generator rotor from
over currents occurring in steady-state and transient operation. High field currents
are normally the result of a sharp drop in network voltage, or of an improper
raising of the voltage set-point by the operating staff. The field current is held
steady at the value TH1, i.e., at the maximum thermal value permissible for the
excitation circuit and the rotor. In order that the generator can support the power
network with its transient overload capacity during brief collapses in voltage, a
temporary switch-over is made to the transient over current limit MAX1 (a higher
setting). When the generator or the converter is operating at a reduced capacity,
these limits TH1/MAX1 can be switched over to the lower settings TH2/MAX2 by
activating the corresponding binary signals. The switch-over from the thermal limit
TH1/2 to the transient over current limit MAX1/2 can be configured in one of three
ways:
This variant enables the transient overcurrent value MAX1/2 whenever a collapse
of voltage in the network is detected. The ENABLE time is fixed, and can be set
using parameter F408. Parameter F40C defines the limiting gradient for detection
of the collapse -dU/dt. The example below shows the typical behavior of the limiter
configured in this way:
EDN 48-1050-01 22
b) Dependent on the over current time integral, with -dU/dt ENABLE:
This variant likewise enables the transient over current value only when a collapse
of network voltage has been detected. However, the switch-back to the thermal
limit is not made dependent upon the time itself, but on the calculated time integral
i²dt of the over current. Parameter F416 can be used to set the maximum i²dt for
the overcurrent in p.u. The setting on Parameter F414 in s/p.u., takes into account
the time the rotor needs to cool down, i.e., the rate of temperature change in the
case of intermittent over current operation. The example below shows how the
timing of the switch-back to the thermal limit depends on the present value for
over current i²dt:
If 2
= i2 dt = ------------- -1 .t
0.9 IfTh
In this variant, the transient over current becomes available without any prior
conditions (without a -dU/dt ENABLE) with the time integral i²dt.
EDN 48-1050-01 23
2.3.7 Inductive Stator Current Limiter
The Inductive Stator Current Limiter holds the stator current Ig within permissible
limits while the generator is in the “over-excited” operating range by reducing the
field current accordingly. The setting TH (thermal limit) provides the limit against
stationary over currents that might occur. To take advantage of the generator’s
transient overload capacity, a switch-over is made to the higher setting MAX. The
principle of operation of this switch-over to the value MAX, permissible only
transiently, is identical to that employed for the field current limiter (refer to the
description above).
When the drive output from the turbine is very high, stator current may exceed
permissible limits even while inductive loading of the generator is low. In this case,
if the stator current limiter is not kept from influencing the field current, the control
circuit will oscillate back and forth between the Inductive Stator Current Limiter
(de-exciting) and the Capacitive Stator Current Limiter (exciting). Parameter F43C
is used to set a function, which will block the stator current limiter when the
reactive current I is low. The output signal of that function then dominates the
control variable of the Ig-dependent limiter via a maximum value selection.
The Capacitive Stator Current Limiter holds the stator current Ig within permissible
limits while the generator is in the “under-excited” operating range by increasing
the field current as required. The positive behavior of this limiter (build-up of
excitation) is due to the way in which the synchronous generator behaves in the
under-excited operating range. In order to reduce the generator current Ig (less -
Ix), the generator calls for an increase in the field current (refer also below: “Power
Chart”). To prevent fluctuations when the reactive current Ix is low (as described
above with regard to the Inductive Stator Current Limiter), this limiter also
possesses a function that can influence the Ig-dependent control variable. This
adjusted value for this function (F43C) is the same as that for the inductive stator
current limiter.
The Load Angle Limiter prevents the synchronous machine from slipping out of
phase due to slippage of the rotor. The load angle , the difference in phase
between the rotor and the stator rotating field, results mainly from the driving
torque (active power P) acting on the generator and the level of rotor current (field
current). If the driving torque remains constant, an increase in the field current
reduces the load angle .
The current load angle at any moment is obtained from the generator current
and generator voltage based on a simplified model of the generator. Whenever
this calculated load angle (F886) exceeds the preset limit angle (F4A0), the
limiter increases the field current until the load angle has dropped back to its
permissible value. The quadrature reactance Xq of the generator (F4A4) and the
network reactance Xe (F4A6) during normal operation must be adjusted on the
regulator in order to obtain the load angle .
EDN 48-1050-01 24
The graph below shows the Power Chart for a salient-pole machine with typical
limiter characteristics:
EDN 48-1050-01 25
considerations of design and economy. Some further action is therefore needed to
increase the damping effect.
The following drastically simplified formula shows the parameters upon which the
amount of active power PE supplied by the generator depends:
PE = active power
It can be seen from the above relationship that the active power that the generator
transfers depends not only on the load angle , but also on the field current If. This
means that, a transient change can be made in the active power PE and with that
in the effective electrical torque ME by varying the field current.
The principle of operation of the DVR Power System Stabilizer becomes clear
from a consideration of the oscillations in power output and frequency (PE, f)
and the vector diagram:
EDN 48-1050-01 26
As can be seen from the vector diagram, by applying proper weighting factors (K1,
K2), and then adding together the signals -PE and f, an overall stabilization
signal can be produced that rotates in advance of the f signal by any angle
desired between 0° and 90°. Because the amplitude of -PE remains proportional
to the amplitude of f, a constant angle in advance of f results for the
compensation of the time constants referred to above.
The Power System Stabilizer PSS is a section of the AVR computer program (see
Block Diagram /YU105 ) and is processed once per network cycle. The voltage at
the generator terminals and the generator current are measured in order to define
the signals PE and f. The calculated signals for P (=PE) and f are then sent
across DC filters “D” (real differentiators) that transmit only the dynamic portion of
the signals. The PE and f signals obtained in this way are then weighted
(multiplied by) with the factors K1 (F330) and K2 (F332) and sent to the summing
point of the voltage regulator.
The PSS stabilization signal is imposed on the automatic voltage regulator only if
the following prerequisites are met:
Generator on line
The stabilization signal is limited at the output from the PSS to the lower and
upper limits of F336/F334. Flag F732 defines whether the stabilization signal is
introduced before or after the PID filter (usually before the filter). Because the PID
filter, as noted above (refer to Sect.2.3.1) already takes the ceiling factor Vp1 into
account, the PSS signal needs to be multiplied by Vp1 if it is added to the voltage
regulator following the PID filter (divider at the input to the min/max limiter).
If the signal “MECH LOAD” (from the turbine) is available, this parameter can be
imposed on the electrical load signal P by activating Flag F736. This precaution
prevents the DC filter “D” in the P-channel from producing an unnecessary
“stabilization” effect in the case of rapid changes in turbine load. As an alternative
for the AVR’s Power System Stabilizer, a stabilization signal from an outside
EDN 48-1050-01 27
system can be imposed by activating the binary input “PSS-SIGN.EXT.” Flag F340
can be used to select between an analog and a 12-bit signal, and F33E to select
the polarity desired for that signal.
The memory subdivisions in the PSS adapter are similar to those in the voltage
regulator. Block I contains the operating program for the PSS adapter. Block II
contains an EPROM with the configuration. Block III is not occupied. Block IV
has an EEPROM where the precalculated weighting factors are tabulated. The
addresses for these factors are given in the attached Report of settings. Finally,
Block V contains the RAM.
The following will be a brief description of the function of the PSS Adapter.
As we already know, the slip stabilizing signal is formed from the sum of two other
signals namely the generator active–power signal and the generator frequency
signal. The amplification and the mixing ration for the two signals are referred to
as the weighting.
If, however, the network conditions do not permit the use of a compromise setting,
the PSS adapter provides a solution.
The complete operating range (power chart ) of the machine is divided into six
operating sub – ranges. Then, using computer program HE 038, the weighting
factors are determined for the six sub – ranges and for three different (expected)
external reactances Xe.
Thus we have a total of 18 operating sub – ranges under consideration. For each
of these sub-ranges, the optimum weighting factors are determined and are stored
EDN 48-1050-01 28
course, have to be weighted separately, so a total of 36 values are stored. From
there, the values are issued to the voltage regulator as 2 x 6 – bit signals which
are next multiplied by the basic weighting factors which have been set. The basic
weighting factors in the voltage regulator can be modified, in 64 steps ( 6 bit ), by
a factor between 0 and 4.
The task of the PSS adapter is now to assess the operating point of the machine
and the instantaneous value of the external reactance. Once this has been done,
the corresponding weighting factors are read from the stored table and are
transferred to the voltage regulator.
The operating point of the machine is determined from the measurement of Iactive
and Ireactive. Measurement of the external reactance Xe is more complicated.
When determining Xe, it is assumed that the voltage at the network center is
constant. If there is now an oscillation in the active power, then the value of angle
also oscillates. As UN is constant , the phase angle of the generator voltage will
thus oscillate about the value e.
From this brief consideration, it can already be seen that identification of Xe can
When the transient dynamics have decayed, and after a subsequent delay time
which is stored at address C3C0, the weighting is reduced by one step. If the
maximum Xe has already been identified, then after another delay period there is
another reduction of one step.
In other words: in steady-state operation, the slip stabilizing works with the lowest
weighting, and thus the maintenance of constant voltage takes priority. If, in
EDN 48-1050-01 29
steady-state operation, the oscillations exceed the value set at address C3C4, the
weighting is raised one step. During the time delay which is set at address C3C2,
there is no further monitoring of the oscillation at steady state. This is to prevent
automatic switching to the maximum weighting when there is oscillation in steady-
state operation.
0000= No fault
0000=No fault
2.4.1 Summary
The independent MANUAL channel has been built as a simple field current
regulator without additional limiters. Its main function is to maintain the excitation
of the generator even if the AUTO channel becomes non-operational. The
MANUAL channel also performs valuable service for purposes of testing,
commissioning, and preventive maintenance.
EDN 48-1050-01 30
2.4.2 Principle of operation
All the functions of the MANUAL channel of operation including Reference value
Generation, PI regulation and generation of firing pulses, have been implemented
in single electronic module, the UN 0663 Gate Control Unit.
For further processing in the UN 0096 Intermediate Pulse Stage, the Gate Control
Unit supplies six firing pulses at its output whose phase position with respect to
the synchronous voltage U is in accordance with control variable U . An
syn contr
internal linearization ensures that the field voltage produced via the firing pulses
remains proportional to the control variable Ucontr throughout the entire range. As
a result, the circuit amplification of the control remains constant over the entire
range.
The UN 0663 Gate Control Unit can be re-functioned (by pre-selection with a
switch ) for purposes of testing to act as a purely firing pulse control. In this case,
the control variable Ucontr is adjusted directly using the RAISE / LOWER push
buttons on the front of the module. In this way, for example, the relationship
between the phase position of the firing pulses and the control variable Ucontr can
be checked easily.
3. Pulse Section
3.1 Pulse Generation and Amplification
refer to block diagram (/YU101)
The UN 0663 Gate Control Units of each channel supplies six firing pulses for
operating the 6-pulse thyristor bridges. The low-power pulse signals from these
Gate Control Units are amplified in the UN 0096 Intermediate Pulse Stage,
galvanically isolated, and then sent to the common pulse bus. On the output end,
the Intermediate Pulse Stage of the stand by channel is always blocked.
The Gate Control Units generate the pulses based on microprocessor control. The
reference voltage used for the firing pulse phase location is the output voltage
from the excitation transformer (Usyn1 and Usyn2). The commutation spikes of
the synchronous voltage caused by the converter are calculated prior to use of the
voltage as a reference value and are deliberately filtered out.
EDN 48-1050-01 31
The lower limit for the firing pulses (double pulses), which are offset from one
another by 60°, is defined by the limit rectifier position (min) and the upper limit
by the limit inverter position (max) for the firing angle. min and max can be
adjusted on the Gate Control Units using DIL(Dual In Line) switches. min
ensures that the firing pulses will not be issued (premature firing) until there is
sufficient positive phase voltage on the thyristor involved. max prevents a
dangerous “tipping” of the thyristor bridge into the rectifier mode if the firing angle
is too large (“late firing”). The critical factors determining max are the overlap
time ümax (max. commutation time) and the “recovery time” of the thyristors
(max < 180° - ümax - ).
An external control signal can force the firing pulses into their inverter limit
position. Other binary inputs can block or direct the firing pulses of the Gate
Control Units so as to produce freewheeling on the Thyristor Bridge. During
freewheeling, the firing pulses for the thyristor pair R and S are blocked and the
pulse signals T+/T- are engaged with chains of pulses.
All Gate Control Units contain a field current monitor that blocks the firing pulses
immediately whenever the current exceeds a preset threshold level. In this case,
the field circuit-breaker is also tripped via an output contact. The purpose of these
provisions is to prevent damage to thyristors and thyristor fuses in case of a slip-
ring short-circuit, or to keep any damage that does occur to a minimum.
4.0 Converter
The UN 0809 Final Pulse Stages adapt the output pulses from the UN 0096
Intermediate Pulse Stage (pulses on the pulse bus) to the gate currents needed
for the thyristors. Each thyristor bridge is equipped with its own Final Pulse Stage.
Each Final Pulse Stages is provided with a power supply module UN 0809.
The module generates a high initial pulse amplitude in order to reach the
necessary gate current gradient. The Final Pulse Stages and their associated
thyristor bridges form single units. All six pulse outputs from a Final Pulse Stage
can be blocked by an external control signal, so that all thyristors in the associated
thyristor bridge will block the current. A blocking of the pulses is initiated whenever
there is a malfunction in the associated thyristor bridge.
Fully controlled thyristor sets in three-phase bridge connection are used. Each of
the 6 bridge arms is fitted with a thyristor and an arm fuse. The thyristors are
generously dimensioned with respect to voltage and current so that the failure rate
is very low.
Each thyristor bridge arm is equipped with current flow monitoring CT’s. The
absence of conduction in any arm is identified by a Current flow monitoring
module and alarm is given.
EDN 48-1050-01 32
5.0 Field Current Circuit
The circuit breaker in the Exciter field circuit is used to isolate the field circuit from
the converter. It is capable of switching off the synchronous machine from full load
under the worst conditions of a 3-phase short-circuit.
In addition to its main contacts, the Exciter field circuit breaker also has a de-
excitation contact with which the stored magnetic energy in the Exciter field can be
dissipated across the de-excitation resistor. The de-excitation contact closes
shortly before the main contacts open so as to ensure proper commutation of the
field current from the main contacts to the de-excitation contact when the breaker
is switched off. The stored energy in Generator field winding is dissipated with
natural time constant of the generator field and Exciter armature circuit.
5.2 De-excitation
refer to block diagram (/YU101)
When malfunctions occur, the stored field energy must be dissipated as quickly
and safely as possible to protect the generator. This is done by the converter, the
field circuit breaker and the de-excitation (discharge) resistor.
De-excitation (with opening of the Exciter field circuit-breaker) takes place in the
following stages:
The converter, driven to its inverter limit position (negative ceiling voltage),
recovers a portion of the field energy in to the network. A trip command is given to
the field circuit breaker.
The de-excitation contact closes, diverting the field voltage to the de-excitation
resistor.
Then, immediately, the main contacts open, building voltage. The field voltage
commutates to the de-excitation resistor.
Due to the reversal of the field voltage by the converter, the Exciter field current
commutates from the main contacts of the Exciter field circuit breaker to the de-
excitation resistor in a very early phase. This reversal of the field voltage prevents
EDN 48-1050-01 33
burn-off on the main contacts and provides effective protection for the field circuit
breaker.
6.0 Monitoring
The actual values for generator voltage Ug and field current I f are monitored for
malfunctions (plausibility). This monitoring is active regardless of whether or not
the Generator Breaker is closed. Essentially, when Excitation is ON, the
measurements are monitored by comparing the signals (the smaller signal reading
is detected as incorrect). If the stand by channel is not faulty, “Active channel Ug
fault” derived by comparison with stand by channel Ug is permitted to initiate
change over action. If Ug is not between 90 to 110% and if difference is > 10%
then also Ug is considered as faulty.
If (Field current) is also monitored by comparing If1 and If2 and whichever is less
is declared as faulty. In addition “If” is monitored for value greater than Ifo when
Generator Circuit Breaker is OFF and for a value less than Ifo when the Generator
Circuit breaker is ON.
7.1 Commands
Pressing the ON button / issuing command through HMI interface closes the
Exciter field circuit breaker when all conditions to PERMIT breaker closing, shown
in the functional representation in schematic diagram GS020-YS501 are satisfied.
EDN 48-1050-01 34
Whenever this command is wired parallel to the command “EXCITATION ON”
(refer to schematic diagram AU020-YB001), excitation is switched on, at the same
time as the Exciter field circuit-breaker (refer to the next section).
Pressing the OFF button / issuing command through HMI interface, switches off
the field circuit breaker and the excitation, which de-energizes the generator
through the converter and the de-excitation resistor. Provided all PERMIT criteria
for Exciter Field Breaker OFF are present as shown in functional representations
on schematic diagram GS020-YS501, pressing the “FIELD BREAKER OFF”
button / issuing command through HMI interface, switches the Exciter Field
breaker OFF.
EXCITATION ON/OFF
Commands with Status
If the logic is so designed then the field circuit breaker must be in the ON position
before the excitation can be switched on. Provided all PERMIT criteria for
Excitation ON are present as shown in functional representations on schematic
diagram GS021-YS501, pressing the “EXCITATION ON” button switches the
Excitation system on, i.e., the enable is given for the firing pulses to the converter.
Pressing the OFF button / issuing Excitation OFF command through HMI,
switches off the excitation, i.e., the converter is directed to inverter operation, de-
energizing the generator, if Excitation OFF PERMIT is available.
Basically, a shift can be made from one channel to the other at any time because
the stand by channel is always matched automatically to the active channel.
Whenever a malfunction is detected on channel-1, a switch-over to the standby
channel is forced, and it is no longer possible to switch back to the channel-1,
while the malfunction is not removed. A switch-over to a faulty channel is not
possible. (refer to the input wiring in schematic diagram AU020/YB001).
That is Ug (Generator Voltage) actual value should be healthy for Auto channel of
operation and If (Field current) actual value should be healthy for Manual channel
of operation
EDN 48-1050-01 35
CHANNEL-1 / CHANNEL-2“RAISE “/”LOWER”
Commands with Status MIN/MAX,
The “RAISE “/”LOWER” push buttons or the commands from HMI are used to
adjust the set point. of the generator voltage. When the generator is operating
under no load, this adjustment changes the generator voltage; in operation under
load, it changes the reactive power output. When the operating limits of the rotor
and the generator are being exploited to the full, appropriate limiters intervene and
disable the “RAISE”/”LOWER” commands in the direction limited (refer to Sect.
2.3 for the limiters).
The “RAISE “/”LOWER” push buttons or the commands from HMI are used to
adjust the set point for field current. When the generator under no load, this
adjustment changes the generator voltage; in operation under load, it changes the
reactive power output. Because there is no limiter available on the MANUAL
channel, care is needed when issuing “RAISE” or “LOWER” commands to see
that the operating limits for the rotor and the generator ( as defined in the Power
Chart) are not exceeded.
Warning signals light up whenever the field current set-point is at its minimum or
maximum value. If both “RAISE” and “LOWER” commands are issued
simultaneously, no adjustment is made in the set point. The field current set-point
is preset automatically at the value for no load excitation current (Ifo) whenever
the excitation is switched on or generator breaker opens.
Field Voltage (Uf), Field Current (If) and Balance Voltage V between the control
variables of the regulator channels are displayed in the control room. The
displays for If and Ug are particularly useful whenever one is operating in the
Manual channel. The V indicator shows the voltage by which control variable of
the selected mode of the stand bychannel differs from that of the selected mode of
the Operating channel.
EDN 48-1050-01 36
The generator can be operated in the AUTOMATIC mode up to the limits set in
generator capability diagram. The permissible operating range for the AUTO
mode is outside the operating range permissible (and set) for the MANUAL mode.
If the stand by channel is selected to be in Manual mode it cannot, in such cases,
track the active channel in Auto mode, the V indicator steadily reports a
difference. During “normal” steady-state operation of the generator, the V
Balance meter must always be at null position. UNLESS THERE IS ANY
SPECIFIC REASON, IT IS ADVANTAGEOUS TO SELECT AUTO MODE FOR
BOTH THE CHANNELS.
7.3 Alarms
The alarm messages in the control room are general messages grouped
according to the information needed by the operating staff. The cause of the
malfunction can be seen in detail on the ALARM INDICATIONS page of the HMI
PICTURE in the Regulation cubicle. A detailed analysis of the malfunction can be
undertaken using LOCAL HMI, by FOLLOW ing the tagname. In addition a
provision has been made to list the, possible causes, Immediate action by
Excitation system and Further procedure to be carried out by maintenance staff,
on LOCAL HMI itself.
EXCITATION TRIP is displayed whenever the excitation and the generator have
been tripped by a critical malfunction of the excitation system. Response: Find out
the exact cause at the local HMI alarm indication on the excitation cubicle. In the
case of a system malfunction, call for Service. In the case of a justifiable protective
operating trip, acknowledge the malfunction signal and restart the unit.
EDN 48-1050-01 37
7.4 Check-List for Operating Staff
The reading for channel tracking (V) is steady in the middle of the dial.
The field current, generator voltage, and reactive power output are stable.
Various monitors check the stand by channels continuously to ensure that they
are functional. Nevertheless, we recommend that a brief switch-over to the other
channel be made periodically, e.g., after a start-up, to test its functional readiness.
The cooling system for the converter cubicle is working properly, air inlets and
outlets are open and free of dirt.
EDN 48-1050-01 38
7.5 Local Operator’s Panel, Exciter Cubicle
refer to block diagram (/YD115)
A LOCAL HMI (Human Machine Interface) door mounted PC has been provided in
Regulation cubicle REG-1
This Industrial PC has been loaded with ValmetDNA software, with which Binary
controls and HMI based operation have been implemented. User shall login as
“dna” and run/open “DNA Operate Client”.
1. ThePC shall be switched on if it is not already on. When the PC is turned on, it
goes through normal boot up routines. When the computer finishes start up
procedure, the Windows 7 Auto Logon dialog appears.
2. Alternatively you may press <CTRL+Alt+Delete> keys to open the logon dialog.
3. Enter your user name as “dna” and password.
4. Once the PC boots up and the Windows 7 desktop appear, and then open a
session of the operator workstation in the PC. i.e.
Goto start menu ->all programs ->metsoDNA -> DNA Operate ->DNA Operate
Client.
On clicking on “DNA Operate Client” the following picture (control panel) will
appear on screen.
5. Click DAVR icon in the toolbar to navigate to the DAVR main picture window.
Various control buttons / soft push buttons are provided for controlling the unit as
part of main picture.
EDN 48-1050-01 39
DAVR Main Picture View
a. Title bar: The title bar of the control panel displays the name of the selected
area. It also contains the standard buttons for minimizing, maximizing, or closing
the control panel
b. Area buttons: By clicking an area button, you select the area to want to
control. When an area button is clicked, the corresponding overview picture
representing a process or sub process is opened in the control panel.
c. Overview picture: The overview picture contains links to more detailed pictures
of the area in question. Its purpose is also to present general information of the
selected area.
d. Toolbar: The toolbar contains buttons for general desktop operations.
EDN 48-1050-01 40
e. Event stepper: When a disturbance occurs, the corresponding disturbance
data is displayed in the event stepper even if the event browser were not open.
f. Event counter: The function of the event counter is to present an overview of
the events currently active in the control room and to provide a quick access to the
information connected to the events. The event counter presents the advancing of
a disturbance in a process from one event area to another. A disturbance is
usually an alarm or a group of alarms requiring an acknowledgement.
The fields in the event counter refer to the process areas which have
unacknowledged events. Up to 5 fields can be displayed in the event counter at a
time. If there are more than 5 fields, the field list can be scrolled in the event
counter in the groups of five by clicking the arrow buttons. The name of the
process area and the number of events active in the area are displayed in each
field. The color of the field represents the highest event priority in the area as
follows:
Red = high alarm priority
Dark orange = medium alarm priority
Light orange = low alarm priority
Gray = notification
Similarly, the color of the arrow button represents the highest event priority in the
group of the next five fields.
Event areas appear in the fields of the event counter at the same pace in which a
disturbance occurs in the area in question. Therefore,
the operator can see (in a chronological order) how a disturbance has advanced in
the process from one event area to another, and find
out the causes and solve the situation.
g. Date and time: This field shows the date and time.
EDN 48-1050-01 41
DAVR main picture details:
Various control commands provided using soft push buttons are as identified in
the above picture.
The corresponding status displays are available near the push button controls.
Display of the following analog signals have been provided on the Main picture.
A. Active power
B. Reactive power
EDN 48-1050-01 42
C. Power factor
D. Exciter Field Voltage
E. Exciter Field Current
F. Generator Voltage
G. Generator Current
H. Channel-1 Control Voltage
I. Channel-2 Control Voltage
J. Channel-3 Control Voltage
It may be noted that first five in the above list are required for the operator to know
the machine parameters while controlling / operating from LOCAL of Excitation
panels. Others though provided are not essential for LOCAL operation. Excepting
Exciter Field voltage, Exciter Field current and Channel balance voltage, all other
displays are indicative in nature, considering the high conversion factors used for
display purposes.
Fault indications have been shown as grouped display in the block diagram
picture. This display shall be GREEN under healthy condition and turns RED
whenever there is a fault.
EDN 48-1050-01 43
A click on this display enables operator to navigate through the detailed alarms list
page. In the detailed alarms list page, the LEDs corresponding to the fault
indications are displayed in RED, when there is a fault. A left click on the LED
enables operator to view the quick trouble shooting support text.
EDN 48-1050-01 44
Micro-Terminal
refer to block diagram (/YD115)
7.6.1 Summary
The Micro-Terminal can be used to view parameters and signal values of the
processor system (UN 0660) and to change stored values within certain address
ranges. To do this, the Micro-Terminal must be connected to the UN 0660
processor in question by plugging a system cable in on its front side. This system
cable also supplies the power to the Micro-Terminal. The Micro-Terminal has a 4-
line LCD display in which 4 addresses (lines) appear simultaneously. The address
appears at the left of these lines and the value for these addresses at the right.
The four values displayed can be measured or recorded at the four measurement
sockets provided below the LCD display.
To select a given address on the display, the cursor must first be moved to the
beginning of the line desired. Then the new address must be typed on the
keyboard, and this address entered using the “RETURN” key. This causes the
value for the newly selected address to be displayed at the right. The Micro-
Terminal automatically translates a number of the addresses into easily
interpreted alphanumeric values. For example, the actual value for generator
voltage is at address F90A in the processor system for the AUTOMATIC mode /
channel. Whenever this address is selected, the term “Uact” appears in the
address column, and the signal value, for example, 102.3% appears in
alphanumeric form.
A new address can also be selected by moving the cursor to a given address in
the address column and “paging through” the addresses with incremental
commands (push buttons: INC / DEC). Because the addresses that can be
selected via the Micro-Terminal are always even-numbered, the Micro-Terminal
rounds up to the next even-numbered address.
The Micro-Terminal can make changes in either the RAM storage or in the
EEPROM storage. Changes in the RAM storage are temporary: they are canceled
again the next time the process is initialized (The value in the EEPROM storage is
taken over again). Changes in the RAM storage are therefore suitable mainly for
test purposes. Changes in the EEPROM storage, on the other hand, are
permanent. The address range for the EEPROM storage is from HEX C000 to
HEX C7FE. The corresponding addresses in the RAM range are exactly HEX
3000 higher. For example, the RAM address F250 corresponds to the EEPROM
address C250.
EDN 48-1050-01 45
Changes in value in the RAM range are made by moving the cursor under the
value to be changed, typing in the new value, and entering it with the “RET” key.
As an alternative, a steady change in value can also be made by pressing the
“INC”/”DEC” keys while the cursor is located under the value that is to be
changed.
Changes in value in the EEPROM range are made by pressing not the “RET” key
alone, but the keys “SHIFT”, “WRITE”, and “RET”, in that sequence. The changed
value in the EEPROM range then appears on the display, but is not yet
functionally effective: The processor is still performing calculations using the “old”
RAM storage value. The new value is not taken over into the RAM storage until
the RAM storage is reinitialized, for example, by pressing the RESET button on
the front of the UN 0660 processor involved.
Note:- The address which generates the indication of the difference can be found
via the micro-terminal when it is connected to the AUTO channel CPU module
(UN0660)::
The processor systems of the Channels-1 and 2 contain software in the form of
unalterable standard functional modules (firmware). The plant-specific overall
function depends on the settings of the software switches, referred to as
“configuration flags” (K-Flags). Because these K-Flags define the Scope of Supply
for the plant software, they cannot be changed in the EEPROM range. The range
of addresses for the K Flags in the RAM storage includes the addresses from
F702 to F7FF.
In the processor system for the AUTOMATIC mode / channel, the values of 12
signals can be selected directly using specific keys on the Micro-Terminal (without
EDN 48-1050-01 46
typing in an address). The list below shows these signal values and their essential
characteristics:
CPhi ind \ cap Power factor (-1024 ..0.. F842 ±1024 ± 10V
+1024 = (0 cap...1...0 ind)
EDN 48-1050-01 47
Secondary (stand by) are used. The two ACN-CSs are connected to form a back
up pair. Process control can be transferred Automatically (fail Over).
The Binary Input (DII8P24) / Output modules (DOI4RO) provide the physical
connection point, for the input / output wiring of signals to and from the process.
The analog inputs required in Binary controls are acquired through the Analog
Input Module (AII8V).
For interfacing ValmetDNA with DAVR hardware Digital Input module (DII8P24)
and Digital output module (DOI4RO) have been used.
The Signal Flow:
Potential free contacts from field Digital Input Module Digital Input Buffer
(DIB) Configuration logic residing inside active ACN-CS Digital output
Buffer (DOB) Digital Output module Aux relay for contact multiplication and
remote use.
The Configuration (software file)
The configuration file is built using FBCAD. The Input modules and Output
modules are defined with the module locations. Each Input module has 8 LEDs on
its front plate which glows to indicate that the particular channel is high. Each
output module has 4 LEDs on its front plate which glows to indicate that the
particular channel is high.
The project specific Logics are built in the configuration file using FBCAD. To have
a structured configuration, they are divided in to groups which replicate the
scheme sheet drg for the logic. The system permits provision of 8 levels of groups.
Inside the groups various atomic function blocks (like AND gate, OR gate, R-S flip
flop, ON delay timer, OFF delay timer etc.) are used to construct the plant specific
logic required. Unique Tag names (DTAG-Digital Tagger) are assigned for Digital
I/O signals in the buffers. Unique Tag names can be assigned / used anywhere a
digital signal needs to be tagged or alarmed.
Similarly unique Tag names (ATAG-Analog Tagger) are assigned for Analog I/O
signals in the buffers. Unique Tag names can be assigned / used anywhere an
Analog signal needs to be tagged or alarmed. Each of the atomic blocks has
appropriate attributes which makes the usage of these blocks versatile.
8.1 Overview
While electronic components themselves do not suffer from aging and show only
insignificant wear, the excitation equipment includes a number of such electro-
mechanical elements as circuit-breakers contactors and fans all of which are
subject to a certain amount of wear.
If, even so, a malfunction should ever occur in the electronic section, there are
various monitors and corresponding annunciation displays available. Certain
functional parts, however, are difficult to monitor and must therefore be inspected
periodically.
EDN 48-1050-01 48
Fouling builds up as a result of the natural draft air cooling of the electronic
equipment. Some of the screw-terminal connections can work themselves loose
due to vibrations.
High voltages and currents (DC!) occur in the exciter circuit. Here, spots in the
insulation that have become dirty present a risk of major damage from voltage
flash-over. Periodic preventive maintenance on the installation reduces this risk
greatly.
We recommend the following preventive maintenance and care for the installation:
* Check for blocking of the vents in the cubicles. These may be washed out
using a suitable cleaning fluid, or with a blower.
* Check the current distribution among the converter blocks and current
conductance of the thyristors.
* Check that the important measured values are correct. To do this, read the
measurements on the Micro-Terminal and compare them with the values on the
instruments in the control room / LOCAL HMI display. Check at least the following
values on the two channels: generator voltage F90A, stator current F91C, field
current F910, and active power output FA80.
* Check for dust deposits in the converter. If it is severely fouled, clean it,
particularly the cooling elements, using dry, oil-free compressed air.
* Check for fouling of the plug-in modules (printed circuit boards and devices) in
the swing frame. Only if necessary: blow the dirty components out with a dry, low-
pressure air jet. In circuit boards or devices with gold-plated contacts (Tier AG,
EDN 48-1050-01 49
AP) clean the contacts carefully using White Spirit or a contact cleaning fluid of
proven quality. If the printed circuit boards are severely blocked (cannot be
cleaned out with an air jet), use special cleaning procedures and then neutralize
and dry them. Be very careful in taking the circuit boards out and putting them
back in, and take the “Electrostatic Discharge” precautions indicated in Sect. 8.3.2
below.
* Check that all screw connections are firmly seated.
* Check all protective equipment in the trip and the signalization circuits.
* Perform a functional test on the complete electronic system as described in
Sect. 8.3.3 below.
The operating staff must familiarize themselves with the details of how the
excitation system works and with its operating controls well enough to enable
them to evaluate the situation correctly in the case of a malfunction based on the
readings of the displays and the malfunction signals received. Always avoid
precipitous action.
The cause of the malfunction must be known before any general acknowledgment
of the system is made. If it is not, determine and record the detailed “malfunction
symptoms” as in the List of Alarms / trouble shooting support text.
EDN 48-1050-01 50
Cyclic self-test routines monitor, malfunctions of the digital electronics of the DVR
system. A processor malfunction is announced on the front plate of the defective
module by a “FAIL” LED, and is signaled to the alarm display. In case of a
malfunction on the channel-I, an automatic switch over to channel-II is made. The
defective module can thus be removed from the channel-I and replaced with a
spare part while the generator is in operation.
The various power packs have voltage monitors of their own. They switch off
automatically whenever the monitor responds and signal the malfunction in the
alarm display.
For circuit boards in Tiers AA, AB, AE switch off the protective circuit-breaker at
the input of the corresponding 692.03.PY2BA module before taking out and
replacing the electronic modules. The voltage must be OFF before attempting to
replace them! The circuit boards in tier AG, AP... may in general not be replaced
while the power supply is ON. In cases the module supply cannot be switched off
selectively, the module must be pulled out and inserted “decisively” (with no
hesitation). Before inserting the replacement module, make all the adjustments on
it, such as switch settings, bridges, special equipment, etc. as described on the
Test and Commissioning Report. (Also compare it with the “old” module!). In the
case of the UN 0660 microprocessor circuit boards, also make certain that the
correct operating program PROM (correct HIER No.) is installed in Location A735
and the correct user’s program PROM is installed in Location A736. Whenever
the parameter values on the replacement circuit board are not being entered
via the Micro-Terminal (refer to Sect.7.6), then the EEPROM in Location A738
must also be changed from the “old” module. The “old” settings of
potentiometers R23 (U1), R24 (U2), R25 (UR), R26 (US), and R28 (UT) must be
carried over on the UN 0661 “Interrupt generator” module.
Caution!
Most of the electronics modules contain CMOS elements that are highly sensitive
to electrostatic discharge (ESD). Whenever these modules have to be handled,
follow the “Guidelines for Handling ESD-Sensitive Electronic Components.
EDN 48-1050-01 51
* Checking for wear on the mechanical parts (e.g., relays, switches).
For a functional test while the machine is at standstill, set testing switch –S20 at
“TEST”, open Q3 and MCB F74 ON. The AC power supply for the electronics and
the synchronous voltages Usyn are then obtained from station auxiliary supply
(Refer to scheme sht. no. CE100-YS601). For normal operation, switch off F74,
close Q3 and switch S20 in service.
The digital control electronics have in built test routines that run cyclically and
check during operation to make sure that the hardware is functional. For that
reason, the functions implemented in the processor do not have to be checked in
routine controls. Either all the functions of a processor system function properly, or
none of them do. The latter is accompanied by an alarm signal from the
processor.
However, the measured data must be checked carefully. To do this, apply the
associated 100% values for voltage and current at the input terminals using a 3-
phase Variac or an electronic function generator.
To check that the conversion in the peripheral input modules and in the
A/D transducer of the processor system is correct, compare the values applied
with the display on the Micro-Terminal (refer also to Sect. 7.6). The addresses for
the measured data in the processor systems are as follows:
The other data measured on the AUTOMATIC channel, such as active and
reactive power output, load angle, etc., are derived by calculation from Ug and Ig
and do not need to be checked in routine inspections.
The power supply units have a voltage monitor built into them. To test this
monitor, open the protective circuit-breaker assigned to the power supply unit.
EDN 48-1050-01 52
Proper functioning of the monitor is signaled on the alarm display and/or on the
module itself.
As a further check, measure the output voltages from the power supply units and
compare them with the data in the Test and Commissioning Report.
Triggering of Channel 1:
* Set testing switch –S20 in the cubicle at “TEST”, Q3 off and F74 ON
* Compare the shape of the pulses with the data on the Data Sheet for the
UN 0663.
* Test all the channels; the two AUTO channels (AA65, AB65) and the
MANUAL channel (AE65).
To test the Intermediate Pulse Stage UN 0096, switch to Channel -1, operation
and view or record all output pulses at measurement sockets R+ ... S- to 0 V.
Repeat the checks for Channel –2 & Channel –3. Compare the shape of these
pulses with the data in the relevant Data Sheet.
To test the Pulse Final Stages UN 0809 check all output pulses at measurement
sockets R+ ...S- to 0 V. Compare the shape of these pulses with the data in the
data sheet.
Next measure the pulses on the thyristors themselves, i.e., downstream from the
pulse transmitters. The pulse amplitude is still approx. 2 to 5 V. If there are firing
pulses at all thyristors, the entire pulse path is OK.
EDN 48-1050-01 53
During major overhauls, it is a good idea to test the inputs and outputs of the
open-loop controls.
To test the inputs, locate the sources of the messages using the schematic
diagram / by FOLLOW ing the signals and simulate a response of the
annunciation contact. The corresponding LED on the DII8P24 Input module must
then light up.
The outputs include the commands for the field circuit-breaker and the field
flashing breaker. Since the OFF commands for the field circuit- breaker are in
redundant circuits, they must be tested individually.
Work carefully when testing the protective equipment. To check the protective
trips for over current, simulate a field current If equal to 105% Ifn at the isolating
terminals. Then change the following settings temporarily, one after the other,
producing an exciter trip each time:
* the UN 0663 for the channel --1 (AA65): S853 to “1”, causing an immediate
trip;
* the UN 0663 for the channel --2 (AB65): S853 to “1”, causing an immediate
trip;
* the UN 0663 for the channel --3 (AE65): S853 to “1”, causing an immediate
trip;
For all trip simulations, always make certain that the trip coil of the field circuit
breaker pulls in and that a generator trip is initiated.
The alarm displays on the LED indications page of the HMI picture and the other
alarm and operating displays on the fronts of modules are used for quick pin-
pointing of malfunctions.
Refer to the appropriate Data Sheets for an interpretation of the operating and
malfunction displays (LED’s) on the fronts of the various modules.
The Excitation System malfunctions are signaled on the LED indications page of
the HMI display using pictorial LED’s. The Plain text descriptions of these alarms
also indicated by the side of pictorial alarm LEDs.
When a malfunction is present, the corresponding LED flashes. The alarm can be
acknowledged using the RESET button. Brief malfunctions are stored in memory
and annunciated also. The indication vanishes once these temporary malfunctions
are acknowledged.
For various disturbances, the malfunctions indication is not only lit for the source
itself, but also for the secondary malfunctions. In such cases, it is often difficult to
EDN 48-1050-01 54
identify the actual root of the problem quickly. “Field breaker First Out/ Field
breaker Protection”, “Excitation First Out / Excitation Protection”, “Channel-1 First
Out”, “Channel-2 First Out” help to identify the actual root cause of the problem
quickly. The first fault within the group will be flashing and rest of the faults will be
steady.
Note the following when using the List of Alarms that follows:
The following general procedure always applies even though not stated in the
“Trouble shooting support display”:
* Check the symptoms listed for the malfunction indications that are still
present.
* “Further Procedure”:
Carry out the instructions step-by-step in the order shown. Once one step has
proven successful (the malfunction has been located and/or eliminated), the steps
that follow are no longer necessary.
EDN 48-1050-01 55
The set point for voltage or field After “EXCITATION ON,” the binary
current is not at the nominal no- controls must issue setting commands for
load value Channel 1and 2 to PRESET reference
value. Refer to EG040-YS505.
PRESET value for Auto Channel
= address F250 in respective
processors (refer to /YU105).
PRESET value for Manual
Channel = Switch S855 on UN 0663
of respective channel (AE65)
Regulator malfunction Is the control variable U of the active
contr
UN 0663 Gate Control Unit positive after
“EXCITATION ON”? If not: For Auto
Channels 1 & 2 do a functional test with the
Micro-Terminal based on /YU105. For Manual
channel, test based on data sheet of UN0663
Over voltage due to improper Switch over to manual mode and build up the
phase sequence voltage. Check the phase position of UR w.r.t
IR, US w.r.t. IS and UT w.r.t IT. At the sockets
of module UN0661 of Auto channel.
Over Voltage due to voltage Switch over to manual mode and build up
regulator voltage. Check the actual values of Auto
channels on the Micro Terminal while exciting
the generator on manual mode. If set point
F270 is too high, check F250, F254 & F256. If
necessary, change the “Soft-Start Time” using
F290
Over Voltage due to the If Switch over to Auto channel and build up
voltage. Check the actual value for field current
regulator in Manual mode
at socket “If” while exciting the generator on
Auto mode. Check Vp and Ta in UN0663
module as per commissioning report.
Gate Control Unit malfunction Check if the control variable Ucontr is correct
(it can be measured at the socket Ucontr),
check the firing pulses R+ ... S- and their
phase position. Check the synchronous
voltages at UR, US, and UT.
EDN 48-1050-01 56
Unstable parallel Operation with the Grid
Periodic Fluctuations in Reactive / Active Power Output
Change in the controlled system If the changes causing the problem cannot be
due to changes on the grid or cancelled, restabilize the control loop. Then
drive end check and/or restabilise the limiters as well.
Adjustments for Vo, Vp, Ta, and Check the settings against the Test and
Tb have shifted. Commissioning Report.
The droop influence is causing Check active current IR and reactive current IX
an irregular voltage effect. at Addresses F906 and F902 (refer to/YU105).
Check external current transducer circuit and
actual value for current Ig against the Test and
Commissioning Report.
Generator is working in an Adjust the set-point and bring the generator
unacceptable operating range back within its normal operating range. Do a
(normally prevented by limiters). functional test on the limiters.
EDN 48-1050-01 57
9.0 Installation and Commissioning
Installation Site
With its thyristor converters, the exciter generates heavy high-voltage DC currents
in the field current circuit. If the installation is subjected to the prolonged effects of
dirt and corrosive gases, there is a risk of extensive damage caused by voltage
flash-over. For that reason, select the location of the exciter in the power plant
carefully and, if necessary, protect it from such dangers.
The converter portion should be located as close as possible to the sliprings and
the exciter transformer so as to keep voltage losses to a minimum.
It goes without saying that the cubicles must be protected against splashing or
spraying water, falling objects, etc.
Ambient Air
The air must be as dry as possible and free of pollution, aggressive gas, insects,
etc. Salty vapors, e.g., due to cooling with salt water, damage the unit.
As a standard rule, the ambient temperature about the exciter must not exceed
50 °C (104 °F). Make certain that the warmed cooling air can flow off. Above the
air pass out area an air space of at least one meter (approx.3 feet) must be left.
Commissioning
Preliminary testing:
Generator commissioning: test runs and testing of the generator protection system
EDN 48-1050-01 58
Preliminary testing includes testing of the measurement, control, TRIP and alarm
circuits, and the functional test on the converter. The following conditions must be
met before these tests are carried out:
The binary input signals must have been tested as far as the LED’s on the input
modules. (Switch on F56, F57, F70, F71 and F81 to F84) and S20 to test position.
The binary output signals must have been tested electrically, starting from the
connection terminals (Jump the output contacts on the connection terminals).
There must be an external power source available for the excitation transformer or
for the converter directly (Also needed for the subsequent generator test runs).
A substitute resistor (> 20 A) must be available for the functional test of the
converter.
Normally, the test runs for the generator include the recording of the generator’s
short-circuit and open circuit characteristics and testing of the generator’s
protective TRIPs. For this purpose, the excitation transformer must be supplied
with power from an outside source (not in shunt connection).
EDN 48-1050-01 59
Approx. time required
Tests ------------------------------------------------------------------------------
Operating Conditions
- Oscillograms for 1 0 to 1 0 0 1
excitation start-up,
de-excitation, AUT0-1
and AUTO-2
- Voltage regulators: 1 1 as as 2*
checking stability with desired desired
the grid
- Reactive load shut-down 1 1 appr. 0 +0.4 0.5 *
(with oscillogram)
EDN 48-1050-01 60
Storage Instructions for Digital Voltage Regulator
Following are the guidelines for storing the above mentioned equipment when received at
site:-
a) UNLOADING
i) Due care should be taken while unloading or shifting the equipment/packages to
avoid damage to components. Dropping of the equipment from trucks can cause
serious damage to performance and life of components which may not be
noticeable externally.
ii) Eye bolts and lifting beams provided should preferably be used for handling.
b) PRELIMINARY INSPECTION
i) Usually the equipment is supplied in completely assembled condition. Certain
components which are likely to fail in trasit due to shocks and vibrations are
removed from panels and are supplied in separate packages.
ii) On receipt of consignment, it should be checked according to the shipping list for
shortages, if any.
iii) Damages, if any, noticed under visual inspection should be immediately brought
to the notice of BHEL and Transporters.
iv) Though due care is taken while packing the material for despatch, sometimes
damages occur due to unforeseen causes like overspeeding of trucks on rough
roads, loose shunting on railway tracks, collisions, etc., which can result in
loosening of supports. These should be tightened and components supplied
loose are to be mounted at proper places.
c) STORAGE
i) If cubicles are to be stored for a long time, i.e., more than 6 to 8 weeks, it is
advisable to preserve the packing material for repacking.
ii) Wooden packing base may be retained to use it as a raised platform for storage.
iv) Equipment after unpacking is not to be left directly on the ground without proper
wooden supports. Raised wooden platform will reduce the chances of damage
due to vermins, fungus, insects, etc..
vi) Due care should be taken to ensure that the equipment is not exposed to fumes,
gases, etc. . Often electrical contacts of relays and terminal boards are affected
by exposure to fumes and gases.
ix) All electronic modules should be removed from its racks and placed in an A/C
room mainted at 20°C till these are required during commissioning.
x) While handling the electronic modules, care should be taken to ensure that the
PCB and the components mounted over the PCBs are not touched with hands.
Module should be carried by holding its front plate firmly.
2 X 660 MW STG
OF
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 1 of 109
Formatno.:EDN95-653-017
Rev.01
TEST CERTIFICATE
DIGITALAUTOMATIC
VOLTAGEREGULATOR
EDNSETNO. :1
W.B.S.Element
No. : CE/1050-5H3-48-01
OGADRG.NO. :3-657-00-00187
SCHEMATIC
DRG.NO. : 3-657-00-05226
TESTREPORT
NO. i2OShSh192
PREPARED
BY .T4STEDBY WITNESSED
BY APPROVEDBY
ft#rmeil, Gr--
oMcl\.!r..a'- r'I
ffiry' tk-#f,
$#ffiF"ffilffiY
Date23.11.2015 ,
o"tL''qlospot! Date:\l>]1L oate:o{loa lzOtJo
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 3 of 109
Format no.: EDN 95-653-017 Rev.01
27 CPU module for CH2 (69203DB1AA,UN0660,AB49) 48 150158720070
28 DC-DC supply module for CH2(69203PY2BA,AB37) 51 150164770009
29 CPU mod. for Xe-identification CH2 52 150158720095
(69203DB1AA,UN0660,AB13)
30 Interrupt Gen. Unit for Xe-identification CH2 54 150158740042
(69203GB1AA ,UN0661,AB17)
31 Analog I/O mod.for Xe-identification CH2 57 150158780117
(69203NA1AA,UN 0610,AB21)
32 Digital I/O mod.for Xe-identification CH2 58 150174890053
(69203NB1AA,UN0662,AB25)
33 V and I measuring module for CH3 59 140158750061
(69203IA1AA,UNC4660,U03)
34 Digital Firing & Control module for CH3 61 150177160030
(69203DU1CA,UN0663, AE65)
35 Pulse Intermediate stage amplifier for CH3 63 150158680058
(69143350,UN0096,AG21)
36 DC-DC supply module for CH3 64 150164770010
(69203PY2BA,AE37)
37 Pulse final stage power supply 64 150161460014
(CE69132260,UN0901,AP07)
38 Pulse final stage power supply 65 150161460011
(CE69132260,UN0901,AP10)
39 Pulse Final stage amplifier for TY1 66 150180240006
(69203MU1BA,UN0809,AP20)
40 Pulse Final stage amplifier for TY2 66 150180240005
(69203MU1BA,UN0809,AP03)
41 MicroTerminal ( 69203TB2AA , UNS 2660, AC45 ) 67 150158840048
42 Memory card ( 69203YV1BA , CT370, AG15) 67 150176030065
43 Memory card ( 69203YV1BA , CT370, AP15) 67 150176030056
44 Test point module (69138840, UN0094, AP23) 67 150160460050
45 Test point module (69138840, UN0094, AG23) 67 150160460042
46 List of Parameters for channel-1(Auto) AA49 68
47 Parameter list for Xe identification AA13 76
48 List of Parameters for channel-2(Auto) AB49 78
49 Parameter list for Xe identification AB13 86
50 AC and DC Power supply circuits 88
51 Tap setting of Transformers 88
52 Checking of Transducers 89
53 Light load test 98
54 Testing of Field-Breaker (Q1) 100
55 Current flow monitor – A31, A32 101
56 Current sharing in thyristor bridges 102
57 Heat run test 103
58 Checking of Local HMI 106
59 Checking of PSS10,PSF10,PSS11,PSF11 107
60 Rotor temp.measurment 107
61 Line up test 108
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 4 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 5 of 109
Format no.: EDN 95-653-017 Rev.01
R3M02 Digital input DII8P24 150176900057
R3M03 Digital input DII8P24 150176900058
R3M04 Digital output DOI4RO 150175030010
R3M05 Digital output DOI4RO 150175030026
R3M06 Digital output DOI4RO 150175030029
R3M07 Digital output DOI4RO 150175030030
R3M08 Digital output DOI4RO 150175030032
R3M09 Digital output DOI4RO 150175030033
R3M10 Digital input DII8P24 150176900071
R3M11 Digital output DOI4RO 150175030034
R3M12 Digital output DOI4RO 150175030023
R3M13 Digital output DOI4RO 150175030037
R3M14 Analog input AII8V
R3M15 Analog input AII8V
IPSP4 Power supply unit 150164730232
IBC4 Bus controller unit 150168540092
R4M00 Digital input DII8P24 150176900051
R4M01 Digital input DII8P24 150176900054
R4M02 Digital input DII8P24 150176900055
R4M03 Digital input DII8P24 150176900073
R4M04 Digital output DOI4RO 150175030013
R4M05 Digital output DOI4RO 150175030043
R4M06 Digital output DOI4RO 150175030044
R4M07 Digital output DOI4RO 150175030045
R4M08 Digital output DOI4RO 150175030046
R4M09 Digital output DOI4RO 150175030047
R4M10 Digital input DII8P24 150176900078
R4M11 Digital output DOI4RO 150175030048
R4M12 Digital output DOI4RO 150175030049
R4M13 Digital output DOI4RO 150175030050
R4M14 Analog input AII8V
R4M15 Analog input AII8V
IPSP5 Power supply unit 150164740118
IBC5 Bus controller unit 150168550105
R5M00 Digital input DII8P24 150176900053
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 6 of 109
Format no.: EDN 95-653-017 Rev.01
R5M01 Digital input DII8P24 150176900065
R5M02 Digital input DII8P24 150176900066
R5M03 Digital input DII8P24 150176900091
R5M04 Digital input DII8P24 150176900063
R5M05 Digital input DII8P24 150176900064
R5M06 Digital input DII8P24 150176900077
R5M07 Digital input DII8P24 150176900059
R5M08 Digital output DOI4RO 150174930270
R5M09 Digital output DOI4RO 150174930269
R5M10 Digital output DOI4RO 150174930290
R5M11 Digital output DOI4RO 140164560266
R5M12 Digital output DOI4RO 140164560279
R5M13 Digital output DOI4RO 140164560300
R5M14 Digital output DOI4RO 150174930279
R5M15 Digital output DOI4RO 140164560179
IPSP6 Power supply unit 150164730137
IBC6 Bus controller unit 150168520012
R6M00 Digital input DII8P24 150176900062
R6M01 Digital input DII8P24 150176900061
R6M02 Digital input DII8P24 150176900060
R6M03 Digital input DII8P24 150176900072
R6M04 Digital input DII8P24 150176900079
R6M05 Digital input DII8P24 150176900080
R6M06 Digital input DII8P24 150176900082
R6M07 Digital input DII8P24 150176900086
R6M08 Digital output DOI4RO 140164560167
R6M09 Digital output DOI4RO 150174930294
R6M10 Digital output DOI4RO 150174930293
R6M11 Digital output DOI4RO 150174930292
R6M12 Digital output DOI4RO 150174930291
R6M13 Digital output DOI4RO 150174930287
R6M14 Digital output DOI4RO 150174930288
R6M15 Digital output DOI4RO 150174930289
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 7 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 8 of 109
Format no.: EDN 95-653-017 Rev.01
11. Exciter Field Excitation requirement
i) No load field voltage Ufo VDC 20.1
ii) No load field current Ifo ADC 39.5
iii) Nominal field voltage Ufn VDC 58.4
iv) Nominal field current Ifn ADC 115
v) Max.cont.rated field voltage Ufmax VDC 58.4
vi) Max.cont.rated field current Ifmax ADC 115
vii) Ceiling voltage Ud VDC 95.2
viii) Ceiling current Id ADC 187.3
ix) Duration of field forcing - Sec. 10.0
12. Field test voltage - KVrms -
13. Synchronising slip - % -
14. AVR CT ratio - AAC AAC 24000/5
15. AVR PT ratio - VAC VAC 21000/110
16. Ambient - Deg.C 50
17. Altitude - meters 1000
18. Permanent Magnet Generator data
i) Rated output KVA 65
ii) Rated Voltage VAC 220
iii) Rated current AAC 195
iv) Rated Frequency Hz 400
2.Specification of Excitation Equipment :
Sl.No Description Unit Value
1 Accuracy of excitation control % ±0.5
2 Range of voltage control in Auto % 90 Ugn - 110 Ugn
3 Range of voltage control in Manual % 0 Ifo-105 Ifn
4 Range reactive current compensation % Up to 15
5 Frequency range of operation Hz 47-52
6 Total No.of THY.bridges No. 2
7 No. of redundant THY.bridges No. 1
8 Protection class - IP 32
9 Excitation equipment rating
a) Voltage VDC 58.4
b) Current ADC 115
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 9 of 109
Format no.: EDN 95-653-017 Rev.01
10 Range of PF regulation NA
11 Range of MVAR regulation NA
12 Station battery supply VDC 220
3.List of measurement and instruments :
SL.No Measurement Accuracy Instrument Equipment
1 a) AC Voltage(<1000V) ±1% Digital Voltmeter to be
used for PT, FB, AC
voltages and AC Input to
Electronic Power supplies
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 10 of 109
Format no.: EDN 95-653-017 Rev.01
NOTE: Least count of the above instruments equipments shall be adequate for reading
measuring the parameters with its specified tolerance (as given in the test instruction
report)
PROGRAMMING SETTINGS
Legend:
A Connection point(solder pin).
R1 Resistor on soldering pins (setting element)
1 Programming link between soldering pins
S,X,J Programming link, plug, jumper
Resistors:
1) 0.25W 2%
2) 0.25W 0.25%
3) 2W 2%
4) 6W 5%
5) 1W 2%
6) 5W 5%
Capacitors:
7) Tantal Elco 33 micro Farad, 35V
ADVISE TO TEST AND COMMISSIONING STAFF:
EVERY BOX “_____ ” IN THE TEST REPORT HAS TO BE FILLED OUT WITH “OK”
OR “VALUE” OR “NA”(Not applicable).
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 11 of 109
Format no.: EDN 95-653-017 Rev.01
4. Insulation Resistance & HV Test
Instruments used Range Make Sl.No.
Megger 500V/1000V Shanti 1613G
HV test set 0-5KV AEL MT-72262908
Details of voltage groups:
Ambient Temperature 29
Humidity 44
Date 24.02.2016
Time 9:25AM
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 12 of 109
Format no.: EDN 95-653-017 Rev.01
5.Metso module settings
General :
1. Check switch setting on MBM120 and MBI8 mounting boards as per the scheme.
2. Power supply connectors to ACNCS, MBM120 and MBI8 modules to be plugged in as per the
Scheme.
3. Insert the corresponding 16 ,10 or 8 pin connector in each input/output module.
OK
RACK 2 S1=1 S2=9 S1=0 S1=4
OK
RACK 3 S1=2 S2=0 S1=0 S1=4
OK
RACK 4 S1=3 S2=9 S1=0 S1=4
OK
RACK 5 S1=4 S2=0 S1=0 S1=4
OK
RACK 6 S1=5 S2=9 S1=0 S1=4
IBC Settings
OK
RACK 2 2,4,5,6 = ON 1,3,7,8 = OFF
OK
RACK 3 2,4,5,6 = ON 1,3,7,8 = OFF
OK
RACK 4 2,4,5,6 = ON 1,3,7,8 = OFF
OK
RACK 5 2,4,5,6 = ON 1,3,7,8 = OFF
OK
RACK 6 2,4,5,6 = ON 1,3,7,8 = OFF
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 13 of 109
Format no.: EDN 95-653-017 Rev.01
6.MCB Settings :
Regulation Over load release Range Recomended Factory
cubicle setting setting/TEST
OK
F56,F57 25A Fixed
OK
F51,F52,F55,F81, 1.6-2.5A 2.5A
F82,F83,F84,F54,
F55
OK
F65.1,F65.2 2.5A-4A 3A
OK
F78,F79,F80 0.63 -1A 0.8A
OK
F70,F71 9-12.5A 12A
OK
F91 9-12.5A 12A
OK
F74 9-12.5A 12A
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 14 of 109
Format no.: EDN 95-653-017 Rev.01
7.V and I measuring module for Channel 1 ( 69203IA1AA , UNC 4660, U01)
Place of unit : U01
Diagram sheet : DE010 / YS601/602
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 15 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 17 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 18 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 19 of 109
Format no.: EDN 95-653-017 Rev.01
9.Analog Input/Output module for CH 1 ( ED 69203NA1AA, UN 0610, AA57)
Place of unit : AA57 Diagram sheet : DE010 / YS702
10. Digital input / output module for Channel 1 (69203NB1AA, UN 0662, AA61)
Place of unit : AA61
Diagram sheet : DE010 / YS703
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 21 of 109
Format no.: EDN 95-653-017 Rev.01
11.Digital inputoutput module for Channel 1 (69203NB1AA, UN 0662, AA69)
Place of unit : AA69
Diagram sheet : DE010 / YS706
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 22 of 109
Format no.: EDN 95-653-017 Rev.01
12.Digital Firing and control module for CH-1 (69203DU1CA, UN 0663, AA65)
Place of unit : AA65
Diagram sheet : DE010 / YS704
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 23 of 109
Format no.: EDN 95-653-017 Rev.01
Digital Firing and control module for CH-1 (69203DU1CA, UN 0663, AA65)
Signal settings
Measurements Testpoint
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 24 of 109
Format no.: EDN 95-653-017 Rev.01
Digital Firing and control module for CH-1 (69203DU1CA, UN 0663, AA65)
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 25 of 109
Format no.: EDN 95-653-017 Rev.01
Block 1 memory
Block 2 memory
Block 3 memory
Block 4 memory *
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 26 of 109
Format no.: EDN 95-653-017 Rev.01
CPU module for channel 1 (69203DB1AA, UN 0660, AA49)
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 27 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 28 of 109
Format no.: EDN 95-653-017 Rev.01
15.DC-DC supply module for channel 1 (69203PY2BA, AA37)
Place of unit : AA37
Diagram sheet : DE010 / YS710
Check whether output voltages are within tolerance when DC input is = OK /_____
220V + 10% and = 220V - 15%
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 29 of 109
Format no.: EDN 95-653-017 Rev.01
16.CPU module for Xe-identification channel 1 (69203DB1AA, UN 0660, AA13)
Place of unit : AA13
Diagram sheet : DE011 / YS710
Block 1 memory
Block 2 memory
Block 3 memory
Block 4 memory
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 30 of 109
Format no.: EDN 95-653-017 Rev.01
Direct memory access
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 31 of 109
Format no.: EDN 95-653-017 Rev.01
17.Interrupt Gen. Unit for Xe-identification Ch-1 (69203GB2AA , UN 0661, AA17)
Place of unit : AA17
Diagram sheet : DE011 / YS701
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 32 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 33 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 34 of 109
Format no.: EDN 95-653-017 Rev.01
18. Analog I/O module Xe-identification CH 1 (ED69203NA1AA,UN0610, AA21)
Place of unit : AA21 Diagram sheet : DE011 / YS702
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 36 of 109
Format no.: EDN 95-653-017 Rev.01
20.V and I measuring module for Channel 2 ( 69203IA1AA , UNC 4660, U02)
Place of unit : U02
Diagram sheet : DE020 / YS601, 602
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 37 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 39 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 40 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 41 of 109
Format no.: EDN 95-653-017 Rev.01
22.Analog Input/Output module for Channel 2(ED69203NA1AA,UN0610, AB57)
Place of unit : AB57 Diagram sheet : DE020 / YS702
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 43 of 109
Format no.: EDN 95-653-017 Rev.01
24.Digital inputoutput module for Channel 2 (69203NB1AA, UN 0662, AB69)
Place of unit : AB69
Diagram sheet : DE020 / YS706
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 44 of 109
Format no.: EDN 95-653-017 Rev.01
25.Digital Firing and control module for CH-2 (69203DU1CA, UN 0663, AB65)
Place of unit : AB65
Diagram sheet : DE020 / YS704
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 45 of 109
Format no.: EDN 95-653-017 Rev.01
Digital Firing and control module for CH-2 (69203DU1CA, UN 0663, AB65)
Signal settings
Measurements Testpoint
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 46 of 109
Format no.: EDN 95-653-017 Rev.01
Digital Firing and control module for CH-2 (69203DU1BA, UN 0663, AB65)
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 47 of 109
Format no.: EDN 95-653-017 Rev.01
27.CPU module for channel 2 (69203DB1AA, UN 0660, AB49)
Place of unit : AB49
Diagram sheet : DE020 / YS710
Block 1 memory
Block 2 memory
Block 3 memory
Block 4 memory
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 48 of 109
Format no.: EDN 95-653-017 Rev.01
CPU module for channel 2 (69203DB1AA, UN 0660, AB49)
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 49 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 50 of 109
Format no.: EDN 95-653-017 Rev.01
Check whether output voltages are within tolerance when DC input is = OK /_____
220V + 10% and = 220V - 15%
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 51 of 109
Format no.: EDN 95-653-017 Rev.01
29.CPU module for Xe-identification CH 2 (69203DB1AA, UN 0660, AB13)
Place of unit : AB13
Diagram sheet : DE021 / YS710
Block 1 memory
Block 2 memory
Block 3 memory
Block 4 memory
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 52 of 109
Format no.: EDN 95-653-017 Rev.01
Direct memory access
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 53 of 109
Format no.: EDN 95-653-017 Rev.01
30.Interrupt Gen. Unit for Xe-identification CH –2 (69203GB2AA , UN 0661, AB17)
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 54 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 55 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 56 of 109
Format no.: EDN 95-653-017 Rev.01
31.Analog I/O module for Xe-identification CH 2(69203NA1AA,UN 0610, AB21)
Place of unit : AB21 Diagram sheet : DE021 / YS702
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 58 of 109
Format no.: EDN 95-653-017 Rev.01
33.V and I measuring module for Channel 3 ( 69203IA1AA , UNC 4660, U03)
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 59 of 109
Format no.: EDN 95-653-017 Rev.01
34.Digital Firing and control module for CH-3 (69203DU1CA, UN 0663, AE65)
Place of unit : AE65
Diagram sheet : DE040 / YS704
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 61 of 109
Format no.: EDN 95-653-017 Rev.01
Digital Firing and control module for CH-3 (69203DU1CA, UN 0663, AE65)
Signal settings
Measurements Testpoint
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 62 of 109
Format no.: EDN 95-653-017 Rev.01
Digital Firing and control module for CH-3 (69203DU1CA, UN 0663, AE65)
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 63 of 109
Format no.: EDN 95-653-017 Rev.01
Check whether output voltages are within tolerance when DC input is = OK /_____
220V + 10% and = 220V - 15%
OK BY
FUNCTION ELEMENT DE- FACTORY
TEST/COMMN
FLT SETTING
OK /____
Check the link position for
220VDC
OK /____
Contact pin X31 OUT
OK /____
Contact pin X32 IN
OK /____
Links (1302) OPEN
OK /____
(1303) OPEN
OK /____
Draw out the parallal unit and measure voltage of one unit at a time
after applying 220V DC at the input.
Measure input battery voltage at AP23/11-12
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 64 of 109
Format no.: EDN 95-653-017 Rev.01
Measure the output voltage at
OK BY
Output voltage Tolerance Testpoint
TEST/COMMN
24.03 DC /____
+24 +10% -5% N1/1 –N1/3
15.01 DC/____
+15 +/- 5% N1/7 –N1/3
-15.18 DC/____
-15 +/-5% N1/9 –N1/3
10.20 DC/____
+10 +/-10% N1/5 –N1/3
OK BY
FUNCTION ELEMENT DE- FACTORY
TEST/COMMN
FLT SETTING
OK /____
Check the link position for
220VDC
OK /____
Contact pin X31 OUT
OK /____
Contact pin X32 IN
OK /____
Links (1302) OPEN
OK /____
(1303) OPEN
OK /____
Draw out the parallal unit and measure voltage of one unit at a time
after applying 220V DC at the input.
Measure input battery voltage at AP/ 31-32
-15.18 DC/____
-15 +/-5% N1/9 –N1/3
10.21 DC/____
+10 +/-10% N1/5 –N1/3
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 65 of 109
Format no.: EDN 95-653-017 Rev.01
39.Pulse Final Pulse stage for Thy-1 (69203MU1BA, UN0809, AP20)
Place of unit : AP20
Diagram sheet : GX010 / YS701
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 66 of 109
Format no.: EDN 95-653-017 Rev.01
41.MicroTerminal ( 69203TB2AA , UNS 2660, AC45)
Diagram sheet : YD115
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 67 of 109
Format no.: EDN 95-653-017 Rev.01
46.List of Parameters for channel-1(Auto):
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 68 of 109
Format no.: EDN 95-653-017 Rev.01
List of Parameters for Auto channel-1:
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 69 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 70 of 109
Format no.: EDN 95-653-017 Rev.01
List of Parameters for channel-1(Auto)
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 71 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 72 of 109
Format no.: EDN 95-653-017 Rev.01
List of Parameters for channel-1 (Auto)
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 73 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 74 of 109
Format no.: EDN 95-653-017 Rev.01
List of Parameters for Auto channel-1
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 75 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 76 of 109
Format no.: EDN 95-653-017 Rev.01
2. Operation points
(Note: P & Q values in p.u.)
P < 0,6 Q < -0.2 C360 p111 0.55 C384 f111 0.14 OK /_____
P > 0,6 Q < -0.2 C362 p211 1.54 C386 f211 0.04 OK /_____
P < 0,6 -0.2 < Q < +0.2 C364 p121 1.5 C388 f121 0.10 OK /_____
P > 0,6 -0.2 < Q < +0.2 C366 p221 1.54 C38A f221 0.06 OK /_____
P < 0,6 Q > +0.2 C368 p131 2.68 C38C f131 0.11 OK /_____
P > 0,6 Q > +0.2 C36A p231 1.73 C38E f231 0.06 OK /_____
P < 0,6 Q < -0.2 C36C p112 1.69 C390 f112 0.05 OK /_____
P > 0,6 Q < -0.2 C36E p212 1.06 C392 f212 0.01 OK /_____
P < 0,6 -0.2 < Q < +0.2 C370 p122 1.38 C394 f122 0.05 OK /_____
P > 0,6 -0.2 < Q < +0.2 C372 p222 1.18 C396 f222 0.01 OK /_____
P < 0,6 Q > +0.2 C374 p132 2.09 C398 f132 0.06 OK /_____
P > 0,6 Q > +0.2 C376 p232 1.06 C39A f232 0.03 OK /_____
P < 0,6 Q < -0.2 C378 p113 1.22 C39C f113 0.01 OK /_____
P > 0,6 Q < -0.2 C37A p213 0.28 C39E f213 0.01 OK /_____
P < 0,6 -0.2 < Q < +0.2 C37C p123 0.87 C3A0 f123 0.06 OK /_____
P > 0,6 -0.2 < Q < +0.2 C37E p223 0.43 C3A2 f223 0.01 OK /_____
P < 0,6 Q > +0.2 C380 p133 0.63 C3A4 f133 0.01 OK /_____
P > 0,6 Q > +0.2 C382 p233 0.00 C3A6 f233 0.01 OK /_____
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 77 of 109
Format no.: EDN 95-653-017 Rev.01
48.List of Parameters for channel-2(Auto):
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 78 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 79 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 80 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 81 of 109
Format no.: EDN 95-653-017 Rev.01
List of Parameters for Auto channel-2
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 82 of 109
Format no.: EDN 95-653-017 Rev.01
List of Parameters for channel-2 (Auto)
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 83 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 84 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 85 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 86 of 109
Format no.: EDN 95-653-017 Rev.01
2. Operation points
(Note: P & Q values in p.u.)
P < 0,6 Q < -0.2 C360 p111 0.55 C384 f111 0.14 OK /_____
P > 0,6 Q < -0.2 C362 p211 1.54 C386 f211 0.04 OK /_____
P < 0,6 -0.2 < Q < +0.2 C364 p121 1.5 C388 f121 0.10 OK /_____
P > 0,6 -0.2 < Q < +0.2 C366 p221 1.54 C38A f221 0.06 OK /_____
P < 0,6 Q > +0.2 C368 p131 2.68 C38C f131 0.11 OK /_____
P > 0,6 Q > +0.2 C36A p231 1.73 C38E f231 0.06 OK /_____
P < 0,6 Q < -0.2 C36C p112 1.69 C390 f112 0.05 OK /_____
P > 0,6 Q < -0.2 C36E p212 1.06 C392 f212 0.01 OK /_____
P < 0,6 -0.2 < Q < +0.2 C370 p122 1.38 C394 f122 0.05 OK /_____
P > 0,6 -0.2 < Q < +0.2 C372 p222 1.18 C396 f222 0.01 OK _/_____
P < 0,6 Q > +0.2 C374 p132 2.09 C398 f132 0.06 OK /_____
P > 0,6 Q > +0.2 C376 p232 1.06 C39A f232 0.03 OK /_____
P < 0,6 Q < -0.2 C378 p113 1.22 C39C f113 0.01 OK /_____
P > 0,6 Q < -0.2 C37A p213 0.28 C39E f213 0.01 OK /_____
P < 0,6 -0.2 < Q < +0.2 C37C p123 0.87 C3A0 f123 0.06 OK /_____
P > 0,6 -0.2 < Q < +0.2 C37E p223 0.43 C3A2 f223 0.01 OK /_____
P < 0,6 Q > +0.2 C380 p133 0.63 C3A4 f133 0.01 OK /_____
P > 0,6 Q > +0.2 C382 p233 0.00 C3A6 f233 0.01 OK /_____
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 87 of 109
Format no.: EDN 95-653-017 Rev.01
50.AC and DC Power supply circuits
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 88 of 109
Format no.: EDN 95-653-017 Rev.01
52.Checking of transducers
1. Transducer for Exciter FIELD CURRENT indication.
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 89 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 90 of 109
Format no.: EDN 95-653-017 Rev.01
5. Transducer Control Voltage CH-1
Device reference : U56 (REG2)
Diagram sheet : CE410 / YS602
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 91 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 92 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 93 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 94 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 95 of 109
Format no.: EDN 95-653-017 Rev.01
Input : 0 to 872.95 MW
Output : 4 to 20mA
Keeping input voltage constant at 110V observe o/p by varying input current alone at
UPF.
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 96 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 97 of 109
Format no.: EDN 95-653-017 Rev.01
53.Light load test
a) Control characteristics
Vac = 220V, 3Ph, 400 Hz"
Load connected : 100 ohms; 5 Amps
Converter limit : 10 deg. Inverter limit : 170 deg.
Set UN 0663 of Manual Channel Switch S865 / 1 to Pos –1
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 98 of 109
Format no.: EDN 95-653-017 Rev.01
b) Instruments used:
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 99 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 100 of 109
Format no.: EDN 95-653-017 Rev.01
CT ratio 125/1 A
DC Current 126.5 A
Ambient Temperature 27
Humidity
3. Instrument details:
Sl.No. Instument used Instrument Sl.No. Make Used for
MT-73148778 Hameg
1 Oscilloscope Synchronisation
2 Digital Multi Meter Control voltage
3 Digital Multi Meter Milli volt across
shunt
4 Digital Multi Meter AC current
5 Digital Multi Meter AC voltage
MT-75021373 Digitherm
6 Thermometer Temperature
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 101 of 109
Format no.: EDN 95-653-017 Rev.01
4. Observations
Record the following readings one hour after passing the current, if only current sharing
test is to be done. In case Heat run test is also done, then record the readings at the end
of heat run test.
P5 of FS
127
4.3. mV drop across the fuses of the thyristors with all bridges in operation
4.4. mV drop across the fuses of the thyristors with ONE bridge in operation
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 102 of 109
Format no.: EDN 95-653-017 Rev.01
57.Heat Run Test (only on one set )
Connect the DC output of AVR to a resistive load of suitable rating or short so that
126.5A DC output current flows, by suitable injection of DC voltage to gate control circuit.
Select the channel for which the the test should be conducted. Close all cubicle doors.
Note down the temperature rise in the selected power group components after every half
an hour till the temperatures stabilise. Current shall be raised to ceiling current 187.3
Amps for 10Secs before stopping of heat run test. The temperatures shall be noted down
at the end of ceiling duration.
Temperature measurement
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 103 of 109
Format no.: EDN 95-653-017 Rev.01
3. OBSERVATIONS
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 104 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 105 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 106 of 109
Format no.: EDN 95-653-017 Rev.01
FUNCTION OK.BY
TEST/COMMN
Input Voltage = 220VDC OK/_____
Expected Output voltage+24 V +/- 10% (21.6V – 26.4) OK/_____
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 107 of 109
Format no.: EDN 95-653-017 Rev.01
43.5 13.136 145 4.70 V 13.14 5706 A 145.4 Deg
61.Line up test
Following logic sequences are to be checked tested as per the scheme by simulating the
fault conditions wherever applicable.
1 Field-breaker `ON'
a) Local OK/_____
b) Remote OK/_____
2 Field breaker `OFF'
OK/_____
a) Local
OK/_____
b) Remote
OK/_____
3 Lock out after tripping of F.B.(for 10 Secs)
4 Excitation ON OFF
OK/_____
a) Local
OK/_____
b) Remote
5 Channel Changeover
i) Local OK /_____
ii) Remote OK /_____
iii) Protective Channel Changeover OK _/_____
- Channel-1 to Channel-2 OK _/_____
- Channel-2 to Channel-1 OK /_____
- Channel-1 to Channel-3 OK _/_____
- Channel-2 to Channel-3 OK _/_____
6. Control of Channel-1, Channel-2 , Channel-3 for RAISE &
LOWER
OK /_____
a) Local
OK /_____
b) Remote
7. Pulse blocking of Channel-1, Channel-2 ,Channel-3
OK /_____
a) When Excitation goes off (With 5secs delay)
OK /_____
b) When Thyristor Input voltage <10%
8. Inverter operation after Excitation off
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 108 of 109
Format no.: EDN 95-653-017 Rev.01
a) Channel-1 _ OK /_____
b) Channel-2 OK /_____
c) Channel-3 OK /_____
OK /_____
9. Field breaker trip for all trip faults as per scheme
OK /_____
10. Auxiliary circuits and fault indication as per scheme
OK /_____
11. Operation of Potential free contacts as per scheme for remote
use
OK /_____
12. Follow up between any operating channel and standby
channel
Project : IB THERMAL POWER STATION - UNIT-3 – DAVR Test Report no.: 205/15/1192
W.B.S.Element : CE/1050-SH3-48-01 Page 109 of 109
Format no.: EDN 95-653-017 Rev.01
2 X 660 MW STG
OF
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 1 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 3 of 109
Format no.: EDN 95-653-017 Rev.01
27 CPU module for CH2 (69203DB1AA,UN0660,AB49) 48 150174880022
28 DC-DC supply module for CH2(69203PY2BA,AB37) 51 160174920051
29 CPU mod. for Xe-identification CH2 52 150174880029
(69203DB1AA,UN0660,AB13)
30 Interrupt Gen. Unit for Xe-identification CH2 54 160178970014
(69203GB1AA ,UN0661,AB17)
31 Analog I/O mod.for Xe-identification CH2 57 150158780104
(69203NA1AA,UN 0610,AB21)
32 Digital I/O mod.for Xe-identification CH2 58 160178960126
(69203NB1AA,UN0662,AB25)
33 V and I measuring module for CH3 59 160181770023
(69203IA1AA,UNC4660,U03)
34 Digital Firing & Control module for CH3 61 150177160014
(69203DU1CA,UN0663, AE65)
35 Pulse Intermediate stage amplifier for CH3 63 160180760037
(69143350,UN0096,AG21)
36 DC-DC supply module for CH3 64 150174920042
(69203PY2BA,AE37)
37 Pulse final stage power supply 64
(CE69132260,UN0901,AP07)
38 Pulse final stage power supply 65 160176040010
(CE69132260,UN0901,AP10)
39 Pulse Final stage amplifier for TY1 66 160180240020
(69203MU1BA,UN0809,AP20)
40 Pulse Final stage amplifier for TY2 66 150182240001
(69203MU1BA,UN0809,AP03)
41 MicroTerminal ( 69203TB2AA , UNS 2660, AC45 ) 67
42 Memory card ( 69203YV1BA , CT370, AG15) 67 150156730030
43 Memory card ( 69203YV1BA , CT370, AP15) 67 150156730006
44 Test point module (69138840, UN0094, AP23) 67 150158620033
45 Test point module (69138840, UN0094, AG23) 67 150160460001
46 List of Parameters for channel-1(Auto) AA49 68
47 Parameter list for Xe identification AA13 76
48 List of Parameters for channel-2(Auto) AB49 78
49 Parameter list for Xe identification AB13 86
50 AC and DC Power supply circuits 88
51 Tap setting of Transformers 88
52 Checking of Transducers 89
53 Light load test 98
54 Testing of Field-Breaker (Q1) 100
55 Current flow monitor – A31, A32 101
56 Current sharing in thyristor bridges 102
57 Heat run test 103
58 Checking of Local HMI 106
59 Checking of PSS10,PSF10,PSS11,PSF11 107
60 Rotor temp.measurment 107
61 Line up test 108
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 4 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 5 of 109
Format no.: EDN 95-653-017 Rev.01
R3M02 Digital input DII8P24 160178610141
R3M03 Digital input DII8P24 160178610144
R3M04 Digital output DOI4RO 160177590001
R3M05 Digital output DOI4RO 160177590014
R3M06 Digital output DOI4RO 160177590013
R3M07 Digital output DOI4RO 160177590029
R3M08 Digital output DOI4RO 160177590034
R3M09 Digital output DOI4RO 160177590030
R3M10 Digital input DII8P24 160178610146
R3M11 Digital output DOI4RO 160177590004
R3M12 Digital output DOI4RO 160177590036
R3M13 Digital output DOI4RO 160177590022
R3M14 Analog input AII8V 160180780157
R3M15 Analog input AII8V 160180780295
IPSP4 Power supply unit 160177980168
IBC4 Bus controller unit 160177810120
R4M00 Digital input DII8P24 160178610161
R4M01 Digital input DII8P24 160178610162
R4M02 Digital input DII8P24 160178610163
R4M03 Digital input DII8P24 160178610160
R4M04 Digital output DOI4RO 160177590050
R4M05 Digital output DOI4RO 160177590026
R4M06 Digital output DOI4RO 160177590010
R4M07 Digital output DOI4RO 160177590031
R4M08 Digital output DOI4RO 160177590041
R4M09 Digital output DOI4RO 160177590002
R4M10 Digital input DII8P24 160178610181
R4M11 Digital output DOI4RO 160177590043
R4M12 Digital output DOI4RO 160177590006
R4M13 Digital output DOI4RO 160177590025
R4M14 Analog input AII8V 160180780131
R4M15 Analog input AII8V 160180780272
IPSP5 Power supply unit 160177980165
IBC5 Bus controller unit 160177810108
R5M00 Digital input DII8P24 160178610192
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 6 of 109
Format no.: EDN 95-653-017 Rev.01
R5M01 Digital input DII8P24 160178610184
R5M02 Digital input DII8P24 160178610188
R5M03 Digital input DII8P24 160178610187
R5M04 Digital input DII8P24 160178610186
R5M05 Digital input DII8P24 160178610183
R5M06 Digital input DII8P24 160178610182
R5M07 Digital input DII8P24 160178610135
R5M08 Digital output DOI4RO 160177590032
R5M09 Digital output DOI4RO 160177590016
R5M10 Digital output DOI4RO 160177590012
R5M11 Digital output DOI4RO 160177590038
R5M12 Digital output DOI4RO 160177590027
R5M13 Digital output DOI4RO 160177590017
R5M14 Digital output DOI4RO 160177590011
R5M15 Digital output DOI4RO 160177590015
IPSP6 Power supply unit 160177980163
IBC6 Bus controller unit 160177810117
R6M00 Digital input DII8P24 160178610185
R6M01 Digital input DII8P24 160178610195
R6M02 Digital input DII8P24 160178610191
R6M03 Digital input DII8P24 160178610159
R6M04 Digital input DII8P24 160178610193
R6M05 Digital input DII8P24 160178610190
R6M06 Digital input DII8P24 160178610189
R6M07 Digital input DII8P24 160178610194
R6M08 Digital output DOI4RO 160177590009
R6M09 Digital output DOI4RO 160177590048
R6M10 Digital output DOI4RO 160177590023
R6M11 Digital output DOI4RO 160177590037
R6M12 Digital output DOI4RO 160177590003
R6M13 Digital output DOI4RO 160177590007
R6M14 Digital output DOI4RO 160177590035
R6M15 Digital output DOI4RO 160177590044
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 7 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 8 of 109
Format no.: EDN 95-653-017 Rev.01
11. Exciter Field Excitation requirement
i) No load field voltage Ufo VDC 20.1
ii) No load field current Ifo ADC 39.5
iii) Nominal field voltage Ufn VDC 58.4
iv) Nominal field current Ifn ADC 115
v) Max.cont.rated field voltage Ufmax VDC 58.4
vi) Max.cont.rated field current Ifmax ADC 115
vii) Ceiling voltage Ud VDC 95.2
viii) Ceiling current Id ADC 187.3
ix) Duration of field forcing - Sec. 10.0
12. Field test voltage - KVrms -
13. Synchronising slip - % -
14. AVR CT ratio - AAC AAC 24000/5
15. AVR PT ratio - VAC VAC 21000/110
16. Ambient - Deg.C 50
17. Altitude - meters 1000
18. Permanent Magnet Generator data
i) Rated output KVA 65
ii) Rated Voltage VAC 220
iii) Rated current AAC 195
iv) Rated Frequency Hz 400
2.Specification of Excitation Equipment :
Sl.No Description Unit Value
1 Accuracy of excitation control % ±0.5
2 Range of voltage control in Auto % 90 Ugn - 110 Ugn
3 Range of voltage control in Manual % 0 Ifo-105 Ifn
4 Range reactive current compensation % Up to 15
5 Frequency range of operation Hz 47-52
6 Total No.of THY.bridges No. 2
7 No. of redundant THY.bridges No. 1
8 Protection class - IP 32
9 Excitation equipment rating
a) Voltage VDC 58.4
b) Current ADC 115
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 9 of 109
Format no.: EDN 95-653-017 Rev.01
10 Range of PF regulation NA
11 Range of MVAR regulation NA
12 Station battery supply VDC 220
3.List of measurement and instruments :
SL.No Measurement Accuracy Instrument Equipment
1 a) AC Voltage(<1000V) ±1% Digital Voltmeter to be
used for PT, FB, AC
voltages and AC Input to
Electronic Power supplies
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 10 of 109
Format no.: EDN 95-653-017 Rev.01
NOTE: Least count of the above instruments equipments shall be adequate for reading
measuring the parameters with its specified tolerance (as given in the test instruction
report)
PROGRAMMING SETTINGS
Legend:
A Connection point(solder pin).
R1 Resistor on soldering pins (setting element)
1 Programming link between soldering pins
S,X,J Programming link, plug, jumper
Resistors:
1) 0.25W 2%
2) 0.25W 0.25%
3) 2W 2%
4) 6W 5%
5) 1W 2%
6) 5W 5%
Capacitors:
7) Tantal Elco 33 micro Farad, 35V
ADVISE TO TEST AND COMMISSIONING STAFF:
EVERY BOX “_____ ” IN THE TEST REPORT HAS TO BE FILLED OUT WITH “OK”
OR “VALUE” OR “NA”(Not applicable).
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 11 of 109
Format no.: EDN 95-653-017 Rev.01
4. Insulation Resistance & HV Test
Instruments used Range Make Sl.No.
Megger 500V/1000V Shanti MT-72677223
HV test set 0-5KV AEL MT-72262906
Details of voltage groups:
Ambient Temperature 26
Humidity 53
Date 15.09.2016
Time 4:25PM
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 12 of 109
Format no.: EDN 95-653-017 Rev.01
5.Metso module settings
General :
1. Check switch setting on MBM120 and MBI8 mounting boards as per the scheme.
2. Power supply connectors to ACNCS, MBM120 and MBI8 modules to be plugged in as per the
Scheme.
3. Insert the corresponding 16 ,10 or 8 pin connector in each input/output module.
OK
RACK 2 S1=1 S2=9 S1=0 S1=4
OK
RACK 3 S1=2 S2=0 S1=0 S1=4
OK
RACK 4 S1=3 S2=9 S1=0 S1=4
OK
RACK 5 S1=4 S2=0 S1=0 S1=4
OK
RACK 6 S1=5 S2=9 S1=0 S1=4
IBC Settings
OK
RACK 2 2,4,5,6 = ON 1,3,7,8 = OFF
OK
RACK 3 2,4,5,6 = ON 1,3,7,8 = OFF
OK
RACK 4 2,4,5,6 = ON 1,3,7,8 = OFF
OK
RACK 5 2,4,5,6 = ON 1,3,7,8 = OFF
OK
RACK 6 2,4,5,6 = ON 1,3,7,8 = OFF
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 13 of 109
Format no.: EDN 95-653-017 Rev.01
6.MCB Settings :
Regulation Over load release Range Recomended Factory
cubicle setting setting/TEST
OK
F56,F57 25A Fixed
OK
F51,F52,F55,F81, 1.6-2.5A 2.5A
F82,F83,F84,F54,
F55
OK
F65.1,F65.2 2.5A-4A 3A
OK
F78,F79,F80 0.63 -1A 0.8A
OK
F70,F71 9-12.5A 12A
OK
F91 9-12.5A 12A
OK
F74 9-12.5A 12A
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 14 of 109
Format no.: EDN 95-653-017 Rev.01
7.V and I measuring module for Channel 1 ( 69203IA1AA , UNC 4660, U01)
Place of unit : U01
Diagram sheet : DE010 / YS601/602
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 15 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 17 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 18 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 19 of 109
Format no.: EDN 95-653-017 Rev.01
9.Analog Input/Output module for CH 1 ( ED 69203NA1AA, UN 0610, AA57)
Place of unit : AA57 Diagram sheet : DE010 / YS702
10. Digital input / output module for Channel 1 (69203NB1AA, UN 0662, AA61)
Place of unit : AA61
Diagram sheet : DE010 / YS703
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 21 of 109
Format no.: EDN 95-653-017 Rev.01
11.Digital inputoutput module for Channel 1 (69203NB1AA, UN 0662, AA69)
Place of unit : AA69
Diagram sheet : DE010 / YS706
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 22 of 109
Format no.: EDN 95-653-017 Rev.01
12.Digital Firing and control module for CH-1 (69203DU1CA, UN 0663, AA65)
Place of unit : AA65
Diagram sheet : DE010 / YS704
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 23 of 109
Format no.: EDN 95-653-017 Rev.01
Digital Firing and control module for CH-1 (69203DU1CA, UN 0663, AA65)
Signal settings
Measurements Testpoint
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 24 of 109
Format no.: EDN 95-653-017 Rev.01
Digital Firing and control module for CH-1 (69203DU1CA, UN 0663, AA65)
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 25 of 109
Format no.: EDN 95-653-017 Rev.01
Block 1 memory
Block 2 memory
Block 3 memory
Block 4 memory *
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 26 of 109
Format no.: EDN 95-653-017 Rev.01
CPU module for channel 1 (69203DB1AA, UN 0660, AA49)
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 27 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 28 of 109
Format no.: EDN 95-653-017 Rev.01
15.DC-DC supply module for channel 1 (69203PY2BA, AA37)
Place of unit : AA37
Diagram sheet : DE010 / YS710
Check whether output voltages are within tolerance when DC input is = OK /_____
220V + 10% and = 220V - 15%
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 29 of 109
Format no.: EDN 95-653-017 Rev.01
16.CPU module for Xe-identification channel 1 (69203DB1AA, UN 0660, AA13)
Place of unit : AA13
Diagram sheet : DE011 / YS710
Block 1 memory
Block 2 memory
Block 3 memory
Block 4 memory
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 30 of 109
Format no.: EDN 95-653-017 Rev.01
Direct memory access
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 31 of 109
Format no.: EDN 95-653-017 Rev.01
17.Interrupt Gen. Unit for Xe-identification Ch-1 (69203GB2AA , UN 0661, AA17)
Place of unit : AA17
Diagram sheet : DE011 / YS701
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 32 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 33 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 34 of 109
Format no.: EDN 95-653-017 Rev.01
18. Analog I/O module Xe-identification CH 1 (ED69203NA1AA,UN0610, AA21)
Place of unit : AA21 Diagram sheet : DE011 / YS702
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 36 of 109
Format no.: EDN 95-653-017 Rev.01
20.V and I measuring module for Channel 2 ( 69203IA1AA , UNC 4660, U02)
Place of unit : U02
Diagram sheet : DE020 / YS601, 602
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 37 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 39 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 40 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 41 of 109
Format no.: EDN 95-653-017 Rev.01
22.Analog Input/Output module for Channel 2(ED69203NA1AA,UN0610, AB57)
Place of unit : AB57 Diagram sheet : DE020 / YS702
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 43 of 109
Format no.: EDN 95-653-017 Rev.01
24.Digital inputoutput module for Channel 2 (69203NB1AA, UN 0662, AB69)
Place of unit : AB69
Diagram sheet : DE020 / YS706
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 44 of 109
Format no.: EDN 95-653-017 Rev.01
25.Digital Firing and control module for CH-2 (69203DU1CA, UN 0663, AB65)
Place of unit : AB65
Diagram sheet : DE020 / YS704
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 45 of 109
Format no.: EDN 95-653-017 Rev.01
Digital Firing and control module for CH-2 (69203DU1CA, UN 0663, AB65)
Signal settings
Measurements Testpoint
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 46 of 109
Format no.: EDN 95-653-017 Rev.01
Digital Firing and control module for CH-2 (69203DU1BA, UN 0663, AB65)
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 47 of 109
Format no.: EDN 95-653-017 Rev.01
27.CPU module for channel 2 (69203DB1AA, UN 0660, AB49)
Place of unit : AB49
Diagram sheet : DE020 / YS710
Block 1 memory
Block 2 memory
Block 3 memory
Block 4 memory
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 48 of 109
Format no.: EDN 95-653-017 Rev.01
CPU module for channel 2 (69203DB1AA, UN 0660, AB49)
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 49 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 50 of 109
Format no.: EDN 95-653-017 Rev.01
Check whether output voltages are within tolerance when DC input is = OK /_____
220V + 10% and = 220V - 15%
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 51 of 109
Format no.: EDN 95-653-017 Rev.01
29.CPU module for Xe-identification CH 2 (69203DB1AA, UN 0660, AB13)
Place of unit : AB13
Diagram sheet : DE021 / YS710
Block 1 memory
Block 2 memory
Block 3 memory
Block 4 memory
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 52 of 109
Format no.: EDN 95-653-017 Rev.01
Direct memory access
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 53 of 109
Format no.: EDN 95-653-017 Rev.01
30.Interrupt Gen. Unit for Xe-identification CH –2 (69203GB2AA , UN 0661, AB17)
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 54 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 55 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 56 of 109
Format no.: EDN 95-653-017 Rev.01
31.Analog I/O module for Xe-identification CH 2(69203NA1AA,UN 0610, AB21)
Place of unit : AB21 Diagram sheet : DE021 / YS702
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 58 of 109
Format no.: EDN 95-653-017 Rev.01
33.V and I measuring module for Channel 3 ( 69203IA1AA , UNC 4660, U03)
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 59 of 109
Format no.: EDN 95-653-017 Rev.01
34.Digital Firing and control module for CH-3 (69203DU1CA, UN 0663, AE65)
Place of unit : AE65
Diagram sheet : DE040 / YS704
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 61 of 109
Format no.: EDN 95-653-017 Rev.01
Digital Firing and control module for CH-3 (69203DU1CA, UN 0663, AE65)
Signal settings
Measurements Testpoint
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 62 of 109
Format no.: EDN 95-653-017 Rev.01
Digital Firing and control module for CH-3 (69203DU1CA, UN 0663, AE65)
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 63 of 109
Format no.: EDN 95-653-017 Rev.01
Check whether output voltages are within tolerance when DC input is = OK /_____
220V + 10% and = 220V - 15%
OK BY
FUNCTION ELEMENT DE- FACTORY
TEST/COMMN
FLT SETTING
OK /____
Check the link position for
220VDC
OK /____
Contact pin X31 OUT
OK /____
Contact pin X32 IN
OK /____
Links (1302) OPEN
OK /____
(1303) OPEN
OK /____
Draw out the parallal unit and measure voltage of one unit at a time
after applying 220V DC at the input.
Measure input battery voltage at AP23/11-12 220VDC
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 64 of 109
Format no.: EDN 95-653-017 Rev.01
Measure the output voltage at
OK BY
Output voltage Tolerance Testpoint
TEST/COMMN
24.0 DC /____
+24 +10% -5% N1/1 –N1/3
15.00 DC/____
+15 +/- 5% N1/7 –N1/3
-15.0 DC/____
-15 +/-5% N1/9 –N1/3
10.0 DC/____
+10 +/-10% N1/5 –N1/3
OK BY
FUNCTION ELEMENT DE- FACTORY
TEST/COMMN
FLT SETTING
OK /____
Check the link position for
220VDC
OK /____
Contact pin X31 OUT
OK /____
Contact pin X32 IN
OK /____
Links (1302) OPEN
OK /____
(1303) OPEN
OK /____
Draw out the parallal unit and measure voltage of one unit at a time
after applying 220V DC at the input.
Measure input battery voltage at AP/ 31-32 220VDC
-15.0 DC/____
-15 +/-5% N1/9 –N1/3
10.0 DC/____
+10 +/-10% N1/5 –N1/3
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 65 of 109
Format no.: EDN 95-653-017 Rev.01
39.Pulse Final Pulse stage for Thy-1 (69203MU1BA, UN0809, AP20)
Place of unit : AP20
Diagram sheet : GX010 / YS701
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 66 of 109
Format no.: EDN 95-653-017 Rev.01
41.MicroTerminal ( 69203TB2AA , UNS 2660, AC45)
Diagram sheet : YD115
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 67 of 109
Format no.: EDN 95-653-017 Rev.01
46.List of Parameters for channel-1(Auto):
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 68 of 109
Format no.: EDN 95-653-017 Rev.01
List of Parameters for Auto channel-1:
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 69 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 70 of 109
Format no.: EDN 95-653-017 Rev.01
List of Parameters for channel-1(Auto)
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 71 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 72 of 109
Format no.: EDN 95-653-017 Rev.01
List of Parameters for channel-1 (Auto)
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 73 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 74 of 109
Format no.: EDN 95-653-017 Rev.01
List of Parameters for Auto channel-1
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 75 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 76 of 109
Format no.: EDN 95-653-017 Rev.01
2. Operation points
(Note: P & Q values in p.u.)
P < 0,6 Q < -0.2 C360 p111 0.55 C384 f111 0.14 OK /_____
P > 0,6 Q < -0.2 C362 p211 1.54 C386 f211 0.04 OK /_____
P < 0,6 -0.2 < Q < +0.2 C364 p121 1.5 C388 f121 0.10 OK /_____
P > 0,6 -0.2 < Q < +0.2 C366 p221 1.54 C38A f221 0.06 OK /_____
P < 0,6 Q > +0.2 C368 p131 2.68 C38C f131 0.11 OK /_____
P > 0,6 Q > +0.2 C36A p231 1.73 C38E f231 0.06 OK /_____
P < 0,6 Q < -0.2 C36C p112 1.69 C390 f112 0.05 OK /_____
P > 0,6 Q < -0.2 C36E p212 1.06 C392 f212 0.01 OK /_____
P < 0,6 -0.2 < Q < +0.2 C370 p122 1.38 C394 f122 0.05 OK /_____
P > 0,6 -0.2 < Q < +0.2 C372 p222 1.18 C396 f222 0.01 OK /_____
P < 0,6 Q > +0.2 C374 p132 2.09 C398 f132 0.06 OK /_____
P > 0,6 Q > +0.2 C376 p232 1.06 C39A f232 0.03 OK /_____
P < 0,6 Q < -0.2 C378 p113 1.22 C39C f113 0.01 OK /_____
P > 0,6 Q < -0.2 C37A p213 0.28 C39E f213 0.01 OK /_____
P < 0,6 -0.2 < Q < +0.2 C37C p123 0.87 C3A0 f123 0.06 OK /_____
P > 0,6 -0.2 < Q < +0.2 C37E p223 0.43 C3A2 f223 0.01 OK /_____
P < 0,6 Q > +0.2 C380 p133 0.63 C3A4 f133 0.01 OK /_____
P > 0,6 Q > +0.2 C382 p233 0.00 C3A6 f233 0.01 OK /_____
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 77 of 109
Format no.: EDN 95-653-017 Rev.01
48.List of Parameters for channel-2(Auto):
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 78 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 79 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 80 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 81 of 109
Format no.: EDN 95-653-017 Rev.01
List of Parameters for Auto channel-2
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 82 of 109
Format no.: EDN 95-653-017 Rev.01
List of Parameters for channel-2 (Auto)
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 83 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 84 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 85 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 86 of 109
Format no.: EDN 95-653-017 Rev.01
2. Operation points
(Note: P & Q values in p.u.)
P < 0,6 Q < -0.2 C360 p111 0.55 C384 f111 0.14 OK /_____
P > 0,6 Q < -0.2 C362 p211 1.54 C386 f211 0.04 OK /_____
P < 0,6 -0.2 < Q < +0.2 C364 p121 1.5 C388 f121 0.10 OK /_____
P > 0,6 -0.2 < Q < +0.2 C366 p221 1.54 C38A f221 0.06 OK /_____
P < 0,6 Q > +0.2 C368 p131 2.68 C38C f131 0.11 OK /_____
P > 0,6 Q > +0.2 C36A p231 1.73 C38E f231 0.06 OK /_____
P < 0,6 Q < -0.2 C36C p112 1.69 C390 f112 0.05 OK /_____
P > 0,6 Q < -0.2 C36E p212 1.06 C392 f212 0.01 OK /_____
P < 0,6 -0.2 < Q < +0.2 C370 p122 1.38 C394 f122 0.05 OK /_____
P > 0,6 -0.2 < Q < +0.2 C372 p222 1.18 C396 f222 0.01 OK _/_____
P < 0,6 Q > +0.2 C374 p132 2.09 C398 f132 0.06 OK /_____
P > 0,6 Q > +0.2 C376 p232 1.06 C39A f232 0.03 OK /_____
P < 0,6 Q < -0.2 C378 p113 1.22 C39C f113 0.01 OK /_____
P > 0,6 Q < -0.2 C37A p213 0.28 C39E f213 0.01 OK /_____
P < 0,6 -0.2 < Q < +0.2 C37C p123 0.87 C3A0 f123 0.06 OK /_____
P > 0,6 -0.2 < Q < +0.2 C37E p223 0.43 C3A2 f223 0.01 OK /_____
P < 0,6 Q > +0.2 C380 p133 0.63 C3A4 f133 0.01 OK /_____
P > 0,6 Q > +0.2 C382 p233 0.00 C3A6 f233 0.01 OK /_____
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 87 of 109
Format no.: EDN 95-653-017 Rev.01
50.AC and DC Power supply circuits
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 88 of 109
Format no.: EDN 95-653-017 Rev.01
52.Checking of transducers
1. Transducer for Exciter FIELD CURRENT indication.
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 89 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 90 of 109
Format no.: EDN 95-653-017 Rev.01
5. Transducer Control Voltage CH-1
Device reference : U56 (REG2)
Diagram sheet : CE410 / YS602
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 91 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 92 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 93 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 94 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 95 of 109
Format no.: EDN 95-653-017 Rev.01
Input : 0 to 872.95 MW
Output : 4 to 20mA
Keeping input voltage constant at 110V observe o/p by varying input current alone at
UPF.
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 96 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 97 of 109
Format no.: EDN 95-653-017 Rev.01
53.Light load test
a) Control characteristics
Vac = 220V, 3Ph, 400 Hz"
Load connected : 100 ohms; 5 Amps
Converter limit : 10 deg. Inverter limit : 170 deg.
Set UN 0663 of Manual Channel Switch S865 / 1 to Pos –1
1 -3 0.2 0.4
2 -2 1.5 1.5
3 -1 10.17 11
4 0 21 22
5 1 31.2 32
6 2 43.5 44
7 3 61.5 62
8 4 89.9 91
9 5 120 122
10 6 149.5 150
11 7 179.24 180
12 8 211.5 212
13 9.0 246.75 251
14 Max 259 263
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 98 of 109
Format no.: EDN 95-653-017 Rev.01
b) Instruments used:
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 99 of 109
Format no.: EDN 95-653-017 Rev.01
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 100 of 109
Format no.: EDN 95-653-017 Rev.01
CT ratio 125/1 A
DC Current 126.5 A
Ambient Temperature 25
Humidity 52
3. Instrument details:
Sl.No. Instument used Instrument Sl.No. Make Used for
MT-73148782 Hameg
1 Oscilloscope Synchronisation
MT-73657737 AGILENT
2 Digital Multi Meter Control voltage
MT-73651746 RISH
3 Digital Multi Meter Milli volt across
shunt
MT-73657737 AGILENT
4 Digital Multi Meter AC current
MT-73651746 RISH
5 Digital Multi Meter AC voltage
6 Thermometer Temperature
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 101 of 109
Format no.: EDN 95-653-017 Rev.01
4. Observations
Record the following readings one hour after passing the current, if only current sharing
test is to be done. In case Heat run test is also done, then record the readings at the end
of heat run test.
P5 of FS
126.6
4.3. mV drop across the fuses of the thyristors with all bridges in operation
4.4. mV drop across the fuses of the thyristors with ONE bridge in operation
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 102 of 109
Format no.: EDN 95-653-017 Rev.01
57.Heat Run Test (only on one set ) (Not applicable for this unit)
Connect the DC output of AVR to a resistive load of suitable rating or short so that
126.5A DC output current flows, by suitable injection of DC voltage to gate control circuit.
Select the channel for which the the test should be conducted. Close all cubicle doors.
Note down the temperature rise in the selected power group components after every half
an hour till the temperatures stabilise. Current shall be raised to ceiling current 187.3
Amps for 10Secs before stopping of heat run test. The temperatures shall be noted down
at the end of ceiling duration.
Temperature measurement
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 103 of 109
Format no.: EDN 95-653-017 Rev.01
3. OBSERVATIONS
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 104 of 109
Format no.: EDN 95-653-017 Rev.01
Temperature (deg C) with one Bridge in operation (TY1 – Off)
Time QA c c c c c c c c c c c c c
Amb Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8 Q9 Q10 Q11 Q12 Q13
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 105 of 109
Format no.: EDN 95-653-017 Rev.01
58. Checking of Local HMI
A) HMI details :
1. Supplier -
2. System Make / Model ADVANTEC
_
3. System serial no.:
_
4. Product key Number .
5. No. of spare USB ports 5
B) Functional checks :
1. Check the proper operation of all spare USB ports OK
2. Check proper functioning of withdrawable type key board OK
3. Check proper functioning of Touch screen monitor OK
4. Ensure proper loading of MetsoDNA software OK
5. Ensure proper Flashing of ACNCS : OK
6. DACNCS -SEE package Name : DP90M & DP90R
PControl room name : D1
U
Alarm Group / Alarm area : __D1A1____
ACNCS address :
Node Token HW address XD_HW-BUS
Main - ACNCS DP90M 49 5621
Reserve - DP90R 50 5641
ACNCS
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 106 of 109
Format no.: EDN 95-653-017 Rev.01
59.Checking of PSS10, PSS11,PSF10&PSF11
Device Reference : PSS10,PSS11,PSF10,PSF11
Diagram sheet : GW030 / YS005
FUNCTION OK.BY
TEST/COMMN
Input Voltage = 220VDC OK/_____
Expected Output voltage+24 V +/- 10% (21.6V – 26.4) OK/_____
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 107 of 109
Format no.: EDN 95-653-017 Rev.01
61.Line up test
Following logic sequences are to be checked tested as per the scheme by simulating the
fault conditions wherever applicable.
1 Field-breaker `ON'
a) Local OK/_____
b) Remote OK/_____
2 Field breaker `OFF'
OK/_____
a) Local
OK/_____
b) Remote
OK/_____
3 Lock out after tripping of F.B.(for 10 Secs)
4 Excitation ON OFF
OK/_____
a) Local
OK/_____
b) Remote
5 Channel Changeover
i) Local OK /_____
ii) Remote OK /_____
iii) Protective Channel Changeover OK _/_____
- Channel-1 to Channel-2 OK _/_____
- Channel-2 to Channel-1 OK /_____
- Channel-1 to Channel-3 OK _/_____
- Channel-2 to Channel-3 OK _/_____
6. Control of Channel-1, Channel-2 , Channel-3 for RAISE &
LOWER
OK /_____
a) Local
OK /_____
b) Remote
7. Pulse blocking of Channel-1, Channel-2 ,Channel-3
OK /_____
a) When Excitation goes off (With 5secs delay)
OK /_____
b) When Thyristor Input voltage <10%
8. Inverter operation after Excitation off
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 108 of 109
Format no.: EDN 95-653-017 Rev.01
a) Channel-1 _ OK /_____
b) Channel-2 OK /_____
c) Channel-3 OK /_____
OK /_____
9. Field breaker trip for all trip faults as per scheme
OK /_____
10. Auxiliary circuits and fault indication as per scheme
OK /_____
11. Operation of Potential free contacts as per scheme for remote
use
OK /_____
12. Follow up between any operating channel and standby
channel
Project : IB THERMAL POWER STATION - UNIT-4 – DAVR Test Report no.: 205/16/451
W.B.S.Element : CE/1050-SH4-48-01 Page 109 of 109