Structural Wind load Calculation as per ASCE

Wind Pressure = qz = 0.613 x Kz x Kzt x Kd x V2 x I = 1480.66916 N/m^2

Kz= 1 (Velocity Pressure Exposure Coefficient for Exposure C given in Table 6-2))
Kzt = 1 (Topographical Factor)
Kd = 1 (Directional Factor)
V= 45.83 m/s (Wind Speed)
I= 1.15 (Importance Factor for Ocupance Category III)

Wind load along X - direction

Length of the structure, L = = 6.5 m


Breadth of the structure, B = = 6.5 m
Height of the structure, h = = 3 m
(up to piping)
Wind force = Wind pressure x area = 28.87 kN
Wind force at X direction = = 1.44 kN/m
Load / member running meter

Wind load along Z - direction

Length of the structure, L = = 4 m


Breadth of the structure, B = = 2.3 m
Height of the structure, h = = 3 m
(up to piping)
Wind force = Wind pressure x area = 17.77 kN
Wind force at Z direction = = 0.89 kN/m
Load / member running meter