www.hilti-me.com Hilti PROFIS Rebar 2.4.

12
Company: Page: 1
Specifier: Project:
Address: Fastening point:
Phone | Fax: | Date: 12/03/2019
E-Mail:
Specifiers comments:

Design standard: HIT Rebar Design


Application type: All applications/Beam to column

1. Loads 2. Drilling & Temperature 3. Material & Safety

Loads Drilling Structure


Md 0.00 kNm Hole Dry Concrete class (existing C30/37
condition structure)
Nd 0.00 kN
Drilling Hammer Char. yield strength (existing) 500 N/mm²
Vd 60.0 kN method drilling Char. yield strength (new) 500 N/mm²
Fire design Drilling aid Drilling aid is Cracks
used
Fire rating None Cracks along parallel No
Temperature (HIT Rebar Design)
Fatigue design member top side
During from 5 °C to
None Cracks along parallel No
installation 40 °C member bottom side
Seismic During 20 °C / 20 °C
Seismic loads No service

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Rebar ( c ) 2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Hilti PROFIS Rebar 2.4.12
Company: Page: 2
Specifier: Project:
Address: Fastening point:
Phone | Fax: | Date: 12/03/2019
E-Mail:

4. Eurocode 2 parameters 5. Post-installed reinforcement

αcc 1.00 EC2 3.1.6(1) Number of layers


αct 1.00 EC2 3.1.6(2) Number of top layers 1.00
Number of bottom layers 1.00
αct,bond 1.00
Top reinforcements parameters
εud 0.0200 Table C.1
Top diameter 16.0 mm
k2 0.850 EC2 6.5.4(4b) Top spacing 114 mm
ν' 0.880 EC2 6.5.2(2) Top layer 1: c 50.0 mm
ρmax 0.0400 EC2 9.2.1.1 Top layer 1: cd (EC2, 8.4.4.1) 35.0 mm
εc2 -3 Table 3.1
2.00•10 Top bond condition Good
εc2u 3.50•10 -3 Table 3.1 Top min. reinforcement 100 mm²/m
Bottom reinforcements parameters
Bottom diameter 16.0 mm
Bottom spacing 114 mm
Bottom layer 1: c 50.0 mm
Bottom layer 1: cd (EC2, 35.0 mm
8.4.4.1)
Bottom bond condition Good
Bottom min. reinforcement 100 mm²/m
Other
Transverse pressure 0.00 N/mm²
Cover of tension force line b 0.00 mm

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Rebar ( c ) 2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Hilti PROFIS Rebar 2.4.12
Company: Page: 3
Specifier: Project:
Address: Fastening point:
Phone | Fax: | Date: 12/03/2019
E-Mail:
Selected solution
Bar size Drill bit size Bar spacing Distance Drilled hole Anchorage for
centre/centre centre/surface required yield of bar
Layer of bars Φ [mm] D [mm] s [mm] cs [mm] ℓvreq [mm] ℓvy [mm]
Top / left 1 16.0 20.0 114 3,058 174 N/A
Bottom / right 1 16.0 20.0 114 3,058 204 476

Required accessories

Drilling Cleaning Setting


- Suitable rotary hammer - Compressed air with required accessories to - Dispenser including cassette and mixer
- Properly sized drill bit blow from the bottom of the hole - For deep installations, a piston plug is
- Proper diameter wire brush necessary

Section Analysis

Strut angle θ 21.8 ° EC2 6.2.3


Inner lever arm z1 284 mm
Compressive reinforcement required? no

Upper layer
Design Input

Design force in bar FE 0.00 kN EC2 9.2.1.4(2)


Stress in bars σsd = FE/As,prov 0.00 N/mm²
Adhesive used Hilti HIT-RE 500 V3

Minimum Anchorage Length

Basic anchorage length (Fyd) lb,rqd,fyd = (Φ/4)•(fyd/fbd) 580 mm EC2 8.4.3

Factor for minimum length fmult,min 1.00 ETA 16/0142


Minimum anchorage length lb,min = fmult,min•max(0.3lb,rqd,fyd; 10Φ; 100 mm) 174 mm EC2 and
German
Nationaler
Anhang

Installation length linst = lbd 174 mm

Lower layer (tension side)


Design Input

Design force in bar FE 37.5 kN EC2 9.2.1.4(2)


Stress in bars σsd = FE/As,prov 187 N/mm²
Adhesive used Hilti HIT-RE 500 V3

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Rebar ( c ) 2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Hilti PROFIS Rebar 2.4.12
Company: Page: 4
Specifier: Project:
Address: Fastening point:
Phone | Fax: | Date: 12/03/2019
E-Mail:

Anchorage Post-Installed Reinforcement

Bond condition Good → η1 1.00 EC2 8.4.3(2)


Bond strength fbd,pi 3.00 N/mm² ETA 16/0142
Basic anchorage length lb,rqd = (Φ/4)•(σsd/fbd,pi) 249 mm
Basic anchorage length (Fyd) lb,rqd,fyd = (Φ/4)•(fyd/fbd,pi) 580 mm

Factor for minimum length fmult,min 1.00


Minimum anchorage length lb,min = fmult,min•max(0.3lb,rqd,fyd; 10Φ; 100 mm) 174 mm EC2 8.4.4(1)
and German
Nationaler
Anhang
Min of clear cover or half spacing cd 35.0 mm ≤ 3Φ EC2
8.4.4(1)

Influence cover/spacing α2 = {0.7 ≤ 1-0.15[(cd-Φ)/Φ] ≤ 1.0} 0.822

Transverse reinforcement ∑Ast = Φt2•π/4 • (1+0.7•lb,rqd/st) 0.00 mm²


Min. transverse reinforcement ∑Ast,min = (EN 1992-1-1, table 8.2) 50.3 mm²
K-factor K = (EN 1992-1-1, table 8.2) 0.0500
Influence of transv. reinf. 2 1.00 EC2 8.4.4(1)
α3 = {0.7 ≤ 1-K(∑Ast-∑Ast,min)/(Φ π/4)≤ 1.0}

Transverse pressure p 0.00 N/mm²


Influence of transv. pressure α5 = {0.7 ≤ 1-0.04p ≤ 1.0} 1.00

Total influence factor α = {α2•α3•α5 ≥ 0.7} 0.822

Splitting bond strength fbd,spl = fbd,pi/α 3.65 N/mm²


Pullout bond strength fbd,po 9.71 N/mm² ETA 16/0143
Controlling bond strength fbd = max(fbd,pi/α2; min(fbd,spl; fbd,po)) 3.65 N/mm²

Design anchorage length lbd = max[(Φ/4)•(σsd/fbd); lb,min] 204 mm

Definition of the installation length

Controlling anchorage length lbd 204 mm

Installation length linst = lbd 204 mm

Remarks
This design exclusively considers the local load transfer from the post-installed tensile reinforcement at the intersection between new and
existing concrete. The joint surfaces for concreting must be roughened to at least such an extent that aggregates protrude. It assumes that
adequate transverse reinforcement is provided in the anchorage area if required.
The shear load carrying capacity of the cross section has to be designed separately.
The HIT Rebar Design is used in this calculation evaluates solely the strength of the connection; serviceability criteria are not considered.
Indications on displacements and creep of post-installed rebars can be found in the European Technical Approvals for anchors. The Installation
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Rebar ( c ) 2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Hilti PROFIS Rebar 2.4.12
Company: Page: 5
Specifier: Project:
Address: Fastening point:
Phone | Fax: | Date: 12/03/2019
E-Mail:
(drilling, cleaning, setting) must be according to the approval!
Fixed diameter and spacing selected. Please be aware that over-reinforcement of the section may lead to brittle failure of the fastening.
The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to be
followed to ensure a proper installation.
Minimum reinforcement requirements are not checked by the software.

Input data and results must be checked for agreement with the existing conditions and for plausibility!