MAN Diesel & Turbo Doc. No.: 11.

99233-2076

Power Plants
(PDS: 0)

Project: 5301959 Nababganj, Bangladesh


Document Code: FA 0
Doc. No.: 11.99233-2076
Revision: D in work
Issued by: PEA
N. Gaikwad, 28.04.2015

MAN Diesel & Turbo - Stadtbachstr. 1 / D-86224 Augsburg / Germany

5301959 FA 0 SCADA+ PLC Architecture (Rev. D in work).vsd 1/9


Copyright © MAN Diesel & Turbo SE
All rights reserved, including reprinting in whole or in part, photomechanical reproductions (photocopy / microcopy) in part or in full and
translation thereof.
I Revision History

Rev. Written Checked Released Release date Status/Edition Issued for Remarks
Commitment/
D N. Gaikwad T. Herzog T. Herzog 28.04.2015 Third ..........
Agreement
C N. Gaikwad T. Herzog T. Herzog 23.01.2015 Second Comment ..........
B T. Herzog R. Meier
T. Herzog 18.06.2014 First Inquiry ..........
H.
A T.T.Win R.Braunmüller 06.05.2013 Preliminary Clarification ..........
Berchtenbreiter
0 R.Braunmüller P.Bulbule 26.03.2012 Preliminary Clarification ..........

5301959 FA 0 SCADA+ PLC Architecture (Rev. D in work).vsd 2/9


Copyright © MAN Diesel & Turbo SE
All rights reserved, including reprinting in whole or in part, photomechanical reproductions (photocopy / microcopy) in part or in full and
translation thereof.
II Legend

Remarks
Several units
*
l Only on last ET200M
n Number depending on plant design
o Optional
g Not applicable for pure gas operation
Connections
Copper Profibus
Copper Profibus (primary ring)
Copper Profibus (secondary ring)
Copper Ethernet
Copper hardwired
Fibre Optic Ethernet
Fibre Optic Profibus (primary ring)
Fibre Optic Profibus (secondary ring)
CAN-Bus
MODBUS
RS 422 (RK512)
RS 232
Geographical stripline
Hardwired connections (Control, Power)

5301959 FA 0 SCADA+ PLC Architecture (Rev. D in work).vsd 3/9


Copyright © MAN Diesel & Turbo SE
All rights reserved, including reprinting in whole or in part, photomechanical reproductions (photocopy / microcopy) in part or in full and
translation thereof.
III Abbrevations

Boiler Auxiliary Panel


BAP
ET200M, OLM, MMU
Turbine Control Panel
TCP
ET200M, OLM
Boiler Control Panel
BCP
S7-300, HMI, ET200M, OLM
Common Auxiliary Panel
CAP
ET200M, OLM, MMU
Common Auxiliary Panel Pumphouse
CAPP
ET200M, OLM, MMU
Common Control Panel
CCP
S7-400H, Panel PC, ET200M, OLM, MMU
Cooling Radiator Panel
CRP
ET200M, OLM, MMU
Engine Ventilator Panel
EVP
ET200M, OLM, MMU
Common Unloading Panel
CUP
ET200M, OLM, MMU
Engine Auxiliary Panel
EAP
ET200M, OLM, MMU
Engine Control Panel
ECP
ET200M, OLM
Engine Radiator Panel
ERP
ET200M, OLM, MMU
Fire Fighting Control Panel
FFCP
ET200M, OLM, MMU

TAP Turbine Auxiliary Panel


Genset Control Panel
GCP S7-400, Panel PC, ET200M, Protection Relay,
OLM, MMU
Genset Interface Panel
GIP
ET200M, OLM
High Voltage Interface Panel
HVIP
ET200M, OLM
LV Swgr Low Voltage Switchgear
Main Civil Distribution Panel
MCDP
OLM, MMU
MMU Multifunctional Monitoring Unit
MV Swgr Medium Voltage Switchgear
NE Swgr Neutral Earthing Switchgear
SaCoS Safety Control System on Engine
TGP Turbine Gauge Panel

5301959 FA 0 SCADA+ PLC Architecture (Rev. D in work).vsd 4/9


Copyright © MAN Diesel & Turbo SE
All rights reserved, including reprinting in whole or in part, photomechanical reproductions (photocopy / microcopy) in part or in full and
translation thereof.
0 1 2 3 4 5 6 7 8 9

Control Room

Operator Station 1 Operator Station 2


Monitor 1 Monitor 2 Monitor 1 Monitor 2

Laser Laser
Printer Printer

Switch

UPS 1

CCP 1.1
GCP1

GCP2

GCP3
GIP1

GIP2

GIP3

to PLC Architecture

D 28.04.2015 N. Gaikwad Edition Date 18.06.2014


C 23.01.2015 N. Gaikwad Editor T. Herzog Supervisory Control and MAN Diesel & Turbo Doc. No. 11.99233-2076 +
B 18.06.2014 T. Herzog Checked R. Meier Data Acquisition (SCADA ) Stadtbachstr. 1 Page 5
Revision Date Name Edition Status First Architecture 86153 Augsburg/Germany 03 x 18V48/60TS +1 Steam Turbine 5301959 Nababganj, Bangladesh Pages 9
0 1 2 3 4 5 6 7 8 9

SCADA Architecture
MAN Scope of Supply: CCP1.1
- CCP G HV - Substation
- HVIP
Control
Bus

MMU MMU

*
*
Prot. MODBUS
MMU
Relay

+00CBA01

+00CBB01
HVIP
HV Substation

CCP

CPU
S7-400
RJ45 RJ45 RJ45

PS

443-1
Panel

CP
PC 677B * Marshalling Kiosks

ET200-M
Control +
X1 X2
RJ45

I/O
I/O
I/O
I/O
IM

341
CP
Protection Panels
* IEC 60870-5-101

ET200-M
OLM

I/O
I/O
I/O
I/O
IM

341
I

CP
RTU
o
Control Room to/from TCP
Dispatch
PLC Architecture Center
K
to/from FFCP
E
PLC Architecture

MV / LV Room

MV Swgr

NE Swgr
+00BAU0x
+00BBA0x
- LV Main Distribution
- UPS
A - DC-System
- BSD
to/from - MCDP
GCP PLC
Architecture

to/from BCP
PLC Architecture
D

+00CDE01
MMU MMU
+00CDD01

CAPP
CAP

* *
ET200-M

ET200-M
I/O
I/O
I/O
I/O

I/O
I/O
I/O
I/O
IM

IM
OLM OLM

Engine Tank Unloading


Hall farm Station

Plant Auxiliaries Plant Auxiliaries Plant Auxiliaries


(Pumps etc.) (Pumps etc.) (Pumps etc.)
(MAN-supplier) (MAN-supplier) (MAN-supplier)

D 28.04.2015 N. Gaikwad Edition Date 18.06.2014


C 23.01.2015 N. Gaikwad Editor T. Herzog MAN Diesel & Turbo Doc. No. 11.99233-2076 +
B 18.06.2014 T. Herzog Checked R. Meier CCP PLC Architecture Stadtbachstr. 1 Page 6
Revision Date Name Edition Status First S7-400 Single Profibus 86153 Augsburg/Germany 03 x 18V48/60TS +1 Steam Turbine 5301959 Nababganj, Bangladesh Pages 9
0 1 2 3 4 5 6 7 8 9

SCADA Architecture

Next Previous o
GIP1 CCP GCP1 GIPn FFCP GCPn
GCP GCP
G E G E

Control
to/from CCP PLC Control
to/from CCP PLC
Bus Architecture Bus Architecture

A A

+nnCDA01
+01CDA01

GCP n
GCP 1

CPU

CPU
S7-400

S7-400
RJ45 RJ45 RJ45 RJ45 RJ45 RJ45 RJ45 RJ45
PS

PS
I/O
I/O
I/O
I/O

I/O
I/O
I/O
I/O
443-1

443-1

443-1

443-1
Panel Panel
CP

CP

CP

CP
o
X1 X2
RJ45 RJ45 PC L 1 to n X1 X2
RJ45 RJ45 PC L o

to/from FFCP o GCPs to/from FFCP o


Prot. PLC Architecture Prot. PLC Architecture
OLM

OLM
RJ45 RJ45
NET
Scalance Relay MMU NET
Scalance Relay MMU
B B

to/from BCP PLC


to/from BCP PLC

Unit Bus
Control Room
Unit Bus

Architecture
Architecture

Engine Hall

SACOS One n
SACOS One 1

+nnCDD01
+01CDD01

EDS-D EDS-D

GIP n
1 to n
GIP 1

ET200-M
Genset 1 Genset n

I/O
I/O
I/O
I/O
I/O
IM
OLM
*
ET200-M

Gensets,
I/O
I/O
I/O
I/O
I/O
IM

OLM NET NET


Scalance
(MAN) Scalance
(MAN)

RJ45 outlet
RJ45 outlet

RJ45 RJ45

GWM
SACOS, GWM

GIP´s

B to/from BCP PLC B to/from BCP PLC


Architecture Architecture

1 to n
+01CDC01

+nnCDC01
EAP 1

EAP n
MMU EAPs MMU
Engine 1 Engine n
* Auxiliaries * Auxiliaries
ET200-M

ET200-M
I/O
I/O
I/O
I/O
I/O

I/O
I/O
I/O
I/O
I/O
IM

IM
OLM OLM

Outside
+01CDG01

+nnCDG01
ERP 1

ERP n

1 to n
Engine
MAN Scope of Supply:
Engine 1 Radiator Fans Engine n - GCP 1 / 2 / 3
Radiator Fans Radiator Fans - GIP 1 / 2 / 3
- SACOS ONE 1 / 2 / 3

D 28.04.2015 N. Gaikwad Edition Date 18.06.2014


C 23.01.2015 N. Gaikwad Editor T. Herzog MAN Diesel & Turbo Doc. No. 11.99233-2076 +
B 18.06.2014 T. Herzog Checked R. Meier GCP PLC Architecture Stadtbachstr. 1 Page 7
Revision Date Name Edition Status First S7-400 Single Profibus 86153 Augsburg/Germany 03 x 18V48/60TS +1 Steam Turbine 5301959 Nababganj, Bangladesh Pages 9
0 1 2 3 4 5 6 7 8 9

PS1
PS2
RJ45 RJ45 RJ45 RJ45
RJ45 RJ45 RJ45 RJ45 SCALANCE
X208

CPU
RJ45

S7-300

PN/DP
PS

315-2
CP
X1 X2
RJ45 RJ45 RJ45
HMI
SIEMENS

+00CJF01
BCP-C
TP900

RJ45 RJ45

PROFINET
SWD

MP DP
GATEWAY

L-, P-Control 1
socket outlet

IM 360

I/O
I/O
I/O
I/O
Control Room

IM
IM
B

OLM
to/from GCP PLC
Architecture
to/from CCP PLC C
Architecture

to/from TCP PLC D


Architecture

Engine Hall

Common Boiler
Auxiliaries
...
(Pumps etc.)

D 28.04.2015 N. Gaikwad Edition Date 18.06.2014


C 23.01.2015 N. Gaikwad Editor T. Herzog MAN Diesel & Turbo Doc. No. 11.99233-2076 +
B 18.06.2014 T. Herzog Checked R. Meier BCP PLC Architecture Stadtbachstr. 1 Page 8
Revision Date Name Edition Status First S7-300 Profibus
86153 Augsburg/Germany 03 x 18V48/60TS +1 Steam Turbine 5301959 Nababganj, Bangladesh Pages 9
0 1 2 3 4 5 6 7 8 9

to/from BCP PLC D E to/from CCP PLC


Architecture Architecture to/from CCP PLC
Architecture

OLM

+00CJA01
ET200-M
Steam Turbine Genset

+00CJJ01

I/O
I/O
I/O
I/O
I/O
IM
BAT 1

GCP
Battery + Battery

TCP
Control Panel
Charger for ELECTRONIC
Steam Turbine GOVERNOR
505 Prot. Syn.
Relay Unit

LV Room Control Room

+00CJK01
Engine Hall

+00CJL01
Steam

TAP
Steam Turbine

TGP
Turbine Steam Turbine
Auxiliary Panel Gauge Panel
(Customer)

Steam Turbine
Auxiliaries

D 28.04.2015 N. Gaikwad Edition Date 18.06.2014


C 23.01.2015 N. Gaikwad Editor T. Herzog MAN Diesel & Turbo Doc. No. 11.99233-2076 +
B 18.06.2014 T. Herzog Checked R. Meier TCP PLC Architecture Stadtbachstr. 1 Page 9
Revision Date Name Edition Status First ET-200M 86153 Augsburg/Germany 03 x 18V48/60TS +1 Steam Turbine 5301959 Nababganj, Bangladesh Pages 9