Vous êtes sur la page 1sur 38

CHAPTER 4.

PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

CHAPTER 4

PV INVERTER - SYSTEM STRUCTURE AND CONTROL


DESIGN

4.1 PV FED THREE-LEVEL INVERTER FOR UTILITY


INTERFACE

In this chapter, the design of the single phase PV inverter power stage with MPPT
capability is described, as shown in Fig. 4.1. Firstly, the inverter design specifications are
given. Secondly, based on the specifications, the choice of the switching scheme is briefly
described. Thirdly, the selection of the DC-link capacitor is discussed based on its lifetime
and size. Following this, the design equations on DC-link capacitance are developed based
on the power balance and double-line frequency ripple voltage. Following, the design guide
for the output filter is discussed based on the IEEE-1547 standard [14] and the filter
configuration is described. The system is applied with two main and important types of
damping schemes.

Fig. 4.1. Power stage configuration of the single phase PV inverter.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 49


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

The power circuit topology includes an LCL filter as a interface between the inverter and
grid. Sinusoidal pulse width modulation (SPWM) with unipolar switching, LCL filter is
employed to achieve decreased switching ripple with only a small increase in filter hardware
as compared to that of the L or LC filter with bipolar switching. The voltage controller
produces the gird current reference by comparing the actual dc link voltage with the
maximum power point voltage given by the MPPT algorithm, which is then multiplied with
the grid voltage template provided by the grid synchronizer. The control voltage produced by
the injected grid current regulator is used to generate pulses for the grid connected PV
inverter. The basic specifications used in simulation for the inverter design are listed in Table
4.1.
Rated grid voltage* 10V (RMS)
Rated grid current 6A (RMS)
Switching frequency 10kHz
Nominal DC-link voltage 21.1V
Percentage DC-link voltage ripple 10%

TABLE 4.1 : Specifications of PV inverter.

A conventional method of grid synchronization for grid connected DC/AC inverter is to


duplicate the grid voltage so that output current reference has the same phase as the grid
voltage. While this method is simple, it carries the distortions and transients from the grid to
the output current, which is undesirable for grid connected applications. In addition, this
method of grid synchronization cannot provide inverters the ability of controlling reactive
power flow.

A full bridge configuration with SPWM unipolar voltage switching scheme is used (as the
switching circuit of the inverter. By selecting the full bridge configuration, the minimal
allowed DC-link voltage can be set to be the peak value of the AC grid voltage (plus
margins). Thus, power MOSFETs, instead of higher voltage IGBTs, can be used as the
switching devices which enable use of a high switching frequency (> 10 k Hz ) without
introduction of excessive switching loss. Using unipolar voltage switching scheme effectively
moves the first major harmonic of the bridge output voltage from order m f  1 to the order

of 2m f  1 , where m f is the frequency modulation ratio - the ratio between the switching

frequency and the fundamental frequency. The output filter thus reduces its size for “free”.
Since this full bridge configuration with SPWM unipolar voltage switching scheme is

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 50


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

commonly used in voltage sourced inverters. The DC-link capacitor is important for the
power decoupling between the input power to the inverter and their output power to the
utility grid. Normally, electrolytic capacitors are used for their large capacitance and low cost.
However, in PV applications where the inverters are usually exposed to outdoor
temperatures, the lifetime of such electrolytic capacitors is shorten drastically. Film capacitors
are a clear the alternative given their long life expectancy and wide operating temperature
range. Unfortunately, film capacitors are far more expensive than the electrolytic ones in
term of cost per farad, hence the size of the capacitance has to be smaller to keep the price
of the capacitor acceptable. However, smaller capacitance would weaken the power
decoupling ability of the DC-link capacitor which may cause DC-link voltage fluctuations
that lead to distortion of the inverter output current to the grid. There are two factors that
can cause undesirable DC-link voltage variations. The first one, which can be referred to as
the transient DC fluctuation is caused by the rapid increase/decrease of the input power
flowing into the DC-link capacitor. However, in PV application, the chance of rapid DC
input power variation is little due to the nature of the sun. Therefore, the transient DC
fluctuation is not a major concern when designing a VSI for PV application. The second
factor, which can be referred to as the AC fluctuation of the DC-link voltage is caused by the
double-line frequency ripple power generated from the grid side (refer to equation (3.15)).
This double-line frequency ripple component can couple through the DC voltage control
loop to cause a significant amount of distortion on the current reference signal. A notch filter
or an average filter can be applied to the feedback signal of the DC-link voltage in the
voltage control loop, so that this double-line frequency ripple component is filtered out
before entering the voltage controller. This prevents the output current from having
distortions that are resulted from the DC voltage control loop. Then the capacitance of the
DC-link capacitor can be easily obtained given the magnitude of the maximum allowed ripple
voltage.
S
C DC  (4.1)
2 g V dcVdcmax
n
, ripple

Finally, substituting, these parameters from the inverter specifications

60
C DC   2.16 mF
2  314  21  2.1
Based on this, a 2.2mF capacitor is selected for the simulation study.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 51


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

4.2 CONTROL SYSTEM COMPONENTS DESIGN

4.2.1 LCL FILTER DESIGN

Traditionally, the grid interface filter was a simple first-order L filter. However, such a
filter is bulky and inefficient, and it cannot meet the regulatory requirements specified in [14]
and [15] for the switching range of mid- to high-power inverter applications. Hence, there
has been a significant interest in higher order filters, particularly LCL filters, to meet the grid
interconnection standards at significantly smaller size and cost. The dynamic performance of
the grid-connected voltage source converter with a third-order LCL filter was comparable to
the performance of the grid-connected voltage source converter with a first-order L filter.
However, selecting the parameters of the LCL filter is a more complicated process compared
to those of an L filter. A step-by-step procedure and the basic guideline for the selection of
the LCL filter parameters for damping the LCL filter of a front end 3-phase active rectifier
was proposed in [16]. The design of filter from the point of view of efficiency considering
the current harmonic requirements of IEEE 1547 (which are derived from IEEE 519-1992
[15]) as the primary criteria for the design of the filter, but with a goal to reduce the size and
weight (and therefore cost) of the individual filter components was proposed in [17]. The
lowest order harmonics that appeared on the harmonic spectrum of the output voltage of the
full-bridge are at the sidebands of 2 m f .Since the inverter switching frequency is set to be

greater than the audible frequency (10 k Hz ), the lowest order of the harmonics of the
inverter is 2m f  1  399 . According to the IEEE Distributed Resource (DR)

interconnection standard, IEEE-1547, any current harmonic which has an order that is
greater than 35 must have a magnitude that is no greater than 0.3% of the rated current of
the DR output. (The original harmonic regulation table in IEEE-1547 can be found in
Appendix A). Thus, the primary design guide for the inverter output filter is to make the
magnitude of the major harmonic current of the inverter less than 0.3% of the rated current.
A third order LCL filter, Fig. 4.2(a), was used to meet the aforementioned harmonic
reduction target. Assumption made here is that the ac supply voltages contain only positive-
sequence fundamental component, which then means that they can be treated as short
circuits with zero impedance when performing system stability and harmonic analyses, Fig.
4.2(b).

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 52


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

(a) (b)
Fig. 4.2. Output LCL filter of the inverter.

v in stands for the terminal voltage or the output voltage of the full bridge, which consists

of a fundamental component and higher order harmonics components. Solving the grid
current in Laplace domain using superposition yields the following transfer functions:

I g s  sC d Rd  1
 (4.2)
Vin s  V 0
s L1 L2 C d  s C d Rd L1  L2   s L1  L2 
3 2
g

I g s  s 2 L1C d  sC d Rd  1
 (4.3)
V g s  s 3 L1 L2 C d  s 2 C d Rd L1  L2   s L1  L2 
Vin  0

From the above equation (4.2) and (4.3), one can observe that the grid current i g t 

depends on both the terminal voltage vin t  and the grid voltage v g t  . As discussed before,

the output filter design will not take harmonic grid voltage distortion into consideration
because IEEE-1547 allows the presence of harmonic current distortion caused by grid
voltage distortion. Therefore, equation (4.3) will not be taken into consideration in output
filter design. The terminal voltage vinv t  contains a fundamental component and higher
frequency components which could result in higher frequency distortions on the grid current
i g t  . Therefore, Equation (4.2) is used as the output filter transfer function as:

I g s  sC d Rd  1
H f s    (4.4)
Vin s  V s L1 L2 C d  s C d Rd L1  L2   s L1  L2 
3 2
g 0

The RMS value of the higher order frequency components of vt(t) can be calculated using
the look up table (refer to Appendix A), given the nominal DC-link voltage V dcn .

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 53


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

Vin  jh g  
1
2
Vˆ  
Ao h Vdcn

1
 k h Vdcn (4.5)
n
2 1 / 2V dc 2 2

The VˆAo  h is the peak value of each harmonic voltage between one leg of the bridge and

the center point of the DC-link. k h  


Vˆ 
Ao h
is tabulated as a function of m a and the
n
1 / 2Vdc

orders of harmonics (refer to Appendix B for details about the harmonics table). table).
Therefore, combining equation (4.4) and (4.5), the RMS value of the harmonic current can
be expressed as:

I g  jh g    H f  jh g   k h   Vdcn


1
(4.6)
2

Remember that I g  jh g  cannot exceed 0.3% of the rated current of the inverter.

Therefore, given the RMS value of the rated grid current the following relationship can be
derived:

0.3%  2  I grated
H f  jh g   (4.7)
Vdcn  k h 

Given from Appendix B, the worst case k h  at 2m f  1 is 0.37. Then, substituting the

parameters from the inverter specification and using a switching frequency of 10kHz, we get
the magnitude of the filter transfer function H f  jh g  at 2m f  1 .

0.3%  2  6
H f  j 2m f  1314   H f  j 125286    3.27  10 3  50 dB (4.8)
21  0.37

At   125286 , the magnitude of H f  j 125286  from the magnitude plot of

H f  j  should at most be -50dB. This is the guideline of choosing the values for L1 , L2 , C d

and R d .Selection of damping resistor value for passive damping must be sufficient to avoid
oscillation, but losses cannot be so high as to reduce efficiency. Hence a careful design is
required which takes into consideration the losses and the stability margin. The tuning of
different passive damping methods and an analytical estimation of the damping losses
allowing the choice of the minimum resistor value resulting in a stable current control and

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 54


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

not compromising the LCL-filter effectiveness has been proposed in [18]. So initially the
damping resistor value is considered to be zero and the value total sum of the inverter side
and grid side inductance L1  L2   0.1 p.u as proposed by [16]. Finally, the LCL filter
components are chosen following this guideline and the values of each component are
shown in Table 4.2 and the MATLAB magnitude plot is shown in Fig. 4.4.

Fig. 4.3. Generic magnitude plot of the output filter transfer function H f s  .

The value of damping resistor is selected based on the criteria

Rd  Rdsw
1 (4.9)
Rdsw 
C f 2f sw
L1 [mH] L2 [mH] C d [µF] R d [Ω]
1 0.5 2.5 4
TABLE 4.2 : LCL filter parameters.

Fig. 4.4. Magnitude plot of using selected filter component values.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 55


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

The consequent resonant frequency is 5.5 kHz, which is approximately one-half of the
switching frequency and thus satisfying the criteria that 10   g    res   sw .The impedance

of the filter capacitor at the resonant frequency is 12Ω. The damping value is chosen as one-
third, i.e., 4Ω which also satisfies the equation (4.8).

For an application with a stiff grid, a passive damping method is often preferred for its
simpleness and low cost. In [19] a new passive damping scheme with low power loss for the
LLCL filters is proposed. Also, a simple engineering design criterion is proposed to find the
optimized damping resistor value, which is both effective for the LCL filter and the LLCL
filter. Compared with the LCL filter, the proposed passive damped LLCL filter can not only
save the total filter inductance and reduce the volume of the filter but also reduce the
damping power losses for a stiff grid application. Fig. 4.5 and Fig. 4.6 shows the different
topological circuits for passive damping proposed by [18] and [19].

Fig. 4.5. Different configurations for passive damping [5].

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 56


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

Fig. 4.6. Different configurations for passive damping [6].

4.2.2 CURRENT CONTROLLER

The current controller is used to regulate the current injected into the grid. The grid
current injected has to be kept in phase with the grid voltage since only active power has to
be transferred from the PV generation system. There are various controllers that are
discussed in literature for such a control; some of the popular controllers are [20].
A. The dq Control

The dq control structure is using the abc → dq transformation module to transform the
control variables from their natural frame abc to a frame that synchronously rotates with the
frequency of the grid voltage. As a consequence, the control variables are becoming dc
signals. Specific to this control structure is the necessity of information about the phase angle
of utility voltage in order to perform the transformation. Normally, proportional–integral
(PI) controllers are associated with this control structure. A typical transfer function of a PI
controller is given by.

Ki
G PI s   K p  (4.9)
s

Where K p is the proportional and K i is the integral gain of the controller

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 57


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

B. Stationary Frame Control

Since in the case of stationary reference frame control, the control variables, e.g., grid
currents, are time-varying waveforms, PI controllers encounter difficulties in removing the
steady-state error. As a consequence, another type of controller should be used in this
situation. The transfer function of resonant controller is defined as

G PR s   K p  K i
s
(4.10)
s 2
2

Because this controller acts on a very narrow band around its resonant frequency ω, the
implementation of harmonic compensator for low-order harmonics is possible without
influencing at all the behavior of the current controller. The transfer function of the
harmonic compensator is given by

GHC s  
s
K
h 3, 5, 7
ih
s  h 
2 2
(4.11)

C. The abc Frame Control

Historically, the control structure implemented in abc frame is one of the first structures
used for pulse width modulation (PWM) driven converters. Usually, implementation of
nonlinear controllers such as hysteresis controller has been used. The main disadvantage of
these controllers was the necessity of high sampling rate in order to obtain high
performance. Nowadays, due to the fast development of digital devices such as
microcontrollers (MCs) and DSPs, implementation of nonlinear controllers for grid-tied
applications becomes very actual.

In this thesis, a proportional resonant (PR) compensator is used to track a sinusoidal


current reference signal since, with the PR controllers, the converter reference tracking
performance can be enhanced and previously known shortcomings associated with
conventional PI controllers can be alleviated. These shortcomings include steady-state errors
in single-phase systems and the need for synchronous d–q transformation in three-phase
systems [21]. Another advantage associated with the PR controllers and filters is the
possibility of implementing selective harmonic compensation without requiring excessive

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 58


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

computational resources. The plant modeling, PR compensator design and the closed loop
stability is discussed in this section. The block diagram of the LCL filter as a interface
between inverter and grid is as shown in the Fig. 4.7.

Fig. 4.7. Block diagram of LCL filter.


From the above block diagram and combining the equation (4.2) and (4.3) the expression
for the grid current can be derived as follows

 s 2 L1C d  sC d Rd  1 
I g s   G p s  V g  Vinv  (4.12)
 sC d Rd  1 

Where,

sCd Rd  1
G p s   (4.13)
s L1 L2 C d  s C d Rd L1  L2   sL1  L2 
3 2

s 2 L1Cd  sCd Rd  1
Since the magnitude and phase response of are 0dB and 0o at the
sCd Rd  1
fundamental frequency of the grid. Therefore, equation (4.12) can be simplified to equation
(4.14).

I g s   G p s Vinv  V g  (4.14)

Given the plant model, a PR compensator, Gc s  is then added to the closed loop and the
equivalent closed loop diagram can be seen in Fig. 4.8.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 59


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

Fig. 4.8. Block diagram of the current controller.

From Fig. 4.8 the relationship between the input and the output of the current loop can
be derived as:

I g s   H 1 s   I g* s   H 2 s   V g s  (4.15)

Where,

G c s   G p s 
H 1 s   (4.16)
G c s   G p s   1

G p s 
H 2 s   (4.17)
1  Gc s   G p s 

To successfully track the i g* t  signal without steady state errors, the magnitude of

H 1  j  in equation (4.15) has to equal to 1 at the fundamental frequency of the i g* t  .Thus,

it is clear that if Gc  j  has a infinite gain at the fundamental frequency, H 1  j  would


have a unity gain. On the other hand, if Gc  j  has a infinite gain at the fundamental

frequency, H 2  j  in equation (4.17) would results in 0 at the fundamental frequency so that

the H 2  j  term can be neglected. Therefore, it is not necessary to have the grid voltage
feed-forward in the current control loop. To conclude, the controller, Gc  j  has to have an

infinite gain at the fundamental frequency in order to track the current reference, i g* t  . A

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 60


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

proportional-resonant (PR) controller meets the aforementioned controller requirement. An


ideal PR controller which has an infinite gain at  g has a transfer function shown in

equation (4.10) and a generic bode plot is shown in Fig. 4.9. However, the infinite gain of the
controller leads an infinite quality factor of the system, which cannot be achieved in either
analog or digital controller implementation. Furthermore, since the gain of an ideal PR
controller at other frequencies is low, it is no adequate either to eliminate the higher order
harmonics influenced by the grid voltage or to react to slight grid frequency variation.

Fig. 4.9. Bode plot of ideal PR controller, K p  1 and K i  20 .

This is undesirable because the harmonic grid voltage distortion would results in a
significant amount of harmonic grid current distortion. Therefore, a damping term ζ is
introduced to form a non-ideal PR controller transfer function shown in equation (5.7). This
damping term ζ reduces the infinite gain at the fundamental frequency to a finite large gain
but increases the bandwidth of the controller.

K i  2    o  s
Gc s   K p  (4.18)
s  2     o  s   02
2

Where  o  2f o , K i is the fundamental harmonic gain, and ξ is the damping factor. The
harmonic compensator G HC s  is responsible for the attenuation of the low-frequency
harmonics injected into the grid. In view of that, the compensator includes a bank of
damped bandpass filters tuned to resonate at odd multiples of the grid frequency

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 61


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

h
K n  2    n  o  s
G HC s    (4.19)
s  2    n   o  s  n o 
2 2
n 3

where n can take the values 3, 5, . . . , h, h being the highest current harmonic to be
attenuated, and K n is the n-harmonic gain. Notice that, in a situation in which no harmonic
attenuation is required, then h = 0 and the compensator transfer function can be written as
G HC s   1 . Fig. 4.10 shows the Bode diagram of the controller Gc s  for different values

of K i and ξ with K p  0 .

(a) (b)

(c)
Fig. 4.10. Bode diagram of the current controller with (a) constant damping factor
ξ, (b) constant harmonic gain K i , and (c) constant product K i ξ.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 62


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

The following properties can be observed: 1) the magnitude peak value is given by 20 log
K i (dB); 2) the magnitude bandwidth and the phase shape are governed by ξ ; and 3) for

constant value of the product K i ξ, the magnitude diagrams overlap for practically all
frequencies, except for anarrow range around the grid frequency. PR controller can provide
large gain at f o , but it also introduces negative phase shift at the frequencies higher than the
selected frequency, especially at the frequencies close to the selected resonance frequency,
which damages the PM of the system. To avoid this side effect, the crossover frequency fc is
suggested to be set far away from the selected resonance frequency [22]. Where the
proportional gain is tuned in the same way as that for a PI controller, and it basically
determines the dynamics of the system in terms of bandwidth, phase, and gain margin. The
closed loop gain of the current control loop with the PR compensator can be simply
obtained by equation (4.20). Fig. 4.11 shows the bode plot uncompensated current loop with
three main frequencies indicated; resonant frequency f r , grid fundamental frequency f o and
the gain cros over frequency f c . The values of the PR controller for improving the

performance of the inner current loop and the improved parametres ( f c and gain at
fundamental frequency T fo ) are as shown in TABLE 4.3.

T s  = GC s   Ginv s   G P s 

 K  2     o  s  Vdc sC d Rd  1
  K P  2 i 
2 
 3 (4.20)
 s  2     o  s   0  Vtri s L1 L2 C d  s C d Rd L1  L2   s L1  L2 
2

Fig. 4.11. Bode diagram of the uncompensated system.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 63


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

Before compensation After compensation


Ki Kp 
f C [Hz] T fo [dB] f C [Hz] T fo [dB]
100 10 0.1 106 10 1.24 10 3 80

TABLE 4.3 : Parameters of PR controller.

Fig. 4.12 shows the bode plot compensated current loop with three main frequencies
indicated and with the improved system performance parameters marked.

Fig. 4.12. Bode diagram of the compensated system.

Fig. 4.13. Step response of the inner current loop.

Fig. 4.14 shows the 50Hz response of the PR current control system. The control loop is
exhibiting a overshoot of 20% and however the transient and steady state response is
satisfactory.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 64


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

Fig. 4.14. 50Hz response of the PR current control system.

4.3.2 VOLTAGE CONTROLLER

The DC-link voltage can be regulated by a closed loop voltage controller. The variation or
imbalance in the PV power and the power being injected into grid is reflected on the DC link
of the inverter. When the PV power is more than the power injected, the dc link voltage
increases and vice-versa. Thus regulation of the dc link voltage requires the amount of
current to be injected and thus a simple PI controller can be used for generation of required
grid current for maintaining the DC link voltage stiff at the reference value. Grid voltage has
to be sensed for the synchronization of the PWM inverter and to maintain the injected grid
current in phase with it. If the grid voltage is sensed directly without any filtering then during
weak grid situation the reference current generated will involve the harmonics and the
current injected gets distorted. Hence a proper grid synchronization method is required for
having unity power factor (UPF) operation of the inverter. A low complexity method of grid
synchronization is introduced in [23]. Effort has been taken to minimize the computational
processes of reproducing a parallel component and an orthogonal component of the grid
voltage by means of using only a two by two state matrix. The grid voltage synchronizer
consists of two parts:

 A grid voltage estimator


 An amplitude identifier
The grid voltage estimator takes the grid voltage as its input and outputs one signal which
is aligned with the grid voltage (parallel component) and the other signal which is 90 leading
the grid voltage (orthogonal component). This estimator has a state space form of:

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 65


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

 A
  B

 x1   0  o   x1   K sync 

 x      x    0  v g  x1 
 2  o 0  2    (4.21)

C

 v g   y1  1 0   x1 
v        
 g   y 2  0 1   x 2 

The term K sync introduces damping to the oscillator which widens the estimator’s

bandwidth and reduces the gain at  o . As a result, x1 tracks the input v g ,at its fundamental

frequency while also rejecting other harmonics that appeared on the grid voltage. The
behaviour of this grid synchronizer is analyzed by means of studying its responses in time
domain. Normally, the harmonics that appeared on the grid voltage are predominately low
order odd harmonics due to thyristor bridges and diode rectifiers in the system. The
harmonics that are multiple of three are mainly trapped inside the delta connection of
distribution transformers so that they are not presented in the local grid. Therefore, the
predominate harmonics that appeared on the local grid are in the order of 5th, 7th, 11th, 13th.
Fig. 4.15 shows the parallel component of the grid voltage produced by the synchronizer
with grid voltage having a %THD of 5%. For grid connected PV system only active (parallel)
component of the grid current control is required.

Fig. 4.15. Time domain response of x1 t  v/s v g t 

The outer voltage loop is modeled which is required for controlling the DC link voltage to
a value corresponding to the VMPP .The differential equation on the DC side is:

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 66


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

dvdc t 
C DC  i dc t  (4.22)
dt

idc t  consists of two components, a DC component, I dc and a double-line frequency AC

component, i dc , ripple t  . Both of them can be obtained from the power balance equation

vdc t   idc t   Vˆg  cos g t  Iˆg  cos g t    (4.23)

Vˆg  Iˆg Vˆg  Iˆg


vdc t   I dc  vdc t   idc,ripplet   cos   cos2 g t    (4.24)
2 2

From (6.3), the two components of the DC current can be expressed as:

Vˆg  Iˆg Vgrms


I dc  cos   Iˆg cos  (4.25)
2vdc t  2vdc t 

Vˆg  Iˆg  cos2 g t   


idc ,ripple t   (4.26)
2v dc t 

Since we align the parallel component of the current reference signal with the grid voltage
using a grid synchronization function block, the grid current i g t  has its parallel component

aligned with the grid voltage. Therefore equation (4.25) can be rewritten to be

V grms
I dc  Iˆg (4.27)
2v dc t 

The complete model of the voltage loop can be drawn and is shown in Fig. 4.16. A notch
filter, H n s  has a form of equation (4.28) is applied to the voltage loop to filter out the
double-line frequency current ripple component idc , ripple t  because the double-line

frequency ripple current produces a double-line frequency ripple voltage on the DC-link.
This is undesirable because this ripple signal would couple through the voltage controller and

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 67


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

cause undesirable high frequency component would appear on the current reference signal of
the current control loop.

s 2  2   1   n  s   n2
H n s   (4.28)
s 2  2   2   n  s   n2

Fig. 4.16. Outer voltage loop of the inverter.


Where  n is twice the fundamental frequency,  1 is chosen to be 0.006 and  2 is chosen

to be 1. The current loop, GCCL s  has the form of

GC s   G P s 
GCCL s   (4.29)
GC s   G P s   1

A simple PI controller is used as the DC voltage loop compensator, which has the form
of:

KI
GV s   K P  (4.30)
s

The bode plot of uncompensated and compensated outer voltage loop are as shown in Fig.
4.17 and Fig. 4.18 respectively.

A selection of K P = 0.2 and K I = 3 yields a phase margin of 64.6 0 and the gain cross over
frequency f C  9.65 Hz which matches with the design that the voltage closed-loop
bandwidth should be approximately equal to 1/150th of the closed current loop to reduce, at
minimum, oscillation in the dc voltage and in the ac current [24]. The reference DC link
voltage to be maintained is generated by the MPPT controller.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 68


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

Fig. 4.17. Bode plot of uncompensated outer voltage loop.

Fig. 4.18. Bode plot of compensated outer voltage loop.

The scheme of DC link voltage reference generator is shown in Fig. 4.19. When
signp / v   0 the integrator increases its output Vdc , and the dc link voltage reference

Vdc , ref moves toward the MPP. When signp / v   0 the integrator decreases its output

Vdc , and the dc link voltage reference Vdc , ref moves back toward the MPP. The input signal

Vdc** represents the initial voltage reference; i.e., the starting value of the integrator. When the

control system is enabled, the quantity Vdc computed by the MPPT algorithm is added to

Vdc** , giving the actual reference of the dc link voltage Vdc , ref .Then, the regulation of the

current I g injected into the mains allows the dc link voltage to be controlled around the

reference value. In this way, all the power coming from the PV generator is transferred to the
grid.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 69


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

Fig. 4.11. DC link voltage reference generator.

4.3 ACTIVE DAMPING OF LCL FILTER

A direct way to damp the resonance of the LCL filter is introducing a passive resistor to
be in series or parallel with the filter inductors or filter capacitor, which is called passive-
damping method. Among which, adding a resistor in series with the filter capacitor has been
widely adopted for its simplicity and relatively low power loss. However, it will weaken the
switching harmonic attenuation ability. Adding a resistor in parallel with the filter capacitor
will not impair the low-and high-frequency characteristics of the LCL filter, but the power
loss brought by this resistor is too large to be accepted. In order to avoid the power loss
resulted from the passive resistor, the concept of virtual resistor was proposed in place of the
passive resistor, and the virtual resistor can be realized through proper control schemes. Such
methods are called active damping methods. In recent years, the design of current regulator
and capacitor– current-feedback active-damping for LCL-type grid-connected inverter has
been extensively discussed. A step-by-step controller design for LCL-type grid-connected
inverter with capacitor–current-feedback active-damping has been proposed in [25]. A hybrid
passive-active damping solution with improved system stability margin and enhanced
dynamic performance is proposed for high power grid interactive converters [26]. In this
thesis, a novel current control strategy based on a new current feedback for grid-connected
voltage source inverters with an LCL-filter proposed in [27] has been applied to grid
connected PV system and the performance is compared with that of the passive damped
LCL filter. The system structure for such a novel current control strategy based grid
connected PV is as shown in Fig. 4.20. In the novel control strategy the capacitor of LCL-
filter is split into two parts, and the current flowing between these two parts is measured and
used as the feedback of a current controller. In this way, without any damping resistor, the
inverter control system is degraded from third-order to first-order, as a first-order system
with L-filter. Consequently, the control loop gain and bandwidth can be increased and many
existent current control methods can be implemented to minimize steady-state error and
current harmonic distortion.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 70


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

Fig. 4.21. System structure for active damping of LCL filter.

Capacitor is split into two parts and the current flowing between them is used as the
feedback current for the current controller.
Assuming C1    C and C1  1     C with then the current i12 between the two
capacitors is given as
i12  i2  1     iC
or (4.31)
i12  1     i1    i2

Where i2 the total currents of filter capacitor and the current is i12 is the weighted average

of the inverter current and the grid current. The transfer function for vinv and i12 as follows.

I 12 s  1     1     L  C  s 2  1
 (4.32)
Vinv s    1     L2  C  s 3  L  s

Where

L2
L = L1  L2 and  
L1

Considering   1   the equation (4.32) becomes

I 12 s  1

Vinv s  L  s

Considering the ESRs of inductor in LCL-filter the transfer function becomes

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 71


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

I 12 s  1

Vinv s  L  s  R1  R2

Thus the transfer function of the LCL filter is degraded from order three to one which makes
the loop gain and the cross-over frequency with new control strategy much higher than those
with conventional control strategies, resulting in minor steady-state error and a better dynamic
response in close-loop control. The design of the PR current controller for controlling the
injected grid current and the voltage controller for regulating the voltage is same as that of the
passive damping. The MSX-60W panel specifications are considered for the simulation study
of the inverter system. The summary of parameters of the PV inverter system used for
simulation of the passive and active damped LCL filter is shown in TABLE 4.4.

Passive damping Active damping


PR PI PR PI
L1 L2 C
Ki Kp  Kp Ki Ki Kp  Kp Ki 
[mH] [mH] [µF]
100 10 0.1 0.2 3 120 14 0.06 0.5 5 0.5 1 2.5 0.5
TABLE 4.4 : Summary of parameters of the PV inverter system.

4.4 PERFORMANCE EVALUATION USING MATLAB/SIMULINK

Simulation was conducted in MATLAB/SIMULINK environment to verify the


effectiveness of the proposed design approach, and all the parameters are chosen to be the
same as those in the aforementioned design. Simulation of the three level inverter with
MPPT for grid connected PV system incorporated with passive and active damped LCL
filter has been carried out. The performance of the power conditioning system connected to
the photovoltaic array has been evaluated both in steady state and transient operating
conditions determined by startup and solar irradiance variations. The transient and steady
state response of the system is tested dynamically for changes in irradiation and also in
temperature. Ripple correlation control MPPT is used for tracking the maximum power
available. The variation in the irradiation and temperature over the PV array is as shown in
Fig. 4.21.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 72


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

Fig. 4.21. System structure for active damping of LCL filter.

Step change in irradiation and temperature is done at t =1s and t =2s. The variation in the
power extracted from the PV array, active and reactive power injected into grid, array current
and DC link voltage is shown in Fig. 4.22 (a)-(e). It can be seen that the reactive power
injected into grid is almost zero ensuring the unity power factor operation of the three level
grid tied inverter. The variation in the array voltage, current is smooth and also the transient
response exhibits fast dynamic behaviour of the control system designed with satisfactory
performance.

Fig. 4.22. MATLAB/SIMULINK simulation results of the proposed topology on the


PV and grid side.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 73


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

The variation in the injected grid current for step change in irradiation is as shown in Fig.
4.23 (a). Fig. 4.23 (b)-(d) shows the magnified view of the selected portion in the Fig. 4.23
(a). The %THD of the grid current for all the selected portion is shown in Fig. 4.23 (e)-(g)
and it can be seen that the injected current %THD is less than 5% for all the variations in the
irradiations which complies with the IEEE STD 1547-1992.

Fig. 4.23. Injected grid current variations for step change in irradiation.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 74


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

The variation in the injected grid current for step change in temperature with irradiation level
maintained at 800 W / m2 is as shown in Fig. 4.24 (a). Fig. 4.23 (b)-(d) shows the magnified
view of the selected portion in the Fig. 4.24 (a). The %THD of the grid current for all the
selected portion is shown in Fig. 4.24 (e)-(g) and it can be seen that the injected current
%THD is less than 5% for all the variations in the temperature which complies with the
IEEE STD 1547-1992.

Fig. 4.24. Injected grid current variations for step change in temperature.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 75


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

(a)

(b)
Fig. 4.25. Transient response of grid current.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 76


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

Fig. 4.26 shows the performance of the PV generation system in tracking the maximum
power point of the PV panels during a transient of solar irradiance. From the starting
operating point, the system reaches the MPP in 1. Then, as a consequence of a 30% increase
of the solar irradiance, the operating points move to the new MPP in 2. Then, as a
consequence of a 50% decrease of the solar irradiance, the operating points move to the new
MPP in 3.

Fig. 4.26. PV array power versus voltage curve during step change in irradiation.

Fig. 4.27 shows the performance of the PV generation system in tracking the maximum
power point of the PV panels during a transient of temperature on PV array. From the
starting operating point, the system reaches the MPP in 1. Then, as a consequence of a 60%
increase of the temperature, the operating points move to the new MPP in 2. Then, as a
consequence of a 40% decrease of the temperature, the operating points move to the new
MPP in 3 and the irradiation level is maintained at 800 W / m 2 .

Fig. 4.27. PV array power versus voltage curve during step change in temperature.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 77


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

The variation in efficiency of the proposed configuration, as it operates from low power
to rated power condition is determined by noting down the power fed extracted from the PV
array and the power fed into the grid. For obtaining variations in the power generated the
irradiation level was changed in a step of 100 W / m 2 . Fig. 4.28 shows the efficiency versus the
power extracted from the PV array for both passive and active damped LCL based grid tied
PV inverter. From the curves it can be seen that the efficiency of power transfer is more with
active damping due to the absence of the damping resistor to damp the inherent resonance
effect of the filter and the efficiency increases with the increase in the power generated.

Fig. 4.20. Efficiency versus input PV power.

The variation in the %THD of the grid current injected for both passive and active damping
method with respect to the power injected into the grid is as shown in Fig. 4.29. The active
damping method shows a reduced %THD as compared to passive damped LCL. However
in both the methods the %THD of the grid current is less than 5% and it decreases with the
increase in the amount of power being injected.

Fig. 4.29. %THD of the current versus output power fed into the grid.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 78


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

4.5 HARDWARE IMPELEMENTATION OF PV INVERTER

Prototype system configuration for testing the three-level PV inverter with an output LCL
filter is as shown in the Fig. 4.30. The block diagram of the circuit configuration is shown in
Fig. 4.31. The prototype includes the following components

1) PV array
2) Three-Level inverter
3) Controller
4) Passive damped LCL filter
5) Fundamental grid voltage extractor
6) Signal sensing circuit

Fig. 4.30. Experimental rig of the three-level PV inverter.

A load of 110Ω is used for testing the performance of the PV inverter. The variation in
efficiency of the configuration, as it operates from low power to rated power condition, a
number of experiments were performed using a resistive load of 110Ω (in place of the grid).
The gating pulses are generated by the DSP, which senses the fundamental grid voltage
extracted using notch filter. A unipolar PWM technique of gating the inverter switches is
employed.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 79


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

Fig. 4.31. System configuration of the three-level PV inverter.

4.5.1 PV ARRAY

The solar array used in the hardware is consists of 74Wp PV module manufactured by
WAREE industry. The panels are kept at 36° on the terrace of Electrical Engineering
Department, VNIT Nagpur. Fig. 4.32 shows the PV array used for the experiment.

Fig. 4.32. Photograph of the PV module used for experimentation.

4.5.2 THREE-LEVEL INVERTER AND LCL FILTER

The three-level inverter implemented consists of four power switches which are pulse
width modulated for controlling the power flow. Fig. 4.33 shows the configuration of the
inverter and the LCL filter. Power MOSFET IRFP250N is used as the power switch. A

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 80


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

Toroid core T-16 is used for the design of inductor, consisting of number of turns wound
using SWG-17 wire. A damping resistor of 5Ω with the capacitor is used

Fig. 4.33. Photograph of the three level inverter used for experimentation.

4.5.3 GATE DRIVER CIRCUIT

The switch between the source and the load is known as high side switch. When the
MOSFET turns on the drain and source terminals are at the same voltage. In order to turn
the MOSFET on, and keep it turned on; the gate to source voltage must be between 10V-
20V. The pulses from the DSP are given to the gate driver circuit which provides isolation
and the amplified pulses that are used for gating the power switches. A TLP 250 IC is used
for gating the switches. The photograph of the driver circuit is as shown in the Fig. 4.34.

Fig. 4.34. Photograph of the gate driver.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 81


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

4.5.4 NOTCH FILTER

When the grid voltage is sensed and feedback is taken directly without any filter, then
during weak grid situation (when voltage consists of harmonics) the current reference wave
gets distorted and there by the actual current. Hence a band pass filter (BPF) tuned to extract
the fundamental component of the grid voltage is implemented for reference current
generation by sensing the grid voltage [14]. The circuit configuration is as shown in Fig. 4.35

Fig. 4.35. Circuit diagram of the analog implementation of BPF.

4.5.5 SIGNAL SENSING CIRCUIT

The MPPT controller needs two input parameters I PV and V PV for deciding the modulation
index at a particular insolation. So sensor circuits give a proportional output of these voltage
and current from the PV array and the output signals from the sensor circuits are given to
ADC channels of DSP. The Winson WCS2702 provides economical and precise solution for
both DC and AC current sensing in industrial, commercial and communications systems.
The output from the current sensor is proportional to the current output from the PV array.
The sensitivity of the sensor is 1mV/mA and the maximum current that can be measured
using WCS 2702 is 2A. The photograph of the voltage and current signal sensing circuit is as
shown in the Fig. 4.36.

Fig. 4.36. Photograph of the voltage and current signal sensing circuit.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 82


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

4.6 GENERATION OF GATING PULSES USING TMS320F28027


DSP TMS320F28027 from Texas Instrument is used as the core controller for producing
the control pulses of the three level inverter. The grid voltage is sensed through BPF and is
given to the adc input of the DSP which is taken as the reference carrier wave for the
production of gate pulses. Some of the features of the controller are

 High-Efficiency 32-Bit CPU ( TMS320C28027)


 60 MHz (16.67-ns Cycle Time)
 50 MHz (20-ns Cycle Time)
 40 MHz (25-ns Cycle Time)
 16 x 16 and 32 x 32 MAC Operations Module
 16 x 16 Dual MAC
 Harvard Bus Architecture – Flash, SARAM, OTP, Boot ROM Available
 Atomic Operations
 Fast Interrupt Response and Processing
 Unified Memory Programming Model
 Code-Efficient (in C/C++ and Assembly)
 Low Cost for Both Device and System: – One SCI (UART) Module
 Single 3.3-V Supply – One SPI Module
 No Power Sequencing Requirement
 Integrated Power-on and Brown-out Resets
 Small Packaging, as Low as 38-Pin Available
 Low Power – High-Resolution PWM (HRPWM) Module
 No Analog Support Pins – Enhanced Capture (eCAP) Module Clocking)
 Two Internal Zero-pin Oscillators
 On-Chip Crystal Oscillator/External Clock Input
 Dynamic PLL Ratio Changes Supported
 Watchdog Timer Module
 Missing Clock Detection Circuitry
 Up to 22 Individually Programmable, – 38-Pin DA Thin Shrink Small-Outline
 Multiplexed GPIO Pins With Input Filtering
 Peripheral Interrupt Expansion (PIE) Block That Supports All Peripheral Interrupts
 Three 32-Bit CPU Timers
The DSP is linked to MATLAB through Code Composer Studio (CCS V5) and the
gating signals are produced using the two PWM blocks. Since the two switches of the
inverter on the same leg should not be turned on at a time, the dead band unit inside the

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 83


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

controller is used for providing the dead band of 2µs. The values of the components used for
experimental work is as tabulated in TABLE 4.5.

f s [kHz] V dc [Volts] L1 [mH] L2 [mH] C d [µF] R d [Ω]


3 20 1 1.5 2.5 2.5

TABLE 4.5 : Summary of parameters used in experimental work.

4.7 EXPERIMENTAL RESULTS

The time response of the band pass filter used for sensing the grid voltage is as shown in the
Fig. 4.37.

Grid voltage
(0.5V/div)
BPF o/p
(0.5V/div)

Fig. 4.37. Time response of BPF.

However the range of voltage that can be sensed through the Analog to Digital Converter
(adc) of the DSP ranges from 0 to 3.3V max, therefore a dc offset is added to the output of
the BPF and the offsetted signal is given as i/p to the adc. Fig. 4.38 shows the o/p of BPF
after adding offset.

BPF o/p (1V/div)

Grid voltage (0.5V/div)

Fig. 4.38. Time response of BPF with dc offset added.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 84


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

It can be seen from the Fig.s that the grid voltage is somewhat distorted and contains
harmonics in it; however the o/p of the BPF is harmonic free, exhibits fast dynamic
response and is in phase with the grid voltage. A load of 110Ω, 5A was used for testing the
performance of the PV inverter and was fixed at a constant value. The modulation index of
the inverter was varied and the resulting current waveforms are as shown in Fig. 4.40 (a)-(b).

current given to the


resistive load
(0.5A/div) with M=0.6

(a)

current given to the


resistive load
(0.5A/div) with M=0.9

(b)

Fig. 4.39. Experimental results: current waveform through a resistive load (M=0.6).

Fig. 4.40 shows the PV inverter o/p voltage and the current fed into the grid for modulation
index M=0.8. It can be seen from the magnified plot of the current that it is has a high
frequency ripple super imposed due to the inverter switching, and spikes in the current is due
to the LCL filter inherent resonance. However the current %THD is found to be 3.8%
which is well below the IEEE-1547 (<5%) criteria. With the same load, and variation in the
modulation index the efficiency of the inverter was calculated.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 85


CHAPTER 4. PV INVERTER-SYSTEM STRUCTURE AND CONTROL DESIGN

Three-Level Inverter
o/p (20V/div)

current given to resistive load


(1A/div) with M=0.8

Fig. 4.40. Three level PV inverter o/p voltage and the current.

Voltage across resistive load


(20V/div) with M=0.6

Power drawn (2VA/div) with M=0.6

Current given to resistive load


(0.5A/div) with M=0.6

Fig. 4.41. Experimental results: voltage and current waveforms across a resistive load.

Fig. 4.41 shows the experimental waveforms of voltage across, current through and
power drawn from the load for M=0.6. The efficiency v/s modulation index curve is as
shown in the Fig. 4.42.

Fig. 4.42. Experimental inverter efficiency V/s modulation index.

SINGLE-PHASE THREE-LEVEL INVERTER WITH MPPT FOR GRID CONNECTED PV SYSTEMS 86

Vous aimerez peut-être aussi