Figure 314–27
Figure 314–33
Figure 314–35
Figure 314–36
Figure 334–2
Figure 334–4
FPN No. 1: Building constructions are defined in NFPA (3) As service-entrance cable.
220, Standard on Types of Building Construction, the appli-
cable building code, or both. (4) In commercial garages having hazardous (classified) loca-
tions as defined in 511.3.
FPN No. 2: See Annex E for determination of building
types [NFPA 220, Table 3-1]. (5) In theaters and similar locations, except where permitted
in 518.4(B).
(4) Cable trays, where the cables are identified for this use. (6) In motion picture studios.
FPN: See 310.10 for temperature limitation of conductors. (7) In storage battery rooms.
(8) In hoistways or on elevators or escalators.
84 334.12 Uses Not Permitted (9) Embedded in poured cement, concrete, or aggregate.
(10) In hazardous (classified) locations, except where per-
(A) Types NM and NMC. mitted by the following:
(1) In any dwelling or structure not specifically permitted in a. 501.10(B)(3)
334.10(1), (2), and (3).
b. 502.10(B)(3)
(2) Exposed in dropped or suspended ceilings in other
than one- and two-family and multifamily dwellings. c. 504.20
Figure 334–5 (B) Type NM. Type NM cables cannot be used under the fol-
lowing conditions or in the following locations:
(1) Where exposed to corrosive fumes or vapors.
(2) Where embedded in masonry, concrete, adobe, fill, or
plaster.
(3) In a shallow chase in masonry, concrete, or adobe and
covered with plaster, adobe, or similar finish.
(4) Where subject or exposed to excessive moisture or damp-
ness.
Figure 334–5
Figure 338–3
Figure 338–2
Question: What size Type SE cable is required to supply a 10 kW, 240V (b) Exterior Installations. Service-entrance cable used for
single-phase fixed space heater with a 3A blower motor? The terminals exterior branch circuits or feeders must be installed in accor-
are rated 75°C. dance with Article 225.
(a) 2 AWG (b) 4 AWG (c) 6 AWG (d) 8 AWG
Author’s Comment: Type SE cable isn’t permitted in ducts,
Answer: (b) 4 AWG plenums, other environmental air spaces [300.22], or in patient
care areas [517.13].
Step 1: Determine the Total Load in Amperes
I = VA/E
I = 10,000W/240V + 3A
I = 44.67A
Step 2: Size Conductor and Protection.
According to 424.3(B), the ungrounded conductors and over-
current protection device for electric space-heating equipment
must be sized no less than 125 percent of the total heating
load. 44.67A x 1.25 = 56A
6 AWG, rated 65A at 75°C would be required with a 60A pro-
tection device
Figure 406–17
Figure 406–16
Figure 408–5
Figure 408–4
Figure 422–12
Figure 422–11
(A) General Requirements. (2) Motor Nameplate Current Rating (FLA). Overload devices
must be sized based on the motor nameplate current rating in
(1) Table Full-Load Current (FLC). The motor full-load accordance with 430.31.
current ratings listed in Tables 430.247, 430.248, and 430.250
are used to determine the conductor ampacity [430.22], the Author’s Comment: The motor nameplate full-load ampere
branch-circuit short-circuit and ground-fault protection rating is identified as full-load amperes (FLA). The FLA rating is
device size [430.52 and 62], and the ampere rating of discon- the current in amperes that the motor draws while producing its
necting switches [430.110]. rated horsepower load at its rated voltage, based on its rated
efficiency and power factor. Figure 430–6
Author’s Comment: The actual current rating on the motor
nameplate full-load amperes (FLA) [430.6(A)(2)] is not permitted
to be used to determine the conductor ampacity, the branch-
circuit short-circuit and ground-fault protection device size, nor
the ampere rating of disconnecting switches. Figure 430–5
• T able 430.247 Direct Current Motors (1) Table 430.52. Each motor branch circuit must be pro-
• Table 430.248 Single-Phase Motors tected against short circuit and ground faults by a protection
• Table 430.250 Three-phase motors device sized no greater than the following percentages listed
in Table 430.52.
Question: What size branch-circuit conductor is required for a 71⁄2 hp,
230V three-phase motor? Figure 430–9
Table 430.52
(a) 14 AWG (b) 12 AWG
Circuit Nontime Dual-Element Inverse-
(c) 10 AWG (d) none of these
Motor Type Delay Fuse Time Breaker
Answer: (c) 10 AWG
Wound Rotor 150% 150% 150%
Motor FLC = 22A [Table 430.250]
Direct Current 150% 150% 150%
Conductor’s Size = 22A x 1.25
All Other Motors 300% 175% 250%
Conductor’s Size = 2 7.5A, 10 AWG, rated 30A at 75°C
[Table 310.16]
Question: What size conductor and inverse-time circuit breaker are Question: What size conductor and inverse-time circuit breaker are
required for a 2 hp, 230V single-phase motor? Figure 430–18 required for a 71⁄2 hp, 230V three-phase motor? Figure 430–19
(a) 14 AWG, 30A breaker (b) 14 AWG, 35A breaker (a) 10 AWG, 50A breaker (b) 10 AWG, 60A breaker
(c) 14 AWG, 40A breaker (d) none of these (c) a or b (d) none of these
Figure 430–25
Figure 430–27
Figure 440–6
Author’s Comments:
Answer: (a) 12 AWG, 30A
• In accordance with 440.22(A), branch-circuit conductors must
have branch-circuit protection sized between 175 percent Step 1: Branch-Circuit Conductor [Table 310.16 and 440.32]
and 225 percent of the rated-load current to provide protec- 18A x 1.25 = 22.5A, 12 AWG, rated 25A at 75°C [Table
tion against short circuits and ground faults. 310.16]
• In accordance with 440.22(A), branch-circuit conductors must
have branch-circuit protection sized between 175 percent Step 2.: Branch-Circuit Protection [240.6(A) and 440.22(A)]
and 225 percent of the rated-load current to provide protec- 18A x 1.75 = 31.5A, next size down = 30A
tion against short circuits and ground faults. If the 30A protection device isn’t capable of carrying the start-
ing current, then the protection device can be sized up to 225
Question: What size conductor and protection device is required for an percent of the equipment load current rating. 18A x 2.25 =
18A motor compressor? Figure 440–7 40.5A, next size down 40A
(a) 12 AWG, 30A (b) 10 AWG, 50A
(c) a or b (d) none of these Author’s Comment: A 30A or 40A protection device is
permitted to protect a 12 AWG conductor. See 240.4(A) and
240.4(G) for details.
Figure 450–2