DISTRIBUTION SYSTEMS
Water Piping
and Pumps
PRESENTED BY:
Michael Ho
carriertdp@gmail.com
424-262-2144
Introduction
Section 1 – Introduction
Copyright © Carrier Corp. 2005
SECTION 2
Coil
Expansion
Tank
Two-Way
Pump 55° F Valve Three-Way
Valve
Includes:
• A chiller and/or a boiler
• Coils that produce cooling or heating
• Two or three-way valves to control the coils
• Piping and pump to circulate water
• An expansion tank (insignificant water contact with air)
Chiller
3 gpm/ton
Condenser
Water Pump 85° F
Cooling Tower
Source of Water to
Piping waste or
water (river)
source
Pump
Boiler
Typical
Heating-Only
Main Piping Loop
Supply and Return
System
(1 size throughout)
System
Pump
Supply
Piping
Boiler Return
Piping
System
Pump
Chiller
Chilled
Water
Supply
Hot
Water
Supply
Boiler
Special 3-pipe
Water Control
Common Return Piping
with Mixed Hot and
Cold Water
System
Chiller Pumps
Chilled
Water
Supply
Hot
Water
Supply
Boiler
System
Chiller Pumps
Supply
Return
Balancing Valves
• Water enters Unit-1 from supply
• Water leaves Unit-1 and returns directly to source
• The first unit supplied is the first returned
• Unequal circuit pressure drops result
• Circuit pressure drop through
Unit-1 < Unit-2 < Unit-3 < Unit-4 < Unit-5
• Balancing valves are a necessity
Section 4 – Direct and Reverse Return Systems
Copyright © Carrier Corp. 2005
Direct Return Vertical Distribution
Return
Supply
Unit-1 Unit-4
Unit-2 Unit-5
Unit-3 Unit-6
Balancing Valves
Supply
Return
Unit-1
Unit-2
Unit-3
Return
Supply
Unit-3
Unit-2
Unit-1
Return
Supply
Weld
Beveled Edge to
Accept Weld
Male
Thread
Thread
Joint
Female
Thread
Male
Tube Capillary
Space
(exaggerated)
Coupling
Clamp
Section 5 – Water Piping Components
and Accessories
Copyright © Carrier Corp. 2005
Various Fittings
Disc
Low cost, low
pressure drop
Disc
Waterflow
Body
Stem
Gland
Packing
Plug
Body Seat Ring
Waterflow
Body
Body
Stem
Bushing
Bonnet
Seat
Packing
Body
Waterflow
Plug
Waterflow
Body
• Low cost
• High capacity
• Low leakage
• Tight sealing
Waterflow
Waterflow
Lift Mechanism
Waterflow
2-Way Modulating
Section 5 – Water Piping Components
and Accessories
Copyright © Carrier Corp. 2005
TM
Circuit Setter
TM
Circuit Setters allow
for pre-set balancing of
waterflow
TM
Triple Duty Valve
on pump discharge
Combines shutoff,
balancing, and check
valve into one
assembly
Waterflow
one
direction
only
Strainers are
most important
in open loop
Mesh Strainer
systems
Section 5 – Water Piping Components
and Accessories
Copyright © Carrier Corp. 2005
Expansion Tanks
Open to Compressed
atmosphere Air Space Diaphragm
Air
Overflow Drain
Open Tank Closed Tank Closed Diaphragm Tank
• Open to air • Very popular • Flexible membrane
• Air-water interface • Captured air space • No air-water interface
• Air-water interface • Very popular
Diaphragm
• Very Popular
Lifting Ring
• Most Cost
Effective
Inlet
Tangential Stainless Steel
flow-thru design Air Collector Tube
Baffle
Outlet
NPT, Grooved
Vessel Shell or Flanged
(3 times the Connections
nominal inlet/outlet
pipe diameter) Vertical Strainer
with Bottom Access
4 Pipe
From Terminal Diameters
Coil
To Return Main
Locate thermometers
and gauges
at inlets and outlets
of equipment
Thermometer
(Typical)
Water-Cooled
Chiller
Condenser Chilled
Water Water
Drain
Drain Flange (Typical) Valve
Valve
Pressure Gauge (Typical)
Strainer (if pump is on return side of chiller)
Air-Cooled Chiller
Pressure
Gauge (Typical)
Return
Supply
Thermometer
Drain Valve (Typical)
Supply Return
Shutoff Valve
Shutoff Control Valve (2-Position On/Off,
Valve 2-Way Modulating or
3-Way Mixing)
Balancing Balancing Valve
Bypass Line Valve
used with 3-way (used with
mixing valve only mixing valve)
Air-Handling
Pete’s Plug
(Typical) Unit Coil
Drain
Valve
Flange
or Union
Check Valve
Drain Strainer
Valve
Minimum of 5 pipe diameters
for end suction pumps
44° F
54° F
44° F
64° F 44° F
54° F
Cooling
Cooling Air Handling Unit
Tower
Tower
Water-Cooled
Chiller
Condenser Chilled
Water Pump Water Pump
Cooling Cooling
Tower Tower
Water-Cooled
Chiller
Chilled Water
Pump
Condenser
Water Pump
Chilled Water
Pump
Water-Cooled
Condenser Chiller
Water Pump
Cooling Cooling
Tower Tower
Water-Cooled
Chiller
Equalization
Line
Automatic Isolation
Valves
Chilled
Water
Pumps
Condenser Water-Cooled
Chiller
Water Pumps
Hydraulic Alternate
Decoupler Bypass Line
(Bridge) minimum
chiller flow
Automatic
Isolation Valves
Control
Valve, sized
for minimum
chiller flow
Bypass
Flow Meter
Variable Speed
Primary Pumps
Cooling Method 1
Tower
Water-Cooled Chiller
Diverting
Valve
Condenser
Water Pump
Cooling Method 2
Tower
Water-Cooled Chiller
Diverting
Valve
Condenser
Water Pump
Cooling Method 3
Tower
Water-Cooled Chiller
Modulating
Valve
Condenser
Water Pump
• Capacity:
– Volume flow measured in
gallons per minute (gpm)
• Head: Feet
– Pressure at the base of a
column of water is usually
measured by the height of
the water column in feet
Pressure
Hd Hs Hd Hu
Hs
Pump
Discharge
A minimum positive
pressure (P) at the pump
(P) Pressure suction flange is required
at Suction to prevent cavitation,
Flange which is the formation of
vapor bubbles.
Impeller Eye
Bearings
Mechanical
Seal
Motor
Centrifugal
Impeller
Coupler Discharge
Shutoff
Pump Curve
Full Flow
Head - ft
Pipe
System Curve
Friction
Head
Static Head
Capacity - gpm
Section 8 – Pump Basics and Types of Pumps
Copyright © Carrier Corp. 2005
Effect of Overestimating Pump Head
Pump Head-
Capacity
Curve
overestimated head
System Head Actual gpm against
actual head
Actual bhp
Estimated bhp
Capacity - gpm
Section 8 – Pump Basics and Types of Pumps
Copyright © Carrier Corp. 2005
Parallel Pumps (Two Identical Pumps)
H
Single Parallel
Pump Pump
Curve Curve
gpm 2 gpm 2
gpm 1 gpm 1
gpm
• Two identical pumps in parallel
• Resulting gpm doubles
• Plot result to obtain parallel pump curve
Section 8 – Pump Basics and Types of Pumps
Copyright © Carrier Corp. 2005
Series Pumps (Two Identical Pumps)
H1 H2
Series
Pump
Single Curve
Pump
Curve Head 1
Head 2
Head 1
Head 2
gpm
• Two identical pumps in series
• Resulting head doubles
• Plot result to obtain series pump curve
Section 8 – Pump Basics and Types of Pumps
Copyright © Carrier Corp. 2005
Variable Speed Pumping
System Curve
Capacity - gpm
• As control valves modulate, the differential pressure across supply and
return lines rises sending signal to VFD to modulate pump speed
• Operating point moves along system curve to new rpm line
(points A - B - C)
• According to the pump affinity laws the energy savings
is a cubed function of the ratio of the pump speeds
Section 8 – Pump Basics and Types of Pumps
Copyright © Carrier Corp. 2005
Pump Selection Process
1. Determine cooling or 6. Flat curved pumps for
heating loads to be closed systems with
pumped control valves
2. Find load gpm from 7. Steep curved pumps for
equipment selections open systems
3. Find total pumping gpm 8. Find final operating point
4. Establish most resistant 9. Check for start-up
pumping path in loop conditions
5. Select pump from 10. Select motor accordingly
manufacturer’s data
100 ft
1000 gpm
Screen Capture courtesy of:
Suction Size = 6” Max Imp Dia = 9” Design Capacity = 1000.0 ITT Bell & Gossett
Discharge Size = 5” Max Imp Dia = 11” Design Head = 100.0 Feet 8200 N. Austin
Cut Dia = 10.875” Motor Size = 40 HP Morton Grove, Il 60053
Motor
Pump
Assembly
Suction
Vertical Suction
and Discharge
Close-
2 2,300 gpm @ 400 ft 2 4
Coupled
End
3 4,000 gpm @ 500 ft 3 1
Suction
Vertical
4 9,000 gpm @ 400 ft 4 2
Split Case
Horizontal
Highest 5 40,000 gpm @ 600 ft Most 5 Good 3
Split Case
3’
Cooling Condenser Loop
Tower
5’ 37’
300 gpm
Water-Cooled Chiller
28’ Located on
150 gpm 10’ ground floor
per pump
10’ 5’
10’ 5’
5’
5’ 5’
10’
5’ C
10’
H
Section 9 – Pump Sizing and
Pump Selection Example
Copyright © Carrier Corp. 2005
Step 5 – Size Pipe & Find Friction Rate for Condenser Water Loop
Using Chart 2,
size the pipe and find
the friction rate
per 100 ft
3’
Cooling Condenser Loop
Tower
Find longest circuit pressure drop
by adding all fittings and pipe lengths
5’ 37’
300 gpm
Water-Cooled Chiller
28’ Located on
10’ ground floor
10’ 5’
10’ 5’
5’
5’ 5’
10’
5’
10’ C
H
Section 9 – Pump Sizing and
Pump Selection Example
Copyright © Carrier Corp. 2005
Step 7 – Sum Pressure Drops for Pump Selection
66 ft
150 gpm
Screen Capture courtesy of:
Pump Series: 1510 Max Imp Dia = 7” Design Capacity = 150.0 ITT Bell & Gossett
Suction Size = 2.5” Max Imp Dia = 9.5” Design Head = 66.0 8200 N. Austin
Discharge Size = 2” Cut Dia = 8.375” Motor Size = 5 HP Morton Grove, Il 60053
66 ft
300 gpm
Screen Capture courtesy of:
Pump Series: 1510 Max Imp Dia = 7” Design Capacity = 150.0 ITT Bell & Gossett
Suction Size = 2.5” Max Imp Dia = 9.5” Design Head = 66.0 8200 N. Austin
Discharge Size = 2” Cut Dia = 8.375” Motor Size = 5 HP Morton Grove, Il 60053
The Power and Eff. Curves shown are only for single pump operation.
Section 9 – Pump Sizing and
Pump Selection Example
Copyright © Carrier Corp. 2005
Step 8 – Size Pipe & Find Friction Rate for Chilled Water Loop
Summary
Section 10 – Summary
Copyright © Carrier Corp. 2005
Work Session
Work Session
3. What are the 4 types of valves that can be used for balancing/throttling?
1. ___________________________________________
2. ___________________________________________
3. ________________________ ____
Work Session
Copyright © Carrier Corp. 2005
Technical Development Program
Thank You
This completes the presentation.