RESIDENTIAL REPORT
1929 Parkwood Ave
Central Point OR 97502
Paul & Tammie Skinner
MARCH 26, 2019
Inspector Agent
Ian Miller Alice Lema
OCHI# 2214 John L. Scott - Medford
5414992125 541-301-7980
ian@rogueinspection.com alicelema@alicelema.com
Table of Contents
Table of Contents 2
SUMMARY 5
1: INSPECTION DETAILS 7
2: EXTERIOR 8
3: ROOF 16
4: FOUNDATION, CRAWLSPACE & STRUCTURE 20
5: HVAC 23
6: FIREPLACE 27
7: PLUMBING 28
8: ELECTRICAL 31
9: ATTIC, INSULATION & VENTILATION 35
10: INTERIOR, DOORS, & WINDOWS 37
11: BUILT-IN APPLIANCES 41
12: GARAGE 44
13: PEST INSPECTION 46
Introduction:
The following numbered and attached pages are your home inspection report. The
report includes pictures, information, and recommendations. This inspection was
performed in accordance with the current Standards of Practice and Code of Ethics of
InterNACHI (International Association of Certified Home Inspectors). The Standards
contain certain and very important limitations, expectations and exclusions to the
inspection. A copy is available upon request.
Scope:
A home inspection is intended to assist in evaluating the overall condition of the
dwelling. The inspection is based on observation of the visible, readily accessible and
apparent condition of the structure and its components on this day. The results of
this inspection are not intended to make any representation regarding the presence
or absence of concealed defects that are not reasonably ascertainable or readily
accessible in a competently performed inspection. No warranty, guarantee or
insurance by Rogue Inspection Services, LLC is expressed or implied. This report does
not include inspection for wood destroying insects, mold, lead or asbestos. A
representative sampling of the building components is viewed in areas that are
accessible at the time of the inspection. No destructive testing or dismantling of
components is performed. Not all defects will be identified during this inspection.
Unexpected repairs should be anticipated. The person conducting your inspection is
not a Structural Engineer or other professional whose license authorizes the
rendering of an opinion as to the structural integrity of a building or its other
component parts. You are advised to seek two professional opinions and acquire
estimates of repair as to any defects, comments, improvements or recommendations
mentioned in this report. Rogue Inspection Services, LLC recommends that the
professional making any repairs inspect the property further, in order to discover and
repair related problems that were not identified in the report. We recommend that all
repairs, corrections and cost estimates be completed and documented prior to
closing or purchasing the property. Feel free to hire other professionals to inspect the
property prior to closing, including Qualified HVAC, Plumbing, Electrical, Engineering
and Roofing Contractors.
Use of photos:
Your report includes many photographs which help to clarify where the inspector
went, what was looked at, and the condition of a system or component at the time of
the inspection. Some of the pictures may be of deficiencies or problem areas, these
are to help you better understand what is documented in this report and may allow
you see areas or items that you normally would not see. A pictured issue does not
necessarily mean that the issue was limited to that area only, but may be a
representation of a condition that is in multiple places. Not all areas of deficiencies or
conditions will be supported with photos.
Inspected (IN) = I visually observed the item, component or unit and if no other
comments were made then it appeared to be functioning as intended allowing for
normal wear and tear.
Not Inspected (NI) = I did not inspect this item, component or unit and made no
representations of whether or not it was functioning as intended and will state a
reason for not inspecting.
Not Present (NP) = This item, component or unit is not in this home or building.
Deficiency (D) = The item, component or unit is not functioning as intended, or needs
further inspection by a qualified contractor. Items, components or units that can be
repaired to satisfactory condition may not need replacement.
105 4 25 1
ITEMS INSPECTED MINOR/MAINTENANCE ISSUE RECOMMENDATION SIGNIFICANT/SAFETY
CONCERN
2.1.1 Exterior - Siding, Flashing & Trim: Caulking Substandard / Missing / Deteriorated
2.1.2 Exterior - Siding, Flashing & Trim: Dry Rot - Siding
2.1.3 Exterior - Siding, Flashing & Trim: Evidence Of Water Intrusion
2.1.4 Exterior - Siding, Flashing & Trim: Failing Paint - Repair
2.1.5 Exterior - Siding, Flashing & Trim: Seal Gaps
2.1.6 Exterior - Siding, Flashing & Trim: Siding / Deteriorated / Damaged / Warped
2.3.1 Exterior - Eaves, Soffits & Fascia: Fascia - Dryrot
2.4.1 Exterior - Sidewalks, Patios & Driveways: Driveway Cracking / Deterioration - Monitor
2.4.2 Exterior - Sidewalks, Patios & Driveways: Sidewalk / Patio Crack / Deterioration - Monitor
2.4.3 Exterior - Sidewalks, Patios & Driveways: Negative Grade/Standing Water In Crawlspace
2.6.1 Exterior - Decks & Steps: Deck Boards Near End Of Life
2.9.1 Exterior - Vegetation : Vegetation In Contact With Building
3.1.1 Roof - Coverings: Seal Fasteners
3.2.1 Roof - Roof Drainage Systems: Downspout Leaking
3.2.2 Roof - Roof Drainage Systems: Downspouts Drain Near House
3.2.3 Roof - Roof Drainage Systems: Gutter Leakage
4.1.1 Foundation, Crawlspace & Structure - Foundation: Efflorescence
4.2.1 Foundation, Crawlspace & Structure - Crawlspace: High Moisture Levels
4.2.2 Foundation, Crawlspace & Structure - Crawlspace: Standing Water
8.2.1 Electrical - Panels: Federal Pacific / Stab-Lok
8.6.1 Electrical - GFCI & AFCI: No GFCI Kitchen/Master Bathroom Outlet
8.7.1 Electrical - Smoke Detectors: Additional Smoke Detectors
9.5.1 Attic, Insulation & Ventilation - Exhaust Systems: Dryer Damper Missing
10.3.1 Interior, Doors, & Windows - Floors: Vinyl Flooring In Master Bathroom Bubbling
10.7.1 Interior, Doors, & Windows - Countertops & Cabinets: Countertop Water Damage
10.7.2 Interior, Doors, & Windows - Countertops & Cabinets: Poor/Missing Caulk
10.8.1 Interior, Doors, & Windows - Bathrooms: Countertop - Damaged
10.8.2 Interior, Doors, & Windows - Bathrooms: Shower Door - Damaged Seal
Weather Conditions
Cloudy
Limitations
General
OCCUPIED HOME
Homes that are occupied at the time of inspection may have conditions that change from the time of
inspection to the time of the closing. It would be wise for the prospective home owner to perform a walk
through inspection after the home has been vacated to determine if there are any conditions that may
have changed.
General
PHOTOS ARE REPRESENTATIVE
Photos are only a representative sample of conditions observed. There may be more than one area of
concern not shown by photo
General
PRE- 1980 HOME
Homes built before 1980 have an increased chance of containing materials like asbestos and lead. These
materials typically don't pose any threat unless they're improperly disturbed, so if you do ever plan on any
remodeling or demolition, you should plan for additional costs related to testing and remediation, and
always hire a certified professional before doing any work yourself.
Information
Siding, Flashing & Trim: Siding Exterior Doors: Exterior Entry Sidewalks, Patios & Driveways:
Material Door Approachment
Engineered Wood Steel, Wood Sidewalk
Sidewalks, Patios & Driveways: Decks & Steps: Appurtenance Decks & Steps: Material
Driveway Material Deck Wood
Concrete
Grounds: Grounds
Level
Limitations
Deficiencies
Information
Limitations
General
LEAKS UNPREDICTABLE
Roofs are designed to shed water like an umbrella and are not waterproof. In events of wind driven rains,
and periods of intense rain, water can sometimes blow into areas such as ridge vents, roof vents and
valleys and present leaking conditions. This occurrence is rare, but can possibly happen in severe storm
events. Unless it is raining at the time of inspection, some roof leaks may not be identified during the
inspection process.
Deficiencies
Information
Floor Structure: Floor Structure Floor Structure: Sub-floor Ceiling Structure: Ceiling
Wood Beams Plank Structure
2x4
Roof Structure & Attic: Attic Info Roof Structure & Attic: Material Roof Structure & Attic: Method
Bedroom Plywood of Observation
Attic Hatch Walked
Limitations
Crawlspace
CRAWL SPACE LIMITATIONS
Structural components such as joists and beams, and other components such as piping, wiring and/or
ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does
not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning
or spacing. The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces
in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of
all types of weather conditions (e.g. heavy rain) would be needed to do so.The inspector attempts to locate
all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings
or stored items. In such cases, the client should ask the property owner where all access points are that are
not described in this inspection, and have those areas inspected. Note that crawl space areas should be
checked at least annually for water intrusion, plumbing leaks and pest activity.
Deficiencies
Information
Heating Equipment: Brand Heating Equipment: Energy Heating Equipment: Heat Type
Lennox Source Forced Air, Heat Pump
Electric
Thermostat & Filters: Filter Thermostat & Filters: Filter Size Thermostat & Filters: Filter Type
Location 16x20 Disposable
Hallway
Many factors including preventive maintenance, consistency of use, and load demand can play a large factor in
the life expectancy of a heating system. Towards the end of a units life, expect to have increased energy usage
and maintenance cost.
Many factors including preventive maintenance, consistency of use, and load demand can play a large factor in
the life expectancy of a cooling system. Towards the end of a units life, expect to have increased energy usage
and maintenance cost.
Limitations
General
HVAC LIMITATIONS
HVAC
The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters;
solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions;
heating components concealed within the building structure or in inaccessible areas; underground utilities
and systems; safety devices and controls (due to automatic operation). Any comments made regarding
these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life
on heating or cooling system components, does not determine if heating or cooling systems are
appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to
be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency
switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are
intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be
monitored while in operation in the future. Where buildings contain furnishings or stored items, the
inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms,
kitchens and living/dining rooms).
Information
Limitations
Information
Drain, Waste, & Vent Systems: Supply Lines & Fixtures: Water Heater: Capacity
Material Distribution Material 50 gallons
ABS Copper
Limitations
Sump Pump
RECOMMEND INSTALLING SUMP PUMP
CRAWLSPACE
Due to the condition of the crawlspace during the initial inspection, it is recommend that a sump pump be
installed in the crawlspace to reduce the moisture level after periods of heavy rainfall.
Information
Service Entrance: Electrical Panels: Main Panel Location Panels: Panel Capacity
Service Conductors Garage 200 AMP
Below Ground, 220 Volts
Panels: Panel Manufacturer Panels: Panel Type Panels: Sub Panel Location
Federal Pacific Circuit Breaker None
Deficiencies
For many years NFPA 72, National Fire Alarm and Signaling Code, has required as a minimum that smoke
Rogue Inspection Services LLC Page 33 of 46
For many years NFPA 72, National Fire Alarm and Signaling Code, has required as a minimum that smoke
alarms be installed inside every sleep room (even for existing homes) in addition to requiring them outside
each sleeping area and on every level of the home. Recommend installing smoke detectors in sleeping
rooms. Recommend installing per manufacture recommendations.
Recommendation
Recommended DIY Project
Information
Attic Insulation: Attic Insulation Attic Insulation: Insulation Type Floor insulation : Floor
Attic Fiberglass, Loose-fill insulation
The attic insulation was Aluminum sheet
sufficient.
Exhaust Systems: Dryer Power Exhaust Systems: Dryer Vent Exhaust Systems: Exhaust Fans
Source Metal - Flex Fan with Light
220 Volt
Deficiencies
Information
Limitations
General
COSMETIC ISSUES NOT ADDRESSED
Issues that are considered as cosmetic are not addressed in this report. (Holes, stains, scratches,
unevenness, missing trim, paint and finish flaws or odors). It is not the intent of this report to make the
house new again.
Deficiencies
Information
Dishwasher: Working
Kitchen
The dishwasher was in good working condition at the time of inspection. It was run on a rinse cycle.
Range/Oven/Cooktop: Working
Kitchen
The cooktop and oven were tested and in good working condition at the time of inspection.
Information
Garage Door: Material Overhead Door & Opener: Brand Overhead Door & Opener:
Metal, Insulated Genie Material
Metal, Insulated
Deficiencies
Information
Evidence Type
NONE NONE
Limitations
General
FUTURE INFESTATIONS
Future infestations of vermin, insects or other animal activity can not be known or predicted.