Vous êtes sur la page 1sur 6

The following article was published in ASHRAE Journal, August 2002.

© Copyright 2002 American Society of Heating, Refrigerating and Air-


Conditioning Engineers, Inc. It is presented for educational purposes only. This article may not be copied and/or distributed electronically or in
paper form without permission of ASHRAE.

By Lewis G. Harriman III, Member ASHRAE, and James Judge, P.E., Member ASHRAE

n recent years, commercial and institutional building owners have stant-volume DX cooling unit removes
I been more willing to invest in dehumidification equipment. Per-
haps, they have been sensitized by litigation regarding indoor air qual-
very little moisture although moisture
loads remain high. The compressor does
not run long enough to make condensed
ity problems that seem related to moisture. Or, perhaps their inter- moisture actually drip off the coil and
into the drain.
est is prompted by comfort problems caused by the moisture load
This problem can be seen in Figure 1,
from higher ventilation rates. which shows the measured dehumidifi-
cation performance of a 3-ton
When the client’s goals in- Measured Cooling Coil Performance @ Rated Conditions (11 kW) cooling unit con-
10
clude humidity control, as op- trolled by temperature alone.1
posed to humidity moderation, The compressor operated for
Latent Capacity (1,000 Btu/h)

manufacturers offer many ON Cycle


only 12 minutes of the 50-
5
novel dehumidification tech- Moisture minute test. When the com-
nologies. This article de- Removal pressor was operating, the coil
scribes three of these condensed moisture, remov-
products, and suggests some 0 ing it from the air. However,
OFF Cycle
techniques a designer might Moisture when the compressor
use to assess the costs and Addition switched off, most of that con-
typical performance for dehu- –5 densed moisture was still on
midif iers in different cli- the coil. Therefore, it re-
mates. First, it may be helpful Compressor evaporated back into the air
to consider why buildings –10 from the coil surface. The
0 10 20 30 40 50
served by thermostatically unit’s dehumidification ca-
Time (min)
controlled cooling equipment pacity is then zero.
Figure 1: After the compressor shuts off, moisture condensed
may have difficulty control- on the cooling coil re-evaporates.1 Henderson’s research sug-
ling humidity. gests that until the run-time
ume direct expansion (DX) cooling sys- exceeds 40% of each hour, the moisture
Ineffective Dehumidification tem only operate for a short portion of removal of a conventional cooling unit
In commercial buildings without de- each hour. As soon as the thermostat is is so small as to be negligible.1
humidifiers, excess humidity may be- satisfied, the compressor shuts off, the Short run times explain why cooling
come a problem during “off-peak” coil stops dehumidifying, and moisture About the Authors
hours—when a building’s sensible heat remaining on its surface can re-evapo- Lewis G. Harriman III is director of research
load is low, but its moisture load remains rate back into the air. At the same time, and consulting at Mason-Grant, Portsmouth, N.H.
high. humid ventilation air flows through that He was the principal investigator for ASHRAE
When the sensible load in the space inactive coil, flooding the building 1047-RP: Development of a Design Guide for
Humidity Control in Commercial Buildings.
is low, the compressors in a typical ther- with excess humidity. The net result is James Judge, P.E., is a principal at LINRIC Com-
mostatically controlled, constant-vol- that when sensible loads are low, a con- pany, Bedford, N.H.

22 August 2002|ASHRAE Journal


Dehumidification

Figure 2: The
largest moisture
load in most
commercial
buildings comes
from the ventila-
tion air.

equipment sized for peak sensible loads and controlled by a the reasons described earlier. Consequently, a dehumidifier
thermostat is not effective in controlling excess humidity. will be most effective if it dries the ventilation air, continu-
Unfortunately, many designers compound this problem by ously removing the largest and most constant moisture load
adding cooling capacity when they see that moisture loads from the rest of the system.
will be high, perhaps under the misimpression that extra ca- That’s why the authors chose to describe three types of
pacity somehow removes moisture. It won’t. Extra cooling dehumidification equipment that are specifically designed
capacity does not remove moisture when the cooling coil is for the difficult task of drying 100% outdoor air.
controlled by the thermostat, as shown in Figure 1.
Undersizing the cooling equipment for the peak sensible load Ventilation Air Dehumidifiers
would be a slightly better strategy to moderate high humid- During the last 10 years, manufacturers have been actively
ity. The compressor would run longer to remove the sensible developing new dehumidification equipment. The alterna-
load, increasing dehumidification at the same time. tives discussed here are not the only commercial dehumidi-
Usually, however, undersizing for the peak sensible load is fication choices, but they all handle 100% outdoor air and
not acceptable. When a building’s owner needs humidity con- are each available from at least two manufacturers. Figure 3
trol rather than just moderation, adding a dedicated dehu- shows three types of rooftop dehumidifiers that meet these
midifier and humidistat is the most effective approach. criteria. They represent commercial rather than scientific in-
In most commercial buildings, the dehumidifier is placed novations—lower-cost and more fault-tolerant combinations
on the incoming ventilation airstream. That way, excess mois- of established mechanical and desiccant-based dehumidifi-
ture is removed before it spreads throughout the building. cation technology.

Location of Dehumidifiers Type 1: Mechanical Dehumidifier with Passive Desiccant


Passive
Legend has it that when Willie Sutton, the notorious bank Wheel
robber was asked why he robbed banks, he replied, “Because This equipment uses a passive desiccant wheel to recover
that’s where the money is.” Similarly, dehumidifiers are usu- the cooling and dehumidification effect contained in the
ally placed on the incoming makeup air because that’s where building’s exhaust air. The passive desiccant wheel adsorbs
most of the moisture is. moisture and heat from the incoming air, reducing the load
Figure 2 illustrates this point. It shows a moisture load on the dehumidifier whenever the wheel is turning, provided
estimate for a medium-size retail store located in Atlanta dur- that the exhaust air is drier than the outdoor air.
ing 0.4% dew-point conditions. (The moisture load is likely At peak sensible load conditions, this combination costs
to be exceeded for only 35 hours in a typical year.) It’s obvi- less to operate than the other ventilation dehumidifier de-
ous that the ventilation moisture load is greater than all other scribed later, because of the partial moisture load reduction
loads combined. ANSI/ASHRAE Standard 62-2001, Ventila- accomplished by the passive desiccant wheel (aka: enthalpy
tion for Acceptable Indoor Air Quality, recommends this level wheel, total heat wheel or rotary enthalpy heat exchanger).
of ventilation, and most local building codes require the Also, compared to the other types shown here, this equip-
ASHRAE-recommended air quantities as the minimum ac- ment is often the most economical to purchase.
ceptable ventilation rate. It is especially important to note It has some limitations, including that it cannot operate
the nature of this load element. During occupied hours, the without exhaust air. Performance depends on the dryness of
ventilation load is continuous. However, the loads from the exhaust, and the exhaust air ductwork must be brought
people, opening doors and infiltration are intermittent. back to the unit. Also, the unit will need reheat to avoid
If the moisture load from ventilation air is allowed to blend delivering air that is too cold for the space. Finally, during
into the return airstream, the simple, constant-volume DX many hours of the year the wheel may not turn. If it did, it
cooling units will have a very difficult time removing it for would recover unwanted heat from the exhaust air. When the

ASHRAE Journal|August 2002 23


Type 1

Type 2

Type 3

Figure 3: Recent commercial innovations for ventilation dehumidification.

wheel is not turning, it does not reduce the moisture load on that is dried with a mechanical dehumidifier. Heat pipes, coil
the dehumidifier. So ironically, operating costs for this type runaround loops and plate-type heat exchangers have been
of equipment can sometimes be highest during part-load used for this purpose.
weather conditions when the passive desiccant wheel is not Because of the second pass through the heat exchanger,
operating. this equipment delivers air closer to the indoor temperature
than the Type 1 configuration. Also, since the Type 2 unit’s
Type 2: Mechanical Dehumidifier with Sensible Heat performance does not require dry exhaust air, this
Exchanger equipment can dry the ventilation air any time the humidity
Avoiding any need for exhaust air, this design uses an air- rises above setpoint. So, it is often configured to control
to-air heat exchanger to pre-cool and reheat the outdoor air humidity rather than just moderate the extreme as in the Type

24 August 2002|ASHRAE Journal


Dehumidification

Figure 4: Using TMY observations to determine the mode (the most typical) outdoor moisture content when the dry-bulb
temperature is 75°F (24°C).2

1 configuration. tion has two compressors, which are staged, and the desiccant
Also, the supply fan must overcome the friction of two wheel can be stopped while the mechanical DH section con-
passes through a heat exchanger. This friction, plus the extra tinues to operate. This allows a close match between chang-
dehumidification work for more hours of the year, sometimes ing loads and energy use. Finally, the air leaves the unit much
makes this equipment more costly to operate. Of course, it’s closer to the indoor air temperature than is the case with
usually doing more work than the Type 1 system. desiccant-only equipment. So, the overall performance of this
configuration is quite impressive in terms of all-weather deep-
Type 3: Two-stage Desiccant/Mechanical Dehumidifier
Two-stage drying capacity as well as low operating costs.
This two-stage equipment uses the condenser heat from a Limitations of this configuration include the fact that the
mechanical dehumidifier to reactivate an active desiccant supply air temperature changes according to how much dry-
wheel. First, ventilation air is precooled and partly dried by ing the desiccant wheel does. So the leaving air temperature
the mechanical dehumidifier. Then the air is dried more deeply from this equipment is neither constant nor controllable.
and also reheated by the desiccant wheel.
This arrangement uses both technologies at favorable Evaluating Ventilation Dehumidifiers
points of performance. Mechanical dehumidifiers are most In commercial HVAC, the needs are very diverse, and so are
effective and economical at higher inlet conditions, and des- the equipment offerings. Any comparison between compet-
iccants gain advantages at cooler and more saturated condi- ing offerings will be specific to a particular set of economic
tions. Also, in this arrangement the heat normally wasted in a and geographic circumstances. The authors would suggest
mechanical dehumidifier is put to productive use drying the that, at the very least, the vendors should be willing to pro-
desiccant wheel. Further, the design allows several stages of vide the designer with the answers to these questions:
capacity modulation. The mechanical dehumidification sec- • What does the unit cost?

ASHRAE Journal|August 2002 25


Figure 5: A two-stage desiccant/mechanical ventilation dehumidifier at 2% dew-point design, and part-load conditions.

• How does it perform at peak dew-point design? (How typical of the bulk of the operating hours than its perfor-
much moisture will it remove from the ventilation air and mance at the peak load.
from the building itself?) As far as the authors are aware, no general agreement exists
• What is the performance at the more common part-load on what constitutes a reasonable and consistent off-peak con-
condition? dition with which to test dehumidifier performance and en-
• How much energy does it use at part-load condition? ergy use. The authors have a suggestion that other designers
The unit’s price is obviously important. Its moisture re- may wish to consider.
moval is equally so, and is useful to note that the perfor-
mance questions really have two parts. Ventilation Part-Load Dehumidification Design Conditions
dehumidifiers remove moisture from incoming air. Also, at Chapter 27 of the 2001 ASHRAE Handbook—Fundamen-
some outdoor conditions, they deliver dry air somewhat be- tals notes that the peak dehumidification design condition
low the indoor design dew point, dehumidifying the space as is a useful checkpoint for part-load cooling conditions. That
well. However, that is not always the case. seems logical, since at the peak moisture, the sensible heat
Under other conditions, the unit may not dry the ventila- load is much reduced. Checking a cooling system’s perfor-
tion air deeply enough to remove any moisture from the build- mance at that point makes sense, because the calculation
ing. The vendor needs to quantify moisture removal from the could expose limitations of control system logic or limita-
space itself as well as the delivered air temperature. With that tions of equipment capacity modulation. The handbook
information, the designer can adapt the rest of the system to makes no similar suggestion of a part-load condition for high-
take advantage of the dehumidifier’s strengths and compen- lighting any limitations of dehumidification systems.
sate for any limitations. We propose a latent part-load design point (the “LPL”) at
Further, although the energy use at peak design is useful which the ventilation load is entirely latent. That is to say,
information, the more important figure is the typical hourly the point when the outdoor dry bulb is the same as the tem-
energy use. In other words, the energy consumed for 98% of perature in the space, so any load from ventilation air in-
the operating hours instead of for just 2% of them. When volves removing moisture alone. To find out how much
possible, an 8,760-hour building simulation will provide the moisture is probable, one can examine the typical hourly
best estimates of operating costs. However, not all projects weather for that location, and determine the “most common”
have design budgets that justify such analysis. Another ap- moisture content of the ventilation air when the outdoor dry
proach is to have the vendor calculate the performance and bulb temperature is neutral. This produces an LPL design
energy use at some “off-peak” condition, which may be more point below the peak sensible and moisture loads, and as

26 August 2002|ASHRAE Journal


Dehumidification

such it allows examination of the “more usual” behavior of to require running both compressors in the dehumidifier. So
the dehumidifier. the total energy does not change. In either Honolulu or Chi-
Figure 4 shows how one can use TMY weather data to con- cago, however, the unit easily achieves the required moisture
struct this off-peak design point for moisture. TMY weather removal with a single compressor, so the typical running en-
data was constructed by the U.S. Department of Energy. It ergy reduces from 9.8 kWh to 5.9 kWh.
contains a full year of hourly observations (8,760 hours). The Also, consider the difference in moisture removal from the
data were selected from the long-term record, and are repre- space at peak load compared to the latent-part-load condi-
sentative of the typical weather pattern at each location.3 tions. Under Miami peak loads, this particular unit does not
First, the full year’s hourly observations of dry-bulb tem- quite bring the outdoor air to a neutral humidity ratio. The
perature and humidity ratio are extracted from the TMY record. 2,000 cfm (944 L/s) of ventilation air still adds about 8 lb/h
Then, the hours are sorted by dry-bulb temperature. Hours (3 kg/h) to the internal moisture load. But at the more com-
when the temperature is between 74.5°F and 75.5°F (23°C mon part-latent-load condition, the equipment dries the in-
and 24°C) are selected for further analysis. The mode (the coming air deeply enough to remove 17 lb/h (6 kg/h) from
most common) of the selected humidity ratios is calculated the space. Given this performance at the more frequent part-
for that range. The latent part-load condition is then 75°F load conditions, the designer might consider whether the
(24°C) with the mode of the humidity ratios that occur at that cooling system can remove any remaining moisture load dur-
temperature. Figure 4 shows the results for Miami. The red ing the few hours of the peak load condition.
horizontal bars on the chart show the number of hours each By asking vendors to quantify part-load performance, the
humidity ratio occurs when the temperature is between 74.5°F designer obtains a better feel for the typical behavior of the
and 75.5°F (23°C and 24°C). Underneath the bars, the color- system with respect to energy consumption and indoor hu-
coded dots indicate the binned TMY hourly observations for midity. The answer to the part-load performance question is
all 8,760 hours of a typical year in Miami. also a way to find out if the vendor has really considered how
Using the mode of humidity ratios for the selected dry- the equipment will modulate and perform under typical rather
bulb temperature range has some advantages. In most loca- than extreme operating conditions. When 8,760-hour analy-
tions, the mode gives higher values than either the mean sis is not practical, quantifying part-load performance at a
(average) or the median (mid-point) of the range. At the mode, single point is a useful way for both the designer and the
the ventilation air is still likely to carry a moisture load with manufacturer to better understand what the building’s occu-
respect to the control point in the building. On the other pants will experience most of the time.
hand, in high altitude or desert climates, the humidity ratio
mode at 75°F (24°C) is likely to show that the dehumidifier Summary
will seldom operate. In those climates, it may be more appro- The case for dehumidifying the ventilation air is strong
priate to compare offerings based on energy use at the peak because air carries the largest part of the building’s total mois-
load, since that condition may be most representative of the ture load. Given the current focus on humidity control, equip-
hours the system will actually operate. ment manufacturers are likely to offer these and other
Figure 5 helps illustrate this point. The 2% dew-point de- innovative ventilation dehumidifiers more widely. Part-load
sign value for Phoenix is surprisingly similar to the more performance analysis is a useful tool to crosscheck a unit’s
humid climate of Chicago. But at the suggested LPL, it’s typical moisture removal effectiveness compared to its more
clear that Chicago usually has a moisture load while that is brief operation at the peak design condition.
seldom the case when the outdoor temperature is 75°F (24°C)
in Phoenix. References
Figure 5 shows how the answers to the questions suggested 1. Henderson, H. 1998. “The impact of part-load air conditioner
earlier help the designer understand how geography affects a operation on dehumidification performance: Validating a latent capac-
ity degradation model.” Proceedings of the 1998 ASHRAE Indoor Air
dehumidification offering. (Note: The results in the table come Quality Conference.
directly from one of the manufacturers of the third equipment 2. Judge, J. 2002. PsycPro™. Psychrometric chart and weather
alternative: the two-stage mechanical/active desiccant dehu- summary program.
midifier. The authors have no means of validating that perfor- 3. Harriman, L.G., G. Brundrett, R. Kittler. 2001. Humidity Con-
mance data independently. So we suggest this particular trol Design Guide For Commercial and Institutional Buildings.
ASHRAE.
information is most useful for understanding the geographic
performance variation of Type 3 equipment, rather than being
Bibliography
useful for comparisons with competing technologies.)
Hickey, D. 2001. “Focus on humidity control.” ASHRAE Journal
Consider the difference in part-load performance of this 43(10):10–11.
particular equipment in Atlanta compared to either Hono- Novosel, D. and D. Munn. 2001. “Design phase commissioning
lulu or Chicago. In Atlanta, the part load is still high enough for dehumidification.” HPAC Engineering Magazine October.

ASHRAE Journal|August 2002 27

Vous aimerez peut-être aussi