Air System Sizing Summary for Cognizant lab

Project Name: Cognizant 03/03/2019


Prepared by: Student 04:43PM

Air System Information


Air System Name ................................... Cognizant lab Number of zones ............................................................. 1
Equipment Class ........................................ PKG ROOF Floor Area ................................................................. 246.0 m²
Air System Type ..................................................... VAV Location .......................................................... Pune, India

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing ........................ Peak zone sensible load
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 125.4 kW Load occurs at ..................................................... Jul 1700
Sensible coil load ................................................... 97.4 kW OA DB / WB ...................................................... 40.9 / 24.7 °C
Coil L/s at Jul 1700 ................................................ 6075 L/s Entering DB / WB ............................................. 26.7 / 17.6 °C
Max block L/s at Jul 1800 ...................................... 6453 L/s Leaving DB / WB .............................................. 12.5 / 10.9 °C
Sum of peak zone L/s ........................................... 6453 L/s Coil ADP ....................................................................... 8.9 °C
Sensible heat ratio ............................................... 0.776 Bypass Factor .......................................................... 0.200
m²/kW ....................................................................... 2.0 Resulting RH ................................................................. 43 %
W/m² ..................................................................... 509.9 Design supply temp. ................................................... 12.8 °C
Water flow @ 5.6 °K rise ......................................... N/A Zone T-stat Check .................................................... 1 of 1 OK
Max zone temperature deviation .................................. 0.0 °K

Supply Fan Sizing Data

Actual max L/s at Jul 1800 .................................... 6453 L/s Fan motor BHP ........................................................... 2.90 BHP
Standard L/s .......................................................... 6036 L/s Fan motor kW ............................................................. 2.30 kW
Actual max L/(s-m²) .............................................. 26.23 L/(s-m²)

Return Fan Sizing Data

Actual max L/s at Jul 1800 .................................... 6453 L/s Fan motor BHP ........................................................... 1.89 BHP
Standard L/s .......................................................... 6036 L/s Fan motor kW ............................................................. 1.50 kW
Actual max L/(s-m²) .............................................. 26.23 L/(s-m²)

Outdoor Ventilation Air Data


Design airflow L/s .................................................. 1053 L/s L/s/person ................................................................... 5.82 L/s/person
L/(s-m²) ................................................................... 4.28 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 13


Zone Sizing Summary for Cognizant lab
Project Name: Cognizant 03/03/2019
Prepared by: Student 04:43PM

Air System Information


Air System Name ................................... Cognizant lab Number of zones ............................................................. 1
Equipment Class ........................................ PKG ROOF Floor Area ................................................................. 246.0 m²
Air System Type ..................................................... VAV Location .......................................................... Pune, India

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing ........................ Peak zone sensible load
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 72.7 5807 1053 Jul 1800 20.0 246.0 23.61

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
Cognizant Lab 1 72.7 Jul 1800 5807 20.0 246.0 23.61

Hourly Analysis Program v4.90 Page 2 of 13


Ventilation Sizing Summary for Cognizant lab
Project Name: Cognizant 03/03/2019
Prepared by: Student 04:43PM

1. Summary
Ventilation Sizing Method ............................................ ASHRAE Std 62.1-2010
Design Condition ........................................................ Minimum flow (cooling)
Occupant Diversity (D) ............................................................................... 1.000
Uncorrected Outdoor Air Intake (Vou) ........................................................ 1053 L/s
System Ventilation Efficiency (Ev) ............................................................. 1.000
Outdoor Air Intake (Vot) .............................................................................. 1053 L/s

2. Space Ventilation Analysis Table


Space Area Time People Breathing
Minimum Floor Outdoor Averaged Outdoor Air Space Zone Space
Supply Air Area Air Rate Occupancy Air Rate Distribution Outdoor Air Outdoor Air Ventilation
(L/s) (m²) (L/(s-m²)) (Occupants) (L/s/person) Effectiveness (L/s) (L/s) Efficiency
Zone Name / Space Name Mult. (Vpz) (Az) (Ra) (Pz) (Rp) (Ez) (Voz) (Vbz) (Evz)
Zone 1
Cognizant Lab 1 1053 246.0 0.60 181.0 5.00 1.00 1053 1053 1.000
Totals (incl. Space Multipliers) 1053 1053 1.000

Hourly Analysis Program v4.90 Page 3 of 13


Air System Design Load Summary for Cognizant lab
Project Name: Cognizant 03/03/2019
Prepared by: Student 04:43PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.9 °C / 24.7 °C HEATING OA DB / WB 8.0 °C / 5.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 295 m² 12587 - 295 m² 10953 -
Roof Transmission 246 m² 16003 - 246 m² 8585 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 20 m² 511 - 20 m² 438 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 5120 W 4660 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 25340 W 24008 - 0 0 -
People 181 10417 10874 0 0 0
Infiltration - 1423 1112 - 0 0
Miscellaneous - 1600 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 71309 11986 - 19975 0
Zone Conditioning - 69901 11986 - -1096 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 6075 L/s 1421 - 1170 L/s -553 -
Ventilation Load 1053 L/s 20505 16051 1053 L/s 885 0
Supply Fan Load 6075 L/s 1990 - 1170 L/s -198 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 5% 3565 - 5% 999 -
>> Total System Loads - 97383 28037 - 37 0
Central Cooling Coil - 97383 28057 - 0 0
>> Total Conditioning - 97383 28057 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 13


Zone Design Load Summary for Cognizant lab
Project Name: Cognizant 03/03/2019
Prepared by: Student 04:43PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.5 °C / 24.3 °C HEATING OA DB / WB 8.0 °C / 5.0 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 295 m² 13074 - 295 m² 10953 -
Roof Transmission 246 m² 16876 - 246 m² 8585 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 20 m² 482 - 20 m² 438 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 5120 W 4680 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 25340 W 24067 - 0 0 -
People 181 10531 10874 0 0 0
Infiltration - 1306 1107 - 0 0
Miscellaneous - 1600 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 72716 11981 - 19975 0

Hourly Analysis Program v4.90 Page 5 of 13


Space Design Load Summary for Cognizant lab
Project Name: Cognizant 03/03/2019
Prepared by: Student 04:43PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' Cognizant Lab '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.5 °C / 24.3 °C HEATING OA DB / WB 8.0 °C / 5.0 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 295 m² 13074 - 295 m² 10953 -
Roof Transmission 246 m² 16876 - 246 m² 8585 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 20 m² 482 - 20 m² 438 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 5120 W 4680 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 25340 W 24067 - 0 0 -
People 181 10531 10874 0 0 0
Infiltration - 1306 1107 - 0 0
Miscellaneous - 1600 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 72716 11981 - 19975 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' Cognizant Lab '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 92 2.830 - 4313 - 3425
SE EXPOSURE
WALL 60 2.830 - 2831 - 2226
SW EXPOSURE
WALL 83 2.830 - 3332 - 3076
DOOR 20 1.703 - 482 - 438
NW EXPOSURE
WALL 60 2.830 - 2598 - 2226
H EXPOSURE
ROOF 246 2.662 - 16876 - 8585

Hourly Analysis Program v4.90 Page 6 of 13


Hourly Air System Design Day Loads for Cognizant lab
Project Name: Cognizant 03/03/2019
Prepared by: Student 04:43PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 31.8 5158 51.8 54.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 31.1 5173 50.3 52.2 0.0 0.0 0.0 0.0 0.0 0.0
0200 30.5 5019 48.5 50.4 0.0 0.0 0.0 0.0 0.0 0.0
0300 30.0 5034 47.1 48.9 0.0 0.0 0.0 0.0 0.0 0.0
0400 29.6 4903 45.8 47.6 0.0 0.0 0.0 0.0 0.0 0.0
0500 29.5 4920 44.3 46.1 0.0 0.0 0.0 0.0 0.0 0.0
0600 29.7 5014 48.3 54.8 0.0 0.0 0.0 0.0 0.0 0.0
0700 30.4 5682 72.7 97.5 0.0 0.0 0.0 0.0 0.0 0.0
0800 31.5 5700 73.5 98.1 0.0 0.0 0.0 0.0 0.0 0.0
0900 33.2 5665 75.3 100.1 0.0 0.0 0.0 0.0 0.0 0.0
1000 35.1 5724 77.8 102.6 0.0 0.0 0.0 0.0 0.0 0.0
1100 37.2 5713 82.9 108.8 0.0 0.0 0.0 0.0 0.0 0.0
1200 39.3 5827 86.5 112.6 0.0 0.0 0.0 0.0 0.0 0.0
1300 40.8 5832 88.3 114.4 0.0 0.0 0.0 0.0 0.0 0.0
1400 41.8 5949 93.0 119.9 0.0 0.0 0.0 0.0 0.0 0.0
1500 42.2 5975 93.6 120.4 0.0 0.0 0.0 0.0 0.0 0.0
1600 41.8 6085 95.0 122.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 40.9 6075 97.4 125.4 0.0 0.0 0.0 0.0 0.0 0.0
1800 39.5 6193 97.2 125.2 0.0 0.0 0.0 0.0 0.0 0.0
1900 37.9 6168 94.7 122.5 0.0 0.0 0.0 0.0 0.0 0.0
2000 36.2 5992 76.5 85.3 0.0 0.0 0.0 0.0 0.0 0.0
2100 34.8 5369 57.9 61.5 0.0 0.0 0.0 0.0 0.0 0.0
2200 33.5 5302 56.6 60.2 0.0 0.0 0.0 0.0 0.0 0.0
2300 32.5 5319 53.7 56.4 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: AUGUST


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 31.8 5143 51.5 53.6 0.0 0.0 0.0 0.0 0.0 0.0
0100 31.1 5158 49.9 51.9 0.0 0.0 0.0 0.0 0.0 0.0
0200 30.5 5005 48.1 50.1 0.0 0.0 0.0 0.0 0.0 0.0
0300 30.0 5019 46.8 48.6 0.0 0.0 0.0 0.0 0.0 0.0
0400 29.6 4890 45.4 47.3 0.0 0.0 0.0 0.0 0.0 0.0
0500 29.5 4907 44.1 45.8 0.0 0.0 0.0 0.0 0.0 0.0
0600 29.7 5004 48.1 54.5 0.0 0.0 0.0 0.0 0.0 0.0
0700 30.4 5671 72.4 97.2 0.0 0.0 0.0 0.0 0.0 0.0
0800 31.5 5692 73.3 97.8 0.0 0.0 0.0 0.0 0.0 0.0
0900 33.2 5652 75.0 99.8 0.0 0.0 0.0 0.0 0.0 0.0
1000 35.1 5715 77.5 102.3 0.0 0.0 0.0 0.0 0.0 0.0
1100 37.2 5704 82.6 108.4 0.0 0.0 0.0 0.0 0.0 0.0
1200 39.3 5685 86.3 112.8 0.0 0.0 0.0 0.0 0.0 0.0
1300 40.8 5812 88.0 114.1 0.0 0.0 0.0 0.0 0.0 0.0
1400 41.8 5939 92.7 119.5 0.0 0.0 0.0 0.0 0.0 0.0
1500 42.2 5969 93.4 120.2 0.0 0.0 0.0 0.0 0.0 0.0
1600 41.8 6077 94.8 121.8 0.0 0.0 0.0 0.0 0.0 0.0
1700 40.9 6067 97.2 125.3 0.0 0.0 0.0 0.0 0.0 0.0
1800 39.5 6188 97.1 125.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 37.9 6161 94.5 122.3 0.0 0.0 0.0 0.0 0.0 0.0
2000 36.2 5983 76.3 85.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 34.8 5356 57.6 61.2 0.0 0.0 0.0 0.0 0.0 0.0
2200 33.5 5286 56.2 59.8 0.0 0.0 0.0 0.0 0.0 0.0
2300 32.5 5303 53.4 56.0 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.90 Page 7 of 13


Hourly Zone Loads for Cognizant lab
Project Name: Cognizant 03/03/2019
Prepared by: Student 04:43PM

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 31.8 24.5 49 4642.2 46709.9 45943.1 0.0 0.0 0.0
0100 31.1 24.5 50 4656.1 45302.3 44504.2 0.0 0.0 0.0
0200 30.5 24.5 50 4517.5 43699.3 42990.8 0.0 0.0 0.0
0300 30.0 24.5 51 4530.8 42470.3 41729.3 0.0 0.0 0.0
0400 29.6 24.5 51 4413.0 41264.3 40594.8 0.0 0.0 0.0
0500 29.5 24.5 52 4428.3 39962.9 39259.9 0.0 0.0 0.0
0600 29.7 24.5 52 4512.3 42612.6 41823.0 0.0 0.0 0.0
0700 30.4 24.6 48 5113.8 60026.2 58749.2 0.0 0.0 0.0
0800 31.5 24.6 48 5130.3 59520.2 58258.9 0.0 0.0 0.0
0900 33.2 24.6 48 5098.2 59311.1 58086.3 0.0 0.0 0.0
1000 35.1 24.6 48 5152.0 59556.0 58297.9 0.0 0.0 0.0
1100 37.2 24.6 46 5141.8 61881.0 60641.0 0.0 0.0 0.0
1200 39.3 24.6 46 5244.0 63068.3 61757.9 0.0 0.0 0.0
1300 40.8 24.6 46 5249.1 62968.0 61668.8 0.0 0.0 0.0
1400 41.8 24.6 44 5353.9 66217.8 64847.7 0.0 0.0 0.0
1500 42.2 24.6 44 5377.1 66361.9 64991.3 0.0 0.0 0.0
1600 41.8 24.7 44 5476.3 68094.9 66661.6 0.0 0.0 0.0
1700 40.9 24.7 43 5467.5 71308.9 69901.2 0.0 0.0 0.0
1800 39.5 24.7 43 5574.0 72715.9 71240.1 0.0 0.0 0.0
1900 37.9 24.7 43 5550.9 72191.9 70755.3 0.0 0.0 0.0
2000 36.2 24.6 42 5392.8 67008.8 65711.6 0.0 0.0 0.0
2100 34.8 24.5 47 4832.3 51952.3 51099.0 0.0 0.0 0.0
2200 33.5 24.5 47 4771.6 50855.8 50018.9 0.0 0.0 0.0
2300 32.5 24.5 49 4786.9 48408.4 47544.6 0.0 0.0 0.0

ZONE: Zone 1
DESIGN MONTH: AUGUST
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 31.8 24.5 49 4628.3 46371.9 45609.2 0.0 0.0 0.0
0100 31.1 24.5 50 4642.2 44973.9 44179.8 0.0 0.0 0.0
0200 30.5 24.5 50 4504.1 43384.6 42679.8 0.0 0.0 0.0
0300 30.0 24.5 51 4517.4 42171.1 41433.9 0.0 0.0 0.0
0400 29.6 24.5 51 4400.6 40981.2 40314.6 0.0 0.0 0.0
0500 29.5 24.5 53 4415.9 39695.6 38995.6 0.0 0.0 0.0
0600 29.7 24.5 52 4503.3 42360.5 41571.4 0.0 0.0 0.0
0700 30.4 24.6 48 5104.0 59786.8 58511.1 0.0 0.0 0.0
0800 31.5 24.6 48 5122.4 59280.6 58019.3 0.0 0.0 0.0
0900 33.2 24.6 48 5087.1 59057.0 57834.9 0.0 0.0 0.0
1000 35.1 24.6 48 5143.3 59286.6 58029.4 0.0 0.0 0.0
1100 37.2 24.6 46 5133.2 61606.1 60367.0 0.0 0.0 0.0
1200 39.3 24.6 45 5116.8 62799.1 61580.9 0.0 0.0 0.0
1300 40.8 24.6 46 5230.8 62712.9 61414.6 0.0 0.0 0.0
1400 41.8 24.6 45 5345.0 65986.9 64613.4 0.0 0.0 0.0
1500 42.2 24.6 45 5371.8 66162.1 64786.1 0.0 0.0 0.0
1600 41.8 24.7 44 5469.5 67925.5 66488.6 0.0 0.0 0.0
1700 40.9 24.7 43 5460.4 71161.4 69751.0 0.0 0.0 0.0
1800 39.5 24.7 43 5568.9 72574.2 71094.4 0.0 0.0 0.0
1900 37.9 24.7 43 5544.6 72028.5 70589.4 0.0 0.0 0.0
2000 36.2 24.6 42 5385.0 66786.5 65488.3 0.0 0.0 0.0
2100 34.8 24.5 47 4820.6 51665.4 50814.5 0.0 0.0 0.0
2200 33.5 24.5 47 4757.2 50530.5 49698.0 0.0 0.0 0.0
2300 32.5 24.5 49 4772.6 48069.1 47209.7 0.0 0.0 0.0

Hourly Analysis Program v4.90 Page 8 of 13


System Psychrometrics for Cognizant lab
Project Name: Cognizant 03/03/2019
Prepared by: Student 04:43PM

July DESIGN COOLING DAY, 1700

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 40.9 0.01425 1053 400 20505 16051
Vent - Return Mixing Outlet 26.7 0.00967 6075 1113 - -
Central Cooling Coil Outlet 12.5 0.00800 6075 1113 97383 28057
Supply Fan Outlet 12.8 0.00800 6075 1113 1990 -
Cold Supply Duct Outlet 13.3 0.00800 5467 1113 - -
Zone Air - 24.7 0.00879 5467 1280 69901 11986
Return Plenum Outlet 24.7 0.00879 5467 1280 0 -
Duct Leakage Air Outlet 12.8 0.00800 607 1113 - -
Return Duct Outlet 23.5 0.00872 6075 1263 - -
Return Fan Outlet 23.7 0.00872 6075 1263 1421 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.129 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2757.0 W/(L/s)
Site Altitude = 560.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 71309 Cooling 69901 24.7 5467 1280 0 0

Hourly Analysis Program v4.90 Page 9 of 13


System Psychrometrics for Cognizant lab
Project Name: Cognizant 03/03/2019
Prepared by: Student 04:43PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 8.0 0.00455 1053 400 -885 0
Vent - Return Mixing Outlet 8.1 0.00455 1170 400 - -
Central Cooling Coil Outlet 8.1 0.00455 1170 400 0 0
Supply Fan Outlet 8.2 0.00455 1170 400 198 -
Cold Supply Duct Outlet 7.4 0.00455 1053 400 - -
Zone Air - 8.3 0.00455 1053 404 1096 0
Return Plenum Outlet 8.3 0.00455 1053 404 0 -
Duct Leakage Air Outlet 8.3 0.00455 117 400 - -
Return Duct Outlet 8.3 0.00455 1170 404 - -
Return Fan Outlet 8.7 0.00455 1170 404 553 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.129 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2757.0 W/(L/s)
Site Altitude = 560.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 -19975 Deadband 1096 8.3 1053 404 0 0

Hourly Analysis Program v4.90 Page 10 of 13


Hourly Air System Design Day Loads for Cognizant lab
Project Name: Cognizant 03/03/2019
Prepared by: Student 04:43PM

Data for July

Total Cooling Total Heating

120
110
100
90
Load ( kW )

80
70
60
50
40
30
20
10
0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Data for August

Total Cooling Total Heating

120
110
100
90
Load ( kW )

80
70
60
50
40
30
20
10
0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program v4.90 Page 11 of 13


Hourly Zone Design Day Loads for Cognizant lab
Project Name: Cognizant 03/03/2019
Prepared by: Student 04:43PM

Zone: Zone 1
Data for July

Zone Sensible Zone Conditioning

70000

60000

50000

40000
W

30000

20000

10000

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
Zone: Zone 1
Data for August

Zone Sensible Zone Conditioning

70000

60000

50000

40000
W

30000

20000

10000

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.90 Page 12 of 13


Psychrometric Analysis for Cognizant lab
Project Name: Cognizant 03/03/2019
Prepared by: Student 04:43PM

Location: Pune, India


Altitude: 560.0 m.
Data for: July DESIGN COOLING DAY, 1700
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0.018
5. Duct Heat
6. Room Air
7. Return Duct Outlet
8. Return Fan Outlet 0.016

Specific Humidity ( kg/kg )


1
0.014

0.012
2
0.010
78 6
34 5
0.008

0.006

0.004

0.002

0.000
0 5 10 15 20 25 30 35 40
Temperature ( °C )

Hourly Analysis Program v4.90 Page 13 of 13