Académique Documents
Professionnel Documents
Culture Documents
April, 2018
Rev: 00
Mechanical Systems Design Criteria
Contents
A. HVAC SYSTEM.........................................................................................................................................................1
1. General...............................................................................................................................................................1
2. Method of calculation........................................................................................................................................1
3. Geographical location of the project site..........................................................................................................1
4. Ambient design conditions................................................................................................................................1
5. Codes and Standards.........................................................................................................................................1
6. Indoor Design Conditions..................................................................................................................................2
7. Indoor heat generation......................................................................................................................................2
8. People Density...................................................................................................................................................2
9. Room Pressurization Requirement....................................................................................................................2
10. Noise Control.................................................................................................................................................3
11. System description........................................................................................................................................3
12. Room pressure control..................................................................................................................................5
13. Fire and smoke control..................................................................................................................................6
14. Chilled water system.....................................................................................................................................6
15. Materials of construction..............................................................................................................................6
B. PLUMBING..............................................................................................................................................................7
1. General...............................................................................................................................................................7
2. Codes and Standards.........................................................................................................................................7
3. Incoming Connections.......................................................................................................................................7
4. Labs Cold and Hot Water Distribution:..............................................................................................................7
5. Water Supply Sizing Criteria...............................................................................................................................8
6. Piping Material...................................................................................................................................................8
7. Drainage System................................................................................................................................................8
C. FIRE FIGHTING........................................................................................................................................................9
1. Codes and Standards.........................................................................................................................................9
2. Incoming Connections.......................................................................................................................................9
3. Fire System for Labs...........................................................................................................................................9
4. Fire Piping Material............................................................................................................................................9
B. Piped Gas services................................................................................................................................................10
1. Codes and Standards.......................................................................................................................................10
2. Medical Gas system for Labs............................................................................................................................10
3. Medical Gas Piping material and sizing:..........................................................................................................10
A. HVAC SYSTEM
1. General
2. Method of calculation
The cooling load of the building will be calculated based on Carrier E20-II
Hourly Analysis Program (HAP). A 10% safety factor will be applied to all
room sensible and 5% latent heat gains. Similarly, a 3% safety factor will be
applied for duct heat gain and 5% for duct air leakage.
City: Karachi
North latitude 25°
East longitude 67°
Altitude/Elevation 13 ft
Summer
Winter
The design and construction of HVAC system will be based on the following
Codes and Standards:
Page |1
Mechanical Systems Design Criteria
The User’s data provided for Microbiology, Epidemiology & Nutrition research lab
gives key equipment operating requirements as under:
No specific requirements have been given by the User for BSL 2 lab.
ASHRAE recommends indoor design conditions as under:
Laboratories
Following design conditions for various spaces are considered in HAP (Hourly
Analysis Program) calculations:
8. People Density
The occupancy for labs and other areas is taken from furniture layouts shown in
the architectural plans. For the areas where furniture layout is not shown,
occupancy is calculated from ASHRAE std. 62.1-2013
In general, the Microbiology lab, Epidemiology lab and other BSL 2 labs on third
floor will be designed to be at negative pressure. The Nutrition Research Lab
(NRL) shall be positively pressurized.
Page |2
Mechanical Systems Design Criteria
The air-conditioning systems will be designed to provide low noise levels in all
areas as recommended in ASHRAE handbooks, Code #.
The supply and exhaust fans will be interlocked and their speed will be
regulated by VFDs.
The supply air will be provided in the lab through diffusers maintaining low
velocity and sound level.
Page |3
Mechanical Systems Design Criteria
In general, the exhaust air from labs will be exhausted into atmosphere by
the exhaust fans located at roof. For specific cases, e.g. contaminated or
hazardous fumes, the exhaust duct from lab to HEPA filters will be of
shortest run for safety of operating personnel. The air after passing through
HEPA filters will be exhausted into atmosphere.
Microbiological, Epidemiological & NRL Labs
AHUs will be re-circulation type and ambient fresh air will be mixed with
return air in the mixing box.
Page |4
Mechanical Systems Design Criteria
Exhaust air will be taken from above the washing sinks and autoclave to control
spread of foul smell.
Page |5
Mechanical Systems Design Criteria
All central air handling units (AHUs) shall be interlocked with fire and smoke
sensors mounted in supply and exhaust air ducts to shut down the AHU on
sensing of smoke/fire and give audio alarm in the control room and
indication on fire panel.
Fire dampers with fusible links as per NFPA will be provided in supply duct
crossing MER floor.
The WCH-COE building is located near the NazerAli Walji building of AKUH.
The chilled water for air conditioning shall be drawn from the central chiller
plant, located in the service building. The chilled water will be tapped from
existing chilled water pipes passing through the services tunnel of NazerAli
Walji building. As the anticipated incoming Chilled Water pressure will be low
therefore, booster Chilled water pumps (1-Duty & 1-Stand By) are proposed
in basement-1 Plant room to distribute chilled water throughout the building.
The pumps shall be provided with Variable frequency drive (VFD) to adjust
as per building chilled water demand and to conserve power. The VFD
pumping system shall operate using the principal of speed control based on
constant pressure. The Pumps shall be interlinked with AKU central BMS
system.
Page |6
Mechanical Systems Design Criteria
B. PLUMBING
1. General
This report is intended only for the Labs and have to be read in conjunction
with “MEP Basis of Design report Rev-01”
The Plumbing systems for Labs shall be designed to comply with the
following codes.
3. Incoming Connections.
As confirmed by AKU, the incoming cold and hot water shall be tapped from
hospital existing network running inside the AKU utility tunnel. All incoming
water connection shall be provided with water meters interlinked with BMS
system.
Up-feed water supply system shall be designed for the building. Both cold and
hot water supply networks shall be provided with a dedicated boosters which
shall be used to boost water to all Labs, Wet areas, Pantries and the rest of
facility.
The booster pump shall be provided with Variable Frequency drive to adjust as
per building Water demand in Peak and Off Peak hours and to conserve power.
Isolating valves will be provided for isolation of service to each lab. Back flow
preventers will be provided as required for hazard areas to prevent backward
flow of contaminated water.
A hot water circulation system shall also be designed to ensure the availability of
hot water at all times. Hot water circulation pump shall also be located in
Basement-1 plant room
Page |7
Mechanical Systems Design Criteria
Water supply piping shall be sized on hospital plumbing fixtures as per ASPE
-3 Handbook Table 2-2. All laboratory sinks shall be 316 S.Steel and shall be
provided with both Cold and hot water supply.
The booster pump shall be sized to ensure that a minimum pressure of 20 psi is
maintained at the most remote outlet as per final fixture selection.
6. Piping Material
Here under are the recommended piping materials for the project.
7. Drainage System
Double stack system comprising of separate Gray and Black water pipes with
properly vented fixtures shall be adopted for building drainage.
All Labs shall have a dedicated Waste pipe which will only be used to collect Lab
drainage. Keeping in mind different PH values drained into the lab sinks,
Polypropylene (PP) pipe shall be used.
All lab drains stacks shall be connected to Acid Waste neutralization Pit which
will eventually be connected to Hospital Sewage system. The neutralization pit
shall be constructed of S.Steel or other acid resistant material and shall be filled
with lime stone or Marble Chip. The Neutralization tank shall be sized for the
dwell time of 2-3 hours as per ASPE guidelines. All labs sink shall be properly
vented with dedicated vent piping.
Traps for Eye wash shall either be provided with Seal trap primer or shall be
connected with nearest lab sink drainage to prevent them from drying out.
Page |8
Mechanical Systems Design Criteria
C. FIRE FIGHTING
The Fire fighting system for Labs shall be designed to comply with the
following codes.
2. Incoming Connections.
As confirmed by AKU, fire water for WCH building shall be tapped form external
AKU fire network. Since the incoming pressure is only 50 Psi which is NOT
enough to accommodate the building needs, a Fire booster set shall be proposed
in the basement plant room.
As per NFPA-99 Section 11-5, portable fire extinguishers shall also be provided
in all labs including Storage areas. Fire will be provided in mechanical, Telecom
and small electrical rooms and in lower compartment of Fire hose cabinets.
All Fire piping shall be seamless black steel schedule 40 as per ASTM A53.
Page |9
Mechanical Systems Design Criteria
The Medical Gas system for Labs shall be designed to comply with the
following codes.
The following medical Gas systems shall be considered for labs based on the
input received from Lab End user.
Medical Oxygen
NO Gas system
N2 Gas system
Medical oxygen shall be tapped from hospital Central oxygen supply network
while Medical Air and Medical Vacuum shall be generated on site by Medical
grade Air compressors and Medical Vacuum Pumps.
Both Medical Compressors and Medical Vacuum Pump shall be located in MEP
plant room at roof level. Medical Compressor and Vacuum shall comply NFPA-
99.
NO, N2 and CO2 gas shall only be considered for Labs as indicated by lab end
user. NO, N2 and Co2 shall be provided through gas cylinders manifolds located
in MEP on the roof in dedicated 2 hour fire rated compartments.
Medical gas piping shall be Type "K" Phosphorous Deoxidized, Non Arsenical,
washed and degreased, seamless copper tubing as per BS EN 13348 with end
free Capillary fittings as per BS EN 1254-1 with wrought copper, brass or bronze
fittings designed expressly for brazed silver solder connections.
All medical gas pipeline design shall be based on 5% Pressure drop from source
of supply to the terminal unit at the specified flows.
Page |
10
Mechanical Systems Design Criteria
Page |
11