APC (EMEA) Sizing Guide for Cisco Switches and Routers with Multiple Power Supplies

Issue 0 - 25th August 2010 Page 1 of 2

*Estimated Max. Power Redundant Solution


Power source Recommended Solution
Consumption (Watts) (One power module to be added to each system for redundancy)
Power Supply Unit connections per Compatible
Series
(PSU) PSU for full Switches & Routers Runtime Runtime
DC loading AC loading
permissible power
on Chassis on UPS 1 hour 2 hours 4 hours 1 hour 2 hours 4 hours

PWR-C45-1000AC (1) IEC320 C16 4503, 4506, 4507R SURTD3000RMXLI + SURTD3000RMXLI + SURTD3000RMXLI + SYH4K6RMI SYH4K6RMI SYH4K6RMI
(data only) inlet on PSU (classic & E models) 800 941 (1) SURT192RMXLBP (1) SURT192RMXLBP (3) SURT192RMXLBP + (1)SYBT2 + (1) SYRMXR4B4I + (2) SYRMXR4B4I

4503, 4506, 4507R, SYH4K6RMI


PWR-C45-1400AC (1) IEC320 C20 SURTD3000RMXLI + SURTD3000RMXLI + SURTD3000RMXLI + SYH4K6RMI SYH4K6RMI
(data only) inlet on PSU
4510R 1120 1318 (1) SURT192RMXLBP (2) SURT192RMXLBP (3) SURT192RMXLBP + (2)SYBT2
+ (1) SYRMXR4B4I
+ (3) SYRMXR4B4I
(classic & E models) + (1) SYRMXR2B4I

SYH4K6RMI SYH4K6RMI
PWR-C45-1300ACV (1) IEC320 C20 4503, 4506, 4507R SURTD3000RMXLI + SURTD3000RMXLI + SURTD3000RMXLI + SYH4K6RMI
(with integrated PoE) inlet on PSU (classic & E models) 1040 1224 (1) SURT192RMXLBP (2) SURT192RMXLBP (3) SURT192RMXLBP + (2)SYBT2
+ (1) SYBT2 + (2) SYBT2
+ (1) SYRMXR4B4I + (2) SYRMXR4B4I
Catalyst
4500
4503, 4506, 4507R, SYH6K6RMI SYH6K6RMI SYH6K6RMI
PWR-C45-2800ACV (1) IEC320 C20 SURTD5000RMXLI + SURTD5000RMXLI + SURT8000RMXLI +
(with integrated PoE) inlet on PSU
4510R 2240 2635 (2) SURT192RMXLBP (4) SURT192RMXLBP (6) SURT192RMXLBP
+ (1) SYRMXR4B4I + (2) SYRMXR4B4I + (5) SYRMXR4B4I
(classic & E models) + (1) SYRMXR2B4I + (1) SYRMXR2B4I + (1) SYRMXR2B4I

4503, 4506, 4507R, SYA8K8RMI SYA8K8RMI


PWR-C45-4200ACV (2) IEC320 C20 SURT8000RMXLI + SURT8000RMXLI + SURT15KRMXLI + SYA8K8RMI
(with integrated PoE) inlet on PSU
4510R 3360 3953 (3) SURT192RMXLBP (5) SURT192RMXLBP (5) SURT192RMXLBP2 + (2) SYARMXR3B3I
+ (1) SYARMXR3B3I + (2) SYARMXR3B3I
(classic & E models) + (1) SYARMXR9B9I + (2) SYARMXR9B9I

4503, 4506, 4507R, SYA12K16RMI


PWR-C45-6000ACV (2) IEC320 C20 SURT10000RMXLI + SURT15KRMXLI + SURT15KRMXLI + SYA12K16RMI SYA12K16RMI
(with integrated PoE) inlet on PSU
4510R 4800 5647 (4) SURT192RMXLBP (3) SURT192RMXLBP2 (7) SURT192RMXLBP2 + (1) SYARMXR9B9I + (2) SYARMXR9B9I
+ (2) SYARMXR3B3I
(classic & E models) + (3) SYARMXR9B9I

(1) IEC320 C16 SURTD3000RMXLI + SURTD3000RMXLI + SURTD3000RMXLI + SYH4K6RMI SYH4K6RMI SYH4K6RMI


PWR-950-AC
inlet on PSU
6503, 6503-E 760 894 (1) SURT192RMXLBP (1) SURT192RMXLBP (2) SURT192RMXLBP + (1) SYBT2 + (1) SYRMXR4B4I + (2) SYRMXR4B4I

(1) IEC320 C16 SURTD3000RMXLI + SURTD3000RMXLI + SURTD3000RMXLI + SYH4K6RMI SYH4K6RMI SYH4K6RMI


WS-CAC-1000W
inlet on PSU
6506, 6509 800 941 (1) SURT192RMXLBP (1) SURT192RMXLBP (3) SURT192RMXLBP + (1)SYBT2 + (1) SYRMXR4B4I + (2) SYRMXR4B4I

SYH4K6RMI
(1) IEC320 C20 SURTD3000RMXLI + SURTD3000RMXLI + SURTD3000RMXLI + SYH4K6RMI SYH4K6RMI
PWR-1400-AC
inlet on PSU
6503, 6503-E 1120 1318 (1) SURT192RMXLBP (2) SURT192RMXLBP (3) SURT192RMXLBP + (2)SYBT2
+ (1) SYRMXR4B4I
+ (3) SYRMXR4B4I
+ (1) SYRMXR2B4I
Catalyst
6500
6506, 6506-E, 6509, SYH6K6RMI
(1) IEC320 C20 SURTD5000RMXLI + SURTD5000RMXLI + SURTD5000RMXLI + SYH6K6RMI SYH6K6RMI
WS-CAC-2500W
inlet on PSU
6509-E, 6509-V-E, 2000 2353 (2) SURT192RMXLBP (3) SURT192RMXLBP (6) SURT192RMXLBP + (1) SYRMXR4B4I
+ (2) SYRMXR4B4I
+ (5) SYRMXR4B4I
6513 + (1) SYRMXR2B4I

SYH6K6RMI
(1) IEC320 C20 SURTD5000RMXLI + SURTD5000RMXLI + SURT8000RMXLI + SYH6K6RMI SYH6K6RMI
PWR-2700-AC/4
inlet on PSU
6504-E 2160 2541 (2) SURT192RMXLBP (4) SURT192RMXLBP (7) SURT192RMXLBP + (1) SYRMXR4B4I
+ (2) SYRMXR4B4I
+ (5) SYRMXR4B4I
+ (1) SYRMXR2B4I

6506, 6506-E, 6509, SYH6K6RMI


(1) IEC320 C20 SURTD5000RMXLI + SURTD5000RMXLI + SURT8000RMXLI + SYH6K6RMI SYH6K6RMI
WS-CAC-3000W
inlet on PSU
6509-E, 6509-V-E, 2400 2824 (2) SURT192RMXLBP (4) SURT192RMXLBP (7) SURT192RMXLBP
+ (1) SYRMXR4B4I
+ (3) SYRMXR4B4I + (6) SYRMXR4B4I
6513 + (1) SYRMXR2B4I

* Estimated Max. Power Consumption data is offered as a guide only and is based on 80% DC loading of the installed power supply units operating at 85% efficiency to provide the UPS loading.
Data assumes that the installed power supplies are in redundant or single mode not combined.

This document is only intended as a Guide and is subject to change without notice. For full details on specific products please go to www.apc.com and
APC (EMEA) Sizing Guide for Cisco Switches and Routers with Multiple Power Supplies
Issue 0 - 25th August 2010 Page 2 of 2

Power source *Estimated Max. Power Redundant Solution


Recommended Solution
Power Supply Unit connections per Compatible Consumption (Watts) (One power module to be added to each system for redundancy)
Series
(PSU) PSU for full Switches & Routers DC loading AC loading Runtime Runtime
permissible power on Chassis on UPS 1 hour 2 hours 4 hours 1 hour 2 hours 4 hours

6506, 6506-E, 6509, SYA8K8RMI SYA8K8RMI


Hardwired to SURT8000RMXLI + SURT8000RMXLI + SURT15KRMXLI + SYA8K8RMI
WS-CAC-4000W-INT 6509-E, 6509-V-E, 3200 3765 + (1) SYARMXR9B9I + (2) SYARMXR9B9I
IEC 60309 plug (3) SURT192RMXLBP (5) SURT192RMXLBP (5) SURT192RMXLBP2 + (2) SYARMXR3B3I
6513 + (1) SYARMXR3B3I + (1) SYARMXR3B3I

SYA8K8RMI SYA8K8RMI
6506, 6509 SURT8000RMXLI + SURT8000RMXLI + SURT15KRMXLI + SYA8K8RMI
3200 3765 + (1) SYARMXR9B9I + (2) SYARMXR9B9I
(Max 4000W) (3) SURT192RMXLBP (5) SURT192RMXLBP (5) SURT192RMXLBP2 + (2) SYARMXR3B3I
+ (1) SYARMXR3B3I + (1) SYARMXR3B3I
WS-CAC-6000W (2) IEC320 C20
inlets on PSU
SYA12K16RMI
6506-E, 6509-E, SURT10000RMXLI + SURT15KRMXLI + SURT15KRMXLI + SYA12K16RMI SYA12K16RMI
4800 5647 + (2) SYARMXR3B3I
6509-V-E, 6513, (4) SURT192RMXLBP (3) SURT192RMXLBP2 (7) SURT192RMXLBP2 + (1) SYARMXR9B9I + (2) SYARMXR9B9I
+ (3) SYARMXR9B9I
Catalyst
6500
SYA8K8RMI SYA8K8RMI
6506, 6509 SURT8000RMXLI + SURT8000RMXLI + SURT15KRMXLI + SYA8K8RMI
3200 3765 + (1) SYARMXR9B9I + (2) SYARMXR9B9I
(Max 4000W) (3) SURT192RMXLBP (5) SURT192RMXLBP (5) SURT192RMXLBP2 + (2) SYARMXR3B3I
+ (1) SYARMXR3B3I + (1) SYARMXR3B3I

SYA12K16RMI
(3) IEC320 C20 6513 SURT10000RMXLI + SURT15KRMXLI + SURT15KRMXLI + SYA12K16RMI SYA12K16RMI
WS-CAC-8700W-E 4800 5647 + (2) SYARMXR3B3I
inlets on PSU (Max 6000W) (4) SURT192RMXLBP (3) SURT192RMXLBP2 (7) SURT192RMXLBP2 + (1) SYARMXR9B9I + (2) SYARMXR9B9I
+ (3) SYARMXR9B9I

SYA16K16RMI SYA16K16RMI
6506, 6506-E, 6509, SURT15KRMXLI + SURT15KRMXLI + SYA16K16RMI SYA16K16RMI
6960 8188 + (1) SYARMXR9B9I + (2) SYARMXR9B9I
6509-E (3) SURT192RMXLBP2 (5) SURT192RMXLBP2 + (5) SYARMXR9B9I + (5) SYARMXR9B9I
+ (1) SYARMXR3B3I + (2) SYARMXR3B3I

SYH6K6RMI
(1) IEC320 C20 SURTD5000RMXLI + SURTD5000RMXLI + SURTD5000RMXLI + SYH6K6RMI SYH6K6RMI
WS-CAC-2500W 7609 2000 2353 + (2) SYRMXR4B4I
inlet on PSU (2) SURT192RMXLBP (3) SURT192RMXLBP (6) SURT192RMXLBP + (1) SYRMXR4B4I + (5) SYRMXR4B4I
+ (1) SYRMXR2B4I

SYH6K6RMI
(1) IEC320 C20 SURTD5000RMXLI + SURTD5000RMXLI + SURT8000RMXLI + SYH6K6RMI SYH6K6RMI
PWR-2700-AC/4 7604 2160 2541 + (2) SYRMXR4B4I
inlet on PSU (2) SURT192RMXLBP (4) SURT192RMXLBP (7) SURT192RMXLBP + (1) SYRMXR4B4I + (5) SYRMXR4B4I
+ (1) SYRMXR2B4I

SYH6K6RMI
(1) IEC320 C20 SURTD5000RMXLI + SURTD5000RMXLI + SURT8000RMXLI + SYH6K6RMI SYH6K6RMI
Catalyst 7600 WS-CAC-3000W 7609, 7609-S, 7613 2400 2824 + (1) SYRMXR4B4I
inlet on PSU (2) SURT192RMXLBP (4) SURT192RMXLBP (7) SURT192RMXLBP + (3) SYRMXR4B4I + (6) SYRMXR4B4I
+ (1) SYRMXR2B4I

SYA8K8RMI SYA8K8RMI
Hardwired to SURT8000RMXLI + SURT8000RMXLI + SURT15KRMXLI + SYA8K8RMI
WS-CAC-4000W-INT 7609, 7609-S, 7613 3200 3765 + (1) SYARMXR9B9I + (2) SYARMXR9B9I
IEC 60309 plug (3) SURT192RMXLBP (5) SURT192RMXLBP (5) SURT192RMXLBP2 + (2) SYARMXR3B3I
+ (1) SYARMXR3B3I + (1) SYARMXR3B3I

SYA12K16RMI
(2) IEC320 C20 OSR-7609, 7609, SURT10000RMXLI + SURT15KRMXLI + SURT15KRMXLI + SYA12K16RMI SYA12K16RMI
WS-CAC-6000W 4800 5647 + (2) SYARMXR3B3I
inlets on PSU 7609-S, 7613 (4) SURT192RMXLBP (3) SURT192RMXLBP2 (7) SURT192RMXLBP2 + (1) SYARMXR9B9I + (2) SYARMXR9B9I
+ (3) SYARMXR9B9I

* Estimated Max. Power Consumption data is offered as a guide only and is based on 80% DC loading of the installed power supply units operating at 85% efficiency to provide the UPS loading.
Data assumes that the installed power supplies are in redundant or single mode not combined.

This document is only intended as a Guide and is subject to change without notice. For full details on specific products please go to www.apc.com and