Criterios de estructuración en

estructuras de acero

Clase 5
04/02/19
 Buscar el menor número de empalmes de
columnas posible.
 Considerar la posibilidad de utilizar una sección
más rígida para evitar la colocación de atiesadores
 Especificar refuerzo en almas de vigas en zona de
huecos para instalaciones sólo donde realmente se
requiera.
 Tratar de utilizar perfiles HSS para contraventeo de
marcos.
 Utilizar elementos compactos cuando estarán
sometidos a efectos de compresion
Detalle de conexión de contraventeo con perfil HSS

Conexión con placa (tipo peine)


Conexión en zona de nudo viga-columna
Detalle de conexión de contraventeo con perfil HSS

Conexión con trabe al centro del claro


AISC Seismic Provisions:
Column Splices
AISC Seismic Provisions:
Column Splices

Column splices in any SLRS frame must satisfy


requirements of Section 8.4a.

Additional requirements for columns splices are


specified for:
- Special Moment Frames (Section 9.9)
- Intermediate Moment Frames (Section 10.9)
- Special Concentrically Braced Frames (Section 13.5)
- Buckling Restrained Braced Frames (Section 16.5c)
AISC Seismic Provisions:
8.4 Column Splices
Based on amplified
8.4a. General seismic loads or
Pu - splice capacity design
analysis

The required strength of


column splices shall equal Mu - splice Based on code
the required strength of Vu - splice level forces
columns, including that
determined from Section 8.3
AISC Seismic Provisions:
8.4 Column Splices
8.4a. General (cont).

Welded column splices subjected to net


tension when subjected to amplified
seismic loads, shall satisfy both of the
following requirements:

1. If partial joint penetration (PJP) groove


welded joints are used, the design strength of
the PJP welds shall be at least 200-percent of
the required strength.
And....
2. The design strength of each flange splice
shall be at least 0.5 Ry Fy Af for the smaller
flange
AISC Seismic Provisions:
Column Splices
General (cont).

PJP Groove Weld


Stress concentration:
Fracture initiation
point.

Design PJP groove


weld for 200 % of
required strength

( PJP Groove welds not permitted in column splices


for Special and Intermediate Moment Frames)
AISC Seismic Provisions:
Column Splices
General (cont).

Where PJP grove welds are used, beveled transitions


are not required.

Where Complete Joint Penetration (CJP) groove


welds are used, beveled transitions are required per
AWS D1.1
AISC Seismic Provisions:
8.4 Column Splices
8.4a. General (cont).

Column web splices shall be bolted or


welded, or welded to one column and
bolted to the other.
AISC Seismic Provisions:
8.4 Column Splices
8.4a. General (cont).

Splices made with fillet welds or


PJP welds shall be located at
least 4-ft. from beam-to-column
connections

4 ft. min
AISC Seismic Provisions:
Column Splices
General (cont).

Splices made with fillet welds or


PJP welds shall be located at
least 4-ft. from beam-to-column
connections

4 ft. min
AISC Seismic Provisions:
Classification of Sections for Local Buckling

Local buckling of members can significantly affect both strength and


ductility of the member.

Members of the SLRS that are expected to experience significant


inelastic action (e.g. beams in SMF, braces in SCBF, links in EBF, etc),
must satisfy strict width-thickness limits to assure adequate ductility
can be developed prior to local buckling.
Such members must be seismically compact.

For seismically compact sections, the width-thickness ratios of the


elements of the cross-section cannot exceed ps, as specified in Table
I-8-1.
Local buckling of a moment frame beam.....
Local buckling of an EBF link.....
Local buckling of an HSS column....
Local buckling of an HSS brace.....
AISC Seismic Provisions:
1
TABLE I-8-1
Limiting Width-Thickness Ratios for
Compression Elements
Width Limiting Width-
Thick- Thickness Ratios
ness ps
Description of Element
Ratio (seismically compact)
Flexure in flanges of rolled or built-up I- b/t 0.30 E / Fy
shaped sections [a], [c], [e], [g], [h]
Uniform compression in flanges of rolled or b/t 0.30 E / Fy
built-up I-shaped sections [b], [h]
Uniform compression in flanges of rolled or b/t
built-up I-shaped sections [d]
0.38 E / Fy
Uniform compression in flanges of channels, b/t
0.30 E / Fy
Unstiffened Elements

outstanding legs of pairs of angles


in continuous contact, and braces
[c], [g]
Uniform compression in flanges of H-pile
sections b/t 0.45 E / Fy

Flat bars[f]
b/t 2.5

Uniform compression in legs of single b/t


angles, legs of double angle
0.30 E / Fy
members with separators, or flanges
of tees [g]
Uniform compression in stems of tees [g] d/t
0.30 E / Fy
Note: See continued Table I-8-1 for stiffened elements.
AISC Seismic Provisions: TABLE I-8-1 (cont.)
Limiting Width-Thickness Ratios for
Compression Elements
Limiting Width-
Width Thickness Ratios
Thickness ps
Description of Element Ratio (seismically compact)
Webs in flexural compression in h/tw 2.45 E / Fy
beams in SMF, Section 9, unless
noted otherwise
Webs in flexural compression or h/tw for Ca  0.125 [k]
combined flexure and axial
E
compression [a], [c], [g], 3.14
Fy
(1 − 1.54Ca )
[h], [i], [ j]

Stiffened Elements
for Ca  0.125 [k]
E E
1.12
Fy
(2.33 −Ca )  1.49 F
y

Round HSS in axial and/or flexural D/t 0.044 E /Fy


compression [c], [g]
Rectangular HSS in axial and/or b/t or 0.64 E / Fy
flexural compression [c], [g] h/tw
Webs of H-Pile sections h/tw 0.94 E / Fy

[a] Required for beams in SMF, Section 9 and SPSW, Section 17.
[b] Required for columns in SMF, Section 9, unless the ratios from Pu
Equation 9-3 are greater than 2.0 where it is permitted to use p in [ k] For LRFD, Ca =
Specification Table B4.1.
bPy
[c] Required for braces and columns in SCBF, Section 13 and braces in bPa
OCBF, Section 14. For ASD, Ca =
[d] It is permitted to use p in Specification Table B4.1 for columns in
Py
STMF, Section 12 and columns in EBF, Section 15. where
[e] Required for link in EBF, Section 15, except it is permitted to use p in Pa = required compressive
Table B4.1 of the Specification for flanges of links of length 1.6Mp / Vp strength (ASD), kips
or less. (N)
[f] Diagonal web members within the special segment of Pu = required compressive
STMF, Section 12. strength (LRFD),
[g] Chord members of STMF, Section 12. kips (N)
[h] Required for beams and columns in BRBF, Section 16. Py = axial yield strength,
[i] Required for columns in SPSW, Section 17. kips (N)
[j] For columns in STMF, Section 12; columns in SMF, if the ratios from b = 0.90
Equation 9-3 are greater than 2.0; columns in EBF, Section 15; or b = 1.67
EBF with flanges of links of length 1.6 Mp / Vp or less, it is permitted to
use the following for p:
E
for Ca  0.125, p = 3.76
Fy
(1 − 2.75Ca )
E E
for Ca > 0.125, p = 1.12
Fy
( 2.33 − Ca )  1.49 F
y

1
 Los perfiles de acero estructural cargados transversalmente son un tipo
común de miembros estructurales en edificios, puentes y otras
estructuras. En la mayoría de los casos, las vigas tienen sus cargas
aplicadas en el plano del alma, produciendo así flexión respecto al eje
de mayor momento de inercia de la sección.
 En algunas situaciones, las cargas se aplican en una dirección
perpendicular al alma y producen entonces flexión respecto al eje débil
de la sección transversal.
 La selección de un perfil laminado apropiado para usarse
como viga se basa a menudo en su capacidad para resistir el
momento flexionante máximo M sin que se exceda el esfuerzo
permisible en sus fibras.

 El modulo de sección requerido S = I / c se da como S=M/Fb,


donde M es el momento flexionante máximo y Fb el esfuerzo
flexionante permisible.
 El esfuerzo permisible básico de flexión Fb, a tensión o a
compresión, se toma como una fracción de la resistencia de
fluencia Fy.

 Habrán requisitos de esfuerzos admisibles para secciones


compactas y esfuerzos admisibles para secciones no
compactas.
 Cuando la geometría de la sección sea compacta se
puede usar:
 Fb = 0.75 Fy

 Cuando la geometría de la sección no sea compacta no


se debe usar un valor mayor que:
 Fb = 0.6 Fy
 Se deberá verificar la flecha máxima según los valores
máximos establecidos por normas, estos valores varían
según el uso de la viga.
 Calcule la sección transversal satisfactoria para la
siguiente viga.
 Considere un tubo HSS
 Considere un perfil W
 En el pre-dimensionamiento de un miembro en
compresión (columna) se conocen por lo general las cargas
máximas y la longitud efectiva del miembro, mientras que
están por determinarse la forma y las dimensiones de la
sección transversal. El área de la sección transversal
requerida A esta determinada por la carga P, y el esfuerzo
permisible promedio F de relación A = P / F; el esfuerzo
permisible F depende de la relación de esbeltez L / r y de
las condiciones de restricción de los apoyos, cantidades que
no se conocen con precisión hasta después de determinar la
forma y el tamaño del miembro
 Los miembros a compresión pueden clasificarse de acuerdo con la
forma en que fallarían al aplicárseles cargas axiales de ruptura. Un
miembro de compresión con una longitud relativamente corta con
respecto a sus dimensiones laterales fallara generalmente por
compresión simple.

 Una columna tiene una gran longitud en relación con su dimensión


menor. La falla de una columna bajo carga axial, involucra la
deformación lateral o pandeo en forma súbita.
 Para una columna muy larga hay una carga limite P,
conocida como la “carga limite de Euler”, la que es
critica para la columna. Cuando se ha alcanzado la
carga critica, la columna se encuentra en la condición
de equilibrio inestable y puede fallar súbitamente por
pandeo local o torsional.
 Sea la columna AB, doblemente
articulada (figura 4.1) de altura L y
sometida a su carga crítica PCR; carga
bajo la cual la columna se pandea
alrededor de su eje débil y pierde su
capacidad de soporte de carga axial.
Esta condición corresponde a la falla
de la columna.
 La longitud sin soporte L de un miembro en
compresión puede reducirse suministrando soportes
intermedios
Hallamos el esfuerzo crítico
Considerando
I=A𝑟 2

donde L/r es la relación de esbeltez L/r < 200


 La restricción ideal de los extremos de las columnas, no
puede ser siempre confiable, el AISC especifica
conservadoramente una modificación de las longitudes
efectivas como sigue:
 Para columnas empotradas en ambos extremos: Kl = 0.65 L
 Para columnas empotradas en un extremo y articuladas en el
otro: Kl = 0.80 L
 Para columnas empotradas en un extremo y libres en el otro:
Kl = 2.10 L
 Ninguna modificación tiene que hacerse para columnas
articuladas en ambos extremos, donde Kl = L. Para otras
restricciones de extremo,
 Predimensionar una columna con los extremos
articulados que debe soportar una carga de 180 Ton.
(180000 Kg.); la longitud de la columna es de 4.0 mt, el
material es acero A-36.