Vous êtes sur la page 1sur 1

Loading Considerations

Sr No Description Descritpion
IS 800 :2007 or As per latest
1 Design Code
( PEB to Quote to options with & without Chapetr 12)
2 Minimum Thickness of primary member 5 mm
Minimum Thickness of secondory 2 mm ( Any purline should not be designed as tie member
3
member to structure)
4 Dead Load - Self weight

5 Live load As per design


6 Wind Speed As per IS

7 Seismic loads As per IS

8 Grade of Base Concrete M20

9 Additional Loads on Roof Sheets Solar panel (25 KG/SQM)

Additional co-lateral load on roof due to


10 suspend service lines to be suspended 45 Kg/Sqm
from the Purlines at any point
Additional co-lateral load on roof due to
suspend service lines to be suspended
11 300 Kg/Rmt
from the rafters (excluding above load on
purlin) at any point

i. The Supendors required to be taken from Rafters in


machine shop mezzanine ( canteen Area) J-K- 6- 10
ii. The load on Strutre shoulde be 30Kg /sqm
12 Suspended gird iii. In addition to point "ii" above Also load on this structure
should be Suitable for men movement
iv. Holes & necesary stiffeners in rafter for supendors
required to provide in this phase only

13 EOT Yes in Foundry Shop 3 MT cpoapcity EOT in central bay


14 Assumed data for Crane Electromech
i.PEB vendor required to Design for critical condition
15 Open condition
ii. Note that 15 % of area may be remain open in any time
i.. 900 mm extent on both sides with load carrying capacity
Brackets & beam (Cable tray Support) of 180 KG / rmt each side
16
along central & peripheral column ii. This should not be designed as a tie member to
structure
Approximate Length of Cable Tray
17 as mentioned in repsective shop specs
Supporting Structure
i. Projected to Support the Fire Hydrant -- load of 250NB
Bracktes on Column (450mm) Projected
water pipe
18 to Support the Fire Hydrant -- load of
ii. This should not be designed as a tie member to
250NB water pipe
structure

19 load of Bus Bar with tray Arrangement

20 Rain fall intensity for Gutter calculations 150mm/hr

1. All mezzanines shall be Desinged for LL of 750 kg/ Sqm


2. The concrete thickness above crest of deck will be 150mm
3. peripheral brickworks of 230mm thivk upto heigth of 4m on
21 load on mezzanine mezaanine beams
4. internal walls will be shwon in Approval drawings
5. There will be sunk of 250mm filled with brick bats in
mezzanine having canteen ( Approx area = 225mm)
Chimeny Exhaust FO & Support from
22
Foundry & machine shop
23 Future Expansion NA
24 Design Approval from IIT is in scope of PEB vendor

Vous aimerez peut-être aussi