www.tyco-fire.com
Contacts
Model RM-1
Riser Manifold
Commercial and Residential
General Optional Pressure Relief Kits feature a
175 psi pressure relief valve and trim
Description components for convenient integration
into commercial and residential riser
The TYCO commercial and residential manifold assemblies.
Model RM-1 Riser Manifold provide The pressure relief valve, installed in
the necessary waterflow alarm, pres- manifold assemblies above the nor-
sure gauge, alarm test orifice, drain, mally closed test and drain or drain
and sight glass equipment in a single valve, automatically bleeds system
assembly for use in NFPA 13 com- pressure exceeding 175 psi through a
mercial sprinkler systems and in NFPA flexible hose connected to the mani-
13D/13R residential sprinkler systems fold drain outlet (Ref. Figure 5), reduc-
as follows: ing system pressure to 175 psi.
NFPA 13*
• 1-1/2 Inch (DN40) NOTICE
Male Thread x Female Thread The Model RM-1 Riser Manifolds
• 2 – 6 Inch (DN50 – DN150) described herein must be installed
Groove x Groove and maintained in compliance with this
document, as well as with the applica-
NFPA 13D ble standards of the National Fire Pro-
• 1 Inch (DN25) tection Association (NFPA), in addition
Female Thread x Female Thread to the standards of any other authori-
ties having jurisdiction. Failure to do so
NFPA 13R
may impair the performance of these
• 1-1/2 Inch (DN40)
devices.
Male Thread x Female Thread
The owner is responsible for main-
• 2 Inch (DN50)
taining their fire protection system
Groove x Groove
and devices in proper operating con-
* Although the Riser Manifold described in this techni- dition. Contact the installing contrac-
cal data sheet is intended for NFPA 13 sprinkler sys-
tems, it may be used for NFPA 13D or 13R residential tor or product manufacturer with any
sprinkler systems, where a test orifice of 2.8K or 4.2K questions.
is acceptable.
1
OUTLET
OPTIONAL
PRESSURE
RELIEF TRIM
CONNECTION
FLOW
3, 4
B
A
INLET C
G H D
F
FIGURE 1
MODEL RM-1 COMMERCIAL RISER MANIFOLDS
1-1/2 – 6 INCH (DN40 – DN150)
TFP963
Page 3 of 8
OPTIONAL
PRESSURE
RELIEF TRIM 1" NPT 1
CONNECTION (FEMALE)
NO DESCRIPTION P/N
2 1 300 psi/2000 kPa
FLOW
10" 11" Water Pressure Gauge �� 90050001
(254 mm) (280 mm) 2 Ball Valve, 1” (DN25) . . . 97111603
3 Flow Switch, VSR-M,
1” (DN25) . . . . . . . . . . . . 91144801
4 Field Replaceable
Retard/Switch . . . . . . . . 91144800
1"
2-1/2"
NPT
(64 mm)
DRAIN
3-3/4"
3-7/8" (96 mm) 3, 4
(100 mm) 1" NPT
4-5/8" (FEMALE)
(118 mm)
10-1/8"
(257 mm)
FIGURE 2
MODEL RM-1 RESIDENTIAL RISER MANIFOLD
1 INCH (DN25)
OPTIONAL
PRESSURE 1
RELIEF TRIM 1-1/2" NPT
CONNECTION (FEMALE)
13-1/4"
(337 mm) NO DESCRIPTION P/N
FLOW
3-7/8" 3-7/8" 3, 4
(100 mm) 1" (100 mm) 1-1/2" NPT
NPT 4-3/4" (MALE)
DRAIN (121 mm)
11-3/8"
(290 mm)
FIGURE 3
MODEL RM-1 RESIDENTIAL RISER MANIFOLD
1-1/2 INCH (DN40)
TFP963
Page 4 of 8
1
2"
(GROOVED)
OPTIONAL
PRESSURE
RELIEF TRIM
CONNECTION
16"
FLOW
(406 mm) NO DESCRIPTION P/N
13" 1 300 psi/2000 kPa
Water Pressure Gauge �� 90050001
(330 mm)
2 Ball Valve, 1” (DN25) . . . 97111603
3 Flow Switch, VSR-M,
2” (DN50) . . . . . . . . . . . . 91144802
2 4 Field Replaceable
Retard/Switch . . . . . . . . 91144800
1/2"
(13 mm)
3-7/8" 4-1/8" 3, 4
(100 mm) 1" (105 mm) 2"
NPT 5" (GROOVED)
DRAIN (127 mm)
11-7/8"
(300 mm)
FIGURE 4
MODEL RM-1 RESIDENTIAL RISER MANIFOLD
2 INCH (DN50)
Manifold Notes:
Where applicable pipe thread sealant
Step 1. Install the manifold body with
the flow arrow pointing in the down-
Installation is to be applied sparingly. Use of a
non-hardening pipe thread sealant is
stream position using threaded con-
nections and/or listed mechanical
grooved connections, as applicable.
TYCO Model RM-1 Riser Manifold recommended.
must be installed in accordance with Step 2. Connect the drain line and on
this section. Never remove any piping component commercial manifolds set the Model
nor correct or modify any piping defi- TD-1 Test and Drain Valve to the OFF
The Model RM-1 Riser Manifold may be ciencies without first depressurizing position or on residential manifolds
installed either horizontally (flow switch and draining the system. close the drain valve.
on top) or vertically (flow going up). The
inlet of the Riser Manifold may be con- Provisions for an alarm test flow on Step 3. Refer to Figure 6 for wiring
nected directly to a shut-off control Residential Models must be made. guidance. All wiring must be performed
valve. The alarm test flow is to be through in accordance with the authority having
an orifice having a flow capacity equal jurisdiction and/or the National Electri-
to or smaller than the smallest orifice cal Code.
sprinkler in the system. One of two
options can be considered. The first Step 4. Refer to Figure 5 for Optional
option is to temporarily install a test Pressure Relief Trim installation.
orifice in the outlet of the drain line Step 5. Place the system in service
prior to performing the alarm test. The by filling the system with water. When
second option is to install an Inspec- filling the system, partially open the
tor’s Test Connection downstream of control valve to slowly fill the system.
the Waterflow Alarm Switch. Filling the system slowly will help avoid
damaging the waterflow alarm switch.
After the system is fully pressurized,
completely open the control valve.
Step 6. Secure all supply valves open.
TFP963
Page 5 of 8
FIGURE 5
MODEL RM-1 COMMERCIAL AND RESIDENTIAL RISER MANIFOLDS
OPTIONAL PRESSURE RELIEF TRIM INSTALLATION
AUDIBLE/VISUAL
ANNUNCIATOR
LOAD OUT TO
BLACK
(LINE/HOT)
CONTACT RATINGS:
Two sets of SPDT (Form C)
10.0 Amps at 125/250VAC
2.0 Amps at 30VDC Resistive
10 mAmps min. at 24VDC NO NC COM COM NC NO
NOTE:
When connecting to a
UL Listed control panel,
use panel resistor rating
for circuit supervision
NOTE:
For supervised circuits, see "Switch Terminal Connections" above. The Waterflow Alarm
Switch has two switches, one can be used to operate a central station, proprietary or remote
signaling unit, while the other contact is used to operate a local audible or visual annunciator.
FIGURE 6
MODEL RM-1 COMMERCIAL AND RESIDENTIAL RISER MANIFOLD
WIRING GUIDANCE
TFP963
Page 7 of 8
MODEL TD-1
TEST AND
DRAIN
VALVE
SIGHT
FLOW
DRAIN
CONNECTION
SET TEST DRAIN FRONT
CONDITION CONDITION CONDITION VIEW
FIGURE 7
MODEL RM-1 COMMERCIAL RISER MANIFOLD
TD-1 TEST AND DRAIN VALVE OPERATION
Residential
1 Inch (DN25) FT x FT �������������������������������� 40671
1-1/2 Inch (DN40) MT x FT ������������������������ 40571
2 Inch (DN50) G x G ���������������������������������� 40591