W-S
Globe valves, 3-way, with flange PN16
• For closed cold and hot water systems
• For modulating water-side control of air
handling units and heating systems

Type overview
Type K vs DN Stroke Sv Ps
[m3/h] [mm] [mm] [kPa]
H7065W-S* 50 65 20 >50 280
H7080W-S 80 80 30 >50 250 / 600
H7100W-S 125 100 40 >50 200 / 450
H7125W-S 200 125 40 >50 110 / 250
H7150W-S 300 150 40 >50 60 / 150
H7200W-S 520 200 40 >50 80
H7250W-S 750 250 40 >50 50
Ps will be variant depends on actuator selection.
*H7065W-S is available for diverting application.

Technical data
Functional data Flow media Cold and hot water, Refrigerant (R12, R22, R134a, R202),
water with max. 50% volume of glycol, Hydrazine,
Phosphate
Temperature of medium 0°C ... +150°C
Rated pressure Ps 1600kPa (PN16)
Flow characteristic Control path A – AB: equal percentage (to VDI/VDE 2173)
n(gl) = 3, optimised in the opening range
Rangeability S v See «Type overview»
Leakage rate Max. 0.02% of kvs value
(DIN EN 1349 and DIN EN 60534-4)
Pipe connection Flange to ISO 7005-2 (PN16)
Stroke See «Type overview»
Valve closing point Up (▲)
Installation position Upright to horizontal (in relation to the stem)
Maintenance Maintenance-free
Materials Body Ductile iron GGG40
Valve cone Stainless steel SS304
Valve stem Stainless steel SS304
Valve seat Stainless steel SS304
Stem gland seal Teflon
Dimensions / Weights Dimensions and weights See «Globe Valves Dimension Size Overview»

Safety notes
• This globe valve has been designed for use in stationary heating, ventilation and air-
conditioning systems and is not allowed to be used outside the specified field of
application, especially in aircraft or in any other airborne means of transport.
• It may only be installed by suitably trained personnel. All applicable legal or institutional
installation regulations must be complied with.
• The valve does not contain any parts that can be replaced or repaired by the user.
V2.0 05.2016• Subject to modification

• The valve is not allowed to be disposed of as household refuse. All locally valid regulations
and requirements must be observed.
• The recognised rules should be applied when determining the flow characteristic of final
controlling elements.

17
H7..W-S Globe valves, 3-way, with flange PN16

Product features
Mode of operation The globe valve is operated by an SV, EV or RV series linear actuator. The linear actuators
are controlled by a standard modulating or 3-point control system and move the cone of the
valve, the throttling device, to the opening position dictated by the control signal.
Flow characteristic An equal-percentage flow characteristic is produced by profiling the valve cone. The bypass
exhibits a equal-percentage characteristic curve.
Manual operation On the SV, EV or RV linear actuator, the valve stem can be actuated manually using a
hexagonal key.

Installation notes
Recommended mounting positions The globe valve may be mounted either vertically or
horizontally.
It is not permissible to mount the globe valve with the stem
pointing downwards.

Water quality requirements • The water quality requirements specified in VDI 2035 must be adhered to.
• Globe valves are relatively sensitive control devices. In order to ensure a long service life,
it is advisable to fit strainers.
Maintenance • The globe valves and linear actuators are maintenance-free.
• Before any kind of service work is carried out on actuator sets of this type, it is essential to
isolate the linear actuator from the power supply (by unplugging the power lead). Any pumps
in the part of the piping system concerned must also be switched off and the appropriate
isolating fittings closed (allow everything to cool down first if necessary and reduce the
pressure in the system to atmospheric).
• The system must not be returned to service until the globe valve and the linear actuator
have been properly reassembled in accordance with the instructions and the pipework has
been refilled in the proper manner.
Direction of flow • The direction of flow, specified by an arrow on the housing, is to be complied with, since
otherwise the globe valve can be damaged.

H7065W-S only
V2.0 05.2016• Subject to modification

18
Globe Valves Dimension Size Overview

Dimensions

H
H2

D2
H1

D4

K
D
L3’
L2
L1

H7..W-S Globe valve 3-way series and H7..W-D (diverting), PN16


DN Dimension[mm] Weight
Model Type
mm B D D2 D4 K L1 L2 L3 H1 H2 H (kg)

H7065W-S 65 22 185 4-18 118 145 290 145 155 105 145.5 376 22.5
H7080W-S 80 22 200 8-18 132 160 310 155 182 118 172.5 502 28.8
H7080W-D 80 22 200 8-18 132 160 310 155 182 118 172.5 502 28.8
H7100W-S 100 23 220 8-18 156 180 350 175 200 135 189.5 519 40.6
H7100W-D 100 23 220 8-18 156 180 350 175 200 135 189.5 519 40.6
H7125W-S 125 24 250 8-18 184 210 400 200 240 160 214.5 544 55.4
H7125W-D 125 24 250 8-18 184 210 400 200 240 160 214.5 544 55.4
H7150W-S 150 25 285 8-22 211 240 480 240 268 169 223.5 553 76.3
H7150W-D 150 25 285 8-22 211 240 480 240 268 169 223.5 553 76.3
H7200W-S 200 26 340 12-22 266 295 500 250 320 263 317.5 647 125.6
H7250W-S 250 31 405 12-26 319 355 600 300 400 315 369.5 699 230.0
V2.0 05.2016• Subject to modification

25
Technical data sheet EVK24A-MP-TPC
Communicative globe valve actuator
with emergency control function for
2-way and 3-way globe valves
• Actuating force 2500 N
• Nominal voltage AC/DC 24 V
• Control modulating, communicative
DC (0)2...10 V Variable
• Nominal stroke 40 mm
• Conversion of sensor signals
• Design life SuperCaps: 15 years
• Communication via Belimo MP-Bus

Technical data
Electrical data Nominal voltage AC/DC 24 V
Nominal voltage frequency 50/60 Hz
Nominal voltage range AC 19.2...28.8 V / DC 21.6...28.8 V
Power consumption in operation 8.5 W
Power consumption in rest position 3W
Power consumption for wire sizing 16.5 VA
Connection supply / control Terminals with cable 1 m, 4 x 0.75 mm²
(Terminal 4 mm²)
Parallel operation Yes (note the performance data)
Functional data Actuating force motor 2500 N
Positioning signal Y DC 0...10 V
Positioning signal Y note Input impedance 100 kΩ
Control signal Y variable Open/Close
3-point (AC only)
Modulating (DC 0...32 V)
Operating range Y DC 2...10 V
Operating range Y variable Start point DC 0.5...30 V
End point DC 2.5...32 V
Position feedback U DC 2...10 V
Position feedback U note Max. 0.5 mA
Position feedback U variable Start point DC 0.5...8 V
End point DC 2.5...10 V
Setting emergency setting position (POP) Actuator spindle 0...100%, adjustable (POP
rotary button)
Bridging time (PF) variable 1...10 s
Position accuracy 5% absolute
Manual override with push-button
Nominal stroke 40 mm
Actuating time motor 150 s / 40 mm
Actuating time variable 90...150 s / 40 mm
Actuating time emergency control 35 s / 40 mm
function
Adaption setting range manual (automatic on first power-up)
Adaption setting range variable No action
Adaption when switched on
Adaption after pushing the gear disengagement
button
Override control MAX (maximum position) = 100%
MIN (minimum position) = 0%
ZS (intermediate position, AC only) = 50%
Override control variable MAX = (MIN + 33%)...100%
MIN = 0%...(MAX – 33%)
ZS = MIN...MAX
Sound power level motor 60 dB(A)
Sound power level emergency control 60 dB(A)
position
Position indication Mechanically, 5...40 mm stroke
Safety Protection class IEC/EN III Safety extra-low voltage
Protection class UL UL Class 2 Supply

www.belimo.com EVK24A-MP-TPC • en-gb • 2016-04-01 • subject to changes 1


SuperCap globe valve actuator, communicative,
EVK24A-MP-TPC modulating, communicative, AC/DC 24 V, 2500 N

Technical data
Safety Degree of protection IEC/EN IP54
Degree of protection NEMA/UL NEMA 2, UL Enclosure Type 2
EMC CE according to 2014/30/EU
Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14
Certification UL cULus according to UL 60730-1A, UL 60730-2-
14 and CAN/CSA E60730-1:02
Mode of operation Type 1.AA
Rated impulse voltage supply / control 0.8 kV
Control pollution degree 3
Ambient temperature range 0...50°C
Non-operating temperature -40...80°C
Ambient humidity 95% r.h., non-condensing
Maintenance Maintenance-free
Weight Weight 4.5 kg
Terms Abbreviations POP = Power off position / emergency setting
position
CPO = Controlled power off / controlled
emergency control function
PF = Power fail delay time / bridging time

Safety notes
• This device has been designed for use in stationary heating, ventilation and air

! conditioning systems and must not be used outside the specified field of application,
especially in aircraft or in any other airborne means of transport.
• Only authorised specialists may carry out installation. All applicable legal or
institutional installation regulations must be complied during installation.
• The switch for changing the direction of motion and so the closing point may be
adjusted only by authorised specialists. The direction of motion is critical, particularly
in connection with frost protection circuits.
• The device may only be opened at the manufacturer’s site. It does not contain any
parts that can be replaced or repaired by the user.
• The device contains electrical and electronic components and must not be disposed
of as household refuse. All locally valid regulations and requirements must be
observed.

2 EVK24A-MP-TPC • en-gb • 2016-04-01 • subject to changes www.belimo.com


SuperCap globe valve actuator, communicative,
EVK24A-MP-TPC modulating, communicative, AC/DC 24 V, 2500 N

Product features
Mode of operation Conventional operation:
The actuator is connected with a standard modulating signal of DC 0...10 V and moves
to the position defined by the positioning signal at the same time as the integrated
capacitors are loaded.
Interrupting the supply voltage causes the valve to be moved to the selected
emergency setting position (POP) by means of stored electrical energy.
Operation on the MP-Bus:
The actuator receives its digital positioning signal from the higher level controller via
the MP-Bus and drives to the position defined. Connection U serves as communication
interface and does not supply an analogue measuring voltage.
Pre-charging time (start up) The capacitor actuators require a pre-charging time. This time is used for charging the
capacitors up to a usable voltage level. This ensures that, in the event of an electricity
interruption, the actuator can move at any time from its current position into the preset
emergency setting position (POP).
The duration of the pre-charging time depends mainly on following factors:
– Duration of the electricity interruption
– PF delay time (bridging time)
Typical pre-charging time
30 30
[s] PF [s] [s]
10 s
25 25

5s
20 2s 20
0s

15 15

10 10

5 5

0 0
0 2 4 6 8 10 [d] 12

PF [s] [d]
0 1 2 7 ≥10
[d] = Electricity interruption in days
[s] = Pre-charging time in seconds 0 5 8 10 15 19
PF[s] = Bridging time 2 6 9 11 16 20
Calculation example: Given an electricity 5 8 11 13 18 22
interruption of 3 days and a bridging time (PF) set
at 5 s, the actuator requires a pre-charging time of 10 12 15 17 22 26
14 s after the electricity has been reconnected (see [s]
graphic).
Delivery condition (capacitors) The actuator is completely discharged after delivery from the factory, which is why the
actuator requires approximately 20 s pre-charging time before initial commissioning in
order to bring the capacitors up to the required voltage level.
Converter for sensors Connection option for a sensor (passive or active sensor or switching contact). The
MP actuator serves as an analogue/digital converter for the transmission of the sensor
signal via MP-Bus to the higher level system.
Parameterisable actuators The factory settings cover the most common applications. Single parameters can be
modified with the Belimo Service Tools MFT-P or ZTH AP.
Simple direct mounting Simple direct mounting on the globe valve by means of form-fit hollow clamping jaws.
The actuator can be rotated by 360° on the valve neck.
Manual override Manual control with push-button possible - temporary. The gear is disengaged and the
actuator decoupled for as long as the button is pressed.
The stroke can be adjusted by using a hexagon socket screw key (5 mm), which
is inserted into the top of the actuator. The stroke spindle extends when the key is
rotated clockwise.
High functional reliability The actuator is overload protected, requires no limit switches and automatically stops
when the end stop is reached.

www.belimo.com EVK24A-MP-TPC • en-gb • 2016-04-01 • subject to changes 3


SuperCap globe valve actuator, communicative,
EVK24A-MP-TPC modulating, communicative, AC/DC 24 V, 2500 N

Product features
Combination valve/actuator Refer to the valve documentation for suitable valves, their permitted medium
temperatures and closing pressures.
Position indication The stroke is indicated mechanically on the bracket with tabs. The stroke range
adjusts itself automatically during operation.
Home position Factory setting: Actuator spindle is retracted.
When valve-actuator combinations are shipped, the direction of motion is set in
accordance with the closing point of the valve.
The first time the supply voltage is switched on, i.e. at the time of commissioning,
the actuator carries out an adaption, which is when the operating range and position
feedback adjust themselves to the mechanical setting range.
The actuator then moves into the position defined by the positioning signal.
Direction of stroke switch When actuated, the direction of stroke switch changes the running direction in normal
operation. The direction of stroke switch has no influence on the emergency setting
position (POP) which has been set.
Adaption and synchronisation An adaption can be triggered manually by pressing the “Adaption” button or with the
PC-Tool. Both mechanical end stops are detected during the adaption (entire setting
range).
Automatic synchronisation after pressing the gearbox disengagement button is
configured. The synchronisation is in the home position (0%).
The actuator then moves into the position defined by the positioning signal.
A range of settings can be adapted using the PC-Tool (see MFT-P documentation)
Emergency setting position (POP) The rotary knob «Emergency setting position» can be used to adjust the desired
rotary knob emergency setting position (POP) between 0 and 100% in 10% increments. The
rotary knob refers to the adapted or programmed height of stroke. In the event of an
electricity interruption, the actuator will move into the selected emergency setting
position (POP), taking into account the bridging time (PF) of 2 s which was set ex-
works.
Settings: The rotary knob must be set to the «Tool» position for retroactive settings
of the emergency setting position (POP) with the Belimo service tool MFT-P. Once
the rotary knob is set back to the range 0…100%, the manually set value will have
positioning authority.
Bridging time Electricity interruptions can be bridged up to a maximum of 10 s.
In the event of an electricity interruption, the actuator will remain stationary in
accordance with the set bridging time. If the electricity interruption is greater than the
set bridging time, then the actuator will move into the selected emergency setting
position (POP).
The bridging time set ex-works is 2 s. This can be modified on site in operation with
the use of the Belimo service tool MFT-P.
Settings: The rotary knob must not be set to the «Tool» position!
Only the values need to be entered for retroactive adjustments of the bridging time
with the Belimo service tool MFT-P.

4 EVK24A-MP-TPC • en-gb • 2016-04-01 • subject to changes www.belimo.com


SuperCap globe valve actuator, communicative,
EVK24A-MP-TPC modulating, communicative, AC/DC 24 V, 2500 N

Accessories

Description Type
Gateways Gateway MP for BACnet MS/TP, AC/DC 24 V UK24BAC
Gateway MP to Modbus RTU, AC/DC 24 V UK24MOD
Gateway MP to LonWorks, AC/DC 24 V, LonMark certified UK24LON
Gateway MP to KNX, AC/DC 24 V, EIBA certified UK24EIB
Description Type
Electrical accessories Connecting cable 5 m, A+B: RJ12 6/6, To ZTH/ZIP-USB-MP ZK1-GEN
Connection cable 5 m, A: RJ11 6/4, B: Free wire end, To ZTH/ZIP- ZK2-GEN
USB-MP
MP-Bus power supply for MP actuators, AC 230/24V for local power ZN230-24MP
supply
Connecting board MP bus suitable for wiring boxes EXT-WR-FP..-MP ZFP2-MP
Auxiliary switch, 2 x SPDT, add-on, grey S2A-H
Description Type
Service Tools Service Tool, for MF/MP/Modbus/LonWorks actuators and VAV- ZTH AP
Controller
Belimo PC-Tool, software for adjustments and diagnostics MFT-P
Adapter to Service Tool ZTH MFT-C

Electrical installation

Notes • Connection via safety isolating transformer.


! • Parallel connection of other actuators possible. Observe the performance data.
• Direction of stroke switch factory setting: Actuator spindle retracted.

Wiring diagrams

AC/DC 24 V, modulating Operation on the MP-Bus


T ~ T ~
– + – +

Y DC (0)2…10 V Y Sensor
U DC 2…10 V U MP

1 2 3 5 Cable colours: 1 2 3 5 Cable colours:


1 = black 1 = black
2 = red 2 = red
3 = white 3 = white
5 = orange 5 = orange

Functions
Functions when operated on MP-Bus

Connection on the MP-Bus Network topology


T ~
– + MP

A)

There are no restrictions for the


network topology (star, ring, tree or
1 2 3 5 mixed forms are permitted).
Supply and communication in one
and the same 3-wire cable
Y U A) more actuators and sensors • no shielding or twisting necessary
(max.8) • no terminating resistors required

www.belimo.com EVK24A-MP-TPC • en-gb • 2016-04-01 • subject to changes 5


SuperCap globe valve actuator, communicative,
EVK24A-MP-TPC modulating, communicative, AC/DC 24 V, 2500 N

Functions
Functions when operated on MP-Bus

Connection of active sensors Connection of external switching contact


T ~ T ~
– + MP – + MP
p

A) A)

A) more actuators and sensors A) more actuators and sensors


(max.8) (max.8)
1 2 3 5 • Supply AC/DC 24 V 1 2 3 5 • Switching current 16 mA @ 24 V
• Output signal DC 0...10 V • Start point of the operating range
(max. DC 0...32 V) must be parameterised on the MP
Y U Y U actuator as ≥ 0.5 V
• (Resolution 30 mV

Connection of passive sensors


T ~
– + MP

A)

Ni1000 –28...+98°C 850...1600 Ω 2)


1 2 3 5 A) more actuators and sensors
PT1000 –35...+155°C 850...1600 Ω 2) (max.8)
1) Depending on the type
Y U NTC –10...+160°C 1) 200 Ω...60 kΩ 2) 2) Resolution 1 Ohm

Functions with basic values (conventional mode)

Override control with AC 24 V with relay contacts Override control with AC 24 V with rotary switch
~ ~
ZS 50%

T T
(DC 0...10 V)
Y
100%
0%

c Y (DC 0...10 V)
a b

a b c e.g. 1N 4007
0%
1 2 3 5 e.g. 1N 4007 1 2 3 5
ZS 50%

100%
Y U Y U
Y

Remote control 0...100% with Minimum limit with positioner SG..


positioner SG..
T ~ T ~
– + T ~ – + T ~
SGA24 SGA24
– + Y Z SGF24 – + Y Z SGF24 Y [V]
1 2 3 4 SGE24 1 2 3 4 SGE24
10

Y (DC 0...10 V)

min
1 2 3 5 1 2 3 5

Y U Y U 0 [%]
0 100

6 EVK24A-MP-TPC • en-gb • 2016-04-01 • subject to changes www.belimo.com


SuperCap globe valve actuator, communicative,
EVK24A-MP-TPC modulating, communicative, AC/DC 24 V, 2500 N

Functions
Follow-up control (position-dependent) Control with 4...20 mA via external resistor
T ~ T ~
– + – +
Y DC (0)2…10 V 500 Ω
(–)
4…20 mA
U DC 2…10 V (+)
U DC 2…10 V

Caution:
1 2 3 5 1 2 3 5 1 2 3 5 The operating range must be set to
DC 2...10 V.
The 500 Ω resistor converts the
Y U Y U Y U 4...20 mA current signal to a voltage
signal DC 2...10 V

Functional check
T ~
– +

Procedure
1. Apply 24 V to connection 1 and 2
2. Disconnect connection 3:
- with upwards direction of motion:
closing point at top
1 2 3 5 - with downwards direction of
motion: closing point at bottom
3. Short circuit connections 2 and 3:
Y U - Actuator runs in the opposite
direction

Functions for actuators with specific parameters (Parametrisation with PC-Tool necessary)

Override control and limiting with AC 24 V with relay contacts Override control and limiting with AC 24 V with rotary switch
T ~ T ~
Close 1)

(DC 0...10 V)
Y
Open
MAX
MIN
ZS

e Y (DC 0...10 V)
a b c d
a b c d e
Close 1)
e.g. 1N 4007
MIN
1 2 3 5 e.g. 1N 4007 ZS 1 2 3 5
1) Caution: This function is only
MAX
guaranteed if the start point of the
Y U Open Y U operating range is defined as min.
Y 0.5 V.

Control Open/Close Control 3-point


T ~ T ~
– +
U U
a b

e.g. 1N 4007

a b

1 2 3 5 1 2 3 5

Y U Y U

www.belimo.com EVK24A-MP-TPC • en-gb • 2016-04-01 • subject to changes 7


SuperCap globe valve actuator, communicative,
EVK24A-MP-TPC modulating, communicative, AC/DC 24 V, 2500 N

Operating controls and indicators


1 Direction of stroke switch
Switch over: Direction of stroke changes
2 Cover, POP button
3 POP button
4 Scale for manual adjustment
5 Position for adjustment with tool
6 Service plug
For connecting the parameterisation and service tools
10
7 Gear disengagement button
Press button: Gear disengaged, motor stops, manual override possible
Release button: Gear engaged, standard mode
1 LED displays
Meaning / function
8 yellow 9 green
2 Off On Operation OK
0.5 Off Flashing POP function active
POP
3 On Off Pre-charging time SuperCap,
7 4 Fault SuperCap or
Tool wiring error in supply
5
8 9 Off Off Not in operation
Status Power
Address Adaption On On Adaptation process active
Flickering On Communication active

8 Push-button (LED yellow)


Press button: Confirmation of addressing
6 9 Push-button (LED green)
Press button Triggers stroke adaptation, followed by standard mode
10 Manual override
Clockwise: Actuator spindle extends
Counterclockwise: Actuator spindle retracts

Setting emergency setting position (POP)

0.5

TOOL

0.5

TOOL

0.5
POP %
TOOL 0 ...100
0.5
POP >
TOOL PC-Tool

8 EVK24A-MP-TPC • en-gb • 2016-04-01 • subject to changes www.belimo.com


SuperCap globe valve actuator, communicative,
EVK24A-MP-TPC modulating, communicative, AC/DC 24 V, 2500 N

Service

Notes • The actuator can be parameterised by PC-Tool and ZTH AP via the service
! socket.

Service Tools connection


ZTH AP connection
T ~ AC 24 V
– + DC 24 V

Y
U

MP
USB
i esc   OK

1 2 3 5

Y U

PC-Tool connection
T ~ AC 24 V
– + DC 24 V

Y
U

MP
USB
i esc   OK
BELIMO
PC-Tool
1 2 3 5

USB
Y U

Dimensions [mm]
Dimensional drawings
256
53 140
276
275

www.belimo.com EVK24A-MP-TPC • en-gb • 2016-04-01 • subject to changes 9