Generator Under Voltage setting (1) values:

Minimum value Maximum value Trip Set point


Set point 40.0% 100.0% 93.0%(10230 V)
Time Delay 0.0 Sec 100 Sec 15 sec
Enable Off On On
Fail class Alarm Trip Alarm
Generator Under Voltage setting (2) values:
Minimum value Maximum value Trip Set point
Set point 40.0% 100.0% 90.0%(9900 V)
Time Delay 0.0 Sec 100 Sec 15 sec
Enable Off On On
Fail class Alarm Trip Trip

Generator High Voltage setting (1) values:


Minimum value Maximum value Trip Set point
Set point 100.0% 120.0% 106.0%(116600 V)
Time Delay 0.0 Sec 100 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Alarm
Generator High Voltage setting (2) values:
Minimum value Maximum value Trip Set point
Set point 100.0% 120.0% 109.0%(11990 V)
Time Delay 0.0 Sec 100 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Trip

Generator Under Frequency setting (1) values:


Minimum value Maximum value Trip Set point
Set point 100.0% 80.0% 93.0%(46.5Hz)
Time Delay 0.0 Sec 100 Sec 10 sec
Enable Off On On
Fail class Alarm Trip Alarm
Generator Under Frequency setting (2) values:
Minimum value Maximum value Trip Set point
Set point 100.0% 80.0% 90.0%(45.0 Hz)
Time Delay 0.0 Sec 100 Sec 10 sec
Enable Off On On
Fail class Alarm Trip Trip

Generator Over Frequency setting (1) values:


Minimum value Maximum value Trip Set point
Set point 100.0% 120.0% 105.0%(52.5Hz)
Time Delay 0.0 Sec 100 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Alarm
Generator Over Frequency setting (2) values:
Minimum value Maximum value Trip Set point
Set point 100.0% 120.0% 107.0%(53.5 Hz)
Time Delay 0.0 Sec 100 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Trip

Reverse Power setting (1) values:


Minimum value Maximum value Trip Set point
Set point 0.0% 200.0% -3.0 %(780KW)
Time Delay 0.0 Sec 100 Sec 10 sec
Enable Off On On
Fail class Alarm Trip Alarm
Reverse Power setting (2) values:
Minimum value Maximum value Trip Set point
Set point 0.0% 200.0% -5.0 %(1300KW)
Time Delay 0.0 Sec 100 Sec 10 sec
Enable Off On On
Fail class Alarm Trip Trip
Generator over current setting (1) values:
Minimum value Maximum value Trip Set point
Set point 50.0% 200.0% 100.0%
Time Delay 0.0 Sec 3200 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Alarm
Generator over current setting (2) values:
Minimum value Maximum value Trip Set point
Set point 50.0% 200.0% 110.0%
Time Delay 0.0 Sec 3200 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Trip
Generator Short Circuit setting (1) values:
Minimum value Maximum value Trip Set point
Set point 150.0% 350.0% 200.0%
Time Delay 0.0 Sec 3200 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Alarm
Generator Short Circuit setting (2) values
Minimum value Maximum value Trip Set point
Set point 150.0% 350.0% 250.0%
Time Delay 0.0 Sec 3200 Sec 1 sec
Enable Off On On
Fail class Alarm Trip Trip
Generator Overload setting (1) values:
Minimum value Maximum value Trip Set point
Set point -200.0% 200.0% 100.0%
Time Delay 0.0 Sec 3200 Sec 10 sec
Enable Off On On
Fail class Alarm Trip Alarm
Generator Overload setting (2) values:
Minimum value Maximum value Trip Set point
Set point -200.0% 200.0% 110.0%
Time Delay 0.0 Sec 3200 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Trip
Loss of Excitation setting values:
Minimum value Maximum value Trip Set point
Set point 0.0% 150.0% 50.0%
Time Delay 0.0 Sec 100 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Alarm
Over Excitation setting values:
Minimum value Maximum value Trip Set point
Set point 0.0% 100.0% 80.0%
Time Delay 0.0 Sec 100 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Trip
Negative Phase Sequence Current setting values:
Minimum value Maximum value Trip Set point
Set point 0.0% 100.0% 10.0%In (0.28A) I sec
Time Delay 0.2 Sec 100 Sec 0.5 sec
Enable Off On On
Fail class Alarm Trip GB Trip GB
Negative Phase Sequence Voltage setting values:
Minimum value Maximum value Trip Set point
Set point 1.0% 100.0% 5.0%(550V)
Time Delay 0.2 Sec 100 Sec 0.5 sec
Enable Off On On
Fail class Alarm Trip GB Trip GB
Bus Bar over Voltage setting (1) values:
Minimum value Maximum value Trip Set point
Set point 100.0% 120.0% 105.0%(11550 V)
Time Delay 0.0 Sec 100 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Alarm
Bus Bar over Voltage setting (2) values:
Minimum value Maximum value Trip Set point
Set point 100.0% 120.0% 107.0%(11770 V)
Time Delay 0.0 Sec 100 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Trip

Differential relay setting values:

Differential Current Set point:


Minimum setting Maximum setting Trip Set point
4% 40 % 10.2 %(0.53 A)
I sec

Differential Current Time Delay Set point:


Minimum setting Maximum setting Time delay
0 Sec 10 Sec 6.547 Sec

Stator Earth Fault relay setting values:

Stator Earth Fault Set point:


Minimum setting Maximum setting Trip Set point
10 % 110 % 26 %(1.3 A) In

Stator Earth Fault Time Delay Set point:


Minimum setting Maximum setting Time delay
0 Sec 5 Sec 1 Sec