Vous êtes sur la page 1sur 36

Chiller Heat Recovery Design

Julian de Bullet
Director of Industry Relations
McQuay International

Chiller Course - Condenser HR 1


Why Consider Heat Recovery?

 Green Is Good (For


Business)
– Conservation of Natural
Resources
 Lower Annual Energy
Usage
– Reduce Operating Cost
 Provide a Good Life Cycle
Analysis

Chiller Course - Condenser HR 2


Why Consider Heat Recovery?

 Air Or Water Side


Economizers Are Not Required
If:
– “Systems That include A
Condenser Heat Recovery
System Complying With
6.3.6.2” (6.3.1)
 Simultaneous Heating And
Cooling Is Allowed If:
– “At Least 75% Of Reheat
Energy Is Provided By Site
Recovered Energy Source”
(6.3.2.1)

Chiller Course - Condenser HR 3


Why Consider Heat Recovery?

 Air Side Energy Recovery


(MUAs) Not Required If:
– “60% or More of Outdoor Heat
Energy Is Provided From Site
Recovered Energy” (6.3.6.1)
 Condenser Heat Recovery
Required For Domestic Hot
Water Systems That:
– Operate 24 Hr/Day
– Total THR Is > 6 Million Btu/Hr
 (400 Ton System)
– DHW Load Is > 1 Million Btu/Hr

Chiller Course - Condenser HR 4


Why Consider Heat Recovery?

 LEED (Leadership in Energy & Environmental Design)


 Score Points For Reducing Energy Cost Below ASHRAE
Std 90.1

Chiller Course - Condenser HR 5


Heat Recovery Requirements
Simultaneous Heating And Cooling

BTU/ft^2

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Month
Heating Cooling

 The Potential Heat Recovery At Any Point In Time


Is The Lesser Of The Heat Source Or The Heat
Load
Chiller Course - Condenser HR 6
Heat Recovery Requirements
Domestic Hot Water

BTU/ft^2

0 6 12 18 24

Hour Of The Day


Domestic Hot Water Use Boiler Power

 Heat Recovery Can Be Used For Preheat Or


Charge Mode

Chiller Course - Condenser HR 7


VAV With Reheat

 VAV Boxes Require Reheat When Minimum Flowrate Is Reached


 Generally Occurs In Mild Or Cold Weather (Winter)
 Can Happen During Morning Warm-up Any Season
 Airside Economizers Will Remove Source

Chiller Course - Condenser HR 8


Constant Volume With Reheat

 Reheat Used To Warm (55°F) Supply Air As Required By Each Zone


 Required Even On A Design Day
 High Reheat Loads In Cold Weather
 Airside Economizers Will Remove Source
 Excellent Choice For Heat Recovery
Chiller Course - Condenser HR 9
Fancoils

 Hot Water Used Whenever A Zone Has A Heat Load


 Four Pipe System Only
 Most Buildings Require Hot Water And Chilled Water In Winter
 WaterSide Economizers Will Remove Source
 Excellent Choice For Heat Recovery
Chiller Course - Condenser HR 10
Unit Ventilators

 Unit Ventilators Require Heat When There Is a Heat Load


 Dehumidification May Require Reheat
 Generally Occurs In Mild Or Cold Weather (Winter)
 Can Happen During Morning Warm-up Any Season
 Airside Economizers Will Remove Source

Chiller Course - Condenser HR 11


Multizone

 Multizone Control Logic May Require Simultaneous Heating


And Cooling
– Only Allowed By Std 90.1 If Reheat Is From Reclaimed Source
 Generally Occurs In Mild Or Cold Weather (Winter)
 Can Happen During Morning Warm-up Any Season
Chiller Course - Condenser HR 12
Single Condenser HR Design
Boiler Loop
Chilled Water
Pump
Cooling Tower

Condenser Water
Pump

Heat Exchanger

Heat Exchanger
3-Way Bypass
Pump
Valve

Chiller Course - Condenser HR 13


Split Condenser HR Design
Cooling Tower Boiler Loop

Split Condenser
Heat Recovery
Chiller

Chilled Water
Pump

Heat Recovery
Pump
3 Way Bypass
Valve

Chiller Course - Condenser HR 14


Heat Recovery Design
 Generally Design Boiler Load Greater Than
Design Chiller THR (Total Heat of Rejection)
– Actual Design Heat Recovery Rate Requires Annual
Energy Analysis
– Almost Never Boiler Or THR Design Capacity
– Load Will Be Met By Combination Of HR And Boiler
 THR = 1.25 x Chiller Capacity
 Only One Chiller Need Be HR Type In Multiple
Chiller Plant
– Must Be First On, Last Off
– System Designs That Backload Chiller Improve HR

Chiller Course - Condenser HR 15


Heat Recovery Design

 Boiler Temperature Range Typically 20°F (180-160°F)


 Condenser Loop Temperature Range 10°F (95-105°F)
 Size Heat Recovery Loop For Design Load
– 3 gpm Per Design Ton At 10°F Range
– This Must Be Less Than The Boiler Flow Rate

 Two Control Schemes


– Maintain Boiler Supply Water Temperature
– Maintain Boiler Return Water Temperature

Chiller Course - Condenser HR 16


Maintain Boiler Supply W.T.

 Load Water Temperature


Range Proportional To THR
 If Boiler Load = 25% Then Condenser Refrigera
nt Temperature

Range = 5°F (Based 20°F 105 Heat Recovery Supply

Temperature
Range) H.R. Cond. W
ater Return

 Maintaining 105°F SWT Will 95

Require 100°F Return Load


Leaving Chilled Water
Water 44
Evaporator Refrigerant
Temperature
 Guarantees High Lift On
Chiller
100
– Surging 10 50
% Cooling Load
– Hot Gas Bypass
 Still Need Boiler “Trim”
 Not Recommended

Chiller Course - Condenser HR 17


Maintain Boiler Return W.T.

ture
 If Boiler Load = 25% Then n t T emp
era
igera
Range = 5°F (Based 20°F se r Refr
de n
Con upply
105 overy S
Range) He a t R e c

Temperature
 Maintaining 95°F RWT Will H.R. Cond. Water Return
95
Provide 100°F Boiler Supply
Temperature Leaving Chilled Water
44
 Minimizes Chiller Lift Evaporator Refrigerant
Temperature

 Boiler Will “Trim” to Meet


Required Supply Temperature 100
10 50
 Recommended % Cooling Load

Chiller Course - Condenser HR 18


Heat Recovery Control
“During Heat Recovery Mode, Maintain Boiler
Return Water Temperature At 95ºF”
– Boiler Supply Water Temperature Will “Float” Depending
On Actual Heating Load In Building
– 25% Boiler Load = 100°F SWT (5°F Temperature Range)
Not
“During Heat Recovery Mode, Maintain Boiler
Supply Water Temperature At 105ºF”
– 25% Boiler Load = 100°F RWT
– Entering Condenser WT will be 5°F Higher Than Above
– Boiler Will Still Be Required
– Same Amount Of Energy Will Be Recovered
– Chiller will Work A Lot (10%) Harder
Chiller Course - Condenser HR 19
Selecting HR Chiller

 HR Design Capacity Can


Be All Or Part Of Chiller
THR
– 100 Ton Chiller
– 125 Tons THR
– HR Can Be 0 to 125 Tons
 Chiller Size Should be
Matched To Source Load
During HR
– Keep The Chiller Loaded!

Chiller Course - Condenser HR 20


What Is A Heat Pump Chiller

 A Water To Water Heat


Recovery Device
 A Heatpump
 Provides Hot Water At A
Specified Temperature
Using Waste Heat From A
Low Temperature Loop

Chiller Course - Condenser HR 21


Design
Chilled Water Boiler Loop
Pump

Condenser Cooling Tower


Water Pump

Std. Chiller

Heat Pump

95 °F 85 °F

130 °F 140 °F 3-Way Bypass


85 °F Valve

Chiller Course - Condenser HR 22


Design

 Boiler Temperature Range Typically 20°F (180-160°F)


 Source Chiller Condenser Loop Temperature Range
10°F (65-75°F)
 If Source Chiller THR Larger Than Heat Pump Try To
Use 5°F On Source Side To Improve Performance
 Bypass Balance Of Condenser Water Around Heat Pump
 Use 10°F Temperature Range On Load Side

Chiller Course - Condenser HR 23


Impact To Rest Of HVAC System

 105°F Supply Water From HR Chillers Will


Require Different Size Reheat Coils
– Increased Capital Cost
– Fan BHP Penalty (Can Be Significant)

 140-160°F Supply Water From Heat Pump Can


Use Same Size Coils In Most Cases
– The Small Loss In Performance From 180°F Design
Condition Is Acceptable Due To Smaller Loads

Chiller Course - Condenser HR 24


Sizing HR Chillers

 Airside Energy Recovery Systems Are


Sized Based On Design Load Conditions

 Water Side Energy Recovery Must Be


Sized During Part Load Conditions

 Requires Annual Energy Analysis

Chiller Course - Condenser HR 25


Sizing HR Chillers

 Using the THR Of Chillers Rated Cooling Capacity


For HR Design Is Not Recommended
– Undersized Chiller Will Miss HR Opportunity
– Oversized Chiller Will Waste Capital
– Possible Surge Issues

 Manual Method Described In ASHRAE Chiller


Heat Recovery Application Guide

Chiller Course - Condenser HR 26


Example

 Acute Care Hospital In Chicago


– 480,000 ft², 3 Story

– 1600 ton Chiller Plant

– 22,000 MBH Boiler Plant

– Constant volume With Reheat

– 409,330 CFM Supply Air

– 192,000 CFM Ventilation Air

Chiller Course - Condenser HR 27


Example

 Option 1 - Base Building


– Two 800 Ton Centrifugals

 Option 2 -
– 472 Ton Heat Pump 4.4 COP
– Two 800 Ton Centrifugals

 Option 3 - Heat Recovery Chiller


– 400 Ton Split Condenser Heat Recovery Chiller 0.73
kW/ton
– 1200 Ton Centrifugal

Chiller Course - Condenser HR 28


Example - Option 2 Heat Pump

 140°F Hot Water


 70 °F Entering Source Water
– 5 °F Source Temperature Range
– 2200 US Gpm
 Source Chiller Condenser Pump Head Increased
By 20 Ft
 Hot Water Tertiary Pump Added

Chiller Course - Condenser HR 29


Example - Option 3 Heat Recovery

 400 Ton Chiller Size Optimized For Heat Recovery


Load (5,324,226 Btu/hr)
 105°F Hot Water
 Supply Fan Static Pressure Increased By 0.20 In.
To Offset Deeper Heating Coils
 Hot Water Tertiary Pump Added

Chiller Course - Condenser HR 30


Results
14000000

12000000

10000000

8000000
kWh

6000000

4000000

2000000

0
Chillers Pumps Towers Fans Boiler HW Pumps

Base Building Templifier HR Chiller

Chiller Course - Condenser HR 31


Results
 Chiller Work Increased
– 55% Due To Heat Pump
– 18% Due To HR Chiller
 Heat Pump Work Increased 15% Due To
Condenser Pump
 HR Supply Fan Work Increased 4% Due To Higher
Static Pressure
 Hot Water Pump Work Increased 25%Due to
Additional Circulation Pump

Chiller Course - Condenser HR 32


Results

 Tower Work Decreased 21% Due To Reduced


Rejection
 Boiler Work Reduced
– 34% Due To Heat Pump
– 28% Due To Heat Recovery Chiller
 Additional Savings Occur When Load > Source
– HR Option Only Has THR From HR Chiller
– Heat Pump Options Has Source Chiller THR + Heat
Pump Compressor Work

Chiller Course - Condenser HR 33


Results

 Both Energy Recovery Options Saved Over 6


Million kBtu/yr
 Heat Pump Saved $108,000/yr
 Payback Less Than 2 years
 80% IRR

Chiller Course - Condenser HR 34


Conclusions

 Water Side Energy Recovery Good Option


 Requires Annual Energy Analysis To Optimize
 Heat Pump Provides 140 To 160°F Hot Water
– Domestic Hot Water Heating Possible
– Domestic Hot Water Preheat Only With HR Chillers
 Right Applications Energy Savings And Financial
Savings Can Be Significant

Chiller Course - Condenser HR 35


Why Consider Heat Recovery?

 Green Is Good (For


Business)
– Conservation of Natural
Resources
 Lower Annual Energy
Usage
– Reduce Operating Cost
 Provide a Good Life Cycle
Analysis

THANK YOU!

Chiller Course - Condenser HR 36

Vous aimerez peut-être aussi