Number Function 110 KW,183A 110 KW,190A 110 KW,195A 132KW,232A 180 KW,322A
1 Protected unit scaling factor, PU scale 0.62 0.64 0.65 0.58 0.64
3 Weighting factor for thermal unit curves, p 50% 50% 50% 50% 50%
5 Prior alarm level for thermal overload, θa> 95% 95% 95% 95% 95%
6 Restart inhibit level for thermal overload, θi> 80% 80% 80% 80% 80%
9 Start-up time for motor or operate time of stage Is> 20 Sec 20 Sec 20 Sec 20 Sec 20 Sec
10 Start value of high set stage overcurrent, I>> 3.5 3.5 3.5 3.5 3.5
11 Operate time of high-set stage overcurrent, t>> 0.05 0.05 0.05 0.05 0.05
12 Start value of earth-fault unit, Io> 10% 10% 10% 10% 10%
13 Operate time of earth-fault unit, to> 0.05 0.05 0.05 0.05 0.05
14 Starting value for undercurrent unit, I< Not used Not used Not used Not used Not used
15 Operate time of the undercurrent unit, t< Not used Not used Not used Not used Not used
20 Operate time of CB failure protection,CBFP Not used Not used Not used Not used Not used