Pump Control Logic

NOTES
Start

1. First Priority shall be to start motor driven 600 USGPM


pump. In case pump is on override, tripped or failed to start,
Check User Defined the logic shall be designed such that to start next
Flowrate 0 USGPM ESD Yes No Action
Flow Input consecutive 600 USGPM motor driven pump will start.
Alarm shall be configured in case of failure of pump start.
No
Flow = 100 USGPM or Above 2. Value should be near to zero. Exact zero value is
unpractical.
Check MOV
1001 Close
No Action ESD
(ZSC-1001)

No

No

Close MOV 1001


No
Confirm Yes
Pump Level
MOV 2001
ESD No
Open
(ZSO-2001)
Check MOV MOV Fail to
Yes 1001 Close No Close Alarm
(ZSC-1001)
Initiate Pump
Start Sequence Yes
for defined flow
rate
Check Min.
Circulation
Line Flow = 0
(FT-1002)

Yes

Time Delay
Pressure
Check
Value>95 psig
(PT-1004)

Value < Preset Flow

Pump Safety Preset Value = 0 Value=<95 psig


Check
Sequence

Confirm
Pump Level
MOV 2001
Close ESD
Open
(ZSO-2001)

Check Flow Open


(FT-
1001+M100
4) Preset Value = 0
Pump Start
Value < Preset Flow Sequence for
0 flow rate
Value > Preset Flow (Note 1)

Pump Started
Backflow =
% Open of Flow
Not Zero (FT1001+M1
MOV1001 as per
(Note 2) 004)-Preset Pump Safety
Backflow
Flow] Check
Sequence

Pump Started
Value<100 Psig

Time Delay Value Near Zero


Petrochemical Engineering Consultants
Time Delay Value<=115 Psig

By: IA Sheet: A3 Doc No:


Check Check
Adjust %Open of Check: SMS 2568-FLC-001
MOV1001
No FT1002 =
Backflow
Yes Pressure
(PT-1004)
RE
Pressure
Check
(PT-1004)

Rev: 0 25/11/2015 Issued For Review


Value=115 psig
Time Delay Value >= 100 Psig

PROJECT: FUEL FARM FACILITY AT


Pump Stop ISLAMABAD INTERNATIONAL AIRPORT

Page 1